UNIT DIAGRAMS
Unit: mm
SMZU75V2AI, SMZU96V2AI
792729
345
613
613
348
SMZU120V2AI
370 602
649
649
1240727
SMZU135V2AI, SMZU150V2AI
376 607
649
649
1240727
SMZU175V2AI, SMZU190V2AI, SMZU215V2AI
376
704
704
607
1240727
UNIT INSTALLATION SPACE REQUIREMENTS
9.1 Selection of outdoor unit installation site
VRF units are used in a lot of situations and serve wider users. If the unit is installed in a living environment, the cooling, heating and noise requirements will be higher, especially for the aged and infants. Therefore, the indoor/outdoor unit model with sufficient capacity and low noise should be preferred during model selection. It is not advisable to install the outdoor unit outside the bedroom, study room, or meeting room. For the commercial site, it is improper to install the outdoor unit near the office.
9.2 External dimensions and mounting hole dimensions of the outdoor unit
Unit: mm
External and installation dimensions of SMZU75V2AI, SMZU96V2AI and SMZU120V2AI:
792
930 765
729
1605
1
22
15
1 Mounting hole postion
External and installation dimensions of SMZU135V2AI and SMZU150V2AI:
1200
7651340
729
1605
2
22
15
2 Mounting hole postion
External and installation dimensions of SMZU175V2AI, SMZU190V2AI and SMZU215V2AI:
1740
729
22
15
1340 765
1200
Mounting hole postion
External unit installation space requirements
Unit: mm
1) If all sides of the outdoor unit (including the top) are surrounded by walls, process according to the following requirements for installation space:Installation space requirements for the single-module unit
Electrical BoxOutlet on this side
Air Outlet
>10
00
>30
00
>1000>1000
>12
00
Installation space requirements for the dual-module unit
Electrical BoxOutlet on this side
Air Outlet
>10
00
>200 >30
00
>1000>1000
>12
00 >200
Installation space requirements for triple-module unit
Electrical BoxOutlet on this side
Air Outlet
>10
00
>200>200 >30
00
>1000>1000
>12
00 >200>200
Installation space requirements for quad-module unit
Electrical BoxOutlet on this side
Air Outlet
>10
00
>200
>200>200>200
>200>200 >30
00
>1000>1000
>12
00
2) If there is a crown wall (such a barrier against wind) above the machine top, the machine top should be more than 3000 mm away from the crown wall in principle. If the spaces around the front, rear, left side, and right side of the machine are all open spaces, the machine top should be more than 1500 mm away from the crown wall, as shown in Figure (a). If the dimension is less than 1500 mm or the spaces around the machine are not open spaces, it is required to use a return duct to keep smooth ventilation, as shown in Figure (b).
Air Outlet
>15
00
Crown wall
When the distance is less than 1500mm, connect an air duct so as to keep good ventilation.
>1000
>200
Figure (a) Figure (b)Installation space requirements of multiple outdoor unitsTo ensure smooth ventilation, an open space must be ensured above the unit top, and there is no barrier against wind.If there is an open space at the front side and left side (or right side) of the outdoor unit, the units should
be installed towards the same direction or reverse direction.
>200 >200 >1000
>12
00>
1000
>200>200
>1000 >1200
>1000
No limit on the height of wall
Front side
Front side
Back side
Back side
Max. 4 sets side by side
>200 >200 >200 >1000
>12
00>
1200
>200>1000 >
1200>
1200
No limit on the height of wall
Front side
Front side
Back sideBack side
Max. 4 sets side by side
3) Considering the seasonal wind in outdoor unit installation
Correct Incorrect:In this case, the defrosting duration will be extended.Seasonal wind Seasonal wind Seasonal windSeasonal wind
Protective cover
Return air
Return air Return air
Return air Front Front
Front
Front
4) Considering snow in outdoor unit installation
Correct Incorrect
Seasonal wind Seasonal wind
Protective cover at the supply air outlet (field supplied)
Protective cover at the return air inlet (field supplied)
The height of the base should higher than that of the snowfall.
5) When the outdoor unit is installed on equipment, an air exhaust pipe should be connected, the aperture opening ratio of the louver cannot be smaller than 80%, and the included angle between the louver and the horizontal plane should be smaller than 20°.