appendices california energy commission 500-2013-134-appendixes

340
Energy Research and Development Division FINAL PROJECT REPORT DEVELOPMENT OF FAULT CURRENT CONTROLLER TECHNOLOGY Prototyping, Laboratory Testing, and Field Demonstration JUNE 2011 CEC-500-2013 -134-AP Prepared for: California Energy Commission Prepared by: University of California, Irvine Appendices

Upload: franco-moriconi

Post on 27-Jul-2015

210 views

Category:

Technology


0 download

TRANSCRIPT

Page 1: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

E n e r g y R e s e a r c h a n d D e v e l o p m e n t D i v i s i o n F I N A L P R O J E C T R E P O R T

DEVELOPMENT OF FAULT CURRENT CONTROLLER TECHNOLOGY

Prototyping, Laboratory Testing, and Field Demonstration

JUNE 2011 CEC-500-2013 -134-AP

Prepared for: California Energy Commission Prepared by: University of California, Irvine

Appendices

Page 2: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

PREPARED BY:

Primary Author(s): Keyue Smedley Alexander Abramovitz

University of California, Irvine

Contract Number: UC MR-064

Prepared for:

California Energy Commission

Jamie Patterson Contract Manager

Fernando Pina Office Manager Energy Systems Research Office

Laurie ten Hope Deputy Director ENERGY RESEARCH AND DEVELOPMENT DIVISION

Robert P. Oglesby Executive Director

DISCLAIMER

This report was prepared as the result of work sponsored by the California Energy Commission. It does not necessarily represent the views of the Energy Commission, its employees or the State of California. The Energy Commission, the State of California, its employees, contractors and subcontractors make no warranty, express or implied, and assume no legal liability for the information in this report; nor does any party represent that the uses of this information will not infringe upon privately owned rights. This report has not been approved or disapproved by the California Energy Commission nor has the California Energy Commission passed upon the accuracy or adequacy of the information in this report.

Page 3: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ACKNOWLEDGEMENTS

The University of California, Irvine gratefully acknowledges the financial support from the California Energy Commission, and the administrative support of the California Institute for Energy & Environment (University of California, Berkeley), which made this project possible. We sincerely thank our collaborators at Southern California Edison Co., Zenergy Power plc, the Electric Power Research Institute (EPRI) and Silicon Power Corporation for their technical expertise, teamwork and support which made this project successful. We also express our sincere appreciation to our knowledgeable and supportive Project Advisory Group for their valuable advice, which has been of critical importance in every phase of the project.

Contributing Authors: Franco Moriconi, Francisco De La Rosa, Alonso Rodriguez, Bert Nelson, Amandeep Singh, Nick Koshnick – Zenergy Power plc Ram Adapa – Electric Power Research Institute Christopher R. Clarke, Ed Kamiab, Syed Ahmed – Southern California Edison Co. Mahesh Gandhi, Swapna Bhat, Simon Bird – Silicon Power Corporation Project Advisory Group: Jamie Patterson – California Energy Commission Lloyd Cibulka – California Institute for Energy and Environment Bert Nelson, Alonso Rodriguez – Zenergy Power plc Ram Adapa – Electric Power Research Institute Alfonso Orozco, Katie Speirs – San Diego Gas & Electric Co. Bob Yinger, Christopher R. Clarke, Russ Neal, Anthony Johnson, Raj Vora, Ed Kamiab – Southern California Edison Co. Ron Sharp – Pacific Gas & Electric Co. Ed Muljadi – National Renewable Energy Laboratory Jim McHan – California Independent System Operator Ken Edwards – Bonneville Power Administration Ron Meyer – Santa Margarita Water District UC–Irvine Technical Contributors: Jun Wen Franco Maddaleno Liang Zhou In Wha Jeong Marco Tedde Sadigh Khoshkbar Arash Chaitanya Vartak Wensheng Song Pengju Sun ZhengSheng Wu Wenchao Xi Zhuo Zhao Fei Gu

i

fmoriconi
Highlight
fmoriconi
Highlight
Page 4: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

PREFACE

The California Energy Commission Energy Research and Development Division supports public interest energy research and development that will help improve the quality of life in California by bringing environmentally safe, affordable, and reliable energy services and products to the marketplace.

The Energy Research and Development Division conducts public interest research, development, and demonstration (RD&D) projects to benefit California.

The Energy Research and Development Division strives to conduct the most promising public interest energy research by partnering with RD&D entities, including individuals, businesses, utilities, and public or private research institutions.

Energy Research and Development Division funding efforts are focused on the following RD&D program areas:

• Buildings End-Use Energy Efficiency

• Energy Innovations Small Grants

• Energy-Related Environmental Research

• Energy Systems Integration

• Environmentally Preferred Advanced Generation

• Industrial/Agricultural/Water End-Use Energy Efficiency

• Renewable Energy Technologies

• Transportation

Development of Fault Current Controller Technology is the final report for the Development of Fault Current Controller Technology project (contract number UC MR-064) conducted by University of California, Irvine. The information from this project contributes to Energy Research and Development Energy Systems Integration Program.

For more information about the Energy Research and Development Division, please visit the Energy Commission’s website at www.energy.ca.gov/research/ or contact the Energy Commission at 916-327-1551.

ii

Page 5: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ABSTRACT

Fault current controller technology, also frequently referred to as fault current limiter technology, has been identified as a potentially viable solution for expanding the capacity of the transmission system and its service life to meet the growing demand for electricity by addressing the impacts of the resulting higher fault currents. This report discusses the development and field demonstration of distribution-class fault current controller technology. The project focused on prototyping, test plan development, laboratory testing, and field testing and demonstration, with a view toward potential further technical development and application of the technology in transmission-level systems.

A full-size three-phase distribution-level high-temperature superconducting fault current controller prototype was designed, built, and field-tested. The prototype fault current controller went through several iterations of extensive testing prior to field installation. It was then installed for field demonstration from March 2009 through October 2010.

The research team completed an initial design for a fault current controller based on solid-state (power electronics) technology. Initial analysis indicated that design changes to the prototype were necessary to improve its thermal management, the immunity of the control circuits to noise and interference and to address mechanical issues. The additional cost for these items was beyond the scope and budget of this project so this prototype design did not advance to the laboratory and field test stages during the project period.

This report provided a survey of fault current controller technology development status, including both the saturable-core and solid-state types represented by this project, followed by detailed design considerations, laboratory test procedures and results, field test installation and metering, and field demonstration outcomes. The report concluded with a summary of the lessons learned and recommendations for future fault current controller research efforts and commercial industry applications.

Keywords: Fault Current, Fault Current Controller, FCC, Fault Current Limiter, FCL, Short Circuit Current, Power System Protection, Saturable-core Reactor FCL, Solid-State FCL, High Temperature Superconductivity, HTS

Please use the following citation for this report:

Smedley, Keyue; Alexander Abramovitz. (University of California, Irvine). 2011. Development of Fault Current Controller Technology. California Energy Commission. Publication number: CEC-500-2013-134-AP.

iii

Page 6: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

TABLE OF CONTENTS

Acknowledgements ................................................................................................................................... i

PREFACE ................................................................................................................................................... ii

ABSTRACT .............................................................................................................................................. iii

TABLE OF CONTENTS ......................................................................................................................... iv

APPENDIX A: Zenergy Power HTS FCL Test Plan ........................................................................ A-1

APPENDIX B: Zenergy Power HTS FCL Laboratory Test Report ............................................... B-1

APPENDIX C: Zenergy Power HTS FCL Dielectric and HV Test ............................................... C-1

APPENDIX D: Zenergy Power HTS FCL Normal State Temperature Rise Test ..................... D-1

APPENDIX E: Zenergy Power HTS FCL Short Circuit Test ......................................................... E-1

APPENDIX F: Zenergy Power HTS FCL High Voltage Field Test .............................................. F-1

APPENDIX G: Zenergy Power HTS FCL Operation Manual ...................................................... G-1

APPENDIX H: Zenergy Power HTS FCL Cryostat Evacuation and Moisture Removal Procedure ............................................................................................................................................... H-1

APPENDIX I: Zenergy Power HTS FCL Liquid Nitrogen Fill Procedure .................................. .I-1

APPENDIX J: Silicon Power SSCL Test Plan ................................................................................... J-1

iv

Page 7: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

A‐1

APPENDIX A: Zenergy Power HTS FCL Test Plan

Page 8: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 1 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Engineering Specifications

Reporting Center (full name and address): Zenergy Power Inc. 379 Oyster Point Blvd., Suite 1 South San Francisco, CA USA 94080-1961 Tel.: +1-650-615-5700

Responsible Person:

Francisco De La Rosa

Project Name: High Temperature Superconductor Fault Current Limiter

Document Title: Test Protocol for FCL 15kV, 1.2kA, 3 Phase

Document #: ZP/ES-2008-05 Reg: # Page 1

Date of issue: 05/05/08 Classification:

Confidential

No. of pages: 33

Client(s): Zenergy Power

Author(s): F. De La Rosa Approved: F. Moriconi Order No.:

Distribution: Franco Moriconi, Bert Nelson, Woody Gibson, Robert Lombaerde, Amandeep Singh, William Schram, Frank Darmann

Distribution page 1:

Keywords: Fault current limiter, high temperature superconducting, air-core reactors, discharge current-limiting reactors, dry-type air-core reactors, dry-type reactors, saturable reactors, filter reactors, reactors, series–connected reactors, series reactor applications, FCL reactor test

Summary: General tests to apply to the Fault Current Limiter according to ZENERGY Power internal procedures for power current characterization and transient faults as well as recommended tests by IEEE relevant standard for Series Connected Reactors and dry-type transformers are described in this document.

fmoriconi
Highlight
fmoriconi
Highlight
Page 9: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 2 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Contents Page

1. SUMMARY OF TESTS TO BE PERFORMED ON FCL...........................4

2. GENERAL ................................................................................................4

3. SCOPE .....................................................................................................5

4. APPLICABILITY.......................................................................................5

5. APPLICABLE DOCUMENTATION ..........................................................5

6. ACRONYMS AND DEFINITIONS ............................................................5 6.1 ACRONYMS......................................................................................................................5 6.2 DEFINITIONS ....................................................................................................................5

7. SERVICE CONDITIONS...........................................................................7 7.1 AMBIENT TEMPERATURE...................................................................................................7 7.2 ENVIRONMENTAL AND APPLICATION RELATED SERVICE CONDITIONS ....................................7

8. ZENERGY PRE-CONNECTION TESTS ..................................................7 8.1 STEADY STATE TEST.........................................................................................................8 8.2 FAULT CURRENT CHARACTERIZATION AND TRANSIENT.......................................................8

9. TESTING PLAN ACCORDING TO IEEE C57.16-1996............................9 9.1 RESISTANCE MEASUREMENTS.........................................................................................11 9.2 IMPEDANCE MEASUREMENTS ..........................................................................................11 9.3 LOSS MEASUREMENTS....................................................................................................12

9.3.1 Loss tests on dry-type series reactors.................................................................................. 13 9.3.2 Temperature of the winding ................................................................................................ 13 9.3.3 Per-Unit values ................................................................................................................... 13 9.3.4 Impedance-Loss and impedance-voltage test of a three-phase reactor .............................. 14 9.3.5 Procedure ............................................................................................................................ 14 9.3.6 Line currents ....................................................................................................................... 14 9.3.7 Stray-Loss component ......................................................................................................... 14 9.3.8 Temperature correction....................................................................................................... 14 9.3.9 Bridge method ..................................................................................................................... 14 9.3.10 Temperature correction for losses.................................................................................. 14

9.4 TEMPERATURE RISE ......................................................................................................15 9.4.1 Loading conditions. ............................................................................................................. 15 9.4.2 Temperature rise – General. ............................................................................................... 15 9.4.3 Altitude effects ..................................................................................................................... 16 9.4.4 Temperature effects ............................................................................................................. 16

9.5 APPLIED VOLTAGE .........................................................................................................16 9.6 RADIO INFLUENCE VOLTAGE (RIV) TEST ..........................................................................16 9.7 TURN-TO-TURN OVERVOLTAGE TEST ...............................................................................16 9.8 IMPULSE TESTING...........................................................................................................18

9.8.1 Reduced full-wave test......................................................................................................... 19 9.9 CHOPPED-WAVE TEST ...................................................................................................19

9.9.1 Wave polarity ...................................................................................................................... 19 9.9.2 Wave-Shape control ............................................................................................................ 20 9.9.3 Impulse oscillograms........................................................................................................... 20 9.9.4 Connections for impulse tests.............................................................................................. 20 9.9.5 Terminals not being tested .................................................................................................. 20 9.9.6 Detection of failure during impulse test .............................................................................. 21 9.9.7 Ground current oscillograms .............................................................................................. 21 9.9.8 Voltage oscillograms........................................................................................................... 21

Page 10: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 3 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.10 AUDIBLE SOUND-LEVEL TEST ..........................................................................................24 9.10.1 Instrumentation............................................................................................................... 24 9.10.2 Test conditions................................................................................................................ 24 9.10.3 Microphone positions ..................................................................................................... 26 9.10.4 Sound-Level measurement.............................................................................................. 26 9.10.5 Calculation of average sound level ................................................................................ 27

10. PERFORMANCE CRITERIA ..............................................................28

11. ADDITIONAL IEEE C57.12.01-2005 RECOMMENDED TESTS. .......29 11.1 DIELECTRIC INSULATION.................................................................................................29 11.2 PARTIAL DISCHARGE......................................................................................................30 11.3 MISCELLANEOUS DRY-TYPE TRANSFORMER TESTS...........................................................31

12. CONCLUSIONS..................................................................................31

13. LIST OF TABLES AND FIGURES......................................................32

LIST OF REVISIONS.....................................................................................33

Page 11: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 4 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

1. Summary of Tests to be performed on FCL a. “Pre-connection Tests” consisting on steady state and fault current

characterization under nominal voltage and load current b. Testing according to IEEE C57.16-1996 and IEEE C57.12.01-2005 These pertinent tests are summarized in table 1

# TEST Location Ref. Observations 1 Pre-connection Powertech 8.1-8.2 2 Winding Resistance T&R 9.1 3 Impedance T&R 9.2 4 Total loss T&R 9.3 5

Temperature rise T&R 9.4 Must be carried out at rated current. Reduced

voltage is allowed. 6

Applied voltage T&R 9.5 @34kV according to

coil manufacturer and IEEE C57.12.01

7 Radio influence voltage(RIV) - 9.6 Not applicable for 15kV class

8 Turn-to-turn Powertech 9.7 9 Lightning impulse @110 kV Powertech 9.8 10 Chopped-wave impulse Powertech 9.9 11 Audible sound T&R or

Shandin 9.10

12 Insulation power factor T&R 11.3 13 Insulation resistance T&R 11.1 14 Partial Discharge T&R 11.2

Table 1: ZENERGY FCL Test Summary

2. General This report presents the test protocol for the ZENERGY Power High Temperature Superconductor Fault Current Limiter. The protocol is largely based on the IEEE C57.16-1996 and IEEE C57.12.01-2005 relevant standards. These address testing procedures for Dry-Type Series-Connected Reactors and Dry-type Distribution and Power Transformers including those with Solid Cast and/or Resin-Encapsulated Windings, respectively. These reactors are connected in the power systems to control power flow under steady state conditions and/or limit fault current under short circuit conditions.

The tests include Impedance measurements, total loss measurements, applied voltage, radio Influence voltage (RIV), turn-to-turn, lightning impulse, chopped-wave impulse test, audible noise, dielectric

Page 12: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 5 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

insulation, partial discharge and average sound level, among other tests.

3. Scope The scope of this work is to portray the test procedures to which the ZENERGY Power HTS Fault Current Limiter shall be submitted previous to the ZENERGY Power short-circuit testing protocol.

4. Applicability High temperature superconducting ZENERGY Power Fault Current Limiter.

5. Applicable documentation • IEEE Std C57.16-1996, IEEE Standard Requirements, Terminology,

and Test Code for Dry-Type Air-Core Series-Connected Reactors • IEEE Std C57.12.01-2005, IEEE Standard General Requirements for

Dry-Type Distribution and Power Transformers Including Those with Solid Cast and/or Resin-Encapsulated Windings

• NEMA -107-1987, Methods of Measurements of Radio Influence Voltage (RIV) of High Voltage Apparatus

6. Acronyms and definitions

6.1 Acronyms FCL Fault Current Limiter HTS High Temperature Superconductor TBD To Be Determined

6.2 Definitions Current Limiting Reactor: A reactor connected in series with the phase conductors for limiting the current that can flow in a circuit under short circuit conditions, or under other operating conditions, such as capacitor switching, motor starting, synchronizing, arc stabilization, etc. Rating of a Series Reactor: The current that a series reactor can carry at its specified reactance together with any other defining characteristics, such as system voltage, Basic Insulation Level (BIL), short circuit current (thermal and mechanical) duty, and frequency. Rated current: The root mean square (rms) power frequency current in amperes that can be carried for the duty specified, at rated frequency without causing further measurable increase in temperature rise under prescribed conditions of test, and within limitations of established standards. Short time duty: A requirement of service that requires operation at substantially constant current for a short and definitely specified time. Nominal voltage: A line to line voltage assigned to a system or circuit of a given voltage class for the purpose of convenient designation.

Page 13: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 6 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Rated system voltage: The voltage of a series reactor to which operational and performance characteristics are referred. It corresponds to the nominal line-to-line or phase-to-phase system voltage of the circuit in which the reactor is intended to be used. Effective resistance (or ac resistance): The value of resistance of a series reactor obtained by dividing the total losses by the current squared at power frequency. Losses: Those losses are due to current flow. They include: ♦ The resistance and the eddy-current loss in the winding due to load

current

♦ Losses caused by circulating current in parallel windings

♦ Stray losses caused by magnetic flux in other metallic parts of the reactor support structure, and in the reactor enclosure when the support structure and the enclosure are supplied as an integral part of the reactor insulation.

Impedance: The phasor sum of the reactance and resistance, expressed in ohms. Impedance voltage drop: The product of the rated ohms’ impedance and the rated current of a series reactor. Per unit reactance: On a rated current base, a dimensionless quantity obtained by referencing the magnitude of the reactance to the rated system line-to-neutral voltage divided by the rated current of the reactor. It can also be defined on an arbitrary megavoltampere (MVA) base. Rated inductance: The total installed inductance at a specified frequency. It may consist of mutual as well as self inductance components. Rated reactance: The product of a rated inductance and rated angular frequency that provides the required reduction in fault current or other desired modification to power circuit characteristics. Reactance: The product of the inductance in henries and the angular frequency of the system. Reactance voltage drop: The component of voltage drop in quadrature with the current. Resistance voltage drop: the component of voltage drop in phase with the current. Ambient sound-pressure level: Is the sound-pressure level measured in the test facility without the reactor energized. Sound-Pressure level, in decibels: is 20 times the logarithm to the base 10 of the ratio of the measured sound pressure to a reference pressure of 20 Pa. Sound-Power level, in decibels: is 10 times the logarithm to the base 10 of the ratio of the emitted sound power to a reference power of 10-12 W. Semireverberant facility: is a room with a solid floor and an undetermined amount of sound-absorbing materials on the walls and ceiling.

Page 14: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 7 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

7. Service Conditions

7.1 Ambient temperature This is the temperature of the air surrounding the reactor. For the purposes of IEEE Std C57.16-1996, it is assumed that the temperature of the cooling air (ambient temperature) does not exceed 40 o C and the average temperature of the cooling air for any 24 hour period does not exceed 30 o C.

7.2 Environmental and application related service conditions Reactor for outdoor application must be designed for conditions such as rain, (ice), snow, fog and ultraviolet (UV) ray exposure. The purchaser should attempt to quantify or qualify environmental conditions, including type and level of pollution. The reactor should also be designed to withstand, without damage or loss of service life, mechanical loads such as electromagnetic forces during short-circuit, wind loading, and stresses caused by thermal expansion and contraction due to ambient temperature and current loading variations. Wind speed data, including gust factors, should be specified by the purchaser.

8. ZENERGY Pre-Connection Tests ZENERGY shall apply a number of pre-connection tests including steady state (applied voltage and load current) and Fault Current Characterization, as depicted in tables 2 and 3.

Page 15: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 8 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.1 Steady state test

Secondary Voltage of

main transformer

bank

Steady state

current through

FCL required

Load bank impedance

on load side of FCL

Source limiting

impedance

Time duration

of steady state

current

Cooling time

kV A Ω Ω s

min

13.1 200 TBD As required 100 <20

13.1 500 TBD As required 100 <20

13.1 750 TBD As required 100 <20

13.1 1200 TBD As required 100 max 20

Quantities to measure: • Line current in the three phases • Voltage drop across the FCL • AC Coil temperature

Quantities to derive from measurements: • FCL impedance • Harmonics

Table 2: ZENERGY Pre-Connection Tests

8.2 Fault Current Characterization and Transient

Page 16: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 9 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

FCL Status

in circuit

Secondary voltage of

main transformer (line to line)

Steady state line current before fault

introduced

Load bank impedance

required

Time duration

of steady state

current required

Steady state fault

current on load

side

Source limiting

impedance required (nominal)

X/R

Time required for fault current to flow

Time required

for steady state

current to flow after

fault

kVrms A(rms) Ω Cycles kA (rms) mΩ cycles cycles

Out/in 13.1 1200 17Δ 10 5 As needed 10-20**

30 20

Out/in 13.1 1200 17Δ 10 10 As needed 10-20**

30 20

Out/in 13.1 1200 17Δ 10 15 As needed 10-20**

30 20

Out/in 13.1 1200 17Δ 10 20* As needed TBD ***

TBD ****

20

• 3-phase fault. Single or 3 phase Point On Wave is possible • 25 kA breaker available, but limited to 20 kA based on source side

resistors when tested at Powertech • ** Unmodified X/R of our source i.e. without addition of series resistors

is approximately 40 • ***X/R must be adjusted in order not to exceed 20 kA symmetric fault • ****Must not exceed thermal rating (will have to be <than 30 cycles)

Table 3. ZENERGY Pre-Connection Tests

9. Testing Plan according to IEEE C57.16-1996 • The recommended tests adapted from this relevant standard are

described in tables 4 through 5 below.

Page 17: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 10 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table 4: Routine, design and other test for dry-type series reactors

Routine tests A routine test is a test made on each and every unit of a specific design and is primarily a verification of quality. Routine tests shall be made on all series reactors in accordance with the requirements of Table 4. Design tests A design test (also referred to as a type test) is a test carried out on a single unit of a specific design and is primarily a verification of the ability to meet in-service application requirements. Design tests shall be made in accordance with the requirements of Table 4. Other tests A test designated as “other” is a test performed on one or all units of a specific design if requested by the purchaser. It is usually requested to demonstrate conformance to special application requirements as opposed to the more general application requirements covered by design tests. When specified (as individual tests), “other” special tests, as listed in Table 4, shall be made on series reactors.

Page 18: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 11 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

For the Zenergy Power FCL 15kV class we shall apply the following tests:

o Resistance measurements o Impedance measurements o Total loss measurements o Applied voltage test o Turn-to-turn test o Lightning impulse test o Chopped-wave impulse test o Audible sound test and only if required by customer o Radio Influence Voltage (RIV) test

9.1 Resistance measurements Resistance measurements are of fundamental importance for three purposes: a) For the calculation of the conductor I2R loss. b) For the calculation of winding temperatures at the end of a temperature rise test. c) For a quality check among units of the same rating. Cold winding resistance measurements are normally converted to a standard reference temperature equal to the rated average winding temperature rise plus 20 °C. In addition, it may be necessary to convert the resistance measurements to the temperature at which the impedance and loss measurements were made. The conversions are accomplished by the following formula:

)()(

km

ksms T

RR++

θθ (1)

where Rs is the resistance at the desired temperature Θs Rm is the measured resistance at temperature Θm Θs is the desired reference temperature, in degrees Celsius Θm is temperature at which resistance was measured, in degrees Celsius, and Tk is 234.5 (Copper) and 225 (Aluminum) Cold resistance measurements shall not be taken in less than 4 hours after the reactor has been moved from a location where ambient temperature differs by more that 5 o C, but less than 10 o C.

9.2 Impedance measurements Resistance and reactance components of the impedance voltage are determined by the use of the following equations:

IPE z

r = (2)

22

rzx EEE −= (3)

Page 19: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 12 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

where Er is the resistive voltage, Ex is the reactance voltage, quadratic component, Ez is the impedance voltage of winding carrying current, Pz is the watts quantity measured in the impedance test of winding carrying current, and I is the current in amperes on that winding where the voltage is applied.

9.3 Loss measurements Since many series reactors (especially high kilovoltampere units) operate at low power factors, small variations in frequency, deviations from the true sine wave in applied voltage, errors in measuring components, and electromagnetic interference may introduce significant errors in loss measurements. Proper test conditions and precision components specifically designed for low power factor measurements, are essential for an accurate determination of reactor losses. a) Impedance bridges are frequently used to measure losses and are generally more accurate than traditional wattmeter measurements. While many configurations of impedance bridge networks are possible, the choice of a particular network shall be determined by the measurement problem at hand and the testing facilities available. It should be noted that modern electronic-based wattmeters can be highly accurate. b) If wattmeters are used to measure losses, connections to the reactor will be the same as those shown in Figures 1 and 2. The voltage is adjusted to the desired value at rated frequency, and simultaneous readings of amperes, volts, watts, and frequency are taken. For low power factors, corrections shall be considered for phase angle and losses in the instruments and instrument transformers.

Fig.1: Single-Phase reactor connections for impedance-loss and impedance-voltage tests (instrument transformers to be added when necessary)

Page 20: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 13 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Fig. 2: Three phase reactor connections for impedance-loss and impedance-voltage tests (instrument transformers to be added when necessary)

9.3.1 Loss tests on dry-type series reactors In these reactors, the losses consist of the I2R (dc resistance) losses in the conductor, the eddy losses in the conductor, and any metallic framework of the clamping structure. Since the losses in these reactors are proportional to I2, the losses can be measured at 100% voltage, or at a reduced voltage. In either case, precision of measurement shall be demonstrated to the purchaser’s satisfaction. The losses are to be corrected to rated current and a reference temperature. In some cases, the actual average winding rise as determined by the temperature rise test plus 20 °C may be used, which is an attempt to reflect actual in-service losses and actual site average ambient temperature.

9.3.2 Temperature of the winding The temperature of the winding shall be taken immediately before and after the impedance measurements in a manner similar to that described for resistance measurements above. The average shall be taken as the true temperature. I2R loss of the winding. The I2R loss of the winding is calculated from the ohmic resistance measurements (corrected to the temperature at which the impedance test was made) and the currents that were used in the impedance measurement. These I2R losses subtracted from the impedance watts give the stray losses of the winding. When reactor windings are enclosed in shielded housings or tanks, part or all of which are magnetic material, part of the stray loss must be considered with the winding I2R when correcting losses from measured temperature to other temperatures. Since this varies with the proportions of the reactor design and type of shield, it will have to be approximated for each design but can be checked by measurement of loss at the start and finish of the temperature run.

9.3.3 Per-Unit values Per-Unit values of the resistance, reactance, and impedance voltage are obtained by dividing the corresponding voltages by the rated

Page 21: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 14 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

voltage. Percentage values are obtained by multiplying per-unit values by 100.

9.3.4 Impedance-Loss and impedance-voltage test of a three-phase reactor

Balanced three-phase voltages of rated frequency and suitable magnitude are applied to the terminals to force rated current to circulate (see Figure 2).

9.3.5 Procedure The procedure is similar to that described for single-phase units, except that all connection and measurements are three phase instead of single phase.

9.3.6 Line currents If the three line currents cannot be balanced, their average rms values should correspond to the desired value.

9.3.7 Stray-Loss component The stray-loss component of the impedance watts is obtained by subtracting from the latter the I2R losses of the reactor.

9.3.8 Temperature correction Temperature correction shall be made as described above.

9.3.9 Bridge method Bridge methods are preferred as they are generally more accurate than the wattmeter method. However, it should be noted that modern electronic-based wattmeters can be highly accurate.

9.3.10 Temperature correction for losses The I2R component of the impedance loss increases with the temperature, the stray-loss component diminishes with the temperature, and therefore, when it is desired to convert the impedance losses from one temperature to another, the two components of the impedance loss are converted separately. Thus,

''

θθ

++

=k

krr T

TPP - - - - - - - - - - - - - - - - - - - (4)

θθ

++

=k

kss T

TPP '' '

'θθ

++

=k

krr T

TPP - - - - - - - - - - - - - - - - - - - (5)

where

Page 22: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 15 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Tk is 234.5 for copper, and Tk is 225 for aluminum Pr and Ps are I2R and stray losses, respectively, at the specified temperature q. P´r and P´s are measured I2R and stray losses at temperature q´. q and q´ are in degrees Celsius.

9.4 Temperature Rise

9.4.1 Loading conditions. Temperature rise test shall be done under load conditions that impose losses as close as possible to those obtained at rated frequency with rated current in the windings. If laboratory power is not sufficient or power control adjustment is not enough to carry out a test at rated current, testing at current levels down to 90% of rated is permissible. In the case of reactors to be installed in a side-by-side configuration, testing of single unit is representative. In case of reactors mounted in three phase configuration, they should be tested in the installed configuration with a three-phase current supply unless otherwise agreed upon between purchaser and manufacturer. Reactors should be completely assembled. The ambient temperature shall be taken as that of the surrounding air, which should be preferably not less than 10 o C, not more than 40 o C.

9.4.2 Temperature rise – General. Temperature rise of metal parts, other than the winding conductor in contact with, or adjacent to insulation, or of other metal parts, shall be determined by thermocouple or by thermometer when required. Caution should be taken with the use of thermocouples to measure surface temperature due to parts being at high voltage. The temperature rise of the winding should be determined by the resistance method, or by a thermometer when so specified. The test current shall be adjusted to produce the total fundamental plus harmonic winding losses as described in Annex A in the IEEE Std C57.16-1996. Also, aspects related to minimization of errors temperature rise of metal parts should be taken into consideration as described in the cited standard. The ultimate temperature rise is considered to be reached when the temperature rise becomes constant. i.e., when temperatures measured by thermometers or thermocouples on the winding do not vary more than 2.5% or 1o C, whichever is greater, during a period of two consecutive hours and the duration of the heat run is at least five thermal time constants.

Page 23: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 16 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.4.3 Altitude effects When a reactor that is tested at an altitude less than 1000 m (3300 ft) is to be operated at an altitude in excess of 1000 m, it shall be assumed that the observed temperature rise will increase in accordance with the following relation: Increase in temperature rise at altitude A m(ft) =

( ) FAAriseObservedftmAAltitudeincreaseTemp ⎟⎟

⎞⎜⎜⎝

⎛−= 1)_(] [__@_

0 - - (6)

where A0 is 1000 m (3300 ft), and F is an empirical factor equal to 0.05. NOTE — The “observed rise” in the foregoing equation is winding rise over the ambient temperature.

9.4.4 Temperature effects When the ambient air temperature is other than 30 °C, a correction shall be applied to the temperature rise of the winding by multiplying it by the correction factor C, which is given by the ratio

θ++

=k

k

TTC 30 - - - - - - - - - - - - - - - - - - - (7)

where Tk is 234.5 for copper, Tk is 225 for aluminum, and θ is the ambient air temperature, in degrees Celsius

9.5 Applied Voltage An applied voltage test shall be made on the reactor’s supporting structure, including insulators. For this FCL unit that uses cast resin coils the test value for the applied voltage test is 34 kV.

9.6 Radio influence voltage (RIV) test According to IEEE STD. C57.16, RIV test is only required for series reactors operating at system voltages 230 kV and higher and is carried out at power frequency according to NEMA 107-1987.

9.7 Turn-to-turn overvoltage test The turn-to-turn test shall consist of a series of high frequency, exponentially decaying exponential voltages between the terminals of each winding, as per IEEE Std C57.16-1996 application procedure. The turn-to-turn test is performed by repeatedly charging a capacitor and discharging it, through sphere gaps, into the reactor windings. The type of overvoltage that the reactor is subjected to is more representative of a switching overvoltage, with an exponentially

Page 24: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 17 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

decaying sinusoidal waveshape. The test duration is for 1 min and the initial crest value of each discharge is to be 2 times the rms value as specified in Table 5. The ringing frequency is a function of the coil inductance and charging capacitor, and is typically on the order of 100 kHz. The test shall consist of not less than 7200 overvoltages of the required magnitude. Primary verification of winding insulation integrity should be based on oscillographic methods. A surge oscilloscope and camera are used to record the last discharge superimposed on a reduced voltage discharge. A change in period or rate of envelope decay, between the reduced and full waves, would indicate a change in coil impedance and thus an inter-turn failure. The crest test voltage level is 2 times the rms voltages listed in column 3 or 4 of Table 5. Secondary verification of insulation integrity is by observation. A failure can be detected by noise, smoke, or spark discharge in the reactor windings. Figure 3 shows the schematic of the test circuit and representative oscillograms of applied test voltage. The use of oscillograms for failure detection is based on change in ringing frequency and a change in rate of envelope decay (damping).

Page 25: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 18 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

f

Fig. 3 – Recommended circuit for turn-to-turn testing

9.8 Impulse testing For dry-type air-core series reactors with nominal system voltages greater than 34.5 kV unless otherwise specified, a lightning impulse test shall be made on each terminal of the reactor (one at a time) by applying a reduced wave and tree full waves, all of positive polarity with crest voltage in accordance with the assigned BIL as specified in table 5 subject to a tolerance of ±3%. Impulse testing is performed using a standard waveform that reaches peak value in 1.2 μs and decreases to half value in 50 μs. The tolerance on time to crest should normally be ±30%. For convenience in measurement, the time to crest may be considered as 1.67 times the time interval measured on the front of the wave from 30% to 90% of the crest value. The tolerance on time to one-half of crest shall normally be ±20%. However, as a practical matter, a) The time to crest shall not exceed 2.5 ms except for windings of large impulse capacitance (low-voltage, high kVA and some high-voltage, high kVA windings). To demonstrate that the large capacitance of the winding causes the long front, the impulse generator series resistance may be reduced,

Page 26: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 19 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

which should cause superimposed oscillations. Only the inherent generator and lead inductances should be in the circuit. b) The impedance of some windings may be so low that the desired time to the 50% voltage point on the tail of the wave cannot be obtained with available equipment. In such cases, the manufacturer should advise the purchaser at proposal stage of the wave shape limitation. Based on agreement, waves of shorter duration are acceptable. The virtual time zero can be determined by locating points on the front of the wave at which the voltage is, respectively, 30% and 90% of the crest value and then drawing a straight line through these points. The intersection of this line with the time axis (zero-voltage line) is the virtual time zero. If there are oscillations on the front of the waves, the 30% and 90% points shall be determined from the average, smooth wave front sketched in through the oscillations. The magnitude of the oscillations preferably should not exceed 10% of the applied voltage. When there are high-frequency oscillations on the crest of the wave, the crest value shall be determined from a smooth wave sketched through the oscillations. If the period of these oscillations is 2 µs or more, the actual crest value shall be used.

9.8.1 Reduced full-wave test This wave is the same as a full wave except that the crest value shall be between 50% and 70% of the full-wave value given in Table 5.

