an enhanced performance of distance relay algorithm to prevent (tesis)

Upload: danielalejandroramosquero

Post on 01-Mar-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    1/89

    AN ENHANCED PERFORMANCE OF DISTANCE RELAY ALGORITHM TO PREVENT

    UNDESIRABLE ZONE 3 OPERATION DURING LOAD ENCROACHMENT

    MR.SATHAPORN SITTIWONG

    A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS

    FOR THE DEGREE OF MASTER OF SCIENCE

    IN ELECTRICAL POWER ENGINEERING

    SIRINDHORN INTERNATIONAL THAI-GERMAN GRADUATE SCHOOL OF ENGINEERING

    (TGGS)

    GRADUATE COLLEGE

    KING MONGKUT'S UNIVERSITY OF TECHNOLOGY NORTH BANGKOK

    ACADEMIC YEAR 2007

    COPYRIGHT OF KING MONGKUT'S UNIVERSITY OF TECHNOLOGY NORTH BANGKOK

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    2/89

    ii

    Name : Mr.Sathaporn Sittiwong

    Thesis Title : An Enhanced Performance of Distance Relay Algorithm to

    Prevent Undesirable Zone 3 Operation During Load Encroachment

    Major Field : Electrical Power Engineering

    King Mongkuts University of Technology North Bangkok

    Thesis Advisor : Assistant Professor Dr.Teratam Bunyagul

    Academic Year : 2007

    Abstract

    Distance relays are used to detect and protect faults in transmission lines. The

    distance relay provide three zones of protection. Zone 3 is necessary as a backup for

    Zone 1 and Zone 2. However Zone 3 has a disadvantage that during a heavy load

    condition it may operates because the high load impedance moves into the zone. If

    Zone 3 misoperates, it causes disconnection to transmission line consequently the

    adjacent lines may be over rated because the change of power flows. This may lead to

    cascading outage and power system instability. The thesis propose the use of steady

    state signal and transient state signal to distinguish between faults and load

    encroachment into Zone 3. The models are built and simulated in PSCAD/EMTDC

    software. Then transient components are detected to distinguish from high load

    moving into Zone 3. The thesis propose the use of steady state signal and transient

    state signal to distinguish between faults and load encroachment into Zone 3. The

    models are built and simulated in PSCAD/EMTDC software.

    (Total 83 pages)

    Keywords : Distance Relay, PSCAD/EMTDC, Load Encroachment

    ______________________________________________________________ Advisor

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    3/89

    iii

    : :

    3

    :

    : . : 2550

    3 3 1 2 3 1 2 3 PSCAD/EMTDC

    (83)

    : , PSCAD/EMTDC,

    _____________________________________________

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    4/89

    iv

    ACKNOWLEDGEMENTS

    I would like to express my sincere gratitude for Assistant Professor Dr.Teratam

    Bunyagul, my advisor, for providing excellent guidance and introduce me to the area

    of power system protection including the subjects in this thesis. It is because of his

    constant assistance that this thesis has been successful. Under her guidance, I have

    learned much more than scientific knowledge.

    I would also like to thank my teachers, friends, the staff of the Electrical

    Engineering Department, Faculty of Engineering and the staff of Sirindhorn

    International Thai-German Graduate School of Engineering, King Mongkut's

    University of Technology North Bangkok for all their support

    Finally, I am extremely grateful to my family for always loving and supporting

    me. This thesis would have not been finished without their encouragement and

    inspiration throughout the duration of my study.

    Sathaporn Sittiwong

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    5/89

    v

    TABLE OF CONTENTS

    Page

    Abstract (in English) ii

    Abstract (in Thai) iii

    Acknowledgements iv

    List of Tables vii

    List of Figures viii

    Chapter 1 Introduction 1

    1.1 Distance relay in power systems 1

    1.2

    Basic Requirement of Protection Systems 1

    1.3

    Fundamental of Distance Protection Systems 2

    1.4 Protection Zones for Distance Relays 3

    1.5 Performance of Zone Protection 4

    1.6

    Zone Protection and Disturbance 4

    1.7 Problems of Distance Protection 8

    1.8 Purpose of The Study 8

    1.9

    Scope of The Study 8

    1.10 Methods 9

    1.11 Utilization of The Study 9

    1.12 The Structure of Thesis 9

    Chapter 2 Distance Relays and Zone Protection 11

    2.1 Fundamentals of Distance Relaying 11

    2.2

    Operation of Distance Relays 12

    2.3

    Zone Application of Distance Relaying 132.4 General Characteristics of Distance Relays 15

    2.5

    Application of Distance Relays 21

    2.6 Types of Disturbances 23

    2.7 Load Power Effect to Distance Relays 26

    2.8

    Load Encroachment 29

    Chapter 3 Literature Survey 31

    3.1 Previous Works on Disturbance for Zone 3 of Distance

    Protection 31

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    6/89

    vi

    TABLE OF CONTENTS (CONTINUED)

    Page

    Chapter 4 Algorithm and Signal Analysis 39

    4.1 Fundamental Considerations 39

    4.2 Digital Distance Measurement 39

    4.3 Fourier Analysis 41

    4.4 Fourier Analysis Based Algorithm 42

    4.5 Principle of Algorithm 43

    Chapter 5 Software Model in PSCAD/EMTDC 45

    5.1 Power System Parameters 45

    5.2 Protection System and Evaluation Setting Values 47

    Chapter 6 Simulation Results 53

    6.1 The Sequence of Simulation 53

    6.2 Three-Phase Fault Condition 54

    6.3 Line-to-Line Fault Condition 66

    6.4 Single Line-to-Ground Fault Condition 70

    Chapter 7 Simulation Results 77

    7.1 Conclusion 77

    7.2 Discrimination 78

    7.3 Speed 79

    References 81

    Biography 83

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    7/89

    vii

    LIST OF TABLES

    Table page

    5-1 Data of transmission lines and generator source 46

    6-1 Setting of threshold value 76

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    8/89

    viii

    LIST OF FIGURES

    Figure page

    1-1 Distance relays characteristic 3

    1-2 The three protection zones for the transmission line 3

    2-1 The distance relay connected to line and instrument transformers 12

    2-2 Principle of the distance relay 12

    2-3 Beam type distance relay 13

    2-4 Step time zones of distance relay protection 14

    2-5 Step time zones of distance relay protection 15

    2-6 Distance relay characteristics on R-X diagram 15

    2-7 Distance relay of mho characteristic type 16

    2-8 Increased arc resistance coverage 17

    2-9 Minimum load impedance permitted with lenticular, offset mho and

    impedance relays 18

    2-10 Quadrilateral characteristic 19

    2-11 Application of out-of-step tripping relay characteristic 20

    2-12 Distance relays on various lengths of adjacent line section 21

    2-13 Effect of infeed on impedance measured by distance relays 22

    2-14 The apparent impedance as the complex power vary and the power

    factor vary 27

    2-15 An apparent impedance as the active and the reactive power vary 29

    2-16 Load encroachment on mho distance element characteristics 30

    3-1 The impedance changes when a power swing with oscillation frequency

    equal to 0.1 Hz 31

    3-2 Power swing blocking characteristic 32

    3-3 Block diagram of the proposed fault detector 35

    4-1 Distance protection measuring principle PD = protection device,

    FR = fault resistance 40

    4-2 Operation of transmission system 43

    4-3 Fault 1 occur at 200 km both breaker 5 and 6 43

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    9/89

    ix

    LIST OF FIGURES(CONTINUED)

    Figure page

    4-4 Fault 2 occur at front of breaker 3 44

    5-1 The single line diagram of circuit typical 230 kV substation 45

    5-2 PI section model for a transmission line 46

    5-3 Distance relay zone protection 47

    5-4 Input signal are into Fast Fourier transform Block 48

    5-5 Input signal are into sequence component Block 48

    5-6 Calculation the line-to-line impedance block 49

    5-7 Calculation the line to ground impedance block 49

    5-8 Mho characteristics of distance relay 50

    5-9 Model of circuit typical 154kV substation 50

    6-1 Model when fault occur on power system 53

    6-2 Active power when fault between 2 s to 2.1 s 54

    6-1 Active power when fault at 5.4 s 55

    6-2 Change rates of active powerbetween 2 s to 2.1 s 55

    6-3 Change rates of active powerat 5.4 s 56

    6-6 Trajectory of impedance distance relay 1 56

    6-7 State of distance relay 1at fault(1) and fault(2) 57

    6-8 Trajectory of impedance distance relay 2 58

    6-9 State of distance relay 2 58

    6-10 Trajectory of impedance distance relay 3 59

    6-11 State of distance relay 3 606-12 Trajectory of impedance distance relay 4 60

