PTM-I/O (DESIGO™ PX, VISONIK™, UNIGYR™),
NK-I/O (INTEGRAL™)
Replacement of legacy I/O modules by TX-I/O or workarounds
CM110563en_04 01 Mar 2012
Building Technologies
2 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Contents 01 Mar 2012
Contents
1 About this document ..............................................................................3 1.1 Revision history.........................................................................................3 1.2 Contents of this document ........................................................................3 1.3 Target readers ...........................................................................................3 1.4 Other applicable documents .....................................................................4 1.5 Before you start .........................................................................................4 1.5.1 Copyright ...................................................................................................4 1.5.2 Quality assurance .....................................................................................4 1.5.3 Use of documents / Request to the reader ...............................................4 2 Workarounds for PTM I/O modules.......................................................5 2.1 Overview ...................................................................................................5 2.2 PTM1.2D250 voltage interrogation ...........................................................6 2.3 PTM1.2D42, voltage interrogation ............................................................7 2.3.1 Solution for AC with external relay ............................................................7 2.3.2 Solutions for DC ........................................................................................8 2.4 PTM1.2I25/020, current input 25 mA ........................................................9 2.5 PTM1.2Q250B, bistable relay .................................................................10 2.6 PTM1.xQD(-M), switch contact(s) with feedback....................................11 2.7 PTM1.4QD-M2, 2-stage load ..................................................................11 2.8 PTM6.1PSI20-M, proportional pneumatic output....................................13 2.9 Overvoltage of DC 0...10 V signals.........................................................14 3 Workarounds for NK modules .............................................................15 3.1 Overview .................................................................................................15 3.2 NKID(H), AC/DC voltage interrogation....................................................16 3.3 NKIA / NKIAU / NKIAI, analog inputs ......................................................17 3.4 NKOAU / NKOAI, analog outputs............................................................18 3.5 NKOA(H) / NKOAL(H) / NILAH, phase-cut .............................................19 3.6 NKDG, NKDW, transducer modules........................................................21 3.7 Special "safety interlock" option ..............................................................22
3 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies About this document 01 Mar 2012
1 About this document 1.1 Revision history
Version Date Changes
Revision_04 03.2012 • Section 2.5, Bistable relay • Section 2.9, Overvoltage of DC 0...10 V signals • Various corrections
Version 4 01. 2009 • New section 2.4 for TX-I/O 25 mA input • Correction in section 2.6: Solution for QD-M2
Service Pack 2.37
01. 2008 • Section 2.6: Solution for QD-M2 • Section 2.3.2: 10 kΩ instead of 100 kΩ
2.37 03.2007 First edition
1.2 Contents of this document
The TX-I/O modules support most types of I/O signal from the UNIGYR, VISONIK and INTEGRAL legacy systems with exactly the same type of signal (functionality). Some rarer types of signal are not supported, or supported only partially.
This document describes some possible ways to proceed in such cases.
– Using other signal types, in order to use the TX-I/O modules and/or
– Using third-party equipment The solutions provide help for the following business case:
Existing field devices (periphery) shall remain in place. They are connected to TX-I/O modules which communicate with a DESIGO, UNIGYR or VISONIK automation station via P-Bus. The solutions can also serve as training documentation for engineers who are experienced with legacy systems and want to engineer a new plant with TX-I/O modules.
1.3 Target readers
• Project managers • Consulting engineers • Service engineers • Control panel manufacturers
4 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies About this document 01 Mar 2012
1.4 Other applicable documents Document Number TX-I/O™ Range overview CM2N8170 TX-I/O™ module data sheets CM2N8172 ff TX-I/O™ power supply module/bus connection module data sheet
CM2N8183
TX-I/O™ Functions and operation CM110561 TX-I/O™ Design and installation manual CM110562 P-bus interface module (data sheet) CM2N8180
1.5 Before you start 1.5.1 Copyright
This document may be duplicated and distributed only with the express permission of Siemens and may be passed only to authorized persons/companies with the required technical knowledge.
