ES-6483 Rev.3
52U–2–AD2MODELINPUT2 : 500V AC / 5AAUXILIARY POWER SUPPLYAD2 : 85 – 253V AC / 85 – 253V DC (universal)
MODEL
Power Transducer Series
52U
Functions & Features• Measures simultaneously several variables of a
heavy-current power system: current, voltage,active, reactive and apparent power, active andreactive energy, neutral contactor current, powerfactor and frequency
• High contrast 14-mm high LED display• All measured values, counter values, display
mode, setting data are stored in the non-volatilememory at the power off
• Conversion factors, system configuration, inter-val times are programmable using the front keys
• Program lockout jumper• AC/DC universal power supply of wide range• IP 66 robust front for tough industrial applications• Conforms to IEC 60688Typical Applications• Multi-functional power monitor incorporated in an
electric device: saves space, wiring works, and cost
MODEL & SUFFIX CODE SELECTION
MULTI POWER MONITOR
P. 1 / 4
ODERING INFORMATIONSpecify code number. (e.g. 52U-2-AD2)•Factory setting
RELATED PRODUCTS•Modbus extension module (model: 52U-TM)
GENERAL SPECIFICATIONSConstruction: 96-mm square (1/4 DIN size) panel
flush mountedEnclosure protection
Front panel: IP66Terminal block and housing: IP20
ConnectionInput: Connector type screw terminal block (ap-
plicable single-core wire size 0.5 – 2.5 mm2
or multi-strand wire size 0.5 – 1.5 mm2)Output, power: Connector type clamp terminal
block (applicable single-core or multi-strand wire size 0.5 – 1.5 mm2)
Configuration: Single phase, 3-phase/3-wire bal-anced/unbalanced load, 3-phase/4-wirebalanced/unbalanced load
Housing material: Flame-resistant resin (black)Isolation: Three way (input to output to power)Program lockout: JumperZero-value suppression
Phase current: < 1%(applied also to power calculation)
Neutral current: < 3%
Measured variablesVoltage U: 1 – N, 2 – N, 3 – N, 1 – 2, 2 – 3, 3 – 1Current I: 1, 2, 3, NAverage current I avg: 1, 2, 3Active power P: 1, 2, 3, ∑Reactive power Q: 1, 2, 3, ∑Apparent power S: 1, 2, 3, ∑Power factor PF, cosϕ: 1, 2, 3, ∑Power factor inductive, minimum value: 1, 2, 3Power factor capacitive, minimum value: 1, 2, 3Frequency: U, IActive energy incoming / outgoing: ∑Reactive energy inductive / capacitive: ∑5 active power intervals (demand): ∑5 reactive power intervals (demand): ∑5 apparent power intervals (demand): ∑
P
52Umm (inch)
96 (3.78)
96(3.78)
53(2.09)
Pulse / alarm output SO1 OFFPulse / alarm output SO2 OFFTransformer ratio 1 : 1System configuration 3-phase/3-wire
unbalanced load
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
ES-6483 Rev.3
Specifications subject to change without notice.
DISPLAYLED display: 14 mm high, red, adjustable bright-
ness;3 digits with sign, frequency: 4 digits,Energy: 8 digits
Display suppression
INPUTRated frequency: 50 / 60 HzRated voltage
Line-to-line (delta voltage): 500VLine-neutral (phase voltage): 290V
Waveform: Sine, 3rd harmonic contents max. 15%Consumption VA
Current circuit: ≤ I2 · 0.01Ω / phaseVoltage circuit: ≤ U2 / 300kΩ / phase
Thermal rating, continuousSingle-phase system: 10A at 346VThree-phase system: 10A at 600V
Thermal rating, short time
Operational rangeVoltage, current, apparent power: ≤120% of the ratingActive/reactive power: ≤ ±120% of the ratingFrequency: 45 – 65 HzPower factor: ≤ ±1Overload indicator: oL
OUTPUTDepending on the function selected, the two digital outputs(open collector) can be used as pulse outputs for actual andreactive energy or as limit alarm outputs.
