“Harmonics and Power Quality”
Case Studies
MSEDCL
28th November 2015
Mohammed Mohtasib
![Page 2: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/2.jpg)
Reactive Power Compensation
• Penalty / incentive mechanism for power
factor improvement
• Maximum 7% incentive on unity power
factor
• In metering, kVArh leading = 0
• Industries tend to keep power factor
leading “BY ADDITIONAL FIXED
CAPACITORS” to avail maximum benefit
5
![Page 3: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/3.jpg)
Impact of additional capacitors
• Harmonic amplification
• Chances of resonance
• Saturation of transformer and motors due
to voltage rise
• Saturated transformer and motors
generates more harmonics
6
![Page 4: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/4.jpg)
8
Power Quality Impact on Consumer
Each consumer have practically few or all power quality issues.
Due to increases non linear loads, harmonic generation is major concern
Generated harmonics distorts voltage waveform
![Page 5: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/5.jpg)
Power Quality Case Studies
15
![Page 6: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/6.jpg)
CASE STUDY
PRODUCTIVITY IMPROVEMENT
AND REDUCTION IN SEC
16
![Page 7: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/7.jpg)
PROBLEMS FACED BY THE PLANT
• Regular failure in a Steel Wire Rope Mill
– High Failure Rate of Motors
– High Failure rate of control cards
– Nuisance tripping of circuit breakers
– Failure of SWG
• SEC was 173 kWh/Ton
• Production cost – INR 1064 per ton
17
![Page 8: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/8.jpg)
HARMONICS
Before……
• High harmonic content – Vthd and Ithd
18
Vthd - Transformer A – 12%
Transformer B - 15%
Ithd - Transformer A – 21%
Transformer B - 60%
![Page 9: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/9.jpg)
HARMONICS
After ……
• After installation of passive filter
19
Vthd - Transformer A – 2.1%
Transformer B - 1.2%
Ithd - Transformer A – 11.2%
Transformer B - 7.2%
![Page 10: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/10.jpg)
BREAK DOWN ANALYSIS
20
![Page 11: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/11.jpg)
SUMMARY OF BREAKDOWN
ANALYSIS
21
Average monthly cost saving of 240,000
Average increase in production time 98 hours per month
![Page 12: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/12.jpg)
SPECIFIC ENERGY CONSUMPTION
& PRODUCTIVITY
22
![Page 13: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/13.jpg)
FINANCIAL ANALYSIS
23
![Page 14: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/14.jpg)
24
![Page 15: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/15.jpg)
CASE STUDY -
Distribution Network Voltage
Related Power Quality Issues
36
![Page 16: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/16.jpg)
Distribution Network Voltage Issues
Coca Cola• Coca Cola – Leading beverage
manufacturer, one of the plant at Khurda,
Orissa
• Receives power from 220 kV grid – 25 KM
from plant
• Same grid also supplies to traction load
37
![Page 17: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/17.jpg)
SLD of Grid Distribution System
38
![Page 18: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/18.jpg)
Problem Faced
39
• Unscheduled power cuts and voltage
unbalance
• Un balanced voltage
![Page 19: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/19.jpg)
Problem Faced …contd
40
• Voltage variation – On 33 kV incomer
variation is from 26.7 to 34.2 kV
![Page 20: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/20.jpg)
Problem Faced …contd
41
• Voltage variation – On LT Side incomer
variation is from 203 to 252 V
• SCADA recorded voltage dips as low as
20 Volts
![Page 21: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/21.jpg)
Problem Faced …contd
42
• Voltage Sags and Swells
![Page 22: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/22.jpg)
Problem Faced …contd
43
• Voltage & Current Harmonics 4.3% &
22.7%
• Voltage harmonics close to limit specified
by IEEE – 519 as 5%
• Current Harmonics on higher side
![Page 23: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/23.jpg)
Impact on Productivity and Financial
Loss
44
• With each interruption and event of power
quality, plant was facing production loss
![Page 24: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/24.jpg)
Temporarily PQ Mitigation Adopted
45
• Use of DG set instead of grid power
• Use of UPS for critical machines – almost
1.8 MVA
![Page 25: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/25.jpg)
Annual Monetary Loss
46
• Annual loss is through:
– Loss in productivity
– Additional cost due to continuous operation of
DG set
• Annual loss suffered by plant in terms of
loss in productivity and higher energy cost
is INR 62.5 Million per year.
![Page 26: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/26.jpg)
Asia Power Quality Initiative• Program initiated in Asia with the background of the European
Experiment (LPQI) – Continuing Professional Development
• A neutral collaborative platform shared by National Support Network (NSN) Partners to promote education and awareness and facilitate policy changes.
• Objective:
– help industries in Asia address Power Quality issues as a means to enhance their competitiveness in terms of better production output quality, reduced production costs, reduced production line interruption and batch losses.
– Building up capacity of industry / service sector in identifying and addressing PQ issues as a means to enhance their continuous quality delivery
– Facilitate policy changes and market transformation towards „Safe and Quality Power for All‟.
47
![Page 27: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/27.jpg)
APQI India
APQI India - National Support Network
Reach out to manufacturing industries
Reach out to electrical engineers and designers
Provide technical content
Support dissemination
• Business intermediaries
• Academics, consultants, PQ advocates
• PQ equipment suppliers, contractors
• Professional associations, institutes, societies
• Specialized media, event organizers
Provide official endorsement,
Lead policy and regulatory activities
• Policy makers, utilities
A neutral collaborative platform shared by National Support Network
(NSN) Partners to promote education and awareness and facilitate
policy / regulatory changes.
49
![Page 28: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/28.jpg)
Learning from APQI : A focus
around 3 Missions
50
Education &
training fine tuned
for individuals
A reference
for all PQ matters
in Asia
Lead the dynamic
through adequate
knowledge
management &
E-disseminationPrint publications
Electronic library
A network of European /Asian
PQ experts
(standardization/certification
body participation)
Leads appropriate PQ study
(PQ Survey,
PQ Regulation report)
Website
Forums
Seminars
Webinars
![Page 29: “Harmonics and Power Quality” - APQI · “Harmonics and Power Quality ... •Saturation of transformer and motors due to voltage rise •Saturated transformer and motors generates](https://reader030.vdocuments.net/reader030/viewer/2022040603/5ea1033106550153c37f9dc0/html5/thumbnails/29.jpg)
Ensuring High Power Quality is every
professional’s responsibility
High Power Quality benefits all
It increases productivity, profitability & competitiveness,
It improves customer relationship & ensures better employee loyalty
Visit : www.apqi.org51