Transformadores SecosSeguros, ecológicos, confiables y eficientes.
ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016
![Page 2: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/2.jpg)
Que es un Transformador seco?
© ABB Group August 26, 2016 | Slide 2
![Page 3: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/3.jpg)
Por que Transformadores secos?
© ABB Group August 26, 2016 | Slide 3
![Page 4: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/4.jpg)
Por que Transformadores secos?
© ABB Group August 26, 2016 | Slide 4
![Page 5: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/5.jpg)
Por que Transformadores secos?
© ABB Group August 26, 2016 | Slide 5
![Page 6: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/6.jpg)
© ABB Group August 26, 2016 | Slide 6
Transformadores secosPortafolio de Producto y desarrollo de tecnologias
![Page 7: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/7.jpg)
© ABB Group August 26, 2016 | Slide 7
Transformadores secosUna historia de innovación
ABB Invierte constantemente en eldesarrollo de nuevas tecnologias,manteniéndose en la punta como unfabricante de talla mundial libre enTransformadores secos
Tradicionalmente los transformadoressecos han sido utilizados para ladistribución y aplicaciones industriales enun rango de potencias no mayor a 15 kVy voltajes hasta 36 kV..
1994 ABB comienza a fabricar en voltajes de 52 kV y BIL 200 kV.
2004 ABB lanza la clase 52 kV con BIL 250 kV.
2010 ABB lanza la clase 72.5 kV y en potencias hasta 63 MVA, con conmutador bajo carga (OLTC) y bajo la tecnologia HiDry72 dry-type transformers
![Page 8: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/8.jpg)
© ABB Group August 26, 2016 | Slide 8
Transformadores secosPG DRY
Capacidad Anual de producción:Ventas Anuales:Número de empleados:Presencia Global:Tecnologías:Participación de ABB en el Mercado:
30,000 MVA650 MUSD1,800Nueve Focus FactoriesAbiertos, encapsulados en resina, Resibloc20%
![Page 9: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/9.jpg)
© ABB Group August 26, 2016 | Slide 9
Transformadores secosFabricante con presencia global
USA
Brasil
BulgariaItaly
Germany
Switzerland
Egypt SaudiArabia
Korea
China
India
Spain
Colombia
![Page 10: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/10.jpg)
© ABB Group August 26, 2016 | Slide 10
Transformadores secosTecnologías hechas a la medidas de las necesidades
Transformadores Encapsulado en Resina
Proceso de encapsulamiento bajo el mas riguroso controlde calidad para asegurar un aislamiento óptimo y unascaracteristicas mecanicas de alta calidad
Transformadores con el nivel de descargas parciales masbajas gracias al novedoso proceso de llenado en vacio,donde la resina es introducida en moldes, posteriormente auna cámara de vacío donde los componentes se moldeancomo una sola sección garantizando la inmersion total delaislamiento en la resina epóxica y evitando burbujas en elencapsulado.
Unico fabricante de Transformadores en resina epoxicacertificado por UL Tanto para Clase H (180 °C) como paraclase F (155 °C)
![Page 11: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/11.jpg)
© ABB Group August 26, 2016 | Slide 11
Transformadores secosTecnologías hechas a la medidas de las necesidades
Resibloc
Transformadores con fibra de vidrio reforzada que ofreceun diseño extremadamente robusto y alto desempeño para soportabilidad a esfuerzos por corto circuito (Fuerzasradiales y axiales).
Transformadores Resibloc probados y certificados para operar en temperaturas inferiores a -60 ºC.
Transformadores Resibloc versatiles (Tailor made), operando en condiciones y procesos criticos en diferentessegmentos de la industria, con un desarrollo tecnológico de mas de 40 años.
![Page 12: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/12.jpg)
© ABB Group August 26, 2016 | Slide 12
Transformadores secosTecnologías hecha a la medidas de las necesidades
Transformadores Abiertos (VPI)
Primera tecnología en Transformadores secos, con unalarga historia y desempeño, especialmente se encuentranen areas de distribución de media tension.
Tecnología VPI ( impregnación de arrollamientos enpoliéster de alta temperatura o en barniz epóxico).
Alto nivel de descargas parciales por el tipo de aislamiento
No apto para ambientes agresivos
Mayor frecuencia de mantenimiento.
![Page 13: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/13.jpg)
© ABB Group August 26, 2016 | Slide 13
Transformadores secosTipos de encerramientos
![Page 14: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/14.jpg)
© ABB Group August 26, 2016 | Slide 14
Transformadores SecosNormas y estándares
![Page 15: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/15.jpg)
Normas Transformadores SecosColombia
NTC3445 del 2008 normaliza las pérdidas, tensión de cortocircuito y corriente sin carga.
