MEDICAL DESIGN GUIDE

DEPARTMENT OF THE ARMY Volume 1

MEDICAL DESIGN GUIDE

Office of the Surgeon General Office of the Chief of EngineersHealth Facility Planning Agency Medical Facilities Design Office

JULY 1988REVISED SEPTEMBER 1994

Page 2: Army Medical Design Guide - SAFE

Table of Contents

Title Page

Preface 1

Room Index )) Clinic Facilities 2

Room Index )) Ancillary Facilities 2

Room Index )) Inpatient Facilities 3

Room Index )) Abbreviations 4

Architectural Schedule )) Notes 5 - 6

Architectural Schedule )) Miscellaneous Abbreviations 7

Architectural Schedule )) Finish Abbreviations 8

Architectural Schedule )) Door Types and Materials 9

Architectural Schedule )) Hardware Sets 10 - 11

Architectural Schedule )) Fire Protection 12

Mechanical Schedule )) Symbols and Notes 13 - 15

Mechanical Schedule )) Piping Note 16

Mechanical Schedule )) Medical Gas Units 17

Mechanical Schedule )) Dental Utility Center 18 - 19

Electrical Schedule )) Notes 20 - 23

Electrical Schedule )) Luminaire Schedule 24 - 26

Electrical Schedule )) Symbols 27 - 28

Communication Schedule )) Notes 29 - 30

Communication Schedule )) Symbols 31 - 34

Doctor's Office/Exam Room Elevations 35 - 42

Patient Service Console Elevations 43 - 58

X-Ray Room Criteria and Elevations 59 - 67

JULY 1988

Page 3: Army Medical Design Guide - SAFE

Preface

The material contained in this Design Guide was compiled and verified by theOffice of the Surgeon General, Health Facilities Planning Agency and theCorps of Engineers, Medical Facility Design Office. This document is intendedto be used as a guide and a supplement to current Technical Manuals and otherpublished criteria, in the planning and design of Army Health Facilities.Information contained in the Design Guide is subject to changes in medicaltechnology and revisions to Technical Manuals or other criteria. The use ofthe Schedules or Room Designs shall not preclude compliance to currentcriteria of any applicable codes and standards. The Medical Design Guide wasprepared by the Joint Venture of Harwood K. Smith & Partners Inc./Wingler &Sharp Inc., and was updated September 1994 by JMGR Inc.

Each Room Design series is composed of five individual plates:

Plate "A" - The Matrix Data Provides specific information on technicalrequirements including architectural, electrical, communication andmechanical requirements. Plate A also includes a specific equipment programincluding Joint Schedule Number (JSN), nomenclature, quantity and thelogistical responsibility category as defined in Military Standard 1691. AJoint Schedule Number with a sub-script is a variation of the basic JSN asdescribed in Military standard 1691.

Plate "B" - The Functional Diagram Illustrates the specific spatialutilization including dimensional requirements, maximum, minimum and/orpreferred dimensions.

Plate "C" - The Floor Plan Locates the equipment scheduled in the equipmentprogram with respect to equipment clearances and functional requirements.Some portable equipment not critical to room layout or utility requirements.may not be indicated in this plan, but can be found in the Medical FaciltyRoom Contents List (MFRCL), which is supplied separately for each project.

Plate "D" - The Reflected Ceiling Plan Coordinates architectural materials,ceiling located equipment, and locates lighting, communications, mechanicaland electrical components with proper relationship to room equipment andfunction.

Plate "E" - The Composite Plan Combines multidisciplinary information fromPlates "C" and "D" to reflect a total room requirement for equipment andbuilding systems.

Refer to the following schedules for general notes and graphic "keys" whichapply to all Room Designs and for specific notes referenced in the MatrixData.

JULY 1988 1REVISED SEPTEMBER 1994

Page 4: Army Medical Design Guide - SAFE

Room Index

VOLUME I CLINIC FACILITIES VOLUME II ANCILLARY FACILITIES

Room Type Room Number Room Type Room Number

Drs Office/Exam Rm 1.01.01 IV Additive Room 2.01.01Treatment Room 1.01.02 Gen Radiography 2.02.01Soiled Utility - CL 1.01.03 Fluoroscopy 2.02.02Satellite Lab 1.01.04 Angiography 2.02.03Reception Area 1.01.05 Mammography 2.02.04Trauma Room 1.02.01 Ultrasound 2.02.05Trauma Room - 2 Table 1.02.02 X-ray Film Processing 2.02.06ER Treatment Cubicle 1.02.03 CT Scanner 2.02.07Central Commo 1.02.04 Linear Accelerator 2.03.01 Decon Shower 1.02.05 Simulator Room 2.03.02Screening 1.02.06 Gamma Camera 2.04.01Immunization Room 1.04.01 Special Imaging 2.04.02ECG Testing/Work Rm 1.05.01 Uptake Workroom 2.04.03Treadmill Room 1.05.02 Radioisotope Lab 2.04.04Pulmonary Function 1.06.01 Radioimmunoassay 2.04.05Proctoscopy Suite 1.07.01 Radiopharmacy (Large) 2.04.06Weights & Measures 1.08.01 Cardiac Cath 2.05.01EEG Testing/Work Rm 1.10.01 Autopsy 2.06.01Cast Room 1.11.01 Hemodialysis Cubicle 2.07.01ENT Exam Room 1.12.01 General OR 2.08.01Audio Testing (Sm) 1.12.02 Special OR 2.08.02Audio Testing (Lg) 1.12.03 Scrub Area 2.08.03Ophthalmology Exam 1.13.01 Decontamination - OR 2.08.04Eye Lane/Office 1.13.02 OR Prep/Hold 2.08.05Ophthalmic Photo Rm 1.13.03 Recovery Module 2.08.06Prev Medicine Lab 1.14.01 Labor Room 2.09.01Mirror Room 1.15.01 Birthing Room 2.09.02 Group Therapy 1.15.02 Stress Testing 2.09.03 Psych Play Therapy 1.15.03 OB Exam/Prep 2.09.04Whirlpool Area 1.16.01 Delivery Room 2.09.05Burn Tank Room 1.16.02 Cystoscopy Room 2.10.01Phys Ther Treatment 1.16.03 Urodynamics Room 2.10.02Daily Living Skills 1.16.04 Oral Surgery 1.17.01 Oral Surgery w/X-ray 1.17.02 Dental Treatment Rm 1.17.03 Dental X-ray Suite 1.17.04 Dental Prosthetics Lab 1.17.05

JULY 1988 2

Page 5: Army Medical Design Guide - SAFE

Room Index (Cont'd)

VOLUME III INPATIENT FACILITIES

Room Type Room Number

CCU Bedroom 3.01.01 ICU Bedroom 3.01.02 ICU Isolation Bedroom 3.01.03 One Bedroom (Mob) 3.02.01 Two Bedroom (Mob) 3.02.02 Four Bedroom (Mob) 3.02.03 Four Bedroom, ALT (Mob) 3.02.04 Isolation Bedroom 3.02.05 Ped-One Bedroom (Mob) 3.02.06 Ped-Two Bedroom (Mob) 3.02.07 Ped-Four Bedroom (Mob) 3.02.08 Ped Isolation Room 3.02.09 Seclusion Room 3.03.01 One Bedroom 3.04.01 Two Bedroom 3.04.02 Four Bedroom 3.04.03 Four Bedroom, ALT 3.04.04 Ped-One Bedroom 3.04.05 Ped-Two Bedroom 3.04.06 Ped-Four Bedroom 3.04.07 Normal Newborn Nursery 3.05.01 Adm/Obs/Cont Care Nrsy 3.05.02 Intermed Care Nursery 3.05.03 ICU Nursery 3.05.04 Isolation Nursery 3.05.05 Nurses Station 3.06.01 Nurses Station CCU/ICU 3.06.02 Mediprep 3.06.03 Soiled Utility-NU 3.06.04 Tub/Shower Room 3.06.05 Nourishment Pantry 3.06.06

JULY 1988 3

Page 6: Army Medical Design Guide - SAFE

Room, Index (Cont'd)

ABBREVIATIONS

ABBREV. DESCRIPTION ABBREV. DESCRIPTION

Adm Admission OB ObstetricsALT Alternate Obs ObservationAudio Audiology, Audiometric OR Operating RoomCath Catherization Ped PediatricsCCU Coronary Care Unit Prep PreparationCL Clinic Photo PhotographicCont Continuing Phys Ther Physical TherapyCommo Communications Prev PreventiveDecon Decontamination Psych PsychiatricDr's Doctor's Rm RoomECG/EKG Electrocardiogram Sm SmallEEG Electroencephlogram w/ withENT Ear, Nose, and Throat (Otorhinolaryngology)ER Emergency RoomExam ExaminationGen GeneralIntermed IntermediateICU Intensive Care UnitIV IntravenousLab LaboratoryLG LargeMediprep Medicine PreparationMob MobilizationNrsy NurseryNU Nursing Unit

JULY 1988 4

Page 7: Army Medical Design Guide - SAFE

Architectural Schedule

ARCHITECTURAL NOTES

GENERAL NOTES

1. Doctor's Office and Examination Room are to be identical in all respects with the exception of the equipment and room designation.

2. Ceiling height to be a minimum of 8'-6" with a minimum of 9'-0" to structural support for ceiling mounted surgical light.

3. A minimum of 6 is required between room walls and prefabricated Audiometric Testing Room. The Audiometric Testing Room will require a recessed slab and special structural design due to the weight of the rooms

4. Add 6 NSF for Nurse Server and 5 NSF for Wardrobe to Bedroom Area.

5. Patient Service Console M5541 shall be provide in all Labor Rooms in Medical Centers and in 25% of the Labor Room in MEDDACS.

6. Area includes 80 SF for Plaster Preparation.

7. Add 12 NSF for Nurse Servers and 10 NSF for Wardrobes to Bedroom Area.

8. Add 24 NSF for Nurse Servers, 20 NSF for Wardrobes and 20NSF for a lavatory to Bedroom Area.

9. Walls for Seclusion Bedroom shall be reinforced with plywood or steel backed GWB. All items to be tamperproof and installed with tamperproof fasteners.

10. Add 8 NSF for undercounter Nurse Server and 5 NSF for Wardrobe to Bedroom Area.

11. Add 16 NSF for Nurse Servers, one undercounter and one full height, 10 NSF for Wardrobes and 20 NSF for a lavatory to Bedroom Area.

12. Add 32 NSF for Nurse Servers, two undercounter and two full height, 20 NSF for Wardrobes to Bedroom Area.

13. Add 8 NSF for one undercounter Nurse Server to Anteroom and 5 NSF for a Wardrobe and 20 NSF for a lavatory to Bedroom Area.

14. Add 6 NSF for Nurse Server to Anteroom and 5 NSF for Wardrobe to Bedroom.

15. Add 6 NSF for Nurse Server to Anteroom and 5 NSF for Wardrobe to Toilet.

16. Provide a minimum of 1 Oral Surgery Room with X-ray capability per Dental Suite.

17. Room requires lead lined walls.

18. Provide 2 Dressing Cubicles at 20 NSF each.

JULY 1988 5

Page 8: Army Medical Design Guide - SAFE

Architectural Schedule (Cont'd)

ARCHITECTURAL NOTES

GENERAL NOTES (Cont'd)

19. Provide undercut (cu) to door.

20. Wall finish as noted with Ceramic Tile Wainscot.

21. Add 8 NSF for undercounter Nurse Server to Bedroom Area.

22. Provide one lavatory at 15 NSF per each six bassinets.

23. Provide one lavatory at 15 NSF per each four bassinets.

24. VWF is an optional wall finish.

25. Interior glazing shall contain integral Mini-Blinds.

26. The columns shown in patient bedrooms are for purposes of establishing the minimum clear width of these rooms. The selection of a structural system that requires columns along the corridor wall will establish a minimum clear dimension of 13 in the patient bedrooms. A structural system without columns on the corridor wall will establish a minimum clear dimension of 12'-6". These dimensions are set, as indicated on the room design for the patient bedroom, by the items to be installed along the corridor wall and entrance to the room. A 13 clear dimension will require a 27' column spacing on the exterior wall and a 12'-6" will require a 26' column spacing. The one patient bedroom indicates the preferred column location when only one exterior column is required.

27. Add 30 NSF to room for x-ray generating equipment.

28. Area requires computer flooring.

29. Square footage must be added to this area as required to meet requirements of largest computer equipment.

30. If Halogen is used for Fire Protection, special exhaust may be required.

31. This room must be located on building exterior, occupied areas should not be located above or below this room.

32. Verify floor tolerances with equipment manufacturer.

33. Provide ICU type patient service consoles for 25% of recovery beds.

34. The quantity and type of equipment, infant incubators and/or infant care centers, will be determined by the user.

35. Wall finish as noted with Ceramic Tile Wainscot.

JULY 1988 6

Page 9: Army Medical Design Guide - SAFE

Architectural Schedule (Cont'd) MISCELLANEOUS ABBREVIATIONS

ABBREV. DESCRIPTION ABBREV. DESCRIPTIONAFF Above Finished Floor MOD Modified

AR As Required MV Medical Vacuum

CFM Cubic Feet Per Minute N Nitrogen

CRS Corrosive Resistive Steel N20 Nitrous Oxide

CR50 Color Corrected Fluor Lamp 5000 K NA Not Applicable

CONFID Confidential NCRP National Council on Radiation ProtectionCW Cool White NP Normal PowerCWX Cool White Deluxe OC On CenterDA Dental Air OE Dental Oral EvacuationEA Each OX OxygenEC Electrical Receptacle, emergency circuit PA Process Air

EFF Efficient PR Pair EP Emergency Power RFI Radio Frequency InterferenceEP Emergency Power S Switch, for type seeEXH Exhaust symbols

F Fluorescent STD Standard G Natural Gas TV Television

HID High Intensity Discharge UON Unless Otherwise Noted

Hosp Hospital VS Vacuum Bottle Slide BracketLA Laboratory Air WAGE Waste Anesthesia GasLG Laboratory Gas Evacuation

LV Laboratory Vacuum W/O Without MA Medical Air WP Weatherproof

MG Medical Gases

MG-MA Medical Gas - Master Alarm Panel

MG-RA Medical Gas - Remote Alarm Panel

MG-ZA Medical Gas - Zone Alarm Panel

MG-ZV Medical Gas - Zone Valves

JULY 1988 7

Page 10: Army Medical Design Guide - SAFE

Architectural Schedule (Cont'd)

FINISH ABBREVIATIONS

FLOOR FINISHES CEILING FINISHES

ABBREV. DESCRIPTION ABBREV. DESCRIPTION

CT Ceramic Tile ACT Lay-In Acoustical TileConc-1 Concrete Sealer - Size to be SpecifiedConc-2 Fluid Applied Membrane ACT(P) Lay-In Acoustical Tile Waterproofing ACT-2* Lay-In Acoustical TileET Epoxy Terrazzo w/Vinyl Protective FinishQT Quarry Tile ACT-3 Concealed SplineSV Sheet Vinyl 1' x 1' or 2' x 2'VCT Vinyl Composition Tile ACT-3(P) Concealed SplineCarpet Carpet - Mineral Tile - 1' x 1' orRF Resinous Flooring 2' x 2' ACT-3(V) Concealed Spline - Mineral Tile - 1' x 1' or 2' x 2' w/Vinyl ProtectiveBASE Finish ACT-4 Concealed SplineCT Ceramic Tile - Metal Tile - 1' x 1' orET Epoxy Terrazzo 1' x 2'QT Quarry Tile ACT-4(P) Concealed SplineIV Integral Vinyl - Metal Tile - 1' x 1' orR Resilient (Vinyl w/Cove 1' x 2' Base is Acceptable) VP -Veneer PlasterConc Concrete GW Gypsum Wallboard GW-LGC Gypsum Wallboard with Liquid Glazed Coating

PARTITION FINISHES * Use ACT-2 gasketed and clipped in place as alternate if 2' x 2' tileABBREV. DESCRIPTION is required as standard.

