NOTES:
CODES & STANDARDS:
VANCOUVER BUILDING BY-LAW - 2014
NFPA 13 - 2013
NFPA 14 - 2010
ALTERNATIVE SOLUTION PREPARED BY CAMPHORA ENGINEERING ISSUED ON NOVEMBER 20, 2017.
MUNICIPAL WATER SUPPLY:
SUMMER STATIC PRESSURE: 52 PSI
RESIDUAL PRESSURE: 49 PSI AT 1200 USgpm
WATER SUPPLY INFORMATION PROVIDED BY THE CITY OF VANCOUVER (MARCH 6, 2018)
SCOPE OF WORK:
NEW CONSTRUCTION WORK THAT REQUIRES COMPLIANCE WITH APPLICABLE CODES AND STANDARDS.
THE SCOPE OF WORK INCLUDES 2 LEVELS OF PARKING BELOW GRADE AND 6 LEVELS OF OCCUPANCY
ABOVE GRADE.
MAJOR OCCUPANCY & BUILDING CONSTRUCTION:
GROUP C (RESIDENTIAL)
GROUP F, DIV 3 (PARKING GARAGES)
BUILDING IS NON-COMBUSTIBLE CONSTRUCTION, SIX STOREYS
TOWNHOUSES ARE COMBUSTIBLE CONSTRUCTION, TWO STOREYS
BUILDING IS SPRINKLERED THROUGHOUT
ALL EQUIPMENT TO BE ULC, cUL LISTED AND FM APPROVED (WHERE APPLICABLE)
HANGERS AND BRACING IN CONFORMANCE WITH NFPA 13
PIPE & FITTINGS:
RESIDENTIAL & LIGHT HAZARD OCCUPANCIES:
1" THRU 3" CPVC BLAZEMASTER
CPVC BLAZEMASTER: TOLCO FIG. 22, 23, OR 24 HANGER AND WITHIN 6" OF EACH SPRINKLER
CPVC BLAZEMASTER MUST BE SEPARATED FROM AREA SERVED BY SPRINKLER SYSTEM BY CEILINGS,
WALLS OR SOFFITS CONSISTING OF A MINIMUM LATH AND PLASTER,
3
8
" GWB,
1
2
" PLYWOOD, OR
SUSPENDED MEMBRANE WITH STEEL SUSPENSION GRIDS AND PANELS OR TILES HAVING A MASS NOT
LESS THAN 0.35 LB/FT².
CPVC BLAZEMASTER MAY BE USED WITHIN A LIGHT HAZARD OCCUPANCY CONTAINING ORDINARY HAZARD
ROOMS EACH NOT EXCEEDING 400 FT² (I.E. MECHANICAL ROOMS, LAUNDRY ROOMS, STORAGE AREAS).
OTHERWISE NON-COMBUSTIBLE PIPE MUST BE USED.
ELECTRICAL WIRE/CABLE SHALL NOT CONTACT CPVC BLAZEMASTER.
EXPOSED AND ORDINARY HAZARD OCCUPANCIES:
1" SCHEDULE 40 BLACK STEEL
C/W O.I. SCREWED FITTINGS
DRY PIPE 1
1
4
" OR LARGER TO BE SCHEDULE 10 BLACK STEEL
WET PIPE 1
1
4
" OR LARGER TO BE SCHEDULE 10 BLACK STEEL
C/W GROOVED FITTINGS
ALL PIPE IS 1" UNLESS NOTED OTHERWISE
PIPE 1.5" OR LARGER RUN IN CONCEALED CEILING SPACES MAY BE INSTALLED WITHIN AND PARALLEL TO
COMPOSITE OR SOLID WOOD JOISTS. OTHERWISE MUST BE HUNG BELOW COMPOSITE OR SOLID WOOD
JOISTS.
ELECTRICAL REQUIREMENTS:
ELECTRICAL CONNECTIONS TO FLOW SWITCHES, PRESSURE SWITCHES, SUPERVISORY SWITCHES, HEAT
TRACING, AIR COMPRESSOR, AND ALARM PANEL SHALL BE PERFORMED BY OTHERS (DIV.16) AND IS NOT
PART OF THE FIRE SPRINKLER CONTRACTORS SCOPE OF WORK.
SUPERVISORY SWITCHES:
SUPERVISORY SWITCHES SHALL BE INSTALLED ON ALL VALVES SUPPLYING THE FIRE SPRINKLER SYSTEM
INSIDE THE BUILDING. CONDUCT TESTS FOR EACH SUPERVISORY SWITCH TO ENSURE THE INDICATION OF
THE TROUBLE CONDITION AND LOCATION ON THE ANNUNCIATOR BOARD PRIOR TO LEAVING THE SYSTEM
IN SERVICE.
FLEXIBLE COUPLINGS - 2.5" OR LARGER (REQUIRED IN AREAS SUBJECT TO EARTHQUAKES):
· FOR RISERS BETWEEN 3' TO 7' IN LENGTH PROVIDE FLEXIBLE COUPLINGS AT EITHER THE TOP ORBOTTOM
· FOR RISERS GREATER THAN 7' HIGH PROVIDE FLEXIBLE COUPLINGS WITHIN 24" OF TOP AND BOTTOM· FOR MULTISTORY BUILDINGS PROVIDE FLEXIBLE COUPLINGS WITHIN 12' ABOVE FLOORS AND WITHIN
24" BELOW FLOORS
· FOR FLOOR ZONE CONTROLS PROVIDE FLEXIBLE COUPLINGS WITHIN 12" BELOW IF FLOOR ZONECONTROL IS AT LEAST 24" BELOW FLOOR
· FOR FIRE SEPARATIONS OR MASONRY WALLS PROVIDE FLEXIBLE COUPLINGS WITHIN 12" OF BOTHSIDES UNLESS CLEARANCE REQUIREMENTS ARE MET (2" NOMINAL CLEARANCE FOR PIPE LESS THAN
4"; 4" NOMINAL CLEARANCE FOR 4" OR LARGER PIPE)
· AT INTERMEDIATE POINTS OF SUPPORT FOR A RISER PROVIDE FLEXIBLE COUPLINGS ABOVE ANDBELOW
FLEXIBLE COUPLINGS - PIPE OF ANY SIZE (REQUIRED IN AREAS SUBJECT TO EARTHQUAKES):
· FOR DROPS TO HOSE LINES, RACKS SPRINKELRS, AND MEZZANINES PROVIDE FLEXIBLE COUPLINGSWITHIN 24" OF THE TOP AND BOTTOM
· FOR DROPS EXCEEDING 15' THAT SUPPLY 2 OR MORE SPRINKLERS PROVIDE FLEXIBLE COUPLINGSWITHIN 24" OF THE TOP
SEISMIC PROTECTION:
SUPPLY AND INSTALL SWAY BRACE HANGERS ON THE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH
NFPA 13. HORIZONTAL PIPING SHALL BE 2-WAY SWAY BRACED EVERY 40 FEET AND 4-WAY SWAY BRACED
EVERY 80 FEET. THE TOP OF ALL RISERS AND THE CORNER OF ALL LOOPS SHALL ALSO BE EQUIPPED
WITH 4-WAY SWAY BRACES. PIPE HANGERS AND ANCHORS SHALL BE LISTED AND DESIGNED TO RESIST
LATERAL LOADS. POWER-ACTUATED FASTENERS AND DROP-IN ANCHORS ARE NOT PERMITTED.
PIPE HANGERS TO BE INSTALLED TO NFPA 13 REQUIREMENTS AND BE ULC LISTED. CONCRETE INSERTS
TO BE HILTI KWIK BOLT TZ (OR EQUAL) EXPANSION TYPE. DROP-IN ANCHORS ARE NOT PERMITTED.
