area of rescue command unit aor series€¦ · area of rescue command unit aor series this fully...

4
AREA OF RESCUE COMMAND UNIT AOR SERIES THIS FULLY INTEGRATED COMMAND UNIT ACCOMMODATES UP TO 32 ADA-COMPLIANT AREA OF RESCUE STATIONS. THE UNIT’S STROBE/SOUNDER INDICATES AN INCOMING CALL, AND LED LIGHTS INDICATE THE CALLING LOCATION. AREA OF RESCUE ASSISTANCE FEATURES n AOR command units are fully compliant with the IBC (2015) §1009, ADAAG §7, ICC A117.1 Ch. 7, and NFPA 72 (2016) §24.10. n Automatically and continuously monitors for integrity (grounds, shorts and opens) and alerts by LED and sounder n Accommodates 8, 16, 24 and 32 ADA compliant area of rescue stations n Stations receive power from command unit, powered by UPS n LEDs on command unit indicate calling station and line status n On-site calling requires no outside phone lines n Off-site calling requires only one phone line for each set of 8 stations n Solid LED indicates active call. Blinking LEDs indicate stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed and phone rings n Siren is activated when emergency call is first detected, shuts off when call has been answered n Strobe is activated when emergency call is first detected and remains active for duration of call n Built-in UPS provides 4-hour power back-up in case of power failure n Includes built-in local phone n Surface or flush mounting options

Upload: others

Post on 19-Jun-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AREA OF RESCUE COMMAND UNIT AOR SERIES€¦ · area of rescue command unit aor series this fully integrated command unit accommodates up to 32 ada-compliant area of rescue stations

AREA OF RESCUE COMMAND UNITAOR SERIES

THIS FULLY INTEGRATED

COMMAND UNIT

ACCOMMODATES UP TO 32

ADA-COMPLIANT AREA OF

RESCUE STATIONS. THE UNIT’S

STROBE/SOUNDER INDICATES

AN INCOMING CALL, AND LED

LIGHTS INDICATE THE CALLING

LOCATION.

AR

EA

OF

RE

SC

UE

AS

SIS

TAN

CE

FEATURES

n AOR command units are fully compliant with the IBC (2015) §1009, ADAAG §7, ICC A117.1 Ch. 7, and NFPA 72 (2016) §24.10.

n Automatically and continuously monitors for integrity (grounds, shorts and opens) and alerts by LED and sounder

n Accommodates 8, 16, 24 and 32 ADA compliant area of rescue stations

n Stations receive power from command unit, powered by UPS

n LEDs on command unit indicate calling station and line status

n On-site calling requires no outside phone lines

n Off-site calling requires only one phone line for each set of 8 stations

n Solid LED indicates active call. Blinking LEDs indicate stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed and phone rings

n Siren is activated when emergency call is first detected, shuts off when call has been answered

n Strobe is activated when emergency call is first detected and remains active for duration of call

n Built-in UPS provides 4-hour power back-up in case of power failure

n Includes built-in local phone

n Surface or flush mounting options

Page 2: AREA OF RESCUE COMMAND UNIT AOR SERIES€¦ · area of rescue command unit aor series this fully integrated command unit accommodates up to 32 ada-compliant area of rescue stations

AR

EA

OF

RE

SC

UE

AS

SIS

TAN

CE

GENER A L SPECIFICATION S

AREA OF RESCUE SYSTEM SERIES

Construction: 16 gauge painted steel enclosure, acrylic windows

Mounting: Surface mount or recess mount with optional trim ring, model AOR-TR32 or AOR-TR16. Strobe/sounder mounts to standard 4” square box.

Communication: Lighted phone with 12-button keypad receives and selectively originates calls

Power Source: Stations receive power from Command Unit, powered by UPS (120VAC)

Wiring: One (1) twisted, shielded pair per station not to exceed 25 ohms resistance

Lighting: Strobe is rated at 15 candela, flashes once per second

Environment: Command Unit is for indoor use, outdoor Area of Rescue Stations are available (ETP-500 Series)

Sound: Sounder ranges from 90 to 100 dBA, has 8 alerting sounds

Call Station Options ETP-110 Series Call Station, ETP-500 Series Call Station

Approvals AOR-8 and AOR-16 Power Supply Approvals: EMI conducted and radiated EN61204-3 Class A, Safety EN60950, UL294 Access Control, UL 603 Burglar Systems, UL 1076 Proprietary Burglar, UL 1481 Fire Alarm Systems

AOR-24 and AOR 32 Power Supply Approvals: UL 294 (6th Edition) listed, UL 603 listed, UL 1481 listed, ULC-S318 listed