CT Ceramic TileCMU Concrete BlockGW Gypsum Wallboard w/Paint type not SpecifiedGW-VWF Gypsum Wallboard w/Vinyl Wall FabricGW-SG Gypsum Wallboard with Semi Gloss PaintCT-WS Ceramic Tile WainscotWG Wall Corner GuardWB Wall Bumper (Mounting Height to be Specified)

JULY 1988 8

Page 11: Army Medical Design Guide - SAFE

Architectural Schedule (Cont'd)

JULY 1988 9REVISED SEPTEMBER 1994

Page 12: Army Medical Design Guide - SAFE

Architectural Schedule (Cont'd)

SET DESCRIPTION

H01 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stop L02101 2 Mop Plates J107 1 Set Head & Jamb Pemko 319AN Gaskets 1 Automatic Pemko 434A Door Bottom

H02 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stretcher Plates J105 2 Mop Plates J107 1 Set Head & Jamb Pemko 319AN Gaskets 1 Automatic Pemko 434A Door Bottom

H03 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stop L02101 2 Mop Plates J107 3 Silencers L03011

H04 1-1/2 PR Butts A5111 1 Stop L02101 1 Stretcher Plate J105 2 Mop Plates J107 3 Silencers L03011

H05 3 PR Butts A5111 1 Lockset F05 w/ Levers (36") 2 Automatic Type 25 (18") Flush Bolts 1 Stop L02101 (36") 1 Holder C01511 (18") 2 Stretcher Plates J105 4 Mop Plates J107 1 Push Plate J301 (18") 1 Pull Glynn-Johnson GJKH1 (18") 2 Silencers L03011 36" Leaf w/ 18" Leaf

H06 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stop L02101 1 Armor Plate J105 2 Mop Plates J107 3 Silencers L03011

H07 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Lock Electronic Cipher type 1 Stop L02101 2 Mop Plates J107 3 Silencers L03011

H08 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Closer C02011 1 Stop L02101

Page 13: Army Medical Design Guide - SAFE

1 Kick Plate J102 1 Stretcher Plate J105 1 Mop Plate J107 1 Head & Jamb Pemko S88 Gaskets 1 Automatic Pemko 412AN Door Bottom

H09 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stretcher Plate J105 2 Mop Plates J107 3 Silencers L03011

H10 1-1/2 PR Butts A5111 1 Hosp Latch Set Glynn-Johnson HL-6 1 Stop L02101 1 Stretcher Plate J105 2 Mop Plate J107 3 Silencers L03011

H11 1-1/2 PR Butts A5111 1 Hosp Latch Set Glynn-Johnson HL-6 1 Closer C02051 or C02061 1 Kick Plate J102 1 Stretcher Plate J105 1 Mop Plate J107 1 Stop L02101 3 Silencers L03011

H12 1-1/2 PR Butts A5111 1 Lockset F02 w/ Levers 1 Holder C01511 1 Stretcher Plate J105 3 Silencers L03011

H13 1-1/2 PR Butts A5111 1 Lockset F02 w/ Levers 1 Stop L02101 2 Mop Plates J107 3 Silencers L03011

JULY 1988 10

Page 14: Army Medical Design Guide - SAFE

Architectural Schedule (Cont'd)SET DESCRIPTION

H14X 1-1/2 PR Butts A5111-5 1 Lockset F02 w/ Levers 1 Stop L02101 1 Mop Plates J107 1 Silencers L03011 Provide lead shields for mortise lock cases. Levers and roses to be lead lined

H15X Pivots (Top, Bottom, & C07111 & C07311 Intermediate) 1 Lockset F17 1 Hatch Latch Set Glynn Johnson HL-6 1 Holder C05531 1 Stretcher Plate J105 2 Mop Plates J107 3 Silencers L03011 Provide lead shields for mortise lock cases. Levers and roses to be lead lined H16 3 PR Butts A5111 w/ Hosp Tips 2 Latch Set E59091 at Head 2 Holder C01511 2 Push Plates J301 2 Pulls Glynn Johnson GJKH1 2 Armor Plates J101 2 Mop Plates J103 2 Silencers L03011 48" Leaf w/ 18" Leaf

H17 1-1/2 PR Butts A5111 w/Hosp Tips 1 Latch Set E59101 1 Closer C02051 or C02061 1 Push Plate J301 1 Pull Glynn-Johnson GJKH1 1 Kick Plate J102 1 Mop Plate J103

H18 1-1/2 PR Butts A5111 w/ Hosp Tips 1 Latch Set E59101 1 Closer C02051 or C02061 1 Push Plate J301 1 Pull Glynn-Johnson GJKH1 1 Armor Plate J101 1 Mop Plate J103

H19 1-1/2 PR Butts A511 1 Lockset F04 w/ Lever 1 Closer C02011 1 Stop L02101 1 Kick Plate J102 1 Mop Plate J103 1 Silencers L03011 1 Set Head & Jamb Pemko 319 AN Gaskets 1 Automatic Pemko 434A Door Bottom Fire Rated Hardware

H20 1-1/2 PR Butts A5111 1 Lockset F04 w/ Levers 1 Stop L02101 2 Mop Plates J107

Page 15: Army Medical Design Guide - SAFE

3 Silencers L03011H21 1-1/2 PR Butts A5111 1 Lockset F18 1 Latch Set E59101 1 Stop L02101 2 Pulls J403 2 Mop Plates J107 1 Set Head & Jamb Pemko 319AN Gaskets 1 Automatic Pemko 434A Door BottomH22 - Hardware by Door Manufacturer

NOTES:

1. Manufacturer's Name and Number are furnished to serve only as examples of the type of products desired and not a proprietary item.

2. All metal kick plates, stretcher plates, armor plates, pulls and push plates shall be stainless steel.

3. All door trim protection plates shall be 2" less than the width of a single door and 1" less for pairs of doors.

4. All closers shall be provided with the capability for regular or parallel arm mounting applications. Delay action type closers will be provided on doors where cart traffic and handicap accessible is a consideration.

JULY 1988 11

Page 16: Army Medical Design Guide - SAFE

Architectural Schedule (Cont'd)

FIRE PROTECTION NOTES

GENERAL NOTES

A. Noncombustible construction with one-hour corridor walls are required for unsprinklered buildings.

B. ICU and CCU patient rooms may be open to a nurse's station as one large room without corridor, provided the space has it s own exits and is not a required exit for another space.

C. Nurse's station may be open to a corridor provided it is staffed 24 hours/day; does not reduce width of corridor; contains only communication and monitoring equipment, counter and seating, space for charts and one day s supply of forms.

D. No more than one day s supply of flammable liquid permitted in a room at one time.

E. One hour enclosure for oil-cooled transformers. Refer to NFPA No. 70 for enclosure ratings for other types and sizes of transformers.

F. Provide smoke detectors only when waiting areas are open to corridors. Open waiting cannot exceed 250 square feet in patient sleeping areas and 600 square feet in non-sleeping areas.

G. When several laboratories are contiguous an. d within applicable total area limitations, the labs may be considered as one room.

H. Engineered Smoke Control/Evacuation System will be considered on a case- by-case basis, depending on building design and other fire protection features utilized. Generally, there will be no equivalences given for such systems.

I. Local fire department support for the building design must be considered. Generally, totally sprinklered buildings will be the most economical design.

J. References:

1. National Fire Protection Association Codes - current edition.

2. Uniform Building Code - current edition (for building type only).

3. MIL-HDBK-1191 - Department of Defense Medical and Dental Treatment Facilities Design and Construction Criteria.

4. MIL-HDBK-1691 - Construction and Medical Schedule for Military Medical and Dental Facilities - current edition.

JULY 1988 12REVISED SEPTEMBER 1994

Page 17: Army Medical Design Guide - SAFE

Mechanical Schedule

JULY 1988 13REVISED SEPTEMBER 1994

Page 18: Army Medical Design Guide - SAFE

Mechanical Schedule (Cont'd)

MECHANICAL NOTES

GENERAL NOTES (Cont'd)

4. HEPA filters having DOP test efficiencies of 99.9% shall be used on air supply systems serving rooms used for clinical treatment of patients with a high susceptibility to infection from leukemia and burns. They shall also be used on the exhaust discharge air from fume hoods or safety cabinets in which infections or highly radioactive materials are processed and shall be designed and equipped to permit safe removal, disposal and replacement of contaminated filters. For radioactive exhaust, use nuclear grade HEPA filters with DOP efficiency at 97.97% at 0.3 micron.

5. See MIL-HDBK-1191 for additional requirements.

SPECIFIC NOTES

6. Air Supply will in general, be obtained from adjacent areas, mechanical exhaust will be provided.

7. The Oral Surgery Operating Rooms will be treated as medical operating rooms. Normal treatment other than oral surgery will be performed in dental treatment rooms.

8. Hood exhausts and equipment exhausts will be considered in balance of supply and exhaust air quantities.

9. Four low air exhausts will be provided for improved distribution of clean air and removal of contaminants in operating room.

10. Audiobooth air supply and return will be through sound attenuating ducts and discharge silencers supplied by the manufacturer. The building supply and return ducts will be connected directly to the audiobooth silencers. These connections will be coordinated with the audiobooth manufacturer.

11. The Bedroom shall be negative to the anteroom, positive to the toilet and the anteroom shall be negative to corridor for a normal isolation room. For positive isolation room, reverse air flow and increase filtration to 95% efficiency except for toilet, which will remain negative.

12. Not Used

13. Temperature and humidity control required.

14. Separate packaged air conditioning unit may be required.

15. The soiled side of all undercounter Nurse Servers must e supplied with on exhaust connection form beneath, when ceiling exhaust cannot be utilized.

JULY 1988 14REVISED SEPTEMBER 1994

Page 19: Army Medical Design Guide - SAFE

Mechanical Schedule (Cont'd) MECHANICAL NOTES

SPECIFIC NOTES (Cont'd)

16. Equipment vent connection required.

17. Exhaust from this room must pass through a filter before being released to atmosphere.

18. Equipment heat loads must be taken into account for calculation purposes.

JULY 1988 15

Page 20: Army Medical Design Guide - SAFE

Mechanical Schedule (Cont'd)

PIPING NOTES

GENERAL NOTES

1. Treatment Rooms - Provide Oxygen and Medical Vacuum in Clinic Treatment Room and Oxygen, Medical Air and Medical Vacuum in Nursing Unit Treatment Room.

2. Medical Gas Remote Zone Panel will be located in the area.

3. Medical Gas Remote Alarm Panel will be located in the room.

4. This area to contain plaster trap under the sink.

5. Refer to Patient Service Console/Service Column for distribution of Medical Gases.

6. One MG-3 required for each 6-8 Bassinets.

7. One MG-3 required for each Observation Bassinet and for each 6-8 Cont. Care Bassinets.

8. Refer to Mechanical Schedule page 17 and 18 for details of Dental Utility Center.

9. Room requires Acid Waste plumbing.

10. Waste Water from this room must be diverted into a Holding Tank and not into the sanitary waste system.

JULY 1988 16

Page 21: Army Medical Design Guide - SAFE

Mechanical Schedule (Cont'd)

JULY 1988 17

Page 22: Army Medical Design Guide - SAFE

Mechanical Schedule (Cont'd)

JULY 1988 18

Page 23: Army Medical Design Guide - SAFE

Mechanical Schedule (Cont'd)

JULY 1988 19

Page 24: Army Medical Design Guide - SAFE

Electrical Schedule

ELECTRICAL NOTES

GENERAL NOTES

1. Ambient illumination levels listed in matrix data are maintained averages for the space, measured in footcandles on a horizontal plane at work plane height and based on the following effective reflectances:

A. Operation Rooms, Delivery Rooms and similar locations:

Walls - 70% Ceilings - 80% Floors - 20%

B. General Rooms with gypsum wallboard ceilings and walls:

Walls - 50% Ceilings - 80% Floors - 20%

C. General Rooms with lay-in tile ceiling:

Walls - 50% Ceilings - 70% Floors - 20%

D. Darkrooms and other film processing rooms:

Walls - 0% Ceilings - 0% Floors - 0%

E. Eye test and eye exam rooms:

Walls - 30% Ceilings - 50% Floors - 20%

F. Rooms with wall mounted luminaires having non-symmetrical distribution:

Walls - 50% Ceilings - Effective reflectance based on IES calculation and IES fig. 9-11 Floors - 20%

2. Luminaire type designation applies only to layouts shown on reflected ceiling plans, and are not functional requirements. When required, utilize 40 watt, rather than 35 watt, fluorescent lamps with appropriate ballast (i.e. color improved lamp or dimmed fixture).

JULY 1988 20

Page 25: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd) ELECTRICAL NOTES

GENERAL NOTES-(Cont'd)

3. Switching:

Std. Single on-off switch adjacent to entrance controlling all general room lighting. Std-by Areas Each area controlled by separate switch adjacent to entrance or as indicated. Ext External, to be controlled from central location. Dim Lighting controlled by a single dimmer switch in Std. location. Fluorescent lighting luminaires shall be equipped with dimmable ballasts and 40 watt lamps. Multi-Sw Multiple switching, by separate switches adjacent to entrance, of multilamp luminaires e.g., 4-lamp luminaire having two switches each disconnecting one 2-lamp ballast from supply circuit.

4. Ambient and task illumination levels shown are from recommended levels specified in MIL-HDBK 1191, Appendix "A" and supplemented by the Illumination Engineering Society and Committee Report CP-29 (Lighting for Health Care Facilities) and IES Lighting Handbook 1987 Application Volume.

SPECIFIC NOTES

5. In radiology rooms provide wall mounted direct/indirect 4 ft. cove lighting luminaires, units mounted in continuous rows.

6. Dark Room, 20 fc. average under normal white light only. Safe light receptacle and darkroom in-use light separately switched at standard location. Film loading bin, when provided, shall have drawer limit switch to be interlocked with normal light and safelight/in-use light to shut off normal light and turn on safe light/in-use light if bin drawer is opened or in open position. Provide switched duplex receptacle for safe light.

7. Scrub area lighting controlled by local switch(es).

8. 25% of lighting shall be provided with battery back-up and separately switched

9. Not Used

10. Illumination should be provided by special fluorescent lamps producing light at CRI of 90-100. Color temperature, 5000 degree Kelvin.

11. Minimum light ratios of 5:1 (clear or laminated mirror glass) or 2:1 (grey mirror glass) must be obtainable from the Group Therapy Room, and other observed rooms, to the Mirror Room. Increased ratios to 10:1 and 4:1, respectively, are preferred.

JULY 1988 21REVISED SEPTEMBER 1994

Page 26: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd)

ELECTRICAL NOTES

SPECIFIC NOTES (Cont'd)

12. Reading light, connected to emergency branch circuit, to be controlled by switch in nurse call handset. Reading light may be wall or ceiling mounted to permit reading in a bed at an angle of 35 to 65 degrees, as well as straight down. Luminaire is to provide 30 fc minimum on reading material at any position.

13. Examination light to be controlled by switch at patient service console.

14. In patient bedrooms, wall mounted uplight/downlight luminaire mounted 6'-6" above finished floor over the beds. Controlled individually from switch on patient service console. All bedroom uplight may be controlled by common switch. Utilize offset type I.V. pole with electrically operated beds to prevent damaging luminaire.

15. Night lights, connected to emergency branch circuit, will be photocell controlled, and be all on or all off . No switch at standard location or nurse station for night light control.

16. Observation light to be controlled by switch at patient service console, except in psychiatric units where they will be switched at the door.

17. X-ray room (having uncontrolled room access) door limit switch to be interlocked with X-ray unit control circuit to shut off or prevent production of X-rays if door is opened or in open position.

18. X-ray in-use light to be interlocked with X-ray unit power on-off control circuit, not X-ray control circuit.

19. Luminaires shall be equipped with RFI and EMI suppression.

20. Locate room to minimize RFI. Coordinate location of room with architects.

21. Not Used

22. Wiring connection as required by manufacturer. (GFI circuit protection required).

23. Not Used

24. Lighting luminaires above work station shall be connected to life safety branch as required to meet NFPA 101 emergency egress requirements.

25. One X-ray film processing room per department to be connected to emergency power.

26. Power supply requirements, exact quantity and location of enclosed circuit breaker disconnect switches and emergency push buttons shall be per manufacturer's recommendations.

JULY 1988 22

Page 27: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd)

ELECTRICAL NOTES

SPECIFIC NOTES (Cont'd)

27. All electrical requirements, including luminaire and switching, shall be per manufacturer's requirements.

28. Dedicated circuit required for equipment.

29. 15% to 25% of lighting shall be provided with 30 minute battery back up and separate switch.

30. Provide a minimum of one simplex receptacle for each infant care station.

31. Provide a minimum of four simplex receptacles for each infant care station.

32. Provide a minimum of sixteen simplex receptacles per ICU infant care station.

33. All utilities to casework must feed from below, utility columns from ceiling to casework are not acceptable.

34. Provide a minimum of one 2" conduit from each bed location to nurses station for physiological monitoring.

35. Provide a minimum of one Radiographic Room and associated support with emergency power.

36. All Remote Alarm Panel, Master Clock Panel, Master Telephone Console, and Security Monitors shall be located in this room.