TRIP TEST CONNECTION:
TRIP TEST CONNECTION NOT LESS THAN 1" TERMINATING IN A SMOOTH BORE CORROSION-RESISTANT
ORIFICE(S) INSTALLED ON THE END OF THE MOST DISTANT SPRINKLER BRANCH LINE(S) WITH A READILY
ACCESSIBLE SHUTOFF VALVE AND PLUG NOT LESS THAN 1" AT LEAST ONE OF WHICH IS BRASS OR NIPPLE
AND CAP.
FLUSHING OF SPRINKLER SYSTEM:
UNDERGROUND MAINS AND FIRE DEPARTMENT CONNECTION SUPPLY LINES SHALL BE FLUSHED BEFORE
CONNECTING TO THE SPRINKLER SYSTEM. FLUSH UNTIL EFFLUENT IS CLEAR AND FREE OF DEBRIS.
AFTER CONSTRUCTION ALL SPRINKLER PIPING SHALL BE FLUSHED TO ENSURE THAT NO DEBRIS IN THE
MAIN OR PIPING SYSTEM IS PRESENT THAT MIGHT OBSTRUCT THE SPRINKLER HEAD ORIFICES. PROVIDE
PROPER DRAINAGE FOR ALL TESTING.
DRAINAGE:
MAINS SHALL BE PITCHED AT LEAST
1
4
" PER 10'.
DRAINS SHALL BE 2".
AUXILIARY DRAINS SHALL CONSIST OF TWO 1" VALVES AND ONE 2"x12" CONDENSATE NIPPLE OR EQUAL,
ACCESSIBLY LOCATED. IDENTIFY LOCATIONS OF AUXILIARY DRAINS IN SYSTEM MAINTENANCE MANUAL.
REVIEW OF WORK DURING CONSTRUCTION:
THE CONTRACTOR SHALL CONTACT CARDINAL ENGINEERING LTD. TO PERFORM CONSTRUCTION REVIEWS
AT "ROUGH-IN" AND AT THE TIME OF THE SYSTEM VERIFICATION AND TRIP TEST FOR FINAL REVIEW PRIOR
TO OCCUPANCY.
DOCUMENTATION:
PROVIDE FIRE ALARM VERIFICATION REPORT, MATERIAL & TEST CERTIFICATES, AND CENTRAL
MONITORING REPORT TO CARDINAL ENGINEERING LTD. PRIOR TO ISSUANCE OF SCHEDULE C-B.
STANDPIPE SYSTEM & ZONING:
SPRINKLER SYSTEM IS ZONED AND MONITORED PER FLOOR
7'-7" CLEARANCE (2.3 M) FOR LOADING AREAS AND PATHWAYS TO PARKING SPACES FOR PERSONS WITH
DISABILITIES AS PER BY-LAW 4.8.1.(c).
CABLE-FREE DEPTH OF CONCRETE REQUIRED TO ACCOMMODATE PIPE ANCHORS :
TO ENSURE ADEQUATE DEPTH FOR SPRINKLER PIPE ANCHORS, THE CONCRETE MUST BE CLEAR OF
ELECTRICAL CABLING WITHIN 3" OF SLAB BOTTOM.
COMBUSTIBLE CONCEALED SPACES:
UNLESS ANY OF THE EXCEPTIONS IN NFPA 13 ARE MET, ALL CONCEALED SPACES ENCLOSED WHOLLY OR
PARTLY BY EXPOSED COMBUSTIBLE CONSTRUCTION SHALL BE PROTECTED BY SPRINKLERS. NOTIFY
ENGINEER IF ANY UNPROTECTED COMBUSTIBLE CONCEALED SPACES.
SYSTEM MAINTENANCE:
FLUSHING OF THE SPRINKLER SYSTEM AND GENERAL MAINTENANCE SHALL BE COMPLETED ON A
REGULAR BASIS AS PER NFPA 25, "INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE
PROTECTION SYSTEMS".
DN
SIDEWALK
THE WONG
RESIDENCE
MAIN ENTRY & FIRE
FIGHTERS' RESPONSE
POINT
3
3
0
.
1
5
'
B
G
1
0
0
.
6
3
m
PARKADE
RAMP
PMT
PROPERTY LINE
54.56 m (179.00')
12'-0" SETBACK
PR
OP
ER
TY
LIN
E
38
.7
0 m
(1
26
.9
7')
10
'-0
" S
ET
BA
CK
54.56 m (179.00')
4'-0" SETBACK
PR
OP
ER
TY
LIN
E
10
'-0
" S
ET
BA
CK
3
3
2
.
3
5
'
B
G
1
0
1
.
3
m
3
3
4
.
5
5
'
B
G
1
0
1
.
9
7
m
3
3
3
.
8
3
'
B
G
1
0
1
.
7
5
m
3
3
3
.
2
0
'
B
G
1
0
1
.
5
6
m
3
3
2
.
9
4
'
B
G
1
0
1
.
4
8
m
3
3
2
.
5
5
'
B
G
1
0
1
.
3
6
m
3
3
1
.
4
6
'
B
G
1
0
1
.
0
3
m
3
3
0
.
8
4
'
B
G
1
0
0
.
8
4
m
14.99 m.
FIREFIGHTER PATH
(Max. 15m)
64.77 m.
FIREFIGHTER PATH
(Max. 65m)
5010 CAMBIE STREET
(TO BE RETAINED WITH
HERITAGE DESIGNATION)
BUILDING ADDRESSING
SIGNAGE
GAS
METER
CAMBIE STREET
'BASALT'
5058 CAMBIE STREET
VANCOUVER, BC
SIAMESE FIRE DEPARTMENT CONNECTION (2
1
2
" x 2
1
2
" x 4")
WITHIN 16' (5 M) OF PRINCIPAL ENTRANCE,
UNOBSTRUCTED FROM STREET, 18"-48" ABOVE GROUND
CITY MAIN (52 PSI STATIC)
DUAL 6" INTERCONNECTED WATER
SUPPLY BLUE BRUTE C900 OR EQUAL
(SEE CIVIL/MECH DRAWINGS)
SPRINKLER CONTRACT
BEGINS IN VALVE ROOM
200'
AP
PR
OX
. DIS
T. F
RO
M F
DC
TO
NE
AR
ES
T H
YD
RA
NT
SPRINKLER SUMMARY:
TY-FRB QR UPRIGHT [122]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES EC-14 UPRIGHT [62]
LISTED COVERAGE: 20' x 20'
155°F, K = 14.0
TY-FRB QR HSW [7]
STANDARD COVERAGE
155°F, K = 5.6
TYCO MODEL SW-24 ECOH HSW [1]
MAXIMUM COVERAGE: 16' x 24'
155°F, K = 11.2
TYCO SERIES LFII RESIDENTIAL PENDENT - TOWER [536]
LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')
MAXIMUM AREA: 170 FT²
155°F, K = 4.9
TY-FRB QR RECESSED PENDENT [60]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES LFII RESIDENTIAL HSW [130]
LISTED COVERAGE: MAX 14' OFF WALL (14'x14')
MAXIMUM AREA: 140 FT²
155°F, K = 4.2
VIKING VK486 RESIDENTIAL HSW [8]
LISTED COVERAGE: 16' x 18'
MAXIMUM AREA: 162 FT²
155°F, K = 4.0
W
TY-FRB QR RECESSED PENDENT [45]
PER ALTERNATIVE SOLUTION
LINEAR COVERAGE: 6'-0" OC
6" TO 12" AWAY FROM GLAZING
MINIMUM FLOW RATE: 27 USGPM
155°F, K = 5.6
TYCO DS-1 QR DRY HSW [3]
STANDARD COVERAGE
155°F, K = 5.6
NOTE: 175°F SPRINKLERS TO BE INSTALLED IN
WASHER/DRYER CLOSETS
TYCO SERIES LFII RESIDENTIAL PENDENT - TH [59]
LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')
MAXIMUM AREA: 170 FT²
155°F, K = 4.9
TYCO DS-1 QR DRY UPRIGHT [24]
MAXIMUM COVERAGE: 15' x 15'
MAXIMUM AREA: 120 FT²
200°F, K = 5.6
DRY PIPE VALVE
SWITCH
SYSTEM LOW AIR PRESSURE ALARM
PRESSURE RELIEF VALVE
W/T TROUBLE CIRCUIT
RESTRICTED ORIFICE
AIR PRESSURE
NOT TO SCALE
VALVE C/W TAMPER SWITCH W/T
TO DRAIN LARGE ENOUGH TO
ACCEPT FULL FLOW.