P. 2 / 4
INPUTNUMBER OVERLOAD
INTERVALSOF INPUTS DURATION
557V, L – N 10 1 sec. 10 sec.100A 10 1 sec. 100 sec.100A 5 3 sec. 5 min.
ALARM OUTPUTThe limit setpoints can be associated with any measurand.Depending on the type of connection, an OR or an ANDoperation is possible for the following values.Measurands applicable to OR/AND operation
3-wire unbalanced load: U12 / U23 / U31, I 1 / I 2 / I 3 /I avg1 / I avg2 / I avg3
4-wire unbalanced load: U1 / U2 / U3, U12 / U23 /U31, I 1 / I 2 / I 3 / I avg1 / I avg2 / I avg3, P1 / P2 /P3, Q1 / Q2 / Q3, S1 / S2 / S3, PF1 / PF2 / PF3
Alarm ON: OR operation of phase measurandsAlarm OFF: AND operation of phase measurandsDelay time: Fixed at 1 sec.
PULSE OUTPUTThe active and reactive energy can be read out at the pulseoutputs for driving electronic and elecromechnical count-ing mechanisms.The pulse rate is programmable.Programmable pulse rate range:
1 to 5000 pulses/Wh thr. GWh1 to 5000 pulses/varh thr. Gvarh
Pulse duration: >100 msec. (fixed)
INSTALLATIONPower input
AC: Operational voltage range 85 – 253V,45 – 400 Hz, ≤ 3VA
DC: Operational voltage range 85 – 253V,ripple 10% p-p max., ≤ 3W (approx.)
Operating temperature: -10 to +50°C (14 to 122°F)Storage temperature: -25 to +55°C (-13 to +131°F)Operating humidity: 93% RH max. (non-condensing)Mounting: Panel flush mountingDimensions: W107×H96×D53 mm (4.21"×3.78"×2.09")Weight: 250 g (0.55 lbs)
PERFORMANCEAccuracy
Voltage, current: ±0.5%Power: ±1%Power factor: ±1%Energy: ±1%Frequency: ±0.02 Hz
Dielectric strength: The voltage inputs are fittedwith protection impedances for doubleinsulation.3700V AC @1 minute(voltage input to power or current inputor output or housing)3700V AC @1 minute (power to currentinput or output or housing)3700V AC @1 minute (current input topower or output or housing)2200V AC @1 minute(current input to current input)
DISPLAY CONDITION
Phase angle PF ---- Sx < 1% of the ratingNeutral current IN 0 IN < 3% of the ratingPhase current Ix 0 Ix < 1% of the rating
+Uext
RL
RL
SO2
SO1
20
21
22
–
U
Uext ≤ 40V DCIL ≤ 150mA
(OFF : Leakage current ≤ 0.1mA)(ON : Terminal voltage ≤ 1.2V)
Pulse Output
Alarm Output
t
U
t
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
ES-6483 Rev.3P. 3 / 4
FRONT & REAR VIEWS
STANDARDS & APPROVALSCE conformity: EMC Directive (2004/108/EC)
EMI EN 61000-6-4EMS EN 61000-6-2
Low Voltage Directive (2006/95/EC)EN 61010-1Class II, Measurement category III,Pollution degree 2
IEC Standard: IEC 60688 usage group II
-180 -90 0 90 180
inductive
outgoing incoming outgoing
capacitive
P Q
inductive capacitive
ϕ
P52U
1
22 21 20 14 15
FRONT VIEW REAR VIEW
2 3 4 5 6 7 8 9 11
Pulse/AlarmOutput
Power Supply
Program Lock Jumper
Unit Display
System Display
Up KeyDown Key
Input
Data Display
Program Key
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS mm (inch)
P
1
22 21 20 14 15
2 3 4 5 6 7 8 9 11
96 (3.78)
107 (4.21)
91.5 (3.60)
91.5
(3.6
0)
46 (1.81)5 (.20)
65 (2.56)*
96 (3
.78)
*52U-TM module
92+
0.8
(3.6
5)0
(3.6
3)
92+0.8 (3.65)
0 (3.63)
PANEL CUTOUT
Panel thickness : 2 to 25.4 mm (0.08 to 1 inch)
FUNCTIONSampling rate: 32 times per cycleStandard to calculate measurands: DIN 40110The instrument measures the currents, the voltages, thefrequency, and the phase angles betwen the individualcurrents and voltages. All other measurands such as theactive / reactive / apparent power, the active / reactiveenergy, the neutral current, are calculated from themeasured valiables.Refer to the figure below for the terminology of the 4-quadrant operation.