37. Dimmer controls for group therapy and play therapy to be located in mirror room.

38. Refer to Patient Service Console/Service Column for electrical outlets and location.

39. Air conditioning equipment for this area shall be on emergency power.

40. Provide a minimum of eight simplex receptacles for each infant care station.

41. 5% of lighting shall be provided with 30 minute battery back-up and separately switched.

42. 25% of power shall be on emergency.

43. Provide empty conduit from antenna location to communication equipment.

44. Ceiling Lighting Fixtures must not be located directly over bassinet or infant care centers in Nurseries.

JULY 1988 23

Page 28: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd)

LUMINAIRE SCHEDULE

COE DWG 40-06-04TYPE DESCRIPTION TYPE SH.

A1 2' x 4' recessed fluor. W/4-F40 CW lamps. 206C 19

A2 2' x 4 recessed fluor. W/4-F40 CWX lamps. 206C 19

B1 2' x 4 recessed fluor. W/2-F40 CW lamps. 206A 19

B2' 2' x 4' recessed fluor. W/2-F40 CWX lamps. 206A 19

C1 2' x 4' recessed fluor. W/3-F40 CW lamps. 206B 19

C2 2' x 4' recessed fluor. W/3-F40 CWX lamps. 206B 19

D1 2' x 4 recessed fluor. W/6-F40 CR50 (CRI 90) SIM TO 19 lamps. 206

D2 2' x 4' recessed fluor. W/6-F40 CWX lamps. SIM TO 19 206

D3 2' x 4' recessed fluor. W/6-F40 CW lamps. SIM TO 19 206

E1 4' surface wall mounted fluor. with up/ down light distribution, aluminum extrusion shell, acrylic prismatic lens on bottom, clear acrylic lens on top and F40 CW lamps (number as req'd) for continuous row mounting. Units may be in continuous extrusion housing. Mount at 18 below finish ceiling unless otherwise indicated.

E2 3' luminaire same as type "E1" except W/ F30 CW lamps (number as req'd)

E3 2' luminaire same as type "E1" except W/ F20 CW lamps (number as req'd)

F1 2 x 4 recessed fluor with 12 cell, 3" deep, semi-specular anodized aluminum parabolic louver and 2-F40 CW lamps.

F2 2 x 4 recessed fluor same type "F1" except W/ 3-F40 CW lamps.

G1 6" x 4' recessed fluor with 1-F40 CW lamp. SIM TO 19 204

G2 6" x 3' recessed fluor with 1-F30 CW lamp. SIM TO 19 204

JULY 1988 24

Page 29: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd)

LUMINAIRE SCHEDULE COE DWG 40-06-04TYPE DESCRIPTION TYPE SH.

G3 6" x 2' recessed fluor with 1-F30 lamp. SIM TO 19 204

H1 4' luminaire similar to type "E1" except with uplight only and F40 CW lamp(s) (number as req'd).

H2 3 luminaire similar to type "E1" except with uplight only and F30 CW lamp(s) (number as req'd).

H3 2' luminaire similar to type "E1" except with uplight only and F20 CW lamp(s) (number as req'd).

J1 4 luminaire similar to type "E1" except with uplight only and F40 CWX lamp(s) (number as req'd).

J2 3' luminaire similar to type "E1" except with uplight only and F30 CWX lamp(s) (number as req'd).

J3 2 luminaire similar to type "E1" except with uplight only and F20 CWX lamp(s) (number as req'd).

K Patient reading light (specification to be developed).

L1 4' single lamp enclosed undercounter mounted fluor w/acrylic prismatic lens, rocker switch and 1-F40 CW lamp.

L2 3' luminaire same as type "L1" except with 1-F30 CW lamps.

L3 2' luminaire same as type "L1" except with 1-F20 CW lamps.

M1 4' luminaire same as type "E1" except with F40 CWX lamps (number as req'd).

M2 3' luminaire same as type "E1" except with F40 CWX lamps (number as req'd).

N1 2' x 4' recessed, gasketed fluor with gasketed SIM TO acrylic prismatic lens (smooth side down) 206C 19 gasketed door and frame, F40 CW lamps (number as req'd) and approved for damp locations.

P1 4' surface, wall mounted, enclosed fluor 223 17 with acrylic prismatic lens and 2-F40 CW lamps.

JULY 1988 25

Page 30: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd) LUMINAIRE SCHEDULE COE DWG 40-06-04TYPE DESCRIPTION TYPE SH.

P2 3' luminaire same as type "P1" except with SIM TO 2-F30 CW lamps. 223 17

P3 2' luminaire same as type "P1" except with SIM TO 2-F20 CW lamps. 223 17

Q1 4' single lamp strip fixture. 220A 26

Q2 3' single lamp strip fixture. SIM TO 220A 26

Q3 2' single lamp strip fixture. SIM TO 220A 26

R1 1' x 4' recessed fluor with 2-F40 CW lamps. 204 19

R2 1' x 4' recessed fluor with 2-F40 CWX lamps. 204 19

R3 1' x 4' recessed fluor with two 1-lamp ballasts and 2-F40 CWX lamps. 204 19

S Recessed incandescent downlight with 6 dia. ceiling aperature, clear polished anodized SIM TO aluminum reflector and "A" shape lamp, 116 9 wattage as req'd.

T Recessed enclosed incandescent luminaire with SIM TO flat acrylic prismatic or fresnel glass lens 127 16 and "A" shape lamp, wattage as req'd.

U Recessed enclosed incandescent luminaire with SIM TO tamperproof construction, polycarbonate or 115 A2 8 impact-resisting tempered glass lens and "A" shape lamp, wattage as req'd.

V Recessed wall mounted incandescent constructed same as type U except with 1-20 watt T shape long life lamp mount at 1'-2" AFF.

W Recessed enclosed and gasketed incandescent SIM TO luminaire with flat acrylic prismatic or fresnel 115 A2 8 glass lens, approved for wet location and with "A" shape lamp wattage as req'd.

X Surface wall mounted incandescent indicating type SIM TO luminaire with 2-20 watt T shape long life 605A 56 (10,000 HRS)lamps, aluminum stencil face having 2" high letters X-RAY IN USE with 3/4" stroke and red polymer diffuser. Mount at + 6'-6" AFF or above door as indicated.

Y Surface wall mounted luminaire same as type "X" SIM TO except reading DARKROOM IN USE. 605A 56

JULY 1988 26

Page 31: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd)

JULY 1988 27

Page 32: Army Medical Design Guide - SAFE

Electrical Schedule (Cont'd)

JULY 1988 28

Page 33: Army Medical Design Guide - SAFE

Communication Schedule

COMMUNICATION NOTES

GENERAL NOTES

1. Telephone System: Total System including instruments - contractor furnished and installed. (Unless directed otherwise by OCE)

2. Public Address/Program Distribution System: Total System - Contractor furnished and installed.

3. Nurse Call System: Total System - Contractor furnished and installed.

4. Room Status System: Total System - Contractor furnished and installed.

5. Central Clock System: Total System - Contractor furnished and installed.

6. Fire Alarm System: Total System - Contractor furnished and installed.

7. Television System (excluding CCTV System):

a. Conduits, antennas, amplifiers, splitters, terminations, outlets, and cables - Contractor furnished and installed.

b. TV mounting brackets, all types - Government furnished and Contractor installed.

c. Television cameras and receivers - Government furnished and installed.

8. Central Dictation System:

a. Conduits, cables and outlets - Contractor furnished and installed.

b. Equipment - Government furnished and installed.

9. Trimis System:

a. Conduits, cables, headend equipment, distribution amplifiers, splitters, couplers, and outlets - Contractor furnished and installed.

b. Data terminals, computers, and bus interface units/modems - Government furnished and installed.

10. Intrusion Detection System:

a. Conduits and outlets - Contractor furnished and installed.

b. Cables, sensors and equipment - Government furnished and installed. (unless directed otherwise by OCE)

11. Closed Circuit Television System:

a. Conduits and outlets - Contractor furnished and installed.

b. Cables, camera and monitors - Government furnished and installed.

JULY 1988 29

Page 34: Army Medical Design Guide - SAFE

Communication Schedule (Cont'd)

COMMUNICATION NOTES

GENERAL NOTES

12. All trimis and television outlet locations will include a duplex electrical receptacle.

13. TV distribution and trimis system will utilize the same cable system. (unless directed otherwise by OCE)

14. All elapse time clocks will include remote controls.

SPECIFIC NOTES

15. Provide Room Status and Nurse Call Emergency Systems in Clinic Treatment Rooms and Nurse Call System with Single Patient Station and duty station in Nursing Unit Treatment Rooms.

16. Coordinate telephone and trimis outlets with Audiometric Room manufacturers.

17. Refer to Patient Service Console for communication requirements.

JULY 1988 30

Page 35: Army Medical Design Guide - SAFE

Communication Schedule (Cont'd)

JULY 1988 31REVISED SEPTEMBER 1994

Page 36: Army Medical Design Guide - SAFE

Communication Schedule (Cont'd)

JULY 1988 32

Page 37: Army Medical Design Guide - SAFE

Communication Schedule (Cont'd)

JULY 1988 33

Page 38: Army Medical Design Guide - SAFE

Communication Schedule (Cont'd)

JULY 1988 34

Page 39: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room

JULY 1988 35REVISED SEPTEMBER 1994

Page 40: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room (Cont'd)

JULY 1988 36REVISED SEPTEMBER 1994

Page 41: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room (Cont'd)

JULY 1988 37REVISED SEPTEMBER 1994

Page 42: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room (Cont'd)

JULY 1988 38REVISED SEPTEMBER 1994

Page 43: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room (Cont'd)

JULY 1988 39REVISED SEPTEMBER 1994

Page 44: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room (Cont'd)

JULY 1988 40REVISED SEPTEMBER 1994

Page 45: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room (Cont'd)

JULY 1988 41REVISED SEPTEMBER 1994

Page 46: Army Medical Design Guide - SAFE

Doctor's Office/Exam Room (Cont'd)

JULY 1988 42REVISED SEPTEMBER 1994

Page 47: Army Medical Design Guide - SAFE

Patient Service Console

JULY 1988 43REVISED SEPTEMBER 1994

Page 48: Army Medical Design Guide - SAFE

Typical Med Gas Locations

SEPTEMBER 1994 43A

Page 49: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 44REVISED SEPTEMBER 1994

Page 50: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 45REVISED SEPTEMBER 1994

Page 51: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 46REVISED SEPTEMBER 1994

Page 52: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 47REVISED SEPTEMBER 1994

Page 53: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 48

REVISED SEPTEMBER 1994

Page 54: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 49REVISED SEPTEMBER 1994

Page 55: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 50REVISED SEPTEMBER 1994

Page 56: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 51REVISED SEPTEMBER 1994

Page 57: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 52REVISED SEPTEMBER 1994

Page 58: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 53REVISED SEPTEMBER 1994

Page 59: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 54REVISED SEPTEMBER 1994

Page 60: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 55REVISED SEPTEMBER 1994

Page 61: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 56REVISED SEPTEMBER 1994

Page 62: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 57REVISED SEPTEMBER 1994

Page 63: Army Medical Design Guide - SAFE

Patient Service Console (Cont'd)

JULY 1988 58REVISED SEPTEMBER 1994

Page 64: Army Medical Design Guide - SAFE

X-ray Rooms Criteria

Universal X-ray Rooms

A. Definition of Universal X-Ray Room:

"The Universal X-ray room shall be capable of accepting allradiographic, fluoroscopic and tomographic equipment regardless ofmanufacture, during initial installation and subsequent replacement actionswith little, if any, facility modifications. The procedures shall be performed unencumbered and without any restriction of system components,patient size or any known procedure that any installed X-ray equipment canperform now or in the future."

B. Criteria:

1. Room Dimensions and Area Requirements:rsal room shall be a maximum

a. Critical dimsnsions are identified on Guide Plates.

2. Electrical Trench Duct System and Electrical Supporty:

a. Locations of the trench ducts are shown on the enclosed elevations.

b. "T" floor trench duct (3-3/8" deep by 12" wide) projects from Wall A with a connecting floor trench (same size) along Wall A to the high voltage power supply.

(1) Trench partitioned fro separation of high/low voltage cables.

(2) Tranch cover plates to be of same load bearing capacity as for the floor.

(3) Trench cover plates should be fitted with a suitable gasket to maintain water tightness or to reduce corrosion to the interior.

c. Vertical lay-in riser ducts (3-1/2" deep z 10" wide) shall be recessed in walls and connected to an overhead horizontal cable tray system (located above the wall partitions within the ceiling drop panels).

(1) Studs (as shown on the enclosure) or unistrut-like supports shall be located on both sides of standard 10" wide riser ducts.

(2) Double studded walls are required where adjacent X-ray rooms are to be located or anticipated.

(3) Cable tray should be partitioned for separation of high/low voltage cables.

JULY 1988 59

Page 65: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd)

d. Manufacturers are to meet a plus or minus five percent supply voltage regulation specification. The requirement for power conditioning equipment should be determined for each project.

e. Provide one 120/208v, three-phase panel per room with minimum of five circuits, located with breaker behind control booth.

f. Provide shunt trip breaker control switch located on recessed riser duct, 5 feet below ceiling height (see Enclosure - Elevation B).

(1) Must meet NFPA 70 requirments.

(2) To assure front clearance, this breaker may optionally be installed on Wall D through vertical riser D-1.

g. Provide main breaker with 150 amp rating located on Wall D behind panel*, and

(1) Include for selective circuit restoration.

(2) Assure for 3-1/2" feet "clear" in front of box face (NFPA 70).

(3) Locate 4'-0" below ceiling height.

* This feature may be combined with the shunt breaker on Wall B.

h. Provide duplex receptacles at 8'-0" on center, 18" above finished floor, with the following exceptions:

(1) Double duplex (4 outlets) located behing the control booth.

(2) Duplex located behind the table in open space of Wall A, and

(3) Duplex located at foot of table.

i. Where single phase is anticipated,k design the raceway system and breaker back box for 80 KW, three-phase capacity. Where three-phase is used, also install single phase for additional flexibility in the future.

j. Normally emergency power for X-ray equipment, illumination and duplex receptacles shall be provided through a manual transfer switch to one or two X-ray rooms (including one fluoroscopic unit, if applicable). One X-ray film processor is also included on the emergency power.

JULY 1988 60

Page 66: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd)

k. Dedicated power:

(1) Where required, size for the smaller of the loads - two largest load or by the Line-Amperage method (largest load plus 22.5 percent of the remaining unit loads).

(a) Substations require nomninal unit loading of 10 to 15 percent of substation capacity.

(b) This substation sizing does not apply where only two units are supported, in which case the designer should investigate the history of brown-outs and the location of the transformers to determine the need for the dedicated power.

(2) Where not required, substation being utilized must not support motor loads but amore constant loading (i.e., lighting), and line losses shall be minimized to avoid X- ray contrast problems.

(3) Required for providing additional cooling to handle transformer heat load where substations are located in electrical rooms to avoid build-up of excessive temperatures.

l. Illumination

(1) Illumination levels and dimmer devices for all Radiographic rooms shall be in accordance with DOD 4270.1M.

(2) Location of luminaires and X-ray viewing boxes are at the discretion of individual service or agency.

(3) Dimmers shall be nearly RFI propogation free.

3. Case Work:

a. Case work shall as shown on Guide Plates.

(1) A pass box shall be specified normally only where the dark room is adjacent to the radiology room. It may be installed for film storage at user's discretion.

(2) Refer to latest edition of DOD MIL-STD-1691 for the lost of other category "A" equipment.

b. Universal design shall include rough-in for hand sink, hot/cold water with drain, location as shown.

c. Warning lights and interlocks should be provided to meet safety regulations.

JULY 1988 61

Page 67: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd) 4. Structural Support System:

a. Mechanical supporting devices on both sides of each vertical riser or vertical studs, shown on the Enclosure, shall:

(1) Provide floor-to-ceiling coverage in all cases with closure strips.

(2) Be capable of supporting static loads of 220 lbs. vertical-to-horizontal pull.

b. Ceiling grid, unistrut or equal:

(1) Spacing is 26" OC with 1-5/8" member thickness resulting in 2'-0" clearance between members and flush with accoustical ceiling.

(2) Ceiling grid channels shall be provided with closure strips.

(3) Dead Load bearing capacity.

(a) Vertical point loading is 800 to 900 pounds.

(b) Uniformly distributed load is 50 lbs.square foot.

c. Support system for ceiling mounted X-ray equipment (i.e., C arms) shall be designed to actual support requirements to suit the particular situation. Specify anchor supports and grid elements to suit situation.