9.9 Chopped-Wave test When specified, this wave shall be the same as a full wave except that the crest value shall be at the required higher level given in Table 5 and the voltage wave shall be chopped at or after the required minimum time to sparkover. In general, the gap or other equivalent chopping device shall be located as close as possible to the terminals and the impedance shall be limited to that of the necessary leads to the gap; however, it shall be permissible for the manufacturer to add resistance to limit the amount of overswing to the opposite polarity to 50% of the amplitude of the chopped wave. The value of resistance added should not increase the time to chop of the chopped wave. Impulse tests are generally applied in the following order: one reduced full wave, one full wave, one reduced chopped wave, two chopped waves, and two full waves (preferably within 10 minutes about the last chopped wave).

9.9.1 Wave polarity For dry-type series reactors, the test wave shall be positive polarity unless otherwise specified.

Page 27: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 20 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.9.2 Wave-Shape control The maximum half value time t2 of an impulse wave tail can be derived from the resonance frequency of the impulse generator capacitance (Cg) with the test object reactance (Lt).

gtCLt32π

= - - - - - - - - - - - - - - - - - - - (8)

This is a theoretical value applying to an undamped oscillation with an opposite polarity peak of 100%. Various amounts of circuit damping will reduce this value accordingly. For instance, with a limitation of 50% for the opposite polarity peak, t2 is

gtCLt 5.02 ≈ - - - - - - - - - - - - - - - - - - - (9)

Equations (8) and (9) are based on the standard impulse test circuit. Values of t2 < 50 µs are typical for low inductance reactors. Values of t2 close to or exceeding those calculated using equations (8) and (9) can be achieved with the use of an inductor in parallel with the series (front) resistor of the impulse circuit with compromises generally required between wave duration, opposite polarity peak, wave front time, and peak overshoot. The manufacturer may also elect to test a low-impedance winding by inserting a resistor of not more than 500 W in the grounded end of the winding. Although this will improve the impulse wave shape, the largest portion of the test voltage will be across the resistor and not across the test coil windings. Therefore, a shorter impulse wave tail is preferable to the insertion of a series resistor between the test object and ground.

9.9.3 Impulse oscillograms All impulses applied to a reactor shall be recorded by a cathode-ray oscillograph or by suitable digital transient recorder. These oscillograms shall include voltage and ground-current oscillograms for all full-wave and reduced full-wave impulses. Sweep times should be on the order of 2 µs to 5 µs for chopped-wave tests, 50 µs to 100 µs for full-wave tests, and 100 µs to 600 µs for ground-current measurements. All voltage and current oscillograms should be included in the test report, including all relevant calibration shots.

9.9.4 Connections for impulse tests In general, the tests shall be applied to each terminal one at a time.

9.9.5 Terminals not being tested One terminal of the winding under test shall be grounded through a low-resistance shunt so that ground current measurements can be made. The resistance of the current shunt should typically be less than 0.1% of the reactance of the test object (reactor) at 5 kHz. The 5 kHz reference frequency is based on the half period of a standard lightning impulse being on the order of 100 µs.

Page 28: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 21 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.9.6 Detection of failure during impulse test Because of the nature of impulse test failures, one of the most important matters is the detection of such failures. There are a number of indications of insulation failure.

9.9.7 Ground current oscillograms In this method of failure detection, the impulse current in the grounded end of the winding tested is measured by means of a cathode-ray oscillograph or by suitable digital transient recorder connected across a suitable shunt inserted between the grounded end of the winding and ground. Any differences in the wave shape between the reduced full wave and final full wave detected by comparison of the two current oscillograms may be indications of failure or deviations due to non injurious causes. A complete investigation is required and should include an evaluation by means of a new reduced-wave and full-wave test. Examples of probable causes of different wave shapes are operation of protective devices or conditions in the test circuit external to the series reactor. The ground current method of detection is not suitable for use with chopped-wave tests. It is difficult to shield the measuring circuit completely from the influence of the high voltage of the surge generator, and some stray potentials are frequently picked up that may produce an erratic record for the first 1 µs or 2 µs. Such influences, if they occur at the start of the current wave (and, to a lesser extent, at the start of the voltage wave), should be disregarded. Where the impedance of the series reactor tested is high with respect to its series capacitance, current measurements may be difficult to make because of the small impulse current. In order to reduce the initial large capacitance current and maintain a reasonable amplitude for the remainder of the wave, a capacitor may be included in the current measuring circuit. The capacitor should not be larger than required to achieve this result.

9.9.8 Voltage oscillograms Any unexplained differences between the reduced full wave and final full wave detected by comparison of the two voltage oscillograms, or any such differences observed by comparing the chopped waves to each other and to the full-wave up to the time of flashover, are indications of failure. Deviations may be caused by conditions in the test circuit external to the series reactor and should be fully investigated and confirmed by a new reduced-wave and full-wave test. Other techniques that can be employed to investigate a suspected problem during the impulse test are the application of additional reduced waves and the subsequent comparison of these oscillograms with the original, the application of a series of full-wave impulses and an examination of the oscillograms for evidence of progressive change and, if a digitally based test system is being employed, the transfer function can be utilized.

Page 29: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 22 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table 5: Insulation test levels for dry-type air-core series reactors

Page 30: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 23 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table 5. Insulation test levels for dry-type air-core series reactors (Continued)

Page 31: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 24 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.10 Audible sound-level test The measurement of sound level on dry-type series reactors is an optional test. If such a test is to be performed, it should be carried out as far as applicable as described in IEEE Std C57.12.90-1993. Audible sound from dry-type air-core reactors originates principally in the reactor winding from which it is radiated as airborne sound. The frequency spectrum of the audible sound for a 60 Hz power system consists primarily of a tone at 120 Hz. The A-weighted measurement or sound-pressure level shall be used to determine the average sound level performance of a dry-type air-core series reactor. The procedures specified for measuring reactor sound-pressure levels are intended to be applicable to reactors being tested indoors or outdoors at the factory or to those that have been installed in the field.

9.10.1 Instrumentation Sound-Pressure level measurements shall be made with instrumentation that meets the requirements of ANSI S1.4-1983 for type 2 meters. A suitable wind screen shall be used when the air velocity due to winds causes the readings to be in error. Sound-Measuring instrumentation shall be calibrated before and after each measurement session. Further, it should be demonstrated prior to the measurement that the magnetic field of the reactor does not affect the rating of the sound level meter. Should the calibration change by more than 1 dB due to the magnetic field, the measurements shall be declared invalid.

9.10.2 Test conditions Measurements should be made in an environment having an ambient sound-pressure level at least 5 dB below the combined sound-pressure level. When the ambient sound-pressure level is 5 dB or more below the combined level of reactor and ambient, the corrections shown in Table 6 shall be applied to the combined reactor and ambient sound pressure level to obtain the reactor sound-pressure level. When the difference between the reactor sound-pressure level and the ambient sound-pressure level is less than 5 dB, and it is only desired to know the sound-pressure level that the reactor does not exceed, a correction of -1.6 dB may be used.

Page 32: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 25 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Difference between average sound level of

combined series reactor and ambient

and average sound level of ambient

(dB)

Correction to be applied to average sound level of combined series reactor

and ambient to obtain average sound level of

series reactor (dB)

5 1.6 6 1.3 7 1.0 8 0.8 9 0.6 10 0.4

Over 10 0.0

Table 6. Correction to sound level

When ambient sound conditions do not comply with the above, suitable corrections may be feasible when the ambient sound conditions are steady. For this condition, the details and method for making the measurements and the ambient corrections shall be agreed upon by those responsible for the design and application of the reactor. The reactor shall be located so that no acoustically reflecting surface is within 3 m (10 ft) of the measuring microphone, other than the floor or ground. Should the reactor be tested within a semireverberant facility, it should be located in an asymmetrical manner with respect to the room geometry. If the specified conditions cannot be met, the measurement results may not be valid. When reactor sound emissions are measured in an enclosed space, sound reflections from walls or other large objects can influence the results because the sound is essentially a discrete tone that may be affected by room acoustics, room geometry, or reflecting objects. Thus, there may be differences in the sound measured in an indoor reactor or outdoor reactor installation. The reactor shall be energized at rated current with rated frequency. If the reactor is designed with means for adjusting the impedance, it should be set for rated impedance. Three-Phase series reactors shall be energized from a three-phase source and single-phase series reactors from a single-phase source. When available test power is insufficient for testing at rated current, then the manufacturer must demonstrate to the user’s satisfaction that reduced-current testing produces sufficiently accurate results when

Page 33: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 26 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

extrapolated to the rated current level. If this cannot be demonstrated to the user, a field test can be performed.

Sound measurements shall begin after the reactor being tested is energized and steady-state sound level conditions are established. Measurements may be made immediately on reactors that have been in continuous operation. When sound-level tests are made at the factory, the mounting conditions that are to be utilized at the final installation should be simulated as much as practicable.

9.10.3 Microphone positions The reference sound-producing surface of a dry-type air-core reactor is its outside winding surface. For single-phase reactors with a winding less than 2.4 m (8 ft) tall, microphone locations shall be at mid-height of the winding. For single-phase reactors greater than 2.4 m tall, microphone locations shall be at one-third and two-thirds of the winding height. For two- and three-coil stacked arrangements, microphone locations shall be at mid-height of each reactor winding. If measurements at the above heights are not possible due to bus bar layout, microphone locations shall be at the mid-height of the base reactor winding. In plan view, the microphone locations shall be laid out clockwise, sequentially along the circumference of a circle having its center at the geometric center of the reactor, and a radius equal to the reactor radius plus 3 m (10 ft). The first station will be on a radial line through the bottom terminal, or as close to it in the clockwise direction as is permitted to comply with minimum clearance distances to live parts. For side-by-side arrangements of single or stacked reactors, microphone locations are determined by the same method as for a single coil or single stack, if the locations do not overlap. If the microphone locations do overlap, measurements shall only be taken around the outermost perimeter of the resulting contour (see Figure 4).

9.10.4 Sound-Level measurement Sound-Pressure levels shall be measured in conformance with IEE Std C57.16-1996 using the sound-level meter A-weighting characteristic.

Page 34: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 27 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Fig. 4 – Microphones locations for audible sound tests

9.10.5 Calculation of average sound level An average sound level value LA shall be calculated from the measured values of the A-weighted sound level LA by using the following equation:

⎟⎠

⎞⎜⎝

⎛= ∑

i

LA

Ai

NL 1.0

10 101log10 - - - - - - - - - - - - - - - - - - - (10)

where LA is the average sound level in decibels, LAi is the measured sound level at location i in decibels, and N is the total number of measurement locations. It should be noted that the above calculated value may have to be corrected for the following factors:

Page 35: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 28 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Ambient noise level Acoustic characteristics of the location where sound readings

are taken, e.g., reverberant properties of the test lab

10. Performance Criteria Routine tests including measurement of inductance and losses and the performance of a turn-to-turn or impulse dielectric test, at 100% specified voltage, should be carried out on the Fault Current Limiting reactors before and after the short-circuit test. Inductance and loss values should be consistent with measurement tolerance limits. Oscillograms from the required dielectric test should show no change, agreeing with the limits of the high-voltage dielectric test systems.

Page 36: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 29 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

11. Additional IEEE C57.12.01-2005 Recommended Tests. Tests in this standard are meant for dry type transformers but are included here as part of the ZENERGY Power FCL testing procedure since they have been identified as part of the SCE Field Testing Acceptance Criteria. Tables 7 through 9 show the relevant tests in accordance with IEEE Std C57.12.01-2005.

11.1 Dielectric Insulation

Table 7. Dielectric insulation levels for dry-type transformers used on systems with BIL ratings 200 kV and below

Page 37: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 30 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

11.2 Partial Discharge

Table 8. Partial discharge limits and pres-stress limits

Page 38: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 31 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

11.3 Miscellaneous dry-type transformer tests

Table 9. Dry type transformer tests

12. Conclusions The test protocol for the ZENERGY Power Fault Current Limiter is presented. Tests are fundamentally based on IEEE relevant standards that address test codes for dry-type air-core series-connected reactors and dry-type distribution and power transformers, including those with solid cast and/or resin encapsulated windings Some of the described tests are regarded as optional and should be conducted only when required by buyers.

Page 39: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 32 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

13. List of Tables and Figures TABLE 1: ZENERGY FCL TEST SUMMARY.......................................................... 4 TABLE 2: ZENERGY PRE-CONNECTION TESTS.................................................... 8 TABLE 3. ZENERGY PRE-CONNECTION TESTS.................................................... 9 TABLE 4: ROUTINE, DESIGN AND OTHER TEST FOR DRY-TYPE SERIES REACTORS .... 10 FIG.1: SINGLE-PHASE REACTOR CONNECTIONS FOR IMPEDANCE-LOSS AND

IMPEDANCE-VOLTAGE TESTS (INSTRUMENT TRANSFORMERS TO BE ADDED WHEN NECESSARY) ............................................................................................. 12

FIG. 2: THREE PHASE REACTOR CONNECTIONS FOR IMPEDANCE-LOSS AND IMPEDANCE-VOLTAGE TESTS (INSTRUMENT TRANSFORMERS TO BE ADDED WHEN NECESSARY) ............................................................................................. 13

FIG. 3 – RECOMMENDED CIRCUIT FOR TURN-TO-TURN TESTING ............................ 18 TABLE 5: INSULATION TEST LEVELS FOR DRY-TYPE AIR-CORE SERIES REACTORS.... 22 TABLE 5. INSULATION TEST LEVELS FOR DRY-TYPE AIR-CORE SERIES REACTORS

(CONTINUED) ............................................................................................ 23 TABLE 6. CORRECTION TO SOUND LEVEL ............................................................ 25 FIG. 4 – MICROPHONES LOCATIONS FOR AUDIBLE SOUND TESTS........................... 27 TABLE 7. DIELECTRIC INSULATION LEVELS FOR DRY-TYPE TRANSFORMERS USED ON

SYSTEMS WITH BIL RATINGS 200 KV AND BELOW ......................................... 29 TABLE 8. PARTIAL DISCHARGE LIMITS AND PRES-STRESS LIMITS............................ 30 TABLE 9. DRY TYPE TRANSFORMER TESTS.......................................................... 31

Page 40: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/ES-2008/05 Rev: 2 Page: 33 of 33

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

List of Revisions

Revision Date Action Modified Page 1 05/05/08 Released 2 07/14/08 Added Table 1.

Changed ms to µs in last paragraph of

section 9.7

page 4 page18

Page 41: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

B‐1

APPENDIX B: Zenergy Power HTS FCL Laboratory Test Report

Page 42: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 1 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

Test Report

Reporting Center (full name and address): SC Power Systems

999 Baker Way, Suite 150

San Mateo, CA 94404-1581

Tel.: +1-650-287-2630

Fax :+1-650-572-2959

Responsible Person: Franco Moriconi

Project Name: High Temperature Superconducting Fault Current Limiter

Document Title: High Voltage Testing – Powertech Labs, Surry BC Canada

Document Ref.No.: SCP/TR-07/03 Reg: # Page 1

Date of issue: 12/31/07 Classification: Confidential No. of pages: 21

Client(s): SC Power

Author(s): F. Moriconi Approved: Bert Nelson Order No.:

Distribution: Frank Lambert (NEETRAC), Lloyd Cibulka (CEC), Keyue Smedley (CEC), Alan Hood (SCE), Victor Gore (SCE), Chris Rose (LANL), Bert Nelson (SCP), Woody Gibson (SCP), Carsten Bührer (Zenergy), Frank Darmann (AS), William Boettger (SCP), William Schram (SCP), Larry Masur (SCP), Randy Proctor (SCP), Alonso Rodriguez (SCP), Stewart Ramsay (SCP), Amadeep Singh (SCP)

Distribution page 1:

Keywords: Fault current limiter, high temperature superconducting Summary: The report presents the results obtained during high voltage testing of our inductive type High-Temperature Superconducting (HTS) Fault Current Limiter (FCL) performed from December 10, 2007 through December 14, 2007 at Powertech Labs in Surry, British Colombia Canada. SCP first large-scale HTS FCL is a three-phase device that is designed to operate at 12.47 kV and 1,200 amps steady-stated current, and to be able to clip a 10,000 to 12,000 kA prospective fault current by 10% to 15% for multiple, rapidly reoccurring faults of up to 30 cycles (1/2 second) in duration. The scope of this work was to measure the FCL capability of clipping a 10-12 kA RMS prospective fault current when operating under nominal conditions at 13kV and 1200A steady state current. The results show a 22% fault current clipping capability for a 16kA prospective fault, and 20% clipping capability for a 10kA prospective fault current. The peak short circuit current was reduced by 23% for the highest fault current settings of 16kA. A summary table of all tests performed is given in section 6 of the report. The test set up is illustrated in section 6. A fault current characterization test, with the FCL out of circuit, was initially performed in order to determine the appropriate source impedance values capable of generating prospective fault current RMS levels of 12,500, 10,000, 5,000 and 2,500 amperes, with an X/R ratio of approximately 10-11. Section 8 presents the results of the short circuit test with the FCL in circuit. Section 9 summarizes the fault clipping capability of our FCL. RMS and peak fault current values are tabulated and plotted for every fault current setting and phase.

fmoriconi
Highlight
fmoriconi
Highlight
Page 43: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 2 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

Contents Page

1. GENERAL 3

2. SCOPE 3

3. APPLICABILITY 4

4. APPLICABLE DOCUMENTATION 4

5. ACRONYMS AND DEFINITIONS 4 5.1 ACRONYMS 4 5.2 DEFINITIONS 4

6. POWERTECH LAB SETUP - HIGH VOLTAGE TESTING 4

7. FAULT CURRENT CHARACTERIZATION – FCL OUT OF CIRCUIT 8

8. FAULT CURRENT TESTS – FCL IN CIRCUIT 9

9. FCL CLIPPING CAPABILITY 11

10. APPENDIX 18 10.1 FCL FUNCTIONAL TESTING SCHEDULE REV 01 NOV 27 2007 18

Page 44: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 3 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

1. General The report presents the results obtained during high voltage testing of our inductive type high-temperature superconducting (HTS) fault current limiter (FCL) performed from December 10, 2007 through December 14, 2007 at Powertech high-power test facility in Surry, British Colombia Canada. SCP first large-scale HTS FCL is a three-phase device that is nominally designed to operate at 12.47 kV and 1,200 amps steady-stated current, and to be able to clip a 10,000 to 12,000 kA prospective fault current by 10% to 15% for multiple, rapidly reoccurring faults of up to 30 cycles (1/2 second) in duration. The test set up is illustrated in section 6 of this report. A fault current characterization test, with the FCL out of circuit, was initially performed in order to determine the appropriate source impedance values capable of generating prospective fault current RMS levels of 12,500, 10,000, 5,000 and 2,500 amperes, with an X/R ratio of approximately 10-11. Reactive and resistive source impedance components available at Powertech are given in figures 2 and 3. The appropriate resistive loads RL were connected in Delta configuration to generate a steady state current of approximately 1200 amps. The list of available resistive components is given in figure 4. The results of the fault current characterization test with the FCL out of circuit are presented in section 7 of this report. The FCL was then connected in series with the circuit as shown in figure 1 and a three phase short circuit was generated with an auxiliary vacuum circuit breaker. A zero voltage crossing point on wave was implemented on phase A. The main circuit breaker and auxiliary breaker pulse intervals were adjusted to generate 10-12 cycles of steady state current prior to fault, 12 cycles of short circuit conditions, and 10-12 cycles of steady state return prior to shut down. The total event was approximately 600 msec. The test was repeated for every combination of source impedance as defined by the fault current characterization test. A list of all short circuit and calibration tests is given in figure 5. Section 8 of this report presents the results of the short circuit test with the FCL in circuit, for prospective fault current RMS levels of 2.5, 5, 10, and 12.5 kA. The 12.5 kA impedance settings was underestimated and the actual fault current level was measured at 16kA. Figure 10 shows a table with the test settings, the values of RMS steady state current and RMS fault currents for every phase, the fault peak values, and the measured X/R ratios. Section 9 summarizes the fault clipping capability of our FCL. RMS and peak fault current values are tabulated and plotted for every fault current setting and phase. Figure 18 shows a 22% fault current clipping capability for a 16kA prospective fault and 20% clipping capability for a 10kA prospective fault current. The peak short circuit current was reduced by 23% for the highest fault current settings of 16kA.

2. Scope The scope of this work was to measure the FCL capability of clipping a 10-12 kA RMS prospective fault current when operating under nominal conditions at 13kV and 1200A steady state current.

Page 45: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 4 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

3. Applicability High temperature superconducting fault current limiter.

4. Applicable documentation SCP/TR-07/001, Test Report “FCL Test Results PG&E San Ramon” FCL Functional testing schedule Rev 01 Nov 27 2007 (in appendix)

5. Acronyms and definitions

5.1 Acronyms FCL Fault Current Limiter HTS High Temperature Superconductor SC Super Conductor DC Direct Current AC Alternating Current EMF Electro Magnetic Force HV High Voltage PT Power Transformer CT Current Transformer VD Voltage Divider

5.2 Definitions Xs Reactive part of source impedance Rs Resistive part of source impedance RL Resistive load TFR Transformer AUX Auxiliary (circuit breaker for bolted 3-phase short circuit) X/R Reactive over resistive impedance ratio Ia, Ib, Ic Nominal current RMS, phase a, b and c I_ss Steady state current RMS I_sc Short circuit current - RMS I_peak Short circuit current - Peak

6. Powertech Lab setup - High Voltage Testing The test set up is illustrated below in Figure1. Reactive and resistive source impedance components available at Powertech are given in figures 2 and 3. The appropriate resistive loads RL were connected in Delta configuration to generate a steady state current of approximately 1200 amps. The list of available resistive components is given in figure 4. A list of all short circuit and calibration tests is given in figure 5.

Page 46: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 5 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

Fig. 1: PowerTech Test Schematic

No. One shot I2t@30C

X/R at20C

Continuouscurrent

# A B C kArms kApeak A2s - Arms1 0.0021 0.0022 0.0021 84.7 244 3.8E+11 95 40002 0.0044 0.0042 0.0040 84.9 237 1.8E+11 90 40003 0.0083 0.0082 0.0082 80.2 224 1.2E+11 89 40004 0.0165 0.0166 0.0165 72.2 201 5.0E+10 84 30005 0.0320 0.0339 0.0325 60.2 168 2.2E+10 69 27006 0.0630 0.0671 0.0609 45.2 126 1.1E+10 79 19007 0.1316 0.1292 0.1315 32.0 89 5.8E+09 75 19008 0.2590 0.2640 0.2590 23.0 64 4.2E+09 89 11009 0.5300 0.5180 0.5210 16.4 46 1.8E+09 94 75010 1.0400 1.0290 1.0360 11.6 32 7.6E+08 79 45011 2.1000 2.0700 2.1000 7.5 21 4.8E+08 82 30012 4.2200 4.2100 4.2300 4.5 12 2.0E+08 82 22013 8.3900 8.3100 8.3100 2.5 7 1.2E+08 83 16014 16.9200 17.0900 16.9600 1.3 4 5.8E+07 83 11015 33.6900 34.3500 34.1000 0.7 2 3.0E+07 77 80

Sum 1-13 16.80 16.66 16.71 - - - -

Reactance @60 Hz at phase

MaximumCurrent

Fig. 2: Source Reactance Values

Page 47: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 6 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

mOhms kA MJR1 4.5 20 16R2 8.5 20 32R3 18.1 20 64R4 31.3 20 72R5 70.2 20 144R6 122 20 128R7 269 18.3 144R8 488 9.3 128R19 888 4.6 144R10 2132 2.3 128R11 4247 1.2 64

Fig. 3: Source Resistor Values

NameA phaseOhms

B phaseOhms

C phaseOhms

EnergyJ

ImaxArms

IcontArms

LR1 2.06 2.08 2.08 6.0E+06 750 105LR2 4.16 4.16 4.19 1.2E+07 750 105LR3 8.27 8.35 8.38 2.4E+07 750 105LR4 16.80 16.92 16.77 4.8E+07 750 105LR5 29.50 29.70 29.60 6.0E+07 600 85LR6 63.00 63.10 63.20 3.0E+07 300 50

Fig. 4: Load Resistor Values

Page 48: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 7 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

Test/Shot Date/Time MimicTest

Record Ia Ib Ic Pulse 1 Pulse 2 Pulse 3 Notes FCL# kV # kA rms kA rms kA rms msec msec msec

Cal_1 Dec 12/7:50 13.1 1 2.5 2.49 2.45 X/R = 11.2 OutCal_2 Dec 12/8:02 13.1 2 4.89 5.01 4.9 X/R = 11.1 OutCal_3 Dec 12/8:14 13.1 3 9.84 9.91 9.72 X/R = 10.7 OutCal_4 Dec 12/10:00 13.1 4 2 2 2 OutCal_5 Dec 12/10:07 13.1 5 1.28 1.26 1.26 10kA / 1200A OutCal_6 Dec 12/10:19 13.1 6 1.37 1.36 1.36 5kA / 1200A OutCal_7 Dec 12/10:29 13.1 7 1.48 3,1 OutCal_8 Dec 12/10:34 13.1 8 1.32 1.32 1.31 OutCal_9 Dec 12/10:53 13.1 9 2.5 2.49 2.45 Out

Cal_10 Dec 12/10:59 13.1 10 4.89 5.01 4.9 OutCal_11 Dec 12/11:03 13.1 11 9.84 9.91 9.72 OutCal_12 Dec 12/11:59 13.1 12 - - - 200 250 150 timing OutCal_13 Dec 12/12:06 13.1 13 1.14 1.12 1.11 191 253 164 10kA / 1200A OutCal_14 Dec 12/12:18 13.1 14 1.1 1.08 1.07 192 252 165 5kA / 1200A OutCal_15 Dec 12/12:25 13.1 15 1.08 1.07 1.07 193 251 165 2.5kA / 1200A Out

1/1 Dec 12/14:51 13.1 16 0.98 0.97 0.97 193 251 165Sparks

Started Video recording InCal_16 Dec 12/15:53 13.1 17 0.98 0.97 0.97 1 sec steady state In

Cal_17 Dec 12/16:14 13.1 18 0.98 0.97 0.97

Removed Top L brakets onlyFewer fault cycles

Sparks In

Cal_18 Dec 12/17:17 13.1 19 0.98 0.97 0.97Removed all top brakets

Sparks In

Cal_19 Dec 13/9:43 13.1 20 0.98 0.97 0.97 100OK No Sparks

6 cycles 1100A steady state In

Cal_20 Dec 13/9:52 13.1 21 0.98 0.97 0.97 500OK No Sparks

30 cycles 1100A steady state In

1/2 Dec 13/10:07 13.1 22 0.98 0.97 0.97 193 251 1652.5kA / 1200A

No Sparks In

2/1 Dec 13/10:30 13.1 23 1.03 1.01 0.99 193 251 1654.2kA / 1200A

Sparks In

2/2 Dec 13/10:45 13.1 24 1.03 1.01 0.99 193 251 165

4.2kA / 1000ATurned off flash light

Sparks In

3/1 Dec 13/11:10 13.1 25 1.08 1.06 1.04 193 251 16510kA / 1000A7.86,7.83,7.7 In

Cal_21 Dec 13/11:50 13.1 26 7.89 6.95 7.46 100 In4/1 Dec 13/13:45 13.1 27 7.89 6.95 7.46 500 In4/2 Dec 13/14:00 13.1 28 193 50 - 7A / 10kA In

4/3 Dec 13/14:04 13.1 29 7900 7860 7720 193 253 1657A / 10kA

Sparks In

4/4 Dec 13/14:18 13.1 30 7900 7860 7720 193 253 1657A / 10kA

Sparks In

4/5 Dec 13/14:26 13.1 31 7900 7860 7720 193 253 1657A / 10kA

Sparks InCal_22 Dec 13/14:43 13.1 32 1100 1090 1070 100 In

5/1 Dec 13/14:50 13.1 33 12700 12800 12500 193 253 16512.5kA / 1100AHTS COIL ON In

5/2 Dec 13/15:01 13.1 34 12700 12800 12500 193 253 16512.5kA / 1100AHTS COIL OFF In

Cal_23 Dec 14/8:29 13.1 35 1140 1120 1120 Load only Out

Cal_24 Dec 14/9:22 13.1 36 16200 16500 16100

Source onlyX/R = 6.8 Out

Fig. 5: Table - Test summary

Page 49: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 8 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

7. Fault Current Characterization – FCL out of circuit A fault current characterization test was performed in order to determine the appropriate source impedance values capable of generating prospective fault current RMS levels of 12,500, 10,000, 5,000 and 2,500 amperes, with an X/R ratio of approximately 10-11. The test with 12.5kA settings was performed in two steps, the first one to characterize the load and the second one to characterize the fault current. The 12.5 kA impedance settings was underestimated and the actual fault current level was measured at 16kA. Test

Record KVIsckA

IsskA

Ia_sskA

Ib_sskA

Ic_sskA

Ia_sckA

Ib_sckA

Ic_sckA X/R

Ia_peakkA

Ib_peakkA

Ic_peakkA Notes FCL

15 13.1 2.5 1.2 1.08 1.07 1.07 2.5 2.49 2.45 11.2 4.84 5.25 3.85 Out14 13.1 5 1.2 1.1 1.08 1.07 4.9 5.0 4.9 11.1 10.80 10.40 8.00 Out13 13.1 10 1.2 1.14 1.12 1.11 9.6 9.6 9.6 10.7 23.20 19.00 17.40 Out35 13.1 - 1.2 1.14 1.12 1.12 - - - - - - - Load only Out36 13.1 12.5 - - - - 16.2 16.5 16.1 6.8 39.30 26.60 31.40 Source only Out

Fig. 5: Fault Current Characterization tests

0 100 200 300 400 500 600 700ms -6

-4

-2

0

2

4kA

Line

Cur

rent

[kA]

s015ias015ibs015ic

Fig. 6: 2.5 kA Fault Current Characterization

0 100 200 300 400 500 600 700ms-15

-10

-5

0

5

10kA

s014ias014ibs014ic

Fig. 7: 5 kA Fault Current Characterization

Page 50: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 9 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

0 100 200 300 400 500 600 700ms-30

-20

-10

0

10

20kA

Line

Cur

rent

[kA]

s013ias013ibs013ic

Fig. 8: 10 kA Fault Current Characterization

20 40 60 80 100 120 140 160 180ms-30

-20

-10

0

10

20

30

40kA

Line

Cur

rent

[kA]

s036ias036ibs036ic

Fig. 9: 12.5 kA Fault Current Characterization

8. Fault Current tests – FCL in circuit The FCL was connected in series with the line and a three phase short circuit was generated with an auxiliary vacuum circuit breaker. A zero voltage crossing point on wave was implemented on phase A. The main circuit breaker and auxiliary breaker pulse intervals were adjusted to generate 10-12 cycles of steady state current prior to fault, 12 cycles of short circuit conditions, and 10-12 cycles of steady state return prior to shut down. The total event was approximately 600 msec. The test was repeated for every combination of source impedance as defined by the fault current characterization test.

TestRecord KV

IsckA

IsskA

Ia_sskA

Ib_sskA

Ic_sskA

Ia_sckA

Ib_sckA

Ic_sckA X/R

Ia_peakkA

Ib_peakkA

Ic_peakkA FCL

22 13.1 2.5 1.2 0.98 0.97 0.97 2.1 2 2 11 4.2 4.95 3.62 In23 13.1 4.2 1.2 1.15 1.28 1.24 4.16 4.17 4.05 11 9.5 10.9 6.6 In24 13.1 4.2 1.0 1.03 1.01 0.99 4.22 4.19 4 11 9.7 10.8 5.9 In25 13.1 10 1.0 1.08 1.06 1.04 7.85 7.85 7.7 10.6 18 20.4 13.5 In33 13.1 12.5 1.1 1.1 1.08 1.08 12.7 12.8 12.5 6 25.5 30.3 23.9 In

Fig. 10: Fault Current Tests – summary table

Page 51: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 10 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

0 100 200 300 400 500 600 700ms -6

-4

-2

0

2

4

6kA

Line

Cur

rent

[kA

]s022ias022ibs022ic

Fig. 11: 2.5kA Fault Current Test

0 100 200 300 400 500 600 700ms-15

-10

-5

0

5

10

15kA

Line

Cur

rent

[kA]

s023ias023ibs023ic

Fig. 12: 5kA Fault Current Test

0 100 200 300 400 500 600 700ms-10

-5

0

5

10

15kA

Line

Cur

rent

[kA]

s024ias024ibs024ic

Fig. 13: 5kA Fault Current Test - Repeat

Page 52: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 11 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

0 100 200 300 400 500 600 700ms-20

-10

0

10

20

30kA

Line

Cur

rent

[kA]

s025ias025ibs025ic

Fig. 14: 10kA Fault Current Test

0 100 200 300 400 500 600 700ms-30

-20

-10

0

10

20

30

40kA

Line

Cur

rent

[kA]

s033ias033ibs033ic

Fig. 15: 12.5kA Fault Current Test

9. FCL clipping capability The FCL clipping capability is reported below. RMS and peak fault current values are tabulated and plotted for every fault current setting and phase. Figure 18 shows a 22% fault current clipping capability for a 16kA prospective fault and 20% clipping capability for a 10kA prospective fault current. The peak short circuit current was reduced by 23% for the highest fault current settings of 16kA.