MOUNTING REQUIREMENTS mm (inch)
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
ES-6483 Rev.3
Specifications subject to change without notice.
Power Supply
Input
Pulse / AlarmOutput
Program LockJumper
U1I1
1
22 21 20 14 15
2 3 4 5 6 7 8 9 11
U2I2
U3I3
N
L1
N
k l
K L
2 11 31
Single-phase
Connect the voltage according to the followingtable for current measurement in L2 or L3:
3-phase/3-wirebalanced loadI : L1
3-phase/3-wireunalanced load
L1
N
v
V
u
Uk l
K L
2 11 31
System /Application Terminal
L1
L2
L3
5 182 3
L1
L2
L3
k l
K L
5 182 3
L1
L2
L3
u
U
v
V
v
V
u
Uk l
K L
5 182 3
Current Terminals 2 5 8
L2 1
1
3
3
L2
L3
L3
L1
L1
L2L3
L1
N
2 11 31
L1
L2
L3
5 182 3 7 9
L1
L2
L3
k l
K L k l
K L
5 182 3 7 9
L1
L2
L3
u
U
v
V
v
V
u
Uk l
K L k l
K L
5 182 3 7 9
L1
L2
L3
k l
K L k l
K L
xxx
uuu
XXX
UU U
5 182 3 7 9
Connect the voltage according to the followingtable for current measurement in L2 or L3:
3-phase/4-wirebalanced loadI : L1
3-phase/4-wireunalanced load
Current Terminal 2 11
L2 1
1
3
3
L2
L3
N
NL3
L1
N
11 312
L2
L3
L1
N
k l
K L
2 11 31
L2
L3
L1
v
V
u
Uk l
K L
2 11 31
N
L2
L3
L1
L2
L3
k l
K L
k l
K L
k l
K LN
xxx
uuu
XXX
UU U
5 1182 1 3 4 6 7 9
L1
L2
L3
N
5 1182 1 3 4 6 7 9
L1
L2
L3
k l
K L
k l
K L
k l
K LN
5 1182 1 3 4 6 7 9
System /Application Terminal
CONNECTING MODE
TERMINAL CONNECTIONS
P. 4 / 4
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 1 / 12
BEFORE USE ....Thank you for choosing M-System. Before use, check thecontents of package you received as below.If you have any problems or questions with the product,please contact M-System's Sales Office or representatives.
PACKAGE INCLUDES:Multi Power Monitor .................................................. (1)
MODEL NO.Check that model No. described on specification label isexactly what you ordered.
INSTRUCTION MANUALThis manual describes necessary points of caution when youuse this product, including installation, connection and basicmaintenance procedures.
POINTS OF CAUTION AUXILIARY POWER INPUT RATINGS• Power input ratings are specified by the model numbersuffix code.
AC power: 85 – 253V AC, 45 – 400 Hz, ≤3VADC power: 85 – 253V DC, ≤3W (approx.)
GENERAL PRECAUTION• Before you remove or mount the unit, turn off the powersupply and input signal for safety.
ENVIRONMENT• Indoor use• When heavy dust or metal particles are present in the air,install the unit inside proper housing and ventilate it.• Do not install the unit where it is subjected to continuousvibration. Do not apply physical impact to the unit.• Environmental temperature must be within -10 to +50°C(14 to 122°F) with relative humidity within 93% RH in orderto ensure adequate life span and operation.
WIRING• Do not install cables (power supply, input and output) closeto noise sources (relay drive cable, high frequency line, etc.).• Do not bind these cables together with those in which noisesare present. Do not install them in the same duct.
AND ....• The unit is designed to function as soon as power issupplied, however, a warm up for 30 minutes is required forsatisfying complete performance described in the data sheet.
