170 University Avenue 3 rd Floor Box 1 Toronto Ontario M5H 3B3 Canada T416.515.9331 F416.515.1640 www.LRiFire.com APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE KING CAMPUS KING CITY, ONTARIO Prepared by: Rita Cherniavskaya & Elias Frechette Technical Consultants Reviewed by: Lisa Miller, C.E.T. Senior Associate Date: March 11, 2016 LRI File: 17629 ©LRI 2016

Upload: others

Post on 29-Sep-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

170 University Avenue 3rd Floor Box 1 Toronto Ontario M5H 3B3 Canada T416.515.9331 F416.515.1640 www.LRiFire.com

APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE KING CAMPUS KING CITY, ONTARIO

Prepared by: Rita Cherniavskaya & Elias Frechette Technical Consultants Reviewed by: Lisa Miller, C.E.T. Senior Associate Date: March 11, 2016 LRI File: 17629 ©LRI 2016

Page 2: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Table of Contents 1.0  INTRODUCTION ................................................................................... 1 

2.0  BUILDING BACKGROUND ....................................................................... 3 

3.0  APPROACH TO AUDIT & SCOPE LIMITATIONS ........................................... 7 

4.0  SUMMARY ........................................................................................... 9 

APPENDIX A - KING CAMPUS AUDIT SUMMARY TABLES

Page 3: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 1

1.0 INTRODUCTION LRI Engineering Inc. (LRI) has conducted a site audit for general barrier-free accessibility within the Seneca College King campus, in accordance with the approved proposal dated November 25, 2015. The audit was conducted on the basis of the 2012 Ontario Building Code (OBC) barrier-free requirements relative to general floor area maneuverability and washroom requirements, as amended (i.e. amendments effective January 1, 2015). Additionally, the site audit included a visual review of barrier-free service counters, fixed queuing guides, recreational trails and general public waiting areas, forming part of the “Design of Public Spaces” standard of the AODA. The audit included all publicly accessible King campus buildings including accessible parking areas, loading area and exterior pedestrian paths. The following buildings on King campus were audited:

Garriock Hall Student Residence Vet Tech Building Eaton Hall KOLTS Daycare Farm Office/Enviro Landscape Management KW Building Greenhouse/Landscaping Law Lodge Log Cabin Red Barn Chalet 1, 2 and 3 Boat House (Rec Island) Pavillion (Rec Island) Camp Office (Rec Island) Quartermaster Store/Tank Storage (Rec Island) Diving Office/UWS Stores (Rec Island) Welding Shop/Rigging Shop (Rec Island)

The Crime Lab building (#4) was under renovation at the time of the site inspection and was inaccessible to LRI staff. This building is not included in this report. The audit took place over several days of site measurements during the month of December 2015. The scope of the review is based on applicable requirements within Section 3.8 of the OBC. It is noted that the recent accessibility amendments to the OBC primarily within Ontario Regulation 368/13, and within Ontario Regulation 191/14, are partially a result of proposed changes for the built environment as part of the Accessibility for Ontarians with Disabilities Act (AODA) legislation.

Page 4: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 2

The requirements of the 2012 OBC are not retroactive. As such, noncompliant existing building elements are not subject to mandatory upgrading, until such time that renovations are proposed.

Page 5: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 3

2.0 BUILDING BACKGROUND The Seneca College King campus is located in King City, Ontario at 13990 Dufferin Street. The campus is situated in a rural area with multiple clusters of buildings scattered on over 280 acres of land. Access to buildings is provided via pedestrian paths and, where paths are not available, via paved or gravel roads. 2.1 GARRIOCK HALL Garriock Hall is the main and largest campus building on-site. The building is two-storeys in height and contains typical classrooms and faculty offices, a library, cafeteria and gym. The building is not equipped with a passenger elevator; however, a wheelchair lift is provided adjacent to the main entrance for persons using mobility devices. Barrier-free accessible washrooms are located on both building levels; no universal washrooms are provided. The following areas of the building were not audited as they were inaccessible during the site inspection:

GH 1116 Open Office GH 1123 Classroom GH 2165 Diving Lab GH 2014 Office GH 2019 Boardroom A GH 2141 Office GH 2134 Classroom GH 2135 Classroom

2.2 STUDENT RESIDENCE The student residence building is three-storeys in height and is served by two passenger elevators. Each residential level contains amenity spaces such as theatre rooms, games rooms and lounges. The building does not contain barrier-free accessible residential units. Barrier-free washroom facilities are located on the ground floor of the building. 2.3 VET TECH BUILDING The Vet Tech building is one-storey in height and contains classrooms, faculty offices, veterinary labs and operating rooms. The following areas of the building were not audited as they were inaccessible during the site inspection due to construction:

KAH 20, 22, 24, 26, 27 & 29

Page 6: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 4

KAH 12 KAH 31, 39 KAH 40, 41, 42, 44 & 46 KAH 16B & 18B (washrooms)

2.4 EATON HALL Eaton Hall is an existing four-storey heritage building located in the northernmost quadrant of the campus grounds. The majority of the building is currently vacant or undergoing renovation. The basement level contains several meeting rooms, a classroom, gym and ancillary storage and mechanical rooms. The ground floor contains multiple sitting rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e. hotel use). The building does not contain barrier-free washroom facilities. The following areas of the building were not audited as they were inaccessible during the site inspection:

113 Round Room 2.5 KOLTS DAYCARE Kolts Daycare is an existing one-storey building containing a child care facility and early childhood education classrooms. The building is provided with two exterior playground areas and dedicated parking. 2.6 FARM OFFICE/ENVIRO LANDSCAPE MANAGEMENT The Farm Office is an existing two-storey building containing classrooms on the ground floor and faculty offices on the second floor. The second floor is accessible by a stair only. The building does not contain barrier-free washroom facilities.  2.7 KW BUILDING The KW Building is a one storey building located adjacent to the Farm Office containing classrooms and workshop spaces. The building does not contain barrier-free washroom facilities.  2.8 GREENHOUSE/LANDSCAPING BUILDING The greenhouse and Enviro Landscape building is located adjacent to the Farm Office. The building is one storey in height an contains workshop spaces, a classroom and a faculty office. The building does not contain barrier-free washrooms facilities. 

Page 7: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 5

2.9 LAW LODGE The Law Lodge is an existing two-storey building located adjacent to the Farm Office containing classrooms on the ground floor and faculty offices on the second floor. The ground floor also contains a replica courtroom for teaching purposes (i.e. a classroom space). The second floor is accessible by a stair only. The building does not contain barrier-free washroom facilities.  2.10 LOG CABIN The Log Cabin is an existing one-storey building located adjacent to the main campus entrance and containing a single open concept classroom. The Log Cabin is not provided with a barrier-free entrance and is accessible only by stairs from the ground level. A stone path from a paved road and dirt/gravel parking lot are the only points of access to the Log Cabin. The building does not contain barrier-free washroom facilities. 2.11 RED BARN The Red Barn is a single storey barn structure located adjacent to the Vet Tech building. The audit of this building was limited to the approach and barrier-free entry into the building. No access was provided into the barn area but it is understood that it is generally an open space used for the housing of animals. The building does not contain barrier-free washroom facilities.  2.12 BOAT HOUSE The Boat House is an existing one-storey building located on Rec Island that consists of workshop and office spaces. The audit of this building was limited to the approach, barrier-free entry into the building, and access to the offices. The building does not contain barrier-free washroom facilities.  2.13 PAVILLION The Pavillion is a single storey building located on Rec Island, directly adjacent to the Camp Office. The building contains a single classroom, which was inaccessible during the time of the site inspection. The building does not contain barrier-free washroom facilities.  2.14 CAMP OFFICE The Camp Office is a single storey building located on Rec island. The building contains several offices, a classroom and/or meeting room and male and female showers and change rooms.

Page 8: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 6

2.15 QUARTERMASTER STORE/TANK STORAGE The quartermaster store is a single storey building located on Rec Island. The building contains instructional diving equipment and is accessible via stairs only. The building does not contain barrier-free washroom facilities.  

2.16 DIVING OFFICE/UWS STORES The Diving Office is a single storey building located on Rec island. The building contains a single room used as faculty office space. The building does not contain barrier-free washroom facilities.  2.17 WELDING SHOP/RIGGING SHOP The Welding Shop is a single storey building located on Rec Island and contains an open workshop area. The building does not contain barrier-free washroom facilities.  

2.18 CHALET 1, 2 & 3 The Chalets are single-storey residential/cottage buildings located south of Eaton Hall. These buildings contain staged scenes (i.e. Crime Scene Labs) and are used only on occasion for Criminology-type programs. It is understood that the washroom facilities in the Chalets are not intended for use by students and are for staging purposes only.

Page 9: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 7

3.0 APPROACH TO AUDIT & SCOPE LIMITATIONS 3.1 General LRI conducted a site audit over multiple days in December of 2015, to take site measurements and obtain visual information regarding the as-built conditions of the public areas of the campus. A general review of the public areas and the public barrier-free washrooms was conducted. Items not addressed within this report were not included with the scope of the audit, such as door opening forces, temperature control of barrier-free lavatory pipes, and other items of a similar nature. The audit was limited to measurements of room dimensions and washroom fixture locations as it pertains to general maneuverability requirements within the floor area as well as exterior barrier-free paths of travel and building entrances. The items covered were:

Designated barrier-free pedestrian entrances, including items such as: - Ramp widths, doors, power-operators

Typical washroom facilities for general floor area/clearance

maneuverability requirements, including items such as: - Water closet locations (from wall and height), stall sizes, lavatories

locations (from wall and floor), and universal washrooms

Typical washroom accessories for general access and dimensional criteria, including items such as:

- toilet paper dispensers, grab-bars, hand dryers, etc.

Exterior paths of travel such as those leading from designated parking areas to the public building(s) (i.e. per OBC) and recreational campus trails (i.e. as part of the Built Environment Standard), including items such as:

- Exterior pathway widths and slope, - Recreational trail widths and slope

Interior circulation, including items such as:

- Corridor widths, doorway widths, door clearances (i.e. clear floor area where no path of travel, latch side clearances, etc.), vestibule clearances

Wheelchair seating within classrooms that are either tiered/fixed seating,

including items such as: - Access into rooms and to designated seating spaces

Accessible shower facilities, including items such as:

Page 10: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 8

- floor area maneuverability, fixture locations, grab bars, and mounting heights of accessories,

Passenger elevators - car area requirements and control heights

Service counters, fixed queuing guides, and general public waiting areas,

forming part of the “Design of Public Spaces” portion of the AODA, including items such as:

- Counter heights and access widths Not at grade exit facilities were not measured in consideration that these elements do not form part of a barrier-free path of travel. In consideration of the numerous small and rural facilities provided at King Campus for Seneca College, the following renovation provisions are also noted herein for reference. It is reiterated that the requirements of the 2012 OBC are not retroactive. As such, noncompliant existing building elements are not subject to mandatory upgrading, until such time that renovations are proposed. It is noted that Part 11 “Renovations” [OBC 11.3.3.2.(2), for mobility device accommodation] of the OBC will require that future renovations comply with OBC 3.8, where:

the suite has an area greater than 300 m2, and the suite is located in,

- a floor area where the existing difference in elevation between the adjacent ground level and the floor level is not more than 200 mm, or

- a normally occupied floor area which is accessible by a passenger type elevator or other platform equipped passenger elevating device from an entrance storey where the existing difference in elevation between the adjacent ground level and the entrance storey level is not more than 200 mm.

