15. SAT 3C/D/F 15. SAT 3C/D/F Installation GuideInstallation Guide
WCC III
WattMaster Controls Inc.8500 NW River Park Drive · Parkville , MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.comVisit our web site at www.wcc-controls.comForm: WCCIII-SAT3CDF-INSTALL-TGD-01A Copyright 2012 WattMaster Controls, Inc. WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.This document is subject to change without notice.
TABLE OF CONTENTS
SECTION 15: SAT 3C/D/F INSTALLATION GUIDE
SAT 3C/D/F General Specifi cations................... 15-1
SAT 3C/D/F Benefi ts and Features .................... 15-2
Typical WCC III System Installation ................. 15-3
Globally Addressable Control Points ............... 15-5
SAT 3C Zone Summary Sheet........................... 15-6
SAT 3D Zone Summary Sheet........................... 15-7
SAT 3F Zone Summary Sheet .......................... 15-8
Dip Switch Settings and LEDs .......................... 15-9
SAT 3C/D/F Controller Installation
and Mounting .................................................. 15-10
SAT 3C Satellite Addressing........................... 15-12
SAT 3D/F Satellite Addressing ........................ 15-13
TUC Addressing .............................................. 15-14
RTU-17 Addressing ......................................... 15-15
SAT 3F Zone Addressing ................................ 15-16
Typical System Confi guration
with SAT 3C ..................................................... 15-17
Typical System Confi guration with SAT 3D ... 15-18
Typical System Confi guration with SAT 3F .... 15-19
System Components ....................................... 15-20
WCC III Technical Guide 15-1
15. SAT 3C/D/F INSTALLATION
SECTION 15: SAT 3C/D/F INSTALLATION GUIDE__________________________________________
SAT 3C/D/F Overview
SAT 3C/D/F General Specifications:
The SAT 3C/D/F controller is a drop-in replacement for the older SAT 2d or SAT 2c line of controllers that WattMasterControls Inc. manufactured from 1983 to 2006. The SAT 3C/D/F is an advanced product improvement over the older SAT 2c/dtype controller.The SAT 3C/D/F is a communication interface that converts/transfers data between the WCC III satellite based system and theWattMaster Controls series of standalone controllers that are referred to as TUC (Terminal Unit Controllers) or RTU (RoofTop Units.The SAT 3C provides the ability to communicate with up to 8 RTUs or TUC5Rs depending on the SAT 3C’s application softwarecode.The SAT 3D provides the ability to communicate with up to 32 TUC2Rs, VAVZ IIs, TUC5RXs or TUC5Rs depending on theSAT 3D’s application software code.The SAT 3F provides the ability to communicate with up to 16 TUC2Rs, VAVZ IIs, TUC5RXs or TUC5R depending on theSAT 3F’s application software code.
The SAT 3C/D/F features the following:Two RS-485 communication ports. The satellite communications port runs at 19.2K baud and is connected to other SAT 3 typedevices, while the TUC communication port runs at 9600 baud and connects between the SAT 3C/D/F interface and to theTUC or RTU type devices.
On the front cover of the SAT 3C/D/F controller, there are 8 LEDs for easier user troubleshooting diagnostics.There are two 8 position dipswitches that are also located on the cover of the SAT 3C/D/F controller. One dipswitch is asatellite address base switch, and the other is an option switch to select various different options on the SAT 3C/D/F controller.
The SAT III type interconnecting communications:It is a WattMaster Controls proprietary RS-485 based protocol, and it is based on packetized data in pre-defined parameterblocks. Troubleshooting of the SAT III RS-485 communication’s loop and the TUC RS-485 communication’s loop is possiblewith a Digital Volt Meter. (The older SAT II communications was based on Manchester encoded data, and was very reliable,but was hard to troubleshoot)
For the WCC III system. WattMaster Controls has developed a new isolated 485 communication bus that can support 239 SATIIIs on four separate communications channels (60 Satellite loads per channel) .A single channel can support up to 60 SAT III type loads on one communications loop. This is for redundant operation—if forsome unknown reason a WCC III communications channel loop goes down, it will not cause other SAT III type controllers onthe other loops to lose communications to the WCC III - MCD.
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommunications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
XCDF
TUC COMMUNICATIONS LOOP
RS-485 @ 9600 BAUD
SAT COMMUNICATIONS LOOP
RS-485 @ 19200 BAUD
OPTION 3OPTION 4
WCC III Technical Guide15-2
15. SAT 3C/D/F INSTALLATION
SAT 3C/D/F Benefits and Features
SAT 3C/D/F CONTROLLER VERSES SAT 2C/D CONTROLLER BENEFITS
THE SAT 3C/D/F CONTROLLER HAS A SMALLER MECHANICAL FOOT PRINT THAN THE OLD SAT 2C/D CONTROLLERTHE SAT 3C/D/F CONTROLLER USES THE SAME WIRING AS THE SAT 2C/D CONTROLLER
THE SAT 3C/D CONTROLLER USES THE SAME TUC AND RTU COMMUNICATION PROTOCOL AS THE SAT 2C/D CONTROLLER -SO IN THEORY, A TUC OR RTU CHANGE OUT IS NOT REQUIRED WHEN CHANGING A SAT 2C/D CONTROLLER TO A SAT 3C/DCONTROLLER. BUT MUCH BETTER CONTROL IS GENERALLY POSSIBLE WITH THE NEWER WCC III BASED TUC/RTU SOFTWARE.THE SAT 3C/D/F CONTROLLER USES THE SAME SATELLITE DATA FILES AS THE SAT 2C/D CONTROLLER
THE SAT 3C/D/F CONTROLLER PROGRAM UPDATES ARE AVAILABLE VIA A "FLASH" PROGRAMMING OR A DOWNLOADEDUPDATE. THE SAT 2C/D CONTROLLER SOFTWARE UPDATES HAD TO BE CHANGED OUT WITH A EPROM. THE SAT 3C/D/FCONTROLLER CAN BE CHANGED BY REMOTELY DOWNLOADING THE SOFTWARE OR BY "FLASHING" A NEW PROGRAMINTO THE SAT 3 D CONTROLLER'S MEMORY. A FLASHC/ /F PROGRAMMING TOOL IS AVAILABLE TO THE CONTRACTOR.BOTH USB AND PARALLEL PORT VERSIONS OF THE FLASH PROGRAMMING TOOL ARE AVAILABLE.