Page 53: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 12 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

Fault CurrentClipping

Peak Current Reduction

KV IsckA Ia_sc Ib_sc Ic_sc Ia_sc Ib_sc Ic_sc % Ia_peak Ib_peak Ic_peak Ia_peak Ib_peak Ic_peak %

13.1 2.5 2.5 2.49 2.45 2.1 2 2 14% 4.84 5.25 3.85 4.2 4.95 3.62 6%13.1 5 4.9 5.0 4.9 4.22 4.19 4 14% 10.80 10.40 8.00 9.7 10.8 5.9 0%13.1 10 9.6 9.6 9.6 7.85 7.85 7.7 20% 23.20 19.00 17.40 18 20.4 13.5 12%13.1 16 16.2 16.5 16.1 12.7 12.8 12.5 22% 39.30 26.60 31.40 25.5 30.3 23.9 23%

FCL OUT FCL IN FCL OUT FCL IN

Fig. 17: FCL Clipping capability – Results table

14% 14%

20%22%

0%

5%

10%

15%

20%

25%

2.5 5 10 16

Perc

ent C

lippi

ng

Prospective Fault Current [kA]

FCL Clipping Capability

Fig. 18: FCL Clipping capability – percent vs. fault current levels

100 200 300 400 500 600ms-30

-20

-10

0

10

20

30

40kA

Line

Cur

rent

[kA]

-s033ias036ia

Fig. 19: 16kA Fault current – FCL In vs. Out – phase A

Page 54: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 13 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

150 200 250 300 350 400 450 500ms-40

-30

-20

-10

0

10

20

30kA

Line

Cur

rent

[kA]

-s033ibs036ib

Fig. 20: 16kA Fault current – FCL In vs. Out – phase B

150 200 250 300 350 400 450 500ms-40

-30

-20

-10

0

10

20

30kA

Line

Cur

rent

[kA]

s033ics036ic

Fig. 21: 16kA Fault current – FCL In vs. Out – phase C

0 100 200 300 400 500 600 700ms-30

-20

-10

0

10

20kA

Line

Cur

rent

[kA

]

s025ias013ia

Fig. 22: 10kA Fault current – FCL In vs. Out – phase A

Page 55: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 14 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

100 200 300 400 500 600ms-20

-15

-10

-5

0

5

10

15kA

Line

Cur

rent

[kA]

-s025ibs013ib

Fig. 23: 10kA Fault current – FCL In vs. Out – phase B

100 200 300 400 500 600ms-15

-10

-5

0

5

10

15

20kA

Line

Cur

rent

[kA

]

s025ics013ic

Fig. 24: 10kA Fault current – FCL In vs. Out – phase C

0 100 200 300 400 500 600 700ms-15

-10

-5

0

5

10kA

Line

Cur

rent

[kA]

s023ias014ia

Fig. 25: 5kA Fault current – FCL In vs. Out – phase A

Page 56: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 15 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

0 100 200 300 400 500 600 700ms-15

-10

-5

0

5

10kA

Line

Cur

rent

[kA]

-s023ibs014ib

Fig. 26: 5kA Fault current – FCL In vs. Out – phase B

0 100 200 300 400 500 600 700ms -8

-6

-4

-2

0

2

4

6

8kA

Line

Cur

rent

[kA]

s023ics014ic

Fig. 27: 5kA Fault current – FCL In vs. Out – phase C

0 100 200 300 400 500 600 700ms -6

-4

-2

0

2

4kA

Line

Cur

rent

[kA]

s022ias015ia

Fig. 28: 2.5kA Fault current – FCL In vs. Out – phase A

Page 57: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 16 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

0 100 200 300 400 500 600 700ms -6

-4

-2

0

2

4kA

Line

Cur

rent

[kA]

-s022ibs015ib

Fig. 29: 2.5kA Fault current – FCL In vs. Out – phase B

0 100 200 300 400 500 600 700ms -4

-2

0

2

4kA

Line

Cur

rent

[kA]

s022ics015ic

Fig. 30: 2.5kA Fault current – FCL In vs. Out – phase C

Page 58: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 17 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

List of Figures Page FIG. 1: POWERTECH TEST SCHEMATIC 5

FIG. 2: SOURCE REACTANCE VALUES 5

FIG. 3: SOURCE RESISTOR VALUES 6

FIG. 4: LOAD RESISTOR VALUES 6

FIG. 5: TABLE - TEST SUMMARY 7

FIG. 5: FAULT CURRENT CHARACTERIZATION TESTS 8

FIG. 6: 2.5 KA FAULT CURRENT CHARACTERIZATION 8

FIG. 7: 5 KA FAULT CURRENT CHARACTERIZATION 8

FIG. 8: 10 KA FAULT CURRENT CHARACTERIZATION 9

FIG. 9: 12.5 KA FAULT CURRENT CHARACTERIZATION 9

FIG. 10: FAULT CURRENT TESTS – SUMMARY TABLE 9

FIG. 11: 2.5KA FAULT CURRENT TEST 10

FIG. 12: 5KA FAULT CURRENT TEST 10

FIG. 13: 5KA FAULT CURRENT TEST - REPEAT 10

FIG. 14: 10KA FAULT CURRENT TEST 11

FIG. 15: 12.5KA FAULT CURRENT TEST 11

FIG. 17: FCL CLIPPING CAPABILITY – RESULTS TABLE 12

FIG. 18: FCL CLIPPING CAPABILITY – PERCENT VS. FAULT CURRENT LEVELS 12

FIG. 19: 16KA FAULT CURRENT – FCL IN VS. OUT – PHASE A 12

FIG. 20: 16KA FAULT CURRENT – FCL IN VS. OUT – PHASE B 13

FIG. 21: 16KA FAULT CURRENT – FCL IN VS. OUT – PHASE C 13

FIG. 22: 10KA FAULT CURRENT – FCL IN VS. OUT – PHASE A 13

FIG. 23: 10KA FAULT CURRENT – FCL IN VS. OUT – PHASE B 14

FIG. 24: 10KA FAULT CURRENT – FCL IN VS. OUT – PHASE C 14

FIG. 25: 5KA FAULT CURRENT – FCL IN VS. OUT – PHASE A 14

FIG. 26: 5KA FAULT CURRENT – FCL IN VS. OUT – PHASE B 15

FIG. 27: 5KA FAULT CURRENT – FCL IN VS. OUT – PHASE C 15

FIG. 28: 2.5KA FAULT CURRENT – FCL IN VS. OUT – PHASE A 15

FIG. 29: 2.5KA FAULT CURRENT – FCL IN VS. OUT – PHASE B 16

FIG. 30: 2.5KA FAULT CURRENT – FCL IN VS. OUT – PHASE C 16

Page 59: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 18 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

10. Appendix

10.1 FCL Functional testing schedule Rev 01 Nov 27 2007

1. FCL Test set up

2. HTS Coil Cool Down and HTS Coil Testing

3. Core Saturation Measurements

4. Magnetic flux mapping measurements

5. Fault Current Characterization – FCL out of circuit

6. Transient Fault Current Limiting – Functional tests – FCL in circuit

7. Steady State Conditions – FCL in circuit

8. Cryostat Heat losses

9. LN2 Temperature Control with increased DC bias current

1. FCL Test set up Saturday 8th , Sunday 9th, Monday 10th

SCP is scheduled to arrive on site Saturday morning and spend the weekend and Monday the 10th to set up the FCL and prepare for testing. LN2 is scheduled to arrive on site Monday morning.

2. HTS Coil Cool Down and HTS Coil Testing Monday 10th, Tuesday 11th • Electrical continuity test of DC coil in dry state • Cool down coil with LN2 according to the recommended Trithor procedure • Electrical continuity in cooled state • Detailed current versus voltage diagram of the DC coil to be measured • Confirm DAQ system hardware and software

3. Core Saturation Measurements Tuesday 11th Search coil tests will be performed to measure core flux density as a function of DC current.

4. Magnetic flux mapping Tuesday 11th

The magnetic field in air around the cryostat and around the FCL structure will be measured with a tri-axis Hall probe. We will establish a map of the magnetic field in air to be compared to FEM results.

5. Fault Current Characterization – FCL out of circuit Wednesday 12th

The fault current without the FCL in the circuit is measured to confirm the impedance bay and load bay set up. Error! Reference source not found. shows the impedance set up for the various tests to be scheduled. The first three of these tests will establish the base case fault current waveforms without the FCL in circuit.

Page 60: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 19 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

FCL status

(in circuit or out

of circuit)

Secondary Voltage of

main Transformer (line to

line)

Steady state line current before fault

introduced

Load bank Z

required

Time duration of

steady state

current required

Steady state fault

current on load

side

Source limiting

impedance required (nominal)

Time required for fault

current to flow

I2t of fault

Time required

for steady state

current to flow after

fault kV rms A (rms) Ω cycles kA

) mΩ cycles A2s (x 106) cycles

Out 13.1 1200 17 ∆ 10 2.50 3025 15 3.125 30 Out 13.1 1200 17 ∆ 10 5.00 1513 15 12.50 30

Out 13.1 1200 17 ∆ 10 10.0 756 15 50.00 30

Table 1. Tests required without the FCL in circuit. Zero voltage crossing on one phase required

6. Transient Fault Current Limiting functional tests – FCL in circuit Wednesday 12th, Thursday 13th

The FCL is connected into the circuit and the complete set of six tests is repeated under exactly the same conditions. Depending on initial results and analysis further sets of analogous tests may be run with different settings on the FCL tap arrangements and biasing conditions.

FCL status

(in circuit or out

of circuit)

Secondary Voltage of main Transformer (line to line)

Steady state line current before fault

introduced

Load bank Z

required

Time duration of

steady state

current required

Steady state fault

current on load

side

Source limiting

impedance required (nominal)

Time required for fault

current to flow

I2t of fault

Time required

for steady state

current to flow after

fault kV rms A (rms) Ω cycles kA

) mΩ cycles A2s (x 106) cycles

In 13.1 7 1100Y 360 2.50 3025 30 1.56 30 In 13.1 7 1100Y 360 5.00 1513 30 6.25 30 In 13.1 7 1100Y 360 10.0 756 30 25.00 30

In 13.1 1200 17 ∆ 10 2.50 3025 15 3.125 30 In 13.1 1200 17 ∆ 10 5.00 1513 15 12.50 30 In 13.1 1200 17 ∆ 10 10.0 756 15 50.00 30

Table 2. Tests required with the FCL in circuit. Nac = 40. Idc = 100. Ndc = 800. Zero voltage crossing on one phase required

7. Steady State Conditions – FCL in circuit Thursday 13th

Table 3 shows the set of tests required to establish the steady state operational characteristics of the FCL. No fault will be introduced for these tests.

Page 61: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 20 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

Secondary Voltage of

main Transformer

bank

Steady state current through FCL required

Load bank Impedance on load side

of FCL

Powertech Source limiting impedance

required

Time duration of steady state

current

I2t of the steady state current

kV A Ω Ω s A2s (x 106) 13.1 200 37.8Y As required ≤ 5 13.1 600 12.6Y As required ≤ 5 13.1 1200 17 ∆ As required ≤ 5

Table 2. With FCL in circuit. Steady state functional tests only. Nac = 40. Idc = 100. Ndc = 800.

8. Cryostat Heat losses Tuesday 11th through Friday 14th

Liquid Nitrogen level will be monitored and logged during testing. Heat losses will be calculated from LN2 level probe.

9. LN2 Temperature Control with increased DC bias current Friday 14th

In this final test we will evacuate the space in the LN2 tank in order to decrease pressure and LN2 temperature. Repeat HTS critical current test at lower temperature. Run HTS coil at the highest DC current allowable. Repeat search coil tests to measure core flux density. If time allows, repeat one steady state condition test and one fault limiting condition test. FRIDAY 14th – END of TEST

Page 62: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

SC Power Systems Report #: SCP/TR-07/03 Issue: 1 Page: 21 of 21

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside SC Power Systems is forbidden. Use of information permitted only in compliance with valid contracts.

Revisions Issue Date Action Modified Page 1 12/31/07 First Release

Page 63: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

C‐1

APPENDIX C: Zenergy Power HTS FCL Dielectric and HV Test

Page 64: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 1 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Test Report

Reporting Center (full name and address): Zenergy Power Inc. 379 Oyster Point Blvd., Suite 1 South San Francisco, CA USA 94080-1961 Tel.: +1-650-615-5700

Responsible Person:

Project Name: CEC Avanti

Document Title: Dielectric and HV Tests 2008

Document Ref.No.: ZP/TR-2008/02 Reg: # Page 1

Date of issue: 11/09/08 Classification: Confidential No. of pages: 29

Client(s):

Author(s): F. De La Rosa

F. Moriconi

A. Singh

W. Schram

Approved: F. Moriconi Order No.:

Distribution: A. Kamiab, A. Hood (SCE), K. Smedley, L. Cibulka (CEC), C. Rose (LANL), F. Lambert (NEETRAC), B. Nelson, W. Gibson, A. Rodriguez, S. Ramsay (Zenergy

USA), C. Buehrer, J. Keller (Zenergy DE), F. Darmann (Zenergy AUS)

Distribution page 1:

Keywords: FCL dielectric test, FCL impedance, DC resistance, insulation power factor, losses, applied voltage, turn to turn test, BIL, lightning, full wave, chopped wave, partial discharge, PD

Summary: Results of tests including dielectric insulation and high voltage tests are presented in this report. These comprise winding DC resistance, impedance, losses, applied voltage and dielectric tests that were conducted at T&R Electric in Colman, South Dakota. High voltage tests conducted at Powertech in Surrey, BC in Canada include turn–to-turn, BIL full lightning and chopped lightning impulse, Partial Discharge and Applied Voltage..

fmoriconi
Highlight
fmoriconi
Highlight
Page 65: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 2 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Contents Page

1. TEST RESULTS SUMMARY ...................................................................3

2. APPLICABILITY.......................................................................................4

3. APPLICABLE DOCUMENTATION ..........................................................4

4. ACRONYMS AND DEFINITIONS ............................................................4 4.1 ACRONYMS......................................................................................................................4 4.2 DEFINITIONS ....................................................................................................................4

5. GENERAL ................................................................................................5

6. DIELECTRIC INSULATION TESTS.........................................................5 6.1 WINDING RESISTANCE MEASUREMENTS ............................................................................6 6.2 IMPEDANCE MEASUREMENT..............................................................................................7 6.3 FCL RESISTIVE LOSS MEASUREMENT...............................................................................9 6.4 FCL TEMPERATURE RISE TEST ......................................................................................10 6.5 FCL APPLIED VOLTAGE TEST.........................................................................................11 6.6 FCL INSULATION POWER FACTOR ..................................................................................11 6.7 INSULATION RESISTANCE MEASUREMENT........................................................................11

7. HIGH VOLTAGE TESTS........................................................................12 7.1 PARTIAL DISCHARGE TEST .............................................................................................12 7.2 LIGHTNING FULL IMPULSE TEST.......................................................................................13 7.3 CHOPPED WAVE IMPULSE TEST ......................................................................................16 7.4 TURN TO TURN TEST......................................................................................................18 7.5 APPLIED VOLTAGE TEST .................................................................................................19

CONCLUSIONS ............................................................................................21

8. LIST OF TABLES AND FIGURES .........................................................22

9. APPENDIX .............................................................................................24 9.1 THERMAL INMAGES OF THE FCL DURING TEMPERATURE RISE TEST AT T&R 24

Page 66: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 3 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

1. Test Results Summary Table 1 summarizes the tests and results on the Avanti circuit FCL. (*) Partially only. Phases A and B OK. Phase C showed multiple flashovers

Table 1: FCL Test Summary

TEST Reference Document RESULTS

Winding Resistance

IEEE Std C57.16-1996 Done

Impedance IEEE Std C57.16-1996 Done

Total loss IEEE Std C57.16-1996 Done

Temperature rise

IEEE Std C57.16-1996

Partially done.

Applied voltage

IEEE Std C57.16-1996

Test OK @15 kV

Insulation power factor

IEEE Std C57-12.01-

2005 Passed

Insulation resistance

measurement

IEEE Std C57-12.01-

2005 Done

Fault current tests

Engineering Spec. ZP-ES-08-05

Done

Turn-to-turn Engineering Spec. ZP-ES-08-05

Passed

Lightning impulse

@110 kV

Engineering Spec. ZP-ES-08-05

Passed

Chopped-wave impulse

Engineering Spec. ZP-ES-08-05

Passed (*)

Audible sound

Engineering Spec. ZP-ES-08-05

Not performed

Partial Discharge

Engineering Spec. ZP-ES-08-05

Passed

Applied voltage

IEEE Std C57.16-1996

Passed @ 34 kV

RIV test

Engineering Spec. ZP-ES-08-05

Not performed

Page 67: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 4 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

2. Applicability Saturable-core HTS Fault Current Limiter 15kV class, 1200A

3. Applicable documentation [1] Engineering Specification, ZP-ES-08-05 rev02 Test Protocol for FCL 15kV

1.2kA 3 Phase Use, ZP Internal Report. [2] Engineering Report, ZP_ER-2008-02 - FCL Insertion Impedance Analysis. [3] IEEE Std C57.16-1996; IEEE Standard Requirements, Terminology, and

Test Code for Dry-Type Air-core Series-Connected Reactors. [4] IEEE Std C57-12.01-2005: IEEE Standard General Requirements for Dry-

Type Distribution and Power Transformers, Including Those with Solid-Cast and/or Resin Encapsulated Windings

[5] NETA’s Maintenance Testing Specifications and Acceptance Testing Specifications.

[6] Fault Current Limiter Dielectric Test Report, Powertech Labs Inc., October 2008

4. Acronyms and definitions

4.1 Acronyms FCL Fault Current Limiter HTS High Temperature Superconductor CEC California Energy Commission BIL Basic Insulation Level PD Partial Discharge

4.2 Definitions Current Limiting Reactor: A reactor connected in series with the phase conductors for limiting the current that can flow in a circuit under short circuit conditions, or under other operating conditions, such as capacitor switching, motor starting, synchronizing, arc stabilization, etc. Rating of a Series Reactor: The current that a series reactor can carry at its specified reactance together with any other defining characteristics, such as system voltage, BIL, short circuit current (thermal and mechanical) duty, and frequency. Rated current: The root mean square (rms) power frequency current in amperes that can be carried for the duty specified, at rated frequency without causing further measurable increase in temperature rise under prescribed conditions of test, and within limitations of established standards. Short time duty: A requirement of service that requires operation at substantially constant current for a short and definitely specified time. Nominal voltage: A line to line voltage assigned to a system or circuit of a given voltage class for the purpose of convenient designation. Rated system voltage: The voltage of a series reactor to which operational and performance characteristics are referred. It corresponds to the nominal

Page 68: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 5 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

line-to-line or phase-to-phase system voltage of the circuit in which the reactor is intended to be used. Effective resistance (or ac resistance): The value of resistance of a series reactor obtained by dividing the total losses by the current squared at power frequency. Losses: Those losses are due to current flow. They include:

• The resistance and the eddy-current loss in the winding due to load current

• Losses caused by circulating current in parallel windings • Stray losses caused by magnetic flux in other metallic parts of the

reactor support structure, and in the reactor enclosure when the support structure and the enclosure are supplied as an integral part

of the reactor insulation. Impedance: The phasor sum of the reactance and resistance, expressed in ohms. Impedance voltage drop: The product of the rated ohms’ impedance and the rated current of a series reactor. Per unit reactance: On a rated current base, a dimensionless quantity obtained by referencing the magnitude of the reactance to the rated system line-to-neutral voltage divided by the rated current of the reactor. It can also be defined on an arbitrary megavoltampere (MVA) base. Rated inductance: The total installed inductance at a specified frequency. It may consist of mutual as well as self inductance components. Rated reactance: The product of a rated inductance and rated angular frequency that provides the required reduction in fault current or other desired modification to power circuit characteristics. Reactance: The product of the inductance in henries and the angular frequency of the system. Reactance voltage drop: The component of voltage drop in quadrature with the current. Resistance voltage drop: the component of voltage drop in phase with the current.

5. General Dielectric and high voltage tests described in this report were conducted as part of the test plan devised at ZENERGY Power for the Avanti High Temperature Superconductor Fault Current Limiter. Test protocols were largely based on the IEEE C57.16-1996 and IEEE C57.12.01-2005 relevant standards, which address testing procedures for Dry-Type Series-Connected Reactors and Dry-type Distribution and Power Transformers including those with Solid Cast and/or Resin-Encapsulated Windings, respectively. These reactors are connected in the power systems to limit fault current under short circuit conditions.

6. Dielectric Insulation Tests Table 2 summarizes the overall tests described in this report. Tests 1-7

were carried out at T&R Electric in Colman, South Dakota.

Page 69: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 6 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table 2: Avanti FCL Tests

6.1 Winding Resistance measurements Table 3 shows the DC resistance values found across different sections of the bushing to bushing pathway on the three phases of the FCL during measurements.

#

TEST Location Date Observations

1 Winding Resistance

T&R Electric

9/23/08 to 9/30/08

2 Impedance T&R Electric

9/23/08 to 9/30/08

3 Total loss T&R Electric

9/23/08 to 9/30/08

4 Temperature

rise T&R Electric

9/23/08 to 9/30/08

Must be carried out at rated current. Reduced voltage is allowed.

5 Applied voltage

T&R Electric

9/23/08 to 9/30/08

@34kV according to coil manufacturer and IEEE C57.12.01

6 Insulation power factor

T&R Electric

9/23/08 to 9/30/08

7 Insulation resistance measurement

T&R Electric

9/23/08 to 9/30/08

8 Turn-to-turn Powertech 10/20/08 to

10/21/08

9 Lightning impulse @110 kV

Powertech 10/20/08 to 10/21/08

10 Chopped-wave impulse Powertech 10/20/08 to

10/21/08

12 Partial Discharge Powertech 10/20/08 to

10/21/08

Page 70: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 7 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

WINDING RESISTANCE MEASUREMENT

Tap/Winding:

DC Resistance

Bushing 1 to Core 1 729 μΩ Bushing 2 to Core 2 751 μΩ Bushing 3 to Core 3 759 μΩ Bushing 4 to Core 4 767 μΩ Bushing 5 to Core 5 750 μΩ Bushing 6 to Core 6 769 μΩ

Bushing 1 to Bushing 6 1.604 mΩ Bushing 2 to Bushing 5 1.644 mΩ Bushing 3 to Bushing 4 1.636 mΩ

Table 3: FCL AC Winding Resistance Test

6.2 Impedance Measurement The impedance of the FCL shown in figure 1 was derived from the voltage drop measurements of figure 2 at the load current levels described in table 4. Voltage was measured across the two coils in one of the phases of the FCL. This was done for two different levels of DC bias current, namely 100 A and 140 A on the DC coil, as illustrated in table 4 and figure1.

Source side avg.

current (A)

Load side

voltage (Vrms)

V drop across

FCL (Vrms)

Idc= 100A

% V.D. for Idc bias =100A

FCL impedance

for Idc=100A (ohms)

V drop across

FCL (Vrms)

Idc= 140A

% V.D. for Idc bias =140A

FCL impedance

for Idc=140A (ohms)

106.1 239.4 5.4 0.07 0.05 5.5 0.08 0.05 213.9 241.3 11.1 0.15 0.05 11.0 0.15 0.05 309.5 243.2 16.2 0.23 0.05 16.2 0.23 0.05 407.5 239.1 22.0 0.31 0.05 21.4 0.30 0.05 509.0 238.5 29.2 0.41 0.06 28.7 0.40 0.06 613.2 239 38.0 0.53 0.06 36.3 0.50 0.06 720.7 241.5 49.7 0.69 0.07 46.0 0.64 0.06 826.0 241 65.8 0.91 0.08 56.4 0.78 0.07 920.1 240 88.3 1.23 0.10 72.8 1.01 0.08

1012.9 240 116.7 1.62 0.12 98.4 1.37 0.10 1125.8 241 159.4 2.21 0.14 n/a n/a n/a

Table 4: FCL Impedance Measurement Test Results

Page 71: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 8 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

0.0 200.0 400.0 600.0 800.0 1000.0 1200.0

Load current [A]

FCL

Impe

danc

e [O

hms]

FCL impedance for Idc=140A (ohms) FCL impedance for Idc=100A (ohms)

Figure1: FCL Ohmic Impedance Measurement

Voltage drop

0.00

0.50

1.00

1.50

2.00

2.50

0.0 200.0 400.0 600.0 800.0 1000.0 1200.0

Load current [A]

%

% V.D. for DC bias=100A % V.D. for DC bias=140A

Figure 2: Voltage Drop on FCL for Different Load Currents

Page 72: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 9 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

6.3 FCL Resistive Loss Measurement Table 5 and figure 3 depict the losses as a function of load current up to 1100 A, which is the maximum test current used during the test. The resistance used for loss calculations was the bushing to bushing DC resistance. The current applied to the HTS coil during this test was 100 A.

Source side avg.

current (A)

Measured Power at Source

side [kW]

Apparent Power at

source side

[kVA]

Load Power factor

Avg. Bushing to Bushing DC

Resistance (Ohms)

FCL Calculated Resistive

Loss (kW)

FCL Losses

%

106.1 44.95 45.10 1.00 0.00163 0.055 0.12 213.9 91.59 92.09 0.99 0.00163 0.224 0.24 309.5 133.60 134.87 0.99 0.00163 0.468 0.35 407.5 173.28 176.03 0.98 0.00163 0.811 0.47 509.0 216.93 222.63 0.97 0.00163 1.265 0.58 613.2 264.54 275.33 0.96 0.00163 1.836 0.69 720.7 312.07 332.90 0.94 0.00163 2.537 0.81 826.0 358.50 395.15 0.91 0.00163 3.332 0.93 920.1 397.62 460.78 0.86 0.00163 4.135 1.04

1012.9 441.85 547.28 0.81 0.00163 5.011 1.13 1125.8 495.77 683.11 0.73 0.00163 6.190 1.25

Table 5: FCL Resistive Losses Results

FCL Bushing to Bushing Losses

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

0.0 200.0 400.0 600.0 800.0 1000.0 1200.0

Load current [A]

%

Figure 3: FCL Losses for Different Load Currents

Page 73: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 10 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

6.4 FCL Temperature Rise Test

Figure 4 depicts the result of the temperature rise test. This test was carried out at 1000 A during a period of over three hours. Temperature was measured at different points on one of the AC coils using thermocouples. The temperature on the AC coil showed the expected increase but the test could not be run long enough to show the expected decrease in rate of rise of temperature required by IEEE C57.16 -1995 (2.5% or 1oC during a period of two consecutive hours).

A collection of thermal images of different parts of the FCL during this test is presented in the Appendix. Zenergy Power will conduct a second test at reduced voltage to try getting to the point where temperature rise decreases at the rate established in IEEE C57.16-1995.

Figure 4. AC Coil Temperature Measured During the Temperature Rise Test

Temperature Rise Test at 1000A rms

AC Coil Temperature

20

25

30

35

40

45

50

55

60

0 10 20 30 40 50 60 70 80 90 100

110

120

130

140

150

160

170

180

190

200

210

220

230

240

Time [Min]

AC

Coi

l Tem

pera

ture

[C]

T1

T2

T3

T4

T5

T6

Page 74: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 11 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

6.5 FCL Applied Voltage Test Due to lack of proper cable terminations to connect onto the bushings of the FCL, applied voltage test at T&R was limited to only 15 kV, which was well endured by the FCL but the test felt short of the 34 kV voltage required by IEEE C57.12.01 for a 15 kV device. This test was successfully repeated at Powertech with the required voltage applied for 60 seconds.

6.6 FCL Insulation Power Factor

This test most indicative of voids in the coil insulation involves measurement of the ratio between capacitance and resistance leakage within the coil insulation material. This test was conducted and yielded the results described in table 6. The measured resistance value of around 1.6 mΩ in table 5 is insignificant compared with the capacitive reactance (around 2.666 MΩ) derived from the measured capacitance in table 5. This yields a near 90 degrees angle, for which the resultant insulation power factor would be well below the 0.5% recommended value in IEEE C57.12.01 [4]

ID kV Cap(pF) mA @ 2.5kV

W @ 2.5kV

mA @ 10kV W @ 10kV

A TO GRD 10 935.14 0.895 0.393 3.58 6.289 B TO GRD 10 1109.4 1.062 0.47 4.248 7.52 C TO GRD 10 942.16 0.9 0.3805 3.603 6.088

Table 6: FCL Insulation Power Factor Test

6.7 Insulation Resistance Measurement

This test was performed to test the integrity of the insulation of the AC coils. Insulation resistance measurements were carried out on the FCL per IEEE C57.12.101-2005 yielding the results described in table 7. The insulation levels found are above the 5000 MΩ level recommended by NETA [5]. The lower level for insulation between phases A and B may be due to LV signal cables from the TP’s and TC’s that were in contact with the power conductors as they passed through the same opening on the dividing wall between the compartments. Another possibility is the proximity of the taps to one of the supporting blocks in one of the coils, where sparkover activity during impulse testing consistently occurred.

Page 75: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 12 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Test applied

between phases:

A-B A-C B-C

Measured Insulation

Resistance Value (MΩ)

54,600 954,000 974,000

Table 7: FCL AC Winding Resistance Test

7. HIGH VOLTAGE TESTS

Tests 8-12 in table 2 were carried out at Powertech Lab in Surrey, BC in Canada. This report summarizes the results of HV testing described in the Powertech Test Report [6].

7.1 Partial Discharge Test The load and source terminals of each phase of the fault current limiter were connected together. Each phase was energized at a pre-stress level of 11.3 kV L-G for 10 seconds. The voltage was then reduced to 9.5 kV, held for 60 seconds and then the partial discharge was measured. After the first partial discharge test each phase was energized at the applied potential test level of 34 kV for 60 seconds. The voltage was then reduced to 9.5 kV [i.e (15/√3)*1.1, or 110% of rated L-G voltage], held for 60 seconds and then the partial discharge level was measured again. As illustrated in table 8, partial discharge levels at 9.5 kV fell below the recommended 100 pC value in the three phases.

Page 76: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 13 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table 8: Partial Discharge Test data

7.2 Lightning Full Impulse test A lightning impulse test was carried out on each phase of the fault current limiter with the source and load terminals of the phase under test connected together. Each phase was subjected to one reduced full wave and three full waves of positive polarity, as illustrated in table 9, with a crest voltage of 110 kV for the full waves. Figure 5 illustrates examples of the measured lightning impulse waveforms.

The FCL initially failed the full wave lightning impulse tests due to flashovers created from the high voltage leads to grounded points. After re-arranging the leads all three phases withstood the lightning impulse tests.

Page 77: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 14 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table 9: Full Wave Lightning Impulse Test data

Page 78: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 15 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 5: Full Wave Lightning Impulse Test Waveforms

Page 79: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 16 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

7.3 Chopped Wave Impulse test A chopped wave impulse test was carried out on each phase of the fault current limiter with the source and load terminals of the phase under test connected together. As depicted in table 10, each phase was subjected to one reduced full wave, one full wave, one reduced chopped wave, two chopped waves, followed by two full waves, with a crest voltage of 110 kV for the full waves and 120 kV for the chopped waves. Figure 6 gives examples of the applied chopped impulse waveforms. The FCL initially had flashovers on the chopped impulse and full wave lightning impulses. After re-arranging the leads A and B phases withstood the required series of impulse waves. C phase failed to withstand the closing test sequence of two full lightning impulse waves.

Table 10: Chopped Lightning Impulse Test data

Page 80: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 17 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 6: Chopped Wave Lightning Impulse Test Waveforms

Page 81: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 18 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

7.4 Turn to Turn Test As described in table 11, the turn-to-turn test was done by applying one reduced and three full wave ringing impulse waveforms of positive polarity to each terminal of the fault current limiter. The un-energized terminals of the fault current limiter were grounded during the tests. The peak of the full waveform was 95 kV. Figure 7 gives an example of the applied waveform. No shift in frequency or damping of the oscillatory pattern between reference voltages was observed during the tests. This indicates that no inter-turn flashover occurred.

Table11: Turn-to-Turn Ringing Wave Test data

Page 82: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 19 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

a) Turn-to-turn A Ø Load Side (Both Waves 95.8 kV)

b) Turn-to-turn B Ø Load Side (Full – 97.6 kV, Reduced – 51.3 kV)

Figure 7. Turn to Turn Test Waveforms

7.5 Applied Voltage test After the first partial discharge test each phase was energized at the applied potential test level of 34 kV for 60 seconds. As illustrated in table 12, the voltage was then reduced to 9.5 kV, held for 60 seconds and then the partial discharge was measured again. The FCL successfully withstood the applied voltage in the three phases.

Page 83: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 20 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table12: Applied Voltage Test data

Page 84: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 21 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Conclusions Dielectric and High Voltage Testing of the Zenergy Power FCL performed at T&R Electric in South Dakota and Powertech in Surrey, B.C. revealed an overall solid performance of the Avanti FCL but also showed the need to perform some additional enhancement work on the jumper cable and cable terminations connecting to the AC coils. The load side coil on phase C showed persistent flashovers during impulse testing apparently initiated at on one of the coil taps and tracking over a supporting dielectric block that was found to be inconveniently close to to the taps. This coil is to be rotated to increase the standoff to prevent impulse flashover. All live exposed parts will be insulated to avoid that corona discharges are initiated at sharp edges.

Page 85: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 22 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8. List of Tables and Figures TABLE 1: FCL TEST SUMMARY............................................................................ 3 TABLE 2: AVANTI FCL TESTS .............................................................................. 6 TABLE 3: FCL AC WINDING RESISTANCE TEST..................................................... 7 TABLE 4: FCL IMPEDANCE MEASUREMENT TEST RESULTS .................................... 7 FIGURE1: FCL OHMIC IMPEDANCE MEASUREMENT ............................................... 8 FIGURE 2: VOLTAGE DROP ON FCL FOR DIFFERENT LOAD CURRENTS.................... 8 TABLE 5: FCL RESISTIVE LOSSES RESULTS ......................................................... 9 FIGURE 3: FCL LOSSES FOR DIFFERENT LOAD CURRENTS .................................... 9 FIGURE 4. AC COIL TEMPERATURE MEASURED DURING THE TEMPERATURE RISE

TEST ........................................................................................................ 10 TABLE 6: FCL INSULATION POWER FACTOR TEST ............................................... 11 TABLE 7: FCL AC WINDING RESISTANCE TEST................................................... 12 TABLE 8: PARTIAL DISCHARGE TEST DATA.......................................................... 13 TABLE 9: FULL WAVE LIGHTNING IMPULSE TEST DATA ......................................... 14 FIGURE 5: FULL WAVE LIGHTNING IMPULSE TEST WAVEFORMS............................ 15 TABLE 10: CHOPPED LIGHTNING IMPULSE TEST DATA.......................................... 16 FIGURE 6: CHOPPED WAVE LIGHTNING IMPULSE TEST WAVEFORMS .................... 17 TABLE11: TURN-TO-TURN RINGING WAVE TEST DATA......................................... 18 FIGURE 7. TURN TO TURN TEST WAVEFORMS..................................................... 19 TABLE12: APPLIED VOLTAGE TEST DATA............................................................ 20

Page 86: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 23 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

List of Revisions

Revision Date Action Modified Page 1 11/09/08 Draft Released 1 12/03/08 Released Page 1

Page 87: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 24 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9. APPENDIX

9.1 THERMAL INMAGES OF THE FCL DURING TEMPERATURE RISE TEST AT T&R

AC COIL TEMPERATURE

AC COIL TEMPERATURE 60oc

Page 88: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 25 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

AC_coil_temp_65C

AC_coil_temp_bottom phA

Page 89: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 26 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

bushing_load-side_01

bushing_load-side_02

Page 90: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 27 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

bushing_source-side_01

bushing_source-side_02

Page 91: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 28 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

FCL_full_58Cmax

FCL_full_66Cmax

Page 92: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP_TR-2008_02 Rev:1 Page: 29 of 29

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Load-bank

Load-bank_full

Page 93: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

D‐1

APPENDIX D: Zenergy Power HTS FCL Normal State Temperature Rise Test

Page 94: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 1 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Test Report

Reporting Center (full name and address): Zenergy Power Inc. 379 Oyster Point Blvd., Suite 1 South San Francisco, CA USA 94080-1961 Tel.: +1-650-615-5700

Responsible Person: Franco Moriconi

Project Name: CEC Avanti

Document Title: Temperature Rise Test

Document Ref.No.: ZP/TR-2008/03 Reg: # Page 1

Date of issue: 11/30/08 Classification: Confidential No. of pages: 19

Client(s): CEC/SCE

Author(s): F. Moriconi

F. De La Rosa

A. Singh

W. Schram

Approved: F. Moriconi Order No.:

Distribution: A. Kamiab (SCE), Alan Hood (SCE), K. Smedley (CEC UC Irvine), F. Moriconi, W. Schram, R. Lombaerde, A. Singh, M. Levitskaya, F. De La Rosa, A. Singh (ZP USA)

Distribution page 1: B. Nelson, W. Gibson, A. Rodriguez, S. Ramsay (ZP USA), F. Darmann (ZP

AUS), C. Buehrer (ZP DE)

Keywords: Fault Current Limiter, Temperature rise, heat-run

Summary: This report presents the results of the temperature rise test on the Avanti circuit Fault Current Limiter carried out at Zenergy Power in South San Francisco, CA, in compliance with the relevant IEEE standard C57.12.01-2005 and under request of Southern California Edison.

fmoriconi
Highlight
fmoriconi
Highlight
fmoriconi
Highlight
fmoriconi
Highlight
Page 95: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 2 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Contents Page

1. APPLICABILITY.......................................................................................3

2. DOCUMENTATION..................................................................................3

3. ACRONYMS AND DEFINITIONS ............................................................3 3.1 ACRONYMS......................................................................................................................3 3.2 DEFINITIONS ....................................................................................................................3

4. GENERAL ................................................................................................3

5. TEMPERATURE RISE TEST RESULTS .................................................4

6. THERMO-GRAPHIC ANALYSIS .............................................................6

7. MISCELLANEOUS PHOTOS.................................................................11

8. CONCLUSIONS .....................................................................................17

9. LIST OF TABLES AND FIGURES .........................................................18

Page 96: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 3 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

1. Applicability Saturable-core HTS Fault Current Limiter 15kV class, 750A.

2. Documentation [1] CEC Avanti Test Plan for Additional FCL Testing, Zenergy Power

Internal Report ZP_ER_2008_06, Dec. 2008. [2] Engineering Specification, ZP-ES-08-05 rev02 Test Protocol for

FCL 15kV 1.2kA 3 Phase Use, ZP Internal Report. [3] IEEE Std C57.16-1996; IEEE Standard Requirements,

Terminology, and Test Code for Dry-Type Air-core Series-Connected Reactors.