1.5.2 Quality assurance
These documents have been prepared with great care. • The contents of all documents are checked at regular intervals. • All the necessary corrections are included in subsequent versions. • Documents are automatically amended as a consequence of modifications and
corrections to the products described. Please ensure that you are aware of the latest revision date of the documentation. If you find any lack of clarity while using this document, or if you have any criticisms or suggestions, please contact the product manager in your nearest branch office. The addresses of the Siemens regional companies are available at www.buildingtechnologies.siemens.com.
1.5.3 Use of documents / Request to the reader
Before using our products, it is important that you read the documents supplied with or ordered at the same time as the products (equipment, applications, tools etc.) carefully and in full. We assume that persons using our products and documents are authorized and trained appropriately and have the technical knowledge required to use our products as intended. More information on the products and applications is available: • On the intranet (Siemens employees only) at
https://intranet10.sbt.siemens.com/business/building_comfort/systems/desigo/. • From the Siemens branch office near you
www.buildingtechnologies.siemens.com or from your system supplier • From the support team at headquarters fieldsupport-zug.ch.sbt@siemens.com
if there is no local point of contact. Please note that without prejudice to your statutory rights, Siemens accepts no liability for any losses resulting from non-observance or improper observance of the points referred to above.
5 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2 Workarounds for PTM I/O modules 2.1 Overview
TX
M1.
8D
TX
M1.
16D
TX
M1.
8U
TX
M1.
8U-M
L
TX
M1.
8X
TX
M1.
8X-M
L
TX
M1.
8P
TX
M1.
6R
TX
M1.
6R-M
TX
M1.
6RL
PTM... DescriptionPTM1.2C Volt.-free NC/NO interrogation (meter pulse max 25Hz) x x x x x xPTM1.2D20 Volt-free NO interrogation (maintained contact) x x x x x xPTM1.2D20S Volt-free NO/NC interrogation (meter pulse max 25Hz) x x x x x xPTM1.4D20 Volt-free NO interrogation (maintained contact) x x x x x xPTM1.4D20R Volt-free NC interrogation (maintained contact) x x x x x xPTM1.8D20E Volt-free NO interrogation (maintained contact) x x x x x xPTM1.2D250 Non-floating AC 5/15/250 V, DC 5/15/100 V
PTM1.2D42 Non-floating AC 5/15/30 V, DC 2.5/7.5/30 V PTM1.2R1K T passive (LG-Ni1000: -50..150 °C) x x x x xPTM1.4R1K T passive (LG-Ni1000: -50..150 °C) x x x x xPTM1.2P1K T passive (Pt1000:..400°C, Ni1000:..150°C), 0..2500 Ohm x x x x xPTM1.2P100 T passive (Pt100:..400C, Ni100:..150C), 0..250 Ohm x
PTM1.2U10 DC 0..10 V (voltage AC 24 V) x2)
x2)
x2)
x2)
x2)
PTM1.2I420 DC 4..25 mA (voltage DC 12..30 V) x x
PTM1.2I25/020 DC 0(4)..20 mA + shunt (voltage DC 1 V) x1)
x1)
DC 0..25 mA + shunt (voltage DC 1 V)PTM6.1PSI20-M PneumaticPTM1.2Y10S DC 0..10 V (voltage AC 24V, storage of control value) x x x xPTM1.2Y10S-M DC 0..10 V (voltage AC 24V, storage of control value) x xPTM1.4Y10S DC 0..10 V (voltage AC 24V, storage of control value) x x x xPTM1.2Y420 DC 4..20 mA x xPTM1.2Q250 Volt-free US AC 230 V, 3A x xPTM1.2Q250-M Volt-free US AC 230 V, 3A x
PTM1.2Q250B Volt-free US AC 230 V, 3A (bi-stable) x3)
