appartus maintenance interval management
DESCRIPTION
Power Transformer Maintenance Interval based on monitored parametersTRANSCRIPT
![Page 1: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/1.jpg)
Copyright © SEL 2006
Apparatus MaintenanceInterval Management
Jeff Pope
Schweitzer Engineering Laboratories, Inc.
![Page 2: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/2.jpg)
Transformer Investment
![Page 3: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/3.jpg)
Aging Leads to Failure
![Page 4: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/4.jpg)
Aging Reduces Withstand Capability
Time, not to scale
Stress
Stress Encountered
Stress Withstand Capability
End of Life
Rate of Aging
![Page 5: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/5.jpg)
Customer Concerns
![Page 6: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/6.jpg)
Costly Replacement Power
![Page 7: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/7.jpg)
Spare Transformer Ready
![Page 8: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/8.jpg)
Relays Are Always There
Modern relays have processing and recording capabilities to keep track of power system assets
![Page 9: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/9.jpg)
Transformer Monitoring
Ambient TemperatureTop Oil TemperatureHot Spot TemperatureInsulation Aging FactorsThrough-Fault MagnitudeThrough-Fault DurationAccumulated Through Faults
![Page 10: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/10.jpg)
Timing Is Important
Time
oo
o
Device Operating Characteristic
xx
x
Sampling Interval
Val
ue
![Page 11: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/11.jpg)
Transformer Temperature Dependent Upon Loading and Ambient
0 5 10 15 20 250
50
100
150
Oil
Conductor Hot spot
Ambient
Hours
Deg
rees
Transformer Loading
0 5 10 15 20 250.5
1.0
1.5
Per
Uni
t
![Page 12: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/12.jpg)
Hot Spot CalculationTemp (°C)
Hottest Spot
Top Oil
Ambient
gθ
oθ
aθ
![Page 13: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/13.jpg)
FAA vs. Winding Hot Spot
Insulation Aging Acceleration Factor
0.00010.001
0.010.1
110
1001000
10000
50 70 90 110 130 150 170 190Winding Hot Spot Temperature
Agi
ng F
acto
r, FA
A
![Page 14: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/14.jpg)
Aging Jumps With Temperature
Time
Hot SpotTemperature
120 C
105 C
90 C
RelativeAging
1 X
135 C
16 X
2 X
4 X
8 X
32 X
64 X
128 X
256 X
Hot SpotTemperature
RelativeAging
![Page 15: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/15.jpg)
Thermal Element Reports Loss of Life
0 5 10 15 20 250
0.01
0.02
0.03
0.04
0.05
0.06
0.07Loss of Life (LOL)
Hours
Perc
enta
ge
LOL Alarm Point
Acceptable LOL Limit
Measured LOL
![Page 16: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/16.jpg)
Don’t Ignore Necessary Data
![Page 17: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/17.jpg)
Relay Thermal Monitor Alarms
Top oil temperatureWinding hot spot temperatureCooling system efficiencyInsulation aging acceleration factor (FAA)Daily loss of lifeTotal loss of life
![Page 18: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/18.jpg)
Thermal Profile ReportHourly and Daily Maximum
Ambient temperatureCalculated top oil temperatureMeasured top oil temperatureHottest spot temperaturePer-unit loadFAA
![Page 19: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/19.jpg)
Thermal Report
![Page 20: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/20.jpg)
Hourly Thermal Report
![Page 21: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/21.jpg)
Daily Thermal Report
![Page 22: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/22.jpg)
Thermal Overloads Are Not the Only Root Cause of Failure
![Page 23: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/23.jpg)
Surges No Longer #1 Failure Cause
![Page 24: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/24.jpg)
Close-In Fault
![Page 25: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/25.jpg)
#1 Cause of Transformer Failure
Relay
Through-Fault Current
![Page 26: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/26.jpg)
Can This Cause a Transformer Failure?
![Page 27: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/27.jpg)
Sudden Failure
![Page 28: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/28.jpg)
Through Faults ReduceTransformer Life
Time, not to scale
Stress
Stress Encountered
Stress Withstand Capability
End of Life
![Page 29: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/29.jpg)
Through-Fault Report
![Page 30: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/30.jpg)
Don’t Drive by the Rear View Mirror
![Page 31: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/31.jpg)
Information Overload
![Page 32: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/32.jpg)
Transformer Worth Protecting IsWorth Monitoring
![Page 33: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/33.jpg)
In-Service Transformer Monitoring
RTDSignals
4–20 mASignals
EIA-232 Modbus
Spread Spectrum Radio EIA-232
Modbus®
Substation PC
TransformerMonitor
PLC Communications Processor
Relay
![Page 34: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/34.jpg)
Simplified Transformer Monitoring
RTDSignals
Optical Fiber
RTDModule
Substation PC
CommunicationsProcessor
Relay
![Page 35: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/35.jpg)
Relay Thermal Monitor
Relay Identification Date: 2/2/05 Time: 11:35 Terminal IdentificationThermal Element Condition : NormalPer Unit Load Current : 123.45In-Service Cooling Stage : 1Ambient Temp. (deg. C) : 123Calculated Top-Oil Temp. (deg. C) : 123Measured Top-Oil Temp. (deg. C) : 123HS Wdg. Temp. (deg. C) : 123Max. FAA for last 24 hours : 123.4Present 24-Hour Avg FAA : 123.4Rate of LOL (%/day)(1) : 99.99Total Accumulated LOL (%)(2) : 99.99Time-Assert TLL (days) : 12345
Relay
Communications Processor
![Page 36: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/36.jpg)
Distribute Report Data Over WAN
Substation
SEL Relay
Control Room
Web ServerComputer With Browser
SEL Relay
SEL Relay
SEL RelayDatabase
SEL-2032 WANDMZ
![Page 37: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/37.jpg)
One-Line Webpage
![Page 38: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/38.jpg)
Thermal Monitor Webpage
![Page 39: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/39.jpg)
Asset Management Makes a Difference
Monitor and understand apparatus health
Perform fact-based risk assessment
Schedule periodic equipment exercises to avoid preventive maintenance
![Page 40: Appartus Maintenance Interval Management](https://reader038.vdocuments.net/reader038/viewer/2022103104/56d6bcfd1a28ab30168c4055/html5/thumbnails/40.jpg)
Asset Management Pays for Itself
Increased device and system productivity
Reduced expenses lower total ownership cost
Justified, defendable business planning based on actual power system data
Increased availability, reliability, revenue, and performance
Documented resolutions to NERC / FERC recommendations and insurance companies