[4] IEEE Std C57-12.01-2005: IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers, Including Those with Solid-Cast and/or Resin Encapsulated Windings

3. Acronyms and definitions

3.1 Acronyms FCL Fault Current Limiter HTS High Temperature Superconductor CEC California Energy Commission SCE Southern California Edison

3.2 Definitions Ambient temperature: this is the temperature of the air surrounding the FCL. For the purposes of IEEE Std C57.16-1996, it is assumed that the temperature of the cooling air (ambient temperature) does not exceed 40 o C and the average temperature of the cooling air for any 24 hour period does not exceed 30 o C.

4. General We successfully measured all HTS and cryostat losses: standby, DC, and induced AC. The FCL was energized with 100A DC bias and 750A AC current 3-phase 60Hz. All measurements were taken at atmospheric pressure and a cryostat temperature of 77K. The cryostat was filled up to 65-70 cm and losses were estimated by measuring the LN2 boil off rate via a calibrated N2 flow meter

Page 97: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 4 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

5. Temperature rise test results The temperature rise test was conducted per test protocol document [1] according to the test setup in figure 1. Temperature was measured on the AC coils with thermocouples on different parts of the AC coils. AC current at 240 V AC from the generator was increased until nominal (750 A) current was reached. The load consisted of resistive load that could be switched on in steps of 5, 10, 25, 50 and 100 kW. Some adjustment on the generator output was applied to compensate for the voltage drop on the FCL.

Vac = AC voltage 240 V Iac = Line Current in steps up to 750 A Idc = DC bias current on HTS coil 100 A Zs = Source Impedance, Ω Zfcl = FCL Impedance, Ω Zload = Load Impedance, Ω

Figure 1: Single-phase view schematic of test setup for temperature rise test on Fault Current Limiter

Plots in figures 2-4 show the recorded data for two consecutive run-up and run-down at 750A AC.

Page 98: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 5 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

CEC AVANTITemperature Rise Test

750A rms AC current - 16 hours

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80

84

88

92

96

100

-2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Elapsed Time [hrs]

Tem

pera

ture

[C]

T = 22+ 35(1-exp(t/3)Initial temperature = 22CTemperature Rise = 35CTime constant = 3 hrs

AC Coil Temp

after 12 hours:less than 2.5% or 1 degree rise in 2 consecutive hours.

5 time constants 5x3 =15 hrs

Figure 2: Measured temperatures during test phase

CEC AVANTITemperature Rise Test

750A rms AC current - 16 hours

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80

84

88

92

96

100

-2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Elapsed Time [hrs]

Tem

pera

ture

[C]

T = 22+ 35(1-exp(t/3)Initial temperature = 22CTemperature Rise = 35CTime constant = 3 hrs

AC Coil Temp

after 12 hours:less than 2.5% or 1 degree rise in 2 consecutive hours.

5 time constants 5x3 =15 hrs

Figure 3: Measured temperature on AC coil during test

Page 99: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 6 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

CEC AVANTITemperature Rise Test

750A rms AC current - 16 hours

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80

84

88

92

96

100

-2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Elapsed Time [hrs]

Tem

pera

ture

[C]

AC Coil Temp

after 12 hours:less than 2.5% or 1 degree rise in 2 consecutive hours.

5 time constants 5x3 =15 hrs

FCL outside metal enclosure

Figure 4: Measured results showing temperature level at metal enclosure

6. Thermo-graphic analysis Figures 5-14 portray a thermo-graphic collection of images showing different parts of the FCL during the temperature rise test. This is very useful information since it allows understanding how heat is dissipated in the different elements of the FCL and their temperature range. It can also help to pinpoint unexpected hot spots on any of the elements or interconnection points.

Page 100: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 7 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 5: Temperature on top part of AC coil

Figure 6: Temperature on bottom part of AC coil

Page 101: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 8 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure7: View of AC coil and power cable with temperatures

Figure 8: Temperature on AC coil termination

Page 102: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 9 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 9: View of another AC coil termination

Figure10: Temperature on power cable jumper

Page 103: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 10 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 11: Temperature on cable jumpers from source side bushings to AC coils

Figure 12: A closer view to the bushing on the source side

Page 104: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 11 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure13: View to a bushing on the outside of the FCL

Figure14: Temperature on connecting cable jumper

7. Miscellaneous Photos Figures 15 through 26 show different aspects and views of the FCL during the temperature rise test conducted at the Zenergy Power warehouse. Figure 15 is a view of the FCL with the power cables and bushings on the source side. Figures 16 -19 depict several views on the 400 kW load banks with control boards displaying relevant parameters during test, while figure

Page 105: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 12 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

20 is a view of the generator display showing L-N and L-L voltage, PF, current, frequency and kW. Figure 21 is a closer view of the FCL on the source side. Figures 22-23 depict the monitored temperature during the test and figures 24-25 show the temperature on one of the bushings on the load side towards the end of the test.

Figure 15: FCL view from the source side

Figure 16: 400 kW load banks

Page 106: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 13 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 17: Load banks during temperature rise test

Figure 18: Control board on Load Bank 1 displaying current on the three phases

Page 107: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 14 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 19: Control board on Load Bank 2 displaying phase-phase voltage, line current and kW power

Figure 20: Generator display showing operation parameters during the FCL temperature rise test

Page 108: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 15 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 21: External view of the FCL on the source side

Figure 22: ZP monitor displaying measured temperatures during test

Page 109: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 16 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 23: A closer view to figure 22

Figure 24: Thermo-graphic view of a bushing on the load side

Page 110: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 17 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 25: Thermo-graphic view of a bushing on the load side as temperature falls at the end of the test

8. Conclusions Results from the temperature rise test carried out on the Avanti FCL at Zenergy Power are presented in this report. The observed temperature rise on the AC coils was 35 degrees C above ambient temperature. The condition to reach this value per IEEE C57.12.01-1995 [4] was when temperature rise in the AC coils were less than 2.5% or 1% within two consecutive hours and the total time were at least 5 thermal constants. After 12 hours we had reached the first condition and the second condition was reached after 16 hours, taking into consideration that the measured thermal constant was equal to three hours. We measured cryostat standby losses of 90 +/- 5 Watts, DC losses of 10 Watts approximately, and AC losses of 12 +/- 1 Watts. The induced AC losses in the HTS coil were measured at 95A DC and 751A AC.

Page 111: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 18 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9. List of Tables and Figures FIGURE 1: SINGLE-PHASE VIEW SCHEMATIC OF TEST SETUP FOR TEMPERATURE RISE

TEST ON FAULT CURRENT LIMITER................................................................ 4 FIGURE 2: MEASURED TEMPERATURES DURING TEST PHASE .................................. 5 FIGURE 3: MEASURED TEMPERATURE ON AC COIL DURING TEST ............................ 5 FIGURE 4: MEASURED RESULTS SHOWING TEMPERATURE LEVEL AT METAL

ENCLOSURE ................................................................................................ 6 FIGURE 5: TEMPERATURE ON TOP PART OF AC COIL.............................................. 7 FIGURE 6: TEMPERATURE ON BOTTOM PART OF AC COIL ....................................... 7 FIGURE7: VIEW OF AC COIL AND POWER CABLE WITH TEMPERATURES .................... 8 FIGURE 8: TEMPERATURE ON AC COIL TERMINATION ............................................. 8 FIGURE 9: VIEW OF ANOTHER AC COIL TERMINATION............................................. 9 FIGURE10: TEMPERATURE ON POWER CABLE JUMPER ........................................... 9 FIGURE 11: TEMPERATURE ON CABLE JUMPERS FROM SOURCE SIDE BUSHINGS TO AC

COILS ....................................................................................................... 10 FIGURE 12: A CLOSER VIEW TO THE BUSHING ON THE SOURCE SIDE ...................... 10 FIGURE13: VIEW TO A BUSHING ON THE OUTSIDE OF THE FCL.............................. 11 FIGURE14: TEMPERATURE ON CONNECTING CABLE JUMPER ................................. 11 FIGURE 15: FCL VIEW FROM THE SOURCE SIDE................................................... 12 FIGURE 16: 400 KW LOAD BANKS ...................................................................... 12 FIGURE 17: LOAD BANKS DURING TEMPERATURE RISE TEST ................................. 13 FIGURE 18: CONTROL BOARD ON LOAD BANK 1 DISPLAYING CURRENT ON THE THREE

PHASES .................................................................................................... 13 FIGURE 19: CONTROL BOARD ON LOAD BANK 2 DISPLAYING PHASE-PHASE VOLTAGE,

LINE CURRENT AND KW POWER................................................................... 14 FIGURE 20: ENTER FIGURE SUBTITLE HERE........................................................ 14 FIGURE 21: EXTERNAL VIEW OF THE FCL ON THE SOURCE SIDE ........................... 15 FIGURE 22: ZP MONITOR DISPLAYING MEASURED TEMPERATURES DURING TEST .... 15 FIGURE 23: A CLOSER VIEW TO FIGURE 22......................................................... 16 FIGURE 24: THERMO-GRAPHIC VIEW OF A BUSHING ON THE LOAD SIDE .................. 16 FIGURE 25: THERMO-GRAPHIC VIEW OF A BUSHING ON THE LOAD SIDE AS

TEMPERATURE FALLS AT THE END OF THE TEST ............................................ 17

Page 112: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/03 Rev: 1 Page: 19 of 19

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

List of Revisions

Revision Date Action Modified Page 1 12/03/08 Released

Page 113: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

E‐1

APPENDIX E: Zenergy Power HTS FCL Short Circuit Test

Page 114: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 1 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Test Report

Reporting Center (full name and address): Zenergy Power Inc. 379 Oyster Point Blvd., Suite 1 South San Francisco, CA USA 94080-1961 Tel.: +1-650-615-5700

Responsible Person: Franco Moriconi

Project Name: CEC Avanti

Document Title: Fault Current Testing – Powertech High Power Labs 2008

Document Ref.No.: ZP/TR-2008/01 Reg: # Page 1

Date of issue: 11/07/08 Classification: Confidential No. of pages: 97

Client(s): CEC/SCE

Author(s): F. Moriconi F. De La Rosa A. Singh W. Schram

Approved: F. Moriconi Order No.:

Distribution: A. Kamiab, A. Hood (SCE), K. Smedley, L. Cibulka (CEC), C. Rose (LANL), F. Lambert (NEETRAC), B. Nelson, W. Gibson, A. Rodriguez, S. Ramsay (Zenergy USA), C. Buehrer, J. Keller (Zenergy DE), F. Darmann (Zenergy AUS)

Distribution page 1:

Keywords: Fault Current Limiter, short circuit, prospective fault current, X/R ratio, fault level

Summary: The report presents the results of high-power short-circuit testing of Zenergy Power High-Temperature Superconducting Fault Current Limiter, performed from October 14 through October 17, 2008 at Powertech Labs in Surry, British Colombia Canada. A total of 77 power and current tests were performed, including fault current calibration, voltage drop, full-power load, and fault current limiting tests. The Zenergy HTS FCL was energized at a nominal 12.47 kV three-phase line-to-line voltage, with a nominal steady-state current of up to 1,200 A. The insertion impedance of the Zenergy HTS FCL (the steady-state voltage drop of the device when inserted into an electrical circuit) was measured repeatedly and found to be significantly less than 1% (on the order of .7% to .8%) at the nominal operating conditions expected for the Avanti Circuit. Twenty-four fault current limiting tests were performed, including a series of tests with a maximum symmetrical fault current of 23 kA RMS and a first peak current of 63 kA. At the maximum prospective fault current of 23 kA, the Zenergy HTS FCL reduced the fault current by 19%. For the single-fault tests, the Zenergy HTS FCL was energized at the steady-state current and voltage levels, faulted for 30 cycles (one-half second), and returned to the steady-state conditions. In addition to the standard single-fault tests, the Zenergy HTS FCL was subjected twice to a double-fault sequence of 20-cycle duration within a two-second time interval. The FCL performed extremely well under these conditions, successfully limiting both faults with no degradation in performance. The FCL was also subjected to an “endurance test” of a symmetrical 20 kA RMS fault current (with a 45 kA peak current) for more than 1.25 seconds. The Zenergy HTS FCL successfully clipped the protracted fault with no degradation.

fmoriconi
Highlight
fmoriconi
Highlight
fmoriconi
Highlight
Page 115: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 2 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Contents Page

1. APPLICABILITY.......................................................................................3

2. APPLICABLE DOCUMENTATION ..........................................................3

3. ACRONYMS AND DEFINITIONS ............................................................3 3.1 ACRONYMS......................................................................................................................3 3.2 DEFINITIONS ....................................................................................................................3

4. GENERAL ................................................................................................3

5. TEST SETUP............................................................................................4

6. RESULTS.................................................................................................7 6.1 FCL INSERTION IMPEDANCE .............................................................................................7 6.2 FCL FAULT CURRENT TEST RESULTS ...............................................................................9

7. LIST OF TABLES AND FIGURES .........................................................12

8. APPENDIX A – INSERTION IMPEDANCE AND VOLTAGE DROP......16 8.1 TEST 43 - 330 A RMS LOAD CURRENT - NO FCL.....................................................16 8.2 TEST 44 - 330 A RMS LOAD CURRENT WITH FCL.....................................................16 8.3 TEST 45 - 520 A RMS LOAD CURRENT NO FCL.......................................................19 8.4 TEST 46 - 520 A RMS LOAD CURRENT.....................................................................19 8.5 TEST 47 - 750 A RMS LOAD CURRENT NO FCL.......................................................22 8.6 TEST 48 - 750 A RMS LOAD CURRENT.....................................................................22 8.7 TEST 49 - 1000 A RMS LOAD CURRENT NO FCL.....................................................25 8.8 TEST 50 - 1000 A RMS LOAD CURRENT...................................................................25 8.9 TEST 51 - 1200 A RMS LOAD CURRENT NO FCL.....................................................28 8.10 TEST 53 - 1200 A RMS LOAD CURRENT...................................................................28 8.11 TEST 54 - 1000 A RMS LOAD CURRENT, 142A DC BIAS .........................................31 8.12 TEST 55 - 1000 A RMS LOAD CURRENT, 160A DC BIAS .........................................32 8.13 TEST 50-54-55 - 1000 A RMS LOAD CURRENT, 100-142-160A DC BIAS ................33

9. APPENDIX B – FAULT CURRENT TESTS ...........................................35 9.1 TEST 69 – FAULT CHARACTERIZATION ONLY 23KA, X/R=44 ............................................35 9.2 TEST 75 – 23KA FAULT X/R=44.....................................................................................36 9.3 TEST 68 – FAULT CHARACTERIZATION ONLY 20KA, X/R=21.6 .........................................41 9.4 TEST 71 – 20KA FAULT X/R=21.6..................................................................................42 9.5 TEST 67 – FAULT CHARACTERIZATION ONLY 15KA, X/R=26.3 .........................................47 9.6 TEST 70 – 15KA FAULT X/R=26.3..................................................................................48 9.7 TEST 64 – FAULT CHARACTERIZATION ONLY 12.5KA, X/R=19.7 ......................................53 9.8 TEST 65 – 12.5KA FAULT X/R=19.7...............................................................................54 9.9 TEST 62 – FAULT CHARACTERIZATION ONLY, 8KA, X/R=19.8 ..........................................60 9.10 TEST 63 – 8KA FAULT X/R=19.8....................................................................................61 9.11 TEST 60 – FAULT CHARACTERIZATION ONLY, 3KA, X/R=22.9 ..........................................68 9.12 TEST 61 – 3KA FAULT X/R=22.9....................................................................................70

10. APPENDIX C – ADDITIONAL FAULT TESTS ...................................77 10.1 TEST 76 - DOUBLE FAULT SEQUENCE 20KA X/R=21.......................................................77 10.2 TEST 77 - 1.25S 80-CYCLE FAULT 20KA X/R=21 ............................................................84 10.3 TEST 78 – SECOND DOUBLE FAULT SEQUENCE 20KA X/R=21 ........................................88

11. APPENDIX D – POWERTECH SOURCE AND LOAD IMPEDANCES95

Page 116: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 3 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

1. Applicability CEC Avanti HTS Fault Current Limiter 15kV class, 1200A

2. Applicable documentation [1] Engineering Specification, ZP-ES-08-05 rev02 Test Protocol for FCL 15kV 1.2kA 3 Phase Use, ZP Internal Report. [2] Engineering Report, ZP_ER-2008-02 - FCL Insertion Impedance Analysis. [3] EEE Std C57.16-1996; IEEE Standard Requirements, Terminology, and Test Code for Dry-Type Air-core Series-Connected Reactors. [4] CEC Avanti Test Plan 2 for the Avanti Fault Current Limiter at PowerTech

3. Acronyms and definitions

3.1 Acronyms FCL Fault Current Limiter HTS High Temperature Superconductor CEC California Energy Commission SCE Southern California Edison POW Point-On-Wave

3.2 Definitions Xs Source impedance - reactive Rs Source impedance - resistive RL Resistive load TFR Transformer AUX Auxiliary (circuit breaker for bolted 3-phase short circuit) X/R Reactive over resistive impedance ratio Ia, Ib, Ic Nominal current RMS, phase a, b and c I_ss Steady state current RMS I_sc Fault current - RMS I_peak Peak fault current VD Voltage Drop L-L Line to Line L-G Line to Ground

4. General The report presents the results obtained during short circuit testing of Zenergy HTS FCL performed from October 14 through October 17, 2008 at Powertech High Power Lab test facility in Surry, British Colombia Canada. Zenergy HTS FCL is a three-phase device designed to operate at 12.47 kV L-L voltage and 1,200 A steady-state current. The FCL is capable of clipping up to 23kA prospective fault current by 20% for multiple, rapidly reoccurring faults of up to 30 cycles (1/2 second) in duration. Under normal steady-state operating conditions the FCL

Page 117: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 4 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

does not introduce harmonics and has extremely low insertion impedance; the voltage drop is less than 1% of the L-G bus voltage. Section 6.1 of this report presents the results of the insertion impedance test. Section 6.2 presents the results of short circuit tests with the FCL in circuit, for prospective fault current RMS levels of 3, 8, 12.5, 15, 20 and 23kA.

5. Test Setup The test circuit is illustrated below in Figure 1. Reactive and resistive source impedance components available at Powertech are given in Appendix D. The appropriate resistive and inductive loads were connected in delta configuration to generate the required steady state load current with a power factor of 0.9 approximately. The list of available resistive components is also given in Appendix D. A list of all short circuit and calibration tests is given in Table 1. In the fault sequence, a make switch was first closed to supply load current for approximately 20 cycles. At the zero crossing of the voltage phase A the auxiliary switch was closed to apply a three phase to ground fault for a duration of 30 cycles. After the fault, the auxiliary switch was opened returning the circuit to normal load current for an additional 20 cycles. The sequence terminated with the final opening of the make switch. The FCL was switched in and out of the circuit via the bypass breaker. To avoid the insertion of unaccountable impedances in the circuit, particular attention was devoted to calibrating the fault characterization with the bypass switch. Table 1 summarizes all the tests performed on the FCL.

Page 118: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 5 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Shunt

RTRV

CTRVPT

XS

RS

MakeSwitch

RL

AC

RTRV

CTRVPT

XS

RS

MakeSwitch

AC

RTRV

CTRVPT

XS

RS

MakeSwitch

RL

Shunt

Shunt

AC

A Ø

B Ø

C Ø

RL

AUX

AUX

AUX

RL

CT

CT

CT

FCL

VoltageDivider

Bypass Breaker

FCL

FCL

Figure 1: High power test circuit - Powertech Lab, Surry BC

Page 119: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 6 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Test ID Date

SourceVoltage

kV

Typeof test

FCLStatus

LoadSetting

A

LoadActual

A

FaultLevel

SettingkA

FaultLevelActual

kA

X/RRatio

DC BiasA Notes

1 14-Oct 3.76 CAL DISC 3 21.8 0 elbow-to-elbow connection2 14-Oct 3.76 CAL DISC 3 2.99 21.8 0 elbow-to-elbow connection3 14-Oct 3.76 CAL DISC 800 833 21.8 0 elbow-to-elbow connection5 14-Oct 3.76 CAL DISC 800 760 0 elbow-to-elbow connection6 14-Oct 3.76 CAL DISC 800 830 21.8 0 elbow-to-elbow connection7 14-Oct 3.76 10-30-20 DISC 830 830 2.99 2.99 21.8 0 Head is too short8 14-Oct 3.76 20-30-20 DISC 830 830 2.99 2.99 21.8 0 Not pure ASYM, RETAKE

9 14-Oct 3.76 20-30-20 DISC 830 830 2.99 2.99 21.8 0 GOOD. May have to adjust line current calibration in PT data

10 15-Oct 3.76 20-30-20 DISC 830 830 2.99 2.99 21.8 0Calibration ob bypass switch. FCL disconnected and elbow are open. Adjuct line current calib for PT data.

11 15-Oct 3.76 20-30-20 BYPSD 830 830 2.99 2.99 21.8 0 Adjuct (1/2) line current calib for PT data.

12 15-Oct 3.76 CAL BYPSD 830 830 100 GOOD13 15-Oct 3.76 Load only IN 830 830 100 GOOD14 15-Oct 3.76 20-30-20 IN 830 830 2.99 2.99 21.8 100 GOOD. Adjust diff PT's scale factor15 15-Oct 3.76 20-30-20 IN 830 830 2.99 2.99 21.8 100 File not aquired16 15-Oct 3.76 20-30-20 IN 830 830 2.99 2.99 21.8 100 GOOD17 15-Oct 3.76 20-30-20 IN 830 830 2.99 2.99 21.8 100 Retake of 1518 15-Oct 3.76 20-30-20 IN 830 830 2.99 2.99 21.8 100 Retake of 1619 15-Oct 3.76 CAL BYPSD 5 5.1 24.8 10020 15-Oct 3.76 CAL BYPSD 800 806 10021 15-Oct 3.76 20-30-20 IN 806 806 5.1 5.1 24.8 100 GOOD22 15-Oct 3.76 20-30-20 BYPSD 806 806 5.1 5.1 24.8 100 GOOD, chech againt test 2023 15-Oct 3.76 CAL BYPSD 8 Low 100 Too low, retake24 15-Oct 3.76 CAL BYPSD 8 8.08 21.2 10025 15-Oct 3.76 CAL BYPSD 800 821 10026 15-Oct 3.76 20-30-20 BYPSD 821 821 8.08 8.08 21.2 100 GOOD27 15-Oct 3.76 20-30-20 IN 821 821 8.08 8.08 21.2 100 GOOD28 15-Oct 3.76 CAL BYPSD 10 Low 10029 15-Oct 3.76 CAL BYPSD 10 10.2 21.2 10030 15-Oct 3.76 CAL BYPSD 800 824 10031 15-Oct 3.76 20-30-20 BYPSD 824 824 10.2 10.2 21.2 100 GOOD32 15-Oct 3.76 20-30-20 IN 824 824 10.2 10.2 21.2 100 GOOD34 15-Oct 3.76 CAL BYPSD 12.5 12.5 21.1 10035 15-Oct 3.76 CAL BYPSD 800 825 10036 15-Oct 3.76 20-30-20 BYPSD 825 825 12.5 12.5 21.1 100 GOOD37 15-Oct 3.76 20-30-20 IN 825 825 12.5 12.5 21.1 100 GOOD, Flashover38 15-Oct 3.76 20-20-20 IN 825 825 12.5 12.5 21.1 100 Reduced num of fault cycles39 15-Oct 3.76 20-30-20 IN 825 825 12.5 12.5 21.1 100 GOOD40 16-Oct 3.76 20-30-20 IN 825 825 12.5 12.5 21.1 140 GOOD41 16-Oct 13.1 CAL BYPSD 300 330 10042 16-Oct 13.1 CAL BYPSD 330 330 100 Differential PT's high noise Phase C43 16-Oct 13.1 CAL BYPSD 330 330 10044 16-Oct 13.1 Load only IN 330 330 100 GOOD45 16-Oct 13.1 CAL BYPSD 500 520 10046 16-Oct 13.1 Load only IN 520 520 100 GOOD47 16-Oct 13.1 CAL BYPSD 750 751 10048 16-Oct 13.1 Load only IN 751 751 100 GOOD49 16-Oct 13.1 CAL BYPSD 1000 1001 10050 16-Oct 13.1 Load only IN 1001 1001 100 GOOD51 16-Oct 13.1 CAL BYPSD 1200 1201 10052 16-Oct 13.1 Load only IN 1201 1201 100 Differential PT's out of range, Retake53 16-Oct 13.1 Load only IN 1201 1201 100 GOOD54 16-Oct 13.1 Load only IN 1001 1001 142 GOOD55 16-Oct 13.1 Load only IN 1001 1001 160 GOOD56 16-Oct 13.1 CAL BYPSD 800 3 19 140 X/R too low, retake57 16-Oct 13.1 CAL BYPSD 820 3 3.02 22.9 14058 16-Oct 13.1 CAL BYPSD 820 140 Missed data due to calibration59 16-Oct 13.1 CAL BYPSD 800 838 14060 16-Oct 13.1 20-30-20 BYPSD 838 838 3.02 3.02 22.9 140 GOOD61 16-Oct 13.1 20-30-20 IN 838 838 3.02 3.02 22.9 140 GOOD62 16-Oct 13.1 20-30-20 BYPSD 816 816 8 8.05 19.8 140 GOOD63 16-Oct 13.1 20-30-20 IN 816 816 8.05 8.05 19.8 140 GOOD64 16-Oct 13.1 20-30-20 BYPSD 800 787 12 12.42 19.7 140 GOOD65 16-Oct 13.1 20-30-20 IN 787 787 12.42 12.42 19.7 140 GOOD66 17-Oct 13.1 CAL BYPSD 800 780 15 31.2 140 X/R too high, retake67 17-Oct 13.1 CAL BYPSD 15 15.2 26.3 14068 17-Oct 13.1 CAL BYPSD 20 21 140 Our CT's overload, >45,450A69 17-Oct 13.1 CAL BYPSD 23 23 44 14070 17-Oct 13.1 20-30-20 IN 780 780 15.2 15.2 26.3 140 GOOD71 17-Oct 13.1 20-30-20 IN 780 780 20 20 21.6 140 GOOD72 17-Oct 13.1 20-30-20 IN 780 780 23 23 44 140 Flash Over73 17-Oct 13.1 20-30-20 IN 780 780 23 23 44 140 Flash Over

74 17-Oct 13.1 CAL IN 300 Changed bus-bar supports. Low amps for a few cycles

75 17-Oct 13.1 20-30-20 IN 780 780 23 23 44 140 GOOD

76 17-Oct 13.1 Double Fault0-20-120-20-30 IN 800 800 20 20 21 140 DAQ out of memeory, must RETAKE

77 17-Oct 13.1 Double Fault0-20-120-20-30 IN 800 800 20 20 21 140 Error in timing. Single fault up to 1.25

sec = 80 Cycles

78 17-Oct 13.1 Double Fault0-20-120-20-30 IN 800 800 20 20 21 140 GOOD

Table 1: List of short circuit tests

Page 120: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 7 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

6. Results

6.1 FCL Insertion Impedance The test circuit was configured with a 60 Hz, 13.1 kV L-L source. Source and load impedances were adjusted to ensure a bus voltage of 12.4kV and a power factor close to 0.9. Baseline measurements were performed at load currents of 330, 520, 750, 1000, and 1200 A. The voltage drop across each phase was measured with differential PT’s. Table 2 below shows the insertion impedance results in terms of maximum voltage drop across each phase. The voltage drop is also computed as a percentage of 12.4kV L-L voltage. The DC bias current in the HTS coil was kept constant at 100A. Two tests at 1000A ac load were repeated with the DC bias increased from 100 to 140A, and to 160A. Figures 2-4 show the FCL voltage drop as a function of AC load and DC bias. The FCL insertion impedance was well predicted and accurately measured. The FCL voltage drop was found to be below 1% for all load currents expected at the Avanti circuit (max load current of 750A.) The FCL did not introduce any harmonics into the system. Line current waveforms and plots of voltage drop can be found in APPENDIX A.

Test IDSourceVoltage

kV

LoadActual

A

DC BiasA

VD ph_A

FCL inV

VD ph_BFCL in

V

VD ph_C

FCL inV

Average3 phases

V

Max3

phasesV

Voltage Drop

percentof 12.47kV

44 13.1 330 100 20.4 18.8 21.8 20.3 21.8 0.30%46 13.1 520 100 35.8 32.8 35.2 34.6 35.8 0.50%48 13.1 751 100 64.3 58.6 62.4 61.8 64.3 0.89%50 13.1 1001 100 135 123 132 130.0 135.0 1.88%53 13.1 1201 100 222 206 217 215.0 222.0 3.08%54 13.1 1001 142 118 107 115 113.3 118.0 1.64%55 13.1 1001 160 109 100 107 105.3 109.0 1.51%

Table 2: Voltage Drop Results Summary

Page 121: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 8 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

CEC FCL Voltage Drop vs. AC line current

0

20

40

60

80

100

120

140

160

180

200

220

240

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

AC Line Current RMS [A]

Max

imum

Vol

tage

Dro

p pe

r pha

se [V

]

0.0%0.2%0.4%0.6%0.8%1.0%1.2%1.4%1.6%1.8%2.0%2.2%2.4%2.6%2.8%3.0%3.2%3.4%3.6%

Vol

tage

Dro

p %

of 1

2kV

[%]

Powertech12.47kV100A DC BiasPredicted150A DC Bias

Figure 2: FCL Voltage Drop vs. AC line current

FCL Voltage Drop vs. DC Bias Current1000A rms AC current

100

110

120

130

140

80 90 100

110

120

130

140

150

160

170

180

DC BIAS CURRENT [A]

Max

imum

Vol

tage

Dro

p pe

r pha

se [V

]

Figure 3: FCL Voltage Drop vs. DC Bias current

Page 122: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 9 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

FCL Voltage Drop vs. AC line current

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

AC Line Current RMS [A]

Max

imum

Vol

tage

Dro

p pe

r pha

se [V

]

0.0%

0.2%

0.4%

0.6%

0.8%

1.0%

1.2%

1.4%

1.6%

1.8%

2.0%

Vol

tage

Dro

p %

of 1

2kV

[%]

140A Bias

160A Bias

Predicted150A DC Bias

Figure 4: FCL Voltage Drop vs. AC current and DC Bias

6.2 FCL Fault Current Test results The same test circuit with a power source of 13.1kV L-L was configured to provide 20 cycles of load current, followed by 30 cycles of fault current, followed by a fault clearance and return to load conditions for 20 cycles. Fault current characterization tests were performed with the FCL disconnected and/or bypassed in order to determine the appropriate source impedance values capable of generating prospective fault current RMS levels of : 3, 8, 12.5, 15, 20, 23 kA, with X/R ratios of more than 21. All faults were bolted 3 phase to ground. Table 3 below shows the FCL clipping performance as a percentage of symmetric prospective fault current. The maximum fault reduction was measured to be 20% of a 20kA symmetric prospective fault. Figure 5 shows the same results in a plot format. Note that for the 23kA fault level, the measured X/R ratio was 44, whereas the predicted clipping was computed for an X/R ratio of 21. Table 5 shows the FCL clipping of the maximum peak fault. Peak clipping was measured at 15-16% for fault levels between 15kA and 23kA. Figure 7 shows the single phase fault current reduction for the 23kA fault level. All fault current reduction waveforms can be found in Appendix B.