    6-13 State of distance relay 4 61

    6-14 Active power when fault between 2 s to 2.1 s 61

    6-15 Active power when fault at 5.4 s 62

    6-16 Change rates of active power between 2 s to 2.1 s 62

    6-17 The power swing and fault(2) at 5.4 s 63

    6-18 State operation of distance relay when fault(1) and fault(2) 63

    6-19 The power swing and fault(2) at 5.4 s 64

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    10/89

    x

    LIST OF FIGURES(CONTINUED)

    Figure page

    6-20 The power swing of impedance and fault(2) at 5.4 s 65

    6-21 State of distance relay 3 65

    6-22 The power swing impedance and fault(2) at 5.4 s 66

    6-23 State of distance relay 4 66

    6-24 Active power when fault at 5.4 s 67

    6-25 Change rates of active power at 5.4 s 68

    6-26 The trajectory of impedance when fault(2) at 5.4 s 686-27 State of distance relay 1 69

    6-28 Active power when fault between 2 s to 2.1 s 69

    6-29 Change rates of active power at 5.4 s 70

    6-30 The power swing and fault(2) at 5.4 s 70

    6-31 State of distance relay 1 71

    6-32 Active power when fault at 5.4 s 71

    6-33 Change rates of active power at 5.4 s 72

    6-34 R-X diagram of distance relay 1 72

    6-35 State of distance relay 1 73

    6-36 Active power when fault between 2 s to 2.1 s 73

    6-37 Active power when fault at 5.4 s 74

    6-38 The power swing impedance and fault(2) at 5.4 s 75

    6-39 State of distance relay 1 75

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    11/89

    CHAPTER 1

    INTRODUCTION

    This chapter introduces fundamental operations of a distance relay and theories

    of transmission line protection. It also describes the purpose and the background of

    the research. The study focuses on discrimination of the distance relays, misoperation

    of distance relays and the effect of disturbance to distance relays.

    1.1 Distance Relay in Power Systems

    Distance relays are protective devices in electrical power system. They detect

    faults in transmission systems and isolate abnormal or fault conditions by sending trip

    signals to associated circuit breaker.

    In the event of an electrical fault, the normal balance between generation and

    load requirement is suddenly disturbed. Most of the energy previously supplied to the

    load is diverted into the fault path. In order to retain system stability and to limit the

    damage at the fault location, rapid isolation of the faulted section is necessary.

    1.2 Basic Requirement of Protection Systems

    Maintaining continuity of electrical supply to customers is a major work of the

    electricity generating authority. Protective relays are responsible for discriminating

    between normal and faulted conditions in the system. When fault happens, a local

    relay should have a high speed operation. The distance relay should detect the faultwithin 20 to 40 milliseconds [1]. Allowing the time of about 40 milliseconds for

    circuit-breaker to operate a total fault clearance time of 80 millisecond or less is

    desirable [1]. Measurement of distance from the current and voltage waveforms

    during the fault period may contain transient errors which affect the accuracy of the

    distance relay. We must be careful when considering the output requirement of the

    current and voltage transformers.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    12/89

    2

    Mal-operation of protective devices can give rise to widespread disturbance in

    the electricity supply system. This emphasizes the need for continued improvements

    in speed of operation, discrimination and reliability [1].

    1.3 Fundamental of Distance Protection Systems

    Distance protection systems are typically used for the protection of transmission

    lines. The protection is managed in overlapping zones. No part of the system is left

    unprotected. A comparison of local signals (voltage and current) enables the relay to

    decide which zone contains the fault [1]. In this way, a distance assessment is made

    from the relay location to the fault location.

    Distance relaying applies the principle of ratio comparison between the voltage

    and current which equates to the impedance. The relay, located at the beginning of a

    line calculates the apparent impedance of the line using the measurements of the

    current and voltage transformers at the same location as the relay. Impedance of

    transmission line increases with the length of the line.Each type of faults produces a

    different impedance value. Due to this reason the settings of a distance relay must be

    selected to distinguish the faults between the phase and the ground. Furthermore, a

    fault resistance may create a problem for distance measurement because the value of

    the fault resistance may affect apparent impedance. This causes inaccuracy of the

    apparent impedance calculation.

    The distance relay is capable of rapidly detecting faults on the transmission

    line. It operates when the impedance of the line is within the impedance characteristic

    of the distance relay (impedance plane circle).The provided operating characteristics

    of distance relay may have different shapes, depending on application and suitability.The characteristic consideration must be adapted to the changes of the loading

    levels, different values of fault resistance, effects of power swings, and reversals of

    fault direction. Most of the relay characteristics that we use are quadrilateral and mho.

    Quadrilateral relay is suitable for protecting ground fault. Mho relay is very effective

    with detecting phase fault. The different operating characteristic shapes are shown in

    Figure 1-1 [2].

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    13/89

    3

    FIGURE 1-1 Distance relays characteristic

    1.4 Protection Zones for Distance Relays

    Most of the transmission line protections are arranged into three protection

    zones. Each zone uses different protect sections. Figure 1-2 shows the arrangement of

    the three protection zones. These protection zones are used to define the relay reach

    and their operation times.

    FIGURE 1-2 The three protection zones for the transmission line

    Each protection zone is set to cover the pre-defined length of the transmission

    line. Typical selection of the zones in the transmission line protection is to cover 80 to

    90% of the line in Zone 1, 120150% in Zone 2, and 200250% in Zone 3 [1]. The

    relays operation times associated with each zones are different: in Zone 1 the relay

    operates instantaneously, Zone 2 is delayed to allow zone 1 relays to operate first, and

    Zone 3 times allows the corresponding relays closer to the fault to operate first in

    either the zone 1 or zone 2.

    This time-step approach for different protection zones allows the relays closest

    to the fault to operate first. If they fail to operate, the relays located at the remoteterminals that see the same fault as in Zone 2 will still disconnect the failed

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    14/89

    4

    component. If Zone 2 relay fails to operate, the relays located further away from the

    faulted line will operate next with the zone 3 settings.

    The advantage of this approach is a redundant coverage of each line section.

    They are also covered with multiple relay zones of the relay located on the adjacent

    lines, ensuring that the faulted component will be eventually removed even if the

    relay closest to the fault fails.

    1.5 Performance of Zone Protection

    When protective relays correctly tripped a faulted line, its current flow will be

    transferred to other lines which may become overloaded. These overloaded lines may

    trip Zone 3 backup relay, eventually leading to a widespread blackout.

    If the overloaded lines can be identified as the flow transferring from the faulted

    line and thus preventing the relays from tripping, cascading trips can be prevented and

    actions such as under-voltage load-shedding and manual load-shedding can be taken

    to save the system and avoid whole system blackout [2].

    Some expert systems are presented to prevent cascading trips but these expert

    systems emphasize only the optimal fault clearance and how to avoid incorrect

    operation of backup relay. They are not, however, intended to avoid the Zone 3

    distance relay trip caused by the aforementioned overloading of other lines.

    Zone 3 distance relay is used to provide remote backup protection in case the

    primary protection fails. Operation of the distance relay depends on the settings of the

    characteristics distance relays. If the relays only take local measurements (such as the

    voltage and current) as inputs without taking the impact of the whole network to make

    decisions to trip, the system will be deteriorated. In the worst scenario even resultingin cascading trips due to flow transferring overloadafter the clearance of a faulted line

    [2].

    1.6 Zone Protection and Disturbance

    Power utility networks are becoming larger and transmission lines are now

    operating closer to their limit than ever before. Power systems are subjected to a

    variety of small or large disturbances during its operating conditions. Changes in the

    regulations and the opening of the power markets result in rapid changes in the way

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    15/89

    5

    that the power grid is operated. As a result, power system are more vulnerable to

    disturbances which increases the possibility that an interconnected network may lose

    stability thereby leading to regional or even total blackout.

    The background of blackout, the power swing and the load encroachment will

    be briefly outlined in this section.

    1.6.1 The background of blackout

    The major blackouts in the United States of America, such as the two blackouts

    in 1996 in the Western region on 2ndJuly 1996 and again on 10thAugust, and 2003 in

    the Midwest and the Northeast on 14 th August, are the results of heavy load and a

    number of multiple outages that had occurred within a short period of time.

    For example, the Northeast Blackout on 9thNovember 1965 resulted in the loss

    of over 20,000 MW of load. The initiation of the disturbance was the faulty setting of

    a relay thus resulting in the tripping of one of the five heavily loaded 230-kV

    transmission lines. The flow of power on the disconnected line was thus shifted to the

    remaining four lines causing them to become overloaded and to trip successively in a

    total of 2.5 seconds. The cascading tripping of additional lines then began which

    resulted in the regional blackout.

