Numerical Multi-Function Overcurrent Protection Relay P20008 issue 2004/05
Section 4: Application Diagrams
The following pages contain example application diagrams for a variety of connections, showing various hardware options.
P2
P1
S2
S1
P2
P1
S2
S1
P2
P1
S2
S1
Notes
1. C T c i r c u i t s a r e s h o w n
connected to 1A inputs - use 5A
inputs for 5A rated CTs.
2. CT and earth connections are
typical only.
3. Diagram shows use of residual
(Holmgreen) connect ion for E/Fcircuit. Alternatively use a ring-core
CT.
4. Rear RS485 port is an ordering
option. On the last Relay on the bus
only, connect wire link as shown to
include 120 ohm terminating resistor
in circuit.
25262728
131415
3
4
567891016
171811121920
S1
RL1
RL2
RL3
RL4
RL52122RL62324RL7
+-
AG1-101, 102
P300001 Argus 1 Connection Diagrams / AG1-101,102
A B C
BUSBARS
see note 3 E/F1A
5A
Rx
Tx
Re
ar
F.O
.com
ms p
ort
s Rear RS485
comms port
see note 4
A
B
Term
Screen
120
Figure 4-1 Typical Connection for Earth-fault Protection
![Page 2: Argus-1](https://reader035.vdocuments.net/reader035/viewer/2022072003/563db9df550346aa9aa0b2e4/html5/thumbnails/2.jpg)
Numerical Multi-Function Overcurrent Protection Relay P20008 issue 2004/05
Notes1. C T c i r c u i t s a r e s h o wnconnected to 1A inputs - use 5Ainputs for 5A rated CTs.2. CT and earth connectionsare typical only.3. Diagram shows use of SEF/REF as an SEF input. Use of theinput for high-impedance REFrequires an addi tional sett ingresistor, and may also require ametrosil.4. R ea r R S 48 5 p o r t i s a n
ordering option. On the last Relayon the bus only, connect wire linkas shown to include 120 ohmterminating resistor in circuit.
1A
5A
25262728
131415
34
5
67891016171811121920
S1
RL1
RL2
RL3
RL4
RL52122RL623
24RL7
P2
P1
S2
S1
+-
AG1-103, 104
P300001 Argus 1 Connection Diagrams / AG1-103,104
A B C
BUSBARS
see note 3
SEFRx
Tx
Re
ar
F.O
.com
ms p
ort
s
Rear RS485
comms port
see note 4
A
B
Term
Screen
120
Figure 4-2 Typical Connection for Sensitive Earth-fault Protection
3738
39
4041424344
RL8
RL9
RL10
RL11
P2
P1
S2
S1
P2
P1
S2
S1
P2
P1
S2
S1
Notes
1. CT c ircuits are shown
connected to 1A inputs - use5A inputs for 5A rated CTs.
2. CT and earth connections
are typical only.
3. Optional expansion card,fitted only on models AG1-311
and AG1-312.
4. Optional expansion card,
fitted only on models AG1-321
and AG1-322.5. Rear RS485 port is an
ordering option. On the last
Relay on the bus only, connect
wire link as shown to include120 ohm terminating resistor in
circuit.48474645
5251504956
555453
13
1415
3
4
56
7891016
1718
111219
20
S1
RL1
RL2
RL3
RL4
RL5
2122RL623
24RL7
3536
333431
322930
S2
S3
S4
S54344
41
4239403738
S6
3536
333431
322930
S2
S3
S4
S5
S7
S8
S9
see note 3 see note 4
+
-
+-+-+
-+-
+-+-+
-+-+-
+
-+-+-
AG1-3x1, 3x2
P300001 Argus 1 Connection Diagrams / AG1-3x1,3x2 1
A B C
BUSBARS
Rx
Tx
Re
ar
F.O
.
co
mm
s p
ort
s
A
B
C1A
5A
1A
5A
1A
5A
Rear RS485
comms port
see note 5
A
B
Term
Screen
120
Figure 4-3 Typical Connection for 3 Phase-fault Protection
![Page 3: Argus-1](https://reader035.vdocuments.net/reader035/viewer/2022072003/563db9df550346aa9aa0b2e4/html5/thumbnails/3.jpg)
Numerical Multi-Function Overcurrent Protection Relay P20008 issue 2004/05
37383940
41424344
RL8
RL9
RL10
RL11
P2
P1
S2
S1
P2
P1
S2
S1
P2
P1
S2
S1
Notes1. CT circui ts are shown
connected to 1A inputs - use5A inputs for 5A rated CTs.2. CT and earth connections
are typical only.3. Diagram shows use ofr e s i d u a l ( H o l m g r e e n )
connection for E/F circuit.Alternatively use a ring-coreCT.