It is further noted that where buildings are not provided with a barrier-free entrance, described above (i.e. greater than 200 mm from adjacent ground level to the entrance storey) [OBC 11.3.3.2.(3), for non-mobility device accommodation], future renovations will be required to comply with:

3.8.1.3.(6), path of travel 3.8.2.3.(6), ambulatory stall 3.8.3.1.(6), signage 3.8.3.3.(19), doors/doorways 3.8.3.7.(1), assistive listening 3.8.3.15.(5), shelves or counters for telephones, and 3.8.3.16.(4), drinking fountains.

Page 11: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

Seneca College – Facilities Management March 11, 2016 Seneca College – King Campus

©LRI 2016 17629 9

4.0 SUMMARY The results of the audit with respect to the barrier-free requirements of the 2012 OBC (including January 2015 amendment) and specific AODA requirements as outlined in Section 1.0 of this report have been summarized in table-format in the attached appendices. Items denoted in red in the appendices indicate elements measured on-site which do not comply with current OBC or AODA dimensional requirements. Where facilities are not provided within a building, the subject matter is removed from the table.

Page 12: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

APPENDIX A

KING CAMPUS AUDIT SUMMARY TABLES

Page 13: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

BOAT HOUSE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior paths forming part of a barrier-free path of travel are not provided (i.e. gravel parking area with no designated pedestrian walking surface).

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

No designated barrier-free/pedestrian path is provided.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable – not loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Not applicable – no designated accessible parking demarcated

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

Not applicable – no designated accessible parking demarcated

Page 14: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

BOAT HOUSE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Not applicable – no designated accessible parking demarcated

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains one pedestrian entrance, which is not designed to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

See above.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

See above.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

Not applicable – entrance contains only a single doorway.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no bridge connections to other buildings.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The building entry door is approximately 655 mm in width. Typical interior doorways are approximately 775 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

No latch-side clearance issues noted.

Page 15: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

BOAT HOUSE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

No latch-side clearance issues noted.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

No latch-side clearance issues noted.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules in building.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

All doors were provided with sufficient clear space on either side.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

Not applicable – building does not contain a Group A occupancy.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibule at building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Not applicable – no washrooms in building.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators in building.

Page 16: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

BOAT HOUSE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators in building.

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators in building.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators in building.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

A barrier-free path of travel throughout the building is provided.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Sufficient lay-by areas provided and no corridors exceed 30 m in length.

1 References are OBC, unless otherwise noted.

Page 17: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CAMP OFFICE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior paths forming part of a barrier-free path of travel are not provided (i.e. gravel parking area with no designated pedestrian walking surface).

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

No designated barrier-free/pedestrian path is provided.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable – not loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Not applicable – no designated accessible parking demarcated

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

Not applicable – no designated accessible parking demarcated

Page 18: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CAMP OFFICE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Not applicable – no designated accessible parking demarcated

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains two pedestrian entrances. Vestibule MI -111 (east entrance) is the designated barrier-free entrance to the building.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

Complies – the main entrance is Vestibule MI-111.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

The main entrance is served by an exterior ramp with an average slope of 9.3%. The ramp is equipped with handrails and guards on both sides and, although does not lead from a designated sidewalk, leads from a level area that is generally wheelchair accessible. The ramp is approximately 1,100 mm in width.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

Both sets of entry doors in Vestibule MI-111 are equipped with power door operators.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no bridge connections to other buildings.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Typical classroom and office doors had a clear width of approximately 835 - 845 mm.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

All doors not equipped with power operators are provided with sufficient latch side clearance.

Page 19: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CAMP OFFICE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

All doors not equipped with power operators are provided with sufficient latch side clearance.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

All doors not equipped with power operators are provided with sufficient latch side clearance.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Vestibule MI-111 had a clearance between series of approximately 1,200 mm between series of doors.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

All doors, with the exception of the doors located in the entry vestibules, were provided with sufficient clear space on their side of the door.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The barrier-free entrance is equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

All series of doors in the barrier-free entrance are equipped with power door operators.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Doors serving public washrooms and change rooms are not equipped with power door operators.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

The power door operators serving the barrier-free entrance are mounted between 940 – 1050 mm above the floor level.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Power door operators were mounted such that sufficient clearance from the swing of the door to the power operator is provided.

Page 20: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CAMP OFFICE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Power operators incorporated the international symbol of Accessibility.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Power operators are located in a visible location and are operable with a closed fist.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

The small corridors created by privacy walls at the entrance to the male and female washrooms/showers are approximately 1010 mm in width.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

The building contains a single public corridor, approximately 1750 mm in width and is less than 30 m in length.

RAMPS

3.8.3.4.(1)(a) Ramps located in a barrier-free path of travel shall have a minimum width of 900 mm between handrails,

The barrier-free ramp at the building entrance is approximately 1080 mm wide between handrails.

3.8.3.4.(1)(c)

have a level area of at least 1 670 mm by 1 670 mm at the top and bottom of a ramp and where a door is located in a ramp, so that the level area extends at least 600 mm beyond the latch side of the door opening, except that where the door opens away from the ramp, the area extending beyond the latch side of the door opening may be reduced to 300 mm,

Sufficient landing space is provided on both ends of the barrier-free ramp.

3.8.3.4.(1)(d)

have a level area at least 1 670 mm long and at least the same width as the ramp, at intervals of not more than 9 m along its length, and where there is a change of 90° or more in the direction or the ramp,

The ramp is divided into three portions, not more than 6 m long and is provided with sufficient landing space at each interval.

3.8.3.4.(1)(e)(i) …be equipped with handrails on both sides… The ramp is equipped with handrails on both sides.

3.8.3.4.(1)(e)(iv) extend horizontally not less than 300 mm beyond the top and bottom of the ramp,

The ramp handrails are provided with the required extensions.

3.8.3.4.(1)(f)(i)

except as provided in Sentence (2), have a wall or a guard on both sides and where a guard is provided the guard shall, be not less than 1 070 mm measured vertically to the top of the guard from the ramp surface, and

The ramp is equipped with guards approximately 1100 mm high.

Page 21: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CAMP OFFICE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.4.(1)(h) provide an intermediate handrail with a minimum clear width of 1100 mm where the ramp is wider than 2200 mm

Not applicable – ramp is less than 2200 mm wide.

SHOWERS

3.8.3.13.(2)(a) A barrier-free shower is to be a minimum of 1 500 mm wide by 900 mm deep

The male and female showers contained barrier-free shower stalls approximately 550 mm wide and 910 mm deep.

3.8.3.13.(2)(b)

Have a clear floor space of not less than 900 mm deep and the same width as the shower, except that fixtures are permitted to project into that space provided they do not restrict access to the shower

The male and female accessible shower stalls were provided with sufficient clearance of the same width as the shower and 900 mm long.

3.8.3.13.(2)(f)(i)

Have a wall mounted continuous L-shaped grab bar conforming to Sentence 3.8.3.8.(7) located on the same wall as the controls, with a horizontal grab bar mounted not more than 850 mm above the finished floor

No grab bars or seats were provided in the male or female barrier-free accessible shower stalls.

1 References are OBC, unless otherwise noted.

Page 22: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

BUILDING NAME: CAMP OFFICEMI 114 MI 116MALE FEMALE

Clear turning radius/interior dimensions (stall) 3.8.3.8(1)(a)  1500 x 1500 1470 x 1570 1520 x 1520Clear turning radius/interior dimensions (universal) 3.8.3.12.(1)(d) 1700 x 1700 n/a n/aClear door width minimum 3.8.3.8.(1)(b)(i) 860 mm 825 830Door swing 3.8.3.8.(1)(b)(ii) Outward Out OutToilet centreline location from wall 3.8.3.8.(2)(a)  460 mm ‐ 480 mm   440 510Toilet seat height 3.8.3.9.(1) 430 mm ‐ 485 mm 610 450Urinal rim height maximum 3.8.3.10.(1) 430 mm 580 n/aTransfer space minimum 3.8.3.8.(2)(a)  900 mm x 1500 mm 980 x 1500 870 x 1500Clearance ‐ stall face to inswinging w/r door minimum 3.8.3.8.(1)(f) 1700 mm * *Clearance ‐ stall face to wall‐mounted fixture/obstruction minimum 3.8.3.8.(1)(f) 1400 mm * *Clear door width 3.8.3.3.(1) 860 mm 845 845Barrier‐free path of travel 3.8.1.3.(1) 1100 mm 1100 1100Latch‐side clearance ‐ push side 3.8.3.3.(10)(b) 300 mm * *Latch‐side clearance ‐ pull side 3.8.3.3.(10)(a) 600 mm * *Power door operator diameter minimum 3.8.3.3.(17)(b) 150 mm not provided not providedPower door operator height (centreline) 3.8.3.3.(17)(a) 900 mm ‐ 1100 mm not provided not providedCentreline location minimum 3.8.3.11.(1)(a) 460 mm * *Top/vanity height 3.8.3.11.(1)(b) 840 mm (max) 790 790Clearance beneath ‐ width 3.8.3.11.(1)(c)(i) 920 mm  * *Clearance beneath ‐ height at front edge 3.8.3.11.(1)(c)(ii) 735 mm 710 690Clearance beneath ‐ height at 205 mm back from front edge 3.8.3.11.(1)(c)(iii) 685 mm 700 690Clearance beneath ‐ height from 300 mm from front edge to wall 3.8.3.11.(1)(c)(iv) 350 mm 700 690Hand dryer height maximum 3.8.3.11.(1)(h) 900 mm ‐ 1200 mm 1040 1080Soap dispensor height maximum 3.8.3.11.(1)(g)(ii) 1200 mm 1100 1170Soap dispensor distance from front edge of vanity maximum 3.8.3.11.(1)(g)(iii) 610 mm 520 530Coat hook height maximum 3.8.3.8.(1)(e) 1200 mm 1200 1200Toilet paper dispensor height minimum 3.8.3.8.(1)(g) 600 mm 570 600Above toilet bar minimum length 3.8.3.8.(6)(a) 600 mm 610 600Above toilet bar mounting height 3.8.3.8.(6)(b) 840 mm ‐ 920 mm 850 890Above toilet bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm 35 35Above toilet bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm 45 45Side wall L‐shape bar minimum length (horizontal component) 3.8.3.8.(5)(a) 750 mm ** **Side wall L‐shape bar minimum length (vertical component) 3.8.3.8.(5)(a) 750 mm ** **Side wall L‐shape bar mounting height 3.8.3.8.(5)(b) 750 mm ** **Side wall L‐shape bar distance from water closet (horizontal) 3.8.3.8.(5)(b) 150 mm ** **Side wall L‐shape bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm ** **Side wall L‐shape bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm ** **

* Signifcantly exceeds OBC minimum dimension, as‐built measurments not taken** Grab bars dimensions not measured (i.e. grab bars not provided or do not conform to current OBC requirements)

Grab Ba

rs2012 OBC REFERENCE

2012 OBC REQUIREMENTBa

rrier‐Free

 Stall

Room

Lavatory

Misc

.

