DESCRIPTION
ARCH-4372/6372. HVAC Distribution & Sizing HVAC Distribution Systems Diffuser Selection and Layout Ductwork Sizing. HVAC Distribution Systems. Distribution System Plans Symbols. Positive Pressure (supply) Negative Pressure (return or exhaust). Distribution System Plans Symbols. - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/1.jpg)
ARCH-4372/6372ARCH-4372/6372ARCH-4372/6372ARCH-4372/6372
HVAC Distribution & SizingHVAC Distribution Systems
Diffuser Selection and LayoutDuctwork Sizing
HVAC Distribution & SizingHVAC Distribution Systems
Diffuser Selection and LayoutDuctwork Sizing
![Page 2: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/2.jpg)
HVAC Distribution Systems
HVAC Distribution Systems
![Page 3: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/3.jpg)
Positive Pressure (supply)
Negative Pressure (return or exhaust)
Distribution System Distribution System Plans SymbolsPlans Symbols
![Page 4: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/4.jpg)
Arrow indicates air flow direction
Distribution System Distribution System Plans SymbolsPlans Symbols
![Page 5: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/5.jpg)
Distribution System Distribution System Plans SymbolsPlans Symbols Flow patterns
1-way
4-way
2-way
3-way
![Page 6: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/6.jpg)
Thermostat
Smoke/FireDamper
Distribution System Distribution System Plans SymbolsPlans Symbols
T
![Page 7: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/7.jpg)
Double Line
Single Line
Distribution System Distribution System Plans SymbolsPlans Symbols
![Page 8: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/8.jpg)
Plan
Section
Distribution System Distribution System Plans SymbolsPlans Symbols
z z
z z12 x 16
16 x 12
![Page 9: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/9.jpg)
Distribution Distribution
System System PlansPlansDouble Line
Single Line
![Page 10: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/10.jpg)
Distribution Distribution
System System PlansPlans
Double LineSingle Line
![Page 11: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/11.jpg)
CeilingCeilingPlenum Plenum
PlansPlansShows duct path from distribution network to supply diffuser or return register
![Page 12: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/12.jpg)
Diffuser Selection and Layout
Diffuser Selection and Layout
![Page 13: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/13.jpg)
Diffuser SelectionDiffuser Selection
Diffuser Selection Criteria
Air flow Throw Noise Criteria (NC) Level Appearance
![Page 14: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/14.jpg)
Diffuser SelectionDiffuser Selection
Air FlowThrowNC Level
![Page 15: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/15.jpg)
Throw:
Distance of air movement
Avoid Gaps and overlap Obstructions/deflectors
Diffuser SelectionDiffuser Selection
Velocity (fpm)
150 100 50
![Page 16: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/16.jpg)
Diffuser LayoutDiffuser Layout1. Use Room Sensible Load (no latent, no ventilation) to determine air flow
Qs=1.08 x CFM x ΔT
where T=|Tsa-Tra|
thus
CFM= Qs (1.08 x ΔT)
![Page 17: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/17.jpg)
Diffuser LayoutDiffuser Layout
2. Define Supply Air temperatures
Heating:Tsa range is 90-110ºF
Tra=68ºF
Cooling: Tsa range is 45-55ºF
Tra=78ºF
![Page 18: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/18.jpg)
Diffuser LayoutDiffuser Layout
3. Define ΔT
Heating: ΔT=|110-68|=42ºF
Cooling: ΔT=|55-78|=23ºF
![Page 19: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/19.jpg)
Diffuser LayoutDiffuser Layout4. Determine Air Flow (CFM)
CFMhtg= Qs
(1.08 x ΔThtg)
CFMclg= Qs
(1.08 x ΔTclg)
Larger result determines air flow
![Page 20: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/20.jpg)
Diffuser LayoutDiffuser Layout
5. Revise discharge air temperature to match required air flow
CFMpeak= Qs
(1.08 x |Tsa-Tra|)
solve for Tsa
![Page 21: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/21.jpg)
Diffuser LayoutDiffuser Layout
6. Select diffuser layout
Regular patternUniform coverage
Avoid “short circuiting” with exhaust/return registers
![Page 22: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/22.jpg)