FROM MAIN WATER SUPPLY
TROUBLE CIRCUIT.
LISTED AIR COMPRESSOR
C/W AIR HOLDING TANK
MAIN DRAIN VALVE
O.S.& Y. OR INDICATING BUTTERFLY
TO OTHER D.P.V's.
ALARM TEST VALVE
W/T ALARM CIRCUIT
ALARM PRESSURE SWITCH
TO SPRINKLER SYSTEM
RESTRICTED ORIFICE OR
SUPPLY SIDE PRESSURE
POTTER BVS
DRY PIPE
VALVE
CHECK VALVE
BALL DRIP
DRAIN CUP
GAUGE
VALVE W/T TROUBLE CIRCUIT.
SYSTEM PRESSURE GAUGE
SUPERVISED ALARM SHUT-OFF
HEAT TRACIING:
HEAT-TRACE & INSULATE WET FIRE PROTECTION PIPING
WHERE INSTALLED IN UNHEATED AREAS. THE FOLLOWING
MATERIALS ARE TO BE EMPLOYED:
-DREXAN HEATRACER MULTIRACE SELF-REGULATING CABLE
-DREXAN TRACEMATE CONTROL AND MONITORING SYSTEM
AND CONNECTED TO FIRE ALARM PANEL
- 1.5" FIBREGLASS PIPE INSULATION AND WEATHERPROOF
EXTERIOR COVERING
-208 V / 3 PHASE
INSTALLATION TO COMPLY WITH DREXAN HEATTRACER FIRE
SPRINKLER FREEZE PROTECTION
DESIGN GUIDE AND INSTALLATION MANUAL: HD102710-1
(OR EQUAL)
24"
12"
FLOW SWITCH W/T ALARM
SWITCH W/T TROUBLE CIRCUIT (0.25 A, 24 VDC OR 125 VAC)
ZONE CONTROL VALVE C/W TAMPER
(VICTAULIC TESTMASTER STYLE 720)
TO SPRINKLERS
DRAIN RISER
FLEXIBLE COUPLING
ALARM TEST MODULE
CHECK VALVE
FLOOR SLAB
FLEXIBLE COUPLING
PRESSURE GAUGE
STANDPIPE
STANDPIPE ANGLE VALVE
WITH CAP & CHAIN
DRAIN RISER
CIRCUIT RETARD SETTING 20 SECONDS
FLOOR ZONE CONTROL W/ CHECK VALVE DETAIL
NOT TO SCALE
(LENGTH NOT TO EXCEED 7'-0")
FIG. 910
1" BLACK STEEL PIPE
TYPICAL
(SCHED. 40)FAST CLAMP
45-59°
FIG. 1000
HANG
ER
TYPICALFIG. 910
212 PIPE CLAMP
FAST CLAMPFIG. 1000
1" BLACK STEEL PIPE (SCHED. 40)
TYPICALFIG. 910
FAST CLAMPFIG. 1000
(SCHED. 40)
1" BLACK STEEL PIPE
LATERAL SWAY BRACING FOR MAINS UP TO 4"
NOT TO SCALE
LONGITUDINAL SWAY BRACING FOR MAINS UP TO 4"
NOT TO SCALE
FAST CLAMP RISER BRACE (FIG. 1000)
NOT TO SCALE
IN SEISMIC ZONES USE HILTI KWIK
BOLT TZ ANCHOR OR EQUAL
IN SEISMIC ZONES USE HILTI KWIK
BOLT TZ ANCHOR OR EQUAL
IN SEISMIC ZONES USE HILTI KWIK
BOLT TZ ANCHOR OR EQUAL
LAG-SCREW IN WOOD
LAG-SCREW IN WOOD
LAG-SCREW IN WOOD
TOLCO FIG. 907
TOLCO FIG. 1000 " FAST CLAMP"
TOLCO FIG. 909 (2)
4-WAY SWAY BRACE:
NOT TO SCALE
IN SEISMIC ZONES USE HILTI KWIK
BOLT TZ ANCHOR OR EQUAL
LAG-SCREW IN WOOD
SPRINKLER PIPE
UNDERGROUND PIPE
2 1/2" HOSE CONNECTION
PRESSURE GAUGE
P
FLOW SWITCH WIRED TO ALARM CIRCUIT
NODE POINTS FOR HYDRAULIC CALCULATION
SUPERVISED CONTROL VALVE W/T TROUBLE CIRCUIT
CHECK VALVE C/W BALL DRIP
N
LEGEND
2 WAY SWAY BRACE
4 WAY SWAY BRACE
DRY OR FROST PROOF HYDRANT WITH FIRE
DEPARTMENT PUMPER CONNECTION
POST INDICATOR VALVE (PIV)
NON-INDICATING STEM VALVE OR DRAIN VALVE
CONCRETE INSERT
10 THREADED ROD
BAND HANGER
HANGER DETAIL - CONCRETE:
NOT TO SCALE
IN SEISMIC ZONES USE HILTI KWIK
BOLT TZ ANCHOR OR EQUAL
PITCH
ACCESSIBLE LOCATION
TEST VALVE IN READILY
PLUG - REMOVE FOR TESTING
CORROSION RESISTANT EQUIVALENT ORIFICE FOR
DRY SYSTEM SPRINKLERS (2 FLOWING)
INSPECTORS TEST CONNECTION FOR DRY SYSTEM
NOT TO SCALE
BRANCH LINE
AL 1 - EXIT EXPOSURE PROTECTION:
· 5.6-K QR, PENDENT SPRINKLERS· 6'-0" SPACING ON-CENTRE AND POSITIONED 6"
TO 12" AWAY FROM GLAZING
· 27 USGPM PER SPRINKLER FED FROM FLOORZONE
· CAN BE USED FOR FLOOR COVERAGE 3' x 6'TOWARDS THE OPPOSITE SIDE OF THE
UNPROTECTED OPENING
NOTE: WHERE STANDARD SPRAY SPRINKLERS ARE
WITHIN 6'-0" OF EACH OTHER OR A RESIDENTIAL
SPRINKLER IS WITHIN 8'-0" OF ANOTHER SPRINKLER A
NON-COMBUSTIBLE CROSS BAFFLE SHALL BE
INSTALLED. THE BAFFLE SHALL BE AT LEAST 8" WIDE
AND 6" HIGH WITH THE BOTTOM OF THE BAFFLE
EXTENDING DOWN TO A LEVEL AT LEAST EQUAL WITH
THE SPRINKLER DEFLECTOR
WATER CURTAIN SPRINKLER AT CEILING
NOT TO SCALE
STANDARD SPRAY PENDENT QR SPRINKLER
SPRINKLER POSITIONED AT CEILING SHALL BE 6"
TO 12" HORIZONTALLY FROM A WALL/BULKHEAD
AT THE PLANE OF THE OPENING
PLANE OF
OPENING
N
SP 1 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
SITE PLAN
SCALE: 3/32" = 1'-0"
-
UP
UP34.78 SFLOCKER
SR-10
34.95 SFLOCKER
SR-09
28.72 SFLOCKER
SR-08
29.84 SFLOCKER
SR-05
28.72 SFLOCKER
SR-06
28.1 SFLOCKER
SR-07
29.78 SFLOCKER
SR-12
29.56 SFLOCKER
SR-13
29.56 SFLOCKER
SR-14
29.56 SFLOCKER
SR-15
29.56 SFLOCKER
SR-16
35.1 SFLOCKER
SR-19
34.32 SFLOCKER
SR-18
35.1 SFLOCKER
SR-17
ELEV. LOBBY
P203
BULK STORAGE
P201
BULK STORAGE
P205
29.14 SFLOCKER
SR-04
29.14 SFLOCKER
SR-03
29.84 SFLOCKER
SR-02
STAIR 4
S4-P2
P2 PARKING
P200
37.87 SFLOCKER
SR-01
E.M.R.