Page 23: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CHALET 1, 2 & 3 – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Designated pedestrian paths to the Chalets are not provided.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1 in 20. See above.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

See above.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, See above.

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

See above.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

No barrier-free entry to the Chalets provided. Due to?

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

See above.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

See above.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

See above.

Page 24: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CHALET 1, 2 & 3 – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no bridge connections provided

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Main Chalet entry doors are approximately 870 mm in clear width. Typical interior Chalet doors are approximately 770 to 850 mm in width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

The following locations are provided with insufficient latch-side clearances where the door swings towards the approach side (applicable to all Chalets): Room 106 Room 103

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

The following locations are provided with insufficient latch-side clearances where the door swings away from the approach side (applicable to all Chalets): Room 106 Room 103

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

Not applicable – no sliding doors provided in buildings.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules provided in buildings.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Sufficient clear space is provided on either side of doors in public portions of the buildings.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The Chalet entry doors are not equipped with power door operators.

Page 25: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

CHALET 1, 2 & 3 – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibules are provided in the buildings.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Not applicable – no useable public washrooms provided in buildings.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

No power door operators provided in the buildings.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

No power door operators provided in the buildings.

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

No power door operators provided in the buildings.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

No power door operators provided in the buildings.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Typical corridors in Chalets are approximately 1010 mm in width.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

See above.

1 References are OBC, unless otherwise noted.

Page 26: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DAY CARE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior walks forming part of a barrier-free path of travel around the building are provided with no abrupt changes in level.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Barrier-free path of travel leading to the entrance is measured to be 1600 mm.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Curb ramps provided where necessary.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides,

Curb ramps have a clear width of at least 1,500 mm.

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Curb ramps do not have detectable warning surfaces. Curb ramps provide a smooth transition.

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

Barrier-free path of travel is provided.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no exterior loading zones

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3,400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Typical barrier-free parking spaces were 5570 mm x 6000 mm.

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

A total of 28 parking spots are provided. As such, a minimum of one Type A barrier-free parking space is required.

Page 27: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DAY CARE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Aisles were between 1500 mm and 2700 mm in width and were marked with contrasting diagonal lines.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building is provided with one (1) pedestrian entrance. A minimum of one (1) barrier-free entrance is required. Entrance 101 is designed to be barrier-free.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

It is understood that Entrance 101 is the principal entry to the building

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Barrier-free building entrances lead from sidewalk level with no abrupt changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

Both series of doors in the vestibule of the barrier-free building entrance are designed in accordance with Article 3.8.3.3.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable - no enclosed walkways or pedestrian bridges provided

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Typical doors have a clear width ranging from 790 mm to 845 mm.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors within a barrier-free path of travel are provided with sufficient latch side clearance on the approach side

Page 28: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DAY CARE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors within a barrier-free path of travel are provided with sufficient latch side clearance away from the approach side

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm on both sides of a sliding door.

Not applicable – no sliding doors

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Entry 101 was measured to be 1740 mm between doors. Vestibule 111 was not measured, but was noted to exceed 1500 mm.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Typical classrooms, offices and public areas are provided with sufficient clear spaces on either side of doors in a barrier-free path of travel.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The exterior door for Entry 101 is not provided with a power door operator. The interior door is provided with a power door operator.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

The exterior door for Entry 101 is not provided with a power door operator.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Washroom 132 and 110 are not provided with a power door operator.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

The power door operator for Entry 101 was measured to be 855 mm above the floor level.

Page 29: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DAY CARE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

The power door operator for Vest 101 was measured to be 480 mm from the door.

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Power door operators do incorporate the International Symbol of Accessibility.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

The power operators are located in a clearly visible position and are capable of being operated by a closed fist.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Typical public corridors are at least 1100 mm in clear width.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Sufficient space provided not more than 30 m apart within barrier-free paths of travel.

1 References are OBC, unless otherwise noted.

Page 30: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

BUILDING NAME: DAYCAREDC 132

Universal WashroomClear turning radius/interior dimensions (stall) 3.8.3.8(1)(a) 1500 x 1500 n/aClear turning radius/interior dimensions (universal) 3.8.3.12.(1)(d) 1700 x 1700 1550 x 2890Clear door width minimum 3.8.3.8.(1)(b)(i) 860 mm 725Door swing 3.8.3.8.(1)(b)(ii) Outward *Toilet centreline location from wall 3.8.3.8.(2)(a)  460 mm ‐ 480 mm   510Toilet seat height 3.8.3.9.(1) 430 mm ‐ 485 mm 440Urinal rim height maximum 3.8.3.10.(1) 430 mm *Transfer space minimum 3.8.3.8.(2)(a)  900 mm x 1500 mm 370 x 1500Clearance ‐ stall face to inswinging w/r door minimum 3.8.3.8.(1)(f) 1700 mm *Clearance ‐ stall face to wall‐mounted fixture/obstruction minimum 3.8.3.8.(1)(f) 1400 mm *Clear door width 3.8.3.3.(1) 860 mm 725Barrier‐free path of travel 3.8.1.3.(1) 1100 mm 1100Latch‐side clearance ‐ push side 3.8.3.3.(10)(b) 300 mm 130Latch‐side clearance ‐ pull side 3.8.3.3.(10)(a) 600 mm *Power door operator diameter minimum 3.8.3.3.(17)(b) 150 mm **Power door operator height (centreline) 3.8.3.3.(17)(a) 900 mm ‐ 1100 mm **Centreline location minimum 3.8.3.11.(1)(a) 460 mm 560Top/vanity height 3.8.3.11.(1)(b) 840 mm (max) 865Clearance beneath ‐ width 3.8.3.11.(1)(c)(i) 920 mm  *Clearance beneath ‐ height at front edge 3.8.3.11.(1)(c)(ii) 735 mm 770Clearance beneath ‐ height at 205 mm back from front edge 3.8.3.11.(1)(c)(iii) 685 mm 730Clearance beneath ‐ height from 300 mm from front edge to wall 3.8.3.11.(1)(c)(iv) 350 mm 390Hand dryer height maximum 3.8.3.11.(1)(h) 900 mm ‐ 1200 mm 900Soap dispensor height maximum 3.8.3.11.(1)(g)(ii) 1200 mm 1100Soap dispensor distance from front edge of vanity maximum 3.8.3.11.(1)(g)(iii) 610 mm 360Coat hook height maximum 3.8.3.8.(1)(e) 1200 mm 1200Toilet paper dispensor height minimum 3.8.3.8.(1)(g) 600 mm 540Above toilet bar minimum length 3.8.3.8.(6)(a) 600 mm 600Above toilet bar mounting height 3.8.3.8.(6)(b) 840 mm ‐ 920 mm 940Above toilet bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm 35Above toilet bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm 45Side wall L‐shape bar minimum length (horizontal component) 3.8.3.8.(5)(a) 750 mm **Side wall L‐shape bar minimum length (vertical component) 3.8.3.8.(5)(a) 750 mm **Side wall L‐shape bar mounting height 3.8.3.8.(5)(b) 750 mm **Side wall L‐shape bar distance from water closet (horizontal) 3.8.3.8.(5)(b) 150 mm **Side wall L‐shape bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm **Side wall L‐shape bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm **

* Signifcantly exceeds OBC minimum dimension, as‐built measurments not taken** Grab bars dimensions not measured (i.e. grab bars not provided or do not conform to current OBC requirements)

Grab Ba

rs2012 OBC REFERENCE

2012 OBC REQUIREMENTBa

rrier‐Free

 Stall

Room

Lavatory

Misc

.

Page 31: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DIVING OFFICE/UWS STORES – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior paths forming part of a barrier-free path of travel are not provided (i.e. gravel parking area with no designated pedestrian walking surface).

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

No designated barrier-free/pedestrian path is provided.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable – not loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Not applicable – no designated accessible parking demarcated

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

Not applicable – no designated accessible parking demarcated

Page 32: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DIVING OFFICE/UWS STORES – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Not applicable – no designated accessible parking demarcated

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The main entrance to the building is approximately 140 mm above grade and is not designed to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

See above.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

See above.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

Not applicable – entrance contains only a single doorway.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no bridge connections to other buildings.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The main entry door is approximately 835 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

No latch-side clearance issues noted.

Page 33: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DIVING OFFICE/UWS STORES – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

No latch-side clearance issues noted.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

No latch-side clearance issues noted.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules in building.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

All doors were provided with sufficient clear space on either side.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

Not applicable – building does not contain a Group A occupancy.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibule at building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Not applicable – no washrooms in building.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators in building.

Page 34: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

DIVING OFFICE/UWS STORES – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators in building.

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators in building.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators in building.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Sufficient barrier-free path of travel provided throughout building.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Wheelchair lay-by areas provided; no corridors exceed 30 m in length.

1 References are OBC, unless otherwise noted.

Page 35: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

EATON HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

The exterior path leading to the building from the parking area containing designated barrier-free spots exceeds the maximum permitted slope of 1:12 and is approximately 1800 mm in width (i.e. ramp from parking area to roadway leading to building entrance).

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20. See above.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Not applicable – no curb ramps required.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps required.

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps required.

RECREATIONAL TRAILS

AODA 80.9 The trail must have a minimum clear width of 1,000 mm.

The trail in the vicinity of the building has a typical clear width of more than 1000 mm.

AODA 80.9 The trail must have a clear height that provides a minimum head room clearance of 2,100 mm above the trail.

Sufficient headroom along the trail is provided throughout.

AODA 80.9 The surface of the trail must be firm and stable.

The surface of the trail is firm and stable throughout.

AODA 80.9 The entrance to the trail must provide a clear opening not less than 850 mm

The entrance to the trail is more than 850 mm in clear width with no obstructions.

AODA 80.9

The trail must have signage indicating the trail length, type of surface, average trail width, maximum slope, and location of amenities, if provided.

The trail is provided with signage indicating the pertinent trail information at the trail entrances on both ends.

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

The pedestrian path leading from the designated accessible parking areas exceeds 1:12 slope (i.e. ramp from parking area to roadway leading to building entrance).

Page 36: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

EATON HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable – no exterior loading zones

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

One accessible spot was noted in the parking lot located near the building. The spot is approximately 5300 x 5800 mm in size (i.e. Type A spot).

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

The number of parking spots provided for Eaton Hall cannot be confirmed via satellite imaging; however, based on the size of the lot, it is estimated that it contains approximately 80 – 100 parking spaces, with one of the spaces designed to be accessible. In conformance with the AODA, the lot is required to have not less than 4 accessible parking spots.