Page 123: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 10 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Test ID

FaultLevelActual

kA

X/RRatio

DC BiasA

Fault I_A

FCL inkA

Fault I_B

FCL inkA

Fault I_C

FCL inkA

Average3 phases

kA

Max3 phases

kA

ClippingSymmetric

61 3.02 22.9 140 2.78 2.75 2.76 2.8 2.8 7.9%63 8.05 19.8 140 6.83 6.98 6.96 6.9 7.0 13.3%65 12.42 19.7 140 10.2 10.4 10.4 10.3 10.4 16.3%70 15.2 26.3 140 12.3 12.5 12.4 12.4 12.5 17.8%71 20 21.6 140 15.7 16 15.7 15.8 16.0 20.0%75 23 44 140 18 18.6 18.4 18.3 18.6 19.1%

Table 3: Fault Clipping Results Summary

CEC AVANTI FCL CLIPPING PERFORMANCE12.47kV, 60Hz, 3-phase

6%7%8%9%

10%11%12%13%14%15%16%17%18%19%20%21%22%

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Prospective RMS Fault Level [kA]

Faul

t Cur

rent

Red

uctio

n [%

]

ClippingSymmetricPrediction Model

Figure 5: Percent Clipping vs. prospective fault level (Note: at 23kA X/R=44 vs. 21 in prediction model)

Test ID

FaultLevelActual

kA

Peak Faultprospective

kA

X/RRatio

DC BiasA

Fault I_A

PeakkA

Fault I_B

PeakkA

Fault I_C

PeakkA

Maxclipped

PeakkA

PeakClipping

61 3.02 7.4 22.9 140 6.2 6.5 5.4 6.5 11.1%63 8.05 20.8 19.8 140 18.7 17.7 10.9 18.7 10.2%65 12.42 31.4 19.7 140 27.6 19.1 24.3 27.6 12.2%70 15.2 40.3 26.3 140 20.9 34.2 30.9 34.2 15.1%71 20 52.4 21.6 140 27.7 43.6 38.4 43.6 16.8%75 23 63.1 44 140 28.1 53.2 48.6 53.2 15.7%

Table 4: Peak Fault Clipping Results Summary

Page 124: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 11 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

CEC AVANTI FCL PEAK CLIPPING PERFORMANCE12.47kV, 60Hz, 3-phase

6%7%8%9%

10%11%12%

13%14%15%16%17%

18%

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Prospective RMS Fault Level [kA]

Peak

Fau

lt C

urre

nt R

educ

tion

[%]

Figure 6: Percent Peak Clipping vs. prospective fault level

0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52 0.54 0.56 0.58-30

-20

-10

0

10

20

30

40

50

60

TEST 75 - 23kA X/R=44, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure 7: FCL Clipping of 23kA fault – single phase

Page 125: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 12 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

7. List of Tables and Figures FIGURE 1: HIGH POWER TEST CIRCUIT - POWERTECH LAB, SURRY BC.................... 5 TABLE 1: LIST OF SHORT CIRCUIT TESTS ............................................................... 6 TABLE 2: VOLTAGE DROP RESULTS SUMMARY...................................................... 7 FIGURE 2: FCL VOLTAGE DROP VS. AC LINE CURRENT ......................................... 8 FIGURE 3: FCL VOLTAGE DROP VS. DC BIAS CURRENT......................................... 8 FIGURE 4: FCL VOLTAGE DROP VS. AC CURRENT AND DC BIAS ............................ 9 TABLE 3: FAULT CLIPPING RESULTS SUMMARY................................................... 10 FIGURE 5: PERCENT CLIPPING VS. PROSPECTIVE FAULT LEVEL (NOTE: AT 23KA

X/R=44 VS. 21 IN PREDICTION MODEL)........................................................ 10 TABLE 4: PEAK FAULT CLIPPING RESULTS SUMMARY .......................................... 10 FIGURE 6: PERCENT PEAK CLIPPING VS. PROSPECTIVE FAULT LEVEL .................... 11 FIGURE 7: FCL CLIPPING OF 23KA FAULT – SINGLE PHASE .................................. 11 FIGURE A1: 330A RMS LOAD CURRENT – FCL BYPASSED.................................. 16 FIGURE A2: 330A RMS LOAD CURRENT – FCL IN .............................................. 16 FIGURE A3: VOLTAGE DROP AT 330A LOAD CURRENT......................................... 17 FIGURE A4: LINE CURRENT PH A - 330A FCL IN VS. OUT.................................. 17 FIGURE A5: LINE CURRENT PH B - 330A FCL IN VS. OUT.................................. 18 FIGURE A6: LINE CURRENT PH C - 330A FCL IN VS. OUT.................................. 18 FIGURE A7: 520A RMS LOAD CURRENT – FCL BYPASSED.................................. 19 FIGURE A8: 520A RMS LOAD CURRENT – FCL IN .............................................. 19 FIGURE A9: VOLTAGE DROP AT 520A LOAD CURRENT......................................... 20 FIGURE A10: LINE CURRENT PH A - 520A FCL IN VS. OUT................................ 20 FIGURE A11: LINE CURRENT PH B - 520A FCL IN VS. OUT................................ 21 FIGURE A12: LINE CURRENT PH C - 520A FCL IN VS. OUT................................ 21 FIGURE A13: 750A RMS LOAD CURRENT – FCL BYPASSED................................ 22 FIGURE A14: 750A RMS LOAD CURRENT – FCL IN ............................................ 22 FIGURE A15: VOLTAGE DROP AT 750A LOAD CURRENT....................................... 23 FIGURE A16: LINE CURRENT PH A - 750A FCL IN VS. OUT................................ 23 FIGURE A17: LINE CURRENT PH B - 750A FCL IN VS. OUT................................ 24 FIGURE A18: LINE CURRENT PH C - 750A FCL IN VS. OUT................................ 24 FIGURE A19: 1000A RMS LOAD CURRENT – FCL BYPASSED .............................. 25 FIGURE A20: 1000A RMS LOAD CURRENT – FCL IN .......................................... 25 FIGURE A21: VOLTAGE DROP AT 1000A LOAD CURRENT ..................................... 26 FIGURE A22: LINE CURRENT PH A - 1000A FCL IN VS. OUT.............................. 26 FIGURE A23: LINE CURRENT PH B - 1000A FCL IN VS. OUT.............................. 27 FIGURE A24: LINE CURRENT PH C - 1000A FCL IN VS. OUT.............................. 27 FIGURE A25: 1200A RMS LOAD CURRENT – FCL BYPASSED .............................. 28 FIGURE A26: 1200A RMS LOAD CURRENT – FCL IN .......................................... 28 FIGURE A27: VOLTAGE DROP AT 1200A LOAD CURRENT ..................................... 29 FIGURE A28: LINE CURRENT PH A - 1200A FCL IN VS. OUT.............................. 29 FIGURE A29: LINE CURRENT PH B - 1200A FCL IN VS. OUT.............................. 30 FIGURE A30: LINE CURRENT PH C - 1200A FCL IN VS. OUT.............................. 30 FIGURE A31: 1000A RMS LOAD CURRENT – FCL IN – DC =142A ...................... 31 FIGURE A32: VOLTAGE DROP AT 1000A LOAD CURRENT – DC 142A ................... 31 FIGURE A33: 1000A RMS LOAD CURRENT – FCL IN – DC =160A ...................... 32 FIGURE A34: VOLTAGE DROP AT 1000A LOAD CURRENT – DC 160A ................... 32 FIGURE A35: LINE CURRENT PH A - 1000A AC, 100 -142 -160A DC.................. 33 FIGURE A36: VOLTAGE DROP PH A - 1000A AC, 100 -142 -160A DC ................ 33

Page 126: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 13 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

FIGURE A37: VOLTAGE DROP PH B - 1000A AC, 100 -142 -160A DC ................ 34 FIGURE A38: VOLTAGE DROP PH C - 1000A AC, 100 -142 -160A DC ................ 34 FIGURE B1: FAULT CHARACTERIZATION 23KA – FCL OUT .................................. 35 FIGURE B2: POW PHASE A- FAULT CHARACTERIZATION 23KA – FCL OUT........... 35 FIGURE B3: FAULT CURRENT TEST- 23KA PROSPECTIVE – FCL IN ....................... 36 FIGURE B4: SINGLE PHASE - 23KA PROSPECTIVE VS. CLIPPED ............................. 36 FIGURE B5: SINGLE PHASE - 23KA PROSPECTIVE VS. CLIPPED ............................. 37 FIGURE B6: PHASE C - 23KA PROSPECTIVE VS. CLIPPED ..................................... 37 FIGURE B7: FCL VOLTAGE - 23KA FCL IN......................................................... 38 FIGURE B8: FCL VOLTAGE - 23KA CLOSE UP ..................................................... 38 FIGURE B9: FCL VOLTAGE - 23KA - ZOOM ......................................................... 39 FIGURE B10: SOURCE VOLTAGE - 23KA - POW ................................................. 39 FIGURE B11: SOURCE VOLTAGE - 23KA............................................................. 40 FIGURE B12: HTS COIL VOLTAGE AND CURRENT - 23KA..................................... 40 FIGURE B13: FAULT CHARACTERIZATION 20KA – FCL OUT ................................ 41 FIGURE B14: POW PHASE A- FAULT CHARACTERIZATION 20KA – FCL OUT......... 41 FIGURE B15: FAULT CURRENT TEST- 20KA PROSPECTIVE – FCL IN ..................... 42 FIGURE B16: FAULT CURRENT TEST- 20KA PROSPECTIVE – FCL IN ..................... 42 FIGURE B17: FCL VOLTAGE - 20KA FCL IN....................................................... 43 FIGURE B18: FCL VOLTAGE - 20KA CLOSE UP ................................................... 43 FIGURE B19: FCL VOLTAGE - 20KA - ZOOM ....................................................... 44 FIGURE B20: SOURCE VOLTAGE - 20KA............................................................. 44 FIGURE B21: SOURCE VOLTAGE - 20KA - POW ................................................. 45 FIGURE B22: SINGLE PHASE - 20KA PROSPECTIVE VS. CLIPPED ........................... 45 FIGURE B23: SINGLE PHASE - 20KA PROSPECTIVE VS. CLIPPED ........................... 46 FIGURE B24: SINGLE PHASE - 20KA PROSPECTIVE VS. CLIPPED ........................... 46 FIGURE B25: FAULT CHARACTERIZATION 15KA – FCL OUT ................................ 47 FIGURE B26: POW PHASE A- FAULT CHARACTERIZATION 15KA – FCL OUT......... 47 FIGURE B27: FAULT CURRENT TEST- 15KA PROSPECTIVE – FCL IN ..................... 48 FIGURE B28: FAULT CURRENT TEST- 15KA PROSPECTIVE – FCL IN ..................... 48 FIGURE B29: FCL VOLTAGE - 15KA FCL IN....................................................... 49 FIGURE B30: FCL VOLTAGE - 15KA FCL IN CLOSE UP........................................ 49 FIGURE B31: FCL VOLTAGE - 15KA FCL IN ZOOM ............................................. 50 FIGURE B32: SINGLE PHASE - 15KA PROSPECTIVE VS. CLIPPED ........................... 50 FIGURE B33: SINGLE PHASE - 15KA PROSPECTIVE VS. CLIPPED ........................... 51 FIGURE B34: PHASE C - 15KA PROSPECTIVE VS. CLIPPED ................................... 51 FIGURE B35: SOURCE VOLTAGE - 15KA............................................................. 52 FIGURE B36: SOURCE VOLTAGE - 15KA - POW ................................................. 52 FIGURE B37: FAULT CHARACTERIZATION 12.5KA – FCL OUT ............................. 53 FIGURE B38: SOURCE VOLTAGE - FAULT CHARACTERIZATION 12.5KA .................. 53 FIGURE B39: POW PHASE A- FAULT CHARACTERIZATION 12.5KA ........................ 54 FIGURE B40: FAULT CURRENT TEST- 12.5KA PROSPECTIVE – FCL IN .................. 54 FIGURE B41: FAULT CURRENT TEST- 12.5KA PROSPECTIVE – FCL IN .................. 55 FIGURE B42: FCL VOLTAGE – 12.5KA FCL IN................................................... 55 FIGURE B43: FCL VOLTAGE – 12.5KA FCL IN CLOSE UP.................................... 56 FIGURE B44: FCL VOLTAGE – 12.5KA FCL IN ZOOM.......................................... 56 FIGURE B45: SOURCE VOLTAGE – 12.5KA......................................................... 57 FIGURE B46: SOURCE VOLTAGE – 12.5KA - POW.............................................. 57 FIGURE B47: SINGLE PHASE – 12.5KA PROSPECTIVE VS. CLIPPED........................ 58 FIGURE B48: SINGLE PHASE – 12.5KA PROSPECTIVE VS. CLIPPED........................ 58 FIGURE B49: PHASE B – 12.5KA PROSPECTIVE VS. CLIPPED................................ 59

Page 127: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 14 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

FIGURE B50: PHASE C – 12.5KA PROSPECTIVE VS. CLIPPED ............................... 59 FIGURE B51: FAULT CHARACTERIZATION 8KA – FCL OUT .................................. 60 FIGURE B52: SOURCE VOLTAGE - FAULT CHARACTERIZATION 8KA ....................... 60 FIGURE B53: POW PHASE A- FAULT CHARACTERIZATION 8KA ............................. 61 FIGURE B54: FAULT CURRENT TEST- 8KA PROSPECTIVE – FCL IN ....................... 61 FIGURE B55: FAULT CURRENT TEST- 8KA PROSPECTIVE – FCL IN ....................... 62 FIGURE B56: FCL VOLTAGE – 8KA FCL IN........................................................ 62 FIGURE B57: FCL VOLTAGE – 8KA FCL IN CLOSE UP......................................... 63 FIGURE B58: FCL VOLTAGE – 8KA FCL IN ZOOM .............................................. 63 FIGURE B59: SINGLE PHASE – 8KA PROSPECTIVE VS. CLIPPED............................. 64 FIGURE B60: PHASE A – 8KA PROSPECTIVE VS. CLIPPED..................................... 64 FIGURE B61: PHASE A – 8KA PROSPECTIVE VS. CLIPPED..................................... 65 FIGURE B62: PHASE B – 8KA PROSPECTIVE VS. CLIPPED..................................... 65 FIGURE B63: PHASE B – 8KA PROSPECTIVE VS. CLIPPED..................................... 66 FIGURE B64: PHASE C – 8KA PROSPECTIVE VS. CLIPPED .................................... 66 FIGURE B65: PHASE C – 8KA PROSPECTIVE VS. CLIPPED .................................... 67 FIGURE B66: SOURCE VOLTAGE – 8KA.............................................................. 67 FIGURE B67: SOURCE VOLTAGE – 8KA - POW .................................................. 68 FIGURE B68: FAULT CHARACTERIZATION 3KA – FCL OUT .................................. 68 FIGURE B69: POW PHASE A- FAULT CHARACTERIZATION 3KA ............................. 69 FIGURE B70: SOURCE VOLTAGE - FAULT CHARACTERIZATION 3KA ....................... 69 FIGURE B71: FAULT CURRENT TEST- 3KA PROSPECTIVE – FCL IN ....................... 70 FIGURE B72: FAULT CURRENT TEST- 3KA PROSPECTIVE – FCL IN ....................... 70 FIGURE B73: FCL VOLTAGE – 3KA FCL IN........................................................ 71 FIGURE B74: FCL VOLTAGE – 3KA FCL IN CLOSE UP......................................... 71 FIGURE B75: FCL VOLTAGE – 3KA FCL IN ZOOM .............................................. 72 FIGURE B76: PHASE A – 4KA PROSPECTIVE VS. CLIPPED..................................... 72 FIGURE B77: PHASE A – 3KA PROSPECTIVE VS. CLIPPED..................................... 73 FIGURE B78: PHASE B – 3KA PROSPECTIVE VS. CLIPPED..................................... 73 FIGURE B79: PHASE B – 3KA PROSPECTIVE VS. CLIPPED..................................... 74 FIGURE B80: PHASE C – 3KA PROSPECTIVE VS. CLIPPED .................................... 74 FIGURE B81: PHASE C – 3KA PROSPECTIVE VS. CLIPPED .................................... 75 FIGURE B82: SOURCE VOLTAGE – 3KA.............................................................. 75 FIGURE B83: SOURCE VOLTAGE – 3KA - POW .................................................. 76 FIGURE C1: DOUBLE FAULT SEQUENCE – 20KA – 2 SECONDS .............................. 77 FIGURE C2: DOUBLE FAULT SEQUENCE – 20KA – FIRST 20 CYCLES...................... 77 FIGURE C3: DOUBLE FAULT SEQUENCE – 20KA – SECOND 20 CYCLES.................. 78 FIGURE C4: DOUBLE FAULT SEQUENCE – 20KA – FCL VOLTAGE ......................... 78 FIGURE C5: DOUBLE FAULT SEQUENCE – FCL VOLTAGE FIRST 20CYCLES ............ 79 FIGURE C6: DOUBLE FAULT SEQUENCE – FCL VOLTAGE SECOND 20CYCLES ........ 79 FIGURE C7: DOUBLE FAULT SEQUENCE – FCL VOLTAGE FIRST FAULT................... 80 FIGURE C8: DOUBLE FAULT SEQUENCE – FCL VOLTAGE SECOND FAULT............... 80 FIGURE C9: DOUBLE FAULT SEQUENCE – SOURCE VOLTAGE ............................... 81 FIGURE C10: DOUBLE FAULT SEQUENCE – SOURCE VOLTAGE FIRST FAULT........... 81 FIGURE C11: DOUBLE FAULT SEQUENCE – SOURCE VOLTAGE SECOND FAULT....... 82 FIGURE C12: HTS COIL VOLTAGE AND CURRENT ............................................... 82 FIGURE C13: HTS COIL VOLTAGE AND CURRENT – FIRST FAULT.......................... 83 FIGURE C14: HTS COIL VOLTAGE AND CURRENT – SECOND FAULT...................... 83 FIGURE C15: ENDURANCE TEST 1.25SEC – 20KA .............................................. 84 FIGURE C16: ENDURANCE TEST 1.25SEC – 20KA .............................................. 84 FIGURE C17: ENDURANCE TEST 1.25SEC – 20KA – FCL VOLTAGE...................... 85

Page 128: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 15 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

FIGURE C18: ENDURANCE TEST 1.25SEC – 20KA – FCL VOLTAGE...................... 85 FIGURE C19: ENDURANCE TEST 1.25SEC – 20KA – FCL VOLTAGE – ZOOM.......... 86 FIGURE C20: ENDURANCE TEST 1.25SEC – 20KA – SOURCE VOLTAGE................ 86 FIGURE C21: ENDURANCE TEST 1.25SEC – 20KA – SOURCE VOLTAGE................ 87 FIGURE C22: ENDURANCE TEST 1.25SEC – 20KA – HTS COIL V AND I ................ 87 FIGURE C23: SECOND DOUBLE FAULT SEQUENCE – 20KA – 2 SECONDS............... 88 FIGURE C24: SECOND DOUBLE FAULT SEQUENCE – 20KA – FIRST FAULT.............. 88 FIGURE C25: SECOND DOUBLE FAULT SEQUENCE – 20KA – SECOND FAULT.......... 89 FIGURE C26: SECOND DOUBLE FAULT SEQUENCE – 20KA – FCL VOLTAGE .......... 89 FIGURE C27: SECOND DOUBLE FAULT SEQUENCE – 20KA – FCL VOLTAGE .......... 90 FIGURE C28: SECOND DOUBLE FAULT SEQUENCE – 20KA – FCL VOLTAGE .......... 90 FIGURE C29: SECOND DOUBLE FAULT SEQUENCE – 20KA – FCL VOLTAGE .......... 91 FIGURE C30: SECOND DOUBLE FAULT SEQUENCE – 20KA – FCL VOLTAGE .......... 91 FIGURE C31: SECOND DOUBLE FAULT – 20KA – SOURCE VOLTAGE..................... 92 FIGURE C32: SECOND DOUBLE FAULT – 20KA – SOURCE VOLTAGE..................... 92 FIGURE C33: SECOND DOUBLE FAULT – 20KA – SOURCE VOLTAGE..................... 93 FIGURE C34: SECOND DOUBLE FAULT – 20KA – HTS COIL V AND I ..................... 93 FIGURE C35: SECOND DOUBLE FAULT – 20KA – HTS COIL V AND I ..................... 94 FIGURE C36: SECOND DOUBLE FAULT – 20KA – HTS COIL V AND I ..................... 94 TABLE D1: SOURCE REACTANCE VALUES........................................................... 95 TABLE D2: SOURCE RESISTOR VALUES.............................................................. 95 TABLE D3: LOAD RESISTOR VALUES .................................................................. 96

Page 129: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 16 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8. APPENDIX A – Insertion impedance and Voltage drop

8.1 TEST 43 - 330 A RMS LOAD CURRENT - NO FCL

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 43 - LOAD ONLY 330A RMS , FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A1: 330A RMS load current – FCL Bypassed

8.2 TEST 44 - 330 A RMS LOAD CURRENT with FCL

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 44 - LOAD ONLY 330A RMS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A2: 330A RMS load current – FCL IN

Page 130: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 17 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-100

-80

-60

-40

-20

0

20

40

60

80

100TEST 44 - LOAD ONLY 330A RMS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase APhase BPhase C

Figure A3: Voltage Drop at 330A load current

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 44 - LOAD ONLY 330A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase A WITH FCLPhase A NO FCL

Figure A4: Line Current Ph A - 330A FCL IN vs. OUT

Page 131: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 18 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 44 - LOAD ONLY 330A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase B WITH FCLPhase B NO FCL

Figure A5: Line Current Ph B - 330A FCL IN vs. OUT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 44 - LOAD ONLY 330A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase C WITH FCLPhase C NO FCL

Figure A6: Line Current Ph C - 330A FCL IN vs. OUT

Page 132: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 19 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.3 TEST 45 - 520 A RMS LOAD CURRENT NO FCL

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 45 - LOAD ONLY 520A RMS , FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A7: 520A RMS load current – FCL Bypassed

8.4 TEST 46 - 520 A RMS LOAD CURRENT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 46 - LOAD ONLY 520A RMS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A8: 520A RMS load current – FCL IN

Page 133: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 20 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-100

-80

-60

-40

-20

0

20

40

60

80

100TEST 46 - LOAD ONLY 520A RMS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase APhase BPhase C

Figure A9: Voltage Drop at 520A load current

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 46 - LOAD ONLY 520A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase A WITH FCLPhase A NO FCL

Figure A10: Line Current Ph A - 520A FCL IN vs. OUT

Page 134: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 21 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 46 - LOAD ONLY 520A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase B WITH FCLPhase B NO FCL

Figure A11: Line Current Ph B - 520A FCL IN vs. OUT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1TEST 46 - LOAD ONLY 520A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase C WITH FCLPhase C NO FCL

Figure A12: Line Current Ph C - 520A FCL IN vs. OUT

Page 135: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 22 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.5 TEST 47 - 750 A RMS LOAD CURRENT NO FCL

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 47 - LOAD ONLY 751A RMS , FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A13: 750A RMS load current – FCL Bypassed

8.6 TEST 48 - 750 A RMS LOAD CURRENT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 48 - LOAD ONLY 751A RMS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A14: 750A RMS load current – FCL IN

Page 136: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 23 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-200

-150

-100

-50

0

50

100

150

200TEST 48 - LOAD ONLY 751A RMS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase APhase BPhase C

Figure A15: Voltage Drop at 750A load current

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 48 - LOAD ONLY 520A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase A WITH FCLPhase A NO FCL

Figure A16: Line Current Ph A - 750A FCL IN vs. OUT

Page 137: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 24 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 48 - LOAD ONLY 751A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase B WITH FCLPhase B NO FCL

Figure A17: Line Current Ph B - 750A FCL IN vs. OUT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 48 - LOAD ONLY 751A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase C WITH FCLPhase C NO FCL

Figure A18: Line Current Ph C - 750A FCL IN vs. OUT

Page 138: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 25 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.7 TEST 49 - 1000 A RMS LOAD CURRENT NO FCL

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 49 - LOAD ONLY 1000A RMS , FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A19: 1000A RMS load current – FCL Bypassed

8.8 TEST 50 - 1000 A RMS LOAD CURRENT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 50 - LOAD ONLY 1000A RMS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A20: 1000A RMS load current – FCL IN

Page 139: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 26 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-250

-200

-150

-100

-50

0

50

100

150

200

250TEST 50 - LOAD ONLY 1000A RMS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase APhase BPhase C

Figure A21: Voltage Drop at 1000A load current

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 50 - LOAD ONLY 1000A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase A WITH FCLPhase A NO FCL

Figure A22: Line Current Ph A - 1000A FCL IN vs. OUT

Page 140: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 27 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 50 - LOAD ONLY 1000A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase B WITH FCLPhase B NO FCL

Figure A23: Line Current Ph B - 1000A FCL IN vs. OUT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 50 - LOAD ONLY 1000A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase C WITH FCLPhase C NO FCL

Figure A24: Line Current Ph C - 1000A FCL IN vs. OUT

Page 141: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 28 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.9 TEST 51 - 1200 A RMS LOAD CURRENT NO FCL

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 51 - LOAD ONLY 1200A RMS , FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A25: 1200A RMS load current – FCL Bypassed

8.10 TEST 53 - 1200 A RMS LOAD CURRENT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 53 - LOAD ONLY 1200A RMS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A26: 1200A RMS load current – FCL IN

Page 142: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 29 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-400

-300

-200

-100

0

100

200

300

400TEST 53 - LOAD ONLY 1200A RMS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase APhase BPhase C

Figure A27: Voltage Drop at 1200A load current

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 53 - LOAD ONLY 1200A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase A WITH FCLPhase A NO FCL

Figure A28: Line Current Ph A - 1200A FCL IN vs. OUT

Page 143: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 30 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 53 - LOAD ONLY 1200A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase B WITH FCLPhase B NO FCL

Figure A29: Line Current Ph B - 1200A FCL IN vs. OUT

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 53 - LOAD ONLY 1200A RMS , FCL IN vs. OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase C WITH FCLPhase C NO FCL

Figure A30: Line Current Ph C - 1200A FCL IN vs. OUT

Page 144: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 31 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.11 TEST 54 - 1000 A RMS LOAD CURRENT, 142A DC BIAS

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 54 - LOAD ONLY 1000A RMS - 142A DC BIAS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A31: 1000A RMS load current – FCL IN – DC =142A

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-200

-150

-100

-50

0

50

100

150

200TEST 54 - LOAD ONLY 1000A RMS - 142A DC BIAS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase APhase BPhase C

Figure A32: Voltage Drop at 1000A load current – DC 142A

Page 145: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 32 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.12 TEST 55 - 1000 A RMS LOAD CURRENT, 160A DC BIAS

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 55 - LOAD ONLY 1000A RMS - 160A DC BIAS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure A33: 1000A RMS load current – FCL IN – DC =160A

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-200

-150

-100

-50

0

50

100

150

200TEST 55 - LOAD ONLY 1000A RMS - 160A DC BIAS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase APhase BPhase C

Figure A34: Voltage Drop at 1000A load current – DC 160A

Page 146: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 33 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

8.13 TEST 50-54-55 - 1000 A RMS LOAD CURRENT, 100-142-160A DC BIAS

0.43 0.435 0.44 0.445 0.45 0.455 0.46 0.465 0.47 0.475 0.48-2

-1.5

-1

-0.5

0

0.5

1

1.5

TESTS 50-54-55 - LOAD ONLY 1000A RMS - 100-142-160A DC BIAS , FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase A 100A BIASPhase A 142A BIASPhase A 160A BIAS

Figure A35: Line Current Ph A - 1000A AC, 100 -142 -160A DC

0.42 0.43 0.44 0.45 0.46 0.47-300

-200

-100

0

100

200

300TESTS 50-54-55 - LOAD ONLY 1000A RMS - 100-142-160A DC BIAS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase A 100A BIASPhase A 142A BIASPhase A 160A BIAS

Figure A36: Voltage Drop Ph A - 1000A AC, 100 -142 -160A DC

Page 147: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 34 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-300

-200

-100

0

100

200

300TESTS 50-54-55 - LOAD ONLY 1000A RMS - 100-142-160A DC BIAS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase B 100A BIASPhase B 142A BIASPhase B 160A BIAS

Figure A37: Voltage Drop Ph B - 1000A AC, 100 -142 -160A DC

0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.5-300

-200

-100

0

100

200

300TESTS 50-54-55 - LOAD ONLY 1000A RMS - 100-142-160A DC BIAS , FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[ V ]

Phase C 100A BIASPhase C 142A BIASPhase C 160A BIAS

Figure A38: Voltage Drop Ph C - 1000A AC, 100 -142 -160A DC

Page 148: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 35 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9. APPENDIX B – FAULT CURRENT TESTS

9.1 Test 69 – Fault Characterization only 23kA, X/R=44

0 0.05 0.1 0.15 0.2 0.25

-40

-20

0

20

40

60

TEST 69 - Fault Characterization Only 23kA X/R=44, FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B1: Fault characterization 23kA – FCL OUT

0.02 0.022 0.024 0.026 0.028 0.03 0.032 0.034 0.036 0.038 0.04

-10

-5

0

5

10

TEST 69 - 23kA X/R=44, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B2: POW phase A- fault characterization 23kA – FCL OUT

Page 149: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 36 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.2 Test 75 – 23kA Fault X/R=44

0 0.2 0.4 0.6 0.8 1 1.2 1.4-50

-40

-30

-20

-10

0

10

20

30

40

50

60TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B3: Fault current test- 23kA prospective – FCL IN

0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

-40

-20

0

20

40

60

TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure B4: Single phase - 23kA prospective vs. clipped

Page 150: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 37 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52 0.54 0.56 0.58-30

-20

-10

0

10

20

30

40

50

60

TEST 75 - 23kA X/R=44, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure B5: Single phase - 23kA prospective vs. clipped

0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52 0.54 0.56 0.58-50

-40

-30

-20

-10

0

10

20

30TEST 75 - 23kA X/R=44, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase C With FCLPhase C NO FCL

Figure B6: Phase C - 23kA prospective vs. clipped

Page 151: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 38 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1 1.2 1.4-6

-4

-2

0

2

4

6TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B7: FCL Voltage - 23kA FCL IN

0.38 0.39 0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48-6

-4

-2

0

2

4

6TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B8: FCL Voltage - 23kA close up

Page 152: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 39 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.645 0.65 0.655 0.66 0.665 0.67 0.675 0.68

-4

-2

0

2

4

6TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B9: FCL Voltage - 23kA - zoom

0.39 0.395 0.4 0.405 0.41 0.415 0.42

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B10: Source Voltage - 23kA - POW

Page 153: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 40 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1 1.2

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B11: Source Voltage - 23kA

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8120

130

140

150

160

170

180

190TEST 75 - 23kA X/R=44, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure B12: HTS coil Voltage and Current - 23kA

Page 154: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 41 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.3 Test 68 – Fault Characterization only 20kA, X/R=21.6

0 0.05 0.1 0.15 0.2 0.25

-40

-20

0

20

40

60

TEST 68 - Fault Characterization Only 20kA X/R=21.6 - FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B13: Fault characterization 20kA – FCL OUT

0.02 0.022 0.024 0.026 0.028 0.03 0.032 0.034 0.036 0.038 0.04

-10

-5

0

5

10

TEST 68 - FAULT CHARACTERISATION 20kA X/R=21.6, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B14: POW phase A- fault characterization 20kA – FCL OUT

Page 155: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 42 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.4 Test 71 – 20kA Fault X/R=21.6

0 0.2 0.4 0.6 0.8 1 1.2 1.4-40

-30

-20

-10

0

10

20

30

40

50TEST 71 - 20kA X/R=21.6, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B15: Fault current test- 20kA prospective – FCL IN

0.38 0.4 0.42 0.44 0.46 0.48-40

-30

-20

-10

0

10

20

30

40

TEST 71 - 20kA X/R=21.6, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B16: Fault current test- 20kA prospective – FCL IN

Page 156: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 43 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1 1.2 1.4-6

-4

-2

0

2

4

6TEST 71 - 20kA X/R=21.6, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B17: FCL Voltage - 20kA FCL IN

0.38 0.39 0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48

-4

-2

0

2

4

6TEST 71 - 20kA X/R=21.6, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B18: FCL Voltage - 20kA close up

Page 157: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 44 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.64 0.645 0.65 0.655 0.66 0.665 0.67 0.675 0.68

-5

-4

-3

-2

-1

0

1

2

3

4

5

TEST 71 - 20kA X/R=21.6, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B19: FCL Voltage - 20kA - zoom

0 0.2 0.4 0.6 0.8 1 1.2

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 71 - 20kA X/R=21.6, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B20: Source Voltage - 20kA

Page 158: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 45 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.38 0.385 0.39 0.395 0.4 0.405 0.41 0.415

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 71 - 20kA X/R=21.6, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B21: Source Voltage - 20kA - POW

0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7-30

-20

-10

0

10

20

30

40

50

60TEST 71 - 20kA X/R=21.6 - FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure B22: Single phase - 20kA prospective vs. clipped

Page 159: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 46 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52 0.54 0.56 0.58-30

-20

-10

0

10

20

30

40

50

60

TEST 71 - 20kA X/R=21.6 - FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure B23: Single phase - 20kA prospective vs. clipped

0.385 0.39 0.395 0.4 0.405 0.41 0.415 0.42 0.425 0.43 0.435

-20

-10

0

10

20

30

40

50

60

TEST 71 - 20kA X/R=21.6 - FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure B24: Single phase - 20kA prospective vs. clipped

Page 160: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 47 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.5 Test 67 – Fault Characterization only 15kA, X/R=26.3

0 0.05 0.1 0.15 0.2 0.25-40

-30

-20

-10

0

10

20

30

40

TEST 67 - FAULT CHARACTERISATION 15kA X/R=26.3, FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B25: Fault characterization 15kA – FCL OUT

0.02 0.022 0.024 0.026 0.028 0.03 0.032 0.034 0.036 0.038 0.04

-10

-5

0

5

10

TEST 67 - FAULT CHARACTERISATION 15kA X/R=26.3, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B26: POW phase A- fault characterization 15kA – FCL OUT

Page 161: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 48 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.6 Test 70 – 15kA Fault X/R=26.3

0 0.2 0.4 0.6 0.8 1 1.2 1.4-40

-30

-20

-10

0

10

20

30

40TEST 70 - 15kA X/R=26.3, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B27: Fault current test- 15kA prospective – FCL IN

0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52-40

-30

-20

-10

0

10

20

30

TEST 70 - 15kA X/R=26.3, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B28: Fault current test- 15kA prospective – FCL IN

Page 162: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 49 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1 1.2 1.4-6

-4

-2

0

2

4

6TEST 70 - 15kA X/R=26.3, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B29: FCL Voltage - 15kA FCL IN

0.39 0.4 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48-6

-4

-2

0

2

4

TEST 70 - 15kA X/R=26.3, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B30: FCL Voltage - 15kA FCL IN close up

Page 163: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 50 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.685 0.69 0.695 0.7 0.705 0.71 0.715

-4

-3

-2

-1

0

1

2

3

4

TEST 70 - 15kA X/R=26.3, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B31: FCL Voltage - 15kA FCL IN zoom

0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7-20

-10

0

10

20

30

40

TEST 70 - 15kA X/R=26.3, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure B32: Single phase - 15kA prospective vs. clipped

Page 164: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 51 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.39 0.4 0.41 0.42 0.43 0.44 0.45-20

-10

0

10

20

30

40

TEST 70 - 15kA X/R=26.3, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase A NO FCL

Figure B33: Single phase - 15kA prospective vs. clipped

0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52 0.54 0.56 0.58

-30

-25

-20

-15

-10

-5

0

5

10

15

20

TEST 70 - 15kA X/R=26.3, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase C With FCLPhase C NO FCL

Figure B34: Phase C - 15kA prospective vs. clipped

Page 165: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 52 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1 1.2

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 70 - 15kA X/R=26.3, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B35: Source Voltage - 15kA

0.38 0.385 0.39 0.395 0.4 0.405 0.41 0.415 0.42

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 70 - 15kA X/R=26.3, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B36: Source Voltage - 15kA - POW

Page 166: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 53 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.7 Test 64 – Fault Characterization only 12.5kA, X/R=19.7

0 0.2 0.4 0.6 0.8 1 1.2

-30

-20

-10

0

10

20

30TEST 64 - FAULT CHARACTERISATION 12.5kA X/R=19.7, FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B37: Fault characterization 12.5kA – FCL OUT

0 0.2 0.4 0.6 0.8 1 1.2

-10

-5

0

5

10

TEST 64 - FAULT CHARACTERISATION 12.5kA X/R=19.7, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B38: Source voltage - Fault characterization 12.5kA

Page 167: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 54 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.355 0.36 0.365 0.37

-10

-5

0

5

10

TEST 64 - FAULT CHARACTERISATION 12.5kA X/R=19.7, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B39: POW phase A- fault characterization 12.5kA

9.8 Test 65 – 12.5kA Fault X/R=19.7

0 0.2 0.4 0.6 0.8 1 1.2 1.4-30

-20

-10

0

10

20

30TEST 65 - 12.5kA X/R=19.7, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B40: Fault current test- 12.5kA prospective – FCL IN

Page 168: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 55 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.36 0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52

-25

-20

-15

-10

-5

0

5

10

15

20

25

TEST 65 - 12.5kA X/R=19.7, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B41: Fault current test- 12.5kA prospective – FCL IN

