approx. dist. from fdc to nearest hydrant 2018.08.pdf · 2018. 9. 14. · 1" schedule 40 black...

12
NOTES: CODES & STANDARDS: VANCOUVER BUILDING BY-LAW - 2014 NFPA 13 - 2013 NFPA 14 - 2010 ALTERNATIVE SOLUTION PREPARED BY CAMPHORA ENGINEERING ISSUED ON NOVEMBER 20, 2017. MUNICIPAL WATER SUPPLY: SUMMER STATIC PRESSURE: 52 PSI RESIDUAL PRESSURE: 49 PSI AT 1200 USgpm WATER SUPPLY INFORMATION PROVIDED BY THE CITY OF VANCOUVER (MARCH 6, 2018) SCOPE OF WORK: NEW CONSTRUCTION WORK THAT REQUIRES COMPLIANCE WITH APPLICABLE CODES AND STANDARDS. THE SCOPE OF WORK INCLUDES 2 LEVELS OF PARKING BELOW GRADE AND 6 LEVELS OF OCCUPANCY ABOVE GRADE. MAJOR OCCUPANCY & BUILDING CONSTRUCTION: GROUP C (RESIDENTIAL) GROUP F, DIV 3 (PARKING GARAGES) BUILDING IS NON-COMBUSTIBLE CONSTRUCTION, SIX STOREYS TOWNHOUSES ARE COMBUSTIBLE CONSTRUCTION, TWO STOREYS BUILDING IS SPRINKLERED THROUGHOUT ALL EQUIPMENT TO BE ULC, cUL LISTED AND FM APPROVED (WHERE APPLICABLE) HANGERS AND BRACING IN CONFORMANCE WITH NFPA 13 PIPE & FITTINGS: RESIDENTIAL & LIGHT HAZARD OCCUPANCIES: 1" THRU 3" CPVC BLAZEMASTER CPVC BLAZEMASTER: TOLCO FIG. 22, 23, OR 24 HANGER AND WITHIN 6" OF EACH SPRINKLER CPVC BLAZEMASTER MUST BE SEPARATED FROM AREA SERVED BY SPRINKLER SYSTEM BY CEILINGS, WALLS OR SOFFITS CONSISTING OF A MINIMUM LATH AND PLASTER, 3 8 " GWB, 1 2 " PLYWOOD, OR SUSPENDED MEMBRANE WITH STEEL SUSPENSION GRIDS AND PANELS OR TILES HAVING A MASS NOT LESS THAN 0.35 LB/FT². CPVC BLAZEMASTER MAY BE USED WITHIN A LIGHT HAZARD OCCUPANCY CONTAINING ORDINARY HAZARD ROOMS EACH NOT EXCEEDING 400 FT² (I.E. MECHANICAL ROOMS, LAUNDRY ROOMS, STORAGE AREAS). OTHERWISE NON-COMBUSTIBLE PIPE MUST BE USED. ELECTRICAL WIRE/CABLE SHALL NOT CONTACT CPVC BLAZEMASTER. EXPOSED AND ORDINARY HAZARD OCCUPANCIES: 1" SCHEDULE 40 BLACK STEEL C/W O.I. SCREWED FITTINGS DRY PIPE 1 1 4 " OR LARGER TO BE SCHEDULE 10 BLACK STEEL WET PIPE 1 1 4 " OR LARGER TO BE SCHEDULE 10 BLACK STEEL C/W GROOVED FITTINGS ALL PIPE IS 1" UNLESS NOTED OTHERWISE PIPE 1.5" OR LARGER RUN IN CONCEALED CEILING SPACES MAY BE INSTALLED WITHIN AND PARALLEL TO COMPOSITE OR SOLID WOOD JOISTS. OTHERWISE MUST BE HUNG BELOW COMPOSITE OR SOLID WOOD JOISTS. ELECTRICAL REQUIREMENTS: ELECTRICAL CONNECTIONS TO FLOW SWITCHES, PRESSURE SWITCHES, SUPERVISORY SWITCHES, HEAT TRACING, AIR COMPRESSOR, AND ALARM PANEL SHALL BE PERFORMED BY OTHERS (DIV.16) AND IS NOT PART OF THE FIRE SPRINKLER CONTRACTORS SCOPE OF WORK. SUPERVISORY SWITCHES: SUPERVISORY SWITCHES SHALL BE INSTALLED ON ALL VALVES SUPPLYING THE FIRE SPRINKLER SYSTEM INSIDE THE BUILDING. CONDUCT TESTS FOR EACH SUPERVISORY SWITCH TO ENSURE THE INDICATION OF THE TROUBLE CONDITION AND LOCATION ON THE ANNUNCIATOR BOARD PRIOR TO LEAVING THE SYSTEM IN SERVICE. FLEXIBLE COUPLINGS - 2.5" OR LARGER (REQUIRED IN AREAS SUBJECT TO EARTHQUAKES): · FOR RISERS BETWEEN 3' TO 7' IN LENGTH PROVIDE FLEXIBLE COUPLINGS AT EITHER THE TOP OR BOTTOM · FOR RISERS GREATER THAN 7' HIGH PROVIDE FLEXIBLE COUPLINGS WITHIN 24" OF TOP AND BOTTOM · FOR MULTISTORY BUILDINGS PROVIDE FLEXIBLE COUPLINGS WITHIN 12' ABOVE FLOORS AND WITHIN 24" BELOW FLOORS · FOR FLOOR ZONE CONTROLS PROVIDE FLEXIBLE COUPLINGS WITHIN 12" BELOW IF FLOOR ZONE CONTROL IS AT LEAST 24" BELOW FLOOR · FOR FIRE SEPARATIONS OR MASONRY WALLS PROVIDE FLEXIBLE COUPLINGS WITHIN 12" OF BOTH SIDES UNLESS CLEARANCE REQUIREMENTS ARE MET (2" NOMINAL CLEARANCE FOR PIPE LESS THAN 4"; 4" NOMINAL CLEARANCE FOR 4" OR LARGER PIPE) · AT INTERMEDIATE POINTS OF SUPPORT FOR A RISER PROVIDE FLEXIBLE COUPLINGS ABOVE AND BELOW FLEXIBLE COUPLINGS - PIPE OF ANY SIZE (REQUIRED IN AREAS SUBJECT TO EARTHQUAKES): · FOR DROPS TO HOSE LINES, RACKS SPRINKELRS, AND MEZZANINES PROVIDE FLEXIBLE COUPLINGS WITHIN 24" OF THE TOP AND BOTTOM · FOR DROPS EXCEEDING 15' THAT SUPPLY 2 OR MORE SPRINKLERS PROVIDE FLEXIBLE COUPLINGS WITHIN 24" OF THE TOP SEISMIC PROTECTION: SUPPLY AND INSTALL SWAY BRACE HANGERS ON THE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH NFPA 13. HORIZONTAL PIPING SHALL BE 2-WAY SWAY BRACED EVERY 40 FEET AND 4-WAY SWAY BRACED EVERY 80 FEET. THE TOP OF ALL RISERS AND THE CORNER OF ALL LOOPS SHALL ALSO BE EQUIPPED WITH 4-WAY SWAY BRACES. PIPE HANGERS AND ANCHORS SHALL BE LISTED AND DESIGNED TO RESIST LATERAL LOADS. POWER-ACTUATED FASTENERS AND DROP-IN ANCHORS ARE NOT PERMITTED. PIPE HANGERS TO BE INSTALLED TO NFPA 13 REQUIREMENTS AND BE ULC LISTED. CONCRETE INSERTS TO BE HILTI KWIK BOLT TZ (OR EQUAL) EXPANSION TYPE. DROP-IN ANCHORS ARE NOT PERMITTED. TRIP TEST CONNECTION: TRIP TEST CONNECTION NOT LESS THAN 1" TERMINATING IN A SMOOTH BORE CORROSION-RESISTANT ORIFICE(S) INSTALLED ON THE END OF THE MOST DISTANT SPRINKLER BRANCH LINE(S) WITH A READILY ACCESSIBLE SHUTOFF VALVE AND PLUG NOT LESS THAN 1" AT LEAST ONE OF WHICH IS BRASS OR NIPPLE AND CAP. FLUSHING OF SPRINKLER SYSTEM: UNDERGROUND MAINS AND FIRE DEPARTMENT CONNECTION SUPPLY LINES SHALL BE FLUSHED BEFORE CONNECTING TO THE SPRINKLER SYSTEM. FLUSH UNTIL EFFLUENT IS CLEAR AND FREE OF DEBRIS. AFTER CONSTRUCTION ALL SPRINKLER PIPING SHALL BE FLUSHED TO ENSURE THAT NO DEBRIS IN THE MAIN OR PIPING SYSTEM IS PRESENT THAT MIGHT OBSTRUCT THE SPRINKLER HEAD ORIFICES. PROVIDE PROPER DRAINAGE FOR ALL TESTING. DRAINAGE: MAINS SHALL BE PITCHED AT LEAST 1 4 " PER 10'. DRAINS SHALL BE 2". AUXILIARY DRAINS SHALL CONSIST OF TWO 1" VALVES AND ONE 2"x12" CONDENSATE NIPPLE OR EQUAL, ACCESSIBLY LOCATED. IDENTIFY LOCATIONS OF AUXILIARY DRAINS IN SYSTEM MAINTENANCE MANUAL. REVIEW OF WORK DURING CONSTRUCTION: THE CONTRACTOR SHALL CONTACT CARDINAL ENGINEERING LTD. TO PERFORM CONSTRUCTION REVIEWS AT "ROUGH-IN" AND AT THE TIME OF THE SYSTEM VERIFICATION AND TRIP TEST FOR FINAL REVIEW PRIOR TO OCCUPANCY. DOCUMENTATION: PROVIDE FIRE ALARM VERIFICATION REPORT, MATERIAL & TEST CERTIFICATES, AND CENTRAL MONITORING REPORT TO CARDINAL ENGINEERING LTD. PRIOR TO ISSUANCE OF SCHEDULE C-B. STANDPIPE SYSTEM & ZONING: SPRINKLER SYSTEM IS ZONED AND MONITORED PER FLOOR 7'-7" CLEARANCE (2.3 M) FOR LOADING AREAS AND PATHWAYS TO PARKING SPACES FOR PERSONS WITH DISABILITIES AS PER BY-LAW 4.8.1.