ADDED SAT 3C/D/F CONTROLLER FEATURESA TUC2R (WM part # 320) would have 2 control relays on board. (With two different types of optional expansion boards there could be eitherOE
A TUC5R (WM part # OE330-21) would have 5 control relays on board. (No expansion possible) (-21 is on metal back plate)A TUC5R+ (WM part # OE331-21)would have 5 control relays on board. (With a series of different types of expansion boards)
A TUC5RX (WM part # OE332-23) would have 5 control relays on board. (With a series of different types of expansion boards)
A VAVZ-II Box Controller (WM part # OE324-23) is an all in one plastic housing for VAV Zoning control that can be used with the optionalWM OE217 LCD display Temperature sensor. An optional I C Relay expansion board is available for this controller, but it is different
2
than the O 321 and OE322. (-23 is in plasticE enclosure)
The most common TUC2R application is what is called VAVBOX control, with a tri-state actuator used to modulate a damper for the temperatureZone. This VAVBOX software can be configured for pressure dependent operation or pressure independent operation with the addition of an optionalpressure sensor. An optional expansion board can be added for control of Series or Parallel Fan and stages of electric Box Heat. There is anotheroptional expansion board that can be added instead for control of series or parallel fan, stages of electric box heat, and an analog output for an analog
WM software version is 2.03. WattMaster WCC III VAVBOX. WM Software # 5010. Updated version of WCC II VAVBOX software thatSSVAVBOX Controllers. Current version is 3.04 and uses the TUC32K2 PAL for use in
The most common TUC5R+ application is what is called a WCC III Heat Pump / CV Air Handler.WattMaster WCC III Heat Pump / CV Air Handler with CO Sensor control. WM Software # SS5011. The current version is 1.02, and it is for a²
New to the WCC III is the VAVZ-II Box Controller. SAT 3D version is WM Software # SS5014, and the current software is version 3.10.When ordering a WattMaster controller, please specify the controller’s "OE" part number followed by the "SS" software part number.
WM part # OE321 is a 4 Relay expansion board for the TUC2R controller and is software dependent. ( 5001 only)SSWM part # OE322 is a 3 Relay and one analog output for HW valve control, is an expansion board for the TUC2R controller, and is software
There was "custom" TUC2R and TUC5R software that was written in 1980s and 1990s, and you would have to read the EPROM label of the boards
to get replacement controllers if needed. Call WattMaster for further details.
THE SAT 3C/D/F CONTROLLER HAS AN ADDITIONAL FOUR LEDS THAT DISPLAY THE STATUS OF THE RECEIVE AND TRANSMITFOR THE SAT LOOP RS-485 AND TUC LOOP RS-485 COMMUNICATIONS. IT DOES THIS FOR BOTH THE SAT III COMMUNICATIONSLOOP AND THE TUC PORT. IN ADDITION, THERE IS A SEPARATE LOCAL SET LED, AND THREE STATUS LEDS.THE SAT 2C/D CONTROLLER ONLY HAD AN LED THAT WAS A COMBINATION - POWER, COMMUNICATIONS, AND LOCAL SETINDICATOR FOR THE SATELLITE MANCHESTER COMMUNICATIONS LOOP.
SAT III - COMMUNICATIONSTHE SAT 3C/D/F CONTROLLER NOW USES RS-485 COMMUNICATIONS. THE SAT 2C/D CONTROLLER USED A TRANSFORMERCOUPLED MANCHESTER ENCODED PROTOCOL THAT WAS DIFFICULT TO TROUBLESHOOT. THE BEST BENEFIT OF HAVINGRS-485 COMMUNICATIONS IS THAT IT CAN BE TROUBLESHOT WITH A DIGITAL VOLTMETER.
SAT 3C/D/F CONTROLLER
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommunications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
D
WATTMASTER CONTROLSSATELLITE PART NUMBERS
OE421 SAT III CONTROLLER(SS5003)
OE454 SAT 3C CONTROLLER(SS5004)
OE455 SAT 3D CONTROLLER(SS5005)
OE456 SAT 3F CONTROLLER(SS5016)
3 or 4 more relays)
(-21 is on metal back plate)
Dependent. (SS5010 only)
TUC5R+ board.
was modified from the WattMaster Control’s other line ofolder versions of the TUC2R controller so that software upgrades are possible.