5. Radiology Shielding

a. As a minimum:

(1) Comply with the design requirements of NRCP Nos. 33, 34, and 49, and certify accordingly.

(2) Lead shielding shall be 1/16 " thick up to 7' high above finished floor.

(3) Where possible, lead shielding shall be applied to exterior side of wall partitions behind gypsum board for protection.

b. Use of modular shielding (Ray Bar or equivalent) for operator's booth is encouraged.

c. Specify the operator's view window at 18" by 24" or next available standard larger size.

d. All duct work, grilles, registers and diffusers shall be located at a height higher than seven feet clear above the finished floor. Thermostats with associated transmission lines shall be surface mounted.

JULY 1988 62

Page 68: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd)

JULY 1988 63

Page 69: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd)

JULY 1988 64

Page 70: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd)

JULY 1988 65

Page 71: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd)

JULY 1988 66

REVISED SEPTEMBER 1994

Page 72: Army Medical Design Guide - SAFE

X-ray Rooms Criteria (Cont'd)

JULY 1988 67

Page 73: Army Medical Design Guide - SAFE

Department of the Army Volume 1

Medical Design Guide

Office of the Surgeon General Office of the Chief of EngineersHealth Facility Planning Agency Medical Facilities Design Office

JULY 1988REVISED SEPTEMBER 1994

Page 74: Army Medical Design Guide - SAFE

Dr's Office/Exam RmMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 100 J.S.N. Log Code Nomenclature Qty Cat

Finishes -Walls - GW A5080 Dispenser, Paper Towel 2 A -Base - R A5115 Mirror 18 X 30 2 A -Floor - VCT A5145 Coat Hook 4 A -Ceiling - ACT A5180 Track & Curtain, Cubicle 2 ACeiling Ht - 8'-0" M1620 Record Holder 2 A P3100 Lavatory, Wall Hung 2 A X3830 Illuminator, X-ray Film 1 ADoor Size & Type - 36A X3930 Illuminator X-ray Film 1 AHardware Set - H01 F0210 Chair, Side 2 CAmbient Noise Level - NC 30-35 F0280 Chair, Rotary w/ Arms 1 CSpeech Privacy Level - Confidential F0300 Chair, Rotary w/o Arms 1 C F0635 Work Station, Doctor 1 CArchitectural Notes - 1 FC695 Work Station, Computer 1 C ref. pp. 5-6 F2000 Waste Receptacle, Off 1 C F2010 Waste Receptacle SS 1 C M3075 Cabinet, Exam Rm 1 CELECTRICAL M7425 Light, Exam, Mobile 1 C M4200 Otoscope/ Ophthalmoscope 1 CAmbient Illum (FC) - 50 M4100 Sphygmomanometer 1 CTask Illum (FC) - 100 M8830 Table Instrument 1 CLuminare Type - A2 M8945 Stool Revolving 1 C M9025 Table, Exam, Cab 1 CSwitching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure (%) - 0Temperature (F) - Sum 78 Win 70

Relative Hum(%) - 30-60

Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 2 AWaste/Vent - Yes RSOSS Selector Switch 3 Button 2 AFloor Drain - No MDOOD Desk Outlet-18" AFF 2 ASteam - No MDOOW Wall Outlet-48" AFF 2 ACondensate - No

Piping Notes -

JULY 1988REVISED SEPTEMBER 1994

Page 75: Army Medical Design Guide - SAFE
Page 76: Army Medical Design Guide - SAFE
Page 77: Army Medical Design Guide - SAFE

1.01.02 ATreatment RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Clinic - 150 (2) Nursing Unit - 150

Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT(2) VCT - Ceiling - (1) ACT(2) ACTCeiling Ht - (1) 8'-6" - (2) 8'-6"

Door Size & Type - 48AHardware Set - H02Ambient Noise Level - NC 30-35Speech Privacy Level - Confidential

Architectural Notes - 2 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 50Task Illum (FC) - (1) 100 (2) 100Luminare Type - (1) A2 - (2) A2

Switching - (1) Std by Area - (2) Std by Area

Electrical Notes -

MECHANICAL

Total Air Changes - (1) 4 (2) 6Outside Air Changes - (1) 1 (2) 1.5Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70

Relative Hum(%) - (1) 30-60 (2) 30-60

Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - Yes Treated Water - No (1) MG-2 - 1Chilled Water - No (2) MG-3 - 2Waste/Vent - YesFloor Drain - No Steam - No Condensate - No

Page 78: Army Medical Design Guide - SAFE

Piping Notes - 1 ref. pp. 16EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02Q0 Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 AC04JO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 2 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM0381 Record Holder 1 AM3620 Dispenser, Paper Towel 1 AM3800 Desk, Folding, Wall Mount 1 AM4740 Light, Exam, Ceiling 1 AM5960 Coat Hook 2 AM7960 Track Curtain, Cubicle 1 AX3990 Illuminator X-ray Film 1 AM4001 Otoscope/ Ophthalmoscope 1 BM4460 Sphygmomanometer 1 BF2010 Waste Receptacle SS 1 CM3051 Defibrillator w/Cart 1 CM7100 Table Exam., Cab 1 CM7400 Table Instrument 1 CM7415 Stand Mayo 1 CM7705 Stool, Revolving 1 CM8160 Scale, Weighing 1 C

COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty Cat

NC001 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOEL Dome Light w/Chime 1 ANCOET Pullcord Station, Emer 1 ANCOOD Duty Station 1 APAOMO Ceiling Speaker-Music Only 1 APAOOV Volume Control 1 ARSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch 3 Button 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A

Communication-Notes - 15 ref. pp. 29-30JULY 1988

Page 79: Army Medical Design Guide - SAFE
Page 80: Army Medical Design Guide - SAFE
Page 81: Army Medical Design Guide - SAFE
Page 82: Army Medical Design Guide - SAFE
Page 83: Army Medical Design Guide - SAFE

1.01.03 ASoiled Utility - CLMatrix Data

ARCHITECTURAL ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT C01C0 Cabinet, U/C, Base 1 A - Ceiling - ACT C02Q0 Cabinet, U/C, Sink 1 ACeiling Ht - 8'-0" CC010 Cabinet, Wall Hung 1 ADoor Size & Type - 36D CS140 Sink, SS, Counter 1 AHardware Set - H19 CT030 Counter Top - P.L 1 AAmbient Noise Level - NC 35-40 M3620 Dispenser, Paper Towel 1 ASpeech Privacy Level - Noncritical P6350 Sink, SVC, Wall Hung 1 A M2020 Trashcan, Mobile 2 C M4500 Hamper, Linen 2 C

Architectural Notes

ELECTRICAL

Ambient Illum (FC) - 20Task Illum (FC) - 20Luminare Type - B1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1Room Pressure(%) - -10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,0

Mechanical Notes

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatChilled Water - No Waste/Vent - Yes TLOOW Wall Outlet-54" AFF 1 A Floor Drain - No TSOOW Wall Outlet-36" AFF 1 ASteam - NoCondensate - No

Piping Notes

JULY 1988

Page 84: Army Medical Design Guide - SAFE

JULY 1988

Page 85: Army Medical Design Guide - SAFE

JULY 1988

Page 86: Army Medical Design Guide - SAFE

JULY 1988

Page 87: Army Medical Design Guide - SAFE

JULY 1988 1.01.04 A

Page 88: Army Medical Design Guide - SAFE

Satellite LabMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 80 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT CC020 Cabinet, Wall Hung 1 A - Ceiling - ACT C0045 Drawer Unit, Double - 36"L 1 ACeiling Ht - 8'-0" C06C0 Cabinet, UC, Base 1 ADoor Size & Type - 36G C06D0 Cabinet U/C, Base 1 AHardware Set - H03 C07C0 Cabinet U/C, Base 1 AAmbient Noise Level - NC 30-35 C07A0 Cabinet, U/C, Sink 1 ASpeech Privacy Level - Normal CS150 Sink, SS, Counter 1 A CT030 Counter Top - P.L. 1 A M3620 Dispenser, Paper Towel 1 A F2000 Waste Receptacle, Off 1 CArchitectural Notes - R6200 Refrigerator, U/C, Lab 1 C

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - C1Switching - Std-by Area

Electrical Notes - 42 ref pp 20-23MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure (%) - - 10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration (%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No TL00W Wall Outlet-54" AFF 1 AWaste/Vent - Yes TS00D Wall Outlet-18" AFF 1 AFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

JULY 1988

Page 89: Army Medical Design Guide - SAFE

JULY 1988

Page 90: Army Medical Design Guide - SAFE

JULY 1988

Page 91: Army Medical Design Guide - SAFE

JULY 1988

Page 92: Army Medical Design Guide - SAFE

JULY 1988

Page 93: Army Medical Design Guide - SAFE

1.01.05 AReception AreaMatrix DataARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 120 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT C0045* Drawer Unit, Single - 36"L 1 A - Ceiling - ACT C0046 Drawer Unit, Double - 48"L 2 ACeiling Ht - 8'-0" C06D0 Cabinet, U/C, Base 2 ADoor Size & Type - 36A C06M0 Cabinet U/C, Base 2 AHardware Set - H03 F0224 Reception Counter 1 AAmbient Noise Level - NC 30-35 F0300 Chair, Rotary w/o Arms 2 CSpeech Privacy Level - Normal F0460 Cabinet, Filing, 5 Drw 1 C

Architectural Notes - * Removable Drawer Sections

ELECTRICAL

Ambient Illum (FC) - 30Task Illum (FC) - 70Luminare Type - B1,L1,Q1Switching - Std-by Area

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure (%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration (%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - No Hot Water - No Qty Treated Water - NoChilled Water - No MG-ZA - 1Waste/Vent - No Floor Drain - No Steam - No Condensate - No Piping Notes - 2 ref. pp. 16

COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty CatNCOAP Clinic Annunciator Panel 1 APAOOM Desk Microphone 1 APAOVR Volume Ctrl. W/By-Pass Relay 1 ARSOAP Annunciator Panel, Desk 1 AMDOOC Counter Outlet - 6" Above CT 2 AMDOOW Wall Outlet - 48" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 94: Army Medical Design Guide - SAFE
Page 95: Army Medical Design Guide - SAFE
Page 96: Army Medical Design Guide - SAFE
Page 97: Army Medical Design Guide - SAFE
Page 98: Army Medical Design Guide - SAFE

1.02.01 ATrauma RoomMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - CT Code Nomenclature Qty Cat - Base - ET - Floor - ET CE040 Cabinet, Wall Hung 1 A - Ceiling - GWT CE050 Cabinet, Wall Hung 1 ACeiling Ht - 9'-6" C02Q0 Cabinet U/C, Sink 1 ADoor Size & Type - 48A/18A C04J0 Cabinet U/C, Base 1 AHardware Set - H16 C05E0 Cabinet U/C, Base 1 AAmbient Noise Level - NC 30-35 CS150 Sink, SS, Counter 1 ASpeech Privacy Level - Confidential CT030 Counter Top - P.L. 1 A M3620 Dispenser, Paper Towel 2 A M4802 Light, Surgical, Ceiling 1 A M5540 Patient SVC Column 1 A M7960 Track & Curtain, Cubicle 1 AArchitectural Notes - M8000 IV Track 1 A P6950 Scrub Sink w/Knee Control 1 A X3990 Illuminator, X-ray Film 1 A M4001 Otoscope/Ophthalmoscope 1 BELECTRICAL M4460 Sphygmomanometer 1 B F1938 Table, Treatment, ER 1 CAmbient Illum (FC) - 100 F2010 Waste Receptacle SS 1 CTask Illum (FC) - 100 M3051 Defibrillator w/ Cart 1 CLuminare Type - D1 M7400 Table, Instrument 1 CSwitching - Multi-Sw M7415 Stand Mayo 1 C M7705 Stool, Revolving 2 C

Electrical Notes - 8,34,38 ref pp 20-23

MECHANICAL

Total Air Changes - 12Outside Air Changes - 3Room Pressure (%) - + 10Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration (%) - 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes Qty Hot Water - YesTreated Water - No M5540 - 1Chilled Water - No Waste/Vent - Yes Floor Drain - No Steam - No Condensate - No

Piping Notes - 5 ref. pp. 16

COMMUNICATION PROGRAM

Commo Log

Page 99: Army Medical Design Guide - SAFE

Code Nomenclature Qty Cat

NCO01 Single Patient Station 1 ANCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet - 54" AFF 1 ATLOKH CAPOC Outlet 1 ATSOOH Trimis Outlet 1 ATSOOW Wall Outlet-36" AFF 1 A

Communication Notes - 17 ref pp 29-30 JULY 1988

Page 100: Army Medical Design Guide - SAFE

JULY 1988

Page 101: Army Medical Design Guide - SAFE

JULY 1988

Page 102: Army Medical Design Guide - SAFE

JULY 1988

Page 103: Army Medical Design Guide - SAFE

JULY 1988

Page 104: Army Medical Design Guide - SAFE

1.02.02 ATrauma Room - 2 TableMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 300 J.S.N. LogFinishes - Walls - CT Code Nomenclature Qty Cat - Base - ET - Floor - ET CE040 Cabinet, Wall Hung 2 A - Ceiling - GWT C02Q0 Cabinet U/C, Sink 1 ACeiling Ht - 9'-6" C04J0 Cabinet U/C, Base 1 ADoor Size & Type - 48A/18A C04L0 Cabinet U/C, Base 1 AHardware Set - H16 CS150 Sink, SS, Counter 1 AAmbient Noise Level - NC 30-35 CT030 Counter Top - P.L. 1 ASpeech Privacy Level - Confidential M3620 Dispenser, Paper Towel 2 A M4740 Light, Exam, Ceiling 2 A M5540 Patient SVC Column 2 A M7960 Track & Curtain, Cubicle 2 A M8000 IV Track 2 AArchitectural Notes - P6950 Scrub Sink w/Knee Control 1 A X3990 Illuminator, X-ray Film 2 A M4001 Otoscope/Ophthalmoscope 2 BELECTRICAL M4460 Sphygmomanometer 2 B F1938 Table, Treatment, ER 2 CAmbient Illum (FC) - 100 F2000 Waste Receptacle SS 2 CTask Illum (FC) - 100 M3051 Defibrillator w/ Cart 1 CLuminare Type - D1 M7400 Table, Instrument 2 CSwitching - Std By Area M7405 Pail 2 C M7410 Carriage 2 C M7415 Stand Mayo 2 C M7705 Stool Revolving 2 C

Electrical Notes - 8,34,38 ref pp 20-23

MECHANICAL

Total Air Changes - 12Outside Air Changes - 3Room Pressure (%) - + 10Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration (%) - 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - No M5540A - 1Chilled Water - No Waste/Vent - YesFloor Drain - No Steam - No Condensate - No

Piping Notes - 5 ref. pp. 16

COMMUNICATION PROGRAM

Commo Log

Page 105: Army Medical Design Guide - SAFE

Code Nomenclature Qty Cat

NC001 Single Patient Station 2 ANCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOKH CAPOC Outlet 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOH Trimis Outlet 2 ATSOOW Wall Outlet-36" AFF 1 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 106: Army Medical Design Guide - SAFE
Page 107: Army Medical Design Guide - SAFE
Page 108: Army Medical Design Guide - SAFE
Page 109: Army Medical Design Guide - SAFE
Page 110: Army Medical Design Guide - SAFE

1.02.03 AER Treatment CubicleMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 120 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT M3620 Dispenser, Paper Towel 2 A - Ceiling - ACT M4802 Light, Exam, Ceiling 3 ACeiling Ht - 8'-6" M5542J Patient SVC Column - ER 3 ADoor Size & Type - M7960 Track & Curtain, Cubicle 3 AHardware Set - M8000 IV Track 3 AAmbient Noise Level - NC 30-35 P3100 Lavatory, Wall Hung 2 ASpeech Privacy Level - Confidential P9145 Bath, Nursing Table 1 A M4001 Otoscope/Ophthalmoscope 3 BArchitectural Notes - M4460 Sphygmomanometer 3 B F1938 Table, Treatment, ER 3 C F2010 Waste Receptacle SS 3 CELECTRICAL Ambient Illum (FC) - 100Task Illum (FC) - 100Luminare Type - D1Switching - Multi-Sw

Electrical Notes - 8,34,38 ref pp 20-23

MECHANICAL

Total Air Changes - 12Outside Air Changes - 3Room Pressure (%) - + 10Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration (%) - 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5542J - 3Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref. pp. 16