LIGHTNING SURGE PROTECTIONIn order to protect the unit from lightning surges enteringthrough signal and power supply cables, use of appropriatelightning surge protectors are recommended. Please contactM-System.
INSTRUCTION MANUAL
MODEL 52UMULTI POWER MONITOR
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 2 / 12
INSTALLATION EXTERNAL DIMENSIONS mm (inch)
PANEL CUTOUT mm (inch)
P
1
22 21 20 14 15
2 3 4 5 6 7 8 9 11
96 (3.78)
107 (4.21)
91.5 (3.60)
91.5
(3.6
0)
46 (1.81)5 (.20)
65 (2.56)*
96 (3
.78)
*52U-TM module
92+
0.8
(3.6
5)0
(3.6
3)
92+0.8 (3.65)
0 (3.63)
PANEL CUTOUT
Panel thickness : 2 to 25.4 mm (0.08 to 1 inch)
ABBREVIATIONS
Display Display
Maximum value
Minimum value
Average value
Maximum average value
Minimam value for power factor, the worst out of the3 values of P1, P2 or P3 is displayed
Neutral current
Inductive
Capacitive
Incoming
∑∆
Outgoing
Active power interval
Reactive power interval
Apparent power interval
Last interval; t-0
Previous intervals; t-1, -2, -3, -4
Overload, out of range indicator
System value
Delta voltage
Energymeter
High tariff
Low tariff (Unavailable without optional module)
Meaning Meaning
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 3 / 12
TERMINAL CONNECTIONS
Power Supply
Input
Pulse / AlarmOutput
Program LockJumper
U1I1
1
22 21 20 14 15
2 3 4 5 6 7 8 9 11
U2I2
U3I3
N
L1
N
k l
K L
2 11 31
Single-phase
Connect the voltage according to the followingtable for current measurement in L2 or L3:
3-phase/3-wirebalanced loadI : L1
3-phase/3-wireunalanced load
L1
N
v
V
u
Uk l
K L
2 11 31
System /Application Terminal
L1
L2
L3
5 182 3
L1
L2
L3
k l
K L
5 182 3
L1
L2
L3
u
U
v
V
v
V
u
Uk l
K L
5 182 3
Current Terminals 2 5 8
L2 1
1
3
3
L2
L3
L3
L1
L1
L2L3
L1
N
2 11 31
L1
L2
L3
5 182 3 7 9
L1
L2
L3
k l
K L k l
K L
5 182 3 7 9
L1
L2
L3
u
U
v
V
v
V
u
Uk l
K L k l
K L
5 182 3 7 9
L1
L2
L3
k l
K L k l
K L
xxx
uuu
XXX
UU U
5 182 3 7 9
Connect the voltage according to the followingtable for current measurement in L2 or L3:
3-phase/4-wirebalanced loadI : L1
3-phase/4-wireunalanced load
Current Terminal 2 11
L2 1
1
3
3
L2
L3
N
NL3
L1
N
11 312
L2
L3
L1
N
k l
K L
2 11 31
L2
L3
L1
v
V
u
Uk l
K L
2 11 31
N
L2
L3
L1
L2
L3
k l
K L
k l
K L
k l
K LN
xxx
uuu
XXX
UU U
5 1182 1 3 4 6 7 9
L1
L2
L3
N
5 1182 1 3 4 6 7 9
L1
L2
L3
k l
K L
k l
K L
k l
K LN
5 1182 1 3 4 6 7 9
System /Application Terminal
CONNECTING MODE
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 4 / 12
DISPLAY & OPERATING FRONT PANEL CONFIGURATION
AVAILABLE MEASUREMENT DATA
P52U
Unit Display
System Display
Up KeyDown Key
Data Display
Program Key
Available measurement dataPhase voltage U1, U2, U3
Top displayexample
230
400
235227
405395
2.35
56.1
2.392.042.07
60.5
1.241.51
2.56
4589 **1234458912349876123498761234
3.43
231
402
236226
406397
2.37
56.20.45
2.402.052.05
60.4125
239
1.542.31
1.231.52
2.58
5.336.230.870.880.890.880.760.84