PTM1.2Y250T 3-position AC 24..250 V, 3A (volt-free/non-floating) x xPTM1.2Y250T-M 3-position AC 24..250 V, 3A (volt-free/non-floating) xPTM1.3Q-M3 Non-floating 3-stage AC 230 V, 3A xPTM1.4Q250A-P Volt-free pulse 2*NO AC 230 V, 3A x xPTM1.4Q250-P Volt-free pulse NC & NO AC 230 V, 3A (on/off) x xPTM1.4Q250-P3 3-stage x xPTM1.2QD Non-floating NO AC 230 V, 3A (feedback)PTM1.2QD-M Non-floating NO AC 230 V, 3A (feedback)PTM1.4QD Non-floating NO AC 230 V, 3A (feedback)PTM1.4QD-M2 Non-floating 2-stage AC 230 V, 3A (feedback)I/O Open 3rd party integration
Workaround
Workaround
WorkaroundWorkaround
Workaround
WorkaroundWorkaroundWorkaround
Existing periphery Solution with TX-I/O
DI Universal DO
Key Signal fully compatible with TX-I/O Workaround described below 1) TXM1.8X(-ML) supports AI: 0..20mA and 4..20mA 2) Field devices that deliver <-1.5 / >11.5 V cause alarms. Solution see section 2.9. 3) Marginal restriction concerning minimum contact current see section 2.5
6 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.2 PTM1.2D250 voltage interrogation
• AC 24 … 250 V DC 24 … 100 V (Max = 250V) Polarity-independent and electrically isolated
• AC "1" Uin > AC 15V "0" Uin < AC 5V Iin ~ 8mA with AC 24 V Iin ~ 4mA with AC 230 V
• DC "1" Uin > DC 15 V "0" Uin < DC 5 V Iin ~ 8mA with DC 24 V Iin ~ 4mA with DC 100 V
External relay controls a digital output:
1056
3A0
1
TXM1.8D, 16D
TXM1.8U(-ML)TXM1.8X(-ML)
Uin
(*)
D20
Electrically "safe" isolation (*) External switches are permitted in the relay coil circuit (AC: up to 230 V, DC: up to 100 V). Configure D20.
Input voltage to be measured
Recommended relays Relay current consumption
AC 24 V Tyco Schrack RT1 24 VAC 32 mA AC 230 V Tyco Schrack RT1 230 VAC 3 mA DC 24 V Tyco Schrack RT1 24 VDC 17 mA DC 100 V Tyco Schrack RT1 110 VDC 4 mA
• The Tyco Schrack bases, type RT 78 724 bases with screw terminals are
suitable for mounting relays on standard rails • In addition to the RT types, types RX1, RY2 and MSR are also suitable.
These are not available for all input voltages but they have a lower current consumption.
Relays from other manufacturers: The contacts must be suitable for extra-low voltage. Use interface relays, not installation relays. Only the former ensure safe isolation between core and contact in accordance with VDE0160/EN50178 for low voltage circuits (SELV or PELV) in relation to hazardous current circuits.
Features of PTM
Solution for TX-I/O
Signal type for TX-I/O
External relay
Notes
Caution
7 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.3 PTM1.2D42, voltage interrogation
• Electrically connected • AC "1" Uin > AC 15V
"0" Uin < AC 5V Ri ~ 3 kOhms Iin =8mA bei AC 24 V
• DC "1" Uin > DC 7.5 V "0" Uin < DC 2.5 V Ri > 100 kOhms Iin = 0.1mA bei DC 10 V
2.3.1 Solution for AC with external relay
1056
3A0
2
TXM1.8D, 16D
TXM1.8U(-ML)TXM1.8X(-ML)
GND
D20
Uin
(*)
(*) External switches are permitted in the relay coil circuit. Configure D20.
Input voltage to be measured
Recommended relay type Relay current consumption
AC 24 V Tyco Schrack RT1 24 VAC 32 mA • The Tyco Schrack bases, type RT 78 724 with screw terminals are suitable for
mounting relays on standard rails. • In addition to the RT types, types RX1, RY2 and MSR are also suitable.
These are not available for all input voltages but they have a lower current consumption.
Features of PTM-I/O
Signal type for TX-I/O
External relay
Notes
8 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.3.2 Solutions for DC
The PTM specifications for DC are such that there is insufficient current for a relay coil. The DC solution, therefore, is to drive an analog input.