    On 2ndJuly 1996 the West Coast Blackout resulted in the loss of 11,850 MW of

    load and affected 2 million people in the West. The outage began when a 345-kV

    transmission line in Idaho sagged into a tree and tripped out. A protective relay on a

    parallel line also detected the fault and incorrectly tripped a second line. Other relays

    tripped two of the four generating units at Jim Bridger plant. About 23 seconds later,

    the Mill Creek to Antelope 230-kV line was tripped by Zone 3 relay. Remedial action

    relays separated the system into five pre-engineered electric islands which collapsedeventually due to stability problems [2].

    On 10thAugust 1996 the second West Coast Blackout resulted in the loss of

    over 28,000 MW of load. Faults caused by treesput three 500-kV line sections out of

    service: (1) at 3:48 p.m., the Keeler-Allston 500-kV line had sagged into a tree and

    tripped, which caused the loss of 1300 MW of loading. The transmission line outages

    overloaded parallel lower-voltage lines in Portland area. (2) About 5 minutes later a

    relay failure tripped a 115-kV line and (3) at the same time a 230-kV line had sagged

    into a tree and also tripped. At about the same time generators at the McNairy

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    16/89

    6

    hydroelectric plants started tripping because of the faulty relays. Increasing

    oscillations soon caused synchronous instability and the ensuing cascading tripping of

    transmission lines broke the interconnection into four electric islands [2].

    On 14th August 2003, the latest blackout in the Midwest and the Northeast

    regions resulted in the loss of 70,000 MW of load. The blackout happened

    consecutively in different locations. At 1:31 p.m. the Eastlake 5 generation unit was

    tripped and at 2:02 p.m. the Stuart-Atlanta 345-kV line was tripped due to contact

    with a tree. From 3:05 to 3:57 p.m. a 345-kV line was tripped due to contact with

    trees. Later, from 3:39 to 4:08 p.m., a 138-kV line was tripped due to overloading.

    Then from 4:05 to 4:10 p.m. many lines which operated on Zone 3 impedance relays

    eventually led to cascading trips and blackout [2].

    These types of events most likely occur following sequential outages on a

    stressed system when the system is operated marginally in compliance with planning

    criteria. For example, some generators and/or lines for maintenance, line trips due to

    fault which overload other lines. If another disturbance occurs, for example, another

    line gets in contact with a tree and then trips, it will bring the system into a more

    serious state, which may result in a blackout [2].

    1.6.2 The power swing

    The power swing is the variation in three phase power flow which occurs when

    the system generator rotor angles are advancing or retarding relative to each other in

    response to changes in load magnitude such as line switching, loss of generation,

    faults, and other system disturbances. In most cases, the power swings are stable if the

    generators do not slip poles and the system reaches a new state of equilibrium.

    On the other hand, if a system is transiently unstable and the power swingresults in the generator experiencing pole-slipping which eventually leads to a loss of

    synchronism between groups of generators, it is called an out-of-step (OOS)

    condition.

    The power system should be maintained to survive larger types of disturbances

    such as faults, loss of a large generator, line switching and heavily loaded. Power

    system disturbances could cause loss of synchronism between a generator, low

    network voltages and consequent voltage or angular instabilities or severe loss of

    interconnected power systems of neighboring utilities. Depending on the severity of

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    17/89

    7

    the disturbance, the system may remain stable or return to a new stability state

    experiencing what is referred to as a stable power swing.

    Large power swings, make stable or unstable happen and unwanted relay

    operations at these events, which it can aggravate further the power system

    disturbance and possibly lead to cascading outages and power blackouts. When power

    swings happen the distance relay must not operate due to the reason that the apparent

    impedance (falls below)decreases withinthe relays operating characteristic.

    Operations of distance relays due to a power swing result in undesired tripping

    of transmission lines or other power system elements, thereby weakening the system

    and possibly leading to cascading outages and the shutdown of major portions of the

    power system.

    Therefore, distance relays should not trip during power system disturbance

    conditions from stable or unstable power swings because the power system may

    return to a stable operating condition after some time.

    Power swing has been proven to influence the distance relays. In some

    situations of power swing and out-of-step conditions, the distance relay cannot

    distinguish the power swing from the three-phase line fault.

    1.6.3 The load encroachment

    The load encroachment is a problem particularly in Zone 3 distance relay

    caused by increasing load. This Zone 3 is given a delay time longer than that

    associated with Zone 2 to achieve time coordination, and the time delay is typically in

    the range of 1-2 s.

    Because Zone 3 is set to detect faults down adjacent lines out of the remote

    station, in-feed at the remote station causes the relay to under-reach. Likewise, out-feed causes an over-reach effect.Additionally, distance relays may misoperate during

    events such as transient and voltage instabilities. This undesirable Zone 3 tripping has

    often contributed to cascading outages.

    According to a report from the latest 2003 blackout in the US, a lot of Zone 3

    distance relays operated under the overload and power swing situations, which further

    stressed the system thereby causing the cascading blackout in the end. Power swing,

    either stable or unstable, may have impacts on distance relays judgment. This kind of

    relay mal-operation may further weakened the system.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    18/89

    8

    1.7 Problems of Distance Protection

    Many problems affect the application of distance protection in a power system.

    These problems are outlined as follows :

    1.7.1 The transient of current and voltage signals at the occurrence of a fault.

    1.7.2

    The distance relay mal-operates during a power swing condition due to the

    reason that the apparent impedance in system may come inside the zone.

    1.7.3 Discrimination between a healthy load and a system fault condition which

    the distance relay must be able to identify these condition to prevent mal-operation.

    1.7.4 The fault resistance may create problems for distance measurements

    because the value of the fault resistance makes to distance relay produce error

    apparent impedance which may be difficult to forecast.

    1.7.5 The current in-feed from other transmission lines causes a voltage drop on

    the fault resistance. Affect to distance relays to measure incorrect apparent

    impedance. This may contribute to incorrect calculation of the apparent impedance.

    1.8 Purpose of The Study

    1.8.1

    To study PSCAD/EMTDC software especially for distance relay

    modeling.

    1.8.2 To study and simulate a distance relay model for Zone 3 protection.

    1.8.3

    To study the effect of power swing on zone protections.

    1.8.4 To identify faults occurring during power swings.

    1.9 Scope of The Study

    The Thesis studies the prevention methods of undesirable Zone 3 protectionoperation during load encroachment and power swing. The aims are to design an

    algorithm, model and simulate the transmission systems using PSCAD/EMTDC

    simulation software; and to design the algorithm using MATLAB software.

    The distance relay is designed to identify between a power swing and a fault

    conditions in order to prevent cascading trips under the power swing condition, which

    might result in a widespread blackout.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    19/89

    9

    1.10 Methods

    1.10.1 To study zone protection of transmission line and distance relay setting.

    1.10.2

    To learn the PSCAD/EMTDC simulation software.

    1.10.3 To study, model and simulate transmission systems using the

    PSCAD/EMTDC software.

    1.10.4 To designs an algorithm that distinguishes between a fault and a power

    swing.

    1.10.5

    To test the algorithm with PSCAD/EMTDC simulation.

    1.11

    Utilization of The Study

    1.11.1

    The algorithm can be used to detect and distinguish a fault occurrence

    during a power swing.

    1.11.2 To prevent the maloperation of distance relay due to power swing.

    1.12 The Structure of Thesis

    The research presents the study of the discrimination of distance relays

    protection at fault occurrence during a power swing. The distance relay is modeled

    and simulated using PSCAD/EMTDC and MATLAB softwares. (The simulation

    results of the distance relay operating sequence and time are analysed.) The model of

    distance relays is confirmed by simulation results of the operating sequence and

    operating time.

    The methodology, data and analysis of the research is divided into six chapters :

    Chapter 2: The basics of the distance relay protection.

    Chapter 3: Literature survey.Chapter 4: The basic algorithm of the mathematic used for the research.

    Chapter 5: The transmission line and the distance relays parameters are

    evaluated and modeled using PSCAD/EMTDC.

    Chapter 6: The simulation results of PSCAD/EMTDC.

    Chapter 7: The conclusion of the research and recommendation for future work.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    20/89

    CHAPTER 2

    DISTANCE RELAYS AND ZONE PROTECTION

    This chapter discusses fundamental, operation, zone application, characteristics

    and the load power effect of the distance relays as well as the disturbance in power

    system and the load encroachment. The causes of the problems in distance relay and

    the disturbances which affect the zone operation of the relay are also presented.

    2.1 Fundamentals of Distance Relaying

    Distance relay detects the fault impedance obtained from the measured ratio of

    voltage to current faults. The apparent impedance is measured between the relay

    location and the point of fault occurrence. If the measured fault impedance is smaller

    than the impedance set for the distance relay to indicate an internal fault happen, then

    send a trip signal to the circuit breaker. At the fault occurrence on a transmission line

    the impedance will move into zone protection impedance because the fault impedance

    is smaller than the load impedance.