(-23 is a Plastic circuit board cover)
controlled actuator for hot water reheat. WattMaster WCC II VAVBOX WM Software #S 5001. Original WCC II VAVBOX - last released 1995. TheS
OPTION 3OPTION 4
WCC III Technical Guide 15-3
15. SAT 3C/D/F INSTALLATION
Typical WCC III System Installation
OE210
TYPICALSENSOR
(X8)
ON/OFF RELAYPUMPS, LIGHTS,ETC.
8
7SAT ADDRESS
21
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
4
3
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
8
7SAT ADDRESS
21
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
4
3
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommuncations Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLELOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
G5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
G5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
G5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
G5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
G5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
OE320TUC-2R
OE331TUC-5R+
W
A
R
M
E
R
C
O
O
L
E
R
OVR
OE213TYPICAL
SENSOR
OE421- SAT III
CONTROLLER
OE454 / O 455 / OE456E
SAT 3C/D/FCONTROLLER
W
A
R
M
E
R
C
O
O
L
E
R
OVR
OE213TYPICAL
SENSOR
WCC II TO WCC IIIGLOBAL BRIDGE
WCC III-MCD
SINGLE PULSEINPUT FROMPOWER METER
UP TO 32 TOTALFAN COIL, HEAT PUMPPD VAV TERMINAL UNITS
PI VAV TERMINAL UNITSPARALLEL FAN BOX, ETC.
VAV BOX
16 OUTPUTSPER SAT III
TO THE ISP
(INTERNET SERVICE PROVIDER)CONNECTION TO THE INTERNET
(BY OTHERS)
HIGH SPEED CABLE
MODEM / ROUTER
ETHERNETCABLE
Optional V-OUT Board
( 8 RELAY OUTS)
(2 PER SAT III)
Optional B-INPUT Board
( 8 BINARY INPUTS)
(2 PER SAT III)
HSS PORT HEAT PUMP
GND
24VAC
C
R/T SHLD
COMM T
COMM RDRIVER
485
EEPROM
VBAT
COMM
CHASSIS GND
POWER
SAT II STAT
SAT II
SAT III
PROGRAM SOCKET
YS102210 REV 1
GLOBAL BRIDGE
MADE IN USA
ADDRESS
24C128
PCF8583
LT1785
WATTMASTER CONTROLS INCCONNECTIONTO OLD WCC IIMANCHESTERCOMM LOOP
PULSE 1
PULSE 2
PULSE 3
PULSE 4
PULSE 5
PULSE 6
PULSE 7
PULSE 8
STAT REC
STAT XMIT
LOCAL SET
STATUS
COMM
ADD
12
4
8
16
3264
128
ADDRESS
SATIII-PPULSE METER BOARD
ATTMASTER CONTROLS
YS102268 REV0
MADE IN USA
P1
P2
P3
P4
P5
P6
P7
P8
GND
GND
POWER
SEL
TESTLOCALL DIS
OPT 1
OPT 2
OPT 3
SH
R
T
24 VAC
GND
OPTIONS
PULSE INPUTS
“P” MODE ADDRESSING NOTESSAT III ADDRESSING STARTSATADDRESS NUMBER 8.EACH "P" MODE SAT III TAKES UP(8) SAT III LOGICAL ADDRESSES.THERE ARE ONLY (8) USED ACTIVEINPUTS PER SAT 3P.ANALOG INPUT #1 (PULSE INPUT #1)ON EACH SAT III ADDRESS IS ACTIVE.ALL OTHER INPUTS AND OUTPUTS ONTHE SAT 3P ARE NOT FUNCTIONAL.
TOTAL WIRING FOR EACH INPUT NOTTO EXCEED 100 FEET.USE 18 GAUGE TWISTED PAIR WITHSHIELD FOR EACH PULSE METERCONNECTION.CONNECT THE SHIELD WIRE TO GND.
HSS PORT
MULTIPLE PULSEINPUTS FROM
POWER METERS
OE455-PSAT 3P
CONTROLLER
UP TO 60 TOTAL SAT III
OR SAT 3C/D/F/P PER LOOP.THERE ARE 4 POSSIBLESAT III RS485COMMUNICATIONS LOOPS
(UP TO 239 SAT III MAXIMUM)
B B
PL102224POWER ANDSWITCHABLE COMM
USUALLY ONEOR TWO PERFLOOR
MAXIMUM OF 2.5 MILES
(USES "ST" CONNECTORS)
BUILDING # 2
8
7SAT ADDRESS
21
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARYINPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
4
3
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
OE421- SAT III
CONTROLLER
8
7SAT ADDRESS
21
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARYINPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
4
3
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
OE421- SAT III
CONTROLLER
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommuncations Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 3
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
OE320TUC-2R
W
A
R
M
E
R
C
O
O
L
E
R
OVR
OE213TYPICALSPACE
SENSOR
OE455
SAT 3DCONTROLLER
VAV BOX
PL102335
RS-485 TO FIBEROPTIC ADAPTER
USED IN MULTIPLESOF TWO
PL102335RS-485 TO FIBEROPTIC ADAPTER
SAT COMM LOOP
SAT COMM LOOP
SAT COMM LOOP
UP TO 32 TOTALFAN COIL, HEAT PUMP
PD VAV TERMINAL UNITSPI VAV TERMINAL UNITSPARALLEL FAN BOX, ETC.
