D A T A F I L E To slow or prevent the spread of fire, building codes require fire-resistant or fire-rated assem- blies in certain locations, occupancies, and types of buildings. When fire-rated walls and/ or floor/ceiling assemblies are required, a fire barrier over the walls is typically necessary to prevent flames from escaping the confine- ment provided by the wall or ceiling assembly. The barrier may be in the form of continuous rim board on top of the wall and parallel with the floor joists or as continuous rim board along the top of the wall and perpendicular to the joists. A fire barrier can also be made by inserting individual sections of snugly fit rated material over the wall and between the floor joists and carefully sealed against fire passage. This last method is more labor intensive, particularly when wood I-joists or trusses are used to support the floor. Because the flammability and ignitability of the adhesive used in the rim boards is less than that of the wood, the adhesive does not melt prior to ignition. The wood itself determines the flammability of the rim boards. The assemblies diagrammed in this publication are based on char rates of APA Rim Boards as determined by the United States Forest Service, Forest Products Laboratory in Madison, Wisconsin. (a) The Rim Boards in this brochure were subjected to fire tests that met the requirements of ASTM E119 and CAN/ULC S101. FIRE-RESISTANT RIM BOARD ASSEMBLIES The rim board assemblies on the following pages will achieve the fire resistances shown. (a) White, R. H. 2003. Fire Resistance of Engineered Wood Rim Board Products. Research Paper FPL-RP-610. USDA Forest Service, Forest Products Laboratory. Madison, WI. Rim Board ® is a registered trademark of APA – The Engineered Wood Association. APA Rim Board ® in Fire-Rated Assemblies A gypsum wall board provides fire resistance for rim board assembly (see “RB1,” next page.) APA Performance-Rated Rim Boards are manufactured and tested under the requirements of ANSI/APA PRR 410 or APA PRR 401

Upload: roger-miller

Post on 17-Aug-2015

45 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: APA Rim in Fire Rated Assemblies D350

D A T A F I L E

To slow or prevent the spread of fire, building

codes require fire-resistant or fire-rated assem-

blies in certain locations, occupancies, and

types of buildings. When fire-rated walls and/

or floor/ceiling assemblies are required, a fire

barrier over the walls is typically necessary

to prevent flames from escaping the confine-

ment provided by the wall or ceiling assembly.

The barrier may be in the form of continuous

rim board on top of the wall and parallel with

the floor joists or as continuous rim board

along the top of the wall and perpendicular to

the joists. A fire barrier can also be made by

inserting individual sections of snugly fit rated

material over the wall and between the floor

joists and carefully sealed against fire passage.

This last method is more labor intensive, particularly when wood I-joists or trusses are used to support the floor.

Because the flammability and ignitability of the adhesive used in the rim boards is less than that of the wood, the

adhesive does not melt prior to ignition. The wood itself determines the flammability of the rim boards.

The assemblies diagrammed in this publication are based on char rates of APA Rim Boards as determined by the United

States Forest Service, Forest Products Laboratory in Madison, Wisconsin.(a) The Rim Boards in this brochure were

subjected to fire tests that met the requirements of ASTM E119 and CAN/ULC S101.

FIRE-RESISTANT RIM BOARD ASSEMBLIES

The rim board assemblies on the following pages will achieve the fire resistances shown.

(a) White, R. H. 2003. Fire Resistance of Engineered Wood Rim Board Products. Research Paper FPL-RP-610. USDA Forest Service, Forest Products Laboratory. Madison, WI.

Rim Board® is a registered trademark of APA – The Engineered Wood Association.

APA Rim Board®in Fire-Rated Assemblies

A gypsum wall board provides fire resistance for rim board assembly (see “RB1,” next page.)

APA Performance-Rated Rim Boards are manufactured and tested under the requirements of ANSI/APA PRR 410 or APA PRR 401

Page 2: APA Rim in Fire Rated Assemblies D350

Form No. D350B ■ © 2015 APA – The Engineered Wood Association ■ www.apawood.org 2

Data File: APA Rim Board in Fire-Rated Assemblies

FIRE RESISTANCE RATED RIM BOARD ASSEMBLY RB1

This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101RB1RB3

RB4

RB5

RB6

RB2

Load

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Load Load

Load

LoadLoad LoadLoad

Load Load

Load Load

LoadLoad LoadLoad

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building OfficialsSame as

right-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

END WALL CONFIGURATION BASE ASSEMBLY

Rim Board Thickness, in.

