Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI 3
Contents1 Revision...................................................................................................................................... 4
2 Unit structure ............................................................................................................................. 52.1 DRC.. drive unit .............................................................................................................. 52.2 Example nameplate and type designation of drive unit .................................................. 6
3 Electrical installation................................................................................................................. 83.1 Installation instructions ................................................................................................... 8
4 Startup...................................................................................................................................... 104.1 Lifting applications ........................................................................................................ 10
2193
1186
/EN
– 0
3/20
15
1 Revision
Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI4
1 Revision
INFORMATIONThis revision contains the following changes regarding the DRC.. electronic motor:
This document does not replace the detailed operating instructions.
• Revised chapter "Unit structure / DRC.. drive unit".
• Revised chapter "Unit structure / Example nameplate and type designation of thedrive unit".
• Revised chapter "Electrical installation / UL-compliant installation".
• Revised chapter "Startup / Lifting applications".
2193
1186
/EN
– 0
3/20
15
2Unit structureDRC.. drive unit
Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI 5
2 Unit structure2.1 DRC.. drive unit
The following figure shows drive units consisting of a DRC1 / DRC2 / DRC3 / DRC4electronic motor and an R gear unit:
R..DRC2-...
[1]
[2]
R..DRC1-...
[1]
[2]
R..DRC2-...
[1]
[2]
R..DRC1-...
[1]
[2]
R..DRC3*-...
R..DRC4*-...
[1]
[2]
[3]
[3]
[3]
13979138315
[1] Electronics cover[2] DRC.. electronic motor with connection unit[3] Gear unit (here: R gear unit)* DRC3 and DRC4 in preparation
2193
1186
/EN
– 0
3/20
15
2 Unit structureExample nameplate and type designation of drive unit
Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI6
2.2 Example nameplate and type designation of drive unit2.2.1 Nameplate
The following figure gives an example of a nameplate. For the structure of the typedesignation, refer to chapter "Type designation".
76646 Bruchsal/Germany
n R
f N
Nm
A M A
Ma pk
i
Made in Germany
3~ EN61800
Hz V
18454941TENV M.L.
Nm
Th.Kl.
°CTa
IN
IP
IM
U N
kg NmM Br
kW
r/minn A[2]
[1]
50-60
26.000
85...0.04
85,6IE4
1.04156-20...40
M1
CLP 220 Miner.Öl/0.65l
1/200023.59
63
155(F)
0.55 S1 380...500
65
RF47 DRC1-005-SNI-A-ECR/IV01.1751709009.0001.11
03
18014403271536395
[1] The bar code on the nameplate (code 39) according to ISO/IEC 16388 repre-sents the unique manufacturing number (with a period as separator).
[2] Unique manufacturing number
2.2.2 Type designationThe following table shows the type designation of the DRC.. drive unit:
RF Gear unit series
47 Gear unit size
DRC Product lineDRC = Electronic motor
1 Electronic motor size1 = DRC1
2 = DRC2
3 = DRC3 (in preparation)
4 = DRC4 (in preparation)
–
005 Power rating005 = 0.55 kW
015 = 1.5 kW
030 = 3.0 kW (in preparation)
040 = 4.0 kW (in preparation)
–
SNI DRC.. installation technologyDBC = Direct Binary Communication
DAC = Direct AS-Interface Communication
DSC = Direct SBus Communication
SNI = Single Line Network Installation
2193
1186
/EN
– 0
3/20
15
2Unit structureExample nameplate and type designation of drive unit
Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI 7
–
A Version
–
ECR Extended control range (standard)ECR = Single-turn encoder / Extended control range
ACR = Multi-turn encoder / Extended control range (in preparation)
/
IV DRC.. optionIV = Plug connector
BY1C = DRC1 brake
BY2C = DRC2 brake
BY4C = DRC3/4 brake (in preparation)
BW1 = Integrated braking resistor DRC1
BW2 = Integrated braking resistor DRC2
BW3 = Integrated braking resistor DRC3/4 (in preparation)
PE = Pressure compensation fitting electronics
2193
1186
/EN
– 0
3/20
15
3 Electrical installationInstallation instructions
Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI8
3 Electrical installation3.1 Installation instructions3.1.1 UL-compliant installation (DRC1/2 only)
INFORMATIONDue to UL requirements, the following chapter is always printed in English independ-ent of the language of the publication.
Power terminals
Observe the following notes for UL-compliant installation:• Use 75 °C copper wire only.• DRC1/2 uses cage clamp terminals
Short circuit current rating
Suitable for use on a circuit capable of delivering not more than 200,000 rms symmet-rical amperes when protected by 600 V non-semiconductor fuses or 500 V minimuminverse time circuit breakers.• DRC1/2, the max. voltage is limited to 500 V. Suitable for motor group installation on a circuit capable of delivering not more than5,000 rms symmetrical amperes when protected by maximum 40 A, 600 V non-semi-conductor fuses or 500 V minimum 40 A maximum inverse time circuit breaker with aninterrupting rating of 5 kA minimum.• DRC1/2, the max. voltage is limited to 500 V.
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.Branch circuit protection must be provided in accordance with the National ElectricalCode and any additional local codes.The table below list the permitted maximum branch circuit protection:
Series Non-semiconductor fuses
Inverse time circuit breakers
DRC1/2 40 A / 600 V 500 V minimum / 40 A maximum
2193
1186
/EN
– 0
3/20
15
3Electrical installationInstallation instructions
Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI 9
Motor overload protection
DRC1/2 is provided with load and speed-sensitive overload protection and thermalmemory retention upon shutdown or power loss.The trip current is adjusted to 150% of the rated motor current.
Ambient temperature
DRC1/2 is suitable for an ambient temperature of 40 °C, max. 60 °C with derated out-put current. To determine the output current rating at temperatures above 40 °C, theoutput current should be derated by 3.0% per K between 40 °C and 60 °C.
Wiring diagrams
For wiring diagrams, refer to chapter "Electrical installation".
2193
1186
/EN
– 0
3/20
15
4 StartupLifting applications
Revision – DRC..-DBC, DRC..-DAC, DRC..-DSC, DRC..-SNI10
4 Startup4.1 Lifting applications
WARNINGDanger of fatal injury if the hoist falls.
Severe or fatal injuries.
• The DRC.. drive unit is not designed for use as a safety device in lifting applica-tions.
• Use monitoring systems and mechanical protection devices to ensure safety.
• In combination with lifting applications and "functional safety", the control must becarried out according to SS1(c) (Safe stop 1, function variant c according toEN 61800-5-2). Observe the "DRC.. electronic motor – functional safety" manual.