Measuring Heavy Fuel Oil consumption at a power station • Replacement of high-maintenance turbine meters • Measuring the feed line and return line allows for evaluation of efficiency • Leak checking in the system 1. Background A power generation company in the UK operates a coal-fired power station. Although the four boilers at the station run predominantly on coal, Heavy Fuel Oil (HFO) is used during the startup phase to get the boilers to optimum operating temperature, or for short-duration operation of the boilers during peak demand. 2. Measurement requirements For measuring the consumption of HFO on each boiler, the company had turbine meters installed. To maintain accuracy, these meters needed to be serviced regularly due to deposits and dirt on the turbine blades, causing significant maintenance costs. Therefore, the company was looking for an alternative flow measurement solution to be operated at much lower cost. Application Data: Medium: Heavy Fuel Oil Flow rate: 10 … 80 kg/sec Temperature: 100 … 140 °C Density: 900 … 930 kg/m 3 Viscosity: 450 … 600 cSt 3. KROHNE Solution KROHNE delivered 8 Coriolis-Mass flow meters OPTIMASS 7300F T80. Nominal size of these meters is DN 80/ 30" with a single straight measuring tube made of titanium. Replacing the turbine meters, the coriolis meters were installed in pairs on each boiler, one measuring the flow to the boiler and the other measuring the return flow of unused oil. APPLICATION NOTE Power Industry

Upload: others

Post on 30-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Application 248 EN 2 - KROHNEkrohne.com/fileadmin/content/files-2/ctry_global/application_reports/... · Medium: Heavy Fuel Oil Flow rate: 10 … 80 kg/sec Temperature: 100 … 3140

Measuring Heavy Fuel Oil consumption at a power station

•Replacementofhigh-maintenanceturbinemeters•Measuringthefeedlineandreturnlineallowsforevaluationofefficiency•Leakcheckinginthesystem

1. Background ApowergenerationcompanyintheUKoperatesacoal-firedpowerstation.Althoughthefourboilersatthestationrunpredominantlyoncoal,HeavyFuelOil(HFO)isusedduringthestartupphasetogettheboilerstooptimumoperatingtemperature,orforshort-durationoperationoftheboilersduringpeakdemand.

2. Measurement requirements

FormeasuringtheconsumptionofHFOoneachboiler,thecompanyhadturbinemetersinstalled.Tomaintainaccuracy,thesemetersneededtobeservicedregularlyduetodepositsanddirtontheturbineblades,causingsignificantmaintenancecosts.Therefore,thecompanywaslookingforanalternativeflowmeasurementsolutiontobeoperatedatmuchlowercost.

Application Data:Medium: HeavyFuelOil Flowrate: 10…80kg/secTemperature: 100…140°C Density: 900…930kg/m3 Viscosity: 450…600cSt

3. KROHNE Solution

KROHNEdelivered8Coriolis-MassflowmetersOPTIMASS7300FT80.NominalsizeofthesemetersisDN80/30"withasinglestraightmeasuringtubemadeoftitanium.Replacingtheturbinemeters,thecoriolismeterswereinstalledinpairsoneachboiler,onemeasuringtheflowtotheboilerandtheothermeasuringthereturnflowofunusedoil.

APPLICATION NOTE Power Industry

Application 248 EN 2.indd 1 15.09.2010 9:13:39 Uhr

Page 2: Application 248 EN 2 - KROHNEkrohne.com/fileadmin/content/files-2/ctry_global/application_reports/... · Medium: Heavy Fuel Oil Flow rate: 10 … 80 kg/sec Temperature: 100 … 3140

©KROHNE09/2010-248

-Su

bjecttoch

ange

with

outn

otice.

4. Customer advantages

TheaccuratemeasurementallowstheoperatorstomonitortheusageofHFOcloselyandpreciselyandtoevaluatetheefficiencyoftheplant.WhentheHFOisnotbeingburnt,itiscontinuouslyrecirculated.Beinginstalledinpairs,themeterscanbeusedasacross-checktoeachotherandalsotocheckforleaksinthesystem.

OPTIMASScoriolismetersdirectlymeasuremassflowrateoftheHFO.Thetitaniumversionwaschosenduetoitshighaccuracyandtemperaturerange.AstandardfeatureofOPTIMASS7000isthatthemetersarecalibratedat3differenttemperaturestocompensateinfluencesoftemperaturechangesonthemeasurement.Acertifiedsecondarycontainment(pressurerating100bar/1450PSI)ensuressafetyofthedevicesastheyareinstalledinahighpressureline.

Astheyhavenomovingpartstobeservicedoradjusted,theOPTIMASSmetersreducemaintenanceefforttozero.Beingastraighttubewithnoinserts,pressuredropisverylowcomparedtotheturbinemetersandthuspumpcapacitycanbereduced,thussavingcosts.

Duetothelocationofthesensorsandforaconvenientread-outon-site,convertersweremountedseparately.Customeralsomadeuseofthefree3yearextendedwarrantywhichensurestotalsupportfromKROHNE.ThiswasadecisivefactortouseOPTIMASSasthemanufacturercouldensurelong-termreliabilityofthedevices.

5. Products used

OPTIMASS 7300• Singlestraighttubemeterwithlowpressuredrop• Highsafetywithstandardpressurerating100bar/1450PSIandPEDapprovedsecondarycontainment

• Noinstallationrestrictions;straightupstreamanddownstreamsectionsarenotrequired

• Allcommonapprovalsavailable• Remoteelectronicssuitableforinstallationupto300mfromthesensor