    The distance protection scheme is normally a multi-zone arrangement in which

    the first zone of protection provides instantaneous tripping and the next zones

    incorporate time delayed tripping. Three protective zones are usually included, giving

    the stepped time-distance characteristic. The aim of the scheme is to provide correct

    high speed tripping of circuit-breakers, with adequate discrimination provided

    between internal and external faults [1].

    This kind of relay is known as a distance relay and is designed to operate only

    for faults that occur between the relay location and the selected reach point thus

    giving discrimination for faults that may occur in different line sections [3].

    The reach point of a relay is the point along the line impedance locus that is

    intersected by the boundary characteristic of the relay. Since this is dependent on the

    ratio of the voltage to current and the phase angle between them, it may be plotted on

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    21/89

    12

    an R/X diagram. The locus of power system impedances as seen by the relay during

    faults, power swings and load variations may also be plotted on the same diagram [3].

    2.2 Operation of Distance Relays

    The distance relay is connected with a power line through instrument

    transformers, as shown in Figure 2-1. Assuming that the fault occurs on the line at a

    distance of 1LnZ W from the relay, the voltage RV on the relay will be the R LI nZ

    drop from the distance relay to the fault since the voltage at the fault is 0 V [4].

    FIGURE 2-1 The distance relay connected to line and instrument transformers

    Therefore, the impedance of the distance relay is :

    R R 1LR 1L

    R R

    V I nZZ nZ

    I I= = = Eq. 2-1

    FIGURE 2-2 Principle of the distance relay

    In Figure 2-2, When a fault occurs between the distance relay and LZ , the

    impedance from the relay is ( )L LZ Z- D W . The restraint force will then be

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    22/89

    13

    ( )R L LI Z Z- D and it will be less than the operating force for the same current

    magnitude. As a result, the beam will incline down at the current end, closing the

    contacts. If the fault is beyond LZ distance, say at ( )L LZ Z+ D W from the relay, then

    the restraint force RV will be greater than the operating force RI . The beam will then

    incline down at the voltage end, and the contacts will not close [4].

    In Figure 2-3 the voltage provides a magnetic force or pull on one end of the

    beam. If, for this fault, the current or the operating force RI on the other end of the

    beam is adjusted to be equal to the voltage or the restraint force RV , the beam will be

    balanced.

    FIGURE 2-3 Beam type distance relay

    2.3 Zone Application of Distance Relaying

    Throughout all transmission lines there will be three protection zones which are

    used to protect a line section and to provide backup for the remote section. The

    common practice has been to use separate distance units for the several protection

    zones. This is in contrast with distance relays that use a single distance-measuring unit

    initially set for Zone 1 reach. If the fault persists, the reach is extended by switching

    to Zone 2 after T2time delay, then after T3to Zone 3.

    Separate units provide the comfort of redundancy because for faults in the Zone

    1 primary reach area, all three distance units will operate. Thus, Zones 2 and 3 are

    used back up in case Zone 1 unit fails.

    These zones and typical settings are illustrated in Figure 2-4 which shows the

    zones at several locations. Each of the three zones uses instantaneous operating

    distance relays. Zone 1 is set for 80 to 90% of the line impedance. The resulting 10-

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    23/89

    14

    20% safety margin ensures that there is no risk in the Zone 1 protection over-reaching

    the protected line due to errors in the current and voltage transformers, inaccuracies in

    line impedance data provided for setting purposes and errors of relay setting and

    measurement.

    FIGURE 2-4 Step time zones of distance relay protection

    Zone 2 is adjusted for 100% of the line, plus approximately 50% of the shortest

    adjacent line off the remote bus which operates through a timer T2. Zone 3 is set for

    100% of both lines, plus approximately 25% of the adjacent line off the remote bus.

    Wherever possible, Zones 2 and 3 provide backups for all the adjacent lines at

    operating times of T2and T3[2]. These original settings define the protection zones

    only if there are no infeed effects.

    Figure 2-5 shows the operating circles for the three zone at bus G, breaker 1

    (solid line) and at bus H, breaker 2 (broken line) plotted on the RX diagram. Therelays operate when the ratio of fault voltage to current falls within the circles.

    Load can be represented on these R-X diagrams as an impedance phasor,

    generally lying near the R axis (depending on the power factor of the load current on

    the line). The phasor lies to the right (first quadrant of the R-X diagram) when

    flowing into the protected line from the bus and to the left (third quadrant of the R-X

    diagram) when flowing out of the line to the bus. The operating circles must be set

    such that they do not operate on any system swings from which the system can

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    24/89

    15

    recover. Such swings occur after a system disturbance, such as faults, sudden loss of

    generation or load, or from switching operations.

    R

    X

    Load areafrom H to G

    Load areafrom G to H

    G

    H

    R

    FIGURE 2-5 Step time zones of distance relay protection

    2.4 General Characteristics of Distance Relays

    The distance relay characteristics plotted on the R-X diagram are shown in

    Figure 2-5. The operating zones are defined such that the apparent impedance falls

    inside the circles for the relay characteristics labeled a, b, and c. In another words,

    whenever the ratio of V/I falls inside the circle, the distance unit operates [4].

    FIGURE 2-6 Distance relay characteristics on R-X diagram

    Figure 2-6a has the non-directional impedance characteristic. When it is used for

    fault protection, a separate directional unit is added to limit the tripping to line faults

    [13]. The mho characteristic of Figure 2-6c is a circumference that passes through theorigin.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    25/89

    16

    In the event that high values of earth fault resistances are expected, the

    reactance protection scheme of Figure 2-6b may be used. In this scheme, it is

    important to ensure that the reach setting of the fault detector dose not result in

    operation during maximum circuit loading condition [1].

    2.4.1

    Mho characteristics

    The mho characteristic in distance protection scheme, as shown in Figure 2-6c,

    is widely used for Zones 1 and 2, with Zone 3 providing back-up protection for fault

    immediately at the relay [1].

    FIGURE 2-7 Distance relay of mho characteristic type

    Figure 2-7 shows the impedance element that will operate only for faults in the

    forward direction along line AB. Advantages are fixed reach as a function of the

    protected line impedance and so independence of system operating and fault levels

    over a very wide range [2].

    2.4.2 Effect of fault resistance with mho relay

    The impedance reach varies with the fault angle. The fault angle will bedependent upon the relative values of R and X at the system operating frequency.

    Under an arcing fault condition, or an earth fault involving additional resistance, such

    as tower footing resistance or fault through vegetation, the value of the resistive

    component of fault impedance will increase. This increase results in a change to the

    impedance angle. Thus relay having a characteristic angle equivalent to the line angle

    will under-reach under resistive fault conditions [3].

    In Figure 2-8 the relay characteristics angle (RCA) is set at less than the line

    angle so that it is possible to accept a small amount of fault resistance without causing

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    26/89

    17

    under-reach. When the line AB corresponds to the length of the line to be protected.

    With set to be less than , the actual amount of line protected, AB, would be equal

    to the relay setting value AQ multiplied by cosine (q-j). Therefore the required relay

    setting AQ is given by

    ( )AB

    AQcos

    =q - j

    Eq. 2-2

    FIGURE 2-8 Increased arc resistance coverage

    When the earth resistance happen, it should be realized that this does not need to

    be considered with regard to the relay settings other than the effect that reduced fault

    current may have on the value of arc resistance seen. The earthing resistance is in the

    source behind the relay and only modifies the source angle and source to line

    impedance ratio for earth faults. It should therefore be taken into account only when

    assessing relay performance in terms of system impedance ratio.

    2.4.3 Application of lenticular characteristic

    Figure 2-9 shows the risk that the offset mho relay may operate under

    maximum load transfer conditions if Zone 3 of the relay has a large reach setting. A

    large Zone 3 reach may be required to provide remote back-up protection for faults on

    the adjacent feeder [3].

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    27/89

    18

    ZD3

    R

    X

    Offset Lenticular

    Characteristic

    LOAD

    AREA

    ZD2ZD1

    a

    b

    0

    Offset Mho

    Characteristic

    Impedance

    Characteristic

    FIGURE 2-9 Minimum load impedance permitted with lenticular, offset mho

    and impedance relays

    To avoid maximum load, a shaped type of characteristic may be used, where the

    resistive coverage is restricted. With a lenticular characteristic, the aspect ratio of the

    lens ( )a b is adjustable, enabling it to be set to provide the maximum fault resistancecoverage consistent with non-operation under maximum load transfer conditions.

    Figure 2-9 shows how the lenticular characteristic can tolerate much higher

    degrees of line loading than offset mho and plain impedance characteristics [3].