0 0.2 0.4 0.6 0.8 1 1.2 1.4-6

-4

-2

0

2

4

6TEST 65 - 12.5kA X/R=19.7, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B42: FCL Voltage – 12.5kA FCL IN

Page 169: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 56 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.355 0.36 0.365 0.37 0.375 0.38 0.385 0.39 0.395-6

-4

-2

0

2

4

TEST 65 - 12.5kA X/R=19.7, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B43: FCL Voltage – 12.5kA FCL IN close up

0.655 0.66 0.665 0.67 0.675 0.68

-4

-3

-2

-1

0

1

2

3

4

TEST 65 - 12.5kA X/R=19.7, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B44: FCL Voltage – 12.5kA FCL IN zoom

Page 170: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 57 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1 1.2

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 65 - 12.5kA X/R=19.7, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B45: Source Voltage – 12.5kA

0.34 0.345 0.35 0.355 0.36 0.365 0.37 0.375 0.38

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 65 - 12.5kA X/R=19.7, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B46: Source Voltage – 12.5kA - POW

Page 171: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 58 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.3 0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48 0.5-20

-15

-10

-5

0

5

10

15

20

25

30TEST 65 - 12.5kA X/R=19.7, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase A With FCLPhase A NO FCL

Figure B47: Single phase – 12.5kA prospective vs. clipped

0.74 0.75 0.76 0.77 0.78 0.79 0.8

-15

-10

-5

0

5

10

15

TEST 65 - 12.5kA X/R=19.7, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase A With FCLPhase A NO FCL

Figure B48: Single phase – 12.5kA prospective vs. clipped

Page 172: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 59 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48

-20

-15

-10

-5

0

5

10

15

20

TEST 65 - 12.5kA X/R=19.7, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase B NO FCL

Figure B49: Phase B – 12.5kA prospective vs. clipped

0.34 0.36 0.38 0.4 0.42 0.44

-30

-25

-20

-15

-10

-5

0

5

10

15

TEST 65 - 12.5kA X/R=19.7, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase C With FCLPhase C NO FCL

Figure B50: Phase C – 12.5kA prospective vs. clipped

Page 173: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 60 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.9 Test 62 – Fault Characterization only, 8kA, X/R=19.8

0 0.2 0.4 0.6 0.8 1 1.2-20

-15

-10

-5

0

5

10

15

20TEST 62 - FAULT CHARACTERISATION 8kA X/R=19.8, FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B51: Fault characterization 8kA – FCL OUT

0 0.2 0.4 0.6 0.8 1 1.2

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 62 - FAULT CHARACTERISATION 8kA X/R=19.8, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B52: Source voltage - Fault characterization 8kA

Page 174: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 61 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.356 0.358 0.36 0.362 0.364 0.366-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 62 - FAULT CHARACTERISATION 8kA X/R=19.8, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B53: POW phase A- fault characterization 8kA

9.10 Test 63 – 8kA Fault X/R=19.8

0 0.2 0.4 0.6 0.8 1 1.2 1.4-20

-15

-10

-5

0

5

10

15

20TEST 63 - 8kA X/R=19.8, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B54: Fault current test- 8kA prospective – FCL IN

Page 175: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 62 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48 0.5-20

-15

-10

-5

0

5

10

15

20TEST 63 - 8kA X/R=19.8, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B55: Fault current test- 8kA prospective – FCL IN

0 0.2 0.4 0.6 0.8 1 1.2 1.4-5

-4

-3

-2

-1

0

1

2

3

4

5TEST 63 - 8kA X/R=19.8, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B56: FCL Voltage – 8kA FCL IN

Page 176: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 63 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.34 0.35 0.36 0.37 0.38 0.39 0.4 0.41-5

-4

-3

-2

-1

0

1

2

3

4

TEST 63 - 8kA X/R=19.8, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B57: FCL Voltage – 8kA FCL IN close up

0.705 0.71 0.715 0.72 0.725 0.73 0.735

-3

-2

-1

0

1

2

3

TEST 63 - 8kA X/R=19.8, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B58: FCL Voltage – 8kA FCL IN zoom

Page 177: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 64 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1-15

-10

-5

0

5

10

15

20TEST 63 - 8kA X/R=19.8, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase A With FCLPhase A NO FCL

Figure B59: Single phase – 8kA prospective vs. clipped

0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46

-10

-5

0

5

10

15

TEST 63 - 8kA X/R=19.8, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase A With FCLPhase A NO FCL

Figure B60: Phase A – 8kA prospective vs. clipped

Page 178: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 65 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.735 0.74 0.745 0.75 0.755 0.76 0.765 0.77 0.775 0.78 0.785

-10

-5

0

5

10

TEST 63 - 8kA X/R=19.8, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase A With FCLPhase A NO FCL

Figure B61: Phase A – 8kA prospective vs. clipped

0 0.2 0.4 0.6 0.8 1 1.2-20

-15

-10

-5

0

5

10

15TEST 63 - 8kA X/R=19.8, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase B NO FCL

Figure B62: Phase B – 8kA prospective vs. clipped

Page 179: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 66 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48

-15

-10

-5

0

5

10

TEST 63 - 8kA X/R=19.8, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase B NO FCL

Figure B63: Phase B – 8kA prospective vs. clipped

0 0.2 0.4 0.6 0.8 1 1.2-20

-15

-10

-5

0

5

10

15TEST 63 - 8kA X/R=19.8, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase C With FCLPhase C NO FCL

Figure B64: Phase C – 8kA prospective vs. clipped

Page 180: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 67 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.3 0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48-20

-15

-10

-5

0

5

10

TEST 63 - 8kA X/R=19.8, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase C With FCLPhase C NO FCL

Figure B65: Phase C – 8kA prospective vs. clipped

0 0.2 0.4 0.6 0.8 1 1.2

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 63 - 8kA X/R=19.8, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B66: Source Voltage – 8kA

Page 181: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 68 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.35 0.355 0.36 0.365 0.37 0.375

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 63 - 8kA X/R=19.8, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B67: Source Voltage – 8kA - POW

9.11 Test 60 – Fault Characterization only, 3kA, X/R=22.9

0 0.2 0.4 0.6 0.8 1 1.2-8

-6

-4

-2

0

2

4

6

8TEST 60 - FAULT CHARACTERISATION 3kA X/R=22.9, FCL OUT

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B68: Fault characterization 3kA – FCL OUT

Page 182: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 69 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.35 0.355 0.36 0.365 0.37 0.375

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 60 - FAULT CHARACTERISATION 3kA X/R=22.9, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B69: POW phase A- fault characterization 3kA

0 0.2 0.4 0.6 0.8 1 1.2

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 60 - FAULT CHARACTERISATION 3kA X/R=22.9, FCL OUT

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B70: Source voltage - Fault characterization 3kA

Page 183: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 70 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.12 Test 61 – 3kA Fault X/R=22.9

0 0.2 0.4 0.6 0.8 1 1.2 1.4-8

-6

-4

-2

0

2

4

6

8TEST 61 - 3kA X/R=22.9, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B71: Fault current test- 3kA prospective – FCL IN

0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48 0.5 0.52-8

-6

-4

-2

0

2

4

6

TEST 61 - 3kA X/R=22.9, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure B72: Fault current test- 3kA prospective – FCL IN

Page 184: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 71 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.2 0.4 0.6 0.8 1 1.2 1.4-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 61 - 3kA X/R=22.9, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B73: FCL Voltage – 3kA FCL IN

0.34 0.35 0.36 0.37 0.38 0.39 0.4 0.41 0.42

-1.5

-1

-0.5

0

0.5

1

1.5

2

TEST 61 - 3kA X/R=22.9, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B74: FCL Voltage – 3kA FCL IN close up

Page 185: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 72 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.665 0.67 0.675 0.68 0.685 0.69-2

-1.5

-1

-0.5

0

0.5

1

1.5

2TEST 61 - 3kA X/R=22.9, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure B75: FCL Voltage – 3kA FCL IN zoom

0 0.2 0.4 0.6 0.8 1

-4

-2

0

2

4

6

8TEST 61 - 3kA X/R=22.9, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase A With FCLPhase A NO FCL

Figure B76: Phase A – 4kA prospective vs. clipped

Page 186: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 73 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.3 0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48

-4

-2

0

2

4

6

TEST 61 - 3kA X/R=22.9, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase A With FCLPhase A NO FCL

Figure B77: Phase A – 3kA prospective vs. clipped

0 0.2 0.4 0.6 0.8 1 1.2-8

-6

-4

-2

0

2

4

6TEST 61 - 3kA X/R=22.9, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase B NO FCL

Figure B78: Phase B – 3kA prospective vs. clipped

Page 187: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 74 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.3 0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48 0.5

-6

-4

-2

0

2

4

TEST 61 - 3kA X/R=22.9, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase B With FCLPhase B NO FCL

Figure B79: Phase B – 3kA prospective vs. clipped

0 0.2 0.4 0.6 0.8 1 1.2-6

-4

-2

0

2

4

6TEST 61 - 3kA X/R=22.9, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase C With FCLPhase C NO FCL

Figure B80: Phase C – 3kA prospective vs. clipped

Page 188: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 75 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.3 0.32 0.34 0.36 0.38 0.4 0.42 0.44 0.46 0.48

-5

-4

-3

-2

-1

0

1

2

3

4

5

TEST 61 - 3kA X/R=22.9, FCL CLIPPING

Time [sec]

Line

Cur

rent

[kA

]

Phase C With FCLPhase C NO FCL

Figure B81: Phase C – 3kA prospective vs. clipped

0 0.2 0.4 0.6 0.8 1 1.2

-10

-5

0

5

10

TEST 61 - 3kA X/R=22.9, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B82: Source Voltage – 3kA

Page 189: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 76 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.34 0.35 0.36 0.37 0.38 0.39

-8

-6

-4

-2

0

2

4

6

8

TEST 61 - 3kA X/R=22.9, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure B83: Source Voltage – 3kA - POW

Page 190: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 77 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

10. APPENDIX C – Additional Fault Tests

10.1 Test 76 - Double Fault Sequence 20kA X/R=21

0.5 1 1.5 2 2.5 3 3.5-50

-40

-30

-20

-10

0

10

20

30

40

50TEST 76 - DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C1: Double fault sequence – 20kA – 2 seconds

0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1-50

-40

-30

-20

-10

0

10

20

30

40

50TEST 76 - DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C2: Double fault sequence – 20kA – first 20 cycles

Page 191: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 78 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

3.05 3.1 3.15 3.2 3.25 3.3 3.35 3.4

-40

-30

-20

-10

0

10

20

30

40

TEST 76 - DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C3: Double fault sequence – 20kA – second 20 cycles

0.5 1 1.5 2 2.5 3 3.5-6

-4

-2

0

2

4

6TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C4: Double fault sequence – 20kA – FCL Voltage

Page 192: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 79 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.7 0.75 0.8 0.85 0.9 0.95 1 1.05-6

-4

-2

0

2

4

6TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C5: Double fault sequence – FCL Voltage first 20cycles

3.05 3.1 3.15 3.2 3.25 3.3 3.35 3.4-6

-4

-2

0

2

4

6TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C6: Double fault sequence – FCL Voltage second 20cycles

Page 193: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 80 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.68 0.685 0.69 0.695 0.7 0.705 0.71 0.715

-4

-2

0

2

4

6TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C7: Double fault sequence – FCL Voltage first fault

3.05 3.06 3.07 3.08 3.09 3.1-6

-4

-2

0

2

4

TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C8: Double fault sequence – FCL Voltage second fault

Page 194: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 81 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.5 1 1.5 2 2.5 3 3.5 4

-10

-5

0

5

10

TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C9: Double fault sequence – Source Voltage

0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C10: Double fault sequence – Source Voltage first fault

Page 195: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 82 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

2.9 3 3.1 3.2 3.3 3.4 3.5

-10

-8

-6

-4

-2

0

2

4

6

8

10

TEST 76 DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C11: Double fault sequence – Source Voltage second fault

6 6.5 7 7.5 8 8.5 9 9.5 10120

130

140

150

160

170

180TEST 76 - DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

6 6.5 7 7.5 8 8.5 9 9.5 10-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure C12: HTS Coil Voltage and Current

Page 196: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 83 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

6 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 7120

130

140

150

160

170

180TEST 76 - DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

6 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 7-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure C13: HTS Coil Voltage and Current – first fault

8.5 8.6 8.7 8.8 8.9 9 9.1 9.2120

130

140

150

160

170

180TEST 76 - DOUBLE FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

8.5 8.6 8.7 8.8 8.9 9 9.1 9.2-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure C14: HTS Coil Voltage and Current – second fault

Page 197: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 84 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

10.2 Test 77 - 1.25s 80-cycle Fault 20kA X/R=21

0.5 1 1.5 2-50

-40

-30

-20

-10

0

10

20

30

40

50TEST 77 - 1.25s - 80 cycles FAULT - 20kA X/R=22, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C15: Endurance Test 1.25sec – 20kA

0.68 0.7 0.72 0.74 0.76 0.78 0.8-50

-40

-30

-20

-10

0

10

20

30

40

50TEST 77 - 1.25s - 80 cycles FAULT - 20kA X/R=22, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C16: Endurance Test 1.25sec – 20kA

Page 198: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 85 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.5 1 1.5 2-8

-6

-4

-2

0

2

4

6

8TEST 77 - 1.25s - 80 cycles FAULT - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C17: Endurance Test 1.25sec – 20kA – FCL Voltage

0.68 0.7 0.72 0.74 0.76 0.78 0.8

-6

-4

-2

0

2

4

6

TEST 77 - 1.25s - 80 cycles FAULT - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C18: Endurance Test 1.25sec – 20kA – FCL Voltage

Page 199: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 86 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.725 0.73 0.735 0.74 0.745 0.75-6

-4

-2

0

2

4

6TEST 77 - 1.25s - 80 cycles FAULT - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C19: Endurance Test 1.25sec – 20kA – FCL Voltage – zoom

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2

-10

-5

0

5

10

TEST 77 - 1.25s - 80 cycles FAULT - 20kA X/R=22, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C20: Endurance Test 1.25sec – 20kA – Source Voltage

Page 200: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 87 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.6 0.62 0.64 0.66 0.68 0.7 0.72 0.74 0.76 0.78

-10

-5

0

5

10

TEST 77 - 1.25s - 80 cycles FAULT - 20kA X/R=22, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C21: Endurance Test 1.25sec – 20kA – Source Voltage

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8120

130

140

150

160

170

180

190TEST 77 - 1.25s FAULT SEQUENCE - 20kA X/R=21, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure C22: Endurance Test 1.25sec – 20kA – HTS Coil V and I

Page 201: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 88 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

10.3 Test 78 – Second Double Fault Sequence 20kA X/R=21

0.5 1 1.5 2 2.5 3 3.5 4-50

-40

-30

-20

-10

0

10

20

30

40

50TEST 77 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C23: Second Double fault sequence – 20kA – 2 seconds

0.7 0.75 0.8 0.85 0.9 0.95 1 1.05-50

-40

-30

-20

-10

0

10

20

30

40

TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C24: Second Double fault sequence – 20kA – first fault

Page 202: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 89 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

3 3.05 3.1 3.15 3.2 3.25 3.3 3.35 3.4 3.45-50

-40

-30

-20

-10

0

10

20

30

40

TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

Line

Cur

rent

[kA

]

Phase APhase BPhase C

Figure C25: Second Double fault sequence – 20kA – second fault

0.5 1 1.5 2 2.5 3 3.5 4-8

-6

-4

-2

0

2

4

6

8TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C26: Second Double fault sequence – 20kA – FCL Voltage

Page 203: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 90 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1

-6

-4

-2

0

2

4

6

TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C27: Second Double fault sequence – 20kA – FCL Voltage

3 3.05 3.1 3.15 3.2 3.25 3.3 3.35 3.4 3.45 3.5

-6

-4

-2

0

2

4

6

8TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C28: Second Double fault sequence – 20kA – FCL Voltage

Page 204: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 91 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

3.25 3.255 3.26 3.265 3.27 3.275 3.28 3.285 3.29 3.295 3.3

-4

-2

0

2

4

6TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C29: Second Double fault sequence – 20kA – FCL Voltage

3.26 3.265 3.27 3.275 3.28 3.285

-4

-2

0

2

4

6TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

DIF

FER

EN

TIA

L V

OLT

AG

E A

CR

OS

S F

CL

[kV

]

Phase APhase BPhase C

Figure C30: Second Double fault sequence – 20kA – FCL Voltage

Page 205: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 92 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.5 1 1.5 2 2.5 3 3.5 4

-10

-5

0

5

10

TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C31: Second Double fault – 20kA – Source Voltage

3 3.05 3.1 3.15 3.2 3.25 3.3 3.35 3.4 3.45 3.5

-10

-5

0

5

10

TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C32: Second Double fault – 20kA – Source Voltage

Page 206: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 93 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1 1.15

-10

-5

0

5

10

TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

BU

S V

OLT

AG

E S

OU

RC

E S

IDE

[kV

]

Phase APhase BPhase C

Figure C33: Second Double fault – 20kA – Source Voltage

0 0.5 1 1.5 2 2.5 3 3.5 4130

135

140

145

150

155

160

165

170

175

180TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

0 0.5 1 1.5 2 2.5 3 3.5 4-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure C34: Second Double fault – 20kA – HTS Coil V and I

Page 207: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 94 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1130

135

140

145

150

155

160

165

170

175

180TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure C35: Second Double fault – 20kA – HTS Coil V and I

2.4 2.5 2.6 2.7 2.8 2.9130

135

140

145

150

155

160

165

170

175

180TEST 78 - DOUBLE FAULT SEQUENCE - 20kA X/R=22, FCL IN

Time [sec]

HTS

CU

RR

EN

T [A

]

2.4 2.5 2.6 2.7 2.8 2.9-20

-15

-10

-5

0

5

10

15

20

HTS

VO

LTA

GE

[V]

Figure C36: Second Double fault – 20kA – HTS Coil V and I

Page 208: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 95 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

11. APPENDIX D – Powertech Source and Load Impedances

No. One shot I2t@30C

X/R at20C

Continuouscurrent

# A B C kArms kApeak A2s - Arms1 0.0021 0.0022 0.0021 84.7 244 3.8E+11 95 40002 0.0044 0.0042 0.0040 84.9 237 1.8E+11 90 40003 0.0083 0.0082 0.0082 80.2 224 1.2E+11 89 40004 0.0165 0.0166 0.0165 72.2 201 5.0E+10 84 30005 0.0320 0.0339 0.0325 60.2 168 2.2E+10 69 27006 0.0630 0.0671 0.0609 45.2 126 1.1E+10 79 19007 0.1316 0.1292 0.1315 32.0 89 5.8E+09 75 19008 0.2590 0.2640 0.2590 23.0 64 4.2E+09 89 11009 0.5300 0.5180 0.5210 16.4 46 1.8E+09 94 75010 1.0400 1.0290 1.0360 11.6 32 7.6E+08 79 45011 2.1000 2.0700 2.1000 7.5 21 4.8E+08 82 30012 4.2200 4.2100 4.2300 4.5 12 2.0E+08 82 22013 8.3900 8.3100 8.3100 2.5 7 1.2E+08 83 16014 16.9200 17.0900 16.9600 1.3 4 5.8E+07 83 11015 33.6900 34.3500 34.1000 0.7 2 3.0E+07 77 80

Sum 1-13 16.80 16.66 16.71 - - - -

Reactance @60 Hz at phase

MaximumCurrent

Table D1: Source Reactance Values

mOhms kA MJR1 4.5 20 16R2 8.5 20 32R3 18.1 20 64R4 31.3 20 72R5 70.2 20 144R6 122 20 128R7 269 18.3 144R8 488 9.3 128R19 888 4.6 144R10 2132 2.3 128R11 4247 1.2 64

Table D2: Source Resistor Values

Page 209: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 96 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

NameA phaseOhms

B phaseOhms

C phaseOhms

EnergyJ

ImaxArms

IcontArms

LR1 2.06 2.08 2.08 6.0E+06 750 105LR2 4.16 4.16 4.19 1.2E+07 750 105LR3 8.27 8.35 8.38 2.4E+07 750 105LR4 16.80 16.92 16.77 4.8E+07 750 105LR5 29.50 29.70 29.60 6.0E+07 600 85LR6 63.00 63.10 63.20 3.0E+07 300 50

Table D3: Load Resistor Values

Page 210: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report: ZP/TR-2008/01 Rev: 1 Page: 97 of 97

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

List of Revisions Revision Date Action Modified Page

1 11/07/08 First Released

Page 211: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

F‐1

APPENDIX F: Zenergy Power HTS FCL High Voltage Field Test

Page 212: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 1 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Test Report

Reporting Center (full name and address): Zenergy Power Inc. 379 Oyster Point Blvd., Suite 1 South San Francisco, CA USA 94080-1961 Tel.: +1-650-615-5700

Responsible Person: Francisco De La Rosa

Project Name: CEC Avanti

Document Title: High Voltage Testing SCE SSID-ESI

Document Ref.No.: ZP/TR-2008/04 Reg: # Page 1

Date of issue: 12/17/08 Classification: Confidential No. of pages: 44

Client(s): CEC/SCE

Author(s): F. De La Rosa

F. Moriconi

W. Schram

A. Singh

Approved: F. Moriconi Order No.:

Distribution: A. Kamiab (SCE), Alan Hood (SCE), K. Smedley (CEC UC Irvine), F. Moriconi, W. Schram, R. Lombaerde, A. Singh, M. Levitskaya, F. De La Rosa, A. Singh (ZP USA)

Distribution page 1: B. Nelson, W. Gibson, A. Rodriguez, S. Ramsay (ZP USA), F. Darmann (ZP

AUS), C. Buehrer (ZP DE)

Keywords: Fault Current Limiter, High Voltage tests, Lightning impulse test, full wave, chopped wave, BIL, Avanti Circuit

Summary: This report presents the results of the additional high voltage tests conducted to the CEC Avanti FCL at SCE SSID-ESI facilities in Westminster, CA. Testing included a 5 kV DC insulation test followed by reduced and full lightning and chopped waves per IEEE C57.12.01-2005 and ending with a 15 kV applied voltage test.

fmoriconi
Highlight
fmoriconi
Highlight
fmoriconi
Highlight
Page 213: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 2 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Contents Page

1. APPLICABILITY.......................................................................................3

2. DOCUMENTATION..................................................................................3

3. ACRONYMS AND DEFINITIONS ............................................................3 3.1 ACRONYMS......................................................................................................................3 3.2 DEFINITIONS ....................................................................................................................3

4. GENERAL ................................................................................................3

5. INSULATION TESTS ...............................................................................4 5.1 FCL AC TERMINALS.........................................................................................................4 5.2 POTENTIAL TRANSFORMERS (PT’S) ..................................................................................4

6. LIGHTNING IMPULSE TESTS.................................................................5

7. IMPULSE VOLTAGE TEST RESULTS....................................................6

8. CONCLUSIONS .......................................................................................6

LIST OF TABLES AND FIGURES ..................................................................7

LIST OF TABLES AND FIGURES ..................................................................7

9. APPENDIX 1 ............................................................................................9

Page 214: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 3 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

1. Applicability Saturable-core HTS Fault Current Limiter 15kV class, 750A.

2. Documentation [1] Test Plan for Additional FCL Testing, ZP/ER_2008/06 Rev 1, ZP

Internal Report [2] NETA-Acceptance Testing Specifications for Electrical Power

Distribution Equipment and Systems, 2007

3. Acronyms and definitions

3.1 Acronyms FCL Fault Current Limiter HTS High Temperature Superconductor CEC California Energy Commission SCE Southern California Edison

3.2 Definitions Ambient temperature: this is the temperature of the air surrounding the FCL. For the purposes of IEEE Std C57.16-1996, it is assumed that the temperature of the cooling air (ambient temperature) does not exceed 40 o C and the average temperature of the cooling air for any 24 hour period does not exceed 30 o C.

4. General The results from the additional high voltage and insulation tests

conducted to the CEC Avanti FCL are described in this report. HV tests were successful and FCL insulation and AC voltage withstand after impulse voltage tests was preserved. All tests were based on the test plan described in [1].

Page 215: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 4 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

5. Insulation tests

5.1 FCL AC terminals Insulation of the FCL was tested as part of a routine check SSID-ESI

carries out prior to subjecting an object to BIL testing. A 1000 VDC insulation resistance (megger) test was applied between every phase on the source side and ground during one minute and the resultant insulation resistance from the instrument display was read. The results obtained are described in table 1. All of them are above the minimum 5000MΩ recommended by NETA [2] for equipment with operating voltages up to 15 kV.

A Phase to Ground Insulation Resistance GΩ

B Phase to Ground Insulation Resistance GΩ

C Phase to Ground Insulation Resistance GΩ

156 151 206

Table 1. Insulation resistance test on the FCL

5.2 Potential Transformers (PT’s) Insulation resistance was also practiced on the PT’s located in the small

enclosure on the load side of the FCL. The insulation of these PT’s had not been tested previously. Tests were conducted on the primary and secondary of the PT’s and yielded results as per table 2. The obtained insulation levels are extraordinarily high, well above the 5000 MΩ desired level [2].

Page 216: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 5 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

PT’s Primary Side PT’s Secondary Side

A Phase to

Ground Insulation

Resistance GΩ

B Phase to

Ground Insulation

Resistance GΩ

C Phase to

Ground Insulation

Resistance GΩ

A Phase to

Ground Insulation

Resistance GΩ

B Phase to

Ground Insulation

Resistance GΩ

C Phase to

Ground Insulation

Resistance GΩ

426 595 550 376 408 496

Table 2. FCL PT’s insulation resistance test

6. Lightning impulse tests These tests consisted on the application of chopped wave impulse tests

on every phase of the FCL between a common point connecting source and load ends and ground. The tests comprised:

a. One reduced (1.2 x 50 μs) full wave– 50% or 55 kV peak wave b. One full (1.2 x 50 μs) wave – 100% or 110 kV peak wave c. One reduced chopped wave – 50% or 60 kV peak wave d. Two full chopped waves - 100% or 120 kV peak waves e. Two full (1.2 x 50 μs) waves (preferably within 10 min after the

last chopped wave)

With chopped wave crest voltage and time to chop as indicated in table 1.

Page 217: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 6 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Table 3: Lightning Impulse Voltage amplitude and time to chop used in the tests, per EEE Std C57.16-1996 [1]

The tests were conducted with no DC bias current on the HTS coil.

7. Impulse voltage test results Test results assembled and documented by SSID are presented in Appendix A. It is noteworthy to notice that after all insulation enhancements performed on the FCL, it successfully passed the lightning impulse tests required in the test plan.

8. Conclusions The tests conducted at SCE SSID high voltage laboratory on the CEC Avanti FCL are described in this report. The FCL endured well and passed the applied tests.

Page 218: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 7 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

List of Tables and Figures TABLE 1. INSULATION RESISTANCE TEST ON THE FCL............................................ 4 TABLE 2. FCL PT’S INSULATION RESISTANCE TEST................................................ 5 TABLE 3: LIGHTNING IMPULSE VOLTAGE AMPLITUDE AND TIME TO CHOP USED IN THE

TESTS, PER EEE STD C57.16-1996 [1] ........................................................ 6

Page 219: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 8 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

List of Revisions

Revision Date Action Modified Page 1 12/17/08 Released

Page 220: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 9 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9. APPENDIX 1

SSID REPORT ON HIGH VOLTAGE TESTS TO THE CEC AVANTI FCL

Page 221: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 10 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 222: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 11 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 223: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 12 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 224: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 13 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 225: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 14 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 226: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 15 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 227: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 16 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 228: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 17 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 229: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 18 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 230: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 19 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 231: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 20 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 232: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 21 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 233: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 22 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 234: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 23 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 235: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 24 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 236: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 25 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 237: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 26 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 238: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 27 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 239: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 28 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 240: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 29 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 241: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 30 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 242: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 31 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 243: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 32 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 244: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 33 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 245: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 34 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 246: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 35 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 247: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 36 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 248: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 37 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 249: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 38 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 250: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 39 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 251: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 40 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 252: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 41 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 253: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 42 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 254: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 43 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 255: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Zenergy Power Inc. Report #: ZP/TR-2008/04 Rev: 1 Page: 44 of 8

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Page 256: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

G‐1

APPENDIX G: Zenergy Power HTS FCL Operation Manual

Page 257: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

Fault Current Limiter Operation Manual June 2011

www.zenergypower.com

Page 258: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 2 of 19

Operation Manual Reporting Entity: Zenergy Power Inc.

379 Oyster Point Boulevard, Suite 1, South San Francisco, CA 94080 USA

Responsible Person: William Schram

Project Name: SCE Avanti Fault Current Limiter

Document Title: SCE Avanti Fault Current Limiter Operation Manual

Document Ref. No.: ZP/02-2009-04-06

Date of issue: 06/04/2009

Client(s):

Author(s): William Schram Approved:

Distribution: Southern California Edison

Summary This manual is intended to provide instructions for setup, startup, shutdown and routine

maintenance of the Zenergy Power Inc. Fault Current Limiter.

Page 259: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 3 of 19

List of Revision

Revision Date Action Modified Page 1 06/04/09 Released

Page 260: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 4 of 19

Contents

1 Applicability 5 2 Acronyms 5 3 Description of the HTS Fault Current Limiter 5 4 Setup Auxiliary Power and Communications 7 4.1 Auxiliary Power 7 4.2 Fiber Optic Communications Via Modbus 9 5 Cool Down of HTS Magnet in Cryostat 11 6 Startup Sequence 13 7 Shutdown Sequence 14 8 Maintenance 15 8.1 Maintenance Schedule 15 8.2 Maintenance Contacts 16 9 Spare Parts List 17 10 Bill of Materials 18 11 References 19

Page 261: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

1 Applicability This manual is intended to provide instructions for setup and shutdown of the Zenergy Power Inc. Fault Current Limiter. Also provided are the maintenance intervals for components and a spare parts list.

2 Acronyms FCL Fault Current Limiter

HTS High Temperature Superconductor

3 Description of the HTS Fault Current Limiter Figure 1 depicts the fundamental principle of the HTS Fault Current Limiter. During normal operation, a single HTS coil provides the DC bias to maintain a saturated core condition in the two cores of every phase of the FCL.

Notice that for a three phase configuration with the cores arranged in the spider arrangement shown in figure 2, six cores limbs pass through the encapsulated cryostat containing the DC coil and a similar number of external core limbs (two per phase) close the magnetic circuit.

Figure 1: Dual Iron Cores Saturated by one HTS DC coil in a single phase FCL configuration

Page 262: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 6 of 19

Figure 2: CEC-Avanti Three Phase Spider Configuration FCL

Under normal operating conditions, the “working region” of the FCL on the B-H curve is as shown in figure 3. AC current boosts the magnetic field in one the cores and bucks it on the other. The inductance of the coil is proportional to dB/dH. Therefore in a simple way we can think of a low AC coil inductance when the core is driven into deep saturation and of a high AC coil inductance when the core is taken out of saturation.

Therefore, the ZP FCL shows fundamentally low insertion impedance under normal operating conditions while it will attain high inductance values under a fault as the current swings between positive and negative peak values. This will drive the AC coils through high inductance regions as they transit over high slope regions on the B-H plane. This is illustrated in figure 4 where the magnetic flux is plotted versus current.

Figure 3: Operating region of the saturable-core type FCL

Page 263: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 7 of 19

Figure 4: Flux versus current under a fault on the ZP FCL

4 Setup Auxiliary Power and Communications

4.1 Auxiliary Power The auxiliary power cable is fed through the bottom of the enclosure base plate into cutout box containing the terminal blocks, as shown in Figures 5 and 6.

Page 264: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 8 of 19

Figure 5: Auxiliary Power Cable Feed Through

Figure 6: Auxiliary Power Terminal Blocks

Once the auxiliary power is wired as shown above be sure to confirm the phasor rotation is negative. Compressor functionality in the FCL is rotation specific.

FCL Load

Source

Disconnect switch

Page 265: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 9 of 19

4.2 Fiber Optic Communications Via Modbus The fiber optic communications to the FCL are transmitted over a single-mode fiber optic cable. This cable is connected inside the electronics cabinet to a Fiber-to-Ethernet converter module, which then connects directly to the programmable automation controller (PAC).

Modbus Connection: Modbus slave set up on IP Address 192.168.140.31, Service Port 502, Address 2.

Modbus Data List:

Measurements Data Type Address Description Status Units

FCLBypass Boolean 100001 True indicates the FCL should be bypassed OK T/F

Heartbeat UInt16 400091 Heartbeat counter that increments by 1 every 200 milliseconds OK numerical

Top Cover 1 Temp Single F400001 Signal from Type-K TC on Cryostat Lid OK Kelvin

Top Cover 2 Temp Single F400003 " OK Kelvin

Ambient Temp Single F400005 Unconnected signal N/A N/A

Digital Input Lines UInt16 400092 Collection of digital inputs to the PAC (listed below without address) OK NIL

Compressor 1 Relay Status Boolean LSB0

Relay controlling power to compressor 1 OK T/F

Compressor 2 Relay Status Boolean LSB1

Relay controlling power to compressor 2 OK T/F

PS2 Relay Status Boolean LSB2 Relay putting PS1 in circuit OK T/F

PS1 Relay Status Boolean LSB3 Relay putting PS2 in circuit OK T/F

UPS Low Battery Boolean LSB4 UPS status OK T/F

UPS On Battery Boolean LSB5 UPS status OK T/F

UPS Fault Battery Boolean LSB6 UPS status OK T/F

Backup Charger Status Boolean LSB7

Auto-actuated relay indicating presence of 120 VAC wall-power supply OK T/F

HTS Backup Enable Relay Status Boolean LSB8

Relay putting HTS Backup battery in circuit OK T/F

PS2 Manual Switch Status Boolean LSB9

Status of switch to manually control PS2 contactor OK T/F

PS1 Manual Switch Status Boolean LSB10

Status of switch to manually control PS1 contactor OK T/F

FCL Bypass Relay Status Boolean LSB11

Unwired placeholder for FCL Bypass switch status readback N/A N/A

Top Cover Heater Relay Status Boolean LSB12

Status of Top Cover heater power contactor OK T/F

HTS Current Single F400021 Current through DC Coil OK Amps

HTS Voltage Single F400023 Voltage across DC Coil OK Volts

Total DC Current Single F400025 Current through DC Coil and dump resistor OK Amps

VTap 1 Single F400027 Voltage diffrential between coil tap 1 and 9 OK Volt

VTap 2 Single F400029 Voltage diffrential between coil tap 2 and 9 OK Volt

VTap 3 Single F400031 " OK Volt

VTap 4 Single F400033 " OK Volt

VTap 5 Single F400035 " OK Volt

Page 266: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 10 of 19

VTap 6 Single F400037 " OK Volt

VTap 7 Single F400039 " OK Volt

VTap 8 Single F400041 " OK Volt

VTap Ref Single F400043 Absolute voltage at tap 9 N/A N/A

LN2 Pressure Single F400007 Nitrogen Pressure inside cryostat OK Torr

Vacuum Pressure Single F400009 Vacuum pressure inside insulating walls of cryostat N/A N/A

Battery Charging Current Single F400011 Current charging backup battery OK Amps

LN2 Level Single F400013 Level of liquid nitrogen inside cryostat OK cm

Phase A Voltage Single F400045 OK V rms

Phase B Voltage Single F400047 OK V rms

Phase C Voltage Single F400049 OK V rms

Phase A Current Single F400051 OK A rms

Phase B Current Single F400053 OK A rms

Phase C Current Single F400055 OK A rms

UPS Voltage Single F400015 Voltage supplied by UPS to PAC and some meters OK Volt

Coil Top Temperature Single F400057 HTS Coil Temperature at top OK Kelvin Coil Bottom Temperature Single F400059 HTS Coil Temperature at bottom OK Kelvin Coldhead 1 Temperature Single F400061

Cryo-cooler 1 temperature (inside cold head) OK Kelvin

Coldhead 2 Temperature Single F400063

Cryo-cooler 2 temperature (inside cold head) OK Kelvin

PS1 Voltage Single F400065 Voltage reading from PS1 OK Volt

PS1 Current Single F400067 Current reading from PS1 OK Amp

PS2 Voltage Single F400069 Voltage reading from PS2 OK Volt

PS2 Current Single F400071 Current reading from PS2 OK Amp

Red Alarm Status UInt16 400094 Red Alarm Status bits (give reason for bypass and shutdown)

UPS Low Battery LSB0 UPS operating on battery and low battery indicator is on OK T/F

UPS Fault LSB1 UPS Faults occur (unused) N/A

UPS Voltage LSB2 UPS voltage supply is out of bounds OK T/F

HTS Temp LSB3 HTS Coil temperature rises above critical level OK T/F

VTap Quench LSB4 HTS Coil voltage differentials above critical level OK T/F

HTS Voltage LSB5 HTS Coil voltage rises above critical level OK T/F

HTS Current LSB6 HTS Coil current drops below critical level OK T/F

HTS Backup Present LSB7

HTS Backup battery drops out of circuit OK T/F

HTS Backup Duration LSB8

HTS Coil running on battery backup longer than configurable duration N/A

240 VAC Supplied LSB9 Wall power not available OK T/F

PT Drop LSB10 Voltage drop across FCL above limit (unused) N/A

User Shutdown LSB11 User initiated shutdown OK T/F

Key:

Page 267: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 11 of 19

Single is a 32-bit floating point number UInt16 is 16-bit unsigned integer The Uint16 is used in two places to hold 16 bits of digital status data,

but for implementation efficiency reasons it is mapped to a UInt memory space in modbus

5 Cool Down of HTS Magnet in Cryostat The cryostat requires approximately 500 liters of gaseous and liquid nitrogen to cool down and fill the vessel to its operating level. Nitrogen dewars (liquid nitrogen containers) can be procured from Praxair, Air Products, or Airgas. The industry standard is the 200-liter Dewar illustrated in Figure 6; the cryostat requires three of these to fill.