TALK-A-PHONE CO. LIMITED WARRANTYTalk-A-Phone Co. warrants Talk-A-Phone Emergency Phone, Wide-Area Emergency Broadcast System (WEBS®), and Area of Rescue equipment against any defects in material and workmanship, under normal use, for a period of twenty-four (24) months from date of installation, provided that Talk-A-Phone receives a completed “Installation Certification” certifying the date on which the system has been installed. An “Installation Certification” card is enclosed with every unit. In the event that no “Installation Certification” is received by Talk-A-Phone, the twenty-four (24) months will commence on the date of ship-

ment by Talk-A-Phone. Warranty period for Models ETP-MT Tower, ETP-MT/R Radius Tower, WEBS-MT/R Radius Tower, WEBS-PM Pedestal Mount, and ETP-PM Pedestal Mount is five (5) years, under the same terms and conditions. Warranty period for Intercommunication Products is three (3) months, under the same terms and conditions. In the event this product is found by Talk-A-Phone to be defective within the warranty period, Talk-A-Phone’s only obligation and your exclusive remedy, shall be the repair and/or replacement of any defective parts, provided the equipment is returned to Talk-A-Phone Co., 7530 N. Natchez Ave., Niles, IL 60714. It is expressly understood that Talk-A-Phone shall have no obligation to furnish labor, nor pay for the labor of any third par-

ties, nor bear the expense of shipping defective products for repair. This warranty shall not apply if Talk-A-Phone determines that the defect was caused by improper use or installation, or damage caused to the equipment by others.

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.

AOR-16

AOR-24

AOR-8

AOR-32

ETP-100E ETP-500E

ETP-SIGN

ETP-SIGN-L

ETP-SIGN-LD

Page 3: AREA OF RESCUE COMMAND UNIT AOR SERIES€¦ · area of rescue command unit aor series this fully integrated command unit accommodates up to 32 ada-compliant area of rescue stations

SPECIFICATION S AOR-8 AOR-16

Model: AOR-8: Eight (8) station area of rescue command unit

AOR-16: Sixteen (16) station area of rescue command unit

Dimensions (W x H x D): 14.5 x 26.7 x 5 in. (368 x 678 x 127 mm)

Dimensions With Trim Ring (W x H x D):

16.2 x 28.5 x 5 in. (411 x 724 x 127 mm)

Weight 19 lbs.

AC Input Rating 90-250VAC, 47-63 Hz, 150W

Power AOR-8: 0.5 A (max), 122VAC

AOR-16: 0.7 A (max), 122VAC

Approvals Power Supply Approvals: EMI conducted and radiated EN61204-3 Class A, Safety EN60950, UL294 Access Control, UL 603 Burglar Systems, UL 1076 Proprietary Burglar, UL 1481 Fire Alarm Systems

All specifications are subject to change without notice.

SPECIFICATION S AOR-24 AOR-32

Model: AOR-24: Twenty-four (24) station area of rescue command unit

AOR-32: Thirty-two (32) station area of rescue command unit

Dimensions (W x H x D): 14.5 x 43.6 x 6 in. (368 x 1107 x 152 mm)

Dimensions With Trim Ring (W x H x D):

16.3 x 45.3 x 6 in. (414 x 1151 x 152 mm)

Weight 59 lbs.

AC Input Rating 115-230VAC, 50-60 Hz, 150W

Power AOR-24: 0.9 A (max), 122VAC

AOR-32: 1.0 A (max), 122VAC

Approvals Power Supply Approvals: UL 294 (6th Edition) listed, UL 603 listed, UL 1481 listed, ULC-S318 listed

Page 4: AREA OF RESCUE COMMAND UNIT AOR SERIES€¦ · area of rescue command unit aor series this fully integrated command unit accommodates up to 32 ada-compliant area of rescue stations

7530 North Natchez Avenue Niles, Illinois 60714

Tel: 773-539-1100 Email: [email protected] Web: www.talkaphone.com

DIMENSIONAL DRAWING

THE LEADERS IN SECURITY AND LIFE SAFETY COMMUNICATIONS

All dimensions are in inches and are provided for reference only.

26.67

14.50

FRONT VIEW

ISOMETRIC VIEW

4.25 3.54

1/4" FLUSHMOUTNING KNOCKOUT

(6 PLCS)

11.25

11.25

1.50

2.00

5.07

SIDE VIEW 12.25

24.01

1.50 1.75

4.38TYP. 2X

3/4" & 1"CONDUIT KNOCKOUTS

(8 PLCS)

2.25

5.00

26.63CUT-OUT CLEARANCE

14.31CUT-OUT CLEARANCE

B

REAR VIEWNOTE: AOR-8/AOR-16

SHOWN WITH TRIM RING "AOR-8/16 TRIM RIING"FOR FLUSH MOUNTING OPTION

1.25

4.38TYP. 2X

1.25

2.25 CL

1.00

1.00

.50

R.28

R.15

DETAIL BSCALE 1 : 2

BOTTOM VIEW

TOP VIEW

CL

CL

PART NO: AOR-8 | AOR-16TITLE: AREA OF RESCUE SERIES

REV. DESCRIPTION DATE APPROVED

REVISIONS

1.0 MARKETING RELEASE 6/22/2016 M OBAL

D

C

B

A

B

C

D

12345678

8 7 6 5 4 3 2 1

E

F

E

F

AREA OF RESUCE SERIES

SHEET 1 OF 1

6/22/2016M OBAL

1.0SCALE: 1:8 WEIGHT:

REVPART NO.