P202
EA
EB
E1
E2
35.37 SFLOCKER
SR-11
STAIR 3
S3-P2
P1
P1
P4
P4
P3
P3
P2
P2
PDPD
PAPA
PCPC
PB
PB
P2 EXHAUST
VESTIBULE
P204
17
'-0
"
1.5
"
19
'-3
"
1.5
"
17
'-0
"
1.5
"
19
'-3
"
1.5
"
17
'-0
"
1.5
"
19
'-3
"
1.5
"
17
'-0
"
1.5
"
19
'-3
"
1.5
"
17
'-0
"
19
'-3
"
1.5
"
17
'-0
"
1.5
"
19'-6" 17'-3"
1.5" 1.5"
19'-6" 17'-3"
1.5" 1.5"
19'-6" 17'-3"
1.5" 1.5"
3'-3"
1"
10'-0"
1"
3'-3"
1"
10'-0"
1"
3'-3"
1"
10'-0"
1"
3'-3"
1"
10'-0"
1"
10
'-0
"
1"
3'-3
"
1"
12
'-9
"
3"
12'-10"
3'-6
"4
'-1
1"
5'-7"8'-9"
6'-7
"
5'-2"6'-2"
7'-2
"3
'-4
"
7'-0"
1"
1.5
"1
.5
"
1.5" 1.5"
1.5
"
1.5"
1"
4'-9"
1.5"
1"
1"1"
4'-5"
1"
4'-1
"5
'-1
0"
4'-8
"
7'-11"
1"
1"
1"
1"
20'-0"
4"
4"
20'-0"
4"
20'-0"
4" 4"
19
'-9
"1
9'-5
"1
0'-9
"8
'-8
"
4"
4"
4"
4"
4"
10'-2"
1.5"
4'-1
"
1"
200°
29'-1"
4"
5'-0"
11
'-1
0"
1"
12
'-9
"
3"
4"
4" UP
26
'-5
"
4"
H.G.
200°
24" A.F.F.
4'-11"
1"
INSPECTOR'S LOW POINT
TEST CONNECTION
10
'-0
"
1"
3'-3
"
1"
10
'-0
"
1"
3'-3
"
1"
4"
9'-11"
4"
9'-11"
7'-2" 12'-10"
4"
11'-8" 7'-1"
4"
11'-1"
1"
5'-7"
1.5"
5'-6"
1.5"
5'-7"
1.5"
5'-6"
1.5"
11'-1"
1.5"
5'-8
"6
'-1
"5
'-6
"1
1'-0
"
3"
3"
3"
3"
7'-2"
1"
4'-0"
1"
4'-0"
1.5"
4'-11" 5'-10" 6'-0"
1.5" 1.5" 1.5"
10'-10" 9'-0"
1" 1"
4'-7" 5'-7" 5'-3" 5'-2"
1.5" 1.5" 1.5" 1.5"
4'-5
"
3"
9'-5
"7
'-9
"5
'-8
"4
'-7
"
3"
3"
3"
3"
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TY-FRB QR UPRIGHT [55]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES EC-14 UPRIGHT [26]
LISTED COVERAGE: 20' x 20'
155°F, K = 14.0
TY-FRB QR HSW [1]
STANDARD COVERAGE
155°F, K = 5.6
N
SP 2 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL P2 PLAN
SCALE: 1/8" = 1'-0"
-
UP
DN
DN
T1
GARBAGE &
RECYCLING
P101
BICYCLES
P106
MECHANICAL
P108
ELECTRICAL
P112
BICYCLES
P107
SERVICE
P102
TYPE TH1
P109
TYPE TH1
P110
TYPE TH1
P111
1087521
AA
BB
CC
D
G
G
EA
EB
E1 E2
TATA
TBTB
T2 T3 T4 T5
F
3
BICYCLES
P105
P1 PARKING
P100
STAIR 3
S3-P1
STAIR 4
S4-P1
ELEV. LOBBY
P103
VESTIBULE
P104
P1
P1
P4
P4
P3
P3
P2
P2
PDPD
PAPA
PCPC
PB
PB
P1 EXHAUST
P2 EXHAUST
VALVE STN.
3'-3"
1"
10'-0"
1"
3'-3"
1"
10'-0"
1"
12
'-9
"
3"
MIN 18" CLEARANCE
BETWEEN TOP OF FLOOR
MOUNTED OBSTRUCTION AND
SPRINKLER DEFLECTOR
MIN 18" CLEARANCE
BETWEEN TOP OF FLOOR
MOUNTED OBSTRUCTION AND
SPRINKLER DEFLECTOR
4'-3
"4
'-2
"
1"
1"
SPRINKLER NOT REQUIRED IN ELECTRICAL
ROOM WITH 2 HRR ENCLOSURE WHERE NO
STORAGE PERMITTED, DRY EQUIPMENT
ONLY, AND DOOR HAS 1.5 HRR RATING
17
'-0
"
1.5
"
19
'-3
"
1.5
"
17
'-0
"
1.5
"
10
'-5
"
1.5
"
17
'-0
"
1.5
"
19
'-3
"
1.5
"
17
'-0
"
1.5
"
17
'-0
"
1.5
"
19
'-3
"
2"
17
'-0
"
1.5
"
10'-5"
1.5"
10'-5"
1.5"
10'-5"
1.5"
10'-5"
1.5"
10'-5"
1"
10'-5"
1"
10'-5"
1"
8'-0"
1"
8'-0"
1"
8'-0"
1"
8'-0"
1"
8'-0"
1"
8'-0"
1"
13
'-3
"
1.5
"
12
'-9
"
1.5
"
6'-11"
2"
9'-7"
2"
5'-8"
2"
8'-1
"
1.5
"
11
'-0
"
1.5
"
8'-1
"
1.5
"
11
'-0
"
1.5
"
5'-7"8'-11"
1"1"
4'-9"
1"
6'-7
"
1"
8'-11"
1"
9'-2
"6
'-1
0"
10
'-1
"
4"
4"
9'-2
"
4"
4"
4"
31
'-2
"
6'-9"
4"
4"
8'-9"
1.5"
8'-1
0"
1.5
"
8'-7"
1.5"
7'-1"
1.5"
10
'-5
"
1.5
"
7'-10"
1.5"
10
'-5
"
1.5
"
16
'-8
"
1.5
"
16
'-8
"
1.5
"
7'-7
"
1.5
"
11'-2"
1.5"
20'-0"
1.5"
5'-9" 14'-3"
1.5" 1.5"
20'-0"
1.5"
5'-9" 14'-3"
1.5" 1.5"
15'-5" 14'-3"15'-5"
1.5" 1.5" 1.5"
4'-9"
1.5"
8'-1
0"
1"
8'-5"
1"
3'-3"
1"
10'-0"
1"
3'-3"
1"
10'-0"
1"
3'-3"
1"
10'-0"
1"
3'-3"
1"
10'-0"
1"
10
'-0
"
1"
8'-2
"
1"
10
'-0
"
1"
8'-2
"
1"
13
'-7
"
27'-5"
9'-7"9'-0" 6'-3"
4'-0
"
3"
6'-1
1"
10
'-1
1"
1.5
"1
.5
"
10
'-1
1"
3"
19
'-5
"3
6'-8
"
4'-10" 15'-0"17'-8"
15'-8" 15'-8"19'-10"19'-10"19'-10"19'-10"
4" 4" 4" 4" 4" 4" 4" 4" 4"
4"
4"
4"
4" 4" 4" 4"
8'-7
"
1.5
"
10
'-9
"1
0'-0
"
13'-0"
1"
1.5
"1
.5
"
8'-8"
1.5"
8'-8"
1.5"
DUAL 6" INTERCONNECTED WATER SUPPLY
BLUE BRUTE C900 OR EQUAL
(SEE CIVIL/MECH DRAWINGS)
SPRINKLER CONTRACT
BEGINS IN VALVE ROOM
01
02
03
04
4" UP WET
17'-0"
11
'-8
"
4"
4"
4" UP
TO FDC
HSW HEADS BELOW
OVERHEAD GATE
3" UP
TO TH 109
3" UP
TO TH 110 & 111
7'-1
1"
4"
51'-4"
4" TO TOWNHOUSES
7'-1
1"
3"
37'-11"
4" TO TOWNHOUSES
83
'-5
"
4" W
ET
T
O T
OW
NH
OU
SE
S
4" UP
WET
0508 06
07
1012
13
11
1" UP 1" UP1" UP
HG HG HG
HG
36'-6"
2.5"
GALVANIZED PIPE
EXTERNALLY WRAPPED
49
4'-1
1"
1"
2.5" UP
TO H/C
71
'-2
"
2.5
" D
RY
30'-4"
2.5" DRY TO H/C
x 3
4" DN
37'-0"
4"
42
'-1
0"
4"
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TY-FRB QR UPRIGHT [60]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES EC-14 UPRIGHT [36]
LISTED COVERAGE: 20' x 20'
155°F, K = 14.0
TY-FRB QR HSW [2]
STANDARD COVERAGE
155°F, K = 5.6
TYCO MODEL SW-24 ECOH HSW [1]
MAXIMUM COVERAGE: 16' x 24'
155°F, K = 11.2
TYCO SERIES LFII RESIDENTIAL PENDENT [9]
LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')
MAXIMUM AREA: 170 FT²
155°F, K = 4.9