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

No access aisle provided adjacent to the accessible parking spot.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building entrance is served by a temporary ramp. The building contains one entrance (Vestibule 200). This entrance was not designed to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

See above.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.3.4. and leads from a sidewalk.

The ramp does not conform to the design requirements of Article 3.8.3.4 (i.e. the slope of the ramp exceeds 1:12, the ramp is not equipped with handrails on either side and the ramp is not provided with sufficient landing space at the top)

Page 37: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

EATON HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

Not applicable.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no pedestrian bridges

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Typical interior doorways are approximately 700 – 840 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Generally, sufficient latch side clearances were provided throughout. The following locations were provided with insufficient clearances where the door swings towards the approach side: door leading from Round Room 113

entrance hallway door leading to Room 110 from

Vestibule 105

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

The following locations were provided with insufficient clearances where the door swings away from the approach side:

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than 300 mm on both sides of a sliding door.

Not applicable – no sliding doors

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Vestibules in a barrier-free path of travel are provided with sufficient clearances between series of doors.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Sufficient clearances on either side of door in a barrier-free path of travel are provided throughout.

Page 38: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

EATON HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The barrier-free entrance to the building is not equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

See above.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

See above.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

See above.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

See above.

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

See above.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

See above.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Typical interior corridors have a clear width of 1130 mm - 1300 mm.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Interior corridors are not more than 30 m in continuous length. Wheelchair lay-by areas are provided where necessary.

RAMPS

3.8.3.4.(1)(a) Ramps located in a barrier-free path of travel shall have a minimum width of 900 mm between handrails,

Interior ramps have a typical width of 920 mm.

Page 39: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

EATON HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.4.(1)(c)

have a level area of at least 1 670 mm by 1 670 mm at the top and bottom of a ramp and where a door is located in a ramp, so that the level area extends at least 600 mm beyond the latch side of the door opening, except that where the door opens away from the ramp, the area extending beyond the latch side of the door opening may be reduced to 300 mm,

Interior ramps are generally provided with sufficient landing space at the top and bottom of the ramp.

3.8.3.4.(1)(d)

have a level area at least 1 670 mm long and at least the same width as the ramp, at intervals of not more than 9 m along its length, and where there is a change of 90° or more in the direction or the ramp,

Interior ramps contain no changes in direction and are not more than 9 m long.

3.8.3.4.(1)(e)(i) …be equipped with handrails on both sides… Interior ramps are not equipped with handrails.

3.8.3.4.(1)(e)(iv) extend horizontally not less than 300 mm beyond the top and bottom of the ramp, See above.

3.8.3.4.(1)(f)(i)

except as provided in Sentence (2), have a wall or a guard on both sides and where a guard is provided the guard shall, be not less than 1 070 mm measured vertically to the top of the guard from the ramp surface, and

Interior ramps are not equipped with guards.

3.8.3.4.(1)(h) provide an intermediate handrail with a minimum clear width of 1100 mm where the ramp is wider than 2200 mm

Interior ramps are not more than 2200 mm in width.

ELEVATORS

CSA B44 – E-5 Elevator cars with doors that are off-centre shall have a clear width of 915 mm

The elevator car door is approximately 700 mm in clear width.

CSA B44 – E-8 Elevator cars with doors that are off-centre shall have side-to-side interior dimensions of 1,725 mm

The elevator side to side dimension is approximately 970 mm.

CSA B44 – E-8 Elevator cars with doors that are off-centre shall have back wall-to-front return dimensions of 1,370 mm

The elevator front to back dimension is approximately 860 mm.

CSA B44 – E-9.3 Buttons with floor designations shall be located at a maximum of 1,220 mm above the floor measured to the centerline of the buttons

Elevator buttons are approximately 1000 mm above the floor level.

CSA B44 – E-10.1

In elevator cars, both audible and visible car floor location indicators shall be provided to identify the floor location of the car

The elevator is not equipped with audio floor location indications.

   

Page 40: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

SHOWERS

3.8.3.13.(2)(a) A barrier-free shower is to be a minimum of 1 500 mm wide by 900 mm deep

Not applicable – no public showers provided

3.8.3.13.(2)(b)

Have a clear floor space of not less than 900 mm deep and the same width as the shower, except that fixtures are permitted to project into that space provided they do not restrict access to the shower

Not applicable – no public showers provided

3.8.3.13.(2)(f)(i)

Have a wall mounted continuous L-shaped grab bar conforming to Sentence 3.8.3.8.(7) located on the same wall as the controls, with a horizontal grab bar mounted not more than 850 mm above the finished floor

Not applicable – no public showers provided

1 References are OBC, unless otherwise noted.

Page 41: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

FARM OFFICE/ENVIRO LANDSCAPE MANAGEMENT – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

The exterior path leading to the barrier-free building entrance consists of a level plane with no abrupt changes in elevation.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths leading to the building have an average width of 1800 mm.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Not applicable – no curb ramps provided

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

A barrier-free path of travel is provided from the accessible parking area to the building.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no passenger loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

The accessible parking spot serving the building is approximately 6000 mm wide by 5770 mm long (Type A).

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

The parking lot serving the building is provided with approximately 150 spots, including a single barrier-free spot. The parking lot requires not less than 5 barrier-free spots.

Page 42: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

FARM OFFICE/ENVIRO LANDSCAPE MANAGEMENT – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

No access aisles are demarcated next to the barrier-free parking spot; however, the spot has a width of 6000 mm, which is sufficient to accommodate a vehicle and an acceptable access/loading area.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains a single entrance, which is designed to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

The principal entrance to the building is designed to be barrier-free accessible.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Entry to the building is provided from the outdoors art sidewalk level with no changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

The barrier-free entrance consists of a single doorway.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no pedestrian bridges provided.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Doors to public spaces on the ground floor level are more than 860 mm in clear width. Typical office entry doors on the second storey are approximately 800 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors are provided with sufficient latch-side clearances.

Page 43: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

FARM OFFICE/ENVIRO LANDSCAPE MANAGEMENT – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules present in barrier-free path of travel.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Sufficient clear space is provided on either side of doors in public portions of the building.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The building entry doors are not equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibules are provided at the barrier-free building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Doors serving public washrooms are not equipped with power door operators.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators provided.

Page 44: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

FARM OFFICE/ENVIRO LANDSCAPE MANAGEMENT – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators provided.

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators provided.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

The corridor on the ground floor of the building leading to the public washrooms has a clear width of approximately 635 mm. Access to the second storey is provided viz stairs only.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

See above.

1 References are OBC, unless otherwise noted.

Page 45: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GARRIOCK HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior walks forming part of a barrier-free path of travel around the building are provided with no abrupt changes in level. Exterior walks connecting the building to the Law Lodge, Farm Office, KW Building, Greenhouse and KOLTS Daycare are in need of maintenance and repair. The existing guards on the bridge along the exterior walk are not Code conforming and are in need of repair. The slope of the path exceeds 1:12.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20. See above.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Curb ramps provided where necessary.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides,

Curb ramps have a clear width of at least 1,500 mm.

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Curb ramps do not have detectable warning surfaces. Curb ramps provide a smooth transition.

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

Barrier-free path of travel provided from accessible parking spaces.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no exterior loading zones

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Typical accessible spots were 2030 mm wide and 5300 mm long (Lot 10C). Accessible spots in Lot 10e were 2600 mm wide by 5500 mm long (i.e. Type B). No Type A parking spots were noted.

Page 46: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GARRIOCK HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

The parking lots serving the building contain a total of approximately 870 parking spots. As such, not less than 19 of the spots are required to be barrier-free accessible. All parking lots combined provide more than 20 accessible spots, with majority of spots located in Lot 10c.

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Aisles were between 1500 mm and 2700 mm in width and were marked with contrasting diagonal lines.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building is provided with a total of five pedestrian entrances. Three entrances are designed to be barrier-free accessible: - South Entrance on the Upper Level - East Entrance (115) on the Lower Level - GH1237 Entrance on the Lower Level.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

The primary entrance to the building is designed to be barrier-free accessible (South Entrance on the Upper Level)

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Barrier-free building entrances lead from sidewalk level with no abrupt changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

At least one doorway in multiple-door barrier-free entrances is designed to be accessible.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable - no enclosed walkways or pedestrian bridges provided

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Typical classroom doors have a clear width or approximately 845 mm. Typical office doors have a width of approximately 845 mm.

Page 47: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GARRIOCK HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

The following doors are not provided with sufficient latch-side clearances where the door swings towards the approach side: GH 2142 Classroom GH 2140 Classroom GH 2153 Classroom GH 2071 Campus Admin GH 2020 Office Entrance GH 2029 Classroom GH 2035 Test Centre GH 2202 AV Storage GH 2030 Classroom GH 2114 Nursing Lab GH 1190 Open Office GH 1165 Classroom GH 1160 Classroom GH 1123 Classroom GH 1105 Corridor GH 1097 Classroom

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

The following doors are not provided with sufficient latch-side clearances where the door swings away from the approach side: GH 2142 Classroom GH 2071 Campus Admin GH 2019 Office GH 1165 Classroom GH 1160 Classroom GH 1123 Classroom GH 1105 Corridor GH 1097 Classroom

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

Not applicable – no sliding doors in barrier-free paths of travel noted

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Vestibule GH 2096 and GH 2097 are provided with approximately 1570 mm clear space between series of doors. Vestibule GH 1237 is provided with approximately 1300 mm clear space between series of doors.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Typical classrooms, offices and public areas are provided with sufficient clear spaces on either side of doors in a barrier-free path of travel.

Page 48: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GARRIOCK HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

All barrier-free entrances are equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Doors leading from barrier-free entrance vestibules are equipped with power door operators.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Barrier-free washrooms GH 1027 and GH 1028 are not equipped with power door operators.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Typical power door operators are mounted between 900 and 1100 mm from the floor level.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Power door operators were mounted too close or too far away from the swing of the door in the following locations: GH 1237 Vestibule (PDO mounted 260 mm from swing of the door)

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Power door operators did not include the International Symbol of Accessibility in the following locations: GH 1237 Vestibule GH 2097 Vestibule

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will be located in a clearly visible position and be capable of being operated with a closed fist.

Typical power door operators are located in a clearly visible location and are capable of being operated with a closed fist.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Typical public corridors are at least 1100 mm in clear width. Corridor GH 1028 (serving faculty offices) is approximately 1060 mm in clear width.

Page 49: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GARRIOCK HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Typical corridors and barrier-free paths of travel are provided with sufficient wheelchair lay-by space at the required intervals.

INTERIOR RAMPS

3.8.3.4.(1)(a) Ramps located in a barrier-free path of travel shall have a minimum width of 900 mm between handrails,

Typical interior ramps have a clear width of at least 900 mm.

3.8.3.4.(1)(c)

have a level area of at least 1 670 mm by 1 670 mm at the top and bottom of a ramp and where a door is located in a ramp, so that the level area extends at least 600 mm beyond the latch side of the door opening, except that where the door opens away from the ramp, the area extending beyond the latch side of the door opening may be reduced to 300 mm,

Typical interior ramps are provided with sufficient clear space at the top and bottom of the ramp.