NTC3445 Aplica solo para transformadores con tensión primaria por debajo de 15kV ósea que para tensiones superiores no es aplicable.
© ABB Group August 26, 2016 | Slide 15
![Page 16: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/16.jpg)
Normas Transformadores SecosColombia
NTC3654 del 2003 es la norma general paratransformadores secos y es copia fiel de laIEC60076-11 con una pequeña y a su vezpeculiar e importante excepción.
En la norma general para transformadoressecos NTC3654, tabla 5, se describen losdiferentes sistemas de tensión y sus tensionesaplicadas y de impulso.
© ABB Group August 26, 2016 | Slide 16
![Page 17: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/17.jpg)
Normas Transformadores SecosColombia
Ensayo con tensión a impulso 1.2/50 micro segundos
El fin de este ensayo es asegurar que eltransformador este realmente en grado desoportar la tensión de impulso definida por lasnormas, semejante a una sobretensión de red,debido a una maniobra o a una descargaatmosférica.
© ABB Group August 26, 2016 | Slide 17
![Page 18: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/18.jpg)
Normas Transformadores SecosColombia
Tabla 5 – Norma NTC 3654
© ABB Group August 26, 2016 | Slide 18
![Page 19: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/19.jpg)
Normas Transformadores SecosNormas Internacionales IEC 60076-11
Consideren que si las especificaciones indican como norma a aplicar la IEC, untransformador con tensión primaria 13.2kV debe tener una tensión de ensayo aplicadade 38kV y un impulso de 95kV, ósea que los transformadores abiertos con tensión deensayo aplicada de 31kV y ensayo de impulso a 60kV son de considerar fuera denorma
© ABB Group August 26, 2016 | Slide 19
![Page 20: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/20.jpg)
Normas Transformadores SecosNormas Internacionales ANSI C57.12.01-2005
© ABB Group August 26, 2016 | Slide 20
![Page 21: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/21.jpg)
© ABB Group August 26, 2016 | Slide 21
Transformadores SecosConceptos de las normas ANSI e IEC
![Page 22: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/22.jpg)
Normas Transformadores SecosInterpretación de la clasificación IEC
Transformador Encapsulado en Resina
Clase H – 180 °C
Clase F – 155 °C
E2 – C2 – F1
Transformador Tipo Abierto
Clase H – 180 °C
Clase F – 155 °C
No cumple clasificación© ABB Group August 26, 2016 | Slide 22
![Page 23: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/23.jpg)
Normas Transformadores SecosInterpretación de la clasificación IEC
© ABB Group August 26, 2016 | Slide 23
![Page 24: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/24.jpg)
Normas Transformadores SecosInterpretación de la clasificación IEC
© ABB Group August 26, 2016 | Slide 24
Clase de aislamiento
A E B F H C
Temperatura total 105 120 135 155 180 220
Incremento 60 75 80 100 125 150
Hot Spot 15 15 15 15 15 15
En función de los materiales aislantes utilizados las clases de aislamiento pueden variar según la siguiente tabla:
Temperatura ambiente + Hot Spot + Incremento
Clase F 40°C + 15°C + 100°C Total 155°CClase H 40°C + 15°C + 125°C Total 180°C
![Page 25: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/25.jpg)
Normas Transformadores SecosConclusiones
© ABB Group August 26, 2016 | Slide 25
Los Parámetros de la norma NTC son inferiores a loestablecido en la Norma IEC 60076-11 y ANSI C57.12.01-2005.
Los Transformadores encapsulados y abiertos pueden ser tipo F(155 °C) o Tipo H (180 °C)
El trasformador encapsulado ofrece mayores ventajas conrelación al abierto:
• un equipo con mayores prestaciones de calidad y seguridad,• Mayor tensión de aislamiento• Mayor protección de los arrollamientos• Menor mantenimiento
![Page 26: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/26.jpg)
Normas Transformadores SecosConclusiones
© ABB Group August 26, 2016 | Slide 26
El trasformador encapsulado ofrece mayores ventajas conrelación al abierto:
• Mayor vida útil por ser libres de descargas parciales <5Pc unabierto tiene descargas parciales muy altas superior a >100Pc.
• El encapsulado respeta las clase climáticas medioambientales y decomportamiento al fuego E2 - C2 - F1 (E2 trabajo con alta humedady polución / C2 trabajo a -25°C / F1 libre de halógenos, ignifugo, yno emisión de gases tóxicos), estos últimos conceptos lostransformadores abiertos no lo pueden respetar.