TUC COMM LOOP
Typical WCC III System Installation - Multiple buildings with fiber optics connecting the two buildings.
The WCC III - MCD is the data collection point for all of the WCC III information. It is also serves as the ethernet
connection point to the internet or building intranet. This WCC III - MCD must be on at all times for the WCC III system
to function.
The SAT III Controller is used for general purpose control and is provided with 8 analog inputs, 8 analog outputs, and
16 control outputs (each relay contact is rated 1.0 Amp @ 24 VAC). Up to two additional optional 8 input Binary Input
boards and three optional binary output boards (two in Binary Output Mode and One in V-Out mode - each relay contact
is rated 1.0 Amp @ 24 VAC) may also be connected to the SAT III Controller via an HSS connector that is located on
the side of the SAT III Controller. Electrically, this SAT III device only takes up "ONE" satellite load. There may be up
to 60 satellite loads per WCC3 satellite communications loop. An optional additional WCC3 M-COMM loop EXP
board is available that will provide an additional two WCC3 satellite communications loops if needed.
The SAT 3D controller is used to interface to terminal unit controllers (TUC type controllers), VAV boxes, heatpumps,
and even small Constant Volume AHU controllers. Each one of the SAT 3D controllers takes up 4 Satellite addresses
and then can communicate with up to 32 of these TUC type controllers. Only a limited amount of data points (4 Analogs
and 2 Binary) from the TUC type controllers can be addressable and then used within the WCC III system.
Electrically, this SAT 3D device only takes up "ONE" satellite load. There may be up to 60 satellite loads per WCC3
satellite communications loop. An optional additional WCC3 M-COMM loop EXP board is available that will provide
an additional two WCC3 satellite communications loops if needed.
The SAT 3F controller is used to interface to terminal unit controllers (TUC type controllers), VAV boxes, heat pumps,
and even small Constant Volume AHU controllers. Each one of the SAT 3F controllers takes up 4 Satellite addresses
and then can communicate with up to 16 of these TUC type controllers. The SAT 3F doubles the amount of data points
(8 Analogs and 8 Binary) from the TUC type controllers that can be addressable and then used within the WCC III
system. Electrically, this SAT 3F device only takes up "ONE" satellite load. There may be up to 60 satellite loads per
WCC3 satellite communications loop. An optional additional WCC3 M-COMM loop EXP board is available that will
provide an additional two WCC3 satellite communications loops if needed.
FIBER OPTIC LINES
OPTION 2
OPTION 4
OPTION 2OPTION 3OPTION 4
WCC III Technical Guide15-4
15. SAT 3C/D/F INSTALLATIONTypical WCC III Installation
The SAT 3C controller is used to interface to dedicated Roof Top controller units (RTU-17 type controllers) and other
more specialized controllers (GPC type devices). Each one of the SAT 3C controllers takes up 8 Satellite addresses and
then can communicate with up to 8 special dedicated controllers. Electrically, this SAT 3C device only takes up "ONE"
satellite load. There may be up to 60 satellite loads per WCC3 satellite communications loop. An optional additional
WCC3 M-COMM loop EXP board is available that will provide an additional two WCC3 satellite communications
loops if needed.
The SAT 3P controller is used to measure up to 8 dry contact closures from up to 8 pulse meters, such as a Emon-Dmon
KWH meters. (Please note: Each SAT III controller can also interface to a single dry contact closure from a single pulse
meter on A1 input.) This SAT 3P controller is a stripped down SAT III controller with only 8 pulse type inputs. Besides
logging abilities, there are not any other functioning satellite features in this SAT 3P controller. Each one of the SAT 3P
controllers takes up 8 Satellite addresses. Electrically, this SAT 3P device only takes up "ONE" satellite load. There may
be up to 60 satellite loads per WCC3 satellite communications loop. An optional additional WCC3 M-COMM loop
EXP board is available that will provide an additional two WCC3 satellite communications loops if needed.
The WCC II to WCC III global bridge is a device that allows for data from the "old" WCC II system to be shared with a
"new" WCC III system. It was designed as a temporary solution while the WCC II system was being changed over to a
WCC III system. Electrically, this WCC II to WCC III Global Bridge device only takes up "ONE" satellite load. There
may be up to 60 satellite loads per WCC3 satellite communications loop. An optional additional WCC3 M-COMM
loop EXP board is available that will provide an additional two WCC3 satellite communications loops if needed.
The high speed cable \DSL modem is used to connect the WCC III - MCD to the internet. Alternate connections to the
internet, or even the building intranet is possible, but they will require additional IT support at the contractor level.
Typical WCC III System Installation - Multiple buildings with fiber optics connecting the two buildings. Also
shown with the use of Power and Switchable comm boards.
OE210
TYPICALSPACE
SENSOR
(X8 MAX)
ON/OFF RELAYPUMPS, LIGHTS,
ETC.8
7SAT ADDRESS
21
4
8 WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
43
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
8
7SAT ADDRESS
21
4
8 WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
43
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES
"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommunications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
OE320
TUC-2R
OE331
TUC-5R+
W
AR
M
ER
CO
O
LE
R
OVR
OE213TYPICAL
SPACESENSOR
OE421- SAT IIICONTROLLER
OE454/O 455/OE456E
SAT 3C/D/FCONTROLLER
WA
R
ME
R
C
O
OL
E
R
OVR
OE213
TYPICALSPACE
SENSOR
WCC II TO WCC III
GLOBAL BRIDGE
WCC III-MCD
SINGLE PULSEINPUT FROM
POWER METER
UP TO 32 TOTAL
FAN COIL, HEAT PUMP
PD VAV TERMINAL UNITSPI VAV TERMINAL UNITS
PARALLEL FAN BOX, ETC.