3.8.3.4.(1)(d)

have a level area at least 1 670 mm long and at least the same width as the ramp, at intervals of not more than 9 m along its length, and where there is a change of 90° or more in the direction or the ramp,

Typical interior ramps are of a straight run configuration with no changes in ramp direction.

3.8.3.4.(1)(e)(i) …be equipped with handrails on both sides… The mobile ramps provided across existing stairs leading to Classroom GH1150 and GH1140 are not equipped with handrails.

3.8.3.4.(1)(e)(iv) extend horizontally not less than 300 mm beyond the top and bottom of the ramp, See above.

3.8.3.4.(1)(f)(i)

except as provided in Sentence (2), have a wall or a guard on both sides and where a guard is provided the guard shall, be not less than 1 070 mm measured vertically to the top of the guard from the ramp surface, and

The mobile ramps provided across existing stairs leading to Classroom GH1150 and GH1140 are not equipped with guards.

3.8.3.4.(1)(h) provide an intermediate handrail with a minimum clear width of 1100 mm where the ramp is wider than 2200 mm

Typical interior ramps do not exceed 2200 mm in width.

VERTICAL LIFTS

CSA B355 The platform dimension for an enclosed vertical wheelchair lift must be not less than 800 mm wide and 1200 mm long

Vertical lift GH1EL01 has interior dimensions of approximately 1370 (deep) x 885 mm (wide)

CSA B355 Operating devices (i.e. call buttons) must be located between 890 and 1370 mm above the adjacent floor level.

Operating devices are located approximately 1125 mm above the floor level.

Page 50: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GARRIOCK HALL – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

SERVICE COUNTERS

AODA 80.41

Service countertop height must be such that it is usable by a person seated in a mobility aid; there must be sufficient knee clearance provided where a forward approach to the counter is required, and the floor space in front of the counter must be sufficiently clear so as to accommodate the mobility aid CSA Standard B651-12 provides prescriptive countertop height and knee clearance height requirements which may be used as a guide, in the absence of prescriptive requirements under AODA. As per the CSA standard, the countertop height must be between 730 to 860 mm and the knee clearance must be not less than 740 mm wide by 480 mm deep by 680 mm high. A clear floor area of not less than 750 mm by 1200 mm is required in front of service counters

The service counter in GH2060 is approximately 755 mm in height and is designed for a side approach. The service counter in GH2100 is approximately 750 mm in height and is designed for a side approach. The service counter in GH2040 is approximately 750 mm in height and is designed for a side approach. The service counter in GH1048 (Bookstore) is approximately 820 mm in height and is designed for a side approach. The service counter in GH1020 is approximately 745 mm in height and is designed for a side approach. The service counter in GH1056 (Cafeteria) is approximately 920 mm in height. The service counter in GH1077 (One Card) is approximately 1000 mm in height.

SHOWERS

3.8.3.13.(2)(a) A barrier-free shower is to be a minimum of 1 500 mm wide by 900 mm deep

No barrier-free shower facilities provided in public shower rooms.

3.8.3.13.(2)(b)

Have a clear floor space of not less than 900 mm deep and the same width as the shower, except that fixtures are permitted to project into that space provided they do not restrict access to the shower

No barrier-free shower facilities provided in public shower rooms.

3.8.3.13.(2)(f)(i)

Have a wall mounted continuous L-shaped grab bar conforming to Sentence 3.8.3.8.(7) located on the same wall as the controls, with a horizontal grab bar mounted not more than 850 mm above the finished floor

No barrier-free shower facilities provided in public shower rooms.

DRINKING FOUNTAINS

3.8.3.16.(2) A barrier-free drinking fountain shall have a spout located near the front of the unit not more than 915 mm above the finished floor.

Typical drinking fountains are approximately 830 mm in height and designed to allow for front wheelchair approach (i.e. knee clearance underneath).

1 References are OBC, unless otherwise noted.

Page 51: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

BUILDING NAME: GARRIOCK HALLGH 1027 GH 1028 GH 1223 GH 1225 GH 2144 GH 2172MALE FEMALE MALE FEMALE MALE FEMALE

Clear turning radius/interior dimensions (stall) 3.8.3.8(1)(a)                 1500 x 1500 1450 x 1380 1500 x 1450  1590 x 1510 1540 x 1571 4070 x 1350 3350 x 1300Clear turning radius/interior dimensions (universal) 3.8.3.12.(1)(d) 1700 x 1700 n/a n/a n/a n/a n/a n/aClear door width minimum 3.8.3.8.(1)(b)(i) 860 mm 765 745 830 825 855 760Door swing 3.8.3.8.(1)(b)(ii) Out Out Out Out Out Out OutToilet centreline location from wall 3.8.3.8.(2)(a)  460 mm ‐ 480 mm   425 440 460 470 450 440Toilet seat height 3.8.3.9.(1) 430 mm ‐ 485 mm 470 480 430 430 460 500Urinal rim height maximum 3.8.3.10.(1) 430 mm 580 n/a 600 n/a 560 n/aTransfer space minimum 3.8.3.8.(2)(a)  900 mm x 1500 mm 700 x 1380 760 x 1450 1100 x 1500 860 x 1500 850 x 1500 700 x 1500Clearance ‐ stall face to inswinging w/r door minimum 3.8.3.8.(1)(f) 1700 mm * * * 1470 * *Clearance ‐ stall face to wall‐mounted fixture/obstruction minimum 3.8.3.8.(1)(f) 1400 mm * * * * * *Clear door width 3.8.3.3.(1) 860 mm 840 830 835 835 840 845Barrier‐free path of travel 3.8.1.3.(1) 1100 mm 1100 1100 1100 1100 1100 1100Latch‐side clearance ‐ push side 3.8.3.3.(10)(b) 300 mm * * 90 110 * *Latch‐side clearance ‐ pull side 3.8.3.3.(10)(a) 600 mm 290 250 * * * *Power door operator diameter minimum 3.8.3.3.(17)(b) 150 mm not provided not provided not provided not provided 140 x 140 150Power door operator height (centreline) 3.8.3.3.(17)(a) 900 mm ‐ 1100 mm not provided not provided not provided not provided 1045 1090Centreline location minimum 3.8.3.11.(1)(a) 460 mm * * * 340 460 *Top/vanity height 3.8.3.11.(1)(b) 840 mm (max) 830 760 865 860 880 845Clearance beneath ‐ width 3.8.3.11.(1)(c)(i) 920 mm  * * * * * *Clearance beneath ‐ height at front edge 3.8.3.11.(1)(c)(ii) 735 mm 740 670 700 700 770 745Clearance beneath ‐ height at 205 mm back from front edge 3.8.3.11.(1)(c)(iii) 685 mm 690 560 700 700 770 590Clearance beneath ‐ height from 300 mm from front edge to wall 3.8.3.11.(1)(c)(iv) 350 mm 690 560 610 630 620 410Hand dryer height maximum 3.8.3.11.(1)(h) 900 mm ‐ 1200 mm 1070 1080 1250 1280 1010 1020Soap dispensor height maximum 3.8.3.11.(1)(g)(ii) 1200 mm 1010 960 1250 1210 1010 990Soap dispensor distance from front edge of vanity maximum 3.8.3.11.(1)(g)(iii) 610 mm 540 380 545 520 590 350Coat hook height maximum 3.8.3.8.(1)(e) 1200 mm 1210 1200 1220 1220 1530 not providedToilet paper dispensor height minimum 3.8.3.8.(1)(g) 600 mm 1020 980 780 810 975 1080Above toilet bar minimum length 3.8.3.8.(6)(a) 600 mm ** ** 640 620 ** **Above toilet bar mounting height 3.8.3.8.(6)(b) 840 mm ‐ 920 mm ** ** 935 935 ** **Above toilet bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm ** ** 35 35 ** **Above toilet bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm ** ** 45 45 ** **Side wall L‐shape bar minimum length (horizontal component) 3.8.3.8.(5)(a) 750 mm ** ** ** ** ** **Side wall L‐shape bar minimum length (vertical component) 3.8.3.8.(5)(a) 750 mm ** ** ** ** ** **Side wall L‐shape bar mounting height 3.8.3.8.(5)(b) 750 mm ** ** ** ** ** **Side wall L‐shape bar distance from water closet (horizontal) 3.8.3.8.(5)(b) 150 mm ** ** ** ** ** **Side wall L‐shape bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm ** ** ** ** ** **Side wall L‐shape bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm ** ** ** ** ** **

* Signifcantly exceeds OBC minimum dimension, as‐built measurment not taken and considered to be in compliance** Grab bars dimensions not measured (i.e. grab bars not provided or do not conform to current OBC requirements)

Grab Ba

rs2012 OBC REQUIREMENT

Barrier‐Free

 Stall

Room

Lavatory

Misc.

2012 OBC REFERENCE

Page 52: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GREENHOUSE & ENVIRO LANDSCAPE BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

The exterior path leading to the barrier-free building entrance consists of a level plane with no abrupt changes in elevation.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths leading to the building have an average width of 1800 mm.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Not applicable – no curb ramps provided

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

A barrier-free path of travel is provided from the accessible parking area to the building.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no passenger loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

The accessible parking spot serving the building is approximately 6000 mm wide by 5770 mm long (Type A).

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

The parking lot serving the building is provided with approximately 150 spots, including a single barrier-free spot. The parking lot requires not less than 5 barrier-free spots.

Page 53: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GREENHOUSE & ENVIRO LANDSCAPE BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

No access aisles are demarcated next to the barrier-free parking spot; however, the spot has a width of 6000 mm, which is sufficient to accommodate a vehicle and an acceptable access/loading area.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains a single entrance, which is designed to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

The principal entrance to the building is designed to be barrier-free accessible.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Entry to the building is provided from the outdoors art sidewalk level with no changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

The barrier-free entrance consists of a single doorway.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no pedestrian bridges provided.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The main entry door is approximately 855 mm in clear width. Typical interior doors are 760 to 845 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors are provided with sufficient latch-side clearances.

Page 54: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GREENHOUSE & ENVIRO LANDSCAPE BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules present in barrier-free path of travel.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Sufficient clear space is provided on either side of doors in public portions of the building.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The building entry doors are not equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibules are provided at the barrier-free building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Doors serving public washrooms are not equipped with power door operators.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators provided.

Page 55: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

GREENHOUSE & ENVIRO LANDSCAPE BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators provided.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Typical public corridors are approximately 1300 mm in width.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Barrier-free paths of travel are provided with sufficient lay-by spaces at appropriate intervals.

1 References are OBC, unless otherwise noted.

Page 56: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

KW BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

The exterior path leading to the barrier-free building entrance consists of a level plane with no abrupt changes in elevation.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths leading to the building have an average width of 1800 mm.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Not applicable – no curb ramps provided

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

A barrier-free path of travel is provided from the accessible parking area to the building.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no passenger loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

The accessible parking spot serving the building is approximately 6000 mm wide by 5770 mm long (Type A).