1056
3A0
3
TXM1.8U(-ML)TXM1.8X(-ML)
GND
U10
DC 10 V<
(*)
1056
3A0
4
TXM1.8U(-ML)TXM1.8X(-ML)
GND
U10
DC 42 V<
10 V
10k
(*)
Configure U10. • The analog value from the module must be converted into a binary value in the
plant operating program, by use of a hysteresis function.
105
63A
08
U7.5.V2.5.V
0
1
• (*) External switches are NOT permitted in the input circuit.
A) Solution for DC ≤10V
B) Solution for DC 10 ... 42 V
Signal type for TX-I/O
Notes
.
.
.
.
.
9 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.4 PTM1.2I25/020, current input 25 mA
Super universal modules TXM1.8X(-ML) support max. 20 mA. For 25 mA use signal type U10 and install a shunt of 200 ... 400 Ohms.
1056
3A21
TXM1.8U(-ML)TXM1.8X(-ML)
GND
U10
DC 25 mA
200 ... 400 Ohm0.5 W, 0.1%
• The shunt may be placed either near the field device or near the module.
– near the field device: measurement sensible to line resistance – near the module: measurement sensible to hum injection
• Resistances currently available:
– E24 value 200 Ohmor E96 value 402 Ohm Example: Precision resistance 0.1%, 0.6 W from Vishay Type MBB/SMA 0207
– 200 Ohm Adjust slope in the AI block for U10 to 0 ... 5 V – 400 Ohm Connect 2 x 200 Ohm in series
Notes
10 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.5 PTM1.2Q250B, bistable relay, small switched current
The bistable relay function is fully replaced by the TXM1.6RL module. See data sheet N8177. There is a small difference in the contact data: Minimum switched current
TXM1.6RL 2Q250B Min. 100 mA at AC 24 V Min. 20 mA at AC 24 V
Special case small switched currents
1056
3A0
7_01
TXM1.6R(-M)
(1)
(2)
AC / DC 24 ... 230 V • A pulsed signal at I/O point (1) switches the external relay into one position, and • A pulsed signal at I/O point (2) switches the external relay into the other position. Configure 1 x Q250A-P for each bistable contact.
Full replacemett by TXM1.6RL
Marginal restriction
Possible solution with TX-I/O
Function
Signal type for TX-I/O
11 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.6 PTM1.xQD(-M), switch contact(s) with feedback
Combination of a relay output with a feedback input. The switch outputs and digital inputs are on separate I/O modules.
PTM1.2QD(-M) (PTM1.4QD = 2 x PTM1.2QD)
1056
3A0
5
TXM1.6R(-M)
(1)
TXM1.8D, 16D
TXM1.8U(-ML)TXM1.8X(-ML)
Q14
D20(1)
Q250
AC 24 ... 230 V
For each 2QD, configure a Q250 output and a D20 input.
2.7 PTM1.4QD-M2, 2-stage load
switching of a 2-stage load with 2 feedback inputs. The two stages are interlocked internally.
Signal types Q-M2 plus 2 x D20
Two single relay contacts • The switching outputs and digital inputs are on separate I/O modules. • The two relay contacts must be wired in series externally. • Use an external safety interlock. • Use modules without local override, otherwise it is possible to force
stage 2, bypassing stage 1.
PTM1.4QD-M2 (2-stage load)
TXM1.6R TXM1.8D, 16D
TXM1.8U(-ML)TXM1.8X(-ML)
(1)
Q250
(2)
Q250
Q14
Q24
AC 24 ... 230 V
D20(1)
D20(2)
K1
K2
K2
K1
1056
3A9
8
• Configure two Q250 outputs and two D20 inputs.
Features of PTM-I/O
Solution for TX-I/O
Signal type for TX-I/O
Features of PTM-I/O
Solution for TX-I/O V4
Solution for TX-I/O V2.37 Alternative 1
Caution!
Signal type for TX-I/O
12 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
Three stage switch • The switching outputs and digital inputs are on separate I/O modules. • The three relay contacts must be wired in series externally. • Outputs 2 and 3 are wired in parallel. • Use an external safety interlock. • Modules with local override are admitted: the 3-stage function does not allow
switching directly to stages 2 and 3. • Disadvantage: 3 instead of 2 outputs are required.