COMMUNICATION PROGRAM

Commo Log Code Nomenclature Qty Cat

NCO01 Single Patient Station 3 ANCODL Dome Light - 3 Lamp 3 A

Page 111: Army Medical Design Guide - SAFE

PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOH Service Console Outlet - 54" AFF 3 ATSOOH Trimis Outlet 3 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 112: Army Medical Design Guide - SAFE

JULY 1988

Page 113: Army Medical Design Guide - SAFE

JULY 1988

Page 114: Army Medical Design Guide - SAFE

JULY 1988

Page 115: Army Medical Design Guide - SAFE

JULY 1988 1.02.04 A

Page 116: Army Medical Design Guide - SAFE

Central CommoMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A4020 Clock, Central System 1 A - Ceiling - ACT C0043 Drawer Unit, Single - 24" L 1 ACeiling Ht - 8-O C0044 Drawer Unit, Single - 30" L 1 ADoor Size & Type - 36G C0045 Drawer Unit, Single - 36" L 2 AHardware Set - H07 C06D0 Cabinet, U/C, Base 1 AAmbient Noise Level - NC 30-35 C06M0 Cabinet, U/C, Base 3 ASpeech Privacy Level - Normal C08F0 Cabinet, U/C, Base 1 A C09J0 Cabinet, U/C, Base 1 A CT030 Counter Top - P.L 1 A F3050 Chalkboard, WCP, 36X48 1 A F3000 Bulletin Board 1 A Architectural Notes - F0300 Chair, Rotary w/o Arms 4 C M4010 Radio Communications Equip. 1 C

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - )-Luminare Type - B1Switching - Std by Area

Electrical Notes - 8,36,39,43 ref. pp. 20-23

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature(F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes - 18 ref. pp. 13-15

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - No Commo LogHot Water - No Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-RA - 1 CCOOM Master Control Unit 1 AWaste/Vent - No CCOOW Wall Outlet 1 AFloor Drain - No FAOCP Main Control Panel 5 ASteam - No NCOOD Duty Station 1 ACondensate - No PAOOM Desk Microphone 1 A TLOMC Master Control Console 1 APiping Notes - 3 MDOOC Counter Outlet-6" Above CT 4 A ref. pp. 16 CTOOM Monitor Outlet 1 C

JULY 1988REVISED SEPTEMBER 1994

Page 117: Army Medical Design Guide - SAFE
Page 118: Army Medical Design Guide - SAFE
Page 119: Army Medical Design Guide - SAFE
Page 120: Army Medical Design Guide - SAFE
Page 121: Army Medical Design Guide - SAFE

1.02.05 ADecon ShowerMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 225 J.S.N. Log Code Nomenclature Qty CatFinishes - Walls - CT - Base - CT P9320 Floor Drain w/Primer 2 A - Floor - CT N/A Hand Held Shower - Ceiling - GW-SGCeiling Ht - 8'-0"Door Size & Type - 48AHardware Set - H08Ambient Noise Level - NC 35-40Speech Privacy Level - Not Critical

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 30Task Illum (FC) - ))Luminare Type - N1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(% - -20Temperature (F) - Sum 78 Win 70Relative Hum(%) - N/AExhaust Air - YesReturn Air - NoFiltration(%) - 25,0,0

Mechanical Notes - 17 ref pp 13-15

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No TLOWP Wall Outlet, WP-54" AFF 1 AWaste/Vent - YesFloor Drain - YesSteam - NoCondensate - No

Piping Notes - 10 ref pp 16JULY 1988

Page 122: Army Medical Design Guide - SAFE
Page 123: Army Medical Design Guide - SAFE
Page 124: Army Medical Design Guide - SAFE
Page 125: Army Medical Design Guide - SAFE
Page 126: Army Medical Design Guide - SAFE

1.02.06 AScreeningMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 60 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A - Ceiling - ACT A5115 Mirror, 18 x 30 1 ACeiling Ht - 8'-0" M1620 Record Holer 1 ADoor Size & Type - 36A P3100 Lavatory, Wall Hung 1 AHardware Set - H01 F0300 Chair, Rotary w/o Arms 1 CAmbient Noise Level - NC 30-35 F0640 Desk, Single Ped 1 CSpeech Privacy Level - Confidential F2095 Chair, Stacking 1 C M4025 Scale, Weighing 1 C M4100 Sphygmomanometer 1 CArchitectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - )-Luminare Type - A1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch, 3 Button 1 AFloor Drain - No MDOOD Desk Outlet-18" AFF 1 ASteam - NoCondensate - No

Piping Notes -

JULY 1988REVISED SEPTEMBER 1994

Page 127: Army Medical Design Guide - SAFE
Page 128: Army Medical Design Guide - SAFE
Page 129: Army Medical Design Guide - SAFE
Page 130: Army Medical Design Guide - SAFE
Page 131: Army Medical Design Guide - SAFE

1.04.01 AImmunization Room

Matrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT M0381 Record Holder 1 A - Ceiling - ACT M3150 Clock, Elapsed Time 1 ACeiling Ht - 8'-0" M3162 Clock, Electric 1 ADoor Size & Type - 48A M3620 Dispenser, Paper Towel 1 AHardware Set - H01 M5252 Medicine SVC Center 1 AAmbient Noise Level - NC 30-35 M7960 Track & Curtain, Cubicle 1 ASpeech Privacy Level - Confidential P3100 Lavatory, Wall Hung 1 A F0300 Chair, Rotary w/o Arms 1 C F0640 Desk. Single Ped 1 C F2010 Waste Receptacle SS 1 CArchitectural Notes - F2095 Chair, Stacking 1 C M3051 Defibrillator w,/ Cart 1 C M5325 Apparatus, Injection 1 C M7300 Table, Exam., SS 1 C M7400 Table, Instrument 1 C M7415 Stand Mayo 1 CELECTRICAL R6090 Refrigerator, Dual Temp 1 C

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A1Switching - Multi-Sw & Std by Area

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-2 - 1 CCOOW Wall Outlet 1 AWaste/Vent - Yes NCOEL Dome Light w/Chime 1 AFloor Drain - No NCOET Pullcord Station, Emer 1 ASteam - No PAOMO Ceiling Speaker-Music Only 1 ACondensate - No PAOOV Volume Control 1 A RSODL Indicator Light, 3 Lamp 1 APiping Notes - RSOSS Selector Switch, 3 Button 1 A TLOOD Desk Outlet-18" AFF 1 A TSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 132: Army Medical Design Guide - SAFE

JULY 1988

Page 133: Army Medical Design Guide - SAFE

JULY 1988

Page 134: Army Medical Design Guide - SAFE

JULY 1988

Page 135: Army Medical Design Guide - SAFE

JULY 1988

Page 136: Army Medical Design Guide - SAFE

1.05.01 AECG Testing/Work RmMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Testing - 125 (2) Work - 110

Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT (2) VCT - Ceiling - (1) ACT (2) ACT Ceiling Ht - (1) 8'-0" (2) 8'-0" Door Size Type - (1) 48A (2) 36AHardware Set - (1) H02 (2) H02Ambient Noise Level - NC 30-35Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 50Tad( Illum (FC) - (1) 100 (2) 100Luminare Type - (1) A1 (2) A1

Switching - (1) Std by Area (2) Std

Electrical Notes -

MECHANICAL

Total Air Changes - (1) 4 (2) 4Outside Air Change - (1) 1 (2) 1Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70

Relative Hum(%) - (1) 30-60 (2) 30-60

Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No MG-2 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No Piping Notes -

EQUIPMENT PROGRAM

Page 137: Army Medical Design Guide - SAFE

J.S.N LogCode Nomenclature Qty Cat

C0200 Cabinet, U/C, Sink 1 AC04E0 Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L 1 AM0381 Record Holder 1 AM3620 Dispenser, Paper Towel 2 AM5300 Mirror 14 x 20 1 AM5960 Coat Hook 2 AM7960 Track & Curtain, Cubicle 1 AP3100 Lavatory, Wall Hung 1 AF0300 Chair, Rotary w/o Arms 2 CF0405 Cabinet, Filing, 5 Drw C 1 CF0780 Table, Work 1 CF2000 Waste Receptacle, Off 1 CF2010 Waste Receptacle SS 1 CM4400 Electrocardiograph 1 CM7100 Table, Exam., Cab 1 C

COMMUNICATION PROGRAM

Commo LogCode Qty Cat

PAOMO Ceiling Speaker - Music Only 1 APAOOV Volume Control 1 ARSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch, 3 Button 1 ATLOOD Desk Outlet - 18" AFF 1 ATLOOK CAPOC Outlet 2 ATLOOW Wall Outlet - 54" AFF 1 ATSOOW Wall Outlet - 36" AFF 2 A

JULY 1988

Page 138: Army Medical Design Guide - SAFE

JULY 1988

Page 139: Army Medical Design Guide - SAFE

JULY 1988

1.05.01 D

Page 140: Army Medical Design Guide - SAFE

ECG Testing/Work Rm

JULY 1988

Page 141: Army Medical Design Guide - SAFE

1.05.01 E ECG Testing/Work Rm

JULY 1988

Page 142: Army Medical Design Guide - SAFE

1.05.02 ATreadmill RoomMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 150 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A4015 Clock, Elapsed Time 1 A - Ceiling - ACT A4020 Clock, Electric 1 ACeiling Ht - 9'- 0" A5080 Dispenser, Paper Towel 1 ADoor Size & Type - 48A A5115 Mirror 18 X 30 1 AHardware Set - H02 A5145 Coat Hook 2 AAmbient Noise Level - NC 35-40 M1620 Record Holder 1 ASpeech Privacy Level - Normal P3100 Lavatory, Wall hung 1 A F0300 Chair, Rotary w/o Arms 1 C F0640 Desk, Single Ped 1 C F2000 Waste Receptacle, Off 1 CArchitectural Notes - F2095 Chair, Stacking 1 C M7655 Defibrillator w/Cart 1 C M7705 Electrocardiograph 1 C M8830 Treadmill 1 C

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 50Luminare Type - C1Switching - Std

Electrical Notes -

MECHANICALTotal Air Changes - 4Outside Air Changes - 1Room Pressure(%) - -10Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAMCold Water - Yes Commo LogHot Water - Yes Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-3 - 1 CCOOW Wall Outlet 1 AWaste/Vent - Yes PAOMO Ceiling Speaker-Music Only 1 AFloor Drain - No PAOOV Volume Control 1 ASteam - No RSODL Indicator Light, 3 Lamp 1 ACondensate - No RSOSS Selector Switch, 3 Button 1 A MDOOD Desk Outlet-18" AFF 1 APiping Notes - MDOOW Wall Outlet - 48" AFF 1 AJULY 1988REVISED SEPTEMBER 1994

Page 143: Army Medical Design Guide - SAFE
Page 144: Army Medical Design Guide - SAFE
Page 145: Army Medical Design Guide - SAFE
Page 146: Army Medical Design Guide - SAFE
Page 147: Army Medical Design Guide - SAFE

1.06.01 APulmonary FunctionMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A - Ceiling - ACT A5115 Mirror 18 x 30 1 ACeiling Ht - 8'-0" A5145 Coat Hook 1 ADoor Size Typo - 36A M1620 Record Holder 1 AHardware Set - H01 P3100 Lavatory, Wall Hung 1 AAmbient Noise Level - NC 35-40 F0210 Chair Side 1 CSpeech Privacy Level - Normal F0300 Chair Rotary w/o Arms 2 C F0640 Desk, Single Ped 1 C M0720 Analyzer, Pulmonary 1 C

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - C1Switching - Std

Electrical Notes

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - -10Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration() - 25,0,0

Mechanical Notes

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-3 - 1 PAOMO Ceiling speaker-Music Only 1 AWaste/Vent - Yes PAOOV Volume Control 1 AFloor Drain - No RSODL Indicator Light, 3 lamp 1 ASteam - No RSOSS Selector Switch 3 button 1 ACondensate - No MDOOD Desk Outlet-18" AFF 1 A

Piping Notes -

JULY 1988REVISED SEPTEMBER 1994

Page 148: Army Medical Design Guide - SAFE
Page 149: Army Medical Design Guide - SAFE
Page 150: Army Medical Design Guide - SAFE
Page 151: Army Medical Design Guide - SAFE

1.07.01 A

Page 152: Army Medical Design Guide - SAFE

Proctoscopy SuiteMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Procto Area - 150 (2) Toilet - 30

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-6" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H02 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Confid (2) Normal

Architectural Notes - (1) 2 (2) 19 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 20Task Illum (FC) - (1) 100 (2) )-Luminare Type - (1) A2 (2) R1

Switching - (1) Std by Area (2) Std

Electrical Notes

MECHANICAL

Total Air Changes - (1) 6 (2) 10Outside Air Changes - (1) 1.5 (2) )-Room Pressure(%) - (1) (2) - 100Temperature (F) - (1) Sum 78 Win 70 (2) Sum )- Win )-

Relative Hum(%) - (1) 30-60 (2) ))Exhaust Air - (1) Yes (2) YesReturn Air - (1) No (2) NoFiltration(%) - (1) 25,0,0 (2) ))

Mechanical Notes - (2) 6 ref. pp. 20-23

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No MG-2 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

Page 153: Army Medical Design Guide - SAFE

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty CatC02QO Cabinet, U/C Sink 1 AC04EO Cabinet, U/C Base 1 AC04JO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 2 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM0381 Record Holder 1 AM3620 Dispenser, Paper Towel 2 AM3800 Desk, Folding, Wall Mount 1 AM4600C Grab Bar, Toilet-36"x48" 1 AM4740 Light, Exam, Ceiling 1 AM5300 Mirror 14 X 20 1 AM5960 Coat Hook 2 AM7960 Track & Curtain, Cubicle 1 AP3000 Lavatory, Wall Hung 1 AP9050 Water Closet 1 AX3990 Illuminator, X-ray Film 1 AM4460 Sphygmomanometer 1 BF2010 Waste Receptacle SS 1 CM3051 Defibrillator w/Cart 1 CM7366 Table, Exam, Procto 1 CM7400 Table, Instrument 1 CM7415 Stand, Mayo 1 CM7705 Stool, Revolving 1 C

COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty Cat

NCOEL Dome Light W/Chime 2 ANCOET Pullcord Station, Emer 2 APAOMO Ceiling Speaker-Music Only 1 APAOOV Volume Control 1 ARSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch, 3 Button 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 154: Army Medical Design Guide - SAFE

JULY 1988

Page 155: Army Medical Design Guide - SAFE

JULY 1988

Page 156: Army Medical Design Guide - SAFE

JULY 1988

Page 157: Army Medical Design Guide - SAFE

JULY 1988

Page 158: Army Medical Design Guide - SAFE

1.08.01 AWeights & MeasuresMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A - Ceiling - ACT A5115 Mirror 18 x 30 1 ACeiling Ht - 8'-0" A5145 Coat Hook 2 ADoor Size & Type - 36A A5180 Track & Curtain, Cubicle 1 AHardware Set - H01 M1620 Record Holder 1 AAmbient Noise Level - NC 30-35 P3100 Lavatory, Wall hung 1 ASpeech Privacy Level - Confidential F0210 Chair, Side 1 C F0300 Chair, Rotary w/o Arms 1 C F0640 Desk, Single Ped 1 C F1907 Table, Equip. Hold 1 CArchitectural Notes - M4010 Scale, Infant 1 C M4040 Scale, Weighing 1 C M4100 Sphygmomanometer 1 CELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A2Switching - Std

Electrical Notes

MECHANICALTotal Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature(F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) -25,0,0

Mechanical Notes

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch 3 Button 1 AFloor Drain - No MDOOD Desk Outlet-18" AFF 1 ASteam - No MDOOW Wall Outlet-48" AFF 1 ACondensate - No

Piping Notes -

JULY 1988REVISED SEPTEMBER 1994

Page 159: Army Medical Design Guide - SAFE
Page 160: Army Medical Design Guide - SAFE
Page 161: Army Medical Design Guide - SAFE

1.10.01 AEEG Testing/Work RmMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Work - 130 (2) Testing - 90

Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT(2)VCT - Ceiling - (1) ACT(2)ACTCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 30A,36A(2) 48AHardware Set - (1) H02(2) H02Ambient Noise Level - NC 25-30Speech Privacy Level - Confidential

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - (1) 70 (2) 0-20Task Illum (FC) - )) (2) 100Luminare Type - (1) A1 (2) A1

Switching - (1) Multi-Sw (2) Dim

Electrical Notes - (1) 20 (2) 9,20 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 4Outside Air Changes - (1) 1 (2) 1Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70

Relative Hum(%) - (1) 30-60 (2) 30-60

Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0

Mechanical Notes

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No (2) MG-2 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 162: Army Medical Design Guide - SAFE