(c). CABLE-FREE DEPTH OF CONCRETE REQUIRED TO ACCOMMODATE PIPE ANCHORS : TO ENSURE ADEQUATE DEPTH FOR SPRINKLER PIPE ANCHORS, THE CONCRETE MUST BE CLEAR OF ELECTRICAL CABLING WITHIN 3" OF SLAB BOTTOM. COMBUSTIBLE CONCEALED SPACES: UNLESS ANY OF THE EXCEPTIONS IN NFPA 13 ARE MET, ALL CONCEALED SPACES ENCLOSED WHOLLY OR PARTLY BY EXPOSED COMBUSTIBLE CONSTRUCTION SHALL BE PROTECTED BY SPRINKLERS. NOTIFY ENGINEER IF ANY UNPROTECTED COMBUSTIBLE CONCEALED SPACES. SYSTEM MAINTENANCE: FLUSHING OF THE SPRINKLER SYSTEM AND GENERAL MAINTENANCE SHALL BE COMPLETED ON A REGULAR BASIS AS PER NFPA 25, "INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS". DN SIDEWALK E WONG SIDENCE MAIN ENTRY & FIRE FIGHTERS' RESPONSE POINT 330.15' BG 100.63m PARKADE RAMP PMT PROPERTY LINE 54.56 m (179.00') 12'-0" SETBACK PROPERTY LINE 38.70 m (126.97') 10'-0" SETBACK 54.56 m (179.00') 4'-0" SETBACK PROPERTY LINE 10'-0" SETBACK 332.35' BG 101.3m 334.55' 01.97m 333.83' 01.75m 333.20' 01.56m 332.94' 01.48m 332.55' 01.36m 331.46' BG 101.03m 330.84' BG 100.84m 14.99 m. FIREFIGHTER PATH (Max. 15m) 64.77 m. FIREFIGHTER PATH (Max. 65m) MBIE STREET RETAINED WITH E DESIGNATION) BUILDING ADDRESSING SIGNAGE GAS METER CAMBIE STREET 'BASALT' 5058 CAMBIE STREET VANCOUVER, BC SIAMESE FIRE DEPARTMENT CONNECTION (2 1 2 " x 2 1 2 " x 4") WITHIN 16' (5 M) OF PRINCIPAL ENTRANCE, UNOBSTRUCTED FROM STREET, 18"-48" ABOVE GROUND CITY MAIN (52 PSI STATIC) DUAL 6" INTERCONNECTED WATER SUPPLY BLUE BRUTE C900 OR EQUAL (SEE CIVIL/MECH DRAWINGS) SPRINKLER CONTRACT BEGINS IN VALVE ROOM 200' APPROX. DIST. FROM FDC TO NEAREST HYDRANT SPRINKLER SUMMARY: TY-FRB QR UPRIGHT [122] STANDARD COVERAGE 155°F, K = 5.6 TYCO SERIES EC-14 UPRIGHT [62] LISTED COVERAGE: 20' x 20' 155°F, K = 14.0 TY-FRB QR HSW [7] STANDARD COVERAGE 155°F, K = 5.6 TYCO MODEL SW-24 ECOH HSW [1] MAXIMUM COVERAGE: 16' x 24' 155°F, K = 11.2 TYCO SERIES LFII RESIDENTIAL PENDENT - TOWER [536] LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18') MAXIMUM AREA: 170 FT² 155°F, K = 4.9 TY-FRB QR RECESSED PENDENT [60] STANDARD COVERAGE 155°F, K = 5.6 TYCO SERIES LFII RESIDENTIAL HSW [130] LISTED COVERAGE: MAX 14' OFF WALL (14'x14') MAXIMUM AREA: 140 FT² 155°F, K = 4.2 VIKING VK486 RESIDENTIAL HSW [8] LISTED COVERAGE: 16' x 18' MAXIMUM AREA: 162 FT² 155°F, K = 4.0 W TY-FRB QR RECESSED PENDENT [45] PER ALTERNATIVE SOLUTION LINEAR COVERAGE: 6'-0" OC 6" TO 12" AWAY FROM GLAZING MINIMUM FLOW RATE: 27 USGPM 155°F, K = 5.6 TYCO DS-1 QR DRY HSW [3] STANDARD COVERAGE 155°F, K = 5.6 NOTE: 175°F SPRINKLERS TO BE INSTALLED IN WASHER/DRYER CLOSETS TYCO SERIES LFII RESIDENTIAL PENDENT - TH [59] LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18') MAXIMUM AREA: 170 FT² 155°F, K = 4.9 TYCO DS-1 QR DRY UPRIGHT [24] MAXIMUM COVERAGE: 15' x 15' MAXIMUM AREA: 120 FT² 200°F, K = 5.6 DRY PIPE VALVE SWITCH SYSTEM LOW AIR PRESSURE ALARM PRESSURE RELIEF VALVE W/T TROUBLE CIRCUIT RESTRICTED ORIFICE AIR PRESSURE NOT TO SCALE VALVE C/W TAMPER SWITCH W/T TO DRAIN LARGE ENOUGH TO ACCEPT FULL FLOW. FROM MAIN WATER SUPPLY TROUBLE CIRCUIT. LISTED AIR COMPRESSOR C/W AIR HOLDING TANK MAIN DRAIN VALVE O.S.& Y. OR INDICATING BUTTERFLY TO OTHER D.P.V's. ALARM TEST VALVE W/T ALARM CIRCUIT ALARM PRESSURE SWITCH TO SPRINKLER SYSTEM RESTRICTED ORIFICE OR SUPPLY SIDE PRESSURE POTTER BVS DRY PIPE VALVE CHECK VALVE BALL DRIP DRAIN CUP GAUGE VALVE W/T TROUBLE CIRCUIT. SYSTEM PRESSURE GAUGE SUPERVISED ALARM SHUT-OFF HEAT TRACIING: HEAT-TRACE & INSULATE WET FIRE PROTECTION PIPING WHERE INSTALLED IN UNHEATED AREAS. THE FOLLOWING MATERIALS ARE TO BE EMPLOYED: -DREXAN HEATRACER MULTIRACE SELF-REGULATING CABLE -DREXAN TRACEMATE CONTROL AND MONITORING SYSTEM AND CONNECTED TO FIRE ALARM PANEL - 1.5" FIBREGLASS PIPE INSULATION AND WEATHERPROOF EXTERIOR COVERING -208 V / 3 PHASE INSTALLATION TO COMPLY WITH DREXAN HEATTRACER FIRE SPRINKLER FREEZE PROTECTION DESIGN GUIDE AND INSTALLATION MANUAL: HD102710-1 (OR EQUAL) 24" 12" FLOW SWITCH W/T ALARM SWITCH W/T TROUBLE CIRCUIT (0.25 A, 24 VDC OR 125 VAC) ZONE CONTROL VALVE C/W TAMPER (VICTAULIC TESTMASTER STYLE 720) TO SPRINKLERS DRAIN RISER FLEXIBLE COUPLING ALARM TEST MODULE CHECK VALVE FLOOR SLAB FLEXIBLE COUPLING PRESSURE GAUGE STANDPIPE STANDPIPE ANGLE VALVE WITH CAP & CHAIN DRAIN RISER CIRCUIT RETARD SETTING 20 SECONDS FLOOR ZONE CONTROL W/ CHECK VALVE DETAIL NOT TO SCALE (LENGTH NOT TO EXCEED 7'-0") FIG. 910 1" BLACK STEEL PIPE TYPICAL (SCHED. 40) FAST CLAMP 45-59° FIG. 1000 HANGER TYPICAL FIG. 910 212 PIPE CLAMP FAST CLAMP FIG. 1000 1" BLACK STEEL PIPE (SCHED. 40) TYPICAL FIG. 910 FAST CLAMP FIG. 1000 (SCHED. 40) 1" BLACK STEEL PIPE LATERAL SWAY BRACING FOR MAINS UP TO 4" NOT TO SCALE LONGITUDINAL SWAY BRACING FOR MAINS UP TO 4" NOT TO SCALE FAST CLAMP RISER BRACE (FIG. 1000) NOT TO SCALE IN SEISMIC ZONES USE HILTI KWIK BOLT TZ ANCHOR OR EQUAL IN SEISMIC ZONES USE HILTI KWIK BOLT TZ ANCHOR OR EQUAL IN SEISMIC ZONES USE HILTI KWIK BOLT TZ ANCHOR OR EQUAL LAG-SCREW IN WOOD LAG-SCREW IN WOOD LAG-SCREW IN WOOD TOLCO FIG. 907 TOLCO FIG. 1000 " FAST CLAMP" TOLCO FIG. 909 (2) 4-WAY SWAY BRACE: NOT TO SCALE IN SEISMIC ZONES USE HILTI KWIK BOLT TZ ANCHOR OR EQUAL LAG-SCREW IN WOOD SPRINKLER PIPE UNDERGROUND PIPE 2 1/2" HOSE CONNECTION PRESSURE GAUGE P FLOW SWITCH WIRED TO ALARM CIRCUIT NODE POINTS FOR HYDRAULIC CALCULATION SUPERVISED CONTROL VALVE W/T TROUBLE CIRCUIT CHECK VALVE C/W BALL DRIP N LEGEND 2 WAY SWAY BRACE 4 WAY SWAY BRACE DRY OR FROST PROOF HYDRANT WITH FIRE DEPARTMENT PUMPER CONNECTION POST INDICATOR VALVE (PIV) NON-INDICATING STEM VALVE OR DRAIN VALVE CONCRETE INSERT 10 THREADED ROD BAND HANGER HANGER DETAIL - CONCRETE: NOT TO SCALE IN SEISMIC ZONES USE HILTI KWIK BOLT TZ ANCHOR OR EQUAL PITCH ACCESSIBLE LOCATION TEST VALVE IN READILY PLUG - REMOVE FOR TESTING CORROSION RESISTANT EQUIVALENT ORIFICE FOR DRY SYSTEM SPRINKLERS (2 FLOWING) INSPECTORS TEST CONNECTION FOR DRY SYSTEM NOT TO SCALE BRANCH LINE AL 1 - EXIT EXPOSURE PROTECTION: · 5.6-K QR, PENDENT SPRINKLERS · 6'-0" SPACING ON-CENTRE AND POSITIONED 6" TO 12" AWAY FROM GLAZING · 27 USGPM PER SPRINKLER FED FROM FLOOR ZONE · CAN BE USED FOR FLOOR COVERAGE 3' x 6' TOWARDS THE OPPOSITE SIDE OF THE UNPROTECTED OPENING NOTE: WHERE STANDARD SPRAY SPRINKLERS ARE WITHIN 6'-0" OF EACH OTHER OR A RESIDENTIAL SPRINKLER IS WITHIN 8'-0" OF ANOTHER SPRINKLER A NON-COMBUSTIBLE CROSS BAFFLE SHALL BE INSTALLED. THE BAFFLE SHALL BE AT LEAST 8" WIDE AND 6" HIGH WITH THE BOTTOM OF THE BAFFLE EXTENDING DOWN TO A LEVEL AT LEAST EQUAL WITH THE SPRINKLER DEFLECTOR WATER CURTAIN SPRINKLER AT CEILING NOT TO SCALE STANDARD SPRAY PENDENT QR SPRINKLER SPRINKLER POSITIONED AT CEILING SHALL BE 6" TO 12" HORIZONTALLY FROM A WALL/BULKHEAD AT THE PLANE OF THE OPENING PLANE OF OPENING N SP 1 OF CARDINAL ENGINEERING LTD. SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3 TEL: 604-605-0606 Email: [email protected] NO. DATE: ISSUED FOR: ENGINEER-OF-RECORD 1 MAR. 23, 2018 REVIEW BASALT 5058 CAMBIE STREET VANCOUVER, BC FIRE SPRINKLER SYSTEM PENNYFARTHING DEVELOPMENT LTD. #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC TEL: 604-734-8443 12 MAR. 23, 2018 DESIGNER: JC 2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS 3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED SITE PLAN SCALE: 3/32" = 1'-0"