HYDRAULIC CALCULATION:
AREA: PARKING LEVEL 1
NFPA 13 - OH GROUP 1
DESIGN AREA: (1500 FT² + 30%) 1950 FT²
ACTUAL DESIGN AREA: 2002 FT²
DENSITY: 0.15 USgpm / FT²
No. OF EC-14 SPRINKLERS FLOWING: 6
COVERAGE / EC-14 SPRINKLER: 20' x 20'
MINIMUM DISCHARGE / EC-14 SPRINKLER: 60 USGPM
SYSTEM DEMAND AT CITY CONNECTION:
643.4 USgpm at 44.0 PSI
EXCESS PRESSURE AT DEMAND FLOW: 7.1 PSI
INCLUDING 250 USGPM OUTSIDE HOSE ALLOWANCE
N
SP 3 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL P1 PLAN
SCALE: 1/8" = 1'-0"
-
T1
10
10875
2
2
1
1
AA
BB
CC
DD
GG
EA
EB
E1 E2
TATA
TBTB
T2 T3 T4 T5
4 6 9
F
F
3
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
7' - 8" A.F.F.
C-1
8' - 2" A.F.F.
C-1
8' - 0" A.F.F.
R-C-7
8' - 0" A.F.F.
R-C-7
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C4
8' - 9" A.F.F.
R-C-7
8' - 0" A.F.F.
C-1
8' - 2" A.F.F.
C-1
8' - 8" A.F.F.
C-1
8' - 8" A.F.F.
C-1
8' - 8" A.F.F.
R-C-7
7' - 8" A.F.F.
4'-7"
1"
4'-7"
1"
4'-7"
1"
4'-7"
1"
8'-3
"
1.5
"
8'-3
"
1.5
"
8'-3
"
1.5
"
4" DN WET
11
'-9
"
4"
19'-3" 85'-10"17'-8"
10
'-2
"
4"
4" 4" 4"
10
'-2
"
4"
4" DN
4" DN
200°
4"
4" 4" 4" 4"
2"
1.5" 1.5" 1.5"
1.5"1.5"
1.5"
1.5"
W
W
W
7'-7
"
1.5
"
14'-11"
1.5"
6'-0
"
1.5
"
2"
1.5
"
2"
2"
W
W
W W
W
W
W
2"
BULKHEAD REQ'D
W W
14'-2"
1.5"
6'-0"
1.5"
17
'-4
"
1.5
"
6'-0
"
1"
6'-0
"
1.5
"
6'-0
"
2"
6'-0
"
2"
4'-0
"
4'-6"
1.5"
2"
7'-0" 8'-0"
4"4"4"
1.5"
1.5"
W
WW
W
W W W
1.5"
ZC
5'-6"
1.5" 2"
1.5"
1.5"
9'-4"
8'-8
"
1.5
"
6'-0"
1.5"
4'-10"
1.5"
18
'-0
"
1.5
"
1.5"1.5"
1.5"
1.5
"
1.2
5"
1.2
5"
2"
1.5
"1
.5
"
1.2
5"
1.2
5"
06
05
07
11
08
10 09
12
13
14
17
15
16
18
19
20
2122
23
24
25
26
7'-0
"
1.5
"
7'-0
"
1.5
"
2"
12'-4"
3'-0"
1.5"1"
1"
4"
27
28
29
3031
32
34 37
33
40
39
41
35
36
38
NOTE: STEEL PIPE TO
BE USED IN AMENITY ROOM
3" DN
3" DN
1.5
"
1.5"
2"
2"2"
1.5"
1.5"
2"2"
2"
2"2"
2"
1.5" UP
1.5" UP
1.5" UP 1" UP
1" UP
1" UP
1.5" UP
1.5" UP
1.5" UP
1.5" UP 1" UP
1.5" UP
1.5" UP1.5" UP
1.5
"
1.5
"
1" DN1" DN 1" DN
SIAMESE FIRE DEPARTMENT CONNECTION (2
1
2
" x 2
1
2
" x 4")
WITHIN 16' (5 M) OF PRINCIPAL ENTRANCE,
UNOBSTRUCTED FROM STREET, 18"-48" ABOVE GROUND
6'-6
"
1"
1"
4'-7"
50
53
545556
52
1.5"
1.5
"
1.5
"
1.5
"
1.5
"
2"
7273
74 7571
2"
3'-0"
BAFFLE REQUIRED
2.5" HOSE
CONNECTION
W
6'-4
"
7'-1
"8
'-4
"
1"
1"
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [77]
LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')
MAXIMUM AREA: 170 FT²
155°F, K = 4.9
TY-FRB QR RECESSED PENDENT [19]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES LFII RESIDENTIAL HSW [27]
LISTED COVERAGE: MAX 14' OFF WALL (14'x14')
MAXIMUM AREA: 140 FT²
155°F, K = 4.2
TY-FRB QR HSW [1]
STANDARD COVERAGE
155°F, K = 5.6
VIKING VK486 RESIDENTIAL HSW [2]
LISTED COVERAGE: 16' x 18'
MAXIMUM AREA: 162 FT²
155°F, K = 4.0
W
TY-FRB QR RECESSED PENDENT [16]
PER ALTERNATIVE SOLUTION
LINEAR COVERAGE: 6'-0" OC
6" TO 12" AWAY FROM GLAZING
MINIMUM FLOW RATE: 27 USGPM
155°F, K = 5.6
TOWNHOUSE SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [20]
LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')
MAXIMUM AREA: 170 FT²
155°F, K = 4.9
TYCO DS-1 QR DRY HSW [3]
STANDARD COVERAGE
155°F, K = 5.6
TY-FRB QR UPRIGHT [7]
STANDARD COVERAGE
155°F, K = 5.6
HYDRAULIC CALCULATION:
AREA: LEVEL1 - AMENITY WITH WATER CURTAIN
NFPA 13 - LIGHT HAZARD
DESIGN AREA: (1500 FT² - 40%) 900 FT²
ACTUAL DESIGN AREA: 602 FT²
DENSITY: 0.10 USGPM / FT²
No. OF SPRINKLERS FLOWING: 7
MAXIMUM DESIGN COVERAGE / SSP SPRINKLER: 225 FT²
MINIMUM FLOW / SSP SPRINKLER: 22.5 USGPM
No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 5 (NODES
19,20,22,23,24,25,26)
MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
490.8 USgpm at 47.5 PSI
EXCESS PRESSURE AT DEMAND FLOW: 3.9 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE LEVEL 1 - UNIT 105
NFPA 13 W/WATER CURTAIN
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 3
LISTED COVERAGE / RES. PENDENT: 18' x 18'
MAXIMUM COVERAGE / RES. PENDENT: 170 FT²
MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm
No. RESIDENTIAL HSW SPRINKLERS FLOWING: 1
LISTED COVERAGE / RES. HSW: 14' x 14'
MAXIMUM COVERAGE / RES. HSW: 140 FT²
MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm
No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 3 (NODES 35,36,41)
MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
272.5 USgpm at 48.1 PSI
EXCESS PRESSURE AT DEMAND FLOW: 3.7 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
W
TY-FRB QR RECESSED PENDENT [4]
PER ALTERNATIVE SOLUTION
LINEAR COVERAGE: 6'-0" OC
6" TO 12" AWAY FROM GLAZING
MINIMUM FLOW RATE: 27 USGPM
155°F, K = 5.6
N
SP 4 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL 1 PLAN