4. Optional expansion card,fitted only on models AG1-311and AG1-312.
5. Optional expansion card,fitted only on models AG1-321and AG1-322.6. Rear RS485 port is an
ordering option. On the last
Relay on the bus only, connectwire link as shown to include
120 ohm terminating resistor in
circuit.
484746455251504956555453
25
131415
34
5678910161718
11121920
S1
RL1
RL2
RL3
RL4
RL52122RL62324RL7
3536333431322930
S2
S3
S4
S543444142
39403738
S6
3536333431322930
S2
S3
S4
S5
S7
S8
S9
see note 4 see note 5
+-
+-+-+-+-
+-+-+-+-+-+-
+-+-
AG1-3x1, 3x2
P300001 Argus 1 Connection Diagrams / AG1-3x1,3x2 2
A B C
BUSBARS
Rx
Tx
Rear
F.O
.com
ms p
ort
s
see note 3
A
E/F
C1A
5A
1A
5A
1A
5A
Rear RS485comms port
see note 6
A
B
Term
Screen
120
Figure 4-4 Typical Connection for 2 Phase-fault and Earth-fault Protection
3738394041424344
RL8
RL9
RL10
RL11
P2
P1
S2
S1
P2
P1
S2
S1
Notes
1. CT circui ts are shownconnected to 1A inputs - use5A inputs for 5A rated CTs.2. CT and earth connectionsare typical only.
3. Diagram shows use ofSEF/REF as an SEF input. Useof the input for high-impedanceREF requires an additional
setting resistor, and may alsorequire a metrosil.4. Optional expansion card,fitted only on models AG1-313and AG1-314.
5. Optional expansion card,fitted only on models AG1-323and AG1-324.6. Rear RS485 port is anordering option. On the last
Relay on the bus only, connectwire link as shown to include120 ohm terminating resistor incircuit.
1A
5A
48474645
56555453
25262728
131415
34
5678910161718
11121920
S1
RL1
RL2
RL3
RL4
RL52122RL62324RL7
3536333431322930
S2
S3
S4
S54344414239403738
S6
3536333431322930
S2
S3
S4
S5
S7
S8
S9
P2
P1
S2
S1
see note 4 see note 5
+-
+-+-+-+-
+-+-+-+-+-+-+-+-
AG1-3x3, 3x4
P300001 Argus 1 Connection Diagrams / AG1-3x3,3x4
A B C
BUSBARS
Rx
Tx
Rea
r F
.O.
com
ms p
ort
s
see note 3
A
C
SEF
1A
5A
1A
5A
Rear RS485comms port
see note 6
A
B
Term
Screen
120
Figure 4-5 Typical Connection for 2 Phase-fault and Sensitive Earth-fault Protection
![Page 4: Argus-1](https://reader035.vdocuments.net/reader035/viewer/2022072003/563db9df550346aa9aa0b2e4/html5/thumbnails/4.jpg)
Numerical Multi-Function Overcurrent Protection Relay P20008 issue 2004/05
3738
3940
41424344
RL8
RL9
RL10
RL11
P2
P1
S2
S1
P2
P1
S2
S1
P2
P1
S2
S1
Notes
1. CT ci rcuits are shown
connected to 1A inputs - use5A inputs for 5A rated CTs.
2. CT and earth connectionsare typical only.
3. Diagram shows use ofr e s i d u a l ( H o l m g r e e n )
connect ion for E/F circuit .Alternatively use a ring-core
CT.4. Optional expansion card,
fitted only on models AG1-411and AG1-412.
5. Optional expansion card,fitted only on models AG1-421
and AG1-422.
6. Rear RS485 port is anordering option. On the last
Relay on the bus only, connectwire link as shown to include
120 ohm terminating resistor incircuit.
48474645
5251504956555453
25262728
131415
34
56789101617
1811
121920
S1
RL1
RL2
RL3
RL4
RL52122RL623
24RL7
3536
333431322930
S2
S3
S4
S54344
4142
39403738
S6
3536
333431322930
S2
S3
S4
S5
S7
S8
S9
see note 4 see note 5
+-
+-+-+-+-
+-+-+-+-+-+
-+-+-
AG1-4x1, 4x2
P300001 Argus 1 Connection Diagrams / AG1-4x1,4x2
A B C
BUSBARS
Rx
Tx
Re
ar
F.O
.com
ms p
ort
s
see note 3
A
B
C
E/F1A
5A
1A
5A
1A
5A
1A
5A
Rear RS485
comms port
see note 6
A
B
Term
Screen
120
Figure 4-6 Typical Connection for 3 Phase-fault and Earth-fault Protection
3738
39
404142
4344
RL8
RL9
RL10
RL11
P2
P1
S2
S1
P2
P1
S2
S1
P2
P1
S2
S1
Notes1. CT circuits are shownconnected to 1A inputs - use5A inputs for 5A rated CTs.2. CT and earth connectionsare typical only.3. Application shows use ofSEF/REF as an SEF input. Useof the input for high-impedanceREF requires an additionalsetting resistor, and may alsorequire a metrosil.4. Optional expansion card,fitted only on models AG1-413and AG1-414.5. Optional expansion card,fitted only on models AG1-423and AG1-424.6. Rear RS485 port is anordering option. On the lastRelay on the bus only, connectwire link as shown to include120 ohm terminating resistor incircuit.