Upload: others

Post on 04-Feb-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • NOTES:

    CODES & STANDARDS:

    VANCOUVER BUILDING BY-LAW - 2014

    NFPA 13 - 2013

    NFPA 14 - 2010

    ALTERNATIVE SOLUTION PREPARED BY CAMPHORA ENGINEERING ISSUED ON NOVEMBER 20, 2017.

    MUNICIPAL WATER SUPPLY:

    SUMMER STATIC PRESSURE: 52 PSI

    RESIDUAL PRESSURE: 49 PSI AT 1200 USgpm

    WATER SUPPLY INFORMATION PROVIDED BY THE CITY OF VANCOUVER (MARCH 6, 2018)

    SCOPE OF WORK:

    NEW CONSTRUCTION WORK THAT REQUIRES COMPLIANCE WITH APPLICABLE CODES AND STANDARDS.

    THE SCOPE OF WORK INCLUDES 2 LEVELS OF PARKING BELOW GRADE AND 6 LEVELS OF OCCUPANCY

    ABOVE GRADE.

    MAJOR OCCUPANCY & BUILDING CONSTRUCTION:

    GROUP C (RESIDENTIAL)

    GROUP F, DIV 3 (PARKING GARAGES)

    BUILDING IS NON-COMBUSTIBLE CONSTRUCTION, SIX STOREYS

    TOWNHOUSES ARE COMBUSTIBLE CONSTRUCTION, TWO STOREYS

    BUILDING IS SPRINKLERED THROUGHOUT

    ALL EQUIPMENT TO BE ULC, cUL LISTED AND FM APPROVED (WHERE APPLICABLE)

    HANGERS AND BRACING IN CONFORMANCE WITH NFPA 13

    PIPE & FITTINGS:

    RESIDENTIAL & LIGHT HAZARD OCCUPANCIES:

    1" THRU 3" CPVC BLAZEMASTER

    CPVC BLAZEMASTER: TOLCO FIG. 22, 23, OR 24 HANGER AND WITHIN 6" OF EACH SPRINKLER

    CPVC BLAZEMASTER MUST BE SEPARATED FROM AREA SERVED BY SPRINKLER SYSTEM BY CEILINGS,

    WALLS OR SOFFITS CONSISTING OF A MINIMUM LATH AND PLASTER,

    3

    8

    " GWB,

    1

    2

    " PLYWOOD, OR

    SUSPENDED MEMBRANE WITH STEEL SUSPENSION GRIDS AND PANELS OR TILES HAVING A MASS NOT

    LESS THAN 0.35 LB/FT².

    CPVC BLAZEMASTER MAY BE USED WITHIN A LIGHT HAZARD OCCUPANCY CONTAINING ORDINARY HAZARD

    ROOMS EACH NOT EXCEEDING 400 FT² (I.E. MECHANICAL ROOMS, LAUNDRY ROOMS, STORAGE AREAS).

    OTHERWISE NON-COMBUSTIBLE PIPE MUST BE USED.

    ELECTRICAL WIRE/CABLE SHALL NOT CONTACT CPVC BLAZEMASTER.

    EXPOSED AND ORDINARY HAZARD OCCUPANCIES:

    1" SCHEDULE 40 BLACK STEEL

    C/W O.I. SCREWED FITTINGS

    DRY PIPE 1

    1

    4

    " OR LARGER TO BE SCHEDULE 10 BLACK STEEL

    WET PIPE 1

    1

    4

    " OR LARGER TO BE SCHEDULE 10 BLACK STEEL

    C/W GROOVED FITTINGS

    ALL PIPE IS 1" UNLESS NOTED OTHERWISE

    PIPE 1.5" OR LARGER RUN IN CONCEALED CEILING SPACES MAY BE INSTALLED WITHIN AND PARALLEL TO

    COMPOSITE OR SOLID WOOD JOISTS. OTHERWISE MUST BE HUNG BELOW COMPOSITE OR SOLID WOOD

    JOISTS.

    ELECTRICAL REQUIREMENTS:

    ELECTRICAL CONNECTIONS TO FLOW SWITCHES, PRESSURE SWITCHES, SUPERVISORY SWITCHES, HEAT

    TRACING, AIR COMPRESSOR, AND ALARM PANEL SHALL BE PERFORMED BY OTHERS (DIV.16) AND IS NOT

    PART OF THE FIRE SPRINKLER CONTRACTORS SCOPE OF WORK.

    SUPERVISORY SWITCHES:

    SUPERVISORY SWITCHES SHALL BE INSTALLED ON ALL VALVES SUPPLYING THE FIRE SPRINKLER SYSTEM

    INSIDE THE BUILDING. CONDUCT TESTS FOR EACH SUPERVISORY SWITCH TO ENSURE THE INDICATION OF

    THE TROUBLE CONDITION AND LOCATION ON THE ANNUNCIATOR BOARD PRIOR TO LEAVING THE SYSTEM

    IN SERVICE.

    FLEXIBLE COUPLINGS - 2.5" OR LARGER (REQUIRED IN AREAS SUBJECT TO EARTHQUAKES):

    · FOR RISERS BETWEEN 3' TO 7' IN LENGTH PROVIDE FLEXIBLE COUPLINGS AT EITHER THE TOP ORBOTTOM

    · FOR RISERS GREATER THAN 7' HIGH PROVIDE FLEXIBLE COUPLINGS WITHIN 24" OF TOP AND BOTTOM· FOR MULTISTORY BUILDINGS PROVIDE FLEXIBLE COUPLINGS WITHIN 12' ABOVE FLOORS AND WITHIN

    24" BELOW FLOORS

    · FOR FLOOR ZONE CONTROLS PROVIDE FLEXIBLE COUPLINGS WITHIN 12" BELOW IF FLOOR ZONECONTROL IS AT LEAST 24" BELOW FLOOR

    · FOR FIRE SEPARATIONS OR MASONRY WALLS PROVIDE FLEXIBLE COUPLINGS WITHIN 12" OF BOTHSIDES UNLESS CLEARANCE REQUIREMENTS ARE MET (2" NOMINAL CLEARANCE FOR PIPE LESS THAN

    4"; 4" NOMINAL CLEARANCE FOR 4" OR LARGER PIPE)

    · AT INTERMEDIATE POINTS OF SUPPORT FOR A RISER PROVIDE FLEXIBLE COUPLINGS ABOVE ANDBELOW

    FLEXIBLE COUPLINGS - PIPE OF ANY SIZE (REQUIRED IN AREAS SUBJECT TO EARTHQUAKES):

    · FOR DROPS TO HOSE LINES, RACKS SPRINKELRS, AND MEZZANINES PROVIDE FLEXIBLE COUPLINGSWITHIN 24" OF THE TOP AND BOTTOM

    · FOR DROPS EXCEEDING 15' THAT SUPPLY 2 OR MORE SPRINKLERS PROVIDE FLEXIBLE COUPLINGSWITHIN 24" OF THE TOP

    SEISMIC PROTECTION:

    SUPPLY AND INSTALL SWAY BRACE HANGERS ON THE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH

    NFPA 13. HORIZONTAL PIPING SHALL BE 2-WAY SWAY BRACED EVERY 40 FEET AND 4-WAY SWAY BRACED

    EVERY 80 FEET. THE TOP OF ALL RISERS AND THE CORNER OF ALL LOOPS SHALL ALSO BE EQUIPPED

    WITH 4-WAY SWAY BRACES. PIPE HANGERS AND ANCHORS SHALL BE LISTED AND DESIGNED TO RESIST

    LATERAL LOADS. POWER-ACTUATED FASTENERS AND DROP-IN ANCHORS ARE NOT PERMITTED.

    PIPE HANGERS TO BE INSTALLED TO NFPA 13 REQUIREMENTS AND BE ULC LISTED. CONCRETE INSERTS

    TO BE HILTI KWIK BOLT TZ (OR EQUAL) EXPANSION TYPE. DROP-IN ANCHORS ARE NOT PERMITTED.

    TRIP TEST CONNECTION:

    TRIP TEST CONNECTION NOT LESS THAN 1" TERMINATING IN A SMOOTH BORE CORROSION-RESISTANT

    ORIFICE(S) INSTALLED ON THE END OF THE MOST DISTANT SPRINKLER BRANCH LINE(S) WITH A READILY

    ACCESSIBLE SHUTOFF VALVE AND PLUG NOT LESS THAN 1" AT LEAST ONE OF WHICH IS BRASS OR NIPPLE

    AND CAP.

    FLUSHING OF SPRINKLER SYSTEM:

    UNDERGROUND MAINS AND FIRE DEPARTMENT CONNECTION SUPPLY LINES SHALL BE FLUSHED BEFORE

    CONNECTING TO THE SPRINKLER SYSTEM. FLUSH UNTIL EFFLUENT IS CLEAR AND FREE OF DEBRIS.

    AFTER CONSTRUCTION ALL SPRINKLER PIPING SHALL BE FLUSHED TO ENSURE THAT NO DEBRIS IN THE

    MAIN OR PIPING SYSTEM IS PRESENT THAT MIGHT OBSTRUCT THE SPRINKLER HEAD ORIFICES. PROVIDE

    PROPER DRAINAGE FOR ALL TESTING.

    DRAINAGE:

    MAINS SHALL BE PITCHED AT LEAST

    1

    4

    " PER 10'.

    DRAINS SHALL BE 2".

    AUXILIARY DRAINS SHALL CONSIST OF TWO 1" VALVES AND ONE 2"x12" CONDENSATE NIPPLE OR EQUAL,

    ACCESSIBLY LOCATED. IDENTIFY LOCATIONS OF AUXILIARY DRAINS IN SYSTEM MAINTENANCE MANUAL.

    REVIEW OF WORK DURING CONSTRUCTION:

    THE CONTRACTOR SHALL CONTACT CARDINAL ENGINEERING LTD. TO PERFORM CONSTRUCTION REVIEWS

    AT "ROUGH-IN" AND AT THE TIME OF THE SYSTEM VERIFICATION AND TRIP TEST FOR FINAL REVIEW PRIOR

    TO OCCUPANCY.

    DOCUMENTATION:

    PROVIDE FIRE ALARM VERIFICATION REPORT, MATERIAL & TEST CERTIFICATES, AND CENTRAL

    MONITORING REPORT TO CARDINAL ENGINEERING LTD. PRIOR TO ISSUANCE OF SCHEDULE C-B.

    STANDPIPE SYSTEM & ZONING:

    SPRINKLER SYSTEM IS ZONED AND MONITORED PER FLOOR

    7'-7" CLEARANCE (2.3 M) FOR LOADING AREAS AND PATHWAYS TO PARKING SPACES FOR PERSONS WITH

    DISABILITIES AS PER BY-LAW 4.8.1.(c).

    CABLE-FREE DEPTH OF CONCRETE REQUIRED TO ACCOMMODATE PIPE ANCHORS :

    TO ENSURE ADEQUATE DEPTH FOR SPRINKLER PIPE ANCHORS, THE CONCRETE MUST BE CLEAR OF

    ELECTRICAL CABLING WITHIN 3" OF SLAB BOTTOM.

    COMBUSTIBLE CONCEALED SPACES:

    UNLESS ANY OF THE EXCEPTIONS IN NFPA 13 ARE MET, ALL CONCEALED SPACES ENCLOSED WHOLLY OR

    PARTLY BY EXPOSED COMBUSTIBLE CONSTRUCTION SHALL BE PROTECTED BY SPRINKLERS. NOTIFY

    ENGINEER IF ANY UNPROTECTED COMBUSTIBLE CONCEALED SPACES.