Rim Board Protection

Ceiling Membrane Req. for 1-hr

Ceiling Membrane Req. for 2-hr

Stud Size

Stud Size

A B C C D E

1

Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4

1-1/8

Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4

1-1/4

Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4

1-1/2

Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x6

1-3/4

Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x6

(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x61) Rim assembly for fire from inside of structure. 2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist. 6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X. 7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails. 9) Rim board needs to be sized for vertical and lateral loads.

Page 3: APA Rim in Fire Rated Assemblies D350

Form No. D350B ■ © 2015 APA – The Engineered Wood Association ■ www.apawood.org 3

Data File: APA Rim Board in Fire-Rated Assemblies

FIRE RESISTANCE RATED RIM BOARD ASSEMBLY RB2

This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101

RB1RB3

RB4

RB5

RB6

RB2

Load

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Load Load

Load

LoadLoad LoadLoad

Load Load

Load Load

LoadLoad LoadLoad

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building OfficialsSame as

right-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

SINGLE WALL CONFIGURATION BASE ASSEMBLY

Rim Board Thickness, in.

Rim Board Protection

Ceiling Membrane Req.for 1-hr

Ceiling Membrane Req.for 2-hr

Stud Size

Stud Size

A B C C D E

1

Unprotected 45-min Fire-rated Assembly 2-hour Fire-rated Assembly 2x6 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x6

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6

(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x8 2x6

(2) 5/8” Type X No Ceiling Required 1/2" Type X 2x8 2x6

1-1/8

Unprotected 45-min Fire-rated Assembly 2-hour Fire-rated Assembly 2x6 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6

(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x8 2x6

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x6

1-1/4

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x6 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x6

1-1/2

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x6 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x8 2x6

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x8

1-3/4

Unprotected 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x8 2x6

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x8 2x81) Rim assembly for fire from either side of wall.2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist.6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer (or more) gypsum wallboards are used, I-joist end nails shall be 16d

box (0.135 inch x 3-1/2 inches) nails.9) Rim board needs to be sized for vertical and lateral loads.

Page 4: APA Rim in Fire Rated Assemblies D350

Form No. D350B ■ © 2015 APA – The Engineered Wood Association ■ www.apawood.org 4

Data File: APA Rim Board in Fire-Rated Assemblies

RB1RB3

RB4

RB5

RB6

RB2

Load

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Load Load

Load

LoadLoad LoadLoad

Load Load

Load Load

LoadLoad LoadLoad

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building OfficialsSame as

right-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

FIRE RESISTANCE RATED RIM BOARD ASSEMBLY RB3

This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101

DOUBLE WALL CONFIGURATION WITH LOAD TRANSFER BASE ASSEMBLY

Rim Board Thickness, in.

Rim Board Protection

Ceiling Membrane Req. for 1-hr

Ceiling Membrane Req.for 2-hr

Stud Size

Stud Size

A B C C D E

1

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4

1-1/8

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X No Ceiling Required 5/8" Type X 2x4 2x4

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4

1-1/4

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 45-min Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X No Ceiling Required 5/8" Type X 2x4 2x4

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4

1-1/2

Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4

(1) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6

1-3/4

Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x6

(1) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x6

(1) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x61) Rim assembly for fire from either side of wall. “With load transfer” assumes load transfers to the adjacent rim board if the fire exposed rim

board fails.2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist.6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box

(0.135 inch x 3-1/2 inches) nails.9) Rim board needs to be sized for vertical and lateral loads.

Page 5: APA Rim in Fire Rated Assemblies D350

Form No. D350B ■ © 2015 APA – The Engineered Wood Association ■ www.apawood.org 5

Data File: APA Rim Board in Fire-Rated Assemblies

RB1RB3

RB4

RB5

RB6

RB2

Load

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Load Load

Load

LoadLoad LoadLoad

Load Load

Load Load

LoadLoad LoadLoad

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building OfficialsSame as

right-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

FIRE RESISTANCE RATED RIM BOARD ASSEMBLY RB4

This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101

DOUBLE WALL CONFIGURATION WITH LOAD TRANSFER BASE ASSEMBLY

Rim Board Thickness, in.

