VERMONT YANKEEO
NUCLEAR POWER CORPORATION
-~
P.O. Box 157, Governor Hunt Road
'yf y) vernon. vermont 05354-0157\
.(802) 257-7711s
!.)m
December 10, 1992VY-RCE-92-045
BVY 92-137
U.S. Nuclear Regulatory CommissionWashington, D.C. 20555
Attn: Document Control Desk
Reference: a) License No. DPR-28 (Docket No. 50-271)
Dear Sir:
Submitted herewith is the Monthly Statistical Report for the VermontYankee Nuclear Power Station for the month of November 1992.
Very truly yours,
Vermont Yankee Nuclear Power Corporatio.'
Wanen P. M|urphyA|tmj)dw.-
V
Senior Vic6 Feesident, O tions
cc: USNRC, Region IUSNRC Resident Inspector, VYNPS
000 0 |9212160250 921130PDR ADOCK 0S000271 i\R PDR
I
..- ._. - - --__. __
'.'.
*
.
9 e
VERMONT YANKEE NUCLEAR POWER STATION
MONTHLY STATISTICAL REPORT 92-11
FOR THE MONTII OF NOVEMBER 1992
.
- . - . , . - .~ . . , , , - . . . . , , , . --n,, .. .-, ,_,, . ,, ,- y~, ,.e., e..,-. re.,m ,.
_-. . __- . _- - - . - - - -
i OPERATING- DATA REPORT:
*
; DOCKET NO. 50-271- -
i DATE- 921210'
! COMPLETED BY G.A..WALLIN'
i
i -TELEPHONE (802)257-7711 j
! OPERATING STATUS'
1. Unit Name: Vermont Yankee ,
I - || 2. Reporting Period: November NOTES: |
: |
j 3. Licensed Thermal Power (MWt) :1593
4. Nameplate Rating (Gross MWe) : 5.4_Q
j 5. Design Electrical Rating (Net MWe): 514 (oc) 504 (cc)!
} 6. Maximum Dependable Capacity (Gross MWe) : 115i
7. Maximum Dependable Capacity (Net MWe) : 124
8. If changes, occur in capacity ratings (Items Number 3 through 7) since;; last report, give reasons:,' N/A,
! 9. Power level to whicF restricted, if any(Net MWe) : N/A
10. keasons for restrictions, if any: N/A
! This Month Yr-to-Date Cumulative| 11. Hours in Reporting Period 720.00 8040.00 175320.00d' .2. Number Of Hours Reactor was Critical 720.00 6998.79 _ 143452.35
11 Reactor Reserve Shutdown Hours 0.00 0.00 0.00;
i -14. Hours Generator On-Line 720.00 6937.43 140510.64; 15. Unit Reserve Shutdown Hours 0.00 0.00 0.00.' '16. Gross Thermal Energy Generated (MWH) 1031273 E 10626233.50 208888771.502
| 17. Gross Electrical Energy Generated 345081.00 3525264.00 69585632.0018. Net Electrical Energy Generated (MWH) 331007.00 3350523.00 66090806.00>
; 19. Unit Service Factor 100.00 86.29 79.3720. Unit Availability Factor 100.00 86.29 79.3721. Unit Capacity Factor (Using MDC Net) 91~.22 82.68 ___ 74.08
! 22. Unit Capacity Factor (Using DER Net) 89.44- 81.08 72.6323. Unit Forced Outage Rate 0.00 0'.19 5-22.
j-24. Shutdowns scheduled over next 6 months (Type, Date, and' Duration of-Each: N/A'
i? 25. If shut down at eIid of report period, estimated date of startup:N/A
26. Units In Test Status (prior to come.ercial operation) : N/A'
Forecast Achieved,
INITIAL CRITICALITYINITIAL ELECTRICITY-
I COMMERCIAL OPERATIONVTDPF 0411.01DP 0411 Rev. 4'
Page 1 of 1-RT No. 13.F01.19F
;
:I|
i
!,
I
. - , - . .-,-- -_
... .- .- .. .- . . - . . - .- .- -
|,
' AVERAGE DAILY UNIT POWER LEVEL'<
: t
! DOCKET NO. 50-271~
.