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

The parking lot serving the building is provided with approximately 150 spots, including a single barrier-free spot. The parking lot requires not less than 5 barrier-free spots.

Page 57: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

KW BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

No access aisles are demarcated next to the barrier-free parking spot; however, the spot has a width of 6000 mm, which is sufficient to accommodate a vehicle and an acceptable access/loading area.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains a single entrance, which is designed to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

The principal entrance to the building is designed to be barrier-free accessible.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Entry to the building is provided from the outdoors art sidewalk level with no changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

The barrier-free entrance consists of a single doorway.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no pedestrian bridges provided.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The door serving Room KW1 is approximately 855 mm in clear width. The doors serving the public washrooms are approximately 850 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors are provided with sufficient latch-side clearances.

Page 58: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

KW BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules present in barrier-free path of travel.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Sufficient clear space is provided on either side of doors in public portions of the building.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The building entry doors are not equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibules are provided at the barrier-free building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Doors serving public washrooms are not equipped with power door operators.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators provided.

Page 59: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

KW BUILDING – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators provided.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

The interior public corridor is approximately 1300 mm in clear width. A barrier-free path of travel is provided throughout the KW rooms.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Sufficient wheelchair lay-by areas are provided.

1 References are OBC, unless otherwise noted.

Page 60: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

BUILDING NAME: KW BUILDINGWC 1 WC 2UNISEX UNISEX

Clear turning radius/interior dimensions (stall) 3.8.3.8(1)(a)                  1500 x 1500 2090 x 1940 2100 x 2130Clear turning radius/interior dimensions (universal) 3.8.3.12.(1)(d) 1700 x 1700 n/a n/aClear door width minimum 3.8.3.8.(1)(b)(i) 860 mm n/a n/aDoor swing 3.8.3.8.(1)(b)(ii) Outward In InToilet centreline location from wall 3.8.3.8.(2)(a)  460 mm ‐ 480 mm   430 440Toilet seat height 3.8.3.9.(1) 430 mm ‐ 485 mm 390 400Urinal rim height maximum 3.8.3.10.(1) 430 mm n/a n/aTransfer space minimum 3.8.3.8.(2)(a)  900 mm x 1500 mm n/a n/aClearance ‐ stall face to inswinging w/r door minimum 3.8.3.8.(1)(f) 1700 mm * *Clearance ‐ stall face to wall‐mounted fixture/obstruction minimum 3.8.3.8.(1)(f) 1400 mm * *Clear door width 3.8.3.3.(1) 860 mm 850 850Barrier‐free path of travel 3.8.1.3.(1) 1100 mm 1100Latch‐side clearance ‐ push side 3.8.3.3.(10)(b) 300 mm * *Latch‐side clearance ‐ pull side 3.8.3.3.(10)(a) 600 mm * *Power door operator diameter minimum 3.8.3.3.(17)(b) 150 mm not provided not providedPower door operator height (centreline) 3.8.3.3.(17)(a) 900 mm ‐ 1100 mm not provided not providedCentreline location minimum 3.8.3.11.(1)(a) 460 mm * *Top/vanity height 3.8.3.11.(1)(b) 840 mm (max) 780 780Clearance beneath ‐ width 3.8.3.11.(1)(c)(i) 920 mm  * *Clearance beneath ‐ height at front edge 3.8.3.11.(1)(c)(ii) 735 mm 720 720Clearance beneath ‐ height at 205 mm back from front edge 3.8.3.11.(1)(c)(iii) 685 mm 610 610Clearance beneath ‐ height from 300 mm from front edge to wall 3.8.3.11.(1)(c)(iv) 350 mm 610 610Hand dryer height maximum 3.8.3.11.(1)(h) 900 mm ‐ 1200 mm 1100 1100Soap dispensor height maximum 3.8.3.11.(1)(g)(ii) 1200 mm 1180 1050Soap dispensor distance from front edge of vanity maximum 3.8.3.11.(1)(g)(iii) 610 mm 340 300Coat hook height maximum 3.8.3.8.(1)(e) 1200 mm n/a n/aToilet paper dispensor height minimum 3.8.3.8.(1)(g) 600 mm 900 850Above toilet bar minimum length 3.8.3.8.(6)(a) 600 mm not provided not providedAbove toilet bar mounting height 3.8.3.8.(6)(b) 840 mm ‐ 920 mm not provided not providedAbove toilet bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm not provided not providedAbove toilet bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm not provided not providedSide wall L‐shape bar minimum length (horizontal component) 3.8.3.8.(5)(a) 750 mm not provided not providedSide wall L‐shape bar minimum length (vertical component) 3.8.3.8.(5)(a) 750 mm not provided not providedSide wall L‐shape bar mounting height 3.8.3.8.(5)(b) 750 mm not provided not providedSide wall L‐shape bar distance from water closet (horizontal) 3.8.3.8.(5)(b) 150 mm not provided not providedSide wall L‐shape bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm not provided not providedSide wall L‐shape bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm not provided not provided

* Signifcantly exceeds OBC minimum dimension, as‐built measurments not taken** Grab bars dimensions not measured (i.e. grab bars not provided or do not conform to current OBC requirements)

Grab Ba

rs2012 OBC REFERENCE

2012 OBC REQUIREMENTBa

rrier‐Free

 Stall

Room

Lavatory

Misc

.

Page 61: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LAW LODGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior paths of travel to the building are level with no abrupt changes in elevation.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths leading to the building have an average width of 1800 mm.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Not applicable – no curb ramps provided

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

A barrier-free path of travel is provided from the accessible parking area to the building.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no passenger loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

The accessible parking spot serving the building is approximately 6000 mm wide by 5770 mm long (Type A).

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

The parking lot serving the building is provided with approximately 150 spots, including a single barrier-free spot. The parking lot requires not less than 5 barrier-free spots.

Page 62: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LAW LODGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

No access aisles are demarcated next to the barrier-free parking spot; however, the spot has a width of 6000 mm, which is sufficient to accommodate a vehicle and an acceptable access/loading area.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains a single entrance, which is designed to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

The principal entrance to the building is designed to be barrier-free accessible.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Entry to the building is provided from the outdoors art sidewalk level with no changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

The barrier-free entrance consists of a single doorway.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no pedestrian bridges provided.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The entry door to the Court Room is approximately 800 mm in clear width. The entry door to the second storey office area is approximately 840 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors are provided with sufficient latch-side clearances.

Page 63: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LAW LODGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules present in barrier-free path of travel.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Sufficient clear space is provided on either side of doors in public portions of the building.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The building entry doors are not equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibules are provided at the barrier-free building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Doors serving public washrooms are not equipped with power door operators.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators provided.

Page 64: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LAW LODGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators provided.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Interior corridors have a minimum width of approximately 1350 mm. Access to the second storey is provided via stairs only. Persons in mobility devices cannot access the second storey.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

See above.

1 References are OBC, unless otherwise noted.

Page 65: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LOG CABIN – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Access to the building is provided by means of an unpaved road and natural stone walkway leading to exterior stairs. No accessible entry is provided.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20. See above.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Not applicable – no curb ramps provided.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided.

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided.

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

A barrier-free path is not provided from the parking area to the building entrance.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable – no exterior loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Not applicable – no parking spaces demarcated in parking area

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

Not applicable – no parking spaces demarcated in parking area

Page 66: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LOG CABIN – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Not applicable – no parking spaces demarcated in parking area

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains one entrance. the entrance is served by a narrow exterior path consisting of gravel and natural stone. The building is accessible via the exterior porch which is served by stairs. No barrier-free ramps are provided.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

See above.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

See above.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

See above.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no bridge connections provided

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The building entry door is approximately 795 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors are provided with sufficient latch-side clearances.

Page 67: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LOG CABIN – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

Doors are provided with sufficient latch-side clearances.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules present in barrier-free path of travel.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Sufficient clear space is provided on either side of doors in public portions of the building.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

The building entry doors are not equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibules are provided at the barrier-free building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Doors serving public washrooms are not equipped with power door operators.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators provided.

Page 68: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

LOG CABIN – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators provided.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators provided.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

The building consists of a single open concept room with no defined public corridors. As such, minimum 1100 mm wide circulation is provided.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

See above.

1 References are OBC, unless otherwise noted.

Page 69: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

QUARTERMASTER STORE/TANK STORAGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior paths forming part of a barrier-free path of travel are not provided (i.e. gravel parking area with no designated pedestrian walking surface).

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

The building contains a single entrance that is barrier-free accessible (however the entry door is less than 860 mm in clear width).

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

The main building entrance is barrier-free accessible.

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

The entrance is flush with exterior grade, however the building is not served by a sidewalk or designated accessible pedestrian path.

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

Not applicable – entrance contains only a single doorway.

Page 70: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

QUARTERMASTER STORE/TANK STORAGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Not applicable – no bridge connections to other buildings.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building is not provided with a barrier-free entrance (stair access only).

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

See above.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

See above.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

See above.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no bridge connections to other buildings.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The main entrance door is approximately 810 mm in clear width. Typical interior doors are approximately 870 mm in clear width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

No latch-side clearance issues noted.

Page 71: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

QUARTERMASTER STORE/TANK STORAGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

No latch-side clearance issues noted.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

No latch-side clearance issues noted.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules in building.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

All doors were provided with sufficient clear space on either side.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

Not applicable – building does not contain a Group A occupancy.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibule at building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Not applicable – no washrooms in building.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators in building.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators in building.

Page 72: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

QUARTERMASTER STORE/TANK STORAGE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Not applicable – no power door operators in building.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

Not applicable – no power door operators in building.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Sufficient barrier-free path of travel provided throughout building.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Wheelchair lay-by areas provided; no corridors exceed 30 m in length.

1 References are OBC, unless otherwise noted.

Page 73: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

RESIDENCE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior walks forming part of a barrier-free path of travel around the building are provided with no abrupt changes in level.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

Barrier-free path of travel leading to the entrance was not measured, but was noted to significantly exceed 1100 mm.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Curb ramps provided where necessary.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides,

Curb ramps have a clear width of at least 1,500 mm.

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Curb ramps do not have detectable warning surfaces. Curb ramps provide a smooth transition.

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

Barrier-free path of travel provided.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no exterior loading zones

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3,400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Typical barrier-free parking spaces were 2650 mm x 5500 mm in the resident parking lot. Barrier-free parking space was measured to be 4440 mm x 5000 mm in the guest parking lot.

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

A total of 28 parking spots are provided. As such, a minimum of one Type A barrier-free parking space is required.

Page 74: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

RESIDENCE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Aisles were between 1500 mm and 2700 mm in width and were marked with contrasting diagonal lines.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building is provided with a total of three (3) pedestrian entrances. Entrance A101 is noted to be barrier-free accessible.

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

It is understood that A101 is the principal entry to the building

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Barrier-free building entrances lead from sidewalk level with no abrupt changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

One doorway of each barrier-free entrance is designed in accordance with 3.8.3.3.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable - no enclosed walkways or pedestrian bridges provided

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Typical doors have a clear width ranging from 820 mm to 845 mm

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors within a barrier-free path of travel are provided with sufficient latch side clearance on the approach side

Page 75: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

RESIDENCE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors within a barrier-free path of travel are provided with sufficient latch side clearance away from the approach side

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm on both sides of a sliding door.