VAV BOX
16 OUTPUTSPER SAT III
UP TO 60 TOTAL SAT III
OR SAT 3C/D/F/P PER LOOP.
THERE ARE 4 POSSIBLESAT III RS485
COMMUNICATIONS LOOPS
(UP TO 239 SAT III MAXIMUM)
TO THE ISP
(INTERNET SERVICE PROVIDER)
CONNECTION TO THE INTERNET
(BY OTHERS)
HIGH SPEED CABLE
MODEM / ROUTER
ETHERNETCABLE
Optional V-OUT Board
( 8 RELAY OUTS)
(2 PER SAT III)
Optional B-INPUT Board
( 8 BINARY INPUTS)
(2 PER SAT III)
HSS PORT HEAT PUMP
SAT II
SAT III
PROGRAM SOCKET
ADDRESS
24C128
PCF8583
LT1785
WATTMASTER CONTROLS INCCONNECTION
TO OLD WCC IIMANCHESTER
COMM LOOP
1
2
4
8
16
32
64
128
ADDRESS
SATIII-P
TEST
LOCAL
L DIS
OPT 1
OPT 2
OPT 3
R
T
24 VAC
GND
OPTIONS
PULSE INPUTS
“P” MODE ADDRESSING NOTESSAT III ADDRESSING STARTSATADDRESS NUMBER 8.EACH "P" MODE SAT III TAKES UP(8) SAT III LOGICAL ADDRESSES.THERE ARE ONLY (8) USED ACTIVEINPUTS PER SAT 3P.ANALOG INPUT #1 (PULSE INPUT #1)ON EACH SAT III ADDRESS IS ACTIVE.ALL OTHER INPUTS AND OUTPUTS ONTHE SAT 3P ARE NOT FUNCTIONAL.
TOTAL WIRING FOR EACH INPUT NOTTO EXCEED 100 FEET.USE 18 GAUGE TWISTED PAIR WITHSHIELD FOR EACH PULSE METERCONNECTION.CONNECT THE SHIELD WIRE TO GND.
HSS PORT
MULTIPLE PULSEINPUTS FROM
POWER METERS
OE455-P
SAT 3P
CONTROLLER
PL102224POWER AND
SWITCHABLE COMM
USUALLY ONEOR TWO PER
FLOOR
SAT COMM LOOP
SAT COMM LOOP
SAT COMM LOOP
TUC COMM LOOP
B B
PL102224POWER AND
SWITCHABLE COMM
USUALLY ONEOR TWO PER
FLOOR
FIBER OPTIC LINES
MAXIMUM OF 2.5 MILES
(USES "ST" CONNECTORS)
BUILDING # 2
8
7SAT ADDRESS
21
4
8 WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4L3L2L1
L6L5
L7
L11
L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
4
3
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
OE421- SAT III
CONTROLLER
8
7SAT ADDRESS
21
4
8 WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4L3L2L1
L6L5
L7
L11
L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
4
3
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
OE421- SAT III
CONTROLLER
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES
"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommunications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
OE320
TUC-2R
WA
R
ME
R
C
OO
L
ER
OVR
OE213TYPICAL
SPACESENSOR
OE455SAT 3D
CONTROLLERVAV BOX
PL102335
RS-485 TO FIBEROPTIC ADAPTER
USED IN MULTIPLES
OF TWO
PL102335RS-485 TO FIBER
OPTIC ADAPTERSAT COMM LOOP
SAT COMM LOOP
SAT COMM LOOP
UP TO 32 TOTAL
FAN COIL, HEAT PUMPPD VAV TERMINAL UNITS
PI VAV TERMINAL UNITSPARALLEL FAN BOX, ETC.
TUC COMM LOOP
OPTION 4OPTION 3
OPTION 4OPTION 3
WCC III Technical Guide 15-5
15. SAT 3C/D/F INSTALLATION
Globally Addressable Control Points
Globally Addressable Control PointsThe main differences between the different types of SAT 3C/D/F controllers primarily have to do with the amount of data from the various TUC/RTU type controllers that then can be globally addressed to a logical control point within the existing satellite data structure and then used within the WCC III system as a recognizable control point.
The SAT 3D controller can allow each TUC/VAVZ II controller to have up to 4 Analog logically addressable control point values and 2 Binary logically addressable control point values that can be globally used within the WCC III program. These address-able control points are “shoehorned” into the existing satellite data structure. As such, there can only be 32 TUC/VAVZ II type controllers connected via the TUC communications loop to the SAT 3D controller. Each one of the SAT 3D controllers takes up 4 physical satellite addresses.
The SAT 3F controller can allow each TUC/VAVZ II controller to have up to 8 Analog logically addressable control point values and 8 Binary logically addressable control point values that can be globally used within the WCC III program. These addressable control points are “shoehorned” into the existing satellite data structure. As such, there can only be 16 TUC/VAVZ II type control-lers connected via the TUC communications loop to the SAT 3F controller. Each one of the SAT 3F controllers takes up 4 physical satellite addresses.