PTM1.4QD-M2 (2-stage load)
1056
3A9
9
TXM1.6R(-M) TXM1.8D, 16D
TXM1.8U(-ML)TXM1.8X(-ML)
(1)
Q-M3
(2)
Q14
Q24
AC 24 ... 230 V
D20(1)
D20(2)
K1
K2
K2
K1
(3)
Q24
• Use a multistate output Q-M3 and proceed as described in
Knowledge Base article 732. – After synchronization, change the IOAddress in the command block (MI) of
the 2-stage element as follows: e.g. from P=15.1(Q_M3,1,2,3,4) to P=15.1(Q_M3,1,2,3,3).
– Limit the enumeration at stage 2: (Off, Stage 1, Stage 2). – Hardware modification: insert a wire link between output Stage 2 and Stage 3. – No feedback is required for stage 3.
Solution for TX-I/O V2.37 Alternative 2
Signaltyp für TX-I/O
13 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.8 PTM6.1PSI20-M, proportional pneumatic output
0 … 138 kPa output signal with manual controls An external voltage/pressure or current/pressure transducer controls the pneumatic field devices.
1056
3A0
6
TXM1.8X-ML
Y10S U
P
DC 0 ... 10 V
TXM1.8X-ML
Y420 I
P
DC 4 ... 20 mAVDC 24 V VDC 24 VDC 0 ... 20 mA
The voltage output of the TX-I/O modules delivers a maximum of 1mA. Configure Y10S or Y420.
Recommended SMC types ITV00XY-Z Compact elektropneumatic regulator
Pressure range X: 1 = 0 ... 100 kPa 2 = 0 ... 500 kPa Operating voltage Y: 0 = DC 24 V, max. 120 mA 1 = 12 ... 15 V DC, max. 180 mA Input signal Z: 0 = DC 4 ... 20 mA 1 = DC 0 ... 20 mA 3 = DC 0 ... 10 V
Manufacturer: www.smceu.com Catalog: http://www.smceu.com/Prod/NEW_EBP/14)Air_Line_Equipment/14.6)Pressure_C_Equip/a)ITV0000/ITV0000_EU.pdf The DC 24 V supply voltage for a transducer with an operating voltage of DC 24 V can be taken from a "V " terminal of the universal or super universal module (field supply AC 24 V).
Features of PTM-I/O
Solution for TX-I/O
STOP Caution
Signal type for TX-I/O
External transducer
Note
14 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for PTM I/O modules 01 Mar 2012
2.9 Overvoltage of DC 0...10 V signals
A fault message is sent if the process value is outside the range of -1.5...11.5 V. This may be the case of certain DC 0...10 V signal converters. This message cannot be suppressed. The fault message can be avoided by connecting a Zener diode. However, real faults can no longer be detected as well.
1056
3A2
3
TXM1.8U(-ML)TXM1.8X(-ML)
GND
U10
DC 0...10 V
10 V
(*)
Solution
15 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
3 Workarounds for NK modules 3.1 Overview
TX
M1.
8D
TX
M1.
16D
TX
M1.
8U
TX
M1.
8U-M
L
TX
M1.
8X
TX
M1.
8X-M
L
TX
M1.
8P
TX
M1.
6R
TX
M1.
6R-M
NK Type Description Meas.