Not applicable – no sliding doors

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Vestibule A101 was not measured, but was noted to be wider than 1500 mm between doors.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Typical public areas are provided with sufficient clear spaces on either side of doors in a barrier-free path of travel.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

All barrier-free entrances are equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

The interior door of entrance A101 is not provided with a power door operator.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Public barrier-free washrooms A107A and A107B are not provided with a power door operator.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

The power door operators for A101 were noted to be located 910 mm above the finished floor for the interior, and 890 mm above the finished floor for the exterior.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

The exterior power door operator for A101 was measured to be 70 mm from the doors.

Page 76: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

RESIDENCE – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Power door operators do incorporate the International Symbol of Accessibility.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

The power operators are located in a clearly visible position and are capable of being operated by a closed fist.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Typical public corridors are at least 1100 mm in clear width. Measured to be between 1470 mm and 1500 mm.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Sufficient space provided not more than 30 m apart within barrier-free paths of travel.

FIXED SEATING

3.8.3.6.(1)(b)

Spaces designed for wheelchair use must be not less than 900 mm wide and 1525 mm long where designed fro a side approach or not less than 1220 mm long where designed for a front or rear approach.

Sufficient space provided within theatre to accommodate a person in a wheelchair.

3.8.3.6.(1)(d)

Wheelchair spaces must be located such that they are accessible via a barrier-free path of travel, without infringing on egress from and row of seating or aisle.

Aisle width of 1060 mm measured to be provided. Minimum clear width of 1100 mm required.

ELEVATORS

CSA B44 – E-5 Elevator cars with doors that are off-centre shall have a clear width of 915 mm

Elevator door measured to have a clear width of 1130 mm.

CSA B44 – E-8 Elevator cars with doors that are off-centre shall have side-to-side interior dimensions of 1,725 mm

Elevator was measured to be 2060 mm in width.

CSA B44 – E-8 Elevator cars with doors that are off-centre shall have back wall-to-front return dimensions of 1,370 mm

Elevator was measured to be 1410 mm in depth.

CSA B44 – E-9.3 Buttons with floor designations shall be located at a maximum of 1,220 mm above the floor measured to the centerline of the buttons

Controls measured to be 920 mm above the floor.

CSA B44 – E-10.1

In elevator cars, both audible and visible car floor location indicators shall be provided to identify the floor location of the car

Elevator cars are equipped with visual floor indication only.

   

Page 77: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

SERVICE COUNTERS

AODA 80.41

Service countertop height must be such that it is usable by a person seated in a mobility aid; there must be sufficient knee clearance provided where a forward approach to the counter is required, and the floor space in front of the counter must be sufficiently clear so as to accommodate the mobility aid CSA Standard B651-12 provides prescriptive countertop height and knee clearance height requirements which may be used as a guide, in the absence of prescriptive requirements under AODA. As per the CSA standard, the countertop height must be between 730 to 860 mm and the knee clearance must be not less than 740 mm wide by 480 mm deep by 680 mm high. A clear floor area of not less than 750 mm by 1200 mm is required in front of service counters

Service counter in A103A was measured to be 765 mm high. Area beneath the counter measured to be 480 mm deep by 1500 mm wide. Clearance beneath the counter was measured to be 660 mm.

1 References are OBC, unless otherwise noted.

Page 78: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

BUILDING NAME: KING RESIDENCEA107B A107AMale Female

Clear turning radius/interior dimensions (stall) 3.8.3.8(1)(a) 1500 x 1500 2590 x 2120 2800 x 2150Clear turning radius/interior dimensions universal) 3.8.3.12.(1)(d) 1700 x 1700 n/a n/aClear door width minimum 3.8.3.8.(1)(b)(i) 860 mm 790 840Door swing 3.8.3.8.(1)(b)(ii) Outward In InToilet centreline location from wall 3.8.3.8.(2)(a)  460 mm ‐ 480 mm   510 490Toilet seat height 3.8.3.9.(1) 430 mm ‐ 485 mm 430 480Urinal rim height maximum 3.8.3.10.(1) 430 mm 610 ‐

Transfer space minimum 3.8.3.8.(2)(a)  900 mm x 1500 mm 900 x 1500 900 x 1500Clearance ‐ stall face to inswinging w/r door minimum 3.8.3.8.(1)(f) 1700 mm * *Clearance ‐ stall face to wall‐mounted fixture/obstruction minimum 3.8.3.8.(1)(f) 1400 mm * *Clear door width 3.8.3.3.(1) 860 mm 845 850Barrier‐free path of travel 3.8.1.3.(1) 1100 mm 1100 1100Latch‐side clearance ‐ push side 3.8.3.3.(10)(b) 300 mm * *Latch‐side clearance ‐ pull side 3.8.3.3.(10)(a) 600 mm * *Power door operator diameter minimum 3.8.3.3.(17)(b) 150 mm * *Power door operator height (centreline) 3.8.3.3.(17)(a) 900 mm ‐ 1100 mm * *Centreline location minimum 3.8.3.11.(1)(a) 460 mm 620 630Top/vanity height 3.8.3.11.(1)(b) 840 mm (max) 790 820Clearance beneath ‐ width 3.8.3.11.(1)(c)(i) 920 mm  * *Clearance beneath ‐ height at front edge 3.8.3.11.(1)(c)(ii) 735 mm 720 745Clearance beneath ‐ height at 205 mm back from front edge 3.8.3.11.(1)(c)(iii) 685 mm 680 720Clearance beneath ‐ height from 300 mm from front edge to wall 3.8.3.11.(1)(c)(iv) 350 mm 680 720Hand dryer height maximum 3.8.3.11.(1)(h) 900 mm ‐ 1200 mm 900 980Soap dispensor height maximum 3.8.3.11.(1)(g)(ii) 1200 mm 940 970Soap dispensor distance from front edge of vanity maximum 3.8.3.11.(1)(g)(iii) 610 mm 540 550Coat hook height maximum 3.8.3.8.(1)(e) 1200 mm 1080 1140Toilet paper dispensor height minimum 3.8.3.8.(1)(g) 600 mm 650 620Above toilet bar minimum length 3.8.3.8.(6)(a) 600 mm 770 770Above toilet bar mounting height 3.8.3.8.(6)(b) 840 mm ‐ 920 mm 910 910Above toilet bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm 35 35Above toilet bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm 45 45Side wall L‐shape bar minimum length (horizontal component) 3.8.3.8.(5)(a) 750 mm ** **Side wall L‐shape bar minimum length (vertical component) 3.8.3.8.(5)(a) 750 mm ** **Side wall L‐shape bar mounting height 3.8.3.8.(5)(b) 750 mm ** **Side wall L‐shape bar distance from water closet (horizontal) 3.8.3.8.(5)(b) 150 mm ** **Side wall L‐shape bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm ** **Side wall L‐shape bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm ** **

* Signifcanlty exceeds OBC minimum dimension, as‐built measurments not taken** Grab bars dimensions not measured (i.e. grab bars not provided or do not conform to current OBC requirements)

Grab Ba

rs2012 OBC REFERENCE

2012 OBC REQUIREMENTBa

rrier‐Free

 Stall

Room

Lavatory

Misc

.

Page 79: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

VET TECH – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior walks forming part of a barrier-free path of travel around the building are provided with no abrupt changes in level.

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1:20.

The barrier-free path of travel leading to the entrance is approximately 1810 mm.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Curb ramps provided where necessary.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides,

Curb ramps have a clear width of at least 1,500 mm.

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Curb ramps do not have detectable warning surfaces or contrasting colors/textures. Curb ramps provide a smooth transition.

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

Barrier-free path of travel provided.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable - no exterior loading zones

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3,400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Typical barrier-free parking spaces were 3620 mm x 5050 mm.

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

A total of 28 parking spots are provided. As such, a minimum of one Type A barrier-free parking space is required.

Page 80: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

VET TECH – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Aisles were between 1500 mm and 2700 mm in width and were marked with contrasting diagonal lines.

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building is provided with a total of six (6) pedestrian entrances. A minimum of three (3) barrier-free entrances are required. Two (2) entrances are designed to be barrier-free accessible: VEST 2 on the north side VEST 1 on the south side

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

It is understood that VEST 1 is the principal entry to the building

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

Barrier-free building entrances lead from sidewalk level with no abrupt changes in elevation.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

One doorway of each barrier-free entrance is designed in accordance with 3.8.3.3.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable - no enclosed walkways or pedestrian bridges provided

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

Typical doors have a clear width of 845 mm

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

Doors within a barrier-free path of travel are provided with sufficient latch side clearance on the approach side

Page 81: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

VET TECH – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

Doors within a barrier-free path of travel are provided with sufficient latch side clearance away from the approach side

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm on both sides of a sliding door.

Not applicable – no sliding doors

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Vestibule VEST 2 was not measured, but was noted to be significantly wider than 1500 mm between doors. Vestibule VEST 1 is provided with approximately 1400 mm between doors. Vestibule KAH 32A was locked and not available for a measurement, but was noted to be less than 1500 mm between doors based on a visual assessment.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

Typical classrooms, offices and public areas are provided with sufficient clear spaces on either side of doors in a barrier-free path of travel.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

All barrier-free entrances are equipped with power door operators.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

The interior doors of VEST 1 and VEST 2 are not provided with power door operators.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Public barrier-free washrooms KAH 4 and KAH 8 are not provided with a power door operator.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

The power door operators for VEST 1 are located at a sufficient height. The power door operators for VEST 2 were noted to be located 845 mm above the finished floor for the interior, and 880 mm above the finished floor for the exterior.

Page 82: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

VET TECH – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

The power door operators for VEST 1 and VEST 2 are located at a sufficient distance from the doors.

3.8.3.3.(15)(f)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, contain the sign incorporating the International Symbol of Accessibility and

Power door operators do incorporate the International Symbol of Accessibility.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located in a clearly visible position and be capable of being operated with a closed fist.

The power operators are located in a clearly visible position and are capable of being operated by a closed fist.

BARRIER-FREE PATH OF TRAVEL

3.8.1.3.(1) Every barrier-free path of travel shall provide an unobstructed width of at least 1100 mm for the passage of wheelchairs.

Typical public corridors are at least 1100 mm in clear width.

3.8.1.3.(4)

Every barrier-free path of travel less than 1600 mm in width shall be provided with an unobstructed space not less than 1800 mm in width and 1800 mm in length located not more than 30 m apart.

Sufficient space provided not more than 30 m apart within barrier-free paths of travel.