CSIZE

TALK-A-PHONE CO.7530 N. NATCHEZ AVE. NILES, IL 60714

WWW.TALKAPHONE.COM

NAME DATE

COMMENTS:

Q.A.

MFG APPR.

ENG APPR.

CHECKED

DRAWN

PROPRIETARY AND CONFIDENTIALTHE INFORMATION CONTAINED IN THISDRAWING IS THE SOLE PROPERTY OFTALK-A-PHONE COMPANY. ANY REPRODUCTION IN PART OR AS A WHOLEWITHOUT THE WRITTEN PERMISSION OFTALK-A-PHONE COMPANY IS PROHIBITED.

A

DWG. TITLE:

FINISHDWG. NO.

AOR-8/ AOR 16

OPTIONS

Model: Description:

Trim Ring:

Model AOR-TR32 is a trim ring for flush mounting AOR-32, and AOR-24.

Model AOR-TR16 is a trim ring for flush mounting AOR-16, and AOR-8

Area of Rescue Sign:

Model ETP-SIGN-RSC is a polycarbonate Area of Rescue sign

Area of Refuge Sign:

Model ETP-SIGN-RFG is a polycarbonate Area of Refuge sign

Push for Help Sign:

Model ETP-SIGN-PFH is a polycarbonate Push for Help sign

Lighted Area of Rescue Sign:

Lighted Area of Rescue Sign: Model ETP-SIGN-BL-RSC is a lighted box Area of Rescue sign

Lighted Area of Refuge Sign:

Model ETP-SIGN-BL-RFG is a lighted box Area of Refuge sign

Edge-Lit Area of Rescue Sign:

Model ETP-SIGN-EL-RSC is an edge-lit Area of Rescue sign with battery backup

Edge-Lit Area of Refuge Sign:

Model ETP-SIGN-EL-RFG is an edge-lit Area of Refuge sign with battery backup

BASE MODELS

AOR-8 = 8 station area of rescuecommand unit

AOR-16 = 16 station area of rescue command unit

AOR-24 = 24 station area of rescue command unit

AOR-32 = 32 station area of rescue command unit

Signage:

14.50

43.58

FRONT VIEW ISOMETRIC VIEW

BOTTOM VIEW

TOP VIEW

26.26

13.50

4.85

4.14

1.75

1.65 5.92

SIDE VIEW 14.25

1.25

2.50

39.51

12.00

1.75

3.38

2.502X

14.31CUT-OUT CLEARANCE

43.38CUT-OUT CLEARANCE

A

REAR VIEWNOTE: AOR-24/AOR-32

SHOWN WITH TRIM RING "AOR-TR32" FOR FLUSH MOUNTING OPTION

CL

3.50 6.30

1.65 1.50

2.21 6.30

1/4" FLUSH MOUNTING HOLE

(4 PLCS)

3.50 7.25

1.65

2.50TYP. 3X

2.13

1.50

CL

R.15

R.28

.50

1.25

1.25

2.75

DETAIL ASCALE 1 : 3

3/4" & 1" CONDUIT KNOCKOUTS(11 PLCS)

CL

2.0

REV. DESCRIPTION DATE APPROVED

REVISIONS

2.0 MARKETING RELEASE 3/23/2016 M OBAL

0.1 PRELIMINARY RELEASE K PATEL

D

C

B

A

B

C

D

12345678

8 7 6 5 4 3 2 1

E

F

E

F

AREA OF RESCUE SERIES

SHEET 1 OF 1

3/23/2016

3/23/2016K PATEL

M OBAL

2.0SCALE: 1:8 WEIGHT:

REVPART NO.

CSIZE

TALK-A-PHONE CO.7530 N. NATCHEZ AVE. NILES, IL 60714

WWW.TALKAPHONE.COM

NAME DATE

COMMENTS:

Q.A.

MFG APPR.

ENG APPR.

CHECKED

DRAWN

PROPRIETARY AND CONFIDENTIALTHE INFORMATION CONTAINED IN THISDRAWING IS THE SOLE PROPERTY OFTALK-A-PHONE COMPANY. ANY REPRODUCTION IN PART OR AS A WHOLEWITHOUT THE WRITTEN PERMISSION OFTALK-A-PHONE COMPANY IS PROHIBITED.

A

DWG. TITLE:

FINISHDWG. NO.

AOR-32/ AOR 24

AOR-8AOR-16

AOR-24AOR-32