Piping Note -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0200 Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L 1 AM0381 Record Holder 1 AM3620 Dispenser, Paper Towel 2 AM5300 Mirror 14 X 20 1 AM5960 Coat Hook 1 AP3100 Lavatory, Wall Hung 1 AF0105 Bed Hospital, Manual 1 CF0300 Chair, Rotary w/o Arms 1 CF0405 Cabinet, Filing, 5 Drw 1 CF0780 Table, Work 1 CF2000 Waste Receptacle, Off 2 CM3702 Electroencephalograph 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

RSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch, 3 Button 1 ATLOOW Wall Outlet-54" AFF 2 ATSOOW Wall Outlet-36" AFF 2 A

JULY 1988

Page 163: Army Medical Design Guide - SAFE

JULY 1988

Page 164: Army Medical Design Guide - SAFE

JULY 1988

Page 165: Army Medical Design Guide - SAFE

JULY 1988

Page 166: Army Medical Design Guide - SAFE

JULY 1988

1.11.01 A

Page 167: Army Medical Design Guide - SAFE

Cast RoomMatrix DataARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 280 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - IV - Floor - SV C03EO Cabinet, U/C, Base 3 A - Ceiling - ACT C03JO Cabinet, U/C. Base 2 ACeiling Ht - 8'-6" C04PO Cabinet, U/C, Sink 1 ADoor Size & Type - 36G,18G CE030 Cabinet, Wall Hung 2 AHardware Set - H05 CE080 Cabinet, Wall Hung 1 AAmbient Noise Level - NC 30-35 CS190 Sink, SS, Counter 1 ASpeech Privacy Level - Non-Critical CT030 Counter Top - P.L 3 A M0381 Record Holder 1 A M3620 Dispenser, Paper Towel 1 A M7960 Track & Curtain, Cubicle 2 AArchitectural Notes - 6 P7600 Plaster Trap 1 A ref. pp. 5-6 X3830 Illuminator, X-ray Film 2 A M2020 Trashcan, Mobile 1 C M4700 Light, Exam, Mobile 1 C M6200 Cast Cutter/Vacuum 2 C M7300 Table Exam., SS 2 CELECTRICAL M7400 Table Instrument 2 C M7415 Stand Mayo 2 CAmbient Illum (FC) - 50Task Illum (FC) - 50Luminare Type - C1Switching - Std by Area

Electrical Notes -

MECHANICALTotal Air Changes - 10 LogOutside Air Changes - 1.5 CatRoom Pressure(%) - - 10 ATemperature (F) - Sum 78 Win 70 ARelative Hum(%) - 30-60 AExhaust Air - Yes AReturn Air - No AFiltration(%) - 25,0,0 A

Mechanical Notes -MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo Log Hot Water - Yes Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-2 - 1 PAOMO Ceiling Speaker-Music Only 2 AWaste/Vent - Yes PAOOV Volume Control 1 AFloor Drain - No RSODL Indicator Light, 3 Lamp 1 ASteam - No RSOSS Selector Switch, 3 Button 1 ACondensate - No TLOOW Wall Outlet-54" AFF 1 A TSOOW Wall Outlet-36" AFF 1 APiping Note - 4 ref. pp. 16JULY 1988

Page 168: Army Medical Design Guide - SAFE

JULY 1988

Page 169: Army Medical Design Guide - SAFE

JULY 1988

Page 170: Army Medical Design Guide - SAFE

JULY 1988

Page 171: Army Medical Design Guide - SAFE

JULY 1988

Page 172: Army Medical Design Guide - SAFE

1.12.01 AENT Exam RoomMatrix DataARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A - Ceiling - ACT A5115 Mirror 18 X 30 1 ACeiling Ht - 8'-0" A5145 Coat Hook 2 ADoor Size & Type - 36A A5180 Track & Curtain, Cubicle 1 AHardware Set - H01 M1620 Record Holder 1 AAmbient Noise Level - NC 30-35 P3100 Lavatory, Wall Hung 1 ASpeech Privacy Level - Confidential X3830 Illuminator, X-ray Film 1 A F0300 Chair, Rotary w/o Arms 1 C F0695 Work Station, Computer 1 C F2010 Waste Receptacle SS 1 CArchitectural Notes - M4915 Chair, Exam 1 C M5510 Cabinet, ENT 1 C M7425 Light, Exam, Mobile 1 C M8540 Microscope ENT 1 C M8945 Stool, Revolving 1 CELECTRICALAmbient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A2Switching - Std

Electrical Notes -

MECHANICALTotal Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAMCold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch, 3 Button 1 AFloor Drain - No MDOOD Wall Outlet-18" AFF 1 ASteam - No MDOOW Wall Outlet-48" AFF 1 ACondensate - No

Piping Notes -

JULY 1988REVISED SEPTEMBER 1994

Page 173: Army Medical Design Guide - SAFE
Page 174: Army Medical Design Guide - SAFE
Page 175: Army Medical Design Guide - SAFE

1.12.02 AAudio Testing (Sm)Matrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 110 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT M0300 Audiometric Booth 2 A - Ceiling - ACT M0381 Record Holder 1 ACeiling Ht - 9'-0" M5960 Coat Hook 1 ADoor Size & Type - 48A F0300 Chair, Rotary w/o Arms 1 CHardware Set - H01 F0780 Table, Equipment 1 CAmbient Noise Level - NC 35-40 F2000 Waste Receptacle, Off 1 CSpeech Privacy Level - Non-Critical F2095 Chair, Stacking 1 C M0255 Audiometer 1 CArchitectural Notes - 3 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) -Luminare Type - C1Switching - Std

Electrical Notes - 27 ref. pp. 20-23

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration() - 25,0,0

Mechanical Notes -10 ref. pp. 13-15

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - No Commo LogHot Water - No Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - No RSOSS Selector Switch, 3 Button 1 AFloor Drain - No TLOOD Desk Outlet-18" AFF 1 ASteam - No TSOOW Wall Outlet-36" AFF 1 ACondensate - No

Piping Notes -

JULY 1988

Page 176: Army Medical Design Guide - SAFE

JULY 1988

Page 177: Army Medical Design Guide - SAFE

JULY 1988

Page 178: Army Medical Design Guide - SAFE

JULY 1988

Page 179: Army Medical Design Guide - SAFE

JULY 1988

Page 180: Army Medical Design Guide - SAFE

1.12.03 AAudio Testing (Lg)Matrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT M0250 Audiometer Testing Rm 1 A - Ceiling - ACT M0381 Record Holder 1 ACeiling Ht - 9'-0" F0255 Chair, Easy 1 CDoor Size & Type - 48A F0300 Chair, Rotary w/o Arms 1 CHardware Set - H01 F0780 Table, Equipment 1 CAmbient Noise Level - NC 35-40 F2000 Waste Receptacle, Off 1 CSpeech Privacy Level - Non-Critical M0255 Audiometer 1 C

Architectural Notes - 3 ref. pp. 5-6ELECTRICAL

Ambient Illum (FC) - 20Task Illum (FC) -Luminare Type - R1Switching - Std

Electrical Notes - 27 ref. pp . 20-23

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room (%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes - 10 ref. pp. 13-15

MECHANICAL PIPING COMMUNICATION PROGRAMCold Water - No Commo LogHot Water - No Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - No RSOSS Selector Switch 3 Button 1 AFloor Drain - No TLOOW Wall Outlet-54" AFF 1 ASteam - No TSOOW Wall Outlet-36" AFF 1 ACondensate - NoPiping Notes -

Communication Notes - 16 ref. pp. 29- 30

JULY 1988

Page 181: Army Medical Design Guide - SAFE

JULY 1988

Page 182: Army Medical Design Guide - SAFE

JULY 1988

Page 183: Army Medical Design Guide - SAFE

JULY 1988

Page 184: Army Medical Design Guide - SAFE

JULY 1988

Page 185: Army Medical Design Guide - SAFE

1.13.01 AOphthalmology ExamMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 160 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A - Ceiling - ACT A5115 Mirror 18 x 30 1 ACeiling Ht - 8'-0" A5145 Coat Hook 1 ADoor Size & Type - 36A M1620 Record Holder 1 AHardware Set - H01 P3100 Lavatory, Wall Hung 1 AAmbient Noise Level - NC 30-35 F0300 Chair, Rotary w/o Arms 1 CSpeech Privacy Level - Confidential F0695 Work Station, Computer 1 C F2010 Waste Receptacle SS 1 C F2095 Chair, Stacking 1 C M5005 Cabinet, Instrument Lens 1 CArchitectural Notes - M5030 Stool Optical Lens 1 C M5560 Projector w/Screen 1 C M5600 Phoropter w/Chair 1 C

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 0-20Luminare Type - A1,SSwitching - Std, Dimmer

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch, 3 Button 1 AFloor Drain - No MDOOD Desk Outlet-18" AFF 1 ASteam - NoCondensate - NoPiping Notes -JULY 1988REVISED SEPTEMBER 1994

Page 186: Army Medical Design Guide - SAFE
Page 187: Army Medical Design Guide - SAFE
Page 188: Army Medical Design Guide - SAFE
Page 189: Army Medical Design Guide - SAFE
Page 190: Army Medical Design Guide - SAFE

1.13.02 AEye Lane/OfficeMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 195 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 2 A - Ceiling - ACT A5115 Mirror 18 X 30 2 ACeiling Ht - 8'-0" A5145 Coat Hook 2 ADoor Size & Type - 36A M1620 Record Holder 2 AHardware Set - H01 P3100 Lavatory, Wall Hung 2 AAmbient Noise Level - NC 30-35 F0210 Chair, Side 2 CSpeech Privacy Level - Confidential F0280 Chair, Rotary w/Arms 2 C F0635 Desk, Double Ped 2 C F2000 Waste Receptacle, Off 2 C M0685 Cabinet, Instrument, Lens 2 CArchitectural Notes - M5030 Stool, Optical 2 C M5560 Projector w/Screen 2 C M5600 Phoropter w/Chair 2 C

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 0-20Luminare Type - B1,SSwitching - Std, Dimmer

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 2 A

Page 191: Army Medical Design Guide - SAFE

Waste/Vent - Yes RSOSS Selector Switch, 3 Button 2 AFloor Drain - No MDOOD Desk Outlet-18" AFF 2 ASteam - No Condensate - No

Piping Notes -

JULY 1988REVISED SEPTEMBER 1994

Page 192: Army Medical Design Guide - SAFE
Page 193: Army Medical Design Guide - SAFE
Page 194: Army Medical Design Guide - SAFE
Page 195: Army Medical Design Guide - SAFE
Page 196: Army Medical Design Guide - SAFE

1.13.03 AOphthalmic Photo RmMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT C02QO Cabinet, U/C, Sink 1 A -Ceiling - ACT C03EO Cabinet, U/C Base 1 ACeiling Ht - 8'-0" C03JO Cabinet, U/C Base 1 ADoor Size & Type - 36A CE030 Cabinet, Wall Hung 2 AHardware Set - H01 CS140 Sink, SS, Counter 1 AAmbient Noise Level - NC 30-35 CT030 Counter Top - P.L. 1 ASpeech Privacy Level - Confidential M0381 Record Holder 1 A M3620 Dispenser, Paper Towel 1 A M3800 Desk, Folding, Wall Mount 1 A M5960 Coat Hook 1 AArchitectural Notes - F0300 Chair, Rotary w/o Arms 1 C F2010 Waste Receptacle SS 1 C M0650 Camera, Fundus 1 C M7715 Stool, Lab 1 C

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) -Luminare Type - A1Switching - Std by Area

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty Cat

Page 197: Army Medical Design Guide - SAFE

Treated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch, 3 Button 1 AFloor Drain - No TLOOW Wall Outlet-54" AFF 1 ASteam - No TSOOW Wall Outlet-36" AFF 1 ACondensate - No

Piping Notes -

JULY 1988

Page 198: Army Medical Design Guide - SAFE

JULY 1988

Page 199: Army Medical Design Guide - SAFE

JULY 1988

Page 200: Army Medical Design Guide - SAFE

JULY 1988

Page 201: Army Medical Design Guide - SAFE

JULY 1988

Page 202: Army Medical Design Guide - SAFE

1.14.01 APrev Medicine LabMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAMSquare Foot Area Net - 250 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A - Ceiling - ACT A5145 Coat Hook 1 ACeiling Ht - 8'- 0" C01D0 Cabinet, U/C, Base 1 ADoor Size & Type - 36G C02D0 Cabinet, U/C, Base 1 AHardware Set - H03 C03J0 Cabinet, U/C, Base 1 AAmbient Noise Level - NC 30-35 C04E0 Cabinet, U/C, Base 2 ASpeech Privacy Level - Normal C04J0 Cabinet, U/C, Base 1 A C04P0 Cabinet, U/C, Sink 1 A C07C0 Cabinet, U/C, Base 1 A C06M0 Cabinet, U/C, Base 1 AArchitectural Notes - CD030 Cabinet, Wall Hung 2 A CD040 Cabinet, Wall Hung 2 A CS120 Sink, SS, Counter 1 A CS200 Sink, SS, Counter 1 A CT080 Counter Top - Epoxy 2 A L2320M Fume Hood, Accessible 1 A F2010 Waste Receptacle SS 1 C F0340 Stool, Self Adjusting w/ 2 C Lockable Height L8130 Incubator, Floor 1 C R7000 Refrigerator 1 CELECTRICAL Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - B1Switching - Std by Area

Electrical Notes - 42 ref. pp . 20-23MECHANICALTotal Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - -10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,0

Mechanical Notes -MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes MG-25 - 2 Commo LogHot Water - Yes MG-26 - 1 Code Nomenclature Qty CatTreated Water - NoChilled Water - No MDOOC Counter Outlet-6" Above CT 3 AWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - NoPiping Notes -JULY 1988REVISED SEPTEMER 1994

Page 203: Army Medical Design Guide - SAFE
Page 204: Army Medical Design Guide - SAFE
Page 205: Army Medical Design Guide - SAFE
Page 206: Army Medical Design Guide - SAFE
Page 207: Army Medical Design Guide - SAFE

1.15.01 AMirror RoomMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 110 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - CPT M7960 Track & Curtain, Cubicle 1 A - Ceiling - ACT F0255 Chair, Easy 4 CCeiling Ht - 8'-0" F0725 Table, Waiting Rm 2 CDoor Size & Type - 36A F1907 Table, Equip. Hold 1 CHardware Set - H01Ambient Noise Level - NC 30-35Speech Privacy Level - Confidential

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 0-20Task Illum (FC) -Luminare Type - SSwitching - Dim

Electrical Notes - 11,37 ref. pp. 20-23

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure (%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - No Commo LogHot Water - No Code Nomenclature Qty CatTreated Water - NoChilled Water - No PAOLA Local Amplifier 2 AWaste/Vent - No TLOOW Wall Outlet-54" AFF 1 AFloor Drain - No TSOOW Wall Outlet-36 AFF 1 ASteam - NoCondensate - No

Piping Notes -

JULY 1988

Page 208: Army Medical Design Guide - SAFE

JULY 1988

Page 209: Army Medical Design Guide - SAFE

JULY 1988

Page 210: Army Medical Design Guide - SAFE

JULY 1988

Page 211: Army Medical Design Guide - SAFE

JULY 1988

Page 212: Army Medical Design Guide - SAFE

1.15.02 AGroup TherapyMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - GW-VWF Code Nomenclature Qty Cat - Base - R - Floor - CPT M3100 Chalkboard-Tackboard, Comb. 1 A -Ceiling - ACT M7965 Drapery Track 1 ACeiling Ht - 8'-0" F0220 Chair, Conference 5 CDoor Size & Type - 36A F0255 Chair, Easy 5 CHardware Set - H01 F0725 Table, End 2 CAmbient Noise Level - NC 30-35 F0825 Table, Round 1 CSpeech Privacy Level - Confidential

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 0-30Task Illum (FC) - )-Luminare Type - B1Switching - Std-Dim

Electrical Notes - 11.37 ref. pp. 20-23

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - No Commo LogHot Water - No Code Nomenclature Qty CatTreated Water - NoChilled Water - No PAOCM Microphone, Ceiling Mounted 1 AWaste/Vent - No PAOMO Ceiling Speaker-Music Only 2 AFloor Drain - No PAOOV Volume Control 1 ASteam - No TLOOW Wall Outlet-54" AFF 1 ACondensate - No TVOOD Wall Outlet-18" AFF 1 A