   

Page 83: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

SERVICE COUNTERS

AODA 80.41

Service countertop height must be such that it is usable by a person seated in a mobility aid; there must be sufficient knee clearance provided where a forward approach to the counter is required, and the floor space in front of the counter must be sufficiently clear so as to accommodate the mobility aid CSA Standard B651-12 provides prescriptive countertop height and knee clearance height requirements which may be used as a guide, in the absence of prescriptive requirements under AODA. As per the CSA standard, the countertop height must be between 730 to 860 mm and the knee clearance must be not less than 740 mm wide by 480 mm deep by 680 mm high. A clear floor area of not less than 750 mm by 1200 mm is required in front of service counters

Service counter in KAH1CR01 was measured to be 775 mm high.

DRINKING FOUNTAINS

3.8.3.16.(2) A barrier-free drinking fountain shall have a spout located near the front of the unit not more than 915 mm above the finished floor.

Drinking fountain measured to be 885 mm high.

1 References are OBC, unless otherwise noted.

Page 84: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

BUILDING NAME: VET TECH BUILDINGKAH8 KAH4Female Male

Clear turning radius/interior dimensions (stall) 3.8.3.8(1)(a)                  1500 x 1500 1500 x 1800 1500 x 1700Clear turning radius/interior dimensions (universal) 3.8.3.12.(1)(d) 1700 x 1700 n/a n/aClear door width minimum 3.8.3.8.(1)(b)(i) 860 mm 880 825Door swing 3.8.3.8.(1)(b)(ii) Outward Out OutToilet centreline location from wall 3.8.3.8.(2)(a)  460 mm ‐ 480 mm   490 560Toilet seat height 3.8.3.9.(1) 430 mm ‐ 485 mm 450 470Urinal rim height maximum 3.8.3.10.(1) 430 mm * 630Transfer space minimum 3.8.3.8.(2)(a)  900 mm x 1500 mm 900 x 1500 900 x 1500Clearance ‐ stall face to inswinging w/r door minimum 3.8.3.8.(1)(f) 1700 mm * *Clearance ‐ stall face to wall‐mounted fixture/obstruction minimum 3.8.3.8.(1)(f) 1400 mm * *Clear door width 3.8.3.3.(1) 860 mm 845 845Barrier‐free path of travel 3.8.1.3.(1) 1100 mm 1100 1100Latch‐side clearance ‐ push side 3.8.3.3.(10)(b) 300 mm * *Latch‐side clearance ‐ pull side 3.8.3.3.(10)(a) 600 mm 550 620Power door operator diameter minimum 3.8.3.3.(17)(b) 150 mm * *Power door operator height (centreline) 3.8.3.3.(17)(a) 900 mm ‐ 1100 mm * *Centreline location minimum 3.8.3.11.(1)(a) 460 mm 730 520Top/vanity height 3.8.3.11.(1)(b) 840 mm (max) 810 820Clearance beneath ‐ width 3.8.3.11.(1)(c)(i) 920 mm  * *Clearance beneath ‐ height at front edge 3.8.3.11.(1)(c)(ii) 735 mm 735 745Clearance beneath ‐ height at 205 mm back from front edge 3.8.3.11.(1)(c)(iii) 685 mm 650 670Clearance beneath ‐ height from 300 mm from front edge to wall 3.8.3.11.(1)(c)(iv) 350 mm 400 410Hand dryer height maximum 3.8.3.11.(1)(h) 900 mm ‐ 1200 mm 1000 1000Soap dispensor height maximum 3.8.3.11.(1)(g)(ii) 1200 mm 1100 1100Soap dispensor distance from front edge of vanity maximum 3.8.3.11.(1)(g)(iii) 610 mm 490 490Coat hook height maximum 3.8.3.8.(1)(e) 1200 mm 1200 1190Toilet paper dispensor height minimum 3.8.3.8.(1)(g) 600 mm 480 500Above toilet bar minimum length 3.8.3.8.(6)(a) 600 mm 620 600Above toilet bar mounting height 3.8.3.8.(6)(b) 840 mm ‐ 920 mm 905 905Above toilet bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm 35 35Above toilet bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm 45 45Side wall L‐shape bar minimum length (horizontal component) 3.8.3.8.(5)(a) 750 mm ** **Side wall L‐shape bar minimum length (vertical component) 3.8.3.8.(5)(a) 750 mm ** **Side wall L‐shape bar mounting height 3.8.3.8.(5)(b) 750 mm ** **Side wall L‐shape bar distance from water closet (horizontal) 3.8.3.8.(5)(b) 150 mm ** **Side wall L‐shape bar diameter 3.8.3.8.(7)(b) 35 mm ‐ 40 mm ** **Side wall L‐shape bar clearance from wall 3.8.3.8.(7)(c) 38 mm ‐ 50 mm ** **

* Signifcantly exceeds OBC minimum dimension, as‐built measurments not taken** Grab bars dimensions not measured (i.e. grab bars not provided or do not conform to current OBC requirements)

Grab Ba

rs2012 OBC REFERENCE

2012 OBC REQUIREMENTBa

rrier‐Free

 Stall

Room

Lavatory

Misc

.

Page 85: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

WELDING SHOP/RIGGING SHOP – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

EXTERIOR WALKS & PATHS

3.8.3.2.(1)(a)

Except as provided by Sentence (2), exterior walks that form part of a barrier-free path of travel shall be provided by means of continuous plane not interrupted by steps or abrupt changes in level,

Exterior paths forming part of a barrier-free path of travel are not provided (i.e. gravel parking area with no designated pedestrian walking surface).

3.8.3.2.(1)(c) have an uninterrupted width of at least 1 100 mm and a gradient not exceeding 1 in 20.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(2)

Where a difference in elevation between levels is not more than 200 mm, a curb ramp conforming to Sentences (3) and (4) may be provided.

Exterior paths forming part of a barrier-free path of travel are not provided.

3.8.3.2.(3)(b) The curb ramp shall have a width not less than 1500 mm exclusive of flared sides, Not applicable – no curb ramps provided

3.8.3.2.(3)(c)

have a surface including flared sides that shall be slip resistant, have a detectable warning surface that is color and texture contrasting with the adjacent surfaces, and have a smooth transition.

Not applicable – no curb ramps provided

ACCESSIBLE PARKING/LOADING AREAS

3.8.2.2.(1) A barrier-free path of travel shall be provided from the entrance described in Article 3.8.1.2. to an exterior parking area.

No designated barrier-free/pedestrian path is provided.

3.8.2.2.(3)

An exterior passenger loading zone shall have an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space, and a curb ramp where there are curbs between the aisle and vehicle pull-up space, and a clearance height not less than 3 600 mm.

Not applicable – not loading zones provided

AODA 80.34

Accessible off-street parking spaces must be sized as follows: Type A – 3400 mm wide (van accessible) Type B – 2,400 mm wide (ambulatory)

Not applicable – no designated accessible parking demarcated

AODA 80.36

The number of accessible parking spots provided must conform to the following: 12 spots (or less) – 1 (Type A) 13-100 spots – 4% (Type A & Type B) 100-200 spots – 1 + 3% (Type A & Type B) 201-1000 spots – 2 +2 % (Type A & Type B) +1000 spots – 11 + 1% (Type A & Type B)

Not applicable – no designated accessible parking demarcated

Page 86: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

WELDING SHOP/RIGGING SHOP – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

AODA 80.35

Access aisles adjacent to barrier-free parking spots must extend the full length of the spot and be not less than 1500 mm in width and must be marked with contrasting diagonal lines. One access aisle may be shared by two parking spots.

Not applicable – no designated accessible parking demarcated

BUILDING ENTRANCES

3.8.1.2.(1)

The building is required to be provided with not less than 1 barrier-free entrance when the building is served by 1 to 3 entrances, not less than 2 barrier-free entrances when the building is served by 4 to 6 entrances, and not less than 50% barrier-free entrances where the building is served by more than 5 entrances.

The building contains a single entrance that is barrier-free accessible (however the entry door is less than 860 mm in clear width).

3.8.1.2.(2) One of the barrier-free entrances required by Sentence (1) shall be the principal entry to the building.

The main building entrance is barrier-free accessible.

3.8.1.2.(4)

A barrier-free entrance will lead from the outdoors at sidewalk level, or a ramp that conforms to Article 3.8.4.3. and leads from a sidewalk.

The entrance is flush with exterior grade, however the building is not served by a sidewalk or designated accessible pedestrian path.

3.8.1.2.(5)

A barrier-free entrance that includes more than one doorway is required to have only one doorway that is designed in accordance with Article 3.8.3.3.

Not applicable – entrance contains only a single doorway.

3.8.1.2.(6)

If a walkway or pedestrian bridge connects two barrier-free storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be barrier-free.

Not applicable – no bridge connections to other buildings.

DOORWAYS 

3.8.3.3.(1) Every door that is located in a barrier-free path of travel shall have a clear width of not less than 860 mm when in the open position.

The main entrance doorway is approximately 835 mm in width.

3.8.3.3.(10)(a)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 600 mm beyond the edge of the door if the door swings towards the approach side,

No latch-side clearance issues noted.

Page 87: APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING ... · rooms, dining rooms and halls for private functions. The above-grade levels contain unoccupied residential suites (i.e

 

 

WELDING SHOP/RIGGING SHOP – KING CAMPUS LRI # 17629

Reference1 Code Requirement Evaluation of Compliance

3.8.3.3.(10)(b)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than, 300 mm beyond the edge of the door if the door swings away from the approach side,

No latch-side clearance issues noted.

3.8.3.3.(10)(c)

Unless a power door operator is provided, a door in a barrier-free path of travel shall have a clear space on the latch side extending the height of the doorway not less than,300 mm on both sides of a sliding door.

No latch-side clearance issues noted.

3.8.3.3.(11)

Vestibules in a barrier-free path of travel shall provide a distance of at least 1 500 mm between a series of doors in a vestibule, plus the width of any doors.

Not applicable – no vestibules in building.

3.8.3.3.(13)

Except as provided in Clause 3.8.3.4.(1)(c), the floor surface on each side of a door in a barrier-free path of travel shall be level within a rectangular area as wide as the door plus required latch-side clearance, and whose dimension perpendicular to the closed door is not less than the width of the barrier-free path of travel but does not need to be more than 1 500 mm.

All doors were provided with sufficient clear space on either side.

POWER DOOR OPERATORS

3.8.3.3.(4)

Every door that provides a barrier-free path of travel through a required barrier-free entrance [in a Group A occupancy] shall be equipped with a power door operator.

Not applicable – building does not contain a Group A occupancy.

3.8.3.3.(5)

Where a required barrier-free entrance incorporates a vestibule, the door leading from the vestibule into the floor area is required to also be equipped with a power door operator.

Not applicable – no vestibule at building entrance.

3.8.3.3.(6)(a) A door shall be equipped with a power door operator where the door serves a public washroom required to be barrier-free.

Not applicable – no washrooms in building.

3.8.3.3.(17)(b)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, have its centre located not less than 900 mm and not more than 1 100 mm from the floor level or ground,

Not applicable – no power door operators in building.

3.8.3.3.(15)(d)

Except as provided in Sentence (18), the control for a power door operator required by Sentences (4), (5), and (6) will, be located not less than 600 mm or greater than 1 500 mm beyond the door swing where the door opens towards the control, and

Not applicable – no power door operators in building.