analysis of cogeneration powered absorption chiller

29
Università degli Studi di Trieste Corso di Dottorato di Ricerca in Tecnologie Chimiche ed Energetiche Analysis of Cogeneration Powered Absorption Chiller Systems in Remote Tropical Areas Anno accademico 2006-2007 Dottorando Stephen Chijioke Nwanya

Upload: others

Post on 30-Oct-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Analysis of Cogeneration Powered Absorption Chiller

Università degli Studi di Trieste

Corso di Dottorato di Ricerca in Tecnologie Chimiche ed Energetiche

Analysis of Cogeneration Powered

Absorption Chiller Systems in Remote

Tropical Areas

Anno accademico

2006-2007

Dottorando

Stephen Chijioke Nwanya

Page 2: Analysis of Cogeneration Powered Absorption Chiller

Target of the research

The study focuses on developing a technology for meeting the

energy needs of a tropical remote area, using minimal

consumption of energy resource and increase energy

efficiency, especially utilizing the waste heat to generate

cooling effect.

Page 3: Analysis of Cogeneration Powered Absorption Chiller

Introduction

Characteristic problems of a typical Nigerian remote area in the tropics

include:

•susceptibility to grid-connected electricity supplies either unavailable,

unreliable or for most of the inhabitants unaffordable;

•in terms of economic activity, is predominately populated by farmers

living in difficult terrain and

•the climate condition has preponderance of high ambient temperature.

Considering the increasing cost of fuel, the last two characteristic

problems draw attention to the necessity for cold generation independent

of grid electricity.

Page 4: Analysis of Cogeneration Powered Absorption Chiller

Introduction

The first characteristic problem underscores need for

sustainable alternative energy mix solution.

Paradoxically, Nigeria has abundant energy resources and the

citizens face serious insufficiency problems.

Some data

Population of Nigeria: 140 million inhabitants

Installed power capacity: 6 GW

Population of Italy: 56 million inhabitants

Installed power capacity: 84 GW

Page 5: Analysis of Cogeneration Powered Absorption Chiller

Fresh tomato fruits in wooden baskets and sealed with paper

as traditional transit preservation method

Typical perishable products from remote areas

Page 6: Analysis of Cogeneration Powered Absorption Chiller

Garden egg fruit

Meat

Vegetable

Other Vegetables

Page 7: Analysis of Cogeneration Powered Absorption Chiller

…from the newspapers

• Energy crisis killing tourism in Cross River

• …Museum groans under two-month blackout

[The Sun, May 15, 2008]

• Nigeria: Total Blackout Looms - Power Supply Now Lowest

Ever [This Day, Feb. 11, 2008]

• Nigeria: Nationwide Blackout Worsens As Funding Stalls

Repairs [This Day, May 14, 2008]

Page 8: Analysis of Cogeneration Powered Absorption Chiller

Question!

The basic question now is which alternative energy

technology can satisfy the energy scenario for the

remote area:

• with extended resource utility;

• enhance standard of living and

• achieve savings in cost monetarily and

environmentally?

Page 9: Analysis of Cogeneration Powered Absorption Chiller

Micro-gas turbine – Capstone 60

Page 10: Analysis of Cogeneration Powered Absorption Chiller

Introduction

Scientific efforts were made in the past to improvise

alternative conventional cooling (storage) system using local

solid absorbent materials. The envisaged storage system was

limited by heat transfer problems.

Under this circumstance, micro-gas turbine, (MGT) system

providing both power and waste heat is being proposed as

viable alternative technology.

The waste heat recovered will be useful to run an absorption

refrigeration chiller system, thus satisfying the necessity for

cold generation (preservation & comfort ).

Page 11: Analysis of Cogeneration Powered Absorption Chiller

Introduction

At present in Nigeria, cogeneration integrated absorption

refrigeration chiller is uncommon system.