    Reduction in load impedance from D3Z to D1Z corresponds to an equivalent increase

    in load current.

    2.4.4 Quadrilateral characteristic

    The quadrilateral impedance characteristic is shown in Figure 2-10. The

    characteristic is provided with forward reach and resistive reach settings that are

    independently adjustable. It therefore provides better resistive coverage than any

    mho-type characteristic for short lines. This is especially true for earth fault

    impedance measurement where the arc resistances and fault resistance to earth

    contribute to the highest values of fault resistance.

    To avoid excessive errors in the zone reach accuracy, it is common to impose a

    maximum resistive reach in terms of the zone impedance reach. Recommendations in

    this respect can usually be found in the appropriate relay manuals [3].

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    28/89

    19

    FIGURE 2-10 Quadrilateral characteristic

    Quadrilateral elements with plain reactance reach lines can introduce reach error

    problems for resistive earth faults where the angle of total fault current differs from

    the angle of the current measured by the relay. This will be the case where the local

    and remote source voltage vectors are phase shifted with respect to each other due to

    pre-fault power flow. This phase difference can be overcome by using a phase current

    for polarization of the reactance reach line. Polygonal impedance characteristics are

    highly flexible in terms of fault impedance coverage for both phase and earth faults.

    2.4.5 Protection against Power Swings-use of the ohm characteristic.

    During severe power swing conditions in which a system is unlikely to recover,

    the system might return to stability if the swinging sources are separated. Where such

    scenarios are identified, power swing or out-of-step tripping protections can be

    deployed to strategically split a power system at a preferred location. Ideally, the split

    should be made so that the plant capacity and the connected loads on either side of the

    split are matched.

    Normally this type of disturbance cannot be correctly identified by an ordinary

    distance protection. As previously mentioned, it is often necessary to prevent distance

    protection schemes from operating during stable or unstable power swings in order to

    avoid cascade tripping.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    29/89

    20

    To initiate system separation for a prospective unstable power swing, an out of

    step tripping scheme employing ohm impedance measuring elements can be

    deployed.

    FIGURE 2-11 Application of out-of-step tripping relay characteristic

    Ohm impedance characteristics are applied along the forward and reverse

    resistance axes of the R/X diagram and their operating boundaries are set to be

    parallel to the protected line impedance vector, as shown in Figure 2-11.

    As the impedance changes during a power swing, the point representing the

    impedance moves along the swing locus, entering the three zones in turn and causing

    the ohm units to operate in sequence.

    When the impedance enters the third zone the trip sequence is completed and

    the circuit breaker trip coil can be energized at a favorable angle between system

    sources for arc interruption with little risk of restriking.

    Only an unstable power swing condition can cause the impedance vector to

    move successively through the three zones. Therefore, other types of system

    disturbance such as power system fault conditions will not result in relay element

    operation.

    Discrimination of the protection zones can be achieved using distance relays

    provided that fault distance is a simple function of impedance. While this is true in

    principle for transmission circuits, the impedances actually measured by a distance

    relay also depend on the following factors:

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    30/89

    21

    2.4.5.1 The magnitudes of current and voltage (the relay may not see all

    the current that produces the fault voltage).

    2.4.5.2

    The fault impedance loop being measured.

    2.4.5.3 The type of fault.

    2.4.5.4

    The fault resistance.

    2.4.5.5 The symmetry of line impedance.

    2.4.5.6 The circuit configuration (single, double or multi-terminal

    circuit).

    2.5

    Application of Distance Relays

    2.5.1

    Distance relays with various lengths.

    When several remote lines have different lengths as shown in Figure 2-12 the

    settings of Zones 2 and 3 are compromised. Since line HV is short compared to lines

    HS and HR, setting Zone 2 at G for 50% of line HV provides a maximum of 5.5%

    coverage for line HR and 8.4% for line HS. This coverage is further reduced by the

    infeed effect.

    FIGURE 2- 12 Distance relays on various lengths of adjacent line section

    Additional coverage could be obtained by increasing the G Zone 2 setting and

    the corresponding T2 setting to coordinate with the T2 times on lines HV, VW, and

    WX. The result would be long end-zone clearing for line G. If pilot relaying is used

    for primary protection, increased backup with longer T2 times could be employed.

    Setting Zone 3 to cover line HR would provide coverage through severalsections HV, VW, WX, and XY requiring a longer T3 setting. Again, the infeed effect

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    31/89

    22

    from lines HS and HV probably would not provide T3 coverage for line HR. This fact

    re-emphasizes the need for local backup in modern power systems.

    2.5.2

    The infeed effect on distance relay

    On interconnected power systems, the effect of fault current infeed at the remote

    busbars will cause the impedance presented to the relay to be much greater than the

    actual impedance to the fault. This effect needs tobe taken into account when setting

    Zone 3. In some systems, variations in the remote busbar infeed can prevent the

    application of remote back-up Zone 3 protection but on radial distribution systems

    with single end infeed, no difficulties should arise [3].

    Undesired operation of Zone 3 distance relays applied for remote backup

    protection during major system disturbances has caused the magnitude of the scope of

    such disturbances to be expanded. Large ohmic settings are typically applied to the

    Zone 3 relaying in order to obtain the desired backup protection. Power swings and

    low voltage conditions that often exist during system disturbances resulted in the

    impedance seen by the Zone 3 relay to be within its operating characteristic for a

    sufficient length of time for it to initiate a trip command. Such experiences have

    resulted in utilities restricting the use or reach applied to Zone 3 relaying [2].

    FIGURE 2-13 Effect of infeed on impedance measured by distance relays

    When there is a source of fault current within the operating zone of the distance

    relay, its reach will be reduced and variable. This infeed effect can be seen from

    Figure 2-13 where there are other lines and sources feeding current to a fault at F from

    bus H. The relays at bus G are set beyond this fault point to F . With a solid 0-V fault

    at F, the voltage for the relay at G is the drop along the lines from the fault to the

    relay, or

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    32/89

    23

    ( )G G L G H HV I Z I I Z= + + Eq. 2-3

    Since relay G receives only current IG, the impedance appears to be

    GG apparent

    G

    HL H H

    G

    HL

    VZ

    I

    IZ Z Z

    I

    ZZ

    K

    =

    = + +

    = +

    Eq. 2-4

    and

    ( )G

    G H

    IKI I= +

    Eq. 2-5

    Where K is the current distribution factor (phasor). This apparent impedance are

    compared to the actual impedance to fault F of [4].

    Gapparent L HZ Z Z= + Eq. 2-6

    If HI is 0 (no infeed), Z apparent equals to Z actual. As the infeed increases in

    proportion to GI , Z apparent increases by the factor( )H G HI I Z . Since this impedance,

    as measured by the distance relay, is larger than the actual impedance, the reach of the

    relay decreases. That is, the relay protects less of the line as infeed increases.

    Since the reach can never be less than LZ as shown in Figure 2-13, Zones 2 and

    3 provide protection for the line. However, remote backup for the adjacent line may

    be limited since infeed is very common and can be quite large in modern power

    systems [4].

    Note that the infeed effect varies with system configurations and that the

    apparent impedance may be a maximum under either maximum or minimum system

    conditions [4].

    2.6

    Types of Disturbances

    The disturbances happen when the power systems are heavy loaded and a

    number of multiple outages occur within a short period of time, causing power

    oscillations between near utility systems, low voltages of network, and consequent

    voltage instability or angular instability.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    33/89

    24

    All of these disturbancescause loss of generation and loads. Power system faults

    such as line switching, generator disconnection, and the loss of load result in sudden

    changes of electrical power. These system disturbances affect the oscillations in

    machine rotor angles and can result in severe power flow swings.

    Distance relay for transmission line protection is designed to isolate the faults

    that occurred within the desired zone only. It is not supposed to trip the line during a

    power swing caused by the disturbances outside the protected line. Even for the out-

    of-step conditions, the preferred operation is to separate the system with an out-of-

    step tripping (OST) protection at pre-selected network locations and blocking other

    distance relays by out-of-step blocking (OSB) protection.

    2.6.1

    Power swing

    This situation is a variation in three phase power flow which occurs when the

    generator rotor angles are advancing or retarding relative to each other in response to

    changes in load magnitude and direction, line switching, loss of generation, faults, and

    other system disturbances.

    Operation of distance relays during a power swing may cause undesired tripping

    of transmission lines, thereby weakening the system and possibly leading to cascading

    outage and the shutdown of major portions. Distance or other relays should not trip

    during abnormal system conditions such as stable or unstable power swings (OOS),

    and sometime after stable power swing may be the power system to return to a stable

    operating condition.

    Distance relay elements possible to operate during stable or transient power

    swings should be restrain from operating to prevent system separation from this event.