    SYSTEM MAINTENANCE:

    FLUSHING OF THE SPRINKLER SYSTEM AND GENERAL MAINTENANCE SHALL BE COMPLETED ON A

    REGULAR BASIS AS PER NFPA 25, "INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE

    PROTECTION SYSTEMS".

    DN

    SIDEWALK

    THE WONG

    RESIDENCE

    MAIN ENTRY & FIRE

    FIGHTERS' RESPONSE

    POINT

    3

    3

    0

    .

    1

    5

    '

    B

    G

    1

    0

    0

    .

    6

    3

    m

    PARKADE

    RAMP

    PMT

    PROPERTY LINE

    54.56 m (179.00')

    12'-0" SETBACK

    PR

    OP

    ER

    TY

    LIN

    E

    38

    .7

    0 m

    (1

    26

    .9

    7')

    10

    '-0

    " S

    ET

    BA

    CK

    54.56 m (179.00')

    4'-0" SETBACK

    PR

    OP

    ER

    TY

    LIN

    E

    10

    '-0

    " S

    ET

    BA

    CK

    3

    3

    2

    .

    3

    5

    '

    B

    G

    1

    0

    1

    .

    3

    m

    3

    3

    4

    .

    5

    5

    '

    B

    G

    1

    0

    1

    .

    9

    7

    m

    3

    3

    3

    .

    8

    3

    '

    B

    G

    1

    0

    1

    .

    7

    5

    m

    3

    3

    3

    .

    2

    0

    '

    B

    G

    1

    0

    1

    .

    5

    6

    m

    3

    3

    2

    .

    9

    4

    '

    B

    G

    1

    0

    1

    .

    4

    8

    m

    3

    3

    2

    .

    5

    5

    '

    B

    G

    1

    0

    1

    .

    3

    6

    m

    3

    3

    1

    .

    4

    6

    '

    B

    G

    1

    0

    1

    .

    0

    3

    m

    3

    3

    0

    .

    8

    4

    '

    B

    G

    1

    0

    0

    .

    8

    4

    m

    14.99 m.

    FIREFIGHTER PATH

    (Max. 15m)

    64.77 m.

    FIREFIGHTER PATH

    (Max. 65m)

    5010 CAMBIE STREET

    (TO BE RETAINED WITH

    HERITAGE DESIGNATION)

    BUILDING ADDRESSING

    SIGNAGE

    GAS

    METER

    CAMBIE STREET

    'BASALT'

    5058 CAMBIE STREET

    VANCOUVER, BC

    SIAMESE FIRE DEPARTMENT CONNECTION (2

    1

    2

    " x 2

    1

    2

    " x 4")

    WITHIN 16' (5 M) OF PRINCIPAL ENTRANCE,

    UNOBSTRUCTED FROM STREET, 18"-48" ABOVE GROUND

    CITY MAIN (52 PSI STATIC)

    DUAL 6" INTERCONNECTED WATER

    SUPPLY BLUE BRUTE C900 OR EQUAL

    (SEE CIVIL/MECH DRAWINGS)

    SPRINKLER CONTRACT

    BEGINS IN VALVE ROOM

    200'

    AP

    PR

    OX

    . DIS

    T. F

    RO

    M F

    DC

    TO

    NE

    AR

    ES

    T H

    YD

    RA

    NT

    SPRINKLER SUMMARY:

    TY-FRB QR UPRIGHT [122]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES EC-14 UPRIGHT [62]

    LISTED COVERAGE: 20' x 20'

    155°F, K = 14.0

    TY-FRB QR HSW [7]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO MODEL SW-24 ECOH HSW [1]

    MAXIMUM COVERAGE: 16' x 24'

    155°F, K = 11.2

    TYCO SERIES LFII RESIDENTIAL PENDENT - TOWER [536]

    LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')

    MAXIMUM AREA: 170 FT²

    155°F, K = 4.9

    TY-FRB QR RECESSED PENDENT [60]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES LFII RESIDENTIAL HSW [130]

    LISTED COVERAGE: MAX 14' OFF WALL (14'x14')

    MAXIMUM AREA: 140 FT²

    155°F, K = 4.2

    VIKING VK486 RESIDENTIAL HSW [8]

    LISTED COVERAGE: 16' x 18'

    MAXIMUM AREA: 162 FT²

    155°F, K = 4.0

    W

    TY-FRB QR RECESSED PENDENT [45]

    PER ALTERNATIVE SOLUTION

    LINEAR COVERAGE: 6'-0" OC

    6" TO 12" AWAY FROM GLAZING

    MINIMUM FLOW RATE: 27 USGPM

    155°F, K = 5.6

    TYCO DS-1 QR DRY HSW [3]

    STANDARD COVERAGE

    155°F, K = 5.6

    NOTE: 175°F SPRINKLERS TO BE INSTALLED IN

    WASHER/DRYER CLOSETS

    TYCO SERIES LFII RESIDENTIAL PENDENT - TH [59]

    LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')

    MAXIMUM AREA: 170 FT²

    155°F, K = 4.9

    TYCO DS-1 QR DRY UPRIGHT [24]

    MAXIMUM COVERAGE: 15' x 15'

    MAXIMUM AREA: 120 FT²

    200°F, K = 5.6

    DRY PIPE VALVE

    SWITCH

    SYSTEM LOW AIR PRESSURE ALARM

    PRESSURE RELIEF VALVE

    W/T TROUBLE CIRCUIT

    RESTRICTED ORIFICE

    AIR PRESSURE

    NOT TO SCALE

    VALVE C/W TAMPER SWITCH W/T

    TO DRAIN LARGE ENOUGH TO

    ACCEPT FULL FLOW.

    FROM MAIN WATER SUPPLY

    TROUBLE CIRCUIT.

    LISTED AIR COMPRESSOR

    C/W AIR HOLDING TANK

    MAIN DRAIN VALVE

    O.S.& Y. OR INDICATING BUTTERFLY

    TO OTHER D.P.V's.

    ALARM TEST VALVE

    W/T ALARM CIRCUIT

    ALARM PRESSURE SWITCH

    TO SPRINKLER SYSTEM

    RESTRICTED ORIFICE OR

    SUPPLY SIDE PRESSURE

    POTTER BVS

    DRY PIPE

    VALVE

    CHECK VALVE

    BALL DRIP

    DRAIN CUP

    GAUGE

    VALVE W/T TROUBLE CIRCUIT.

    SYSTEM PRESSURE GAUGE

    SUPERVISED ALARM SHUT-OFF

    HEAT TRACIING:

    HEAT-TRACE & INSULATE WET FIRE PROTECTION PIPING

    WHERE INSTALLED IN UNHEATED AREAS. THE FOLLOWING

    MATERIALS ARE TO BE EMPLOYED:

    -DREXAN HEATRACER MULTIRACE SELF-REGULATING CABLE

    -DREXAN TRACEMATE CONTROL AND MONITORING SYSTEM

    AND CONNECTED TO FIRE ALARM PANEL

    - 1.5" FIBREGLASS PIPE INSULATION AND WEATHERPROOF

    EXTERIOR COVERING

    -208 V / 3 PHASE

    INSTALLATION TO COMPLY WITH DREXAN HEATTRACER FIRE

    SPRINKLER FREEZE PROTECTION

    DESIGN GUIDE AND INSTALLATION MANUAL: HD102710-1

    (OR EQUAL)

    24"

    12"

    FLOW SWITCH W/T ALARM

    SWITCH W/T TROUBLE CIRCUIT (0.25 A, 24 VDC OR 125 VAC)

    ZONE CONTROL VALVE C/W TAMPER

    (VICTAULIC TESTMASTER STYLE 720)

    TO SPRINKLERS

    DRAIN RISER

    FLEXIBLE COUPLING

    ALARM TEST MODULE

    CHECK VALVE

    FLOOR SLAB

    FLEXIBLE COUPLING

    PRESSURE GAUGE

    STANDPIPE

    STANDPIPE ANGLE VALVE

    WITH CAP & CHAIN

    DRAIN RISER

    CIRCUIT RETARD SETTING 20 SECONDS

    FLOOR ZONE CONTROL W/ CHECK VALVE DETAIL

    NOT TO SCALE

    (LENGTH NOT TO EXCEED 7'-0")

    FIG. 910

    1" BLACK STEEL PIPE

    TYPICAL

    (SCHED. 40)FAST CLAMP

    45-59°

    FIG. 1000

    HANG

    ER

    TYPICALFIG. 910

    212 PIPE CLAMP

    FAST CLAMPFIG. 1000

    1" BLACK STEEL PIPE (SCHED. 40)

    TYPICALFIG. 910

    FAST CLAMPFIG. 1000

    (SCHED. 40)

    1" BLACK STEEL PIPE

    LATERAL SWAY BRACING FOR MAINS UP TO 4"

    NOT TO SCALE

    LONGITUDINAL SWAY BRACING FOR MAINS UP TO 4"

    NOT TO SCALE

    FAST CLAMP RISER BRACE (FIG. 1000)

    NOT TO SCALE

    IN SEISMIC ZONES USE HILTI KWIK

    BOLT TZ ANCHOR OR EQUAL

    IN SEISMIC ZONES USE HILTI KWIK

    BOLT TZ ANCHOR OR EQUAL

    IN SEISMIC ZONES USE HILTI KWIK

    BOLT TZ ANCHOR OR EQUAL

    LAG-SCREW IN WOOD

    LAG-SCREW IN WOOD

    LAG-SCREW IN WOOD

    TOLCO FIG. 907

    TOLCO FIG. 1000 " FAST CLAMP"

    TOLCO FIG. 909 (2)

    4-WAY SWAY BRACE:

    NOT TO SCALE

    IN SEISMIC ZONES USE HILTI KWIK

    BOLT TZ ANCHOR OR EQUAL

    LAG-SCREW IN WOOD

    SPRINKLER PIPE

    UNDERGROUND PIPE

    2 1/2" HOSE CONNECTION

    PRESSURE GAUGE

    P

    FLOW SWITCH WIRED TO ALARM CIRCUIT

    NODE POINTS FOR HYDRAULIC CALCULATION

    SUPERVISED CONTROL VALVE W/T TROUBLE CIRCUIT

    CHECK VALVE C/W BALL DRIP

    N

    LEGEND

    2 WAY SWAY BRACE

    4 WAY SWAY BRACE

    DRY OR FROST PROOF HYDRANT WITH FIRE

    DEPARTMENT PUMPER CONNECTION

    POST INDICATOR VALVE (PIV)

    NON-INDICATING STEM VALVE OR DRAIN VALVE

    CONCRETE INSERT

    10 THREADED ROD

    BAND HANGER

    HANGER DETAIL - CONCRETE:

    NOT TO SCALE

    IN SEISMIC ZONES USE HILTI KWIK

    BOLT TZ ANCHOR OR EQUAL

    PITCH

    ACCESSIBLE LOCATION

    TEST VALVE IN READILY

    PLUG - REMOVE FOR TESTING

    CORROSION RESISTANT EQUIVALENT ORIFICE FOR

    DRY SYSTEM SPRINKLERS (2 FLOWING)

    INSPECTORS TEST CONNECTION FOR DRY SYSTEM

    NOT TO SCALE

    BRANCH LINE

    AL 1 - EXIT EXPOSURE PROTECTION:

    · 5.6-K QR, PENDENT SPRINKLERS· 6'-0" SPACING ON-CENTRE AND POSITIONED 6"

    TO 12" AWAY FROM GLAZING

    · 27 USGPM PER SPRINKLER FED FROM FLOORZONE

    · CAN BE USED FOR FLOOR COVERAGE 3' x 6'TOWARDS THE OPPOSITE SIDE OF THE

    UNPROTECTED OPENING

    NOTE: WHERE STANDARD SPRAY SPRINKLERS ARE

    WITHIN 6'-0" OF EACH OTHER OR A RESIDENTIAL

    SPRINKLER IS WITHIN 8'-0" OF ANOTHER SPRINKLER A

    NON-COMBUSTIBLE CROSS BAFFLE SHALL BE

    INSTALLED. THE BAFFLE SHALL BE AT LEAST 8" WIDE

    AND 6" HIGH WITH THE BOTTOM OF THE BAFFLE

    EXTENDING DOWN TO A LEVEL AT LEAST EQUAL WITH

    THE SPRINKLER DEFLECTOR

    WATER CURTAIN SPRINKLER AT CEILING

    NOT TO SCALE

    STANDARD SPRAY PENDENT QR SPRINKLER

    SPRINKLER POSITIONED AT CEILING SHALL BE 6"

    TO 12" HORIZONTALLY FROM A WALL/BULKHEAD

    AT THE PLANE OF THE OPENING

    PLANE OF

    OPENING

    N

    SP 1 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    SITE PLAN

    SCALE: 3/32" = 1'-0"

  • UP

    UP34.78 SFLOCKER

    SR-10

    34.95 SFLOCKER

    SR-09

    28.72 SFLOCKER

    SR-08

    29.84 SFLOCKER

    SR-05

    28.72 SFLOCKER

    SR-06

    28.1 SFLOCKER

    SR-07

    29.78 SFLOCKER

    SR-12

    29.56 SFLOCKER

    SR-13

    29.56 SFLOCKER

    SR-14

    29.56 SFLOCKER

    SR-15

    29.56 SFLOCKER

    SR-16

    35.1 SFLOCKER

    SR-19

    34.32 SFLOCKER

    SR-18

    35.1 SFLOCKER

    SR-17

    ELEV. LOBBY

    P203

    BULK STORAGE

    P201

    BULK STORAGE

    P205

    29.14 SFLOCKER

    SR-04

    29.14 SFLOCKER

    SR-03

    29.84 SFLOCKER

    SR-02

    STAIR 4

    S4-P2

    P2 PARKING

    P200

    37.87 SFLOCKER

    SR-01

    E.M.R.

    P202

    EA

    EB

    E1

    E2

    35.37 SFLOCKER

    SR-11

    STAIR 3

    S3-P2

    P1

    P1

    P4

    P4

    P3

    P3

    P2

    P2

    PDPD

    PAPA

    PCPC

    PB

    PB

    P2 EXHAUST

    VESTIBULE

    P204

    17

    '-0

    "

    1.5

    "

    19

    '-3

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    19

    '-3

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    19

    '-3

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    19

    '-3

    "

    1.5

    "

    17

    '-0

    "

    19

    '-3

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    19'-6" 17'-3"

    1.5" 1.5"

    19'-6" 17'-3"

    1.5" 1.5"

    19'-6" 17'-3"

    1.5" 1.5"

    3'-3"

    1"

    10'-0"

    1"

    3'-3"

    1"

    10'-0"

    1"

    3'-3"

    1"

    10'-0"

    1"

    3'-3"

    1"

    10'-0"

    1"

    10

    '-0

    "

    1"

    3'-3

    "

    1"

    12

    '-9

    "

    3"

    12'-10"

    3'-6

    "4

    '-1

    1"

    5'-7"8'-9"

    6'-7

    "

    5'-2"6'-2"

    7'-2

    "3

    '-4

    "

    7'-0"

    1"

    1.5

    "1

    .5

    "

    1.5" 1.5"

    1.5

    "

    1.5"

    1"

    4'-9"

    1.5"

    1"

    1"1"

    4'-5"

    1"

    4'-1

    "5

    '-1

    0"

    4'-8

    "

    7'-11"

    1"

    1"

    1"

    1"

    20'-0"

    4"

    4"

    20'-0"

    4"

    20'-0"

    4" 4"

    19

    '-9

    "1

    9'-5

    "1

    0'-9

    "8

    '-8

    "

    4"

    4"

    4"

    4"

    4"

    10'-2"

    1.5"

    4'-1

    "

    1"

    200°

    29'-1"

    4"

    5'-0"

    11

    '-1

    0"

    1"

    12

    '-9

    "

    3"

    4"

    4" UP

    26

    '-5

    "

    4"

    H.G.

    200°

    24" A.F.F.

    4'-11"

    1"

    INSPECTOR'S LOW POINT

    TEST CONNECTION

    10

    '-0

    "

    1"

    3'-3

    "

    1"

    10

    '-0

    "

    1"

    3'-3

    "

    1"

    4"

    9'-11"

    4"

    9'-11"

    7'-2" 12'-10"

    4"

    11'-8" 7'-1"

    4"

    11'-1"

    1"

    5'-7"

    1.5"

    5'-6"

    1.5"

    5'-7"

    1.5"

    5'-6"

    1.5"

    11'-1"

    1.5"

    5'-8

    "6

    '-1

    "5

    '-6

    "1

    1'-0

    "

    3"

    3"

    3"

    3"

    7'-2"

    1"

    4'-0"

    1"

    4'-0"

    1.5"

    4'-11" 5'-10" 6'-0"

    1.5" 1.5" 1.5"

    10'-10" 9'-0"

    1" 1"

    4'-7" 5'-7" 5'-3" 5'-2"

    1.5" 1.5" 1.5" 1.5"

    4'-5

    "

    3"

    9'-5

    "7

    '-9

    "5

    '-8

    "4

    '-7

    "

    3"

    3"

    3"

    3"

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TY-FRB QR UPRIGHT [55]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES EC-14 UPRIGHT [26]

    LISTED COVERAGE: 20' x 20'

    155°F, K = 14.0

    TY-FRB QR HSW [1]

    STANDARD COVERAGE

    155°F, K = 5.6

    N

    SP 2 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL P2 PLAN

    SCALE: 1/8" = 1'-0"

  • UP

    DN

    DN

    T1

    GARBAGE &

    RECYCLING

    P101

    BICYCLES

    P106

    MECHANICAL

    P108

    ELECTRICAL

    P112

    BICYCLES

    P107

    SERVICE

    P102

    TYPE TH1

    P109

    TYPE TH1

    P110

    TYPE TH1

    P111

    1087521

    AA

    BB

    CC

    D

    G

    G

    EA

    EB

    E1 E2

    TATA

    TBTB

    T2 T3 T4 T5

    F

    3

    BICYCLES

    P105

    P1 PARKING

    P100

    STAIR 3

    S3-P1

    STAIR 4

    S4-P1

    ELEV. LOBBY

    P103

    VESTIBULE

    P104

    P1

    P1

    P4

    P4

    P3

    P3

    P2

    P2

    PDPD

    PAPA

    PCPC

    PB

    PB

    P1 EXHAUST

    P2 EXHAUST

    VALVE STN.

    3'-3"

    1"

    10'-0"

    1"

    3'-3"

    1"

    10'-0"

    1"

    12

    '-9

    "

    3"

    MIN 18" CLEARANCE

    BETWEEN TOP OF FLOOR

    MOUNTED OBSTRUCTION AND

    SPRINKLER DEFLECTOR

    MIN 18" CLEARANCE

    BETWEEN TOP OF FLOOR

    MOUNTED OBSTRUCTION AND

    SPRINKLER DEFLECTOR

    4'-3

    "4

    '-2

    "

    1"

    1"

    SPRINKLER NOT REQUIRED IN ELECTRICAL

    ROOM WITH 2 HRR ENCLOSURE WHERE NO

    STORAGE PERMITTED, DRY EQUIPMENT

    ONLY, AND DOOR HAS 1.5 HRR RATING

    17

    '-0

    "

    1.5

    "

    19

    '-3

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    10

    '-5

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    19

    '-3

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    17

    '-0

    "

    1.5

    "

    19

    '-3

    "

    2"

    17

    '-0

    "

    1.5

    "

    10'-5"

    1.5"

    10'-5"

    1.5"

    10'-5"

    1.5"

    10'-5"

    1.5"

    10'-5"

    1"

    10'-5"

    1"

    10'-5"

    1"

    8'-0"

    1"

    8'-0"

    1"

    8'-0"

    1"

    8'-0"

    1"

    8'-0"

    1"

    8'-0"

    1"

    13

    '-3

    "

    1.5

    "

    12

    '-9

    "

    1.5

    "

    6'-11"

    2"

    9'-7"

    2"

    5'-8"

    2"

    8'-1

    "

    1.5

    "

    11

    '-0

    "

    1.5

    "

    8'-1

    "

    1.5

    "

    11

    '-0

    "

    1.5

    "

    5'-7"8'-11"

    1"1"

    4'-9"

    1"

    6'-7

    "

    1"

    8'-11"

    1"

    9'-2

    "6

    '-1

    0"

    10

    '-1

    "

    4"

    4"

    9'-2

    "

    4"

    4"

    4"

    31

    '-2

    "

    6'-9"

    4"

    4"

    8'-9"

    1.5"

    8'-1

    0"

    1.5

    "

    8'-7"

    1.5"

    7'-1"

    1.5"

    10

    '-5

    "

    1.5

    "

    7'-10"

    1.5"

    10

    '-5

    "

    1.5

    "

    16

    '-8

    "

    1.5

    "

    16

    '-8

    "

    1.5

    "

    7'-7

    "

    1.5

    "

    11'-2"

    1.5"

    20'-0"

    1.5"

    5'-9" 14'-3"

    1.5" 1.5"

    20'-0"

    1.5"

    5'-9" 14'-3"

    1.5" 1.5"

    15'-5" 14'-3"15'-5"

    1.5" 1.5" 1.5"

    4'-9"

    1.5"

    8'-1

    0"

    1"

    8'-5"

    1"

    3'-3"

    1"

    10'-0"

    1"

    3'-3"

    1"

    10'-0"

    1"

    3'-3"

    1"

    10'-0"

    1"

    3'-3"

    1"

    10'-0"

    1"

    10

    '-0

    "

    1"

    8'-2

    "

    1"

    10

    '-0

    "

    1"

    8'-2

    "

    1"

    13

    '-7

    "

    27'-5"

    9'-7"9'-0" 6'-3"

    4'-0

    "

    3"

    6'-1

    1"

    10

    '-1

    1"

    1.5

    "1

    .5

    "

    10

    '-1

    1"

    3"

    19

    '-5

    "3

    6'-8

    "

    4'-10" 15'-0"17'-8"

    15'-8" 15'-8"19'-10"19'-10"19'-10"19'-10"

    4" 4" 4" 4" 4" 4" 4" 4" 4"

    4"

    4"

    4"

    4" 4" 4" 4"

    8'-7

    "

    1.5

    "

    10

    '-9

    "1

    0'-0

    "

    13'-0"

    1"

    1.5

    "1

    .5

    "

    8'-8"

    1.5"