Piping Notes -

JULY 1988

Page 213: Army Medical Design Guide - SAFE

JULY 1988

Page 214: Army Medical Design Guide - SAFE

JULY 1988

Page 215: Army Medical Design Guide - SAFE

JULY 1988

Page 216: Army Medical Design Guide - SAFE

JULY 1988

Page 217: Army Medical Design Guide - SAFE

1.15.03 APsych Play TherapyMatrix Data

ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM

Square Foot Area Net - 150 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - CPT M1530 Chalkboard 1 A - Ceiling - ACT M1860 Bulletin Board 1 ACeiling Ht - 8'-0" M3620 Dispenser, Paper Towel 1 ADoor Size & Type - 36A M7965 Drapery Track 1 AHardware Set - H01 P3650 Lavatory, Wall Hung, Ped. 1 AAmbient Noise Level - NC 30-35 F0215 Chair, Child 8 CSpeech Privacy Level - Normal F2000 Waste Receptacle, Off 2 C

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 0-30Task Illum (FC) - )-Luminare Type - C1Switching - Std-Dim

Electrical Notes - 11,37 ref. pp. 20-23

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure((%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING COMMUNICATION PROGRAM

Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No PAOCM Microphone, Ceiling Mounted 1 AWaste/Vent - Yes TLOOW Wall Outlet-54" AFF 1 AFloor Drain - No TVOOD Wall Outlet-18" AFF 1 ASteam - NoCondensate - No

Piping Notes -

JULY 1988

Page 218: Army Medical Design Guide - SAFE

JULY 1988

Page 219: Army Medical Design Guide - SAFE

JULY 1988

Page 220: Army Medical Design Guide - SAFE

JULY 1988

Page 221: Army Medical Design Guide - SAFE

JULY 1988

Page 222: Army Medical Design Guide - SAFE

1.16.01 AWhirlpool AreaMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Extremity - 80 (2) Lowboy - 90 (3) Treatment - 120 (4) Wk. Sta. - 60Finishes - Walls - (1) CT (2) CT (3) CT (4) CT - Base - (1) OT (2) QT (3) QT (4) QT - Floor - (1) OT (2) QT (3) QT (4) QT - Ceiling - (1) GW-SG (2) GW-SG (3) GW-SG (4) GW-SGCeiling Ht - 8'-6"Door Size & Type - 48AHardware Set - H04Ambient Noise Level - (1) NC 30-35 (2) NC 30-35 (3) NC 30-35 (4) NC 30-35Speech Privacy Level - (1) Confidential (2) Confidential (3) Confidential (4) ConfidentialArchitectural Notes -

ELECTRICAL

Ambient Illum (FC) - (1) 20 (2) 20 (3) 20 (4) 20Task Illum (FC) - (1) )- (2) )- (3) )- (4) )-Luminare Type - (1) B1 (2) B1 (3) B1 (4) B1Switching - (1) Std-by Area (2) Std-by Area (3) Std-by Area (4) Std-by Area

Electrical Notes - 22 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 6 (3) 6 (4) 6Outside Air Changes - (1) 1.5 (2) 1.5 (3) 1.5 (4) 1.5Room Pressure(%) - (1) 0 (2) 0 (3) 0 (4) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70 (3) Sum 78 Win 70 (4) Sum 78 Win 70Relative Hum(%) - (1) 30-60 (2) 30-60 (3) 30-60 (4) 30-60Exhaust Air - (1) Yes (2) Yes (3) Yes (4) YesReturn Air - (1) No (2) No (3) No (4) NoFiltration(%) - (1) 25,0,0 (2) 25,0,0 (3) 25,0,0 (4) 25,0,0Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-2 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - No

Page 223: Army Medical Design Guide - SAFE

Condensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CE030 Cabinet, Wall Hung 1 ACE040 Cabinet, Wall Hung 1 AC02QO Cabinet, U/C Sink 1 AC03EO Cabinet, U/C Base 1 AC04EO Cabinet, U/C, Base 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 ACW140 Cabinet, Full Height 1 AM1000 Bath, Whirlpool, Arm 1 AM1250 Bath, Whirlpool, Leg 1 AM1260 Bath, Whirlpool, Hip 1 AM3620 Dispenser, Paper Towel 1 AM7960 Track & Curtain, Cubicle 5 AP9560 Cleaner, Whirlpool 3 AR4760 Ice Maker 1 AF2010 Waste Receptacle SS 2 CM1095 Lamp Infra-Red 1 CM1295 Chair, Hydrotherapy 2 CM1297 Stool, PT 3 CM2101 Generator, Ultrasonic 1 CM4500 Hamper, Linen 1 CM7105 Table, Treatment, PT 1 CM7415 Stand Mayo 1 CM7510 Table, Instrument 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOEL Dame Light w/o Chime 4 ANCOES Pullcord Station-WP, Shower 4 ANCOZL Zone Indicator Light 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 4 ATLOOW Wall Outlet-54" AFF 1 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 224: Army Medical Design Guide - SAFE

JULY 1988

Page 225: Army Medical Design Guide - SAFE

JULY 1988

Page 226: Army Medical Design Guide - SAFE

JULY 1988

Page 227: Army Medical Design Guide - SAFE

JULY 1988

Page 228: Army Medical Design Guide - SAFE

1.16.02 ABurn Tank RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 235Finishes -Walls - CT - Base - QT - Floor - QT - Ceiling - GW-SGCeiling Ht - 8'-6"Door Size & Type - 48AHardware Set - H02Ambient Noise Level - NC 35-40Speech Privacy Level - Confidential

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - )-Luminare Type - N1Switching - Multi-Sw

Electrical Notes - 22 ref pp 20-23

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure (%) - +10Temperature F - Sum 95 Win 75Relative Hum(%) - 50-80Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,90/95

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CW040 Cabinet, Full Height 1 AM1290 Bath, Hydro-Burn 1 AM3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3620 Dispenser, Paper Towel 1 AM7960 Track & Curtain, Cubicle 1 A

Page 229: Army Medical Design Guide - SAFE

P3100 Lavatory, Wall Hung 1 AF0355 Foot Stool 2 CF2010 Waste Receptacle SS 2 CM4500 Hamper, Linen 1 CM7300 Table, Exam., SS 1 CM7415 Stand Mayo 2 CM7510 Table, Instrument 2 CM7705 Stool, Revolving 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOEL Dame Light w/ Chime 1 ANCOEC Pullcord Station, Ceiling 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 230: Army Medical Design Guide - SAFE

JULY 1988

Page 231: Army Medical Design Guide - SAFE

JULY 1988

Page 232: Army Medical Design Guide - SAFE

JULY 1988

Page 233: Army Medical Design Guide - SAFE

JULY 1988

Page 234: Army Medical Design Guide - SAFE

1.16.03 APhys Ther TreatmentMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net (1) Cubicle - 120 (2) Workstation - 60 (One per 2 Cubicles)Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT (2) VCT - Ceiling - (1) ACT (2) ACTCeiling Ht - (1) 8'-0" (2) 8'-0"Door Size & Type -Hardware Set -Ambient Noise Level - (1) NC 35-40 (2) NC 35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 50Task Illum (FC) - (1) )) (2) ))Luminare Type - (1) E1,R1 (2) A1 ,B1Switching - (1) Std-by Area (2) Std

Electrical Notes - 24 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 6Outside Air Changes - (1) 1.5 (2) 1.5Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70Relative Hum(%) - (1) 30-60 (2) 30-60Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

Page 235: Army Medical Design Guide - SAFE

C02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C Base 1 AC04JO Cabinet, U/C Base 1 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 ACW140 Cabinet, Full Height 1 AM3620 Dispenser, Paper Towel 1 AM7960 Track & Curtain, Cubicle 3 AF2010 Waste Receptacle SS 3 CM1297 Stool, PT 3 CM2080 Heater, Heat Treatment 3 CM2100 Cold Therapy Apparatus 3 CM2101 Generator, Ultrasonic 6 CM3360 Diathermy, Shortwave 3 CM7105 Table, Treatment, PT 3 CR5135 Freezer U/C 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOEL Dome Light w/o Chime 3 ANCOET Pullcord Station, Toilet 3 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOC Counter Outlet-6" Above 1 A

JULY 1988

Page 236: Army Medical Design Guide - SAFE

JULY 1988

Page 237: Army Medical Design Guide - SAFE

JULY 1988

Page 238: Army Medical Design Guide - SAFE

JULY 1988

Page 239: Army Medical Design Guide - SAFE

JULY 1988

Page 240: Army Medical Design Guide - SAFE

1.16.04 ADaily Living SkillsMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Living - 320 (2) Bathroom - 80Finishes - Walls - (1) GW (2) CT - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"Door Size & Type - (1) 36A (2) 36AHardware Set - (1) H03 (2) H13Ambient Noise Level - (1) NC 25-0 (2) )-Speech Privacy Level - (1) Normal (2) )-

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) 30 (2) )-Luminare Type - (1) A1,B1 (2) C1,P2Switching - (1) (2) Std-by Area

Electrical Notes -

MECHANICAL

Total Air Changes - (1) 4.0 (2) 10.0Outside Air Changes - (1) 1.0 (2) 0.0Room Pressure - (1) -10 (2) -100Temperature (F) - (1) Sum 78 Win 68 (2) Sum )) Win ))Relative Hum(%) - (1) 30-60 (2) N/AExhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(S) - (1) 25,0,0 (2) 0,0,0

Mechanical Notes - (1) 16 (2) 6 ref pp 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWater/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A5045 Cabinet, Comb., CRS, 1 Shelf 1 AA5110C Grab Bar, Toilet-36"x 48" 1 A

Page 241: Army Medical Design Guide - SAFE

A5110H Grab Bar, Toilet-36"x 48" 1 AA5110J Grab Bar, Toilet-36"x 48" 1 AA5145 Coat Hook 1 AA5170 Shower Curtain and Rod 1 AA5175 Soap Dish w/ Grab Bar 1 AA5195 Toilet Paper Holder, Surface 1 AA5205 Bar, Towel, 1" Diameter 2 AC01D0 Cabinet, U/C, Base 1 AC02D0 Cabinet, U/C, Base 1 AC02C0 Cabinet, U/C, Base 1 AC02D0 Cabinet, U/C, Base 2 AC03E0 Cabinet, U/C, Base 1 AC03P0 Cabinet, U/C, Sink 1 ACD030 Cabinet, Wall Hung 5 ACD040 Cabinet, Wall Hung 3 ACS050 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 3 AK2515 Dishwasher 1 AK4500 Range w/Oven & Hood 1 AP0700 Bath Tub 1 AP3070 Lavatory, Counter 1 AP5100 Shower 3' x 3' 1 AP9050H Water Closet 1 AF0260 Chair, Side 2 CF0375 Sofa-6' 1 CF0460 Washer, Household 1 CF0725 Table, Waiting Room 2 CF2010 Waste Receptacle SS 1 CM0465 Dryer, Household 1 CR7000 Refrigerator 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOEL Emer Dome Light w/Chime 2 ANCOES Pullcord Station-WP, Shower 2 ANCOET Pullcord Station 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 AMDOOD Desk Outlet-18" AFF 1 AMDOOW Wall Outlet-48" AFF 1 ATVOOD Wall Outlet-18" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 242: Army Medical Design Guide - SAFE
Page 243: Army Medical Design Guide - SAFE
Page 244: Army Medical Design Guide - SAFE
Page 245: Army Medical Design Guide - SAFE
Page 246: Army Medical Design Guide - SAFE

1.17.01 AOral SurgeryMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 115Finishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - ACTCeiling Ht - 8'-6"Door Size & Type - 48AHardware Set - H02Ambient Noise Level - NC 30-35Speech Privacy Level - Confidential

Architectural Notes - 17 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 100Task Illum (FC) - 150Luminare Type - A2Switching - Multi-Sw

Electrical Notes - 8,10 ref pp 20-23

MECHANICAL

Total Air Changes - 12.0Outside Air Changes - 3.0Room Pressure(%) - + 20Temperature (F) - 68-76Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,90-95

Mechanical Notes - 7 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-19 - 1Chilled Water - No Utility Center - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 8 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A1130 Control Cabinet, Nitrogen 1 AA4015 Clock, Elapsed Time 1 A

Page 247: Army Medical Design Guide - SAFE

A4020 Clock 1 AA5080 Dispenser, Paper Towel 2 AA5115 Mirror 18 X 30 2 AA5145 Coat Hook 1 AD0810 Sink, Dental, S.S. 2 AD9250 Apron Rail, Length-A.R. 2 AD9280 Legs, Apron Rail 2 AD9400 Cabinet, Wall Hung 1 AD9420 Cabinet, Wall Hung 1 AD9540 Base Unit, Single Swing Door 2 AD9940 Counter Top - P.L. 2 AM1620 Record Holder 1 AX3830 Illuminator, X-ray Film 1 AD3320 Chair, Dental Operating 1 9D8250 Operating Unit, Dental 1 BD3390 Stool, Dental 2 CD9030 Cabinet, Mobile, Dental 1 CF2010 Waste Receptacle SS 2 CD6050 Light, Dental Operating 1 E

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet-54" AFF 2 AMDOOC Counter Outlet-6" Above 1 AMDOOW Wall Outlet-48" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 248: Army Medical Design Guide - SAFE
Page 249: Army Medical Design Guide - SAFE
Page 250: Army Medical Design Guide - SAFE
Page 251: Army Medical Design Guide - SAFE
Page 252: Army Medical Design Guide - SAFE

1.17.02 AOral Surgery w/X-rayMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 115Finishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - ACTCeiling Ht - 8'-6"Door Size & Type - 48AXHardware Set - H15Ambient Noise Level - NC 30-35Speech Privacy Level - Confidential

Architectural Notes - 17 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 100Task Illum (FC) - 150Luminare Type - A2Switching - Multi--Sw

Electrical Notes - 8,10 ref pp 20-23

MECHANICAL

Total Air Changes - 12.0Outside Air Changes - 3.0Room Pressure(%) - + 20Temperature (F) - 68-76Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,90-95

Mechanical Notes - 7 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-19 - 1Chilled Water - No Utility Center - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 8 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A1130 Control Cabinet, Nitrogen 1 AA4015 Clock, Elapsed Time 1 AA4020 Clock 1 A

Page 253: Army Medical Design Guide - SAFE

A5080 Dispenser, Paper Towel 2 AA5115 Mirror 18 X 30 2 AA5145 Coat Hook 1 AD0810 Sink, Dental, S.S. 2 AD9250 Apron Rail, Length-A.R. 2 AD9280 Legs, Apron Rail 2 AD9400 Cabinet, Wall Hung 1 AD9420 Cabinet, Wall Hung 1 AD9540 Base Unit, Single Swing Door 2 AD9940 Counter Top - P.L. 2 AM1620 Record Holder 1 AX3830 Illuminator, X-ray Film 1 AD3320 Chair, Dental Operating 1 BD8250 Operating Unit, Dental 1 BD3390 Stool, Dental 2 CD9030 Cabinet, Mobile, Dental 1 CF2010 Waste Receptacle SS 2 CD6050 Light, Dental Operating 1 EX6450 X-ray Unit, Dental-15 1 F

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet-54" AFF 2 AMDOOC Counter Outlet-6" Above 1 AMDOOW Wall Outlet-48" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 254: Army Medical Design Guide - SAFE
Page 255: Army Medical Design Guide - SAFE
Page 256: Army Medical Design Guide - SAFE
Page 257: Army Medical Design Guide - SAFE
Page 258: Army Medical Design Guide - SAFE

1.17.03 ADental Treatment RmMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 115Finishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 48GHardware Set - H02Ambient Noise Level - NC 30-35Speech Privacy Level - Confidential

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 100Task Illum (FC) - 150Luminare Type - A2Switching - Std

Electrical Notes - 10 ref pp 20-23

MECHANICAL

Total Air Changes - 6.0Outside Air Changes - 1.5Room Pressure(%) - 0Temperature (F) - Sum 75 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No Utility Center - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 8 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A5080 Dispenser, Paper Towel 2 AA5115 Mirror 18 X 30 2 AA5145 Coat Hook 1 AD0810 Sink, Dental, S.S. 2 AD9250 Apron Rail, Length-A.R. 2 A

Page 259: Army Medical Design Guide - SAFE

D9280 Legs, Apron Rail 2 AD9400 Cabinet, Wall Hung 1 AD9420 Cabinet, Wall Hung 1 AD9540 Base Unit, Single Swing Door 2 AD9940 Counter Top - P.L. 2 AM1620 Record Holder 1 AX3830 Illuminator, X-ray Film 1 AD3320 Chair, Dental Operating 1 9D8250 Operating Unit, Dental 1 BD3390 Stool, Dental 2 CD9030 Cabinet, Mobile, Dental 1 CF2010 Waste Receptacle SS 2 CD6050 Light, Dental Operating 1 E