SCALE: 1/8" = 1'-0"
-
10
10875
2
2
1
1
AA
BB
CC
DD
GG
EA
EB
E1 E2
4 6 9
F
F
3
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
7' - 8" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
C-1
8' - 6" A.F.F.
W/D
W/D
W/D
T1
TA
TB
T2 T3 T4 T5
TYPE TH1
109
TYPE TH1
110
TYPE TH1
111
1.5
"
1.5"
2"1.5"2"
1.5
"
1.25"
2"
1.5
"
2" 1.25"
1.5
"
1.2
5"
1.2
5"
W
W
WW
W
W
W
W
W
W
W
WW
W
W
W W
BULKHEAD REQ'D
BULKHEAD REQ'D
BULKHEAD REQ'D
BULKHEAD REQ'DBULKHEAD REQ'D
BULKHEAD REQ'D
BULKHEAD REQ'D
W
1.5"
4'-5
"
1.5
"
5'-8
"7
'-9
"
1.5
"1
.5
"
2"
2"
2"
2"
9'-4
"9
'-3
"
6'-0"
11'-0"
11'-1"
4'-4
"
1.5
"
3'-9"
1.5"
13
'-8
"
1.5
"
10
'-4
"
2"
6'-0"
2"
4'-9"
2"
3'-8
"
2"
2"
4'-5
"
2"
5'-6"
2"
6'-6"
2"
3'-5"
2"
5'-0
"
2"
28'-9"
1.5"
6'-1
"6
'-0
"
1.5
"1
.5
"
6'-0"
2"
6'-0"
2"
12'-10"
2"
05
060708 26
28
30
2731
32 34
36
37
35
38
40
43
39
41
42
13
0912
14
15
19
1817
16
22
BULKHEAD REQ'D
33
44
46
47
48
2"
1.5
"1
.5
"
2"
1.25"
1.5"1.5"
1.5"
W
BULKHEAD REQ'D
1.5"
2"
P
3" 3" 3" 3"
05
29
2"
200°
2"
1.5" 1.5" 1.5"1.5"
W
W
7'-7
"
1.5
"
14'-11"
1.5"
6'-0
"
1.5
"
2"
2"
2"
2"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.5" DN
1.5" DN
1.5" DN
1" DN
1" DN
1" DN
W W
1.5" DN
6'-0"
1.5"
W W
1.5" DN
6'-0"
1.5"
WATER CURTAIN SPRINKLERS
IN RAISED CEILING SUCH THAT
DEFLECTOR IS ABOVE ADJACENT CEILING
HEIGHT TO PREVENT COLD SOLDERING
3"
66
68
70
69
67
62
61
57
63
65
64
58
59
60
1.5" DN
1" DN 1" DN
76
77
78
79
80
82
81
8384
85
86
87
CONCRETE PILLAR
TO ACT AS BAFFLE
13'-4"
1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP
1" UP 1" UP 1" UP
1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP
1" UP
WATER CURTAIN SPRINKLERS
IN RAISED CEILING SUCH THAT
DEFLECTOR IS ABOVE ADJACENT CEILING
HEIGHT TO PREVENT COLD SOLDERING
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [92]
LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')
MAXIMUM AREA: 170 FT²
155°F, K = 4.9
TY-FRB QR RECESSED PENDENT [7]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES LFII RESIDENTIAL HSW [38]
LISTED COVERAGE: MAX 14' OFF WALL (14'x14')
MAXIMUM AREA: 140 FT²
155°F, K = 4.2
TY-FRB QR HSW [1]
STANDARD COVERAGE
155°F, K = 5.6
VIKING VK486 RESIDENTIAL HSW [3]
LISTED COVERAGE: 16' x 18'
MAXIMUM AREA: 162 FT²
155°F, K = 4.0
W
TY-FRB QR RECESSED PENDENT [21]
PER ALTERNATIVE SOLUTION
LINEAR COVERAGE: 6'-0" OC
6" TO 12" AWAY FROM GLAZING
MINIMUM FLOW RATE: 27 USGPM
155°F, K = 5.6
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE LEVEL 2 - UNIT 210
NFPA 13 W/WATER CURTAIN
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 2
LISTED COVERAGE / RES. PENDENT: 18' x 18'
MAXIMUM COVERAGE / RES. PENDENT: 170 FT²
MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm
No. RESIDENTIAL HSW SPRINKLERS FLOWING: 2
LISTED COVERAGE / RES. HSW: 14' x 14'
MAXIMUM COVERAGE / RES. HSW: 140 FT²
MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm
No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 5 (NODES 14,15,17,18,19)
MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
331.5 USgpm at 48.0 PSI
EXCESS PRESSURE AT DEMAND FLOW: 3.7 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
TOWNHOUSE SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [30]
LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')
MAXIMUM AREA: 170 FT²
155°F, K = 4.9
W
TY-FRB QR RECESSED PENDENT [4]
PER ALTERNATIVE SOLUTION
LINEAR COVERAGE: 6'-0" OC
6" TO 12" AWAY FROM GLAZING
MINIMUM FLOW RATE: 27 USGPM
155°F, K = 5.6
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE TOWNHOUSE LEVEL 2 - UNIT 110
NFPA 13 W/WATER CURTAIN
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 8
LISTED COVERAGE / RES. PENDENT: 18' x 18'
MAXIMUM COVERAGE / RES. PENDENT: 170 FT²
MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm
No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 2 (NODES 61,62)
MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
333.3 USgpm at 48.9 PSI
EXCESS PRESSURE AT DEMAND FLOW: 2.9 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE TOWNHOUSE LEVEL 2 - UNIT 111
NFPA 13
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 8
LISTED COVERAGE / RES. PENDENT: 18' x 18'
MAXIMUM COVERAGE / RES. PENDENT: 170 FT²
MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
258.8 USgpm at 45.2 PSI
EXCESS PRESSURE AT DEMAND FLOW: 6.6 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
N
SP 5 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL 2 PLAN
SCALE: 1/8" = 1'-0"
-
10
10875
2
2
1
1
AA
BB
CC
DD
GG
EA
EB
E1 E2
4 6 9
F
F
3
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
7' - 8" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
RD
RDC4
8' - 0" A.F.F.