    Power Swing Block (PSB) function is available to prevent unwanted distancerelay element from operating during power swings. The main purpose of the PSB

    function is to identify the faults and power swings and to block distance or other relay

    elements from operating during a power swing. Faults that occur during a power

    swing must be detected and cleared with a high degree of selectivity and

    dependability.

    The effect of system disturbances results from large separation of generator

    rotor angles, large swings of power flows, large swing of voltages and currents, and

    last mean loss of synchronism between groups of generators or between neighbouring

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    34/89

    25

    utility systems. Large power swings, stable or unstable, can cause unwanted relay

    operations which can aggravate further the power-system disturbance and possibly

    lead to cascading outages and power blackouts.

    The power swing block and out of step will use the difference in the rate of

    change of the positive-sequence impedance to detect a power swing or an out of step

    condition and then send a to block (or not to block) signal before the apparent

    impedance move into the protective relay operating characteristics.

    Power swing detectors prevent distance relays from mal-operation under power

    swing and out-of-step conditions. In another words, the rate of change of the

    impedance will be observed from a trajectory slow during power swings.

    It takes a finite time for the generator rotors to change position with respect to

    each other because of their large inertias. On the contrary, the rate of change of the

    impedance phasor is very fast during a system fault.

    In theory, the impedance rate of change is normally measured using two

    impedance measurement elements together with a timing device. If the measured

    impedance stays between the settings of the two impedance measurement elements

    for a predetermined time, the relay sees and decision be a power swing condition and

    thus issues a blocking signal to block the distance relay element operation. After a

    predetermined time the relay will trip if the power swing element is not reset.

    It is not recommended to apply power swing blocking for unstable power

    swings without some form of OST being applied at some predetermined location.

    2.6.2 Out-of-Step Detection

    Out-of-step or unstable power swing are conditions that result from system

    instability such as short-circuits fault, line switching and generator tripping [5]. Whensystem instability occurs in a power system they may lead to outage in the

    transmission system and also create stress on the electrical equipment.

    At a damped oscillation the generators will be able to return to a normal state

    condition which is known as stable power swing. In some cases the swing is so large

    that the generators lose synchronism and run out of step. This power swing and out of

    step situations cause the current and the voltage of the power system network not to

    be constant and affect also the swing in amplitude and phase.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    35/89

    26

    An impedance calculation error based on voltages and currents will also

    oscillate in amplitude and phase with the power swing frequency. Every time a power

    swing or out of step happen the apparent impedance can become small such that it

    will enter the zone detect fault of operation distance relay or as well the instantaneous

    zone of a distance relay and lead to a mal-operation of the distance relay element.

    A trip due to out of step and power swing situation can be desirable on

    transmission lines to separate the unstable interconnect. An additional logic in the

    protection relay should distinguish between a stable power swing where the system

    get back to stable system and an unstable out of step situation particularly issued only

    for the out of step situation, must be sent logic trip to circuit breaker tripping in

    system [6].

    The main operation of Out-of-Step Trip (OST) is provided in distance relays to

    detect a power swing and block the operation of a distance relay due to the power

    swing. To maintain power system stability and service continuity the most common

    method used to detect a power swing is to measure the rate of change of impedance as

    it travels into the protection zones of the relay.

    2.7 Load Power Effect to Distance Relays

    The load which is serviced by the transmission line and affect to the distance

    relay as impedance. When the load increases will affect to the impedance in distance

    relay measurement to decreases also. In some situations the load is large enough that

    it overlaps the relay characteristic. This is referred to generally as load encroachment.

    If it occurs, the distance relay will detect the reduced load impedance. It can move

    within the characteristic circle of distance relay. The distance relay not identifybetween fault and actually load. The decrease impedance affect to see as indicating a

    fault condition on the line, and will trip the circuit breaker. This of course is no fault

    condition is in fact present on the line. It is a false trip, which is undesirable the false

    trip occurs at a very inconvenient time in the operation of the power system, when the

    demand for power is very high [7].

    The load encroachment caused by load power is a problem to distance relay

    using Zone 3. An impedance depends on the magnitude and the power factor of the

    load impedance.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    36/89

    27

    The apparent impedance as seen by a distance relay is given by

    ( )

    2 2

    2 2 2a

    V P jQ V S Z

    P Q S

    += =+

    Eq. 2-7

    aZ = The apparent impedance seen by a distance relay.

    V = The line voltage.

    S = The complex power.

    ,P Q = The active and reactive powers

    If the magnitude of complex power fixed is follow in Equation 2-8. The

    apparent impedance is illustrated in Figure 2-14 where the radius of circle is increased

    because of the larger of the magnitude of the complex power and the m1 direction of

    apparent impedance as the power factor decreases [8].

    2

    a

    VZ

    S= Eq. 2-8

    a1

    a2

    r1

    r2

    m1

    m1 m2

    R

    X

    bZone 3

    FIGURE 2-14 The apparent impedance as the complex power vary ( )1 2,a a and

    the power factor vary ( )1m

    In Figure 2-14, when the power factor is fixed, the apparent impedance is

    illustrated follows and the m2 direction of apparent impedance as the magnitude of

    the complex power becomes larger. This scenario is possible as the distance relay

    mal-operates due to the reason that the load power becomes greater [8].

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    37/89

    28

    The apparent impedance of the real parts and imaginary part are written as

    2

    2 2

    V P

    RP Q= +

    Eq. 2-9

    2

    2 2

    V QX

    P Q=

    + Eq. 2-10

    The R and X can written as

    4

    2 2

    2 2

    VR X

    P Q+ =

    + Eq. 2-11

    If Equation 2-11 written depend on R and X from Equation 2-9 and Equation

    2-10 can be written as

    2

    2 2 R V

    R XP

    + = Eq. 2-12

    22 4

    2

    22 4

    V VR X

    P P

    - + =

    Eq. 2-13

    2

    2 2 X VR X

    Q+ = Eq. 2-14

    22 4

    2

    22 4

    V VR X

    Q Q

    + - =

    Eq. 2-15

    When P and Q fixed, Equation 2-12 and Equation 2-14 is a circle with

    Center of P :

    2

    ,0

    2

    V

    P

    , Radius of P:

    2

    2

    V

    P

    Center of Q:

    2

    0,2

    V

    Q

    , Radius of Q:

    2

    2

    V

    Q

    In Figure 2-15 the apparent impedance is the direction when the active power

    increases. In part direction when reactive power increases. Therefore, the distance

    relay may lead to mal-operation because to encroach Zone 3.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    38/89

    29

    X

    R

    Zone3

    a

    m1

    b

    m2

    0

    2

    V

    Q

    2

    V

    P

    FIGURE 2-15 An apparent impedance as the active and the reactive power vary

    2.8 Load Encroachment

    The maximum load that, sometime greater than loadability limit in system. Until

    distance relay can not distinguish from a fault and last will lead to trip of transmission

    line.The impedance of heavy loads can actually be less than the impedance of some

    faults. However, the protection must be made selective enough to discriminate

    between load and fault conditions. Unbalance aids selectivity for all faults except

    three-phase faults [9].

    When power flows out, the load impedance is in the wedge-shaped load-

    impedance area to the right of the X-axis. When power flows in, the load impedance

    is in the left-hand load impedance area.

    There is overlap (shaded solid) between the mho circle and the load areas.

    Should the load impedance lie in the shaded area, the impedance relay will detect the

    under-impedance condition and trip the heavily-loaded line. Such protection

    unnecessarily limits the load carrying capability of the line.

    For better load rejection, the mho circle can be squeezed into a lenticular or an

    elliptical shape. Unfortunately, this also reduces the fault coverage.

    Alternatively, we could use additional comparators to make blinders parallel to

    the transmission line characteristic to limit the impedance-plane coverage, and

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    39/89

    30

    exclude load from the tripping characteristic. Or, we could build quadrilateral

    characteristics, which box-out load.

    FIGURE 2-16 Load encroachment on mho distance element characteristics

    All traditional solutions have the same common approach: shape the operating

    characteristic of the relay to avoid load. The traditional solutions have two major

    disadvantages:

    2.8.1 Reducing the size of the relay characteristic desensitizes the relay to faults

    with resistance. Avoiding a small area of load encroachment often requires sacrificing

    much larger areas of fault coverage.

    2.8.2 From a user's point of view, the more complex shapes become hard to

    define, and the relays are harder to set.

    However, long lines, infeed, and load encroachment may cause difficulties to

    obtain that result in a secure manner. It is the opinion of the authors that uncontrolled

    disconnection of power lines should be avoided during voltage instability [10].

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    40/89

    CHAPTER 3

    LITERATURE SURVEY

    3.1 PreviousWorks on Disturbance for Zone 3 of Distance Protection

    This chapter present previous works on disturbance affect distance protection.