    8'-8"

    1.5"

    DUAL 6" INTERCONNECTED WATER SUPPLY

    BLUE BRUTE C900 OR EQUAL

    (SEE CIVIL/MECH DRAWINGS)

    SPRINKLER CONTRACT

    BEGINS IN VALVE ROOM

    01

    02

    03

    04

    4" UP WET

    17'-0"

    11

    '-8

    "

    4"

    4"

    4" UP

    TO FDC

    HSW HEADS BELOW

    OVERHEAD GATE

    3" UP

    TO TH 109

    3" UP

    TO TH 110 & 111

    7'-1

    1"

    4"

    51'-4"

    4" TO TOWNHOUSES

    7'-1

    1"

    3"

    37'-11"

    4" TO TOWNHOUSES

    83

    '-5

    "

    4" W

    ET

    T

    O T

    OW

    NH

    OU

    SE

    S

    4" UP

    WET

    0508 06

    07

    1012

    13

    11

    1" UP 1" UP1" UP

    HG HG HG

    HG

    36'-6"

    2.5"

    GALVANIZED PIPE

    EXTERNALLY WRAPPED

    49

    4'-1

    1"

    1"

    2.5" UP

    TO H/C

    71

    '-2

    "

    2.5

    " D

    RY

    30'-4"

    2.5" DRY TO H/C

    x 3

    4" DN

    37'-0"

    4"

    42

    '-1

    0"

    4"

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TY-FRB QR UPRIGHT [60]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES EC-14 UPRIGHT [36]

    LISTED COVERAGE: 20' x 20'

    155°F, K = 14.0

    TY-FRB QR HSW [2]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO MODEL SW-24 ECOH HSW [1]

    MAXIMUM COVERAGE: 16' x 24'

    155°F, K = 11.2

    TYCO SERIES LFII RESIDENTIAL PENDENT [9]

    LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')

    MAXIMUM AREA: 170 FT²

    155°F, K = 4.9

    HYDRAULIC CALCULATION:

    AREA: PARKING LEVEL 1

    NFPA 13 - OH GROUP 1

    DESIGN AREA: (1500 FT² + 30%) 1950 FT²

    ACTUAL DESIGN AREA: 2002 FT²

    DENSITY: 0.15 USgpm / FT²

    No. OF EC-14 SPRINKLERS FLOWING: 6

    COVERAGE / EC-14 SPRINKLER: 20' x 20'

    MINIMUM DISCHARGE / EC-14 SPRINKLER: 60 USGPM

    SYSTEM DEMAND AT CITY CONNECTION:

    643.4 USgpm at 44.0 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 7.1 PSI

    INCLUDING 250 USGPM OUTSIDE HOSE ALLOWANCE

    N

    SP 3 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL P1 PLAN

    SCALE: 1/8" = 1'-0"

  • T1

    10

    10875

    2

    2

    1

    1

    AA

    BB

    CC

    DD

    GG

    EA

    EB

    E1 E2

    TATA

    TBTB

    T2 T3 T4 T5

    4 6 9

    F

    F

    3

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    7' - 8" A.F.F.

    C-1

    8' - 2" A.F.F.

    C-1

    8' - 0" A.F.F.

    R-C-7

    8' - 0" A.F.F.

    R-C-7

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C4

    8' - 9" A.F.F.

    R-C-7

    8' - 0" A.F.F.

    C-1

    8' - 2" A.F.F.

    C-1

    8' - 8" A.F.F.

    C-1

    8' - 8" A.F.F.

    C-1

    8' - 8" A.F.F.

    R-C-7

    7' - 8" A.F.F.

    4'-7"

    1"

    4'-7"

    1"

    4'-7"

    1"

    4'-7"

    1"

    8'-3

    "

    1.5

    "

    8'-3

    "

    1.5

    "

    8'-3

    "

    1.5

    "

    4" DN WET

    11

    '-9

    "

    4"

    19'-3" 85'-10"17'-8"

    10

    '-2

    "

    4"

    4" 4" 4"

    10

    '-2

    "

    4"

    4" DN

    4" DN

    200°

    4"

    4" 4" 4" 4"

    2"

    1.5" 1.5" 1.5"

    1.5"1.5"

    1.5"

    1.5"

    W

    W

    W

    7'-7

    "

    1.5

    "

    14'-11"

    1.5"

    6'-0

    "

    1.5

    "

    2"

    1.5

    "

    2"

    2"

    W

    W

    W W

    W

    W

    W

    2"

    BULKHEAD REQ'D

    W W

    14'-2"

    1.5"

    6'-0"

    1.5"

    17

    '-4

    "

    1.5

    "

    6'-0

    "

    1"

    6'-0

    "

    1.5

    "

    6'-0

    "

    2"

    6'-0

    "

    2"

    4'-0

    "

    4'-6"

    1.5"

    2"

    7'-0" 8'-0"

    4"4"4"

    1.5"

    1.5"

    W

    WW

    W

    W W W

    1.5"

    ZC

    5'-6"

    1.5" 2"

    1.5"

    1.5"

    9'-4"

    8'-8

    "

    1.5

    "

    6'-0"

    1.5"

    4'-10"

    1.5"

    18

    '-0

    "

    1.5

    "

    1.5"1.5"

    1.5"

    1.5

    "

    1.2

    5"

    1.2

    5"

    2"

    1.5

    "1

    .5

    "

    1.2

    5"

    1.2

    5"

    06

    05

    07

    11

    08

    10 09

    12

    13

    14

    17

    15

    16

    18

    19

    20

    2122

    23

    24

    25

    26

    7'-0

    "

    1.5

    "

    7'-0

    "

    1.5

    "

    2"

    12'-4"

    3'-0"

    1.5"1"

    1"

    4"

    27

    28

    29

    3031

    32

    34 37

    33

    40

    39

    41

    35

    36

    38

    NOTE: STEEL PIPE TO

    BE USED IN AMENITY ROOM

    3" DN

    3" DN

    1.5

    "

    1.5"

    2"

    2"2"

    1.5"

    1.5"

    2"2"

    2"

    2"2"

    2"

    1.5" UP

    1.5" UP

    1.5" UP 1" UP

    1" UP

    1" UP

    1.5" UP

    1.5" UP

    1.5" UP

    1.5" UP 1" UP

    1.5" UP

    1.5" UP1.5" UP

    1.5

    "

    1.5

    "

    1" DN1" DN 1" DN

    SIAMESE FIRE DEPARTMENT CONNECTION (2

    1

    2

    " x 2

    1

    2

    " x 4")

    WITHIN 16' (5 M) OF PRINCIPAL ENTRANCE,

    UNOBSTRUCTED FROM STREET, 18"-48" ABOVE GROUND

    6'-6

    "

    1"

    1"

    4'-7"

    50

    53

    545556

    52

    1.5"

    1.5

    "

    1.5

    "

    1.5

    "

    1.5

    "

    2"

    7273

    74 7571

    2"

    3'-0"

    BAFFLE REQUIRED

    2.5" HOSE

    CONNECTION

    W

    6'-4

    "

    7'-1

    "8

    '-4

    "

    1"

    1"

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [77]

    LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')

    MAXIMUM AREA: 170 FT²

    155°F, K = 4.9

    TY-FRB QR RECESSED PENDENT [19]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES LFII RESIDENTIAL HSW [27]

    LISTED COVERAGE: MAX 14' OFF WALL (14'x14')

    MAXIMUM AREA: 140 FT²

    155°F, K = 4.2

    TY-FRB QR HSW [1]

    STANDARD COVERAGE

    155°F, K = 5.6

    VIKING VK486 RESIDENTIAL HSW [2]

    LISTED COVERAGE: 16' x 18'

    MAXIMUM AREA: 162 FT²

    155°F, K = 4.0

    W

    TY-FRB QR RECESSED PENDENT [16]

    PER ALTERNATIVE SOLUTION

    LINEAR COVERAGE: 6'-0" OC

    6" TO 12" AWAY FROM GLAZING

    MINIMUM FLOW RATE: 27 USGPM

    155°F, K = 5.6

    TOWNHOUSE SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [20]

    LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')

    MAXIMUM AREA: 170 FT²

    155°F, K = 4.9

    TYCO DS-1 QR DRY HSW [3]

    STANDARD COVERAGE

    155°F, K = 5.6

    TY-FRB QR UPRIGHT [7]

    STANDARD COVERAGE

    155°F, K = 5.6

    HYDRAULIC CALCULATION:

    AREA: LEVEL1 - AMENITY WITH WATER CURTAIN

    NFPA 13 - LIGHT HAZARD

    DESIGN AREA: (1500 FT² - 40%) 900 FT²

    ACTUAL DESIGN AREA: 602 FT²

    DENSITY: 0.10 USGPM / FT²

    No. OF SPRINKLERS FLOWING: 7

    MAXIMUM DESIGN COVERAGE / SSP SPRINKLER: 225 FT²

    MINIMUM FLOW / SSP SPRINKLER: 22.5 USGPM

    No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 5 (NODES

    19,20,22,23,24,25,26)

    MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    490.8 USgpm at 47.5 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 3.9 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE LEVEL 1 - UNIT 105

    NFPA 13 W/WATER CURTAIN

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 3

    LISTED COVERAGE / RES. PENDENT: 18' x 18'

    MAXIMUM COVERAGE / RES. PENDENT: 170 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm

    No. RESIDENTIAL HSW SPRINKLERS FLOWING: 1

    LISTED COVERAGE / RES. HSW: 14' x 14'

    MAXIMUM COVERAGE / RES. HSW: 140 FT²

    MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm

    No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 3 (NODES 35,36,41)

    MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    272.5 USgpm at 48.1 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 3.7 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    W

    TY-FRB QR RECESSED PENDENT [4]

    PER ALTERNATIVE SOLUTION

    LINEAR COVERAGE: 6'-0" OC

    6" TO 12" AWAY FROM GLAZING

    MINIMUM FLOW RATE: 27 USGPM

    155°F, K = 5.6

    N

    SP 4 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL 1 PLAN

    SCALE: 1/8" = 1'-0"

  • 10

    10875

    2

    2

    1

    1

    AA

    BB

    CC

    DD

    GG

    EA

    EB

    E1 E2

    4 6 9

    F

    F

    3

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    7' - 8" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    C-1

    8' - 6" A.F.F.