Diffuser Layout ExampleDiffuser Layout Example
Office space with overhead heating and cooling supply
NC level 35
8’
16’
![Page 23: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/23.jpg)
Diffuser Layout ExampleDiffuser Layout ExampleHeating Qs= 11,800 Btuh @ 68ºFCooling Qs=8,600 Btuh @ 78ºF
CFMhtg= Qs
(1.08 x ΔT) =11,800/(1.08 x 42)=260 CFM
CFMclg= Qs
(1.08 x ΔT) =8,600/(1.08 x 23)=346 CFM
![Page 24: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/24.jpg)
Diffuser Layout ExampleDiffuser Layout ExampleRevise Heating Tsa
CFMpeak= Qs (1.08 x ΔT)
=346=11,800/(1.08 x |Tsa-68|)
Tsa=99.6ºF
![Page 25: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/25.jpg)
Diffuser Layout ExampleDiffuser Layout Example
Define Pattern
346 Cfm
Round up to 0 or 5 cfm
1@350 cfm2@175=350 cfm3@115=345 cfm4@90=360 cfm
![Page 26: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/26.jpg)
Define Pattern
346 Cfm
Round up to 0 or 5 cfm
1@350 cfm 2-way2@175=350 cfm 4-way3@115=345 cfm 3-way4@90=360 cfm 2-way
Diffuser Layout ExampleDiffuser Layout Example
8’
16’
![Page 27: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/27.jpg)
Diffuser SelectionDiffuser Selection
NC 35 Air FlowThrow
Select8” Rd4-way
![Page 28: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/28.jpg)
Define Pattern
346 Cfm
2@175=350 cfm 4-way
Diffuser Layout ExampleDiffuser Layout Example
8’
16’
4’
4’
4’
4’
4’
4’
4’
4’
![Page 29: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/29.jpg)
Return Register SelectionReturn Register Selection
Selection Criteria
Air flow Noise Criteria (NC) Level Appearance
![Page 30: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/30.jpg)
Return Register SelectionReturn Register Selection
Air FlowNC Level
![Page 31: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/31.jpg)
Avoid Short circuiting with supply diffusers Locating in visually obtrusive location
Return Register LayoutReturn Register Layout
![Page 32: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/32.jpg)
Define Pattern
Supply=350 cfm
Return1@350=350 cfm
Return Register LayoutReturn Register Layout
8’
16’
![Page 33: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/33.jpg)
Return Register SelectionReturn Register SelectionAir Flow 350 cfmNC Level 35
Select10” x 8”350 cfmNC 27db
![Page 34: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/34.jpg)
Define Pattern
Supply=350 cfm
Return1@350=350 cfm10” x 8”NC 27db
Return Register LayoutReturn Register Layout
8’
16’
![Page 35: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/35.jpg)
Ductwork SizingDuctwork Sizing
![Page 36: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/36.jpg)
Ductwork SizingDuctwork Sizing
Volume (Q) is a function of cross sectional area (A) and velocity (V)
Q=AV
however, momentum, friction and turbulence must also be accounted for in the sizing method
![Page 37: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/37.jpg)
MomentumMomentum
As air leaves fan, centrifugal motion creates momentum
FAN
![Page 38: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/38.jpg)
FrictionFriction
As air moves along a duct, friction slows the velocity at the edges
FAN
![Page 39: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/39.jpg)
TurbulenceTurbulence
As ducts change direction or cross-sectional dimensions, turbulence is created
FAN
![Page 40: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/40.jpg)
Static PressureStatic Pressure
Force required to overcome friction and loss of momentum due to turbulence
As air encounters friction or turbulence, static pressure is reduced
Fans add static pressure
![Page 41: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/41.jpg)
Pressure MeasurementPressure Measurement
Static pressure is measured in inches of force against a water column
Inches-water gauge
Positive pressure pushes airNegative pressure draws air
![Page 42: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/42.jpg)
Pressure MeasurementPressure Measurement
Straight ducts have a pressure loss of
“w.g./100’
based on diameter and velocity
![Page 43: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/43.jpg)
Friction Friction Loss ChartLoss Chart
What is the pressure loss/100 ft in a 12” diameter duct delivering 1000 cfm of air? Velocity?