The SAT 3C controller can allow each RTU/TUC controller to have up to 32 Analog logically addressable control point values and 48 Binary logically addressable control point values that can be globally used within the WCC III program. These addressable control points are “shoehorned” into the existing satellite data structure. As such, there can only be 8 RTU/TUC type controllers connected via the TUC communications loop to the SAT 3C controller. Each one of the SAT 3C controllers takes up 8 physical satellite addresses.
Typical Control point data from a single VAVZ II controller that is connected to a SAT 3F controller. (Please note: These points are application software specifi c.)
ANALOG VALUESXXXA1 - Room Temperature XXXA2 - Carbon Dioxide XXXP1 - Damper Position XXXP2 - Proportional Heat Signal XXXR1A - Heat/Cool Demand XXXR2A - Discharge TemperatureXXXR1B - Airfl ow CFM XXXR2B - Supply Air Temperature
BINARY VALUESXXXL1 - Override XXXL2 - Heating Mode XXXL9 - Generic Alarm XXXL10 - Cooling Mode XXXK1H - Not Used XXXK1C - Not Used XXXK2H - Not Used XXXK2C - Not Used XXXXO1 - Fan XXXXO2 - Heat Relay #1 XXXXO9 - Heat Relay # 2 XXXXO1O - Auxiliary HeatXXX = 1 to 239 and corresponds to the satellite address of 1 to 239.
Typical Control point data from a single TUC2R controller that is connected to a SAT 3D controller. (Please note: These points are application software specifi c.)
ANALOG VALUESXXXA1 - Room Temperature XXXP1 – Damper Position XXXR1A - Heat/Cool Demand XXXR1B - Airfl ow (CFM)
BINARY VALUESXXXL1 - Override XXXL9 - Generic Alarm XXX = 1 to 239 and corresponds to the satellite address of 1 to 239.
WCC III Technical Guide15-6
15. SAT 3C/D/F INSTALLATION
SAT 3C Zone Summary Sheet
WCC III Technical Guide 15-7
15. SAT 3C/D/F INSTALLATION
SAT 3D Zone Summary Sheet
WCC III Technical Guide15-8
15. SAT 3C/D/F INSTALLATION
SAT 3F Zone Summary Sheet
WCC III Technical Guide 15-9
15. SAT 3C/D/F INSTALLATION
Dip Switch Settings and LEDs
24VAC & GND (POWER CONNECTIONS)This SAT 3C/D/F controller’s power requirements are 24VAC and it draws 10 VA. Please note: You must observe polarity when connecting thepower connections to the SAT 3C/D/F controller or else damage to the SAT 3C/D/F controller could result.
.
R & T & SHIELD (SAT COMMUNICATIONS CONNECTIONS)
Communications loop can be “home run" to a power and switchable comm board - WM part # PL102224. The use of a shielded twisted pairwire is required, such as WM part # WR-NL-WR-18 or WR-LL-WG-18. When connecting the communication wiring from satellite controllersto other satellite controllers, you must wire "R" to "R" and "T" to "T", and "SHIELD" to SHIELD". The shield connection for all of the WCC IIItype RS-485 communications loops is required for all WCC III devices, SAT III, SAT 3C/D/F, SAT 3P, TUCs, RTUs, and VAVZ II controllers.
R & T & SHIELD (TUC COMMUNICATIONS CONNECTIONS)This RS-485 TUC communications loop can be daisy chained from one TUC/RTU type controller to the next TUC/RTU type controller or the TUCcommunications loop can be "home run" to a power and switchable comm board - WM part # PL102224. The use of a shielded twisted pair wireis required, such as WM part # WR-LL-WG-18 or WR-NL-WR-18. When connecting the TUC communication's loop wiring from the satellitecontrollers (SAT 3C/D/F) to the first TUC/RTU device, you must wire "R" to "T" and "T" to "R" and "SHLD" to "SHLD". But other TUC/RTU
WCC III type RS-485 communications loops is required for all WCC III devices, SAT III, SAT 3C/D/F, SAT 3P, TUCs, RTUs, and VAVZ II controllers.
SAT 3C/D/F ADDRESS DIPSWITCH
TOP DIPSWITCH
OPTION 2 switch is not used at this time.OPTION 1 switch is not used at this time.LOCAL SET DISABLE switch is used to disable the SAT 3C/D/F controller's LOCSET (LOCAL SET) mode.
TEST switch is used for testing purposes.
LEDsThere are eight LEDs on the front of the SAT 3C/D/F controller.
TUC REC- Every time a communications packet is received by the SAT 3C/D/F controller this LED will blink.
TUC XMIT - transmitted .Every time a communications packet is by the SAT 3C/D/F controller this LED will blink
LOCAL SET - The local set will turn on if the SAT 3 C/D/F controller stops communicating with the WCC III - MCD.