*; UNIT y_gImont Yankee*
j DATE 5 1210COMPLETED 3Y 1 A. WALLIN
; TELEPHONE 1102)257-7711:' MONTH Novemberj s
| DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL| (MWe-Net) (MWe-Net)
,
\.
j 1. 516 17, 517
: 2. 516 18. 517ii 3. 517 19. 519
| 4. 517 20. 517 '
it
i 5. 517 21, 517;
I 6. 517 22, 516
| 7. 518 23, 5161-; 8. 293 24, 517.
;
{ 9. 370 25. 517|-! 10. 175 26. 5171-
| 11, 177_. 27. 517-i
i 12. 183 28. 517!
! 13. __, 227 29. 517i! 14. _ 479 .3 0. 517i
. 15. 515 31. ---
16. 517
j INSTRUCTIONS:.
. .
: On this format, list the average daily unit power level in MWE-Netfor each day in the reporting month. -Compute to the-nearest whole
,
r megawatt.!
: VYDPF 0411.02| DP 0411 Rev. 4! Page 1 af 1"
RT No. 13.F01.18V
i
i
i
:
-
- . . - . . --- -- .. - - .
.. - . - ~. . . - . .- . . . - - _ .- . . _ . - . - - . - . - . . - . - . - = . - .. - - . - ~
UNIT SHUTDOWNS AND POWER REDUCTIONS .
'
REPORT MONTH NOVEMBER DOCKET NO 50-271 .
UNIT NAME Vermont Yankch*DATE 921210
COMPLETED BY G.A. WallinTELEPHONE (802)257-7711
!1 2 3
No. Date Type Duration Reason Method of License System Component Cause and Corrective(hours) Shutting Event Code Code Action to Prevent
Down Report # 4 5 RecurrenceReactor
92-08 921108 F 0.00 A 4 N/A CB ELECON "A" recirculation pumpPower trip due to MG set
Reduction excitation circuitrymalfunction
,
92-09 921109 F 0.00 A 4 N/A CB ELECON "A" recirculation pumpPower trip due to MG set
Reduction excitation circuitrymalfunction
1 F: Forced 2 Reason: 3 Method: 4 Exhibit G- InstructionsS: Scheduled A-Equipment Failure (Explain) 1 - Manual for Preparation of Data
B-Maintenance or Test 2 - Manual Scram Entry Sheets for LicenseC-Refueling 3 - Automatic Scram Event Report (LER) FileD-Regulatory Restriction 4 - Other (Explain) (h"JREG 0161)E-Opera *.or Training and-
License Examination 5 Exhibit I - Same SourceVYDPF 0411.03 F- Administrat.ive,
DP 0411 Rev. 4 G-Operational Error (Explain)Page 1 of 1 H-(Explain) - ,
i
,
. . .. . _ . - - -. . . . . _ - - - _ _ - _ _ _ _ _
,
i
|-
"DOCKET NO. 50-271
DATE 9_212103 ,
COMPLETED BY G.A. WALLIN4
TELEPHONE 1802)257-7711.
i REPORT MONTH November
i$ SUMMARY OF OPERATING EXPERIENCES
i Highlightg
|- Vermont Yankee operated at 89.9% of rated therms tower for the month..8% design electricalj Gross electrical generation was 345.081 MWHe r i
; capacity.i
| Ooeratina Summarv!
The following is a chronological description of plant operations including'
other pertinent items of interest for the month:
I the beginning of the reporting period the plant was operating at 99.8%at
; of rated thermal pcwer,iI 921108 At 0424 hours, the "A" recirculation pump tripped due to a MG set; excitation circuitry malfunction. (See Unit Shutdowns and Powerj. Reductions)| 921108 At 1233 houra, started the "A" recirculation-pump and began a1 return to full power.! 921109 At 1428 hours, the "A" recirculation Innnp tripped due to a MG set, excitation circuitry malfunction. (See Unit Shutdowns and Power .
! Reductions)[ 921113 At 1130 hours, started the "A" tecirculation pump and began a
return to full power.>
|-!
!
!
!6
ii
!!
!i.!
!
|
!
4
}
;- At-the end of the reporting period the plant was operating at 99.9% of--;- rated thermal power.1
-VYDPF 0411.04<
'
DP 0411 Rev. 4Page-1 of 1 j'
; -IEC No. 13.F01.18X, -
. - , , . , . ,_ _ , . . .,-