NKIDP Volt-free NC/NO interrogation (maintained contact) x x x x x x
NKIDP/C1Volt-free NC/NO interrogation (maintained contact, sig. extension 6s)
x x x x x x
NKIDPH 1) Volt-free NC/NO interrogation (maintained contact) x 1) x 1) x 1) x 1) x 1) x 1)NKIDP/8 Volt-free NO interrogation (maintained contact) x x x x x xNKIC Volt-free NO interrogation (meter pulse 0.2..5Hz) x x x x x xNKID Non-loating AC/DC 6/13/240 V
NKIDH Non-floating AC/DC 6/13/240 V
NKIAVN T passive (LG-Ni1000:-50..150C, +-2K correction) x x x x xNKIAVA T passive (Pt100: 0..100C, +-2K correction) xNKIAVB T passive (Pt100: 0..200C, +-2K correction) xNKIAVC T passive (Pt100: 0..500C, +-2K correction) xNKIAVD T passive (Pt100: -50..50C, +-2K correction) xNKIT T passive (T1: -50..150C, +-4K correction) x x x xNKIAU DC 0..10 V (electr. isolated functions 500V)NKIA DC 0..10 V (voltage AC 24 V, differential)
NKIAI DC 0 (4)..20 mA (electr. isolated functions 500V)
NKOASA DC 0..10 V (voltage AC 24V) x x x xNKOAS DC 0..10 V (voltage AC 24V, safety interlock) x 2) x 2) x 2) x 2)NKOASH DC 0..10 V (voltage AC 24V, safety interlock) x 2) x 2)NKOAU DC 0..10 V (electr. isolated functions 500V)NKOAI DC 0 (4)..20 mA (electr. isolated functions 500V)NKOA Phase-cut DC 0..20V, 26 W (safety interlock)NKOAH Phase-cut DC 0..20V, 26 W (safety interlock)NKOAL Phase-cut DC 0..20V, 40 W (safety interlock)
NKOALH Phase-cut DC 0..20V, 40 W (safety interlock)
NILAH Klimo housing (phase-cut 120W)
NKDG DC 0..10 V transd., DC 15 V (volt-free DI, AI sensor/transmitter)
NKDW DC 0..10 V transd., AC 24 V (volt-free DI, AI sensor/transmitter) x x x x
NKOD Volt-free changeover, AC 250 V, 2A (safety interlock) x 2) x 2)NKODH Volt-free changeover AC 250 V, 2A (safety interlock) x 2)NKOK 3-point AC 24 V, 0.4 A (volt-free, safety interlock) x 2) x 2)NKOKFH 3-point, AC 24 V, 0.4 A (volt-free, safety interlock, spring return) x 2)
Existing Periphery
WorkaroundWorkaround
Workaround 2)
WorkaroundWorkaround
DI Universal DO
Workaround
Solution with TX-I/O
WorkaroundWorkaround
Workaround
Workaround
Key Signal fully compatible with TX-I/O Workaround described below 1) There is no manual control for inputs in the TX-I/O range 2) Safety interlock: See workaround under 3.7
16 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
3.2 NKID(H), AC/DC voltage interrogation
Digital input module for non-floating AC/DC 13V…240V signals. The module provides safe electrical isolation between the output (field device) and input (controller). External relay. Pay special attention to the voltage!
1056
3A0
1
TXM1.8D, 16D
TXM1.8U(-ML)TXM1.8X(-ML)
Uin
(*)
D20
Electrically "safe" isolation (*) External switches are permitted in the relay coil circuit. Configure D20.
Input voltage to be measured
Recommended relays Relay current consumption
AC 24 V Tyco Schrack RT1 24 VAC 32 mA AC 230 V Tyco Schrack RT1 230 VAC 3 mA DC 24 V Tyco Schrack RT1 24 VDC 17 mA DC 100 V Tyco Schrack RT1 110 VDC 4 mA
• The Tyco Schrack bases, type RT 78 724 with screw terminals are suitable for
mounting relays on standard rails • In addition to the RT types, types RX1, RY2 and MSR are also suitable.
These are not available for all input voltages but they have a lower current consumption.
Relays from other manufacturers: The contacts must be suitable for extra-low voltage. Use interface relays, not installation relays. Only the former ensure safe isolation between core and contact in accordance with VDE0160/EN50178 for low voltage circuits (SELV or PELV) in relation to hazardous current circuits.