Figure 7: Liquid Nitrogen Dewars

To fill the cryostat, remove the ISO KF 25 clamp and cap from the KF 25 flange located above the cryostat vacuum valve and adjacent to the recondenser basin. In Image of the KF 25 flange is shown below in Figure 8.

Page 268: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 12 of 19

Figure 8: Liquid Nitrogen Fill Port

Connect the appropriate fill hose and purge the vessel with cold gaseous nitrogen for two hours. Then switch to liquid nitrogen and begin filling. The vessel should cool at a rate no greater than 50 Kelvin per hour; this information can be acquired from the bottom coil temperature sensor readout on the Lab View User Interface.

Once the bottom coil temperature reads 100 Kelvin the cool-down rate can be neglected and the vessel can be filled as fast as the liquid nitrogen can be delivered. The stop point for filling is 83.9 centimeters on the nitrogen level readout; this value is 100 percent of the calibration range above this height no sensing is available. When the fill height is achieved, ensure all flanges on the lid of the cryostat are tightly sealed.

Page 269: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 13 of 19

6 Startup Sequence Begin by turning on all switches of the electronics cabinet, as shown in Figure 9.

Figure 9: Power Switches in ON Position

Currently the controller receives commands from a remote terminal operated by Zenergy Power for completion of the startup sequence. This is a safety precaution to ensure the superconducting magnet is not energized without a Zenergy Power staff member present.

A Zenergy representative will then turn on Compressor One. This is accomplished by closing the switch for Compressor One located on the LabVIEW user interface. A relay should be heard closing and then the compressor will turn on. Next the HTS magnet will be manually ramped to a 100 amp bias on the LabVIEW user interface. This will conclude the Startup Sequence for the fault current limiter. Now the FCL can be switched into the circuit.

Page 270: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 14 of 19

7 Shutdown Sequence In the event of a decommissioning or auxiliary power failure, the fault current limiter will initiate the shut down procedure. This implies a shut down can be initiated simply by opening the auxiliary power circuit. First the disconnect relay will trip to initiate the automated disconnect of the FCL and an alert will be sent via the modbus communication indicating the FCL is shutting down. Next the battery backup will ramp down the superconductor coil. Once confirmation has been made that ramp down of the magnet has completed, this is done by visually confirming the HTS Coil Amperage meter is at zero amps on the display window, turn all switches on the electronics cabinet off as shown in Figure 10 below.

Figure 10: Power Switches in OFF Position

Page 271: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 15 of 19

8 Maintenance Maintenance is to be performed by Zenergy Power staff and will require the participation and assistance of SCE in scheduling a bypass of the FCL.

8.1 Maintenance Schedule

Figure 11: Maintenance Schedule, Assuming a March 3rd Commissioning Date

HVAC System (Pages 15-18 of the Liebert Intelecool2 User Manual)

• Filter: Replace quarterly.

• Blower: Check quarterly for debris, the shaft should rotate freely.

• Economizer: Check quarterly for debris.

• Refrigeration: Check quarterly for signs of wear and proper operation.

Cryomech Compressor and Cold Head Assemblies:

• Compressor Filter: Every quarter or 2000 hours of operation replace compressor filter.

• Cold Head: After four quarters or 10,000 hours of operation the piston assembly in the cold head should be inspected by a Cryomech trained service representative.

• After eight quarters of operation or 20,000 hours a complete overhaul of the piston assembly is necessary. The cold head should be extracted from the roof of the FCL enclosure and shipped to Cryomech for service. In advance of this service a replacement cold-head assembly should be procured.

Lambda Power Supplies: Power Electronics in the power supply are rated for a four-year operating life or sixteen quarters. After the power supply has been in service for four years replace the units to ensure no discontinuity in service.

Page 272: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 16 of 19

8.2 Maintenance Contacts

Primary Contact

Company: Zenergy Power

Office Phone (8-5): 650-615-5720

Address: 379 Oyster Point Blvd, Suite 1

South San Francisco

Emergency Contact: Franco Moriconi

Emergency Phone: 510-334-9534

Service Contacts

Company: Liebert Corporation, Associates of San Francisco

Tech Support: 1-800-543-2778

Address: 1050 Dearborn Drive

P.O. Box 29186

Columbus, OH. 43229

Company: Cryomech, Inc.

Office: 315-455-2555

Address: 113 Falso Drive

Syracuse, NY. 13211

Company: Lambda Americas, Inc.

Office: 732-922-9300

Address: 405 Essex Road

Neptune, NJ. 07753

fmoriconi
Highlight
Page 273: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 17 of 19

9 Spare Parts List

1. Air filter for the Cryomech compressor, two units

2. Air filter for HVAC, one unit per

3. 5 amp fuse

4. 10 amp fuse

5. 20 amp fuse

6. Sidewalk Bolts, 0.25 inch DIA by 2 inch

7. NI cFP-2200 National Instruments Controller

8. Replacement cold-head, Modified AL-300

9. Potential transducers spare 15kV fuse

10. 24Volt Relay

11. 120 volt Relay

Page 274: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 18 of 19

10 Bill of Materials Item number Part number Description Default/QTY.

1 CEC-08-0000 CEC-FCL-092408 1

2 CEC-08-0001 Reactor Assembly 1

3 CEC-08-0002 DC Cables 4

4 CEC-08-0003 AUX Power Box 1

5 CEC-08-0004 Baseplate Assembly 1

6 CEC-08-0005 AC Current Transducer Model CTDZ 3

7 CEC-08-0006 Pie Core Assembly 6

8 CEC-08-0007 900 Amp Bushing 052008 6

9 CEC-08-0008 Deadbreak stand 6

10 CEC-08-0009 Step Enclosure 1

11 CEC-08-0010 Electronics Assembly 1

12 CEC-08-00101 Compressor 2

13 CEC-08-00102 Enclosure Power Supply 1

14 CEC-08-00103 AC Unit 1

15 CEC-08-00104 U-channel 2

16 CEC-08-00105 Lapp Insulator 4

17 CEC-08-0011 02-1002-2002-05 AC Coil 050708 6

18 CEC-08-0012 Enclosure 051208 1

19 CEC-08-0013 Busbar Shorter 3

20 CEC-08-0014 Thermalsyphon Side 041508 1

21 CEC-08-0015 Cryostat 1

22 CEC-08-0016 He Hose 2

23 CEC-08-0017 HVAC System 1

Page 275: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/02-2009-04-06 Page 19 of 19

11 References “Liebert InteleCool 2: User Manual – Outdoor Wall-Mount Air Conditioner, 1.5-5 Tons, 50-60 Hz”, HVAC Manual

“Cryomech AL300 Cryogenic Refrigerator – Installation, Operation, Routine Maintenance Manual”, Cryo-Refrigeration Manual

“Fieldpoint Operating Instructions and Specifications –

CFP-2200/2210/2220”, Controller Manual from National Instruments

“Material Safety Data Sheet – Liquid Nitrogen”, Air Products.

MSDS number 30000000010

Page 276: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

H‐1

APPENDIX H: Zenergy Power HTS FCL Cryostat Evacuation and Moisture Removal Procedure

Page 277: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 1 of 18

Engineering Report Cryostat Evacuation and Moisture Removal Process June 2011

www.zenergypower.com Confidential & Proprietary

Page 278: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 2 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Engineering Report Status (Final or Draft): DRAFT

Reporting Entity: Zenergy Power Inc.

379 Oyster Point Boulevard, Suite 1, South San Francisco, CA 94080 USA

Responsible Person: Amandeep Singh

Project Name: SCE Avanti Fault Current Limiter

Document Title: Cryostat Evacuation and Moisture Removal Process

Document Ref. No.: ZP/ER-2009-09A

Date of issue: MM/DD/YYYY

Client(s): Zenergy USA Internal

Author(s): Erica Klett

Distribution: Internal Approved: F. Moriconi

Executive Summary The FCL at Shandin substation required Liquid Nitrogen fill. This report describes the process for evaporating the remaining LN2, removing moisture and vacuuming system to acceptable level for the Cryomech Cold-Head test. The LN2 chamber was successfully evacuated, to a final vacuum level of ~2mTorr.

fmoriconi
Highlight
Page 279: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 3 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

List of Revisions

Revision Date Action Modified Page

A MM/DD/YY Initial Release

Page 280: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 4 of 18

Contents 1 Scope Error! Bookmark not defined. 2 Acronyms 5 3 Process 5 4 Initial Conditions 5 5 Required Tools, Test Equipment and Drawings 5 5.1 Tools and Equipment 5 5.2 Test Equipment 5 5.3 Drawings or Schematics 6 6 Hazards, PPE and Equipment Protection 6 6.1 Hazards 6 6.2 Personal Protective Equipment 6 6.3 Equipment Protection 6 7 Isolation and Shutdown Procedure for LN2 Wire Repair 6 8 Steps to Troubleshoot and Provide Power to LN2 Heaters 6 9 Liquid Nitrogen evaporation and Moisture Removal Process 10 9.1 LN2 Evaporation Observations: 11 9.2 Evaporation Results 12 10 Remove Moisture and Heat to Ambient Temperature 13 11 Repairing the Electrical Plug for the LN2 Heater Wires 15 12 Evacuating the LN2 Chamber 16 13 Conclusion 18 14 References 18 15 Index of Figures 18 16 Index of Tables 18

Page 281: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 5 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

1 Objective In order to service and refill the Fault Current Limiter Liquid Nitrogen chamber, the remaining liquid must be removed and all the moisture evaporated. Heat, warm nitrogen gas and vacuum pumping can aid the evaporation process and remove the moisture.

2 Acronyms FCL Fault Current Limiter LN2 Liquid Nitrogen AMI American Magnetics, Inc. HTS High Temperature Superconductor PPE Personal Protective Equipment

3 Process 1. Evaporate LN2 2. Remove Moisture 3. Achieve Ambient Temperature 4. Vacuum Pump System

4 Initial Conditions The FCL had about 25cm of remaining LN2 in the vessel. The Liquid Nitrogen chamber has a heater coil installed to heat the internal chamber and assist in evaporating the LN2. However, it was discovered after inspection, that the electrical connection for the LN2 heaters was disconnected from the input power. In addition, it appeared that the wires were too short to reach the connector to attach a power source. Before we could continue, modification of the wire connections was required to connect power to heat the coils.

5 Required Tools, Test Equipment and Drawings

5.1 Tools and Equipment • Screwdriver • (2) 10 foot pieces of electrical wire • (4) Alligator Clips • Insulated material for wire repair • Electrical tape • Heat shrink tubing • Heat gun • Space heater • Vacuum sealed cryogenic hose • KF clamp • Compressed Nitrogen gas • Hose for Nitrogen bottle

5.2 Test Equipment • Fluke Clamp Meter

Page 282: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 6 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

• Fluke Multimeter

5.3 Drawings or Schematics Electrical Schematic for Heater Circuit

6 Hazards, PPE and Equipment Protection

6.1 Hazards • Regardless of protective equipment, never touch live electrical parts. • Compressed Nitrogen gas is a material considered hazardous by the OSHA Hazard Communications

Standard (29 CFR 1910.1200). Effects of a Single (Acute) Overexposure: o Inhalation. Asphyxiant. Effects are due to lack of oxygen. Moderate concentrations may cause

headache, drowsiness, dizziness, excitation, excess salivation, vomiting, and unconsciousness. Lack of oxygen can kill.

6.2 Personal Protective Equipment When dealing with the compressed Nitrogen, the following PPE should be used: • Skin Protection: Wear work gloves when handling cylinders and metatarsal shoes for cylinder

handling. Select in accordance with OSHA 29 CFR 1910.132 and 1910.133. • Eye/Face Protection: Wear safety glasses when handling cylinders. Select in accordance with

OSHA 29 CFR 1910.133.

6.3 Equipment Protection Referred to design of heaters to verify electrical limitations and discussed our process with management. It was decided that it was safe for the equipment inside the chamber to be heated for as long as required.

7 Isolation and Shutdown Procedure for LN2 Wire Repair Removed all power to the plug and heater circuit (already disconnected)

8 Steps to Troubleshoot and Provide Power to LN2 Heaters

1. Reviewed schematic for heaters 2. Heaters are rated for 230V and 190 Ohms, current 1.217 Amps, 280 Watts 3. Measured resistance of internal heaters to confirm proper value per design:

a. Brown and Blue wires = 190ohms b. Brown and Yellow/Green wires = Infinity c. Blue and Yellow/Green wires = Infinity

4. Determined that the Brown and Blue wires are connected to the heaters, which is consistent with the available circuit documentation.

5. Very slowly and carefully lifted the outer flange and the feed-through away, to make space for repair. See Figure 1 below.

Page 283: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 7 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 1: Carefully removed plug to assess repair

Figure 2: Wires for heaters are disconnected and too short to reach plug

Page 284: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 8 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

6. Tried pulling out the heater wires with no success. a. Made connections locally (right inside the hole) with insulated alligator clips. Figure 2 below shows

connection. b. Provided insulation between connections for additional safety

Figure 3: Made connection to heaters via alligator clips

7. Applied 238VAC momentarily to energize the heater coil and measured current with a Fluke meter. a. Current Measured: 1.20 Amps (consistent with the specifications for the heaters) (See Figure

6) 8. Applied constant 238VAC to energize the heater coil and apply heat to the LN2 chamber.

Page 285: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 9 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 4: Checking phase to ground voltage

Figure 5: Voltage source used to energize heaters

Page 286: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 10 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 6: Clamp meter measuring current across heater circuit, with ~238 Volts applied

9 Liquid Nitrogen evaporation and Moisture Removal Process

1. Applied ~238V to heaters to apply local heat to LN2 chamber. 2. Attached a clamp meter for continuous measurement of heater current. 3. Connected an air source (Heat Gun) to the port of the LN2 chamber to inject air into the space, see

Figure 7. 4. Monitored LN2 level on the AMI 186 and FCL monitor. Refer to Figure 8 for plot of data.

Figure 7: Ambient cool air injected into port of LN2 chamber

Page 287: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 11 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

9.1 LN2 Evaporation Observations: When the gauges showed that the LN2 level reached zero, we measured the LN2 level with the dipstick. It was discovered that the measured level did not match the gauge reading. After extrapolating the data, we determined that it would take several more hours to completely remove the moisture from the chamber, according to the dipstick measurements. We installed a floor heater in the FCL cabinet, to increase the ambient air temperature that would go into the heat gun attached to the chamber. Figure 9 shows the floor heater.

Figure 8: Plot of LN2 level over time, with applied heat

Page 288: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 12 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 9: Area heater to safely heat the ambient air for the heat gun

9.2 Evaporation Results The FCL was left overnight (11/3) in the following configuration:

• Heat gun attached to a fill port (cool temp setting) • Floor heater placed inside the closed FCL cabinet • LN2 heater coil energized with 238 Volts

When we returned to the site at 7AM the next day (11/4), we measured the LN2 level with a dipstick. The dipstick outer wall was dry and the tip was slightly moist. Early morning (11/4) data showed that the HTS top and bottom temperatures converged, which further indicated that most of the nitrogen liquid had evaporated. Table 1 lists the HTS temperatures and associated time, as measured by the PLC. Figure 10 is the graphic illustration of the data table. TIME (Military) HTS TOP (Kelvin) HTS BOTTOM (Kelvin) 0325 119 129 0537 158 168 0813 183 184 0902 195 206 1011 214 233 1102 226 233 1200 239 242 1305 252 252 1400 262 262 1452 270 272

Table 1: HTS temperature readings as captured by the PLC system

Page 289: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 13 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 10: HTS Temperatures Rising Over Time

10 Remove Moisture and Heat to Ambient Temperature At 10:00am a bottle of “warm” compressed nitrogen was attached to the LN2 chamber to begin warming of the space. The warm nitrogen was connected and LN2 heaters remained on, for about 5.5 hours. The heat gun was removed.

Page 290: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 14 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 11: Compressed Nitrogen Bottle attached to get chamber at ambient temperature

At 3:40pm, we used the Endoscope to inspect the chamber for any remains of liquid. Figure 12 illustrates the position of the Endoscope probe as it was placed inside the chamber and Figure 13 shows the image on the Endoscope monitor.

Page 291: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 15 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 12: Location of Endoscope in relation to the measurement inside chamber

Figure 13: Image on Endoscope - shows droplets of liquid on floor of LN2 chamber

11 Repairing the Electrical Plug for the LN2 Heater Wires At this point in the process, we de-energized the LN2 heater coil. Before connected the plug back to the top lid of the chamber, we insulated the pins for the HTS coil power. Insulation was installed to prevent the chance of electrical shorting occurring across the energized pins and the loose LN2 heater pins inside the mounting hole. The copper gasket was replaced on the port and the connector was reinstalled.

Page 292: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 16 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

Figure 14: Insulation installed on exposed pins of connector plug

Figure 15: Plug with pins completely insulated

12 Evacuating the LN2 Chamber At 5pm we connected two scroll pumps (provided by vendor, PTB Sales) to the LN2 chamber and began to evacuate the chamber down to 1mTorr, to reach proper vacuum for the Cold-Head test and to ensure that the

Page 293: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 17 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

moisture was completely removed. Figure 16 is an image of the pumps connected and the “warm” nitrogen compressed air still attached.

Figure 16: (2) Edwards 20cfm Scroll Vacuum Pumps were installed in the system

Pumps ran on the system overnight, and by morning the vacuum in the system was 2.9mTorr, as displayed in Figure 17. Turbo pump was then attached to the system and further vacuumed the chamber to 2mTorr.

Figure 17: Vacuum level at 9AM 11/5

Page 294: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP/ER-2009-09A Page 18 of 18 Rev A

All rights reserved. Reproduction as well as disclosure or transmission to third parties outside Zenergy Power Inc. is forbidden. Use of information permitted only in compliance with valid contracts.

13 Conclusion The LN2 was successfully evaporated with this process, as well as all the moisture removed from the chamber. The internal vacuum level was at ~2mTorr after final pumping.

14 References MSDS No. P-4631-H, Praxair, Inc.

15 Index of Figures Figure 1: Carefully removed plug to assess repair 7 Figure 2: Wires for heaters are disconnected and too short to reach plug 7 Figure 3: Made connection to heaters via alligator clips 8 Figure 4: Checking phase to ground voltage 9 Figure 5: Voltage source used to energize heaters 9 Figure 6: Clamp meter measuring current across heater circuit, with ~238 Volts applied 10 Figure 7: Ambient cool air injected into port of LN2 chamber 10 Figure 8: Plot of LN2 level over time, with applied heat 11 Figure 9: Area heater to safely heat the ambient air for the heat gun 12 Figure 10: HTS Temperatures Rising Over Time 13 Figure 11: Compressed Nitrogen Bottle attached to get chamber at ambient temperature 14 Figure 12: Location of Endoscope in relation to the measurement inside chamber 15 Figure 13: Image on Endoscope - shows droplets of liquid on floor of LN2 chamber 15 Figure 14: Insulation installed on exposed pins of connector plug 16 Figure 15: Plug with pins completely insulated 16 Figure 16: (2) Edwards 20cfm Scroll Vacuum Pumps were installed in the system 17 Figure 17: Vacuum level at 9AM 11/5 17

16 Index of Tables Table 1: HTS temperature readings as captured by the PLC system 12

Page 295: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

I‐1

APPENDIX I: Zenergy Power HTS FCL Liquid Nitrogen Fill Procedure

Page 296: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZPZP/ES-2009-XPage 1 of 10

XXA

R F

J

wC

Report

FCL-CEC: Err

June 2011

www.zeneConfidenti

ror! Referen

2010

ergypower.al & Propr

nce source

.com rietary

not found.

Page 297: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP

A

ZP/ES-2009-Page 2 of 10

Report Status (Final

Reporting Entit

Responsible P

Project Name:

Document Title

Document Ref

Date of issue:

Client(s):

Author(s):

Distribution:

Summary

List of Re

Revision DA M

-XXA

l or Draft):

ty: Zene

379 O

Person: Chris

FCL-C

e: FCL-C

f. No.: ZP/ES

11/04

South

Chris

evisions

Date AMM/DD/YY In

Final

rgy Power Inc.

Oyster Point Bou

toph Linden

CEC

CEC: Preparat

S-2009-XXA

4/2009

hern California

toph Linden

Action nitial Release

ulevard, Suite 1

tion / Error! Re

< Assigned by

Edison, Shand

1, South San Fr

eference sourc

Erica

din Substation

Approved:

Modified Pa

rancisco, CA 94

ce not found.

Christoph L

age

4080 USA

Linden

Page 298: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP

2

ZP/ES-2009-Page 3 of 10

Contents 1 2 P3 F

-XXA

Introduction / bPreparation Filling with liqu

basic informatio

uid nitrogen

on Error! BBookmark nott defined. 5 8

Page 299: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP

VVt

T

ZP/ES-2009-Page 4 of 10

1 IntroducBefore the deschambers and

Volume 2 is theVolume 1 and thermal condu

The important

-XXA

ction / basic scription of pre (for filling up)

e chamber, whthe volumes 3ction.

Picture 2: Oveflanges to fill u

information eparation and fimportant flang

Picture 1

hich is filled up are chambers

erview of importaup volume 2 wit

filling up liquid ges.

1: overview cham

with liquid nitro that are evacu

ant flanges for filth liquid nitroge

nitrogen into t

mbers of the sys

ogen. Inside thuated to avoid

lling up en are “LN2 fill

the system, he

tem

is chamber theheat getting in

port” and “LN2

re is an overvi

ere is the HTS the system du

2 pressure”.

iew over the sy

coil and its formue to convection

ystem, its

mer. n and

Page 300: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP

2

A

VTvtt

TT

tt

VTTT

v

ZP/ES-2009-Page 5 of 10

2 PreparaDuring the leaAs you can reasystem. Volume 1: The vacuum pvalue with thethe new assemthe fill up procsurfaces. You Information: The vacuum inThe vacuum, wnew angle valvto the moleculetesting and disin 5 hours. Witpossibilities ofoutside tempecould and stop Volume 3: The vacuum pThe vacuum pThese values wpressure depevolume 3. Betw

-XXA

ation k detection of ad in the introd

ressure we rea vacuum gaug

mbled parts of cess. If the surwill see this eff

nside volume 1we reached aftve then, the pres and the sen

sconnecting theth this leakage this effect arerature. To kee

pped short befo

ressure we rearessure we reawere measure

ends on the lonween the Turbo

Picture 3: E

the system (seduction, the ev

ached in volume “Atmion”, whthe system, plrfaces then gefect later in this

was first in theter pumping doressure increasnsor, if you close leak detectore rate of volumee for example oep the pressureore starting the

ached in volumached in volumd with a sensong distance beo and the cham

Evacuation of vol

ee report of thevacuation of the

me 1 before stahich we assemease see the r

et cold, the pres report (chapte

e range of 10-2

own the volumsed a little bit. se the valve. B (leakage rate e 1 it would nooutgassing of se of 1,5 · 10-4 fill up process

me 3 surroundinme 3 surroundinor that was conetween Turbo mber there is an

lumes 3

e leak detectioese chambers

rting to fill up vmbled at the anreport of the leessure will decer “filling with li

mbar as we opme a few days w

This behavior But we saw also

of vol.1: <1,0 ·ormally take 26some materialsmbar before fi.

ng re-condenseng re-condensennected directlpump and voln about 2m lon

on), we evacua is necessary t

volume 2 was pngle valve of voeak detection). crease further diquid nitrogen”)

pened the valvwas in the ranis normal, beco, that the pres· 10-8 mbar·l/s) 6 days to increas and a desorpilling we pump

er 1 was p = 7,3er 2 was p = 1,6y to the volumume 3. There

ng hose (see pi

ated volume 1 to create an in

p = 1,5 · 10-4 molume 1. (For This pressure due to freezing).

e of the chambge 10-4 / 10-5 m

cause there is nssure increase from 3,1 · 10-3

ase the pressuption of molecuped down this c

3 · 10-3 mbar. 6 · 10-2 mbar.

me. The problem is no way to fcture below).

and the two vosulation vacuu

mbar. We measmore informat is good enougg molecules at

ber. mbar. As we cno more pumpd for example

3 mbar to 3,5 · ure in this way.ules due to a inchamber as lo

m of not gettinfix the Turbo d

olumes 3. um for the

sured this tion about gh to start t the cold

closed the ping effect after leak 10-3 mbar The only ncreasing ng as we

g a lower directly to

Page 301: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP

t

Tt

ZP/ES-2009-Page 6 of 10

Because we d3, we installedtemperatures w

Picture 4: Information: The vacuum inthe pressures(forepump andpump station, current leak demachine there

-XXA

on’t have a vad a temperatuwe can check,

Temperature se

nside both volu (described ond Turbo). Like instead they onetection, you re was a starting

cuum gauge aure sensor to if there is still a

ensor at the outs

umes 3 was firsn page beforethe company

nly used the ineach a pressur

g pressure from

at these chambthe outside tu

an insulation va

side tube of the r

st in the rangee), we pumpedof leak detecttegrated pumpre in the range

m only 10-1 mba

bers and we coube of re-condacuum during t

re-condenser

e of 10-1 mbar ad down half aion said, they

ps of the leak de of 10-1 mbar oar, which could

ould not check denser 1 (seethe operation o

as we opened day with thedid not pump

detector. With tof the volumes have been a p

for leaks at thee picture belowof the machine.

the valves of t pump station down the voluhese integrate

s 3. So during tproblem.

e valves of thew). With the m.

the chambers. n of the US coumes 3 with ad pumps, we sthe last operat

e volumes measured

To reach olleagues separate

saw at the tion of the

Page 302: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP

t

vA

ZP/ES-2009-Page 7 of 10

Safety valve: Because we foto change the before starting

During the opebecause of thevalve, switch thAfter this last nitrogen. This

-XXA

ound a leak at valve during th to fill up volum

eration the ange leak we founhe current valvpreparation anprocess is des

the safety valvhe operation wme 2.

Picture 5: ne

gle valve must nd, you can dove with a new ond after finishicribed in the fo

ve (old and newithout opening

ew assembly of

be open to havo this during opone and open ang the leak de

ollowing chapte

w one), we wan volume 2. On

safety valve

ve the safety vperation with c

again the angleetection we ster.

nted to have a the following p

valve working. closed volume e valve. tarted the proc

n assembly, wpicture you see

If you want to c 2. For it you h

cess of filling u

which makes it ve this assembly

change the safhave to close

up volume 2 w

very easy y, we built

fety valve the angle

with liquid

Page 303: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZPZP/ES-2009-Page 8 of 10

3 Filling 1.) We st

valve

2.) After to thenitrog

3.) We oventinopen the co

1

1

2

2

3

tempe

rature [K]

In thisdewaradjustaveracool dAt 5pwantepress

-XXA

with liquid ntarted our fill u was still open

preparing the ce “LN2 fill port”gen)

pened the liqung with nitroge this flange is nooling process

0

50

00

50

00

50

00

14:52 15:

c

s diagram you sr too fast, so ted the dewar ge temperatur

down the HTS pm we mounteed no more cyure” are still op

nitrogen up process with (only plastic ca

chamber we co”. (information

id outlet a littleen gas we left not so importan with the cold g

21 15:50

ooling cu

see that we insthat the HTS outlet again soe decreasing dBottom with co

ed the safety vycling gas frompen.

h opening the fap), we left it o

onnected a redabout choosin

e bit and cooled the safety valnt, we left it opgas and a very

16:19 16:4

urves ‐ ve

serted the hose bottom tempeo that you canduring this venool gas only to valve-assembly

m this point bu

flanges “LN2 fiopen and remov

d rubber hose tng the rubber h

d down volumeve flange ope

pen, because it low rate of tem

48 17:16

time

enting w

e to the bottomerature decrean see constant nting with cold 77K. y to close the

ut a faster sub

ill port” and “LNved the plastic

to the first dewhose you can r

e 2 with a slown to have circt was already).

mperature redu

17:45 18:14

with cold g

m of the chambeased too fast d and slow temnitrogen gas is

e KF16-flange.bcooling. The o

N2 pressure”. T cap.

ar (liquid outletread in manua

w flow of cold nulating flow th. In the followinction.

4 18:43

gas

er. The first mindown to 220Kperature reducs 48K/h. We to

We closed thother flanges “

The flange of t

t) and insertedal of filling up w

nitrogen gas. Drough the chang diagram you

HTS Bottom

HTS Top

nutes we open. That’s the rection at about 4ook a time of 3

his flange, bec“LN2 fill port” a

the safety

the hose with liquid

During this mber (To u can see

m

ed the eason we 4pm. The 3 hours to

cause we and “LN2

Page 304: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZPZP/ES-2009-Page 9 of 10

4.) At thisconnelevel adiagra

tempe

rature [K] /

level [cm

]vacuum

pressure [m

bar]

You sof 77cliquidthe leaboutunder

-XXA

s point we opeected a secondand the openeams you see th

0

50

100

150

200

250

14:52

1,00E‐06

2,10E‐05

4,10E‐05

6,10E‐05

8,10E‐05

1,01E‐04

1,21E‐04

1,41E‐04

1,61E‐04

1,81E‐04

14:52

see that it took cm. During this nitrogen in sev

evel with a endt checking the r maximum lev

ened the liquid d hose to a secd outlets of two

he complete co

16:04 17

curv

16:04

pre

us about 8 hous time the insuveral steps (50doscope throug level with an el.

outlet of the dcond dewar liqo dewars we g

ooling curves, t

7:16 18:2

ve of cooling

17:16

essure ‐ ins

urs for the comulation vacuum0cm, 60cm, 70cgh “LN2 fill poendoscope an

dewar more anduid outlet to ac

get more and mhe liquid nitrog

28 19:40

time

g ‐ complete

18:28

time

sulation va

mplete subcoolim of volume 1 dcm, 72cm…77crt” (see the m

nd the maximu

d more to reacccelerate the fi

more liquid nitrogen level in volu

20:52

e to 77cm LN

19:40 2

acuum volu

ng and filling pdecreased to acm). Every steanual of fillingm level). With

ch a faster sublling process n

ogen into the chume 2 and the

22:04

N2 level

20:52 22:

ume 1

process. We filla range of 10-6

p we closed bo liquid nitrogen a level of 77c

bcooling. Additinow. At this temhamber. In the pressure of vo

23:16

H

H

L

04 23:16

ed up the LN26 mbar. We filleoth dewars andn for further incm we were a

onally we mperature following

olume 1.

HTS Bottom

HTS Top

LN2 level

6

to a level ed up the d checked formation bout 1cm

Page 305: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

ZP

T

ZP/ES-2009-Page 10 of 10

5.) After gun. W

6.) Now wsaw tunder

7.) Becauflangeundernot alDue tthe tu

8.) We cltime w

The following “Zenergy Powe(2)”.

-XXA 0

reaching and We cleaned all

we turned on that there was rpressure in vo

use of missinges again, whenrpressure we lel of the air free

to the venting, rned off cold h

leaned up agaiwe closed both

steps and tester – FCL CEC

checking the le sealings and c

cold head 1 ano more venti

olume 2. The co

the closing pon the cold heaet vent the nitr

ezes directly ou we refilled theead on increas

in all componeh flanges (“LN2

ts we did to coC - exactly histo

evel, we pulledcomponents to

nd missed unfng of the nitrogoldhead reache

oint, we turnedd reached aborogen gas for aut at the cold sue lost liquid nitrsed to about 10

ents and sealing fill port” and “L

ool down the lory of testing b

d out the hoseo close the flang

fortunately the gen gas out ofed 67K at this m

d off cold headout 79K. For geabout 20 minuurfaces, so tharogen with one00K.

gs, melted the LN2 pressure”)

iquid nitrogen by remote in S

es and got rid oges later.

80K point to cf the open flanmoment.

