ANTI-REVERSE CURRENT SOLUTIONS GoodWe (Germany) Fürstenrieder Str. 279a 81377 München, Germany T: +49 8974120210 [email protected] [email protected] GoodWe (China) No.189 Kunlunshan Rd., SND, Suzhou, 215163, China T: +86 (0) 512 6239 6771 [email protected] [email protected] GoodWe (Netherlands) Franciscusdreef 42C, 3565AC Utrecht, the Netherlands T: +31 (0) 30 737 1140 [email protected] [email protected] GoodWe (India) 1202, G-Square Business Park, Sector 30A, Opp. Sanpada Railway Stn., Vashi, Navi Mumbai- 400703 T: +91 (0) 2249746788 [email protected] [email protected] GoodWe (Mexico) Oswaldo Sanchez Norte 3615, Col. Hidalgo, Monterrey, Nuevo Leon, Mexico, C.P. 64290 T: +52 1 81 2871 2871 [email protected] [email protected] GoodWe (Turkey) Adalet Mah. Megapol Tower K: 9 No: 110 Bayraklı - Izmir T: +90 (232) 935 68 18 [email protected] [email protected] GoodWe (UK) 6 Dunhams Court, Dunhams Lane, Letchworth Garden City, SG6 1WB UK T:+ 44 (0) 333 358 3184 [email protected] [email protected] GoodWe (Italy) No. 17 Via Galimberti, Biella 13900, Italy T: +31 (0) 30 737 1140 [email protected] [email protected] GoodWe (Australia) Level 14, 380 St. Kilda Road, Melbourne, Victoria, 3004, Australia T: +61 (0) 3 9918 3905 [email protected] [email protected] GoodWe (Brazil) Rua Abelardo 45, Recife/PE, 52050-310 T: +55 54 992504491 [email protected] [email protected] www.goodwe.com

Upload: others

Post on 05-Jan-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

ANTI-REVERSECURRENT SOLUTIONS

GoodWe (Germany) Fürstenrieder Str. 279a 81377 München, Germany T: +49 [email protected]@goodwe.com

GoodWe (China) No.189 Kunlunshan Rd., SND, Suzhou, 215163, ChinaT: +86 (0) 512 6239 [email protected]@goodwe.com

GoodWe (Netherlands) Franciscusdreef 42C, 3565AC Utrecht, the Netherlands T: +31 (0) 30 737 [email protected]@goodwe.com

GoodWe (India) 1202, G-Square Business Park, Sector 30A, Opp. Sanpada Railway Stn., Vashi, Navi Mumbai- 400703T: +91 (0) [email protected]@goodwe.com

GoodWe (Mexico) Oswaldo Sanchez Norte 3615, Col. Hidalgo, Monterrey, Nuevo Leon, Mexico, C.P. 64290T: +52 1 81 2871 [email protected]@goodwe.com

GoodWe (Turkey) Adalet Mah. Megapol Tower K: 9 No: 110 Bayraklı - Izmir T: +90 (232) 935 68 [email protected]@goodwe.com.tr

GoodWe (UK) 6 Dunhams Court, Dunhams Lane, Letchworth Garden City, SG6 1WB UKT:+ 44 (0) 333 358 [email protected]@goodwe.com.uk

GoodWe (Italy) No. 17 Via Galimberti, Biella 13900, ItalyT: +31 (0) 30 737 [email protected]@goodwe.com

GoodWe (Australia) Level 14, 380 St. Kilda Road, Melbourne, Victoria, 3004, AustraliaT: +61 (0) 3 9918 [email protected]@goodwe.com

GoodWe (Brazil) Rua Abelardo 45, Recife/PE, 52050-310 T: +55 54 [email protected]@goodwe.com

www.goodwe.com

SINGLE PHASE INVERTER

ANTI-REVERSE WIRING

WHAT IS ANTI-REVERSECURRENT

FOR ONE PIECE GRID-TIED INVERTER

Limit the max power exporting to grid from solar system after feeding loads

× No need to use anti-reverse function

Pi: Inverter output power

Pl: Loads power

Pg: Power from/feed to grid

GOODWESINGLE-PHASE INVERTER

(NS / DNS SERIES)

CT - FROM GOODWE 1000 / 1, 90A

Anti-Reverse solution for a single phase inverter ( NS & DNS series )

1, Purchase a CT from GoodWe 2, Put CT on the main L line, and connect CT cable to inverter

3, Press 'Enter' button on the inverter to 'Set Power Limit'

Pi: Inverter output power

Pl: Loads power

Pg: Power from/feed to gridLimit Pg to 0 Limit Pg to a certain value

1 Finish wiring 2 Configure on inverter display

SINGLE PHASE

STEPS

THREE PHASE 1KW ~ 70KW

Scenario A: Pl = Pi + Pg

Scenario B: Pg = Pi – Pl

Logic:

Based on power limit value set on inverter display

Only works with goodwe CT

Anti-Reverse solution for a three phase inverter ( SDT & DT series )1, Purchase an EzMeter from GoodWe 2, Cut the Main L lines and then connect to EzMeter

3, A RS485 cable is used to communicate between inverter and EzMeter

4, Press inverter button to set the limit ON and Ratio

Logic:CT detects is there any or how much current stream flowing to/from the grid, then it sends signal to tell inverter to reduce or increase output power accordingly.

3-phase EzMeter communicates with the inverter and detects (on each phase) if there is any or how much current stream flowing to/from grid, then feedbacks the data to the inverter, which will know how much power (in total) it should produce after calculation.