In view of this there is need to determine relevant thermo-

physical properties, working conditions together with the

economy of heat delivery for better efficiency of the integrated

system.

This is essence of the analytical study on the cogeneration

powered absorption chiller system.

Page 12: Analysis of Cogeneration Powered Absorption Chiller

Purpose of study

The purpose of this study include:

• point out advantages of cold availability;

• analyze available technologies to provide cold and to

provide electricity in remote locations; provide “easy to

handle” information regarding the new technologies

preferably in language spoken by technicians;

• develop a thermoeconomic analysis of a small scale

microturbine-absorption chiller cogeneration plant.

Page 13: Analysis of Cogeneration Powered Absorption Chiller

Specific objectives

The following specific objectives are pursued:

•estimation of optimal thermodynamic property

conditions for absorption refrigeration system;

•estimation of the unit cost of thermal energy supply

and;

•determination of whether cogeneration will provide

substantial reductions in annual energy bill and justify

the required capital investment.

Page 14: Analysis of Cogeneration Powered Absorption Chiller

Methodology

•energy balances,

•mass conservation,

• exergy analysis and

•thermoeconomic principles are sequentially employed in

order to realize the set objectives.

In the course of analytical work, a simple Libr/H20 absorption

chiller system was configured using set of thermodynamic

equations and operated at steady state conditions. An

important tool for this work is Engineering Equation Solver,

EES computer software.

Page 15: Analysis of Cogeneration Powered Absorption Chiller

Modelling a simple absorption refrigeration system

To build up system, two important circuits are defined:

•The heat addition circuit consists of evaporator service side temperature

and evaporator absorption side temperature

•The heat loss circuit comprises condenser absorption side temperature

and condensing side temperature.

Once these temperatures are established the mixture chamber primary

properties can be determined from Pressure(P)-Temperature(T)-

Concentration(X), PTX diagram or built-in EES data base.

Page 16: Analysis of Cogeneration Powered Absorption Chiller

CONDENSER GENERATOR

EVAPORATOR ABSOBER

330C

480C

(9)

(10)

T2 = 900C

1200C (12)

1300C (11)

T3 = 330C 3

T4150C 4

QC

(rejection)Q

g (Heat supply)

2

1

A

Pump

E T=400C

Tg=900CCPTp = 450C

Solution Heat

Exchanger

Qa (rejection)

330C 480C

(7) (8)

290C 180C

(5) (6)

T1 = 150C

Qe (in)

W

Motor

D

Ta =400C

Simplified schematic of a Absorption Refrigeration Cycle

Page 17: Analysis of Cogeneration Powered Absorption Chiller

Mechanism of operation of the absorption chiller

The system is energized by a heat medium, steam at 130 0C from

recuperator of a micro-gas turbine.

The chiller uses a solution of lithium bromide and water, under a

vacuum, as absorbent and refrigerant, respectively.

The operation mechanism is such that keeping the evaporator

temperature lower than refrigeration load temperature, it is possible for

refrigerant to extract sensible heat from the load.

Page 18: Analysis of Cogeneration Powered Absorption Chiller

Detailed operation of absorption Chiller

Page 19: Analysis of Cogeneration Powered Absorption Chiller

0.90

0.91

0.91

0.92

0.92

0.93

0.93

0.94

0.94

0.95

0.95

0.96

6 8 10 12 14 16 18

T1

CO

P/C

OP

re

f

Example of sensitivity analysis

Influence of evaporator temperature, T1 on COP

Page 20: Analysis of Cogeneration Powered Absorption Chiller

0.007 – 0.05N/A0.01 – 0.020.0045 –

0.0105

0.0075–

0.0150.004

Operating

and

Maintenance

s cost($/kWh)

2500 – 35001300 –

2000900 – 1500450 – 950800 – 1600

1000 –

2000

Average cost

Investment

(S/kW)

10 – 201010202025 – 35Life cycle

(year)

GoodGoodFairFairGoodPoorPart load

Performance

90 – 95N/A9896 – 989590 – 95Availability

(%)