2356 ***56782356567854329876
23412310.1
54329876
3.44
229 VVVVVVAAAAAkWkWkWkWVArVArVArVArVAVAVAVAϕ
ϕ
ϕ
ϕ
ϕ
ϕ
kWhHz
kWhkWhkWhkVarhkVarhkVarhkVarhkWVArVA ∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∑
∆
∆
∆ 398
231225
403396
2.34
56.5
2.382.072.04
60.3
1.221.54
2.60
49.99
3.67
Center displayexample
Bottom displayexample
Unitsdisplay
Systemdisplay
Maximum phase voltage U1max, U2max, U3max
Minimun phase voltage U1min, U2min, U3min
Delta voltage U12, U23, U31
Maximum delta voltage U12max, U23max, U31max
Minimum delta voltage U12min, U23min, U31min
Phase current I1, I2, I3
Maximum phase current I1max, I2max, I3max
Average phase current I1avg, I2avg, I3avg
Maximum average phase current I1avgmax, I2avgmax, I3avgmax
Neutral current INActive power P1, P2, P3
Maximum active power P1max, P2max, P3max
Active power system PMaximum active power system Pmax
Reactive power Q1, Q2, Q3
Maximum reactive power Q1max, Q2max, Q3max
Reactive power system QMaximum reactive power system Qmax
Apparent power S1, S2, S3
Maximum apparent power S1max, S2max, S3max
Apparent power system SMaximum apparent power system Smax
Power factor PF1, cosϕPower factor PF2, cosϕPower factor PF3, cosϕPower factor system PF, cosϕMinimum value power factor inductiveMinimum value power factor capacitiveFrequency FActive energy incoming EP high tariffActive energy incoming EP low tariff *Active energy outgoing EP high tariffActive energy outgoing EP low tariff *Reactive energy incoming EQ high tariff
Reactive energy incoming EQ low tariff *Reactive energy outgoing EQ high tariffReactive energy outgoing EQ low tariff *5 active power intervals Pint0, Pint1, ...5 reactive power intervals Qint0, Qint1, ...5 apparent power intervals Sint0, Sint1, ...
*Available with optional 52U-TM module. **Upper 8 digits. ***Lower 8 digits.
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 5 / 12
P
1
a b c d e f
U2
U3
U1
U2max.
U3max.
U1max.
U23
U31
U12
U23max.
U31max.
U12max.
U2min.
U3min.
U1min.
U23min.
U31min.
U12min.
2 I2I3
I1I2max.
I3max.
I1max.
I2avgmax.
I3avgmax.
I1avgmax.
IN
Displaylevels
I2avg
I3avg
I1avg
3 P2
P3
P1
P2max.
P3max.
P1max.
Pmax.P
Qmax.Q
Smax.S
4 Q2
Q3
Q1
Q2max.
Q3max.
Q1max.
5
6
S2
S3
S1
S2max.
S3max.
S1max.
10 QPF
PSF
P
PF1 PF2 PF PFminind PFmincapPF3
7 F
8 EP inc HT1 EP inc LT2 EP out LT1EP out HT1
9 EQ ind HT1 EQ inc LT2 EQ out LT1EQ out HT1
11 Pint0 Pint1 Pint3 Pint4Pint2
Qint0 Qint1 Qint3 Qint4Qint2
Sint0 Sint1 Sint3 Sint4Sint2
12
13
INmax.
P
1
a b c d e
U2
U3
U1
U2max.
U3max.
U1max.
U2min.
U3min.
U1min.
2 I2I3
I1I2max.
I3max.
I1max.
I2avgmax.
I3avgmax.
I1avgmax.
Displaylevels
I2avg
I3avg
I1avg
3 P Pmax.
4 Q Qmax.
5
6
S Smax.
10 QPF
PSF
P
PF PFminind PFmincap
7 F
8 EP inc HT1 EP inc LT2 EP out LT1EP out HT1
9 EQ ind HT1 EQ inc LT2 EQ out LT1EQ out HT1
11 Pint0 Pint1 Pint3 Pint4Pint2
Qint0 Qint1 Qint3 Qint4Qint2
Sint0 Sint1 Sint3 Sint4Sint2
12
13
P
1
a b c d e
U Umax. Umin.