STATUS, "C" MODE and "D" MODE- See chart listed below:
Heart Beat : Blinks for every calculation loopSATIII Status3 LEDSAT3C LED "C"SAT3D LED "D"SAT3F LED "D"
Second Blink: Blinks for every secondSAT3 Status1 LEDSATC Status LEDSATD Status LEDSATF Status LED
Power On Delay: Blinks for every second during power on delaySAT3 Status2 LEDSAT3C LED "D"SAT3D LED "C"SAT3F LED "C"
Watchdog Enable: Blinks for every 8 seconds if watchdog is enabledSAT3 Status2 LEDSAT3C LED "D"SAT3D LED "C"SAT3D LED "C"
SAT XMIT- Every time a communications packet is transmitted by the SAT 3C/D/F controller, this LED will blink. This communications packet originatesat the SAT 3C/D/F controller.
SAT REC - Every time a communications packet is received by the SAT 3C/D/F controller, this LED will blink. This communications packet originates
LOCAL SET switch is used to enable the SAT 3C/D/F controller’s LOCSET mode and is used when the SAT 3C/D/F controller is still communicating
at the WCC III - MCD.
BAT ON/OFF switch does nothing. It was originally intended to blank out the memory on the satellite’s CPU RAM chip and was a carry-overfrom the old SAT 2 C/D controller.
Address to #20. Whenever setting this address dipswitch setting, you must cycle power up to the SAT 3C/D/F controller.switch #3 and switch #4 ON sets the SAT 3 D/F Controller’s to #12. Another example setting with switches #3 and #5 on, sets the SAT 3 D/F controller’sSets the SAT 3C/D/F controller’s address to #64. Switch #8 ON sets the SAT 3 C/D/F controller’s address to #128. These 8 switches are additive, so setting
This dipswitch sets the address setting for the SAT 3 C/D/F controller. The SAT 3 D/F controller has a valid address range is from 4 to 239 in incrementsof 4 starting at address #4. The SAT 3C controller has a valid address range from 8 to 239 in increments of 8 starting at address #8. The following explainshow to set the SAT 3C/D/F controller’s address: Switch #3 ON sets the SAT 3D/F controller’s address to #4. Switch #4 ON sets the SAT 3C/D/F controller’saddress to #8. Switch #5 ON, sets the SAT 3C/D/F controller’s address to #16. Switch #6 ON sets the SAT 3C/D/F controller’s address to #32. Switch #7 ON
type controllers on the TUC communications loop must be wired "R" to "R" and "T" to "T", and "SHIELD". The shield connection for all of the
The RS-485 satellite communications loop can be daisy chained from one satellite controller to the next satellite type controller or the satellite
OPTION 4 switch is not used at this time.OPTION 3 switch is not used at this time.
WCC III Technical Guide15-10
15. SAT 3C/D/F INSTALLATION
SAT 3C/D/F Installation and Mounting
WCC III Technical Guide 15-11
15. SAT 3C/D/F INSTALLATION
SAT 3C/D/F Installation and Mounting
WCC III Technical Guide15-12
15. SAT 3C/D/F INSTALLATION
SAT 3C Satellite Addressing
WCC III Technical Guide 15-13
15. SAT 3C/D/F INSTALLATION
SAT 3D/F Satellite Addressing
WCC III Technical Guide15-14
15. SAT 3C/D/F INSTALLATION
TUC Addressing
WCC III Technical Guide 15-15
15. SAT 3C/D/F INSTALLATION
RTU-17 Addressing
WCC III Technical Guide15-16
15. SAT 3C/D/F INSTALLATION
SAT 3F Zone Addressing
WCC III Technical Guide 15-17
15. SAT 3C/D/F INSTALLATION
Typical System Configuration with SAT 3C
8
7SAT ADDRESS
21
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SETFOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
43
56
21
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SETFOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FORA 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENTINPUT
THERMISTORINPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10VINPUT
0 TO 5VINPUT
0 TO 1VINPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
LOAD
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
TO THE REST OF SAT IIION SAT LOOP 1 TO 60
24VACLINE
VOLTAGE
24VACLINE
VOLTAGE
TO THE REST OF SAT III
ON SAT LOOP 61 TO 120
TO THE REST OF SAT IIION SAT LOOP 121 TO 180
TO THE REST OF SAT IIION SAT LOOP 181 TO 239
(MASTER COMMUNICATIONS DEVICE)
OPTIONAL EXPANSION
TO THE ISP
(INTERNET SERVICE PROVIDER)CONNECTION TO THE INTERNET
(BY OTHERS)
HIGH SPEED DSL / CABLE MODEM / ROUTER
ETHERNETCABLE
WCCIII - MCD - Rear View
120V LINEVOLTAGE
TYPICAL SYSTEM CONFIGURATION WITH SAT 3C
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommunications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
CONNECTIONFOR TUC LOOP
1 TO 8 UNITS
TO THE REST OF SAT IIION SAT LOOP 1 TO 60
24VAC INPUT FOR UPS LOSSOF POWER DETECTION
UP TO 4000 FT. OFCOMMUNICATIONSWIRE MAX PER LOOP.