    W/D

    W/D

    W/D

    T1

    TA

    TB

    T2 T3 T4 T5

    TYPE TH1

    109

    TYPE TH1

    110

    TYPE TH1

    111

    1.5

    "

    1.5"

    2"1.5"2"

    1.5

    "

    1.25"

    2"

    1.5

    "

    2" 1.25"

    1.5

    "

    1.2

    5"

    1.2

    5"

    W

    W

    WW

    W

    W

    W

    W

    W

    W

    W

    WW

    W

    W

    W W

    BULKHEAD REQ'D

    BULKHEAD REQ'D

    BULKHEAD REQ'D

    BULKHEAD REQ'DBULKHEAD REQ'D

    BULKHEAD REQ'D

    BULKHEAD REQ'D

    W

    1.5"

    4'-5

    "

    1.5

    "

    5'-8

    "7

    '-9

    "

    1.5

    "1

    .5

    "

    2"

    2"

    2"

    2"

    9'-4

    "9

    '-3

    "

    6'-0"

    11'-0"

    11'-1"

    4'-4

    "

    1.5

    "

    3'-9"

    1.5"

    13

    '-8

    "

    1.5

    "

    10

    '-4

    "

    2"

    6'-0"

    2"

    4'-9"

    2"

    3'-8

    "

    2"

    2"

    4'-5

    "

    2"

    5'-6"

    2"

    6'-6"

    2"

    3'-5"

    2"

    5'-0

    "

    2"

    28'-9"

    1.5"

    6'-1

    "6

    '-0

    "

    1.5

    "1

    .5

    "

    6'-0"

    2"

    6'-0"

    2"

    12'-10"

    2"

    05

    060708 26

    28

    30

    2731

    32 34

    36

    37

    35

    38

    40

    43

    39

    41

    42

    13

    0912

    14

    15

    19

    1817

    16

    22

    BULKHEAD REQ'D

    33

    44

    46

    47

    48

    2"

    1.5

    "1

    .5

    "

    2"

    1.25"

    1.5"1.5"

    1.5"

    W

    BULKHEAD REQ'D

    1.5"

    2"

    P

    3" 3" 3" 3"

    05

    29

    2"

    200°

    2"

    1.5" 1.5" 1.5"1.5"

    W

    W

    7'-7

    "

    1.5

    "

    14'-11"

    1.5"

    6'-0

    "

    1.5

    "

    2"

    2"

    2"

    2"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.5" DN

    1.5" DN

    1.5" DN

    1" DN

    1" DN

    1" DN

    W W

    1.5" DN

    6'-0"

    1.5"

    W W

    1.5" DN

    6'-0"

    1.5"

    WATER CURTAIN SPRINKLERS

    IN RAISED CEILING SUCH THAT

    DEFLECTOR IS ABOVE ADJACENT CEILING

    HEIGHT TO PREVENT COLD SOLDERING

    3"

    66

    68

    70

    69

    67

    62

    61

    57

    63

    65

    64

    58

    59

    60

    1.5" DN

    1" DN 1" DN

    76

    77

    78

    79

    80

    82

    81

    8384

    85

    86

    87

    CONCRETE PILLAR

    TO ACT AS BAFFLE

    13'-4"

    1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP

    1" UP 1" UP 1" UP

    1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP 1" UP

    1" UP

    WATER CURTAIN SPRINKLERS

    IN RAISED CEILING SUCH THAT

    DEFLECTOR IS ABOVE ADJACENT CEILING

    HEIGHT TO PREVENT COLD SOLDERING

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [92]

    LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')

    MAXIMUM AREA: 170 FT²

    155°F, K = 4.9

    TY-FRB QR RECESSED PENDENT [7]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES LFII RESIDENTIAL HSW [38]

    LISTED COVERAGE: MAX 14' OFF WALL (14'x14')

    MAXIMUM AREA: 140 FT²

    155°F, K = 4.2

    TY-FRB QR HSW [1]

    STANDARD COVERAGE

    155°F, K = 5.6

    VIKING VK486 RESIDENTIAL HSW [3]

    LISTED COVERAGE: 16' x 18'

    MAXIMUM AREA: 162 FT²

    155°F, K = 4.0

    W

    TY-FRB QR RECESSED PENDENT [21]

    PER ALTERNATIVE SOLUTION

    LINEAR COVERAGE: 6'-0" OC

    6" TO 12" AWAY FROM GLAZING

    MINIMUM FLOW RATE: 27 USGPM

    155°F, K = 5.6

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE LEVEL 2 - UNIT 210

    NFPA 13 W/WATER CURTAIN

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 2

    LISTED COVERAGE / RES. PENDENT: 18' x 18'

    MAXIMUM COVERAGE / RES. PENDENT: 170 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm

    No. RESIDENTIAL HSW SPRINKLERS FLOWING: 2

    LISTED COVERAGE / RES. HSW: 14' x 14'

    MAXIMUM COVERAGE / RES. HSW: 140 FT²

    MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm

    No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 5 (NODES 14,15,17,18,19)

    MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    331.5 USgpm at 48.0 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 3.7 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    TOWNHOUSE SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [30]

    LISTED COVERAGE: MAX 9-FEET OFF WALL (18'x18')

    MAXIMUM AREA: 170 FT²

    155°F, K = 4.9

    W

    TY-FRB QR RECESSED PENDENT [4]

    PER ALTERNATIVE SOLUTION

    LINEAR COVERAGE: 6'-0" OC

    6" TO 12" AWAY FROM GLAZING

    MINIMUM FLOW RATE: 27 USGPM

    155°F, K = 5.6

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE TOWNHOUSE LEVEL 2 - UNIT 110

    NFPA 13 W/WATER CURTAIN

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 8

    LISTED COVERAGE / RES. PENDENT: 18' x 18'

    MAXIMUM COVERAGE / RES. PENDENT: 170 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm

    No. EXPOSURE PROTECTION SPRINKLERS FLOWING: 2 (NODES 61,62)

    MINIMUM DISCHARGE/ EXPOSURE PROTECTION SPRINKLER: 27 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    333.3 USgpm at 48.9 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 2.9 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE TOWNHOUSE LEVEL 2 - UNIT 111

    NFPA 13

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 8

    LISTED COVERAGE / RES. PENDENT: 18' x 18'

    MAXIMUM COVERAGE / RES. PENDENT: 170 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 17.0 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    258.8 USgpm at 45.2 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 6.6 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    N

    SP 5 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL 2 PLAN

    SCALE: 1/8" = 1'-0"

  • 10

    10875

    2

    2

    1

    1

    AA

    BB

    CC

    DD

    GG

    EA

    EB

    E1 E2

    4 6 9

    F

    F

    3

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    7' - 8" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    RD

    RDC4

    8' - 0" A.F.F.

    T1

    TATA

    TBTB

    T2 T3 T4 T5

    200°

    P

    2.5

    "

    2.5" 2.5" 2.5" 2.5"

    1.2

    5"

    1.2

    5"

    1.25"

    1.25" 1.25" 1.25" 1.25"

    1.25"1.25"1.25"1.25"

    1.25"1.25" 1.25"

    1.2

    5"

    1.25"

    1.25"

    1.25"

    1.2

    5"

    1.25" 1.25"

    05

    06

    08

    09

    10

    11

    12

    13

    14

    15

    16

    17

    18

    20

    19

    21

    22

    23

    24

    25 38

    28

    27

    26

    31

    30

    29

    32

    33

    34

    35

    36

    37

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [91]

    LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')

    MAXIMUM AREA: 145 FT²

    155°F, K = 4.9

    TY-FRB QR RECESSED PENDENT [7]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES LFII RESIDENTIAL HSW [36]

    LISTED COVERAGE: MAX 14' OFF WALL (14'x14')

    MAXIMUM AREA: 140 FT²

    155°F, K = 4.2

    TY-FRB QR HSW [1]

    STANDARD COVERAGE

    155°F, K = 5.6

    VIKING VK486 RESIDENTIAL HSW [3]

    LISTED COVERAGE: 16' x 18'

    MAXIMUM AREA: 162 FT²

    155°F, K = 4.0

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE LEVEL 3 - UNIT 304

    NFPA 13

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 6

    LISTED COVERAGE / RES. PENDENT: 16' x 16'

    MAXIMUM COVERAGE / RES. PENDENT: 145 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm

    No. VK486 HSW SPRINKLERS FLOWING: 2

    LISTED COVERAGE / RES. HSW: 16' x 18'

    MAXIMUM COVERAGE / RES. HSW: 162 FT²

    MINIMUM DISCHAGE / RES. HSW: 16.2 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    254.1 USgpm at 47.4 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 4.4 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    TYCO DS-1 QR DRY UPRIGHT [24]

    MAXIMUM COVERAGE: 15' x 15'

    MAXIMUM AREA: 120 FT²

    200°F, K = 5.6

    N

    SP 6 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL 3 PLAN

    SCALE: 1/8" = 1'-0"

  • 10

    10875

    2

    2

    1

    1

    AA

    BB

    CC

    DD

    GG

    EA

    EB

    E1 E2

    4 6 9

    F

    F

    3

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    7' - 8" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    T-BAR

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    RD

    RD

    RD

    RD

    RD

    RD

    RD

    RD

    RD

    RD

    RD

    RD

    RDRD

    C-2

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    8' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-1

    8' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    P

    2.5

    "

    2.5" 2.5" 2.5" 2.5"

    200°

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.25" 1.25" 1.25" 1.25" 1.25"

    1.25"1.25"1.25"1.25"1.25"1.25" 1.25"

    1.25"

    1.25" 1.25"

    1.25"

    1.25"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [124]

    LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')

    MAXIMUM AREA: 145 FT²

    155°F, K = 4.9

    TY-FRB QR RECESSED PENDENT [8]

    STANDARD COVERAGE

    155°F, K = 5.6

    N

    SP 7 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL 4 PLAN

    SCALE: 1/8" = 1'-0"

  • 10

    10875

    2

    2

    1

    1

    AA

    BB

    CC

    DD

    GG

    EA

    EB

    E1 E2

    4 6 9

    F

    F

    3

    C-1

    8' - 6" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    C-1

    9' - 0" A.F.F.

    T-BAR

    9' - 0" A.F.F.

    T-BAR

    9' - 0" A.F.F.

    200°

    P

    2.5

    "

    2.5" 2.5" 2.5" 2.5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.25"

    1.25"

    1.25" 1.25" 1.25" 1.25"

    1.25"1.25"1.25"

    1.25"

    1.25"1.25" 1.25"

    1.25"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    05

    06

    07

    08

    09

    10

    11

    12

    13

    14

    15

    1617

    18

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    33

    34

    1.25" 1.25"

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [64]

    LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')

    MAXIMUM AREA: 145 FT²

    155°F, K = 4.9

    TY-FRB QR RECESSED PENDENT [7]

    STANDARD COVERAGE

    155°F, K = 5.6

    TYCO SERIES LFII RESIDENTIAL HSW [28]

    LISTED COVERAGE: MAX 14' OFF WALL (14'x14')

    MAXIMUM AREA: 140 FT²

    155°F, K = 4.2

    TY-FRB QR HSW [1]

    STANDARD COVERAGE

    155°F, K = 5.6

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE LEVEL 5 - UNIT 502

    NFPA 13

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 4

    LISTED COVERAGE / RES. PENDENT: 16' x 16'

    MAXIMUM COVERAGE / RES. PENDENT: 145 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm

    No. RESIDENTIAL HSW SPRINKLERS FLOWING: 4

    LISTED COVERAGE / RES. HSW: 14' x 14'

    MAXIMUM COVERAGE / RES. HSW: 140 FT²

    MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    233.2 USgpm at 48.1 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 3.8 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    N

    SP 8 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL 5 PLAN

    SCALE: 1/8" = 1'-0"

  • 10

    10875

    2

    2

    1

    1

    AA

    BB

    CC

    DD

    GG

    EA

    EB

    E1 E2

    4 6 9

    F

    F

    3

    C-2

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    9' - 0" A.F.F.

    C-2

    10' - 0" A.F.F.

    C-2

    10' - 0" A.F.F.

    C-2

    10' - 0" A.F.F.

    C-2

    10' - 0" A.F.F.

    C-2

    10' - 0" A.F.F.