NKID(H)
Solution for TX-I/O
Signal type for TX-I/O
External relay
Notes
Caution
17 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
3.3 NKIA / NKIAU / NKIAI, analog inputs
Third-party modules are required for these functions. We recommend modules supplied by Phoenix (Internet path for ordering and information see further below). Input module for DC 0…10 V (differential) with high-resistance isolation (input, output, supply) and a common-mode range of +/- 50V. Phoenix Type MCR-C-U-U-DC Order No. 2814469 Input module for DC 0…10 V with electrically isolated functions (500V) Phoenix Type MCR-C-U-U-DC Order No. 2814469 Input module for DC 0 (4)…20mA with electrically isolated functions (500V) (range 0 … 20mA or 4 … 20mA can be selected on front panel) For 0…20mA: Phoenix Type MCR-C-U-0-DC Order No. 2814498 For 4…20mA: Phoenix Type MCR-C-U-4-DC Order No. 2814511
TXM1.8X(-ML)
GND
DC 24 V
1056
3A1
5
1
2
5
6
8
7
GND1 GND2
U, I
http://www.phoenixcontact.com Search for MCR-C-I-U-0-DC or MCR-C-I-U-4-DC
NKIA
Solution
NKIAU
Solution
NKIAI
Solution
Ordering from Phoenix
18 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
3.4 NKOAU / NKOAI, analog outputs
Third-party modules are required for these functions. We recommend modules supplied by Phoenix (URL for ordering and information see below). Output module for DC 0…10 V with electrically isolated functions (500V) Phoenix Type MCR-C-U-U-DC Order No. 2814469 Output module for DC 0 (4)…20mA with electrically isolated functions (500V) (range 0…20mA or 4…20mA can be selected on front panel) For 0…20mA: Phoenix Type MCR-C-U-I-0-DC Order No. 2814472 For 4…20mA: Phoenix Type MCR-C-U-I-4-DC Order No. 2814371
U, I
1056
3A1
6
GND
DC 24 V
TXM1.8X(-ML)
GND3
+20..30 V
1
2 GND1
8
7
5
6GND2
http://www.phoenixcontact.com Search for MCR-C-U-I-0-DC or MCR-C-U-I-4-DC.
NKOAU
Solution
NKOAI
Solution
Ordering from Phoenix
19 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
3.5 NKOA(H) / NKOAL(H) / NILAH, phase-cut
Output module for DC 0..20V Staefa phase-cut 26W ("H" indicates module type with manual switch) Output module for DC 0..20V Staefa phase-cut 40W ("H" indicates module type with manual switch) Use Siemens interface module UA9 (40W, without manual switch), see data sheet N5133 Configure Y10.
AC 24 V
DC 0...10 V
1
2
3
4
5
6
7
8
9
NS
LS
Phs 1
Phs 2
C
Y
C
Y1
0...20 V PHS
UA9
1056
3A0
9
V
Y10s
TXM1.8U(-ML)TXM1.8X(-ML)
T1 = System transformer (the supply voltage for the UA9 can come from the system transformer or from a separate transformer))
Y1 = Magnetic valve, max. 40 W The AC 24 V supply voltage for the UA9 with an operating voltage of AC 24 V can be taken from a "V " terminal of the universal or super universal module (field supply AC 24 V). One module can supply a maximum of 4 A. Interface converter, DC 0…10V to DC 0…20V Staefa phase-cut 120W Stand-alone module in Staefa klimo housing (NB: not NK module) From 2007 this device is no longer available! Operation of an existing NILAH module from a TX-I/O module.
This requires the following power supplies:
– Separate AC 24 V transformer (must NOT be earthed on the secondary side) – DC power supply module, 15V / min.30mA Configure Y10.
NKOA(H)
NKOAL(H)
Solution
Signal type for TX-I/O
Note
NILAH
Solution 1
Signal type for TX-I/O
20 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
AC 24 V
DC 0...10 V
1
2
3
4
5
6
24
AC 24 V
Y1
0...20 V PHS
105
63A
10
7
8
23
22
21
15 V
SGND
0...10 V
ON
OFF
2
Y
T1
NILAH
DC 15 V +/- 5 %min. 30mA
T2
Y10s
TXM1.8U(-ML)TXM1.8X(-ML)
T1 = Separate transformer (must NOT be earthed on the secondary side) T2 = DC power supply module, 15V / min. 30mA
(requires safe isolation in accordance with VDE 0160 / EN 50178) Y1 = Magnetic valve, max. 120 W Replacement of a NILAH by parallel connection of up to 4 Siemens interface modules UA9, see data sheet N5133.