1A
5A
48
4746455251
504956
5554
53
25
262728
1314
15
34
5
678
9101617
181112
1920
S1
RL1
RL2
RL3
RL4
RL5
2122RL62324RL7
353633
34313229
30
S2
S3
S4
S54344
41
423940
3738
S6
353633
34313229
30
S2
S3
S4
S5
S7
S8
S9
P2
P1
S2
S1
see note 4 see note 5
+-
+-+
-+-+
-
+-+
-+-+
-+-
+
-+-
+-
AG1-4x3, 4x4
P300001 Argus 1 Connection Diagrams / AG1-4x3,4x4 1
A B C
BUSBARS
Rx
Tx
Rea
r F
.O.
com
ms p
ort
s
see note 3
A
E/F
C
SEF
1A
5A
1A
5A
1A
5A
Rear RS485comms port
see note 6
A
B
Term
Screen
120
Figure 4-7 Typical Connection for 2 Phase-fault, Earth-fault and Sensitive Earth-fault Protection
![Page 5: Argus-1](https://reader035.vdocuments.net/reader035/viewer/2022072003/563db9df550346aa9aa0b2e4/html5/thumbnails/5.jpg)
Numerical Multi-Function Overcurrent Protection Relay P20008 issue 2004/05
3738394041424344
RL8
RL9
RL10
RL11
P2
P1
S2
S1
P2
P1
S2
S1
P2
P1
S2
S1
Notes1. CT c ircuits are shownconnected to 1A inputs - use5A inputs for 5A rated CTs.2. CT and earth connectionsare typical only.3. Application shows use ofSEF/REF as an SEF input. Useof the input for high-impedanceREF requires an additionalsetting resistor, and may also
require a metrosil.4. Optional expansion card,fitted only on models AG1-413and AG1-414.5. Optional expansion card,fitted only on models AG1-423and AG1-424.6. Rear RS485 port is anordering option. On the lastRelay on the bus only, connectwire link as shown to include120 ohm terminating resistor incircuit.
484746455251504956555453
25262728
131415
34
567891016171811121920
S1
RL1
RL2
RL3
RL4
RL52122RL62324RL7
3536333431322930
S2
S3
S4
S54344414239403738
S6
3536333431322930
S2
S3
S4
S5
S7
S8
S9
P2
P1
S2
S1
see note 4 see note 5
+-
+-+-+-+-
+-+-+-+-+-+-+-+-
AG1-4x3, 4x4
P300001 Argus 1 Connection Diagrams / AG1-4x3,4x4 2
A B C
BUSBARS
Rx
Tx
Rear
F.O
.com
ms p
ort
s
see note 3
A
B
C
SEF1A
5A
1A
5A
1A
5A
1A
5A
Rear RS485comms port
see note 6
A
B
Term
Screen
120
Figure 4-8 Typical Connection for 3 Phase-fault and Sensitive Earth-fault Protection
A B C
Rx
Tx
Re
ar
F.O
.co
mm
s p
ort
s
P2
P1
S2
S1
P2
P1
S2
S1
P2
P1
S2
S1
see note 3
Notes
1. CT circuits are shown connected to 1A inputs.
Relays rated for 5A CTs use the same terminal
numbers and are an ordering option.
2. CT and earth connections are typical only.
3. Diagram shows use of residual (Holmgreen)
connection for E/F circuit. Alternatively use a ring-
core CT.
4. Status inputs S2 and S3 have a common
(terminal 4) negative supply input.
5. Rear RS485 port is an ordering option. On
the last Relay on the bus only, connect wire link asshown to include 120 ohm terminating resistor in
circuit.
2423
2625
2827
2122
867
910
S1
RL1
RL2
1920RL5
A
BC
Phase rotation
AG1-43xBUSBARS
A
B
C
E/F1A
1A
1A
1A
12
+-
3 +
54
+-
131415
S2
S3
11
18
1716
RL3
see note 4
Rear RS485comms port
see note 5
A
B
Term
Screen
120
see note 112RL4
P300001 Argus 1 Connection Diagrams / AG1-43x - 1A Version
Figure 4-9 Typical Connection for 3 Phase-fault and Earth-fault Protection – 1A or 5A Version