0.2”/100 FT
1325 fpm
![Page 44: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/44.jpg)
Equivalent LengthEquivalent Length
Describes the amount of static pressure lost in a fitting that would be comparable to a length of straight duct
![Page 45: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/45.jpg)
Ductwork ComparisonDuctwork Comparison
Round ductwork is the most efficient but requires greater depth
Rectangular ductwork is the least efficient but can be reduced in depth to accommodate smaller clearances
Avoid aspect ratios greater than 5:1
![Page 46: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/46.jpg)
Equal Friction MethodEqual Friction Method
Presumes that friction in ductwork can be balanced to allow uniform friction loss through all branches
![Page 47: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/47.jpg)
Equal Friction MethodEqual Friction Method
1. Find effective length (EL) of longest run2. Establish allowed static pressure loss/100’
ΔP=100(SP)/EL3. Size ducts4. Repeat for each branch
Note: velocity must be higher in each upstream section
![Page 48: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/48.jpg)
Equal Friction Method Equal Friction Method ExampleExample
Size ductwork serving office diffusers from earlier example
Elbow equivalent length: 10’
Straight fitting equiv. length: 5’AHU connection: 50’
AHU
4’ 4’
6’ 6’
30’ 12’ 8’
6’
175 cfm (typ.)
![Page 49: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/49.jpg)
Equal Friction Method Equal Friction Method ExampleExample
Supply Diffuser pressure loss: 0.038”Return Register pressure loss: 0.159”
Fan: 0.535”w.g. (75% for supply)
![Page 50: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/50.jpg)
Equal Friction MethodEqual Friction Method
1. Find effective length of longest run
Identify longest runLabel duct sections
AHU
4’ 4’
6’ 6’
30’ 12’ 8’
6’
175 cfm (typ.)
1
234
![Page 51: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/51.jpg)
WorksheetWorksheet
Duct Actual Equiv Effective Air ΔP Duct AirSection Length Length Length Vol. ”/100’ Diam Velocity
1 6’ 10’ 16’ 1752 8’ 5’ 13’ 1753 12’ 5’ 17’ 3504 30’ 50’ 80’ 700
56’ 70’ 126’
AHU
4’ 4’
6’ 6’
30’ 12’ 8’
6’
175 cfm (typ.)
1
234
![Page 52: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/52.jpg)
Equal Friction MethodEqual Friction Method
2. Establish allowed static pressure loss/100’
Fan SP: 0.533”-Supply Diff: 0.038”-Return Reg: 0.159”
Available: 0.336”
x 0.75= 0.252”
ΔP/100’ =100(SP)/EL= 100(.252)/126= 0.2”/100’
![Page 53: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/53.jpg)
WorksheetWorksheet
Duct Actual Equiv Effective Air ΔP Duct AirSection Length Length Length Vol. ”/100’ Diam Velocity
1 6’ 10’ 16’ 175 0.22 8’ 5’ 13’ 175 0.23 12’ 5’ 17’ 350 0.24 30’ 50’ 80’ 700 0.2
56’ 70’ 126’
AHU
4’ 4’
6’ 6’
30’ 12’ 8’
6’
175 cfm (typ.)
1
234
![Page 54: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/54.jpg)
Equal Friction MethodEqual Friction Method
3. Size ducts
RR-6
![Page 55: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/55.jpg)
Equal Friction MethodEqual Friction Method3. Size ducts
1 175cfm 7” diam @ 620 fpm2 175cfm7” diam @ 620 fpm3 350 cfm 9” diam @ 800 fpm4 700 cfm 12” diam @ 900 fpm
![Page 56: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/56.jpg)
WorksheetWorksheet
Duct Actual Equiv Effective Air ΔP Duct AirSection Length Length Length Vol. ”/100’ Diam Velocity
1 6’ 10’ 16’ 175 0.2 7” 620 fpm2 8’ 5’ 13’ 175 0.2 7” 620 fpm3 12’ 5’ 17’ 350 0.2 9” 800 fpm4 30’ 50’ 80’ 700 0.2 12” 900 fpm
56’ 70’ 126’
AHU
4’ 4’
6’ 6’
30’ 12’ 8’
6’
175 cfm (typ.)
1
234
![Page 57: ARCH-4372/6372](https://reader038.vdocuments.net/reader038/viewer/2022102622/5681300b550346895d957edd/html5/thumbnails/57.jpg)