T1
TATA
TBTB
T2 T3 T4 T5
200°
P
2.5
"
2.5" 2.5" 2.5" 2.5"
1.2
5"
1.2
5"
1.25"
1.25" 1.25" 1.25" 1.25"
1.25"1.25"1.25"1.25"
1.25"1.25" 1.25"
1.2
5"
1.25"
1.25"
1.25"
1.2
5"
1.25" 1.25"
05
06
08
09
10
11
12
13
14
15
16
17
18
20
19
21
22
23
24
25 38
28
27
26
31
30
29
32
33
34
35
36
37
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [91]
LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')
MAXIMUM AREA: 145 FT²
155°F, K = 4.9
TY-FRB QR RECESSED PENDENT [7]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES LFII RESIDENTIAL HSW [36]
LISTED COVERAGE: MAX 14' OFF WALL (14'x14')
MAXIMUM AREA: 140 FT²
155°F, K = 4.2
TY-FRB QR HSW [1]
STANDARD COVERAGE
155°F, K = 5.6
VIKING VK486 RESIDENTIAL HSW [3]
LISTED COVERAGE: 16' x 18'
MAXIMUM AREA: 162 FT²
155°F, K = 4.0
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE LEVEL 3 - UNIT 304
NFPA 13
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 6
LISTED COVERAGE / RES. PENDENT: 16' x 16'
MAXIMUM COVERAGE / RES. PENDENT: 145 FT²
MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm
No. VK486 HSW SPRINKLERS FLOWING: 2
LISTED COVERAGE / RES. HSW: 16' x 18'
MAXIMUM COVERAGE / RES. HSW: 162 FT²
MINIMUM DISCHAGE / RES. HSW: 16.2 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
254.1 USgpm at 47.4 PSI
EXCESS PRESSURE AT DEMAND FLOW: 4.4 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
TYCO DS-1 QR DRY UPRIGHT [24]
MAXIMUM COVERAGE: 15' x 15'
MAXIMUM AREA: 120 FT²
200°F, K = 5.6
N
SP 6 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL 3 PLAN
SCALE: 1/8" = 1'-0"
-
10
10875
2
2
1
1
AA
BB
CC
DD
GG
EA
EB
E1 E2
4 6 9
F
F
3
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
7' - 8" A.F.F.
C-1
8' - 0" A.F.F.
C-2
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-2
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
T-BAR
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-2
8' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
8' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-2
8' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
8' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
8' - 0" A.F.F.
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RDRD
C-2
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
8' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-1
8' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
P
2.5
"
2.5" 2.5" 2.5" 2.5"
200°
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.25" 1.25" 1.25" 1.25" 1.25"
1.25"1.25"1.25"1.25"1.25"1.25" 1.25"
1.25"
1.25" 1.25"
1.25"
1.25"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [124]
LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')
MAXIMUM AREA: 145 FT²
155°F, K = 4.9
TY-FRB QR RECESSED PENDENT [8]
STANDARD COVERAGE
155°F, K = 5.6
N
SP 7 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL 4 PLAN
SCALE: 1/8" = 1'-0"
-
10
10875
2
2
1
1
AA
BB
CC
DD
GG
EA
EB
E1 E2
4 6 9
F
F
3
C-1
8' - 6" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
C-1
9' - 0" A.F.F.
T-BAR
9' - 0" A.F.F.
T-BAR
9' - 0" A.F.F.
200°
P
2.5
"
2.5" 2.5" 2.5" 2.5"
1.2
5"
1.2
5"
1.2
5"
1.25"
1.25"
1.25" 1.25" 1.25" 1.25"
1.25"1.25"1.25"
1.25"
1.25"1.25" 1.25"
1.25"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
05
06
07
08
09
10
11
12
13
14
15
1617
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
1.25" 1.25"
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [64]
LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')
MAXIMUM AREA: 145 FT²
155°F, K = 4.9
TY-FRB QR RECESSED PENDENT [7]
STANDARD COVERAGE
155°F, K = 5.6
TYCO SERIES LFII RESIDENTIAL HSW [28]
LISTED COVERAGE: MAX 14' OFF WALL (14'x14')
MAXIMUM AREA: 140 FT²
155°F, K = 4.2
TY-FRB QR HSW [1]
STANDARD COVERAGE
155°F, K = 5.6
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE LEVEL 5 - UNIT 502
NFPA 13
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 4
LISTED COVERAGE / RES. PENDENT: 16' x 16'
MAXIMUM COVERAGE / RES. PENDENT: 145 FT²
MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm
No. RESIDENTIAL HSW SPRINKLERS FLOWING: 4
LISTED COVERAGE / RES. HSW: 14' x 14'
MAXIMUM COVERAGE / RES. HSW: 140 FT²
MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
233.2 USgpm at 48.1 PSI
EXCESS PRESSURE AT DEMAND FLOW: 3.8 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
N
SP 8 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL 5 PLAN
SCALE: 1/8" = 1'-0"
-
10
10875
2
2
1
1
AA
BB
CC
DD
GG
EA
EB
E1 E2
4 6 9
F
F
3
C-2
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
9' - 0" A.F.F.
C-2
10' - 0" A.F.F.
C-2
10' - 0" A.F.F.
C-2
10' - 0" A.F.F.
C-2
10' - 0" A.F.F.
C-2
10' - 0" A.F.F.
RD
RDRDRD
RD RD
RD
RD
RD
RD
RDRD
RD
T-BAR
9' - 0" A.F.F.
T-BAR
9' - 0" A.F.F.
C-2
8' - 6" A.F.F.