0.005 – 0.010.23d0.10.3 – 0.50.2 – 1.0c

NOX

emissions

(kg/MWh)

430 – 490672d720580 – 680500 – 620cCO

2

emissions

(kg/MWh)

0.8 – 1.11.2 – 1.71.2 – 1.70.2 – 0.80.5 – 0.70.1– 0.5Heat to

Power ratio

85 – 9065 – 8560 – 8565 – 8770 – 9260 – 80Efficiencyoverall (%)

37 – 604015 – 3025 – 4225 – 437 – 40Efficiencyelectrical

(%)

Hydrogen

and fuelscontaining

hydrocarbons

Any (gas,

alcohol,butane,

biogas)

Gas, propane,distillate oils

biogas

Gas, propane,distillate oils

biogas

Gas, biogas,liquid fuels,

propane

AnyFuel used

5kW – 2MW1kW –

1.5MW

15kW –

300kW

250kW –

50MW3kW – 6MW

50kW–500

MW

Capacity

range

Fuel cellsStirling

engines

Micro-

turbinesGas turbines

Spark

ignition

engines

Steam

turbine

Characteristics of some prime movers used for cogeneration

Page 21: Analysis of Cogeneration Powered Absorption Chiller

Modelling micro-gas turbine

Assumptions

•The cogeneration system based on a gas turbine operates at steady state;

•ideal gas mixture principles apply for the air and combustion products;

•fuel is natural gas taken as ideal gas;

•the fuel combustion in combustion chamber is complete;

Key tools applied in modelling include:

energy balances, mass balances where necessary and composition of

reacting elements. These tools will be expressed using a set of governing

equations.

Page 22: Analysis of Cogeneration Powered Absorption Chiller

Schematic of the cogeneration micro-gas turbine

Page 23: Analysis of Cogeneration Powered Absorption Chiller

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 1.5 2 2.5 3 3.5 4 4.5

pressure ratio [-]

effic

iency [-]

electrical efficiency

thermal efficiency

total efficiency

Example of sensitivity analysis

Influence of pressure ratio on MGT performance

Page 24: Analysis of Cogeneration Powered Absorption Chiller

Schematic of the recuperator used for the

integrated absorption chiller

Page 25: Analysis of Cogeneration Powered Absorption Chiller

Exergy and thermoeconomic analysis

An exergy evaluation is necessary for the absorption cycle to:

• identify presence of irreversibility;

• determine available useful exergy; and

• quantify the exergy destroyed

Assumptions:

• the system flows under steady-state conditions;

• the reference environmental state point for system is T0 = 250C and,

P0 =101.325KPa;

Page 26: Analysis of Cogeneration Powered Absorption Chiller

Exergy cost balancing schematic diagram

EvaporatorAssembly

Con Eva Ab Val

SHX

GENQinlet

Pump

Pel

QlostQcool.effect

Page 27: Analysis of Cogeneration Powered Absorption Chiller

10

11

12

13

14

15

16

17

80 85 90 95 100 105 110 115

Heat source Temp. [°C]

Exerg

eti

c e

ffic

ien

cy [

%]

Example of sensitivity analysis

Influence of heat source temperature on Exergetic Efficiency

Page 28: Analysis of Cogeneration Powered Absorption Chiller

Conclusion

• The work has reduced knowledge gap on how to provide

alternative energy technology for remote areas in Nigeria,

• contributed towards the domestication, both the technology

of, and

• expertise in cogeneration operated absorption refrigeration in

Nigeria.

• Throughout the literature survey presented, no example of

previous work or existing functional system understudy is seen

for Nigeria.

• Adoption of both cogeneration and absorption refrigeration

technologies can be feasible and would benefit rural lifestyle

and boost agricultural production.

Page 29: Analysis of Cogeneration Powered Absorption Chiller

Grazie a tutti per l’attenzione !