PRINTER PORT - LASERPRINTER NOT SUPPORTED
ETHERNET
CABLE
C
OMRONG5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
G5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
OMRON
OMRONG5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
G5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
OMRON
OMRONG5LE-14P
24VDC
CONTACT:
UL / CSA 10A250VAC
OE330-21
OPTION 4OPTION 3
WCC III Technical Guide15-18
15. SAT 3C/D/F INSTALLATION
Typical System Configuration with SAT 3D
8
7SAT ADDRESS
21
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
43
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FORA 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENTINPUT
THERMISTORINPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10VINPUT
0 TO 5VINPUT
0 TO 1VINPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
LOAD
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
TO THE REST OF SAT IIION SAT LOOP 1 TO 60
24VACLINE
VOLTAGE
24VACLINE
VOLTAGE
TO THE REST OF SAT IIION SAT LOOP 61 TO 120
TO THE REST OF SAT IIION SAT LOOP 121 TO 180
TO THE REST OF SAT IIION SAT LOOP 181 TO 239
(MASTER COMMUNICATIONS DEVICE)
OPTIONAL EXPANSION
TO THE ISP
(INTERNET SERVICE PROVIDER)CONNECTION TO THE INTERNET
(BY OTHERS)
HIGH SPEED DSL / CABLE MODEM / ROUTER
ETHERNETCABLE
WCCIII - MCD - Rear View
120V LINEVOLTAGE
TYPICAL SYSTEM CONFIGURATION WITH SAT 3D
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommunications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
CONNECTIONFOR TUC LOOP1 TO 32 UNITS
TO THE REST OF SAT IIION SAT LOOP 1 TO 60
24VAC INPUT FOR UPS LOSSOF POWER DETECTION
UP TO 4000 FT. OFCOMMUNICATIONSWIRE MAX PER LOOP.
PRINTER PORT - LASERPRINTER NOT SUPPORTED
ETHERNETCABLE
G5L-114P-PS
24VDC
CONTACT:
UL / CSA 5A250VAC
G5L-114P-PS
24VDC
CONTACT:
UL / CSA 5A250VAC
OMRON
OMRON
G5L-114P-PS
24VDC
CONTACT:
UL / CSA 5A250VAC
OMRON
OMRONG5L-114P-PS
24VDC
CONTACT:
UL / CSA 5A250VAC
G5L-114P-PS
24VDC
CONTACT:
UL / CSA 5A250VAC
OMRON
W
A
R
M
E
R
C
O
O
L
E
R
OVR
OE271
(-)L
O
OUT
GND
IN
setra2631005WD4MZZCWM1
RANGE: 0-5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2801 3635
OE213
OE282
OE320
D
OE321
OPTION 4OPTION 3
WCC III Technical Guide 15-19
15. SAT 3C/D/F INSTALLATION
Typical System Configuration with SAT 3F
8
7SAT ADDRESS
21
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARYINPUTS
BINARYINPUTS
L8
ON OFF
128
3216
64
L4L3L2L1
L6L5
L7
L11L12
ON OFF
L10L9
ON OFF
L15L16
L14L13
CH
43
56
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SETLOCAL SET DISABLE
BATT ON/ OFFPULSE INPUT
OPTION 1
TEST
OPTION 3OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FORA 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENTINPUT
THERMISTORINPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10VINPUT
0 TO 5VINPUT
0 TO 1VINPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
21 3 4
21 3 4
5 6 7 8
5 6 7 8
V
OUT
GND
LOAD
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
TO THE REST OF SAT IIION SAT LOOP 1 TO 60
24VACLINE
VOLTAGE
24VACLINE
VOLTAGE
TO THE REST OF SAT IIION SAT LOOP 61 TO 120
TO THE REST OF SAT IIION SAT LOOP 121 TO 180
TO THE REST OF SAT IIION SAT LOOP 181 TO 239
(MASTER COMMUNICATIONS DEVICE)
OPTIONAL EXPANSION
TO THE ISP
(INTERNET SERVICE PROVIDER)CONNECTION TO THE INTERNET(BY OTHERS)
HIGH SPEED DSL / CABLE MODEM / ROUTER
ETHERNETCABLE
WCCIII - MCD - Rear View
120V LINEVOLTAGE
TYPICAL SYSTEM CONFIGURATION WITH SAT 3F
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICDCommunications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS1
STATUS
LOCAL SET
16
42
8
6432
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
CONNECTIONFOR TUC LOOP1 TO 16 UNITS
TO THE REST OF SAT IIION SAT LOOP 1 TO 60
24VAC INPUT FOR UPS LOSSOF POWER DETECTION
UP TO 4000 FT. OFCOMMUNICATIONSWIRE MAX PER LOOP.
PRINTER PORT - LASERPRINTER NOT SUPPORTED
ETHERNETCABLE
OE217
F
OE320-23
DisplayOverride
OVERRIDEALARM
STAT
THERM
4-20mA
0-10V
0-5V
COMM
OPTION 4OPTION 3
WCC III Technical Guide15-20
15. SAT 3C/D/F INSTALLATION
System Components
WCC III Technical Guide 15-21
15. SAT 3C/D/F INSTALLATION
Sensors
WCC III Technical Guide15-22
15. SAT 3C/D/F INSTALLATION
OE320-23, OE324-23, & OE310-21
WCC III Technical Guide 15-23
15. SAT 3C/D/F INSTALLATION
OE330-21 & OE331-21
WCC III Technical Guide15-24
15. SAT 3C/D/F INSTALLATION
OE256-01, OE325-01, & PL102224-21
WCC III Technical Guide 15-25
15. SAT 3C/D/F INSTALLATION
Notes
WCC III Technical Guide15-26
15. SAT 3C/D/F INSTALLATION
Notes
WCC III Technical Guide 15-27
15. SAT 3C/D/F INSTALLATION
Notes