1 and saw theetting out the ates. We think tt we can vent i

e hose to 77cm

ice on the flan) over a temper

bath you can SF” and the wo

of the ice at th

close the flangges, instead th

e nitrogen gas air that was suthat in this shot out.

m. During this t

ges and restarrature of 80K o

read summariord documents

he flanges with

ges of the chamhere was alrea

venting out ofucked in becauort “underpress

time the tempe

rted cold head of cold head on

ized in the pres “cool down o

h the heat

mber. We ady a little

the open use of the sure time”

erature of

one. This ne.

esentation of cryostat

Page 306: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

J‐1

APPENDIX J: Silicon Power SSCL Test Plan

Page 307: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

1-1

Test Plan For

15kV 1200A Solid State Fault Current Limiter (SSCL)

For Field Evaluation Testing At

Southern California Edison (SCE) Revision 2 – August 15, 2008

Prepared by

Mahesh Gandhi, Ph 484‐913‐1520

Silicon Power Corporation, Malvern, PA

Page 308: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

1-2

CONTENTS 1 INTRODUCTION .................................................................................................................... 1-4 2 SSCL DESIGN ........................................................................................................................ 2-1

2.1 SSCL Design .................................................................................................................. 2-1 2.2 Standard Building Block ................................................................................................. 2-1 2.4 Final Packaging .............................................................................................................. 2-3 2.5 SSCL Accessories ......................................................................................................... 2-4 2.6 Control System ............................................................................................................... 2-5 2.7 Auxiliary Power Architecture .......................................................................................... 2-6

3 SSCL SPECIFICATIONS ....................................................................................................... 3-1 4 LIST OF TESTS ...................................................................................................................... 4-2

4.1 Component Level Tests ................................................................................................. 4-2 4.2 Design Verification Tests (Controlled Testing) ............................................................... 4-2 4.3 Testing at SCE ............................................................................................................... 4-3

5 TEST PROCEDURES ............................................................................................................ 5-5 5.1 Component Level Tests ................................................................................................. 5-5 5.2 Design Verification Testing (Controlled Tests) ............................................................... 5-6 5.3 Testing at SCE ............................................................................................................. 5-17

6 SCHEDULE ............................................................................................................................ 6-1

APPENDIX A TABLE OF TESTS…………………………………………………………………..A-1

Page 309: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

1-3

LIST OF FIGURES

Figure 2-1 Voltage Level Building Block .................................................................................................... 2-1 Figure 2-2 Voltage Level Building Block, 5kV 1500A ................................................................................ 2-2 Figure 2-3 Stack Assembly, 15kV 1500A .................................................................................................. 2-3 Figure 2-4 Tank Assembly ......................................................................................................................... 2-4 Figure 2-5 SSCL Accessories .................................................................................................................... 2-5 Figure 2-6 Control Architecture .................................................................................................................. 2-6 Figure 2-7 Auxiliary Power Supply Architecture......................................................................................... 2-7 Figure 5-1 Test Schematic for Power Frequency Withstand Voltage Test ................................................ 5-8 Figure 5-2 Waveform for lightning impulse tests per IEEE Std 4 ............................................................... 5-9 Figure 5-3 Schematic for Full Wave Impulse Test ................................................................................... 5-10 Figure 5-4 Waveform for Chopped Wave Impulse Test .......................................................................... 5-11 Figure 5-5 Test Schematic for Chopped Wave Impulse Test .................................................................. 5-12 Figure 5-6 Asymmetric Fault Current ....................................................................................................... 5-13 Figure 5-7 Efficiency Test Schematic ...................................................................................................... 5-14 Figure 5-8 Operational Test Schematic ................................................................................................... 5-19

Page 310: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

1-4

1 INTRODUCTION The increase in available fault current levels due to added distributed generation and increased load has stressed many transmission and distribution substations to their limits. In some cases fault current levels are exceeding the interrupting capability of existing substation circuit breakers. This increase in fault current levels either requires the replacement of large numbers of substation breakers or the development of some means to limit fault current. By using a Solid State Current Limiter (SSCL), fault currents can be limited well before it reaches the 1st peak and to the desired value within ¼ cycles (4ms). This will allow near instantaneous breaking of bus ties in transmission and distribution substations to reduce the available short circuit current and allow existing circuit breakers to clear at lower fault current levels.

When new capacity, such as the additional generation created by independent power producers, is merged with existing power systems, higher levels of fault current is introduced in the system. The increased fault current can cause failure of circuit breakers at a substation if they exceed their fault clearing or breaking ratings. While the breakers might be replaced with higher-rated equipment, this solution may not be economical or viable due to space constraints, and the difficulties associated with outages necessary for replacement may be severe. This device will provide performance similar to a circuit breaker, but with the added function of current limiting. Unlike a circuit breaker, the SSCL will act to limit high current faults even before the first current peak is reached. This limiting effect is provided well before interruption of the fault occurs. Whereas a high speed circuit breaker typically interrupts high current faults in about two and a half cycles, the SSCL will interrupt them after one-half cycle. SSCL can be an even better environmental alternative to the use of breakers, which employ greenhouse gasses (SF6).

SSCL offer many other benefits such as:

New Capacity - Solid-state current limiters could be applied to new capacity additions and/or “surgically” at strategic locations, such as substation bus ties, to effectively mitigate the fault current from multiple generation sources. This would provide a flexible tool that could be used to accommodate new capacity from generation or transmission distributed or aggregate generation energy storage.

Grids Operations Alternatives -The new functionality made possible by the flexibility of power electronics will also enable innovative alternatives in operation of the grid. For example, power electronics can mitigate unexpected load increases or major asset failures with temporary generation, protect “line commutated” FACTS devices from close proximity solid state s and improve the performance of superconducting cables.

Superconducting Cables - A solid state current limiter added in series with a superconducting cable can improve the cable's performance and enable design of smaller cable sizes, as well as eliminate loss of superconducting cable operation during cryogenic recovery time following an external fault. The insulation system of

Page 311: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

1-5

a superconducting cable is likely to have limited strength because of the need for minimal mechanical cross section bracing spanning the vacuum segment. It may not be capable of handling the magnetic forces occurring in the worst case of a high current fault, particularly in transmission applications, which will draw fault currents from higher impedance parallel paths. The solid state current limiter will be an essentially enabling adjunct to the regular use of superconducting cables.

Inrush Current - The Solid State Current Limiter has a unique capability to limit inrush current, even for capacitive loads, by gradually phasing in the switching device. This may be of particular benefit in mitigating stress on generator shafts, while preserving the reliability benefits of multi-shot reclosure on generator buses, particularly as distributed generators are deployed at various voltage levels and locations across utility grids.

Open Access - Because of the critical role of solid state current limiting as an early enabler within EPRI/DoE’s Roadmap Document to support “open access,” transmission and generation capacity increases, energy storage needed for improved asset utilization and renewable economics, distributed and aggregate generation, this new functionality is also being pursued in a parallel development effort for transmission level solid state current limiters using superconducting and other technologies.

In 2000 EPRI began a project to develop a solid state current limiter (SSCL). A three phase, 15 kV, 1200 A, distribution class prototype SSCL has been constructed and underwent design tests. The design uses the Thyristor as main switching devices. The next steps will be to (1) design SSCL to incorporate the latest device technology and experience gained to date and then (2) subject this updated and improved unit to a field trial.

At present no real world field application experience exists for the EPRI developed solid state current limiter (SSCL). This information is vitally needed by the utility community to effectively apply and operate the SSCL. Areas that need to be studied include electrical and mechanical performance, reliability and availability, maintainability, effectiveness of power quality enhancement, and coordination with existing power system components. This will give the design team information about any needed improvements and will provide evidence to utilities that the SSCL is a practical reality.

The objective of this phase of program is to conduct a field trial of a medium voltage SSCL. SPCO will deliver One (1) 15kV 1200A. The SPCO SSCL design uses advanced power semiconductor technologies, latest electrical components and insulating materials and state of the art manufacturing practices. The unit will be field evaluated at Southern California Edison.

This document provides detail test plan of test to be performed on unit at factory and at field. The sections includes list of tests, detail test procedures, and test schedule.

Page 312: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

2-1

2 SSCL DESIGN 2.1 SSCL Design The SSCL design is modular and scalable. It is based on a standard building block which can be stacked to get the desired voltage and current ratings. On the 15kV SSCL the power stacks will be submerged in a cooling and insulating liquid. The overall design will be similar to a liquid cooled outdoor transformer. It will have cover-mounted power bushings for ease of connections. The tank shall have sufficient mechanical strength for the years of service and to withstand environmental conditions. The tank shall have accessories like: liquid level gauge, liquid temperature gauge, pressure vacuum gauge and pressure-relief device, control cabinet mounting, and cooling radiators.

2.2 Standard Building Block In order to facilitate manufacturing, and reduce the maintainability and the ownership cost of the unit, standard-building blocks – Voltage Level Blocks – concept is approached. Each of these building blocks is a complete SSCL switch rated to up to 2kA and about 5kV blocking, and resembles a fully functional SSCL. The needed number of series levels is determined by the breakdown voltage of the main switch modules and the arrestor voltage. SGTO die are typically rated at 6.5kV, although, at present modules containing these die are very conservatively rated to 5kV. Because resonant turn-off is so benign, there is virtually no voltage overshoot of the arrestor allowing it to be set as high as 4.5kV. We have selected 4kV for the 15kV SSCL.

The physical arrangement for the building block is depicted in Figure 2-1.

Figure 2‐1 Voltage Level Building Block

Page 313: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

2-2

The Figure 2-2 provides the detail mechanical layout of the key level block elements. The Main and the Aux SGTO switch modules will be mounted on a common heat sink, which provides the mechanical backbone of the level block. The resonant capacitor is placed at one end of the heat sink and four varistors and the Current Limiting Inductor (CLI) at the other. This forms a 5kV 1500A Building Block.

Figure 2‐2 Voltage Level Building Block, 5kV 1500A

2.3 Standard Power Stack

The number of levels in series, N, is then based on assuring that the average varistor losses during worst case limiting operation are well within their ratings. The number of series Voltage Level Blocks (VLB’s) is first governed by the transient blocking voltage rating and the margin chosen between that voltage and the arrestor voltage (at 9 kA current). 15kV SSCL will have 10 of the 5kV (blocking voltage) 1500A units per phase, all stacked in series. The stack assembly is seen in Figure 2-3.

Page 314: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

2-3

Figure 2‐3 Stack Assembly, 15kV 1500A

2.4 Final Packaging The system is packaged as one 3-phase assembly. It can be seen in Figure 2-4 that one stack makes a single phase and 3 such are placed in a single tank filled with oil for cooling.

Page 315: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

2-4

Figure 2‐4 Tank Assembly

2.5 SSCL Accessories The SSCL will be provided with the accessories shown in figure 2-5.

Page 316: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

2-5

Figure 2‐5 SSCL Accessories

2.6 Control System The 15kV SSCL is designed to operate primarily from the remote. It also has the capability to operate locally. The controls shall include ON/OFF controls, equipment Protection, Supervisory Controls and Data Acquisition (SCADA), Display and Monitoring of Operating parameters, Fault Log, Access Protection, e-Tagout, Safety Padlocking, etc. Control and communication system shall be compatible with communication standard IEC-61850. The SSCL controls will provide a trip free feature where any close signal shall not inhibit the SSCL from opening upon command.

The communication between the VLC boards and the trip controller is provided with the help of fiber optics as shown in figure 2-6.

Page 317: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

2-6

Figure 2‐6 Control Architecture

The main components involved in the control system are: High Speed dI/dt Sensor, Bushing mount CT, Industrial Panel Mount Controller, Trip Controller, VLC/ PS Board and Gate Drive Boards.

2.7 Auxiliary Power Architecture Another aspect of the SSCL is its modular power supply to the control and gate drive boards. Each power module is designed as a floating power supply. This allows necessary isolation of the modular power system from the earth ground. The externally powered module requires isolated AC voltages from the substation external power that meet the required isolation level.

The power supply input is from the station aux supply of 120V ac. The concept of the power supply design is to use an inverter that supplies high frequency transformers with necessary isolation. These high frequency transformers further feed the toroidal power supply transformers at the building block level. Figure 2-7 shows the auxiliary power supply architecture.

Page 318: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

2-7

Figure 2‐7 Auxiliary Power Supply Architecture

Page 319: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

3-1

3 SSCL SPECIFICATIONS

Parameters Rating/Specification

• Rated Maximum Voltage, kV rms 15.5

• Rated Maximum Continuous Current, Ampere rms 1200

• Rated Power Frequency 60

• Available fault current, kA rms 23

• Rated Let-thru Current, kA rms 9

• Rated Let-thru Current Duration, cycles 30

• Rated Dielectric Withstand

– Power Frequency 1 min dry kV, rms 50

– Impulse, Full-wave Withstand, kV peak 110

– Impulse, Chopped Wave (2uS) Withstand, kV peak 142

– Partial Discharge at 16.5kV, pC 100

– Rated Power Factor Measurement ?

– Rated Insulation Resistance at 500V DC Megohmeter 13000 M-ohm

• Ambient Temp, Degree C -30 to +50

• Rated Control Power, V AC 120

• Efficiency Goal 99.75%

• Audible Noise at 6 feet, dB 68

• Radio Influence Voltage ?

Note: Ratings based on ANSI C37-04, C57.16, C57.12.01, C57.12.90 and Customer Comments

Page 320: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

4-2

4 LIST OF TESTS 4.1 Component Level Tests

The tests in this section will be performed at the component level. 4.1.1 Current Limiting Reactor 4.1.1.1 Let Through Current/MMF Test 4.1.1.2 DC Resistance Measurement Test 4.1.1.3 Winding Resistance Measurement 4.1.1.4 Winding Impedance Measurement 4.1.1.5 Turn-to-Turn Test 4.1.2 Auxiliary Power Supply Transformer 4.1.2.1 Isolation test 4.1.2.2 Loading test at rated kVA 4.1.2.3 Continuous operation/Temperature rise test 4.1.3 Auxiliary Power Supply Inverter 4.1.3.1 Continuous operation test 4.1.3.2 Insulation/Isolation test 4.1.4 Standard Building Block (Power Block) 4.1.4.1 Current interruption Test 4.1.4.2 Continuous Current/Temperature Rise Test

4.2 Design Verification Tests (Controlled Testing) These tests will be performed on the SSCL unit. 4.2.1 Dielectric Test

4.2.1.1 Power frequency Voltage Withstand Test 4.2.1.2 Full-wave lightning impulse withstand voltage tests 4.2.1.3 Chopped wave lightning impulse withstand voltage tests 4.2.1.4 Partial Discharge

4.2.1.5 Insulation Power Factor Measurement 4.2.1.6 Insulation Resistance Measurement

4.2.2 Current Limiting Test 4.2.3 Efficiency Test

Page 321: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

4-3

4.2.4 Continuous Current Carrying Test/ Temperature Test 4.2.5 Audible Noise Test

4.2.6 Radio Influence Voltage (RIV) Test 4.2.7 Electrical noise/EMI Test

4.3 Testing at SCE

These tests will be performed on the SSCL unit by SCE with the support of Silicon Power.

4.3.1 SSCL Interfaces 4.3.2 Acceptance Test at SCE

4.3.2.1 Winding Resistance Test 4.3.2.2 Winding Impedance Measurement 4.3.2.3 Turn to Turn Test 4.3.2.4 Total Loss Measurement Test 4.3.2.5 Voltage-freq Withstand Test 4.3.2.6 RIV Test 4.3.2.7 BIL Test 4.3.2.8 Chopped-wave Test 4.3.2.9 Audible Noise Test 4.3.2.10 Partial Discharge Test 4.3.2.11 Insulation Resistance Measurement 4.3.2.12 Fault current Limiting Test followed by Normal Operation Test

4.3.3 Field Evaluation Testing at Shandin Sub-station 4.3.3.1 Pre-connection Testing

4.3.3.1.1 External Inspection

4.3.3.1.2 Tank Pressure

4.3.3.1.3 Winding Resistance Measurement

4.3.3.1.4 Winding Impedance Measurement

4.3.3.1.5 Insulation Power Factor Test

4.3.3.1.6 Insulation Resistance

Page 322: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

4-4

4.3.3.2 Field evaluation tests

4.3.3.2.1 Operational Test (Steady-state & Transient)

Page 323: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-5

5 TEST PROCEDURES 5.1 Component Level Tests 5.1.1 Current Limiting Inductor Test 5.1.1.1 Let Through Current/MMF Test The let through current of 9000A for 0.5 sec will be passed through the inductor and the MMF handling capability of the inductor will be tested.

5.1.1.2 DC Resistance Measurement Test The DC resistance will be measured between the terminals of the inductor.

5.1.1.3 Winding Resistance Measurement The resistance will be measured between the terminals of the inductor.

5.1.1.4 Winding Impedance Measurement The impedance will be measured between the terminals of the inductor.

5.1.1.5 Turn to Turn Test The insulation between the turns will be measured for the inductor.

5.1.2 Auxiliary Power Supply Transformer 5.1.2.1 Isolation Test The Transformer will be tested for its isolation at the KEMA power labs. Isolations up to 3kV will be tested.

5.1.2.2 Loading Test The transformer will be loaded to its rated VA that is 51VA

5.1.2.3 Continuous Operation/Temperature Rise Test The transformer will be tested for continuous operation and the temperature will also be monitored.

5.1.3 Auxiliary Power Supply Inverter 5.1.3.1 Continuous Operation Test The Inverter will be tested for continuous operation

5.1.3.2 Insulation/Isolation Test The Insulation test up to 3kV will be performed at the KEMA power lab.

Page 324: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-6

5.1.4 Standard Building Block (Power Block) 5.1.4.1 Current interruption test The building block will be tested at 5000A peak from a 23kA rms available fault current at the KEMA power labs.

5.1.4.2 Continuous Current/Temperature Rise Test The Building Block will be tested at a continuous current of 1200A rms at a low voltage at the KEMA power labs.

5.2 Design Verification Testing (Controlled Tests) 5.2.1 Dielectric Test Objective: The dielectric integrity of a SSCL is demonstrated by subjecting it to a power frequency, a lightning impulse test, and where required, a chopped wave lightning impulse and a switching impulse test.

5.2.1.1 Tests conditions

a) Dielectric Voltage Withstand tests on SSCL shall be made under atmospheric pressure, temperature, and humidity conditions normally prevailing at the testing facility.

b) The SSCL shall be clean and in good condition, and shall not have been put into commercial operation.

c) Correction factors shall not be used on normal power frequency dry tests, unless allowed by industry standard. The values of correction factors for atmospheric pressure and atmospheric humidity to be used for impulse and power frequency wet tests are to be taken from IEEE Std 4-1978 curves and formulas applicable to atmospheric bushings, except where otherwise noted.

d) The bushing and rod gap correction factors will not always have the optimum accuracy for a specific design of SSCL. In cases where more accurate correction factors can be made available for a specific design or class of designs, they may be used.

e) When revisions in correction factors in IEEE Std 4-1978 are made, they shall be applicable to new designs only and it shall not be necessary to repeat design tests on designs for which such tests have been completed.

f) Dielectric test voltages shall be measured in accordance with IEEE Std 4-1978 voltage measurement standards.

g) For lightning impulse and chopped wave tests, atmospheric temperature and pressure correction factors shall be applied to define the test voltage. For SSCLs, the use of humidity correction factors is required (see IEEE Std C37.20.2-1993).

Page 325: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-7

5.2.1.2 Insulation paths

When performing dielectric tests, two classes of insulation paths are to be considered:

1. Atmospheric paths: Paths entirely through atmospheric air, such as along the porcelain surface of an outdoor bushing.

2. Non atmospheric paths: All other paths, such as through a liquid such as oil, through a solid, or through a combination thereof.

Non atmospheric paths In order to meet the requirements for non atmospheric paths, at least three dry withstand tests must be accumulated at each polarity, at the rated lightning impulse and related chopped wave voltages (in addition to one dry power frequency withstand test), all without benefit of reduction of voltages due to correction factors. The purpose is to apply full stresses to these non atmospheric paths; therefore, tests in which a flashover occurs through an atmospheric path may be ignored. It is permissible to raise the dielectric strength of the atmospheric paths by artificial means, such as an extra high-voltage shield or a corona ring. In some atmospheric conditions, it may be desirable to delay testing of the non atmospheric paths until conditions improve.

Atmospheric paths

There is no separate atmospheric path requirement for the dry-power frequency test.

Page 326: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-8

5.2.1.3 Power frequency withstand voltage tests

Figure 5‐1 Test Schematic for Power Frequency Withstand Voltage Test

Wet test procedure The wet tests are made only on outdoor SSCL or on external components such as bushings, in accordance with the procedure described in IEEE Std C57.19.00-1991. For those bushings, where their voltage distribution is negligibly influenced by their surroundings, and which have been tested separately as individual bushings in accordance with IEEE Std C57.19.00-1991, the tests need not be repeated in the assembled SSCL.

5.2.1.4 Full-wave lightning impulse withstand voltage tests These tests are made on SSCL, under dry conditions, to verify their ability to withstand their rated full-wave lightning impulse withstand voltages. In these tests, both positive and negative, lightning impulse voltages having a peak value equal or greater than the rated full-wave lightning impulse withstand voltage, 110kV, shall be applied to the terminals of the SSCL. NOTE—some insulating materials retain a charge after an impulse test. For these cases, care should be taken when reversing the polarity of the test voltage. To allow the insulating materials to discharge, the use of appropriate methods, such as the application of impulses of the reverse polarity at lower voltages (50–75% of rated value), are recommended.

Page 327: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-9

Waveform for lightning impulse tests

Figure 5‐2 Waveform for lightning impulse tests per IEEE Std 4

The waveform and application of the full-wave test voltage shall be as described in IEEE Std 4-1978 and shall have the following limits:

a) A full-wave test voltage with a virtual front time based on the rated full wave impulse test voltage, equal to or less than 1.2 µs;

b) A peak voltage equal to or exceeding the rated full wave impulse voltage; and c) A time to the 50% value of the peak voltage, equal to or greater than 50 µs.

If the capacitance of a test sample is too high for the test equipment to be able to produce a virtual front time as short as the 1.2 µs while maintaining the peak value, the most rapid rise possible may be used, subject to agreement between the user and the manufacturer.

Page 328: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-10

Test procedure

Figure 5‐3 Schematic for Full Wave Impulse Test

The test procedure shall consist of the following tests performed in any order

• Apply three consecutive positive lightning impulse voltage waves individually to each phase of the circuit breaker with the other phases and the frame grounded.

• Apply three consecutive negative lightning impulse voltage waves individually to each phase of the circuit breaker with the other phases and the frame grounded.

If a flashover occurs on one of the above mentioned tests, a second group of nine tests shall be made. If the SSCL successfully withstands all nine of the second group of tests, the flashovers in the first set of tests shall be considered a random flashover and the SSCL shall be considered as having successfully passed the test.

5.2.1.5 Chopped wave lightning impulse withstand voltage tests These tests shall be performed on SSCL that have a rated maximum voltage of 15.5 kV and above to verify their ability to withstand their assigned rated chopped wave lightning impulse withstand voltage. The magnitude of this voltage is 142kV. It shall be applied to the terminals of the SSCL, without causing damage or producing a flashover, following the same procedure as described in 5.1.1.4.

Page 329: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-11

The waveform and application of the chopped wave test voltage, and the type of rod gap and its location, shall be as described in IEEE Std 4-1978.

Figure 5‐4 Waveform for Chopped Wave Impulse Test

The chopped wave shall have the following limits:

a) The virtual front time, based on the rated chopped wave test voltage, shall be equal to or less than 1.2 µs.

b) The peak voltage shall be equal to or greater than the rated chopped wave test voltage. c) The time to the point of chop on the tail of the wave shall be no less than 2 µs. If the

capacitance of a test sample is too high for test equipment to be able to produce a virtual front time as short as 1.2 µs, while maintaining the peak value, the most rapid rise obtainable may be used, subject to agreement between the user and the manufacturer.

NOTE—Flashovers external to the SSCL at the specified chop times, or longer, do not constitute failure

to pass the test

Page 330: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-12

Figure 5‐5 Test Schematic for Chopped Wave Impulse Test

5.2.1.6 Partial Discharge Test Apparent internal partial discharges (apparent charge) shall be measured and reported in units of picocoulombs (pC). A partial discharge meter shall be used to measure the apparent charge generated by any internal partial discharges. The partial discharge detector, based on IEEE Std C57.113-1991, is used to measure the partial discharge levels at the terminals. General principles and circuits are described in IEEE Std 454-1973 [B6] and in IEEE Std C57.113-1991.

5.2.1.7 Insulation Power Factor Measurement The voltage to be applied for measuring insulation power factor shall not exceed half of the low-frequency test voltage given in Table 5 of IEEE Std C57.12.00-2006 or 10 000 V, whichever is lower.

5.2.1.8 Insulation Resistance Measurement A Megohmeter with nominal voltage of 500V will be used to measure insulation resistance.

5.2.2 Current Limiting Test Objective: The current-limiting test of the SSCL is to demonstrate the current-limiting performance and the related capabilities of the SSCL.

5.2.2.1 Test conditions 5.2.2.1.1 Power factor For current-limiting tests, the power factor of the testing circuits shall not exceed 5.9% lagging, equivalent to X/R = 17 at 60 Hz or 7.1% lagging equivalent to X/R = 14 at 50 Hz.

5.2.2.1.2 Frequency of test circuit Tests demonstrating current-limiting capabilities shall be made at rated power frequency.

Page 331: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-13

5.2.2.1.3 Current asymmetry Current-limiting tests are required with both symmetrical and asymmetrical currents. Any current-limiting test in which the asymmetry of the current is less than 20% is considered a symmetrical test. Figure 5.1 shows the asymmetric fault current required to test the SSCL.

Figure 5‐6 Asymmetric Fault Current

5.2.2.1.4 Obtaining the most severe switching conditions To demonstrate the required current limiting capability of a SSCL, it is necessary to show that the SSCL is capable of meeting the requirements for the rated fault current. It must be shown that the SSCL is capable of limiting the rated current. Figure

5.2.3 Efficiency Test

Objective: The objective of this test is to measure the losses of the SSCL at various loads.

Test Schematic: Figure shows the proposed test schematic for the efficiency test.

Asymmetric Fault Current

Page 332: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-14

Figure 5‐7 Efficiency Test Schematic

Test Description: A three phase, 0.85 power factor, load bank with 100%/ 85%/ 75%/ 50% taps will be connected to the load side of the SSCL. Readings will be taken using Voltage and current sensors at both ends of the SSCL as shown in the figure 5.2.

5.2.4 Continuous Current-carrying tests Continuous current-carrying tests demonstrate that the SSCL can carry its rated continuous current, at its rated power frequency, without exceeding any of the temperature limitations.

5.2.4.1 Test conditions

a) The ambient temperature shall be between 10° C and 50° C, so that no correction factors

need to be applied. b) SSCL`s if normally equipped with current transformers shall be tested with transformers

in place and connected to carry rated secondary current. c) Tests demonstrating current carrying ability shall be done at voltage necessary to get

rated continuous current. d) Tests demonstrating current carrying ability shall be made at rated power frequency

except that where tests are performed at 60 Hz they shall be considered to be valid for the same current rating with 50 Hz rated power frequency.

e) SSCL shall be tested with cables or buses of a size corresponding to the SSCL current rating connected to the SSCL terminals by means of typical terminal connectors of corresponding rating.

5.2.4.2 How tests shall be made a) Three-phase SSCL`s shall be tested on a three-phase or single-phase basis.

Page 333: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-15

b) Where there is no possibility of magnetic influence, but there may be thermal influence from other phases of the SSCL, tests may be made with single-phase current passed through the three poles in series.

5.2.4.3 Duration of continuous current tests The continuous current test shall be continued for a period of time such that the temperature rise of any monitored point in the assembly has not changed by more than 1.0 °C as indicated by three successive readings at 30 min intervals. The equipment is considered to have passed the test if the established temperature limits specified in IEEE Std C37.04-1999 have not been exceeded in any of the last three readings.

5.2.4.4 How temperatures are measured Temperatures shall be measured by any of the following methods (see IEEE Std 119 Aug.1950): a) Thermocouple b) Thermometer (allowed method only for ambient temperature measurements; not acceptable for temperature measurement of current carrying components) The measuring device shall be located at a point where measurement of the hottest accessible spot can be made. Measurements shall be made at junction points of insulation and conducting parts to prevent exceeding temperature limits of the insulation.

5.2.4.5 How ambient temperature is determined The ambient temperature is the average temperature of the surrounding air, external to the circuit breaker enclosures. The ambient temperature shall be between 10°C and 50°C, so that no correction factors need be applied. The ambient temperature shall be determined by taking the average of the readings of three measurements that are made at locations unaffected by drafts approximately 300 mm (12 in), away, horizontally, from the projected periphery of the SSCL or enclosure, and approximately in line, vertically, as follows:

a) One approximately 300 mm (12 in) above the SSCL (including bushings). b) One approximately 300 mm (12 in) below the SSCL. c) One approximately midway between the above two positions.

Page 334: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-16

To avoid errors that are due to the time lag between the temperature of large apparatus and the variations in the ambient temperature, the measuring device used for determining the ambient temperature shall be immersed in a suitable liquid, such as oil, which is contained in a suitable heavy metal cup.

5.2.5 Audible Sound Test The audible sound will be measured using microphones at Alion/R&B Laboratory.

5.2.6 Radio Influence Voltage (RIV) Test The conducted radio noise will be measured using a test circuit in accordance with NEMA and ANSI C36.2 specifications.

5.2.7 Electrical Noise/EMI Test

Electrical Noise/Electromagnetic interference will be measured at Alion/R&B Laboratory.

Page 335: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-17

5.3 Testing at SCE 5.3.1 SSCL Interfaces SSCL will be equipped with the following sensors

• Dial Type Thermometer

• Pressure Gauge

• Current Transformer

• SEL HMI – RS232 and Ethernet ports for system voltage and current monitoring

5.3.2 Acceptance Test at SCE These tests will be performed by SCE at their Westminster facility in accordance with their test procedures.

5.3.2.1 Winding Resistance Test

5.3.2.2 Winding Impedance Measurement

5.3.2.3 Turn to Turn Test

5.3.2.4 Total Loss Measurement Test

5.3.2.5 Voltage-freq Withstand Test

5.3.2.6 RIV Test

5.3.2.7 BIL Test

5.3.2.8 Chopped-wave Test

5.3.2.9 Audible Noise Test

5.3.2.10 Partial Discharge Test

5.3.2.11 Insulation Resistance Measurement

5.3.2.12 Fault current Limiting Test followed by Normal Operation Test

5.3.2 Field Evaluation Testing at Shandin Sub-station 5.3.2.1 Pre-connection

5.3.2.1.1 External Inspection All SSCLs will be carefully tested at the manufacturing unit and will be in good condition before the shipment is made. Once received at site an external inspection of the SSCL tank and fittings will be done which will include the following points:

Page 336: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-18

1. Is there any indication of external damage? 2. Is the paint finish damaged? 3. Are the attached fittings loose or damaged? 4. Is there evidence of fluid leakage on or around the tank coolers? 5. Are any of the bushings broken or damaged? 6. Is there any visible damage to the parts or packaging which shipped separately from the SSCL?

5.3.2.1.2 Tank Pressure The tank pressure may be positive or negative when received, depending on liquid temperature. In some cases, the vacuum pressure gauge may read zero, which could indicate a tank leak. In such cases, pressure test of the tank shall be done.

5.3.2.1.3 Winding Resistance Measurement This test will be performed by SCE in accordance with their test procedures.

5.3.2.1.4 Winding Impedance Measurement This test will be performed by SCE in accordance with their test procedures.

5.3.2.1.5 Insulation Power factor Test This test will be performed by SCE in accordance with their test procedures.

5.3.2.1.6 Insulation Resistance This test will be performed by SCE in accordance with their test procedures.

5.3.2.2 Field evaluation testing

5.3.2.2.1 Operational Test (Steady State & Transient) Objective: The objective of this test is to monitor the SSCL performance under Steady-State condition of the system in which the SSCL is connected.

Test Schematic: Figure shows the proposed test schematic for the operational test

Page 337: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

5-19

Figure 5‐8 Operational Test Schematic

Test Description: The SSCL will be connected to the 15kV line and load side. Readings will be taken using voltage and current sensors at both ends of the SSCL as shown in the figure. Power, voltage current and power factor will be monitored and recorded with the help of the power monitoring/ recorder. Temperature of the surface of the tank and the cooling liquid will be measured and recorded with the help of the temperature sensors and recorder as shown in the test schematic. Cooling liquid pressure will also be monitored with the help of a pressure gauge.

Page 338: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

6-1

6 SCHEDULE Test # Description Month-1 Month-2 Month-3 Month-4 Month-5 Month-6 Month-7 Month-8 Month-9 Month-10 Month-11 Month-12

Design verification TestsDielectric tests

1 Power Freq. Voltage Withstand test2 Basic Impulse Voltage Withstand test3 Chopped wave Voltage Withstand test4 Current-limiting tests5 Elect. Efficiency tests6 Continuous current capabolity Tests7 Dielectric/ Power Freq. Voltage Withstand test

Refurbish & ship Unit to SCEField evaluation Tests

8 Pre-installation tests9 Field testing

Page 339: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

A-1

A TABLE OF TESTS Name of Test Description Location of Test Component level: CLR – Inductance/Impedance Meas.

144 µH KEMA Power Labs

CLR – Turn‐to‐turn Voltage Meas.

KEMA Power Labs

CLR – Let‐through Current 9000A rms sym. for 0.5sec KEMA Power Labs

Aux Power Supply Transformer Insulation, loading & cont. operation test

SPCO/ KEMA Power Labs

Aux Power Supply Inverter Insulation, loading & cont. operation test

SPCO/ KEMA Power Labs

Current Interruption Test (Building Block)

At 5000A peak from 23kA rms sym. Available fault current

KEMA Power Labs

Continuous Current/Temp. rise Test (Building Block)

1200A rms at low voltage KEMA Power Labs

System level At SPCO:

Insulation resistance (Megger) test

13000 M‐ohm at 3000V DC KEMA Power Labs

Current Limiting Test Limiting to 9kA rms sym from available 23kA rms sym

KEMA Power Labs

Efficiency Test @ 25%, 50%, 75%, 90%, 100% Load

KEMA Power Labs

Audible Noise Test @ 25%, 50%, 75%, 90%, 100% Load

KEMA Power Labs

Nominal‐freq voltage withstand test

50kV rms for 1minute KEMA Power Labs

BIL Test 110kV KEMA Power Labs

Chopped wave test 142 kV peak KEMA Power Labs

Continuous Current/ Temp. rise Test

1200A rms at low voltage KEMA Power Labs

BIL Test (repeat test after continuous current test)

110kV KEMA Power Labs

Partial Discharge Up to 15kV. 100 pC KEMA Power Labs

RIV Test TBD R&B /Alion Lab

Electrical noise/EMI Test TBD R&B /Alion Lab

Page 340: APPENDICES California Energy Commission 500-2013-134-APPENDIXES

A-2

Acceptance test At SCE Lab:

Winding resistance test Westminster facility

Winding impedance test Westminster facility

Turn to turn test Westminster facility

Total loss measurement Test Westminster facility

Voltage‐freq withstand test 50kV rms for 1minute Westminster facility

RIV Test At 120% of Nominal Voltage Westminster facility

BIL Test 110kV Westminster facility

Chopped‐wave 142kV peak Westminster facility

Audible Noise Test Westminster facility

Partial Discharge 19.5kV pre‐stressed, 16.5kV , 100 pico‐coulomb

Westminster facility

Insulation Measurement at 10kV 13,000 mega‐ohm Westminster facility

Insulation power factor test Westminster facility

Fault current limiting test followed by normal operation

23kA for 10 cycles Westminster facility

System level At SCE Field:

Winding resistance Shandin Substation, CA

Winding impedance Shandin Substation, CA

Insulation PF test Shandin Substation, CA

Insulation resistance Shandin Substation, CA

Operations test Normal, Current‐limiting Shandin Substation, CA