    Which simulation on software to test influence of disturbance on distance protection.

    3.1.1 Evaluation and Performance Comparison of Power Swing Detection

    Algorithms[11]

    Research comparison of power swing detection algorithms. The research

    studied operation of the power swing detectors, analyzed for different conditions and

    the operation of different algorithms. The method utilize compare such as the

    decreased impedance method, the Vcosj algorithm, the superimposed method and

    the decreased resistance method. Result of research found that the decreasing

    resistance algorithm has the best behavior, because this method is able to detect slow

    and fast power swings and can detect three-phase fault during power swing better

    other method.

    FIGURE 3-1 The impedance changes when a power swing with oscillation

    frequency equal to 0.1 Hz

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    41/89

    32

    Testing simulating different types of conditions on the power system and

    include power swing without and with fault, and different types of faults without

    power swing. Varying the load angle of generator with different frequencies and the

    maximum power angle creates different power swings. Such disturbances on the

    system will cause the power to swing with different oscillation frequencies.

    Simulation result for the power swing curve of the proposed model is given in

    Figure 3-1. These figures show the impedance changes when a power swing with

    oscillation frequency equal to 0.1 Hz has occurred.

    3.1.1.1 The Decreased Impedance Method

    The principle of this method is based on the impedance locus changes slower

    during a power swing than when a fault occurs. Figure 3-2 shows power swing

    blocking characteristics, which consists of two concentric mho characteristics. The

    outer characteristic is an offset mho characteristic and set concentric with the inner

    mho characteristic. The criteria for operation is the time t taken for the impedance

    locus to pass through the area between the two mho characteristics. If there is a fault

    condition, the impedance locus will move instantaneously from the load position to

    the fault position inside the power swing blocking characteristic, and no blocking will

    occur. During a power swing however, the locus moves much slower, at a speed

    determined by the inertia of the system, and if the time taken to travel between the

    outer characteristic and the inner characteristic exceeds setting t, the power swing

    blocking unit will operate.

    FIGURE 3-2 Power swing blocking characteristic

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    42/89

    33

    3.1.1.1.1 The simulation in various frequency of slip

    Test the method can the outputs of distance relay and Power Swing Detector

    (PSD) for a power swing with fs = 0.1 Hz and max = 180 degrees. As shown the

    PSD has operated at t=1.6 s and the distance relay has operated at t=2s. Operation of

    PSD will block operation of the distance relay. When power swing occurs the

    impedance enters the distance relay characteristic, and cause relay misoperation if

    steps are not taken to prevent this.

    Then to test in case at fs = 5 Hz and max = 90 degrees. It shows that the PSD

    has not operated but the distance relay has operated. More tests show that this method

    cant distinguish power swings with slop frequency of 5 Hz or more than that.

    3.1.1.1.2

    The simulation when earth fault with high resistance

    When test an earth fault, the outputs as shown, the distance relay has not

    operated but the PSD has operated. The time the impedance locus will take to pass the

    power swing blocking characteristic at this type of fault has been longer than setting

    time ( tD ) and therefore the PSD has operated.

    a) The conclusion disadvantage of the method as

    follows.

    b)

    This method is not able to distinguish fast power

    swings.

    c) This method may operate for earth faults with high

    fault resistance.

    d) If during a power swing a three-phase fault occurs, it

    is possible that the blocking relay will not reset.

    3.1.1.2

    The Vcos Algorithm.When power swings occur different electrical quantities vary as a function of

    the angle at a greater or lesser speed. When a fault occurs, however, these quantities

    change suddenly. Those, which vary considerably regardless of the location in a wide

    range around phase opposition, are the voltage component Vcos.

    This algorithm evaluates the change in Vcos as a function of time. The

    criterion upon which the response by the power swing-blocking relay depends is the

    steady reduction in the absolute value of Vcos. This value is measured once every

    half-cycle.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    43/89

    34

    As shown, after the fault, the value of Vcos decreases as before fault.

    Therefore if during a power swing a three-phase fault occurs, it is possible that the

    blocking relay will not reset and that the distance relay will remain blocked.

    3.1.1.3 The Superimposed Method.

    A power swing produces continuous superimposed signals as a result of the

    change in current and voltage signals between power frequency cycles. This method

    uses the superimposed current signals for detecting the power swing.

    When test simulated changes in superimposed currents for a three phase fault

    that has occurred during a power swing with fs = 0.1 Hz and max = 180 degrees. As

    shown, after the fault, the value of superimposed currents change as continually.

    Therefore if during a power swing a three phase fault occurs, the blocking relay will

    not reset and the distance relay will remain blocked. As shown, after power swing

    superimposed currents increased for two cycles and this increase can be used as the

    criteria for detection of faults. But when faults with high resistance occur, this

    increase is low and cannot detect these faults.

    3.1.1.4 The Decreased Resistance Method.

    When power swing occurs, the resistance component of the measured

    impedance will change continuously. But when a fault occurs, the resistance

    component of the measured impedance will not change except at the initial instant of

    short circuit. This phenomenon is proposed to be used to distinguish between the

    system fault and power swing.

    Results of simulation show that is able to detect slow and fast power swings.

    This method can even detect three-phase fault during power swing.

    Result to compare the behavior of different algorithms, the response of each oneof the algorithms was obtained for different power swings with presence of fault and

    without it. The test results of different algorithms during power swings with different

    power angles and different slip frequency. As shown, the Vcos method and the

    superimposed method have operated for all conditions but the decreased impedance

    method is unable to detect fast power swings.

    The test results of different algorithms for different three-phase faults during

    power swings with different conditions. It is shown that the decreasing resistance

    algorithm is always able to detect faults during power swings at different conditions

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    44/89

    35

    and for more cases other methods are not reset and the distance relay has remained

    blocked.

    The performance studies that the superimposed method is better than other

    methods. This method is able to detect different power swings and it can detect faults

    during power swing. In addition it is stable for high resistance faults.

    This paper describes the evaluation and performance comparison of different

    power swing detectors. The purpose several conventional algorithms were evaluated.

    It is found that the decreasing resistance algorithm has the best behavior, because this

    method is able to detect slow and fast power swings and can even detect three-phase

    fault during power swing.

    3.1.2

    An Enhanced Zone 3 Algorithm of a Distance Relay Using Transient

    Components and State Diagram[12]

    This research presents a novel zone 3 scheme based on combining the steady-

    state components and the transient components. The simulation results show the novel

    zone 3 distance relay elements using the proposed method operate correctly for the

    various events.

    The frequency components can also be used to detect the transient state during

    faults. The fundamental frequency component of the voltage or current is very large

    and the other frequency components are much smaller in pre-fault. However, during a

    fault, the other frequency components become prominent. In this paper are used to

    extract the TCs by digital algorithms based on fast Fourier transform (FFT).

    FIGURE 3-3 Block diagram of the proposed fault detector

    Figure 3-3 shows a block diagram of the fault detector using the steady-state

    and transient state characteristics. Signal S are generated by the fault detector using

    steady-state. At the same time signal T are generated by the fault detector using

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    45/89

    36

    transient state characteristics. In this paper, the signal S is generated when the

    apparent impedance as seen by a relay is within zone 3, whereas the signal T is

    generated when the sum value of the transient components (amplitudes) exceeds the

    preset threshold value.

    Conclusion of a novel scheme for transmission line fault detection using zone 3

    and the transient components that are combined by using the state diagram. Two fault

    detection signals and are generated based on the steady-state and transient state

    characteristics, respectively. A comprehensive set of simulation results has shown that

    a distance relay employing the proposed method has no problems of the

    maloperations that are caused by the heavy loading or the voltage instability

    associated with conventional distance relay. Furthermore, as an adjunct to the

    aforementioned attributes, faults can also be detected during encroachment of zone 3

    due to heavy loading.

    3.1.3

    Use of Wavelets for out of step Blocking Function of Distance Relays

    [13]

    Present wavelet analysis to detect power swings. Analysis power swing during a

    symmetrical fault occurrence. Different power swing conditions and fault instants are

    simulated with PSCAD/EMTDC software to test the methodology.

    Out of step blocking is function in distance relays to detect a power swing and

    block the operation of a distance relay due to the power swing. The method to detect a

    power swing is to measure the rate of change of impedance as it travels into the

    protection zones of the relay. However, if there is a fault during a power swing, this

    function must unblock and agree to let the relay trip.

    However, if a symmetrical fault occurs during a power swing when theimpedance has already passed the blinders, it is impossible to detect with this

    methodology. This could result in the relay not being able to clear a fault.