2 I Imax. Iavgmax.
Displaylevels
Iavg
3 P Pmax.
4 Q Qmax.
5
6
S Smax.
10 QPF
PSF
P
PF PFminind PFmincap
7 F
8 EP inc HT1 EP inc LT2 EP out LT1EP out HT1
9 EQ ind HT1 EQ inc LT2 EQ out LT1EQ out HT1
11 Pint0 Pint1 Pint3 Pint4Pint2
Qint0 Qint1 Qint3 Qint4Qint2
Sint0 Sint1 Sint3 Sint4Sint2
12
13
DISPLAY LEVELSWithin a level (1, 2, 3, ....) you can change the 3 displays to thenext mode (a, b, c, ....) with the P key. From the last mode, thedisplay changes to mode ‘a’ again.Change to the next level with the Up or Down keys.
4-WIRE UNBALANCED LOAD
3-WIRE UNBALANCED LOAD
SINGLE PHASE AND 3-WIRE/4-WIRE BALANCED LOAD
OPERATING BRIGHTNESS13 levels: Press Down key continuously to change the displaydarker, Up key to brighter.
DELETE / CLEARTo delete the minimum or maximum values, or the energyvalues of the displayed measurements, press the Up / Downkeys at once.If the jumper is in the Lock position, resetting of the abovemeters is disabled.
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 6 / 12
PROGRAMMINGFor modifications, the jumper on the backside of the device must be removed.The following tables show all parameters with their adjustable ranges or possible selections respectively. The black numbersgive a cross-reference to the appropriate item No. in the table.1) Starting at the measurands display by pressing the key P, you may go to the menu level.
Then you can select the desired menu item by pressing the key P for a short period.2) Use Down key to enter the level where the desired parameter is displayed.3) Pressing P for a short period will force the selectable element to flash.
The flashing content may be modified using the keys Down or Up.4) Press P for a longer time to leave the parameter or menu level.5) All settings will be stored in the non-volatile memory even in case of power off.
HintsFirst you have to set the system configuration and the transformer ratios because further measurand selections, alarm limitsettings, etc. will depend on them.
PARAMETERS OVERVIEW
1
Topmost displayMiddle display
Undermost display(* default)
Meaning HintsNo.
3-phase/4-wire, unbalanced load
3-phase/3-wire, unbalanced load
3-phase/4-wire, balanced load
3-phase/3-wire, balanced load
Single-phase system
Enter any 3-digit number followed by the appropriate power unit selection in steps of factor 10.
No output
System configuration
2 Primary voltage of an external transformer on the voltage input (phase voltage)
Secondary voltage of an external transformer on the voltage input (phase voltage)
Primary current of an external transformer on the current input
Secondary current of an external transformer on the current input
Operating mode of both digital outputsout.1 and out.2
Output switched-off
Energy pulse output
Alarm output
*
3 *
4 *
5 *
100V to 999kV
100V to 999V
1.00A to 999kA
1.00 A to 9.99A
*
6 /
*
The output generates energy pulses depending on the rate set under 11 .The meter measurands to output may beselected under 10 .
If the alarm limit 8 is exceeded, the output will be active (current flows).If the measurand is below limit 9 ,the output will be passive.The source of the monitored is selectable under 7 .
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 7 / 12
7 / Alarm supervision source
Frequency
Neutral current
Apparent power interval
Reactive power interval
Active power interval
Power factor (cosϕ)
Apparent power
Reactive power
Active power
Voltage
Phase voltage (line-neutral)
Delta voltage (line-to-line)
Average current (bimetal)
Phase current
Alarm ON limit
: ON = OR-operation of phase measurandsOFF = AND-operation of phase measurands
The maximum values of the alarm limits depend on the possible measuring range, converted into possible primaryvalues given by the selected system configuration and transformation ratios.Alarm OFF limit
Source of energy meters for pulse output
Reactive energy capacitive, low tariff
Reactive energy capacitive, high tariff
Reactive energy inductive, low tariff
Reactive energy inductive, high tariff
Active energy outgoing, low tariff
Active energy outgoing, high tariff
Active energy incoming, low tariff
Active energy incoming, high tariff
System Configuration Type
1L3Lb4Lb
3Lu
4Lu
*
8
9 /
*
*
/
10 /
*
Topmost displayMiddle display
Undermost display(* default)
Meaning HintsNo.