Rim Board Protection

Ceiling Membrane Req. for 1-hr

Ceiling Membrane Req. for 2-hr

Stud Size

Stud Size

A B C C D E

1

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

1-1/8

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4

1-1/4

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4

1-1/2

Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4

(1) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6

1-3/4

Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(1) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x61) Rim assembly for fire from either side of wall. “With load transfer” assumes load transfers to the adjacent rim board if the fire exposed rim

board fails.2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist.6) Use only fire rated gypsum wallboard. Type C may be substituted for Type X.7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box

(0.135 inch x 3-1/2 inches) nails.9) Rim board needs to be sized for vertical and lateral loads.

Page 6: APA Rim in Fire Rated Assemblies D350

Form No. D350B ■ © 2015 APA – The Engineered Wood Association ■ www.apawood.org 6

Data File: APA Rim Board in Fire-Rated Assemblies

FIRE RESISTANCE RATED RIM BOARD ASSEMBLY RB5

This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101

RB1RB3

RB4

RB5

RB6

RB2

Load

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Load Load

Load

LoadLoad LoadLoad

Load Load

Load Load

LoadLoad LoadLoad

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building OfficialsSame as

right-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

DOUBLE WALL CONFIGURATION WITH NO LOAD TRANSFER BASE ASSEMBLY

Rim Board Thickness, in.

Rim Board Protection

Ceiling Membrane Req.

for 1-hr

Ceiling Membrane Req.

for 2-hr

Stud Size

Stud Size

A B C C D E

1

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

1-1/8

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

1-1/4

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

1-1/2

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x6

1-3/4

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x6

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x61) Rim assembly for fire from either side of wall. “With no load transfer” assumes no load transfers to the adjacent rim board if the fire

exposed rim board fails.2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist.6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2 layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135

inch x 3-1/2 inches) nails.9) Rim board needs to be sized for vertical and lateral loads.

Page 7: APA Rim in Fire Rated Assemblies D350

Form No. D350B ■ © 2015 APA – The Engineered Wood Association ■ www.apawood.org 7

Data File: APA Rim Board in Fire-Rated Assemblies

FIRE RESISTANCE RATED RIM BOARD ASSEMBLY RB6

This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101

RB1RB3

RB4

RB5

RB6

RB2

Load

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Load Load

Load

LoadLoad LoadLoad

Load Load

Load Load

LoadLoad LoadLoad

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building OfficialsSame as

right-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum boards (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (D)

Rated wall assembly

Gypsum board (B)

Rim board (A)

Ceiling and wall ratingsas required by Building Officials

Ceiling membrane (C)

Stud (E)

Rated wall assembly

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Jan. 4, 2013Fire_Assembly_Bosie_Rim_Board_2013_v4.eps

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

Same asright-handside drawing

DOUBLE WALL CONFIGURATION WITH NO LOAD TRANSFER BASE ASSEMBLY

Rim Board Thickness, in.

Rim Board Protection

Ceiling Membrane Req. for 1-hr

Ceiling Membrane Req. for 2-hr

Stud Size

Stud Size

A B C C D E

1

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

1-1/8

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

1-1/4

Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4

1-1/2

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4

(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6

1-3/4

Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4

(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4

(1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4

(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6

(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x61) Rim assembly for fire from either side of wall. “With no load transfer” assumes no load transfers to the adjacent rim board if the fire

exposed rim board fails.2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist.6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box

(0.135 inch x 3-1/2 inches) nails.9) Rim board needs to be sized for vertical and lateral load.

Page 8: APA Rim in Fire Rated Assemblies D350

APA Rim Board® in Fire-Rated AssembliesWe have field representatives in many major U.S. cities and in Canada who can help answer questions involving APA trademarked products.

For additional assistance in specifying engineered wood products, contact us:

APA HEADQUARTERS7011 So. 19th St. ■ Tacoma, Washington 98466

(253) 565-6600 ■ Fax: (253) 565-7265

PRODUCT SUPPORT HELP DESK(253) 620-7400 ■ [email protected]

DISCLAIMERThe information contained herein is based on APA – The Engineered Wood Association’s continuing programs of laboratory testing, product research, and comprehensive field experi-ence. Neither APA, nor its members make any warranty, expressed or implied, or assume any legal liability or responsibility for the use, application of, and/or reference to opinions, findings, conclusions, or recommendations included in this publication. Consult your local jurisdiction or design professional to assure compliance with code, construction, and performance require-ments. Because APA has no control over quality of workmanship or the conditions under which engineered wood products are used, it cannot accept responsibility of product performance or designs as actually constructed.

Form No. D350B/Revised February 2015