    A distance relay can also trip on load. In relaying parlance, this behavior is

    known as load encroachment. Usually, loads have a large power factor. Hence, the

    relay characteristic is modified to avoid this region. A line-tripping contingency can

    also lead to load encroachment. It can be detected by computing the relay impedance

    from a load flow analysis.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    46/89

    37

    3.1.4Adaptive Blinder for Distance Relay Based on Sensitivity Factors[14]

    After clearance of fault, some transmission lines may be overloaded, which may

    cause cascading trips even total blackout. This paper presents an adaptive distance

    relaying based on linear sensitivity

    In this research study one part of algorithm to enhance discriminate overload

    and fault, and block zone 3 trip caused by overload. The result can take work together

    with blinder scheme of distance relays.

    3.1.5

    A Novel Scheme to Identify Symmetrical Faults Occurring During Power

    Swings[15]

    In this paper present fast unblocking scheme for distance protection to identify

    symmetrical fault occurring during power swings. When the power swing occurs

    affect to a change appear in the reactive voltage phase angle between machine. The

    method use the change rate of change of active power and reactive power. When a

    fault occurs, the rate of change will level off to zero. Convention algorithm for power

    swing detection such as the decreasing impedance, the rate of change angle voltage,

    the superimposed current method.

    The conclusion of disadvantage of the purpose. First, the relay may not respond

    to genuine faults occurring during the power swing period since it is blocked from

    operation. Second, the time delay has to be set with a knowledge of the likely speed of

    movement of the impedance during the power swing.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    47/89

    CHAPTER 4

    ALGORITHM AND SIGNAL ANALYSIS

    4.1 Fundamental Considerations [16]

    Continuously vary signal usually sinusoidal current and voltage from C.T. and

    P.T. are applied to the input of the converter. These, however, may not just consist of

    the fundamental, but may include superimposed high frequency interference,

    harmonics, subharmonics and also a DC component. The general equation for the

    input signal is thus.

    ( ) ( ) ( )ap

    t T1 1 1 0 k 1 k

    k 2

    v t V cos t V e V cos k t-

    =

    = w - a + + w - a Eq. 4-1

    Where

    1V = Amplitude of the fundamental at rated frequency

    2 pV ...V = Amplitude of the harmonics k times higher than the rated frequency

    0V = Initial value of the DC component which decays at a time constant aT

    4.2 Digital Distance Measurement [16]

    By far the greater part of all the publication on the subject of selective digital

    protection are concerned with the determination of the distance between the relay

    location and fault on highvoltage line. This complex of problems is so dominant that

    even the equation for the discrete power were mere by-products during the

    development of the algorithm for calculating reactance and resistance.

    As is the case with analog protection device, the operation principle of most

    digital distance protection systems is based on the determination of whether the values

    of resistance and reactance (or resistance and inductance) measured at the relay

    location lie inside the operating characteristic, thus indicating a fault in the zone of

    protection.

    The majority of digital distance relay perform their task by first calculating the

    resistances

    R and the reactance s 1 sX L= w from the given input variable for the

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    48/89

    40

    current ( )i t and voltage ( )u t and then determining whether the values obtained lie

    within the operating characteristic in the R X plane.

    FIGURE 4-1 Distance protection measuring principle PD = protection device,

    FR =fault resistance

    There many factors which influence the accuracy of the values determined for

    the resistance and reactance of a fault on the values determined for the resistance and

    reactance of a fault on an overhead line. Amongst these are:

    4.2.1

    Distortion of the current and voltage curves by decaying DC component

    and high frequency oscillation

    4.2.2 Fault resistance ( )FR

    4.2.3 C.T and P.T. errors, primarily saturation phenomena caused by decaying

    DC components.

    4.2.4 Inductive coupling and insulation breakdown the conductors of the

    faulted line, respectively between the faulted and healthy circuit of a double circuit

    line.

    The derivations of the algorithm for calculating sR and sX generally only take

    account of the above factors, because it is assumed that the mutual impedance

    between conductors can be compensated with the aid of the zero-sequence

    component, respectively with the aid of the current of healthy lines. It is also assumed

    that the amplitude and phase errors of C.T. and P.T. and the error due to the fault

    resistance FR are relatively small compared with the reactance sX and may therefore

    be neglected. As is explained later, these assumption are not permissible in all cases.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    49/89

    41

    4.3 Fourier Analysis [17]

    4.3.1 Trigonometric form

    Any periodic function ( )f t can normally be represented by a Fourier series of

    discrete harmonics

    ( ) 0 n 0 n 0n 1 n 1

    af t a cos n t b sin n t

    2

    = =

    = + w + w Eq. 4-2

    Where 0w is the angular fundamental frequency 02 f 2 T= p = p

    T is the time period of the fundamental component

    0nw is the nth harmonic angular frequency

    1t is arbitrary

    Given the known function ( )f t (which in most practical situation is a function

    is a function that varies with time), the coefficients 0 1 1 n na , a , b ,...a , b can be

    determined from expressions of the from of Equation 3-2 to 3-4

    ( )1

    1

    t T

    0

    t

    2a f t dt

    T

    +

    = Eq. 4-3

    ( )1

    1

    t T

    n 0

    t

    2a f t cos n t dt

    T

    +

    = w Eq. 4-4

    ( )1

    1

    t T

    n 0

    t

    2b f t sin n t dt

    T

    +

    = w Eq. 4-5

    Alternative, by combining corresponding sine and cosine terms of the same

    frequency, Equation 4-2 can be written as

    ( ) ( )n 0 nn 0

    f t A cos n t

    =

    = w + q Eq. 4-6

    Where

    0n 0

    aA , 0

    2= q = Eq. 4-7

    And

    ( )

    2 2 1 n

    n n n n

    bA a b , tan n 1,2,...

    a

    -= + q = = Eq. 4-8

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    50/89

    42

    4.3.2 Complex form

    In some applications it is more convenient to use the complex form of Fourier

    series give in Equation 4-9. It will be apparent that the latter equation is directly

    equivalent to the basic Fourier series expression given in Equation 4-2.

    ( ) 0jn tnn

    f t F e

    w

    =-

    = Eq. 4-9

    Where

    ( )n n n

    0

    F a jb 2,n 1, 2 ...

    a 2, n 0

    = - =

    = =

    By substituting Equation 4-2 to 4-4 into the above equation, nF reduces to

    ( )

    ( )

    01

    1

    1

    1

    jn tt T

    nt

    t T

    t

    f t e dt, n 1, 2...1F

    T

    1f t dt, n 0

    T

    - w+

    +

    = =

    = =

    Eq. 4-10

    4.4 Fourier Analysis Based Algorithm [17]

    Function of time ( )f t can be represented by s Fourier series and each

    coefficient of the series can be found according to the formula given in Equation 4-1

    to 4-3.

    Voltage and current waveforms are of course function of time and they can be

    consequently expanded using the Fourier series. If we take, for example, a voltage

    waveform ( )v t , then

    ( ) 0 n 0 n 0n 1 n 1

    av t a cos n t b sin n t2

    = == + w + w Eq. 4-11

    And from Equation 4-4 and 4-5

    ( )1

    1

    t T

    n 0

    t

    2a v t cos n t dt,n 0,1,...

    T

    +

    = w = Eq. 4-12

    ( )1

    1

    t T

    n 0

    t

    2b v t sin n t dt, n 1,2,...

    T

    +

    = w = Eq. 4-13

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    51/89

    43

    Where 0w is the angular frequency of the fundamental component and T is its

    period.

    Equation 4-12 and 4-13 show that the fundamental component of a voltage and

    current waveform can be extracted from the corresponding faulted waveform simply

    by setting n 1=

    4.5 Principle of Algorithm

    Figure 4-5 to add block diagram of sT and Theshold part. This blocks will

    detect fault. The detecting fault will operate when change rate power increase morn

    than threshold value setting.

    FIGURE 4-2 Algorithm of detection fault

    In Figure 4-3, the algorithm suppose fault 1 occur between circuit breaker 5 and

    6 at 2 second. Then fault clear at 2.1 second. After that the power swing occurring and

    effect to circuit breaker 1, 2, 3 and 4. This occurrence result from the power swing

    blocking (PSB) function to operate because the impedance move to zone protection of

    distance relay. Then fault 2 occurring in front of circuit breaker 3.

    FIGURE 4-3 Fault 1 occur at 200 km both breaker 5 and 6

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    52/89

    44

    As fault 2 occurrence during power swing, the relay cannot to operate because

    relay perform blocking from power swing blocking(PSB). This is maloperation of the

    relay and effect to system instability.

    FIGURE 4-4 Fault 2 occur at front of breaker 3

    In thesis to present solve this problem by unblock scheme to detect fault

    occurring between power swing. When power swing occur cause distance relay no

    operate. Because distance relay block operate by power swing block function.

  • 7/25/2019 An Enhanced Performance of Distance Relay Algorithm to Prevent (Tesis)

    53/89

    CHAPTER 5