This selection is presented only ifoperating mode 6 is set to ALM previously.
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 8 / 12
11
12 *
/ *
13
16
*14
15 *
*
*
Number of pulses per dislayed energyunit. After entering a number from 1 to 5000 you may input the scaling.
Time interval in minutes for the calculation of power intervals
1 to 5000 /Wh to GWh
1200, 2400, 4800、9600, 19.2k
1 to 60 minutes
Digital input operating mode
Input inactive
High/low tariff switching input
Power interval input synchronization
Baud rate selection Unavailable without optional module.
Unavailable without optional module.
Unavailable without optional module.
Unavailable without optional module.
Unavailable without optional module.
Unavailable without optional module.
Unavailable without optional module.no parity
even parity
odd parity
space
Device address (Modbus)
Topmost displayMiddle display
Undermost display(* default)
Meaning HintsNo.
LOCKING THE CONFIGURATIONPlace the jumper in the LOCK position to prevent any settingchange.
FACTORY SETTINGPulse / alarm output SO1: OFFPulse / alarm output SO2: OFFTransformer ratio: 1 : 1Jumper: NOT in the LOCK positionSystem configuration: 3-phase/3-wire unbalanced loadInterval: 15 minutes
LOCK
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 9 / 12
PROGRAMMING EXAMPLES 3-PHASE/3-WIRE UNBALANCED LOAD VOLTAGE TRANFORMER RATIO &
SYNCHRONIZATION INTERVAL
1. Press > 2 sec.
2. Press (present setting is displayed)
3. Press (alterable parameters flashes)
4. Press / to select desired setting
5. Press (takes over new setting).
Display stops flashing
P
P
P
5. Press > 2 sec. to return to display levelP
1. Press > 2 sec.P
2. Press (transformer ratio menu)P
4. Press (leftmost digit flashes)P
6. Press (middle digit flashes)P
8. Press (rightmost digit flashes)P
10. Press (decimal point flashes)P
12. Press (takes over new value).
The display stops flashingP
3. Press (present setting of primary voltage)
5. Press / to select desired setting
7. Press / to select desired setting
9. Press / to select desired setting
11. Press / until the decimal point is on the
disired position and the kilo/Mega display is correct.
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 10 / 12
14. Programming procedure same as for primary voltage (1 thr. 12)
13. Press (present setting of secondary voltage)
15. Press until the topmost display as shown
16. Press three timesP
17. Press (present setting of synchronization interval
in minutes)
18. Press (left digit flashes)P
19. Press / to select desired setting
21. Press / to select desired setting
20. Press (right digit flashes)P
22. Press (takes over new value).
The display stops flashingP
23. Press > 2 sec. (return to display level)P
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 11 / 12
FLOWCHART
P P P
1 2 6 6
1073
4 8 11
95
Pulse/alarm output 1
A
B
C
Transformer ratiosSystem configuration
Menu level
Parameter level
Display level
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
52U
EM-6483 Rev.2P. 12 / 12
P P
P< 2 s
6 6 12 13 14
15
15
107
8 11
5
P< 2 s
PP
Measurand display
A
B
C
Back from any other display
Pulse/alarm output 2 Digital input
Parameters valid with optional 52U-TM module
COMPower interval
M-SYSTEM WARRANTYM-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that suchproduct was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. Tosubmit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIEDWARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL ORSPECIAL DAMAGES OF ANY KIND WHATSOEVER.M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: info@m-system.co.jp
Rugghölzli 2CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18Fax +41 (0)56 222 10 12
mailbox@sentronic.comwww.sentronic.comProdukte, Support und Service
SENTRONICAG
top related