MT SERIES INVERTER

THREE PHASE INVERTER

ANTI-REVERSE WIRING

HOW ANTI-REVERSE FUNCTION WORKS SINGLE PHASE HOW ANTI-REVERSE FUNCTION WORKS THREE PHASE

1 Finish wiring 2 Configure on inverter display

1 Finish wiring 2 Configure CT ratio on EzMeter 3 Set power limit value on inverter display

STEPS

STEPS

CT *3 EZMETER - FROM GOODWE GOODWE THREE-PHASE INVERTER

GOODWE THREE-PHASE INVERTER

(DT / SDT SERIES)

(MT SERIES) 100A/250A/1000A/500A : 5A

EZMETER - FROM GOODWE

(80A)

Example: (Power Limit 0W)

Total Loads: 6KWInverter output: 6KW (2KW on each phase)

1, Purchase an EzMeter from GoodWe and CTs from GoodWe or anywhere else 2, Put CTs on main L lines and connect CT cables to EzMeter CT ports

3, Connect L lines and Neutral line from anywhere to EzMeter power ports 4, An RS485 cable is used to communicate between inverter and EzMeter

5, Press EzMeter button to set CT ratio 6, Press inverter button to set the limit ON and Ratio

3-phase EzMeter communicates with inverter and CT detects (on each phase) is there any or how much current stream flowing to/from grid, then feedbacks data to the inverter, which tells how much power (in total) it should produce after calculation.

Press to change the value

Press to jump to another character

Note: CT is available from GoodWe or from external vendor (Ratio: ***/5A)

For the connection, CT1 (connected on Ia & Ia*) must be connected to the same phase line with Ua, same for CT2 & Ub, CT3 & Uc.

Wrong wir ing wil l cause inaccurate data detection which further lead to malfunction of solar system

Example: (Power Limit 0W)

Total Loads: 6KWInverter output: 6KW (2KW on each phase)

Anti-Reverse solution for a three phase inverter ( MT series )

Here to set CT ratio:

Logic:

Warning:

HOW ANTI-REVERSE FUNCTION WORKS

CT RATIO CONFIGURATION

ANTI-REVERSE WIRING

EZMETER & CT CONNECTION

FOR MULTI INVERTERS

EZMETER & CT CONNECTION

CONFIGURATION ON PROMATE

1, Purchase EzMeter and EzLogger Pro from GoodWe, CTs can be purchased from GoodWe or anywhere else

2, Put CTs on the main L lines and connect CT cables to EzMeter CT ports 5, Connect inverters to EzLogger Pro COM1/COM2/COM3

3, Connect L lines and Neutral line from anywhere to EzMeter power ports 6, Connect a laptop to EzLogger Pro net port and run ‘ProMate’

4, An RS485 cable is used to communicate between EzLogger Pro COM4 and EzMeter 7, Set power/current limit in the ‘ProMate’

Anti-Reverse solution for multiple three phase inverters

For the connection, CT1 (connected on Ia & Ia*) must be connected to the same phase line with Ua, same for CT2 & Ub, CT3 & Uc.

Wrong wiring wil l cause inaccurate data detection which further lead to malfunction of solar system

Warning:

1. Choose “EzLogger Pro”

2. Wait untill it shows “Connection Succeed” and serial No. & Version

3. Click ‘Refresh’ to check inverter SN connected to this EzLogger Pro

4. Here to configure monitoring a. set system parameters and CT ratio b. choose “Export Enab” c. Phase current & power display here

FOR MULTI-PIECES GRID-TIED INVERTERS

THREE PHASE LARGE SCALE PROJECTSSINGLE PHASE

1 Finish wiring 2 Set power limit value and CT ratio on EzLogger Pro STEPS

GOODWE 3-PHASE INVERTERS* 60 (MAX)

EZLOGGER PRO* 1

3-PHASE EZMETER* 1

CT * 3250A/1000A/5000A

Logic:

Note: CT is available from GoodWe or from external vendor (Ratio: **/5A)

250/5A 90 / 114 / 40 22 / 32

250/5A , 1000/5A 114 / 140 / 36 42 / 62

1000/5A 122 / 162 /40 42 / 82

1000/5A 144 / 159 / 36 82 / 82

M a x t o t a l c u r r e n t s t re a m t h ro u g h A C cable or copper bar

Ratio (A) W / H / D (mm) a /e (mm)

GOODWE CT SPECIFICATION

APP -> Set ->Advanced Setting ->Export Power Limit & Power Value

Support Information for CT selection

*The min space between AC cable or copper bars* The sizes of your cable or copper bars

5000/5A 164 / 234 / 52 62 / 142

5000/5A

K-30X20

K-60X40

K-80X40

K-80X80

Model

K-140X60

K-160X80 184 / 254 / 52 82 / 162

Example:(Power Limit 0W; Total Loads: 60KW)

EzMeter + CT detect curent flow and communicate with hybrid inverter, then inverter will keep extra power charging battery or drop inverter production to achieve power export limit.

1, Purchase a CT & EzMeter unit from GoodWe

2, Put CT on the main L line, and connect Ethernet cable from inverter to EzMeter

3, Connect inverter wireless signal ‘Solar-WiFi’ with a phone and run PV Master app

4, Switch ‘Export Power Limit’ to ON and set ‘Power Value’

Logic:

Anti-Reverse solution for one hybrid inverter ( ES, EM and BP series )

1 Finish wiring 2 Configure Power Limit Value on GoodWe APP

EzMeter + CT detect curent flow and communicate with Ezlogger Pro, then EzLogger Pro sends commands to inverters to drop output power.

CT SPECIFICATION & SELECTION EZMETER & CT CONNECTION

HOW ANTI-REVERSE FUNCTION WORKS HYBRID INVERTER SERIES(ES & EM)

STEPS

GOODWE HYBRID INVERTER

CONFIGURE POWER LIMIT ON APP

SMART METER - FROM GOODWE (ES / EM SERIES) (120A)

2.Export Power Limit

& Power Value

1.Advanced Setting