• The first UA9 (the master) is needed to convert DC 0…10V into a phase-cut DC 0…20 V signal.
• The other up to three modules (slaves) together supply a maximum of 120 VA. • As the "V " terminals of a universal or super universal module deliver only 4A,
a separate AC 24 V transformer is needed to feed four UA9 devices. It must NOT be earthed (earth loop).
• Use the connection diagram below – the diagram in the data sheet N5133 is incorrect!
Configure Y10.
Phs1 Phs2
1 2 3 4 5 6
8 9
NS LS
Y C+
Phs1 Phs2
5 6
8 9Y C+
UA9 MasterUA9 Slavemax. 40 VA
UA9 Slavemax. 40 VA
UA9 Slavemax. 40 VA
105
63A
11
Y C+Y C+ Y C+ Y C+
+
TXM1.8U(-ML)
TXM1.8X(-ML)
Y10S
max. 120 VA
Y1
AC 24 V
T1
1 2NS LS Phs1 Phs2
5 6
8 9Y C+
1 2NS LS Phs1 Phs2
5 6
8 9Y C+
1 2
Solution 2
Signal type for TX-I/O
21 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
3.6 NKDG, NKDW, transducer modules
The transducer modules transmit voltage signals 1:1 from input to output or from output to input without electrical separation. In addition, they have a field supply terminal for active sensors / transmitters / actors: • NKDW: AC 24 V • NKDG: DC 15 V • TX-I/O Universal or Super universal module;
Supply of the active sensors / transmitters / actors from terminal "V ". Configure U10 (input) or Y10S (output).
TXM1.8U(-ML)TXM1.8X(-ML)
GNDU10
DC 0 ... 10 V
AC 24 VL
N
1056
3A1
3
TXM1.8U(-ML)TXM1.8X(-ML)
Y10SGND
DC 0 ... 10 V
AC 24 VL
N
• TX-I/O Universal or Super universal module
plus a bus connection module, where DC 15 V is supplied (with a secure electrical separation which MUST NOT be earthed); Supply of the active sensors / transmitters / actors from terminal "V ".
• TX-I/O Universal or Super universal module plus an external supply DC 15 V with a secure electrical separation for the active sensors / transducers / actors which MUST NOT be earthed.
Configure U10 (input or Y10S (output).
TXM1.8U(-ML)TXM1.8X(-ML)
GNDU10
DC 0 ... 10 V
DC 15 V
1056
3A1
4
TXM1.8U(-ML)TXM1.8X(-ML)
Y10SGND
DC 0 ... 10 V
TXS1.EF10
V3
4
DC 15 V
GND
DC 15 VDC +15 VDC +15 V
TXM1.8U(-ML)TXM1.8X(-ML)
GNDU10
DC 0 ... 10 V
TXM1.8U(-ML)TXM1.8X(-ML)
Y10SGND
DC 0 ... 10 V
DC +15 VDC +15 V
DC 15 V + DC 15 V+
NK function
Solution for NKDW
Signal type for TX-I/O
Solution for NKDG
Signal type for TX-I/O
22 / 22
Siemens Replacement of legacy I/O modules by TX-I/O or workarounds CM110563en_04 Building Technologies Workarounds for NK modules 01 Mar 2012
3.7 Special "safety interlock" option (This option is also known as "forced control")
The NK output modules are fitted with "safety interlock" terminals. • This enables the signal from the controller to be overridden via an external
contact. • If the "OFF" terminal is switched to SGND voltage via the external contact, the
signal output goes to OFF or 0%. • If the "ON" terminal is switched to SGND voltage via the external contact, the
signal output goes to ON or 100%. • For modules with a manual switch (NKOxH) the manual switches takes priority
over the safety interlock. For migration of the safety interlock function, the states of the ON/OFF contacts must be transferred via digital input data points. These must be linked to the appropriate output data point in the application.
NK function
Solution
Siemens Switzerland Ltd. Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.buildingtechnologies.siemens.com
© 2007 - 2012 Siemens Switzerland Ltd.Subject to change