    RD

    RDRDRD

    RD RD

    RD

    RD

    RD

    RD

    RDRD

    RD

    T-BAR

    9' - 0" A.F.F.

    T-BAR

    9' - 0" A.F.F.

    C-2

    8' - 6" A.F.F.

    200°

    P

    05

    06

    07

    11

    10

    08

    09

    12

    15

    13

    16

    18

    17

    19

    20

    21

    2514

    22 23 24 26

    27

    28

    29

    30

    31

    32

    33

    35

    36

    39

    41

    42

    43

    34

    40

    1" UP

    45

    2.5

    "

    2.5" 2.5" 2.5" 2.5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.2

    5"

    1.25" 1.25" 1.25" 1.25" 1.25" 1.25"

    1.25" 1.25"

    1.25"1.25"1.25"1.25"1.25"1.25" 1.25"

    2.5"

    2.5" UP

    TO ROOF HC

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL PENDENT [88]

    LISTED COVERAGE: MAX 8-FEET OFF WALL (16'x16')

    MAXIMUM AREA: 145 FT²

    155°F, K = 4.9

    TY-FRB QR RECESSED PENDENT [12]

    STANDARD COVERAGE

    155°F, K = 5.6

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE LEVEL 6 - UNIT 603

    NFPA 13

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 8

    LISTED COVERAGE / RES. PENDENT: 16' x 16'

    MAXIMUM COVERAGE / RES. PENDENT: 145 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    233.2 USgpm at 48.1 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 3.8 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    HYDRAULIC CALCULATION:

    AREA: RESIDENTIAL SUITE LEVEL 6 - UNIT 602

    NFPA 13

    DENSITY: 0.10 USgpm / FT²

    No. RESIDENTIAL PENDENT SPRINKLERS FLOWING: 7

    LISTED COVERAGE / RES. PENDENT: 16' x 16'

    MAXIMUM COVERAGE / RES. PENDENT: 145 FT²

    MINIMUM DISCHARGE / RES. PENDENT: 14.5 USgpm

    No. RESIDENTIAL HSW SPRINKLERS FLOWING: 1

    LISTED COVERAGE / RES. HSW: 14' x 14'

    MAXIMUM COVERAGE / RES. HSW: 140 FT²

    MINIMUM DISCHAGE / RES. HSW: 14.0 USgpm

    SYSTEM DEMAND AT CITY CONNECTION:

    231.8 USgpm at 48.7 PSI

    EXCESS PRESSURE AT DEMAND FLOW: 3.2 PSI

    INCLUDING 100 USgpm OUTSIDE HOSE ALLOWANCE

    N

    SP 9 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    LEVEL 6 PLAN

    SCALE: 1/8" = 1'-0"

  • DN

    DN

    DN

    DN

    DN

    10

    10875

    2

    2

    1

    1

    A

    BB

    CC

    DD

    GG

    EA

    EB

    E1 E2

    4 6 9

    F

    F

    3

    3

    SD

    SDSDSD

    SD SD

    SD

    SD

    SD

    SD

    RDRD

    SD

    W81

    44

    1" DN

    20100

    5

    SCALE 1/8"= 1'-0"

    SPRINKLER SUMMARY:

    TYCO SERIES LFII RESIDENTIAL HSW [1]

    LISTED COVERAGE: MAX 14' OFF WALL (14'x14')

    MAXIMUM AREA: 140 FT²

    155°F, K = 4.2

    N

    SP 10 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    ROOF PLAN

    SCALE: 1/8" = 1'-0"

  • Tectonic Copyright 2007

    333'-0"

    LEVEL 1

    342'-10"

    LEVEL 2

    352'-6"

    LEVEL 3

    362'-2"

    LEVEL 4

    373'-4"

    LEVEL 5

    384'-0"

    LEVEL 6

    320'-5"

    LEVEL P1

    310'-10"

    LEVEL P2

    395'-7"

    ROOF

    398'-5"

    ELEVATOR

    R-F-6

    R-F-6

    R-F-6

    R-F-6

    R-F-6

    R-F-5

    F-1

    R-F-6

    R-F-6

    R-F-6

    R-F-6

    R-F-6

    R-F-5

    F-1

    TYPE PH4

    STAIR 2

    STAIR 4

    PARKING RAMP

    PARKING RAMP

    TYPE A1

    TYPE A1

    TYPE A1

    TYPE A1

    TYPE B2

    TYPE B2

    TYPE B2

    STAIR 3

    STAIR 1

    AMENITY

    TYPE B7

    TYPE B7

    TYPE A3

    TYPE PH1

    TYPE A2

    TYPE A2

    TYPE A2

    LOBBY

    BICYCLES

    TYPE B2 TYPE A1

    TYPE A1

    TYPE A1

    TYPE A1

    P2 PARKING

    GARBAGE &

    RECYCLING

    BULK STORAGE

    TYPE PH1

    TYPE PH5

    TYPE PH5

    TYPE PH4

    TYPE B3

    TYPE B6

    TYPE B6

    TYPE B6

    2

    A8.10

    STAIR 1

    STAIR 1

    STAIR 1

    STAIR 1

    STAIR 4

    STAIR 2

    STAIR 2

    STAIR 2

    STAIR 2

    STAIR 2 TYPE PH3

    TYPE PH3

    TYPE B6

    TYPE B6

    TYPE B6

    STAIR 1

    12

    A6.01

    P1 PARKING

    Sim

    9

    A6.01

    Sim

    9

    A6.02

    Sim

    12

    A6.02

    SIM.

    1

    A8.10

    R-R-5

    R-R-4

    R-R-4

    F-2

    F-1

    STAIR 4

    STAIR 3

    F-2

    20100

    5

    SCALE 1/8"= 1'-0"

    320'-5"

    LEVEL P1

    310'-10"

    LEVEL P2

    334'-0"

    TH L1

    344'-0"

    TH L2

    354'-0"

    TH ROOF

    4

    A6.03

    ELECTRICALP1 PARKINGP1 PARKINGP1 PARKING

    P2 PARKING BULK STORAGE

    TYPE TH1

    111

    TYPE TH1

    110

    TYPE TH1

    109

    P1 E

    XH

    AU

    ST

    333'-0"

    LEVEL 1

    342'-10"

    LEVEL 2

    352'-6"

    LEVEL 3

    320'-5"

    LEVEL P1

    310'-10"

    LEVEL P2

    334'-0"

    TH L1

    344'-0"

    TH L2

    354'-0"

    TH ROOF

    TYPE TH1

    110

    P1 PARKING

    P2 PARKING

    SP 11 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    BUILDING SECTION

    SCALE: 1/8" = 1'-0"

    TOWNHOUSE SECTION

    SCALE: 1/8" = 1'-0"

  • 6" DI

    P P

    2

    3

    6"

    DOUBLE CHECK VALVE ASSEMBLY

    4" AMES 2000SS

    C/W MONITOR AND SWITCHES

    DUAL 6" INTERCONNECTED U/G

    WATER SUPPLY FROM CITY BLUE

    BRUTE C900 OR EQUAL

    (SEE MECH/CIVIL)

    ~

    PA

    RK

    IN

    G P

    2

    FIRE DEPARTMENT

    CONNECTION

    (2.5" x 2.5" x 4")

    L1 - 330'-0"

    DRAIN

    L2 - 342'-10"

    RISER DIAGRAM & VALVE STATION SCHEMATIC

    NTS

    DRY VALVE C/W TRIM & GAUGES, AIR COMPRESSOR, ALARM SWITCH & LOW AIR PRESSURE SWITCH

    QUICK OPENING DEVICE NOT REQUIRED FOR SYSTEMS < 500 USG; FOR SYSTEMS < 750 USG WHERE A QUICK

    OPENING DEVICE IS INSTALLED A TRIP TIME IS NOT REQUIRED, OTHERWISE:

    LIGHT HAZARD: 1 ORIFICE OPEN = 60 SECONDS

    ORDINARY HAZARD: 2 ORIFICES OPEN = 50 SECONDS

    EXTRA HAZARD: 4 ORIFICES OPEN = 45 SECONDS (TWO DIFFERENT TEST HEADERS x 2 ORIFICES PER HEADER)

    COMPRESSOR SIZE: 425 USG = 3/4 HP, 115/230 V

    NOTE: VALVE STATION LOCATED IN WATER

    ENTRY ROOM AT PARKING LEVEL P1

    DOMESTIC

    4" STEEL

    VO

    LU

    ME

    : 350 U

    SG

    STAIR 1

    L3 - 352'-6"

    L4 - 362'-2"

    L5 - 373'-4"

    ~

    4"

    PA

    RK

    IN

    G P

    1

    VO

    LU

    ME

    : 425 U

    SG

    4"

    L1 - 4"

    P

    L4 - 2.5"

    P

    L3 - 2.5"

    P

    L2 - 3"

    P

    4"

    4"

    4"

    4"

    4"

    P1 - 320'-5"

    P

    4" DRY TO F.D.C.

    2.5"

    STAIR 2

    4"

    4"

    4"

    4"

    ~

    P

    4"

    4" T

    O T

    OW

    NH

    OU

    SE

    S

    N/C, C/W BALL DRIP

    TO DRAIN

    4

    P2 - 310'-10"

    4"

    L6 - 384'-0"

    L5 - 2.5"

    P

    4"

    4"

    ROOF - 395'-7"

    L6 - 2.5"

    P

    STAIR 3

    STAIR 4

    4" 4" 4"

    4"

    4"

    4"

    4"

    4"

    4"

    4"

    C/W BALL DRIP

    CHECK VALVE

    ~

    2.5"

    2.5" E

    XT

    ER

    IO

    R H

    OS

    E

    CO

    NN

    EC

    TIO

    N

    6"

    SP 12 OF

    CARDINAL ENGINEERING LTD.

    SUITE 709, 610 GRANVILLE STREET, VANCOUVER, BC, V6C 3T3

    TEL: 604-605-0606 Email: [email protected]

    NO. DATE: ISSUED FOR:

    ENGINEER-OF-RECORD

    1 MAR. 23, 2018 REVIEW

    BASALT

    5058 CAMBIE STREET

    VANCOUVER, BC

    FIRE SPRINKLER SYSTEM

    PENNYFARTHING DEVELOPMENT LTD.

    #100 1450 CREEKSIDE DRIVE, VANCOUVER, BC

    TEL: 604-734-8443

    12

    MAR. 23, 2018

    DESIGNER:

    JC

    2 JUL 19, 2018 UPDATED FOR AL SOLUTIONS

    3 AUG 30, 2018 UPDATED PER CODE/MECH/ARCH COMMENTS - BACKGROUNDS UPDATED

    Sheets and ViewsSP-5058 Cambie Street, Van (Basalt)-1SP-5058 Cambie Street, Van (Basalt)-2SP-5058 Cambie Street, Van (Basalt)-3SP-5058 Cambie Street, Van (Basalt)-4SP-5058 Cambie Street, Van (Basalt)-5SP-5058 Cambie Street, Van (Basalt)-6SP-5058 Cambie Street, Van (Basalt)-7SP-5058 Cambie Street, Van (Basalt)-8SP-5058 Cambie Street, Van (Basalt)-9SP-5058 Cambie Street, Van (Basalt)-10SP-5058 Cambie Street, Van (Basalt)-11SP-5058 Cambie Street, Van (Basalt)-12