200°
P
05
06
07
11
10
08
09
12
15
13
16
18
17
19
20
21
2514
22 23 24 26
27
28
29
30
31
32
33
35
36
39
41
42
43
34
40
1" UP
45
2.5
"
2.5" 2.5" 2.5" 2.5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.2
5"
1.25" 1.25" 1.25" 1.25" 1.25" 1.25"
1.25" 1.25"
1.25"1.25"1.25"1.25"1.25"1.25" 1.25"
2.5"
2.5" UP
TO ROOF HC
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL PENDENT [88]
LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')
MAXIMUM AREA: 145 FT²
155°F, K = 4.9
TY-FRB QR RECESSED PENDENT [12]
STANDARD COVERAGE
155°F, K = 5.6
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE LEVEL 6 - UNIT 603
NFPA 13
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 8
LISTED COVERAGE / RES. PENDENT: 16' x 16'
MAXIMUM COVERAGE / RES. PENDENT: 145 FT²
MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
233.2 USgpm at 48.1 PSI
EXCESS PRESSURE AT DEMAND FLOW: 3.8 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
HYDRAULIC CALCULATION:
AREA: RESIDENTIAL SUITE LEVEL 6 - UNIT 602
NFPA 13
DENSITY: 0.10 USgpm / FT²
No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 7
LISTED COVERAGE / RES. PENDENT: 16' x 16'
MAXIMUM COVERAGE / RES. PENDENT: 145 FT²
MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm
No. RESIDENTIAL HSW SPRINKLERS FLOWING: 1
LISTED COVERAGE / RES. HSW: 14' x 14'
MAXIMUM COVERAGE / RES. HSW: 140 FT²
MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm
SYSTEM DEMAND AT CITY CONNECTION:
231.8 USgpm at 48.7 PSI
EXCESS PRESSURE AT DEMAND FLOW: 3.2 PSI
INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE
N
SP 9 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
LEVEL 6 PLAN
SCALE: 1/8" = 1'-0"
-
DN
DN
DN
DN
DN
10
10875
2
2
1
1
A
BB
CC
DD
GG
EA
EB
E1 E2
4 6 9
F
F
3
3
SD
SDSDSD
SD SD
SD
SD
SD
SD
RDRD
SD
W81
44
1" DN
20100
5
SCALE 1/8"= 1'-0"
SPRINKLER SUMMARY:
TYCO SERIES LFII RESIDENTIAL HSW [1]
LISTED COVERAGE: MAX 14' OFF WALL (14'x14')
MAXIMUM AREA: 140 FT²
155°F, K = 4.2
N
SP 10 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
ROOF PLAN
SCALE: 1/8" = 1'-0"
-
Tectonic Copyright 2007
333'-0"
LEVEL 1
342'-10"
LEVEL 2
352'-6"
LEVEL 3
362'-2"
LEVEL 4
373'-4"
LEVEL 5
384'-0"
LEVEL 6
320'-5"
LEVEL P1
310'-10"
LEVEL P2
395'-7"
ROOF
398'-5"
ELEVATOR
R-F-6
R-F-6
R-F-6
R-F-6
R-F-6
R-F-5
F-1
R-F-6
R-F-6
R-F-6
R-F-6
R-F-6
R-F-5
F-1
TYPE PH4
STAIR 2
STAIR 4
PARKING RAMP
PARKING RAMP
TYPE A1
TYPE A1
TYPE A1
TYPE A1
TYPE B2
TYPE B2
TYPE B2
STAIR 3
STAIR 1
AMENITY
TYPE B7
TYPE B7
TYPE A3
TYPE PH1
TYPE A2
TYPE A2
TYPE A2
LOBBY
BICYCLES
TYPE B2 TYPE A1
TYPE A1
TYPE A1
TYPE A1
P2 PARKING
GARBAGE &
RECYCLING
BULK STORAGE
TYPE PH1
TYPE PH5
TYPE PH5
TYPE PH4
TYPE B3
TYPE B6
TYPE B6
TYPE B6
2
A8.10
STAIR 1
STAIR 1
STAIR 1
STAIR 1
STAIR 4
STAIR 2
STAIR 2
STAIR 2
STAIR 2
STAIR 2 TYPE PH3
TYPE PH3
TYPE B6
TYPE B6
TYPE B6
STAIR 1
12
A6.01
P1 PARKING
Sim
9
A6.01
Sim
9
A6.02
Sim
12
A6.02
SIM.
1
A8.10
R-R-5
R-R-4
R-R-4
F-2
F-1
STAIR 4
STAIR 3
F-2
20100
5
SCALE 1/8"= 1'-0"
320'-5"
LEVEL P1
310'-10"
LEVEL P2
334'-0"
TH L1
344'-0"
TH L2
354'-0"
TH ROOF
4
A6.03
ELECTRICALP1 PARKINGP1 PARKINGP1 PARKING
P2 PARKING BULK STORAGE
TYPE TH1
111
TYPE TH1
110
TYPE TH1
109
P1 E
XH
AU
ST
333'-0"
LEVEL 1
342'-10"
LEVEL 2
352'-6"
LEVEL 3
320'-5"
LEVEL P1
310'-10"
LEVEL P2
334'-0"
TH L1
344'-0"
TH L2
354'-0"
TH ROOF
TYPE TH1
110
P1 PARKING
P2 PARKING
SP 11 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
BUILDING SECTION
SCALE: 1/8" = 1'-0"
TOWNHOUSE SECTION
SCALE: 1/8" = 1'-0"
-
6" DI
P P
2
3
6"
DOUBLE CHECK VALVE ASSEMBLY
4" AMES 2000SS
C/W MONITOR AND SWITCHES
DUAL 6" INTERCONNECTED U/G
WATER SUPPLY FROM CITY BLUE
BRUTE C900 OR EQUAL
(SEE MECH/CIVIL)
~
PA
RK
IN
G P
2
FIRE DEPARTMENT
CONNECTION
(2.5" x 2.5" x 4")
L1 - 330'-0"
DRAIN
L2 - 342'-10"
RISER DIAGRAM & VALVE STATION SCHEMATIC
NTS
DRY VALVE C/W TRIM & GAUGES, AIR COMPRESSOR, ALARM SWITCH & LOW AIR PRESSURE SWITCH
QUICK OPENING DEVICE NOT REQUIRED FOR SYSTEMS < 500 USG; FOR SYSTEMS < 750 USG WHERE A QUICK
OPENING DEVICE IS INSTALLED A TRIP TIME IS NOT REQUIRED, OTHERWISE:
LIGHT HAZARD: 1 ORIFICE OPEN = 60 SECONDS
ORDINARY HAZARD: 2 ORIFICES OPEN = 50 SECONDS
EXTRA HAZARD: 4 ORIFICES OPEN = 45 SECONDS (TWO DIFFERENT TEST HEADERS x 2 ORIFICES PER HEADER)
COMPRESSOR SIZE: 425 USG = 3/4 HP, 115/230 V
NOTE: VALVE STATION LOCATED IN WATER
ENTRY ROOM AT PARKING LEVEL P1
DOMESTIC
4" STEEL
VO
LU
ME
: 350 U
SG
STAIR 1
L3 - 352'-6"
L4 - 362'-2"
L5 - 373'-4"
~
4"
PA
RK
IN
G P
1
VO
LU
ME
: 425 U
SG
4"
L1 - 4"
P
L4 - 2.5"
P
L3 - 2.5"
P
L2 - 3"
P
4"
4"
4"
4"
4"
P1 - 320'-5"
P
4" DRY TO F.D.C.
2.5"
STAIR 2
4"
4"
4"
4"
~
P
4"
4" T
O T
OW
NH
OU
SE
S
N/C, C/W BALL DRIP
TO DRAIN
4
P2 - 310'-10"
4"
L6 - 384'-0"
L5 - 2.5"
P
4"
4"
ROOF - 395'-7"
L6 - 2.5"
P
STAIR 3
STAIR 4
4" 4" 4"
4"
4"
4"
4"
4"
4"
4"
C/W BALL DRIP
CHECK VALVE
~
2.5"
2.5" E
XT
ER
IO
R H
OS
E
CO
NN
EC
TIO
N
6"
SP 12 OF
CARDINAL ENGINEERING LTD.
SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3
TEL: 604-605-0606 Email: [email protected]
NO. DATE: ISSUED FOR:
ENGINEER-OF-RECORD
1 MAR. 23, 2018 REVIEW
BASALT
5058 CAMBIE STREET
VANCOUVER, BC
FIRE SPRINKLER SYSTEM
PENNYFARTHING DEVELOPMENT LTD.
#100 1450 CREEKSIDE DRIVE, VANCOUVER, BC
TEL: 604-734-8443
12
MAR. 23, 2018
DESIGNER:
JC
2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS
3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED
Sheets and ViewsSP-5058 Cambie Street, Van (Basalt)-1SP-5058 Cambie Street, Van (Basalt)-2SP-5058 Cambie Street, Van (Basalt)-3SP-5058 Cambie Street, Van (Basalt)-4SP-5058 Cambie Street, Van (Basalt)-5SP-5058 Cambie Street, Van (Basalt)-6SP-5058 Cambie Street, Van (Basalt)-7SP-5058 Cambie Street, Van (Basalt)-8SP-5058 Cambie Street, Van (Basalt)-9SP-5058 Cambie Street, Van (Basalt)-10SP-5058 Cambie Street, Van (Basalt)-11SP-5058 Cambie Street, Van (Basalt)-12