![Page 27: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/27.jpg)
© ABB Group August 26, 2016 | Slide 27
Transformadores secos encapsulados en resinaMultiples beneficios
Seguridad para las personas y la propiedad:
No riesgo de incendio No inflammable y autoextinguible No se requieren medidas adicionales
de seguridad
Ecológico y ambientalmente seguro:
Procesos y materiales definidos con base en el respecto por el medio ambiente
Apto para instalar en zonas pobladas o cerca a los puntos de consumoreduciendo las pérdidas generadas porlos cables de transmisión.
No hay riesgo de fugas, contaminaciónde fuentes de agua o generación de humos tóxicos.
Libres de mantenimiento
Confiabilidad y Calidad ABB:
40 años de experiencia Cientos de miles de unidades
operando exitosamente en todo el mundo
Alta experiencia en aplicaciones complejas
Transformadores de larga duración Diseños optimizados Fabricas especializadas (Focus
factories) Diseñados para trabajar en ambientes
agresivos (Humedad, Polucion) Alta capacidad para soportar esfuerzos
de corto circuito Alta capacidad de sobrecarga Alto desempeño sismico Soportabilidad de vibraciones y
esfuerzos mecanicos
Fácil y rápida instalación
Less civil work needed Plug and play
![Page 28: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/28.jpg)
© ABB Group August 26, 2016 | Slide 28
Transformadores SecosDonde tenemos experiencia?
![Page 29: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/29.jpg)
Transformadores secos Aplicaciones para Infrastructura
© ABB Group August 26, 2016 | Slide 29
Hospitales Colegios Aeropuertos Centros comerciales Edificios residenciales
Transformadores de uso interno y externo
Transformadores de alta eficiencia Encerramientos hasta grado IP54 Transformadores para sistemas de
variación de velocidad
![Page 30: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/30.jpg)
Transformadores secos Aplicaciones marinas
© ABB Group August 26, 2016 | Slide 30
Transformadores para propulsionmarina de 3 devanados o mas ypotencias hasta 20 MVA
Diseños Robustos para soportaresfuerzos mecánicos a los que seexponen los barcos Rompe hielos
Tecnología Resibloc para operar entemperaturas inferiores a -60 °C
Alta confiabilidad de equipos ya quese ubican en el casco del barco y suacceso es imposible para extraer elTransformadores
![Page 31: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/31.jpg)
Transformadores secos Aplicaciones Petroleras Off Shore
© ABB Group August 26, 2016 | Slide 31
Mas de 25 años de experiencia en aplicaciones off-shore y refinerías
Alta confiabilidad, desempeño y seguridad en plataformas de perforación.
Transformadores con diversos tipos de refrigeración: AN/AF/WF
![Page 32: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/32.jpg)
Transformadores secos Data centers
© ABB Group August 26, 2016 | Slide 32
Maximizar la eficiencia en redes conalto contenido de electronica, enpresencia de armónicos.
ABB ha diseñado solucionesespecificas para data centerscaracterizadas por alta eficiencia ysistemas patentados como el TVRT(capaz de filtrar sobre voltajes yasegurar la protección delTransformador).
![Page 33: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/33.jpg)
Transformadores secos Aplicaciones Eólicas
© ABB Group August 26, 2016 | Slide 33
Mas de 15.000 unidades entregadaspara aplicaciones eólicas.
Soluciones customizadas
Diseños compactos y livianos
Soportabilidad a vibraciones: IEC 68-2-6/59, EN 60068.
Clase H - Sobrecarga continua sin afectar aislamiento (Vida util) .
Confiabilidad y alto desempeño, diseños libres de mantenimiento .
![Page 34: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/34.jpg)
Transformadores secos Otras Aplicaciones
© ABB Group August 26, 2016 | Slide 34
![Page 35: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/35.jpg)
© ABB Group August 26, 2016 | Slide 35
Eficiencia EnergéticaTOC
![Page 36: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/36.jpg)
© ABB Group August 26, 2016 | Slide 36
![Page 37: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/37.jpg)
© ABB Group August 26, 2016 | Slide 37
![Page 38: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/38.jpg)
© ABB Group August 26, 2016 | Slide 38
![Page 39: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/39.jpg)
© ABB Group August 26, 2016 | Slide 39
![Page 40: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/40.jpg)
© ABB Group August 26, 2016 | Slide 40
![Page 41: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/41.jpg)
© ABB Group August 26, 2016 | Slide 41
![Page 42: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/42.jpg)
© ABB Group August 26, 2016 | Slide 42
![Page 43: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/43.jpg)
© ABB Group August 26, 2016 | Slide 43
![Page 44: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/44.jpg)
© ABB Group August 26, 2016 | Slide 44
![Page 45: ANDRES SALAZAR – PEREIRA FACTORY / PGTR-DRY 2016](https://reader035.vdocuments.net/reader035/viewer/2022072301/62da6d64ea660a575936b13c/html5/thumbnails/45.jpg)
© ABB Group August 26, 2016 | Slide 45