Commo LogCode Nomenclature Qty Cat

PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet-54" AFF 2 AMDOOC Counter Outlet-6" Above 1 AMDOOW Wall Outlet-36" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 260: Army Medical Design Guide - SAFE
Page 261: Army Medical Design Guide - SAFE
Page 262: Army Medical Design Guide - SAFE
Page 263: Army Medical Design Guide - SAFE
Page 264: Army Medical Design Guide - SAFE

1.17.04 ADental X-ray SuiteMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Dental X-Ray - 85 (2) Dental X-Ray - 85 (3) Dark Room - 60 (4) Control - 60Finishes - Walls - (1) GW (2) GW (3) GW (4) GW - Base - (1) R (2) R (3) CT (4) R - Floor - (1) VCT (2) VCT (3) CT (4) VCT - Ceiling - (1) ACT (2) ACT (3) ACT (4) ACTCeiling Ht - (1) 8'-0" (2) 8'-0" - (3) 8'-0" (4) 8'-0"Door Size & Type - (3) Dark Room Door (4) 36AHardware Set - (3) H22 (4) H03Ambient Noise Level - (1) NC 35-40 (2) NC - 5-40 (3) NC 35-40 (4) NC 35-40Speech Privacy Level - (1) Normal (2) Normal (3) Normal (4) Normal

Architectural Notes - (1) 17 (2) 17 (3) 19 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 10 (3) 20 (4) 10Task Illum (FC) - (1) )) (2) )) (3) )) (4) )-Luminare Type - (1) B1 (2) B1 (3) C1 (4) B1Switching - (1) Std (2) Std (3) Std (4) Std

Electrical Notes - 6 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 6 (3) 10 (4) 6Outside Air Changes - (1) 1.5 (2) 1.5 (3) 2 (4) 1.5Room Pressure(%) - (1) +10 (2) +10 (3) -10 (4) +10Temperature (F) - (1) Sum 75 Win 68 (2) Sum 75 Win 68 (3) Sum 75 Win 68 (4) Sum 75 Win 68Relative Hum(%) - (1) 30-60 (2) 30-60 (3) 30-60 (4) 30-60Exhaust Air - (1) No (2) No (3) Yes (4) NoReturn Air - (1) Yes (2) Yes (3) No (4) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0 (3) 25,0,0 (4) 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - Yes

Page 265: Army Medical Design Guide - SAFE

Treated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C10G0 Cabinet, U/C, Base 1 ACB020 Cabinet, Wall Hung 1 AC02C0 Cabinet, U/C, Base 1 AC02D0 Cabinet, U/C, Base 3 AC02Q0 Cabinet, U/C, Sink 3 ACS140 Sink, SS, Counter 3 ACT030 Counter Top - P.L. 3 AM3620 Dispenser, Paper Towel 3 AM5300 Mirror 14x20 2 AM5960 Coat Hook 2 AP2050 Eyewash, Hand Desk 1 AX3150 Rack, Apron & Glove 2 AX3830 Illuminator, X-ray Film 1 AX6650 Safe Light 1 AX7700 Film Processor 1 AD3300 Chair, Dental, X-ray 1 CF2000 Waste Receptacle, Off 2 CX5350 Processor Dental Film 1 EX6450 X-ray Unit, Dental-15 1 FX6500 X-ray Unit, Dental-Pano 1 F

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 2 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 266: Army Medical Design Guide - SAFE

JULY 1988

Page 267: Army Medical Design Guide - SAFE

JULY 1988

Page 268: Army Medical Design Guide - SAFE

JULY 1988

Page 269: Army Medical Design Guide - SAFE

JULY 1988

Page 270: Army Medical Design Guide - SAFE

1.17.05 ADental Prosthetics LabMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 115Finishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 36AHardware Set - H03Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - C2Switching - Multi-Sw

Electrical Notes -

MECHANICAL

Total Air Changes - 10.0Outside Air Changes - 1.5Room Pressure (%) - 10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,80,0

Mechanical Notes - 8 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-20 -1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CA040 Cabinet, Wall Hung 1 AD0410 Cabinet, U/C, Base 1 AD0460 Dust Collector, Ped 1 AD0500 Cabinet, U/C, Base 1 AD0520 Cabinet, U/C, Base 2 AD0530 Cabinet, U/C, Base 2 A

Page 271: Army Medical Design Guide - SAFE

D0660 Drawer Unit 1 AD0710 Counter Top - Epoxy 2 AD0800 Sink, SS, Counter 1 AD0830 Plaster Trap 1 AD0860 Bench Light, Dental 1 AD0880 Hood w/Blast Gate 2 AD4600 Fumehood, Dental 1 AD8620 Plaster Bin 1 AD8650 Plaster Chute 1 AD9055 Valve, Model Trimmer 1 AD9056 Needle Cook, Air 1 AD9057 Needle Cook, Gas 1 AM3620 Dispenser, Paper Towel 1 AP2050 Eyewash, Hand Deck 1 AD6600 Mixer-Investor 1 BD3290 Chair, Dental Prosthetic 1 CD6500 Grinding/Polishing Machine 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

TLOOW Wall Outlet-54" AFF 1 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 272: Army Medical Design Guide - SAFE

JULY 1988

Page 273: Army Medical Design Guide - SAFE

JULY 1988

Page 274: Army Medical Design Guide - SAFE

JULY 1988

Page 275: Army Medical Design Guide - SAFE

JULY 1988

Page 276: Army Medical Design Guide - SAFE

Department of the Army Volume 2

Medical Design Guide

Office of the Surgeon General Office of the Chief of EngineersHealth Facility Planning Agency Medical Facilities Design Office

JULY 1988REVISED SEPTEMBER 1994

Page 277: Army Medical Design Guide - SAFE

2.01.01 AIV Additive RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 150Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 48AHardware Set - H03Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - C1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0045 Drawer Unit, Double - 36" L 1 AC07CO Cabinet, U/C, Base 1 AC07DO Cabinet, U/C, Base 1 AC08PO Cabinet, U/C, Sink 1 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AF0300 Chair, Rotary w/o Arms 2 C

Page 278: Army Medical Design Guide - SAFE

L2290 Hood, Laminar Flow, Floor 1 CM6800 Shelving, Storage 1 CR6080 Refrigerator, Dual Temp 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

PAOMO Ceiling Speaker-Music Only 1 APAOOV Volume Control 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOC Counter Outlet-6" Above 1 A

JULY 1988

Page 279: Army Medical Design Guide - SAFE

JULY 1988

Page 280: Army Medical Design Guide - SAFE

JULY 1988

Page 281: Army Medical Design Guide - SAFE

JULY 1988

Page 282: Army Medical Design Guide - SAFE

JULY 1988

Page 283: Army Medical Design Guide - SAFE

2.02.01 AGen RadiographyMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 270Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 9'-6"Door Size & Type - 36AX,48AXHardware Set - H14,H15Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes - 17,18,28 ref pp 5- 6

ELECTRICAL

Ambient Illum (FC) - 0-10Task Illum (FC) - )-Luminare Type - B1,H1Switching - Dim & Std-by Areas

Electrical Notes - 5,17,18,35 ref pp 20-23

MECHANICAL

Total Air Changes - 6.0Outside Air Changes - 1.5Room Pressure (%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM3620 Dispenser, Paper Towel 1 A

Page 284: Army Medical Design Guide - SAFE

F2000 Waste Receptacle, Off 1 CX1400 Cassette Holder 1 FX5900 X-ray Unit-800 Ma 1 F A. Control Unit B. Transformer C. Electronic Cabinet D. Table-Rad, Tilting E. Tubemount/equipment carriage F. Cable Raceway-below finished floor

ref pp 59-67 for X-Ray Criteria

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOEL Dome Light w/Chime 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 285: Army Medical Design Guide - SAFE
Page 286: Army Medical Design Guide - SAFE
Page 287: Army Medical Design Guide - SAFE
Page 288: Army Medical Design Guide - SAFE
Page 289: Army Medical Design Guide - SAFE

2.02.02 AFluoroscopyMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 300Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 9'-6"Door Size & Type - 36AX,48AXHardware Set - H14,H15Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes - 17,18,26 ref pp 5- 6

ELECTRICAL

Ambient Illum (FC) - 0-10Task Illum (FC) - )-Luminare Type - H1,P1Switching - Dim & Std-by Area

Electrical Notes - 5,17,35 ref pp 20-23

MECHANICAL

Total Air Changes - 6.0Outside Air Changes - 1.5Room Pressure (%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM3620 Dispenser, Paper Towel 1 A

Page 290: Army Medical Design Guide - SAFE

F2000 Waste Receptacle, Off 1 CX1400 Cassette Holder 1 FX6180 X-ray Unit-1000 Ma 1 F A. Control Unit B. Transformer C. Electronic Cabinet D. Table-Rad, Tilting E. Tubemount/Equipment carriage F. Cable Raceway-below finished floor G. Video Monitor

ref pp 59-67 for X-ray Criteria

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOEL Dome Light w/ Chime 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 291: Army Medical Design Guide - SAFE
Page 292: Army Medical Design Guide - SAFE
Page 293: Army Medical Design Guide - SAFE
Page 294: Army Medical Design Guide - SAFE
Page 295: Army Medical Design Guide - SAFE

2.02.03 AAngiographyMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net (1) Exposure - 550 (2) Control - 100 (3) Scrub - 80 - Walls - (1) GW (2) GW (3) GW-SGFinishes - Base - (1) R (2) R (3) R - Floor - (1) VCT (2) VCT (3) VCT - Ceiling - (1) ACT (2) ACT (3) ACTCeiling Ht - (1) 10'-0" (2) 8'-0" (3) 8'-0"Door Size & Type - (1) 36AX,48AX (2) 36AHardware Set - (1) H14,H15 (2) H03Ambient Noise Level - (1) NC 30-35 (2) NC 30-35 (3) NC 35-40Speech Privacy Level - (1) Normal (2) Normal (3) Normal

Architectural Notes - 17 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 0-50 (2) 0-50 (3) 100Task Illum (FC) - (1) )) (2) )) (3) )-Luminare Type - (1) E1 (2) C1 (3) A1Switching - (1) Dim (2) Dim (3) Std

Electrical Notes - 5,17,41 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 15.0 (2) 6.0 (3) 6.0Outside Air Changes - (1) 5.0 (2) 1.5 (3) 1.5Room Pressure(%) - (1) +20 (2) 0 (3) +10Temperature (F) - (1) 68-76 (2) Sum 78 Win 70 (3) Sum 75 Win 75Relative Hum(%) - (1) 50-60 (2) 30-60 (3) 30-60Exhaust Air - (1) No (2) No (3) NoReturn Air - (1) Yes (2) Yes (3) YesFiltration(%) - (1) 25,0,90-95 (2) 25,0,90 (3) 25,0,90

Mechanical Notes - (1) 13 (2) 13 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG- 13 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - No

Page 296: Army Medical Design Guide - SAFE

Steam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 AC04JO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 2 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L 1 AM3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3620 Dispenser, Paper Towel 1 AP6980A Scrub Station - 2 Bay 1 AX3990 Illuminator, X-ray Film 1 AF2010 Waste Receptacle SS 1 CX6170 X-ray Unit-1000 Ma 1 F A. Control Console B. Table-Angiographic C. Power Unit D. Transformer E. Systems Cabinet F. Vertical Control Cabinet G. Multiformat Camera H. Storage Cabinet I. Wall Raceway J. Cable Raceway-Below K. Support System

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOOS Staff Station 1 ANCOEL Emergency Dome Light w/ Chime 3 ANCOEW Pushbutton 1 APAOOC Ceiling Speaker 1 APAOOM Desk Microphone 1 APAOOV Volume Control 1 APAOCM Microphone, Ceiling Mounted 1 APAOLA Local Amplifier 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 2 ATSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 297: Army Medical Design Guide - SAFE

JULY 1988

Page 298: Army Medical Design Guide - SAFE

JULY 1988

Page 299: Army Medical Design Guide - SAFE

JULY 1988

Page 300: Army Medical Design Guide - SAFE

JULY 1988

Page 301: Army Medical Design Guide - SAFE

2.02.04 AMammographyMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Mammography - 100 (2) X-Ray Processing - 60Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT (2) VCT - Ceiling - (1) ACT (2) ACTCeiling Ht - (1) 10'-0" (2) 8'-0"Door Size & Type - (1) 36AX (2) Dark Room DoorHardware Set - (1) H14 (2) H22Ambient Noise Level - (1) NC 35-40 (2) NC 35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 17,18 (2) 34 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 0-10 (2) 20Task Illum (FC) - (1) )) (2) )-Luminare Type - (1) B1 (2) C1Switching - (1) Dim (2) Std

Electrical Notes - (1) 17 (2) 6 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 4.0 (2) 10.0Outside Air Changes - (1) 1.0 (2) 2.0Room Pressure(%) - (1) 0 (2) -10Temperature(F) (2) Sum 78 Win 70 (3) Sum 75 Win 68Relative Hum(%) - (1) 30-60 (2) 30-60Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,0,0 (2) 25,0,0

Mechanical Notes - (2) 8 ref pp 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - (2) 9 ref pp 16

EQUIPMENT PROGRAM

Page 302: Army Medical Design Guide - SAFE

J.S.N. LogCode Nomenclature Qty Cat

A5080 Dispenser, Paper Towel 2 AA5115 Mirror, 18 X 30 1 AA5145 Coat Hook 1 AM1620 Record Holder 1 AP2000 Eye Wash, Hand, Wall 2 AP3100 Lavatory, Wall Hung 1 AP4700 Basin Sink, Mop 1 AP6500 Sink, SVC 1 AX1000 Counter Top, P.L. 1 AX1020 Cabinet, Wall, Cassette 1 AX1040 Cabinet, Wall, Storage 1 AX1070 Cabinet, U/C, Waste 1 AX1080 Cabinet, U/C, Identifier 1 AX1100 Bin, Film, Loading 1 AX1600 Cabinet, Cassette, Transfer 1 AX6650 Safe Light 1 AX5325 Mixer, X-ray Chemicals 1 BF2000 Waste Receptacle, Off 1 CX5320 Processor, X-ray Film 1 EX5430 Mammography Unit 1 F

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 AMDOOW Wall Outlet-48" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 303: Army Medical Design Guide - SAFE
Page 304: Army Medical Design Guide - SAFE
Page 305: Army Medical Design Guide - SAFE
Page 306: Army Medical Design Guide - SAFE
Page 307: Army Medical Design Guide - SAFE

2.02.05 AUltrasoundMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Ultrasound - 150 (2) Toilet - 40Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"Door Size & Type - (1) 36A, 36A, 48A (2) 36AHardware Set - (1) H04, H13, H04 (2) H13Ambient Noise Level - (1) NC 35-40 (2) NC 35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - 18 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 20Task Illum (FC) - (1) )) (2) )-Luminare Type - (1) A1,H1 (2) R1Switching - (1) Std-by Area (2) Std

Electrical Notes -

MECHANICAL

Total Air Changes - (1) 4.0 (2) 10Outside Air Changes - (1) 1.0 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum )- Win )-Relative Hum(%) - (1) 30-60 (2) N/AExhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25.0,0 (2) 0,0,0

Mechanical Notes - (2) 6 ref pp 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

Page 308: Army Medical Design Guide - SAFE

A5080 Dispenser, Paper Towel 2 AA5090 Receptacle, Feminine Napkin 1 AM5115 Mirror 18 X 30 1 AA5145 Coat Hook 2 AA5195 Toilet Paper Holder 1 AM1620 Record Holder 1 AP3000 Lavatory, Wall Hung 1 AP3100 Lavatory, Wall Hung 1 AP9050 Water Closet 1 AX3990 Illuminator, X-ray Film 1 AF2000 Waste Receptacle, Off 1 CF2010 Waste Receptacle SS 1 CX9800 Ultrasound System 1 F

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOEL Dome Light w/ Chime 3 ANCOET Pullcord Station 1 AMDOOD Wall Outlet-18" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 309: Army Medical Design Guide - SAFE
Page 310: Army Medical Design Guide - SAFE
Page 311: Army Medical Design Guide - SAFE
Page 312: Army Medical Design Guide - SAFE
Page 313: Army Medical Design Guide - SAFE

2.02.06 AX-ray Film ProcessingMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 120Finishes - Walls - GW - Base - CT - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - Dark Room DoorHardware Set - H22Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes - 19 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 20Task Illum (FC) - )-Luminare Type - B1Switching - Std

Electrical Notes - 6,25 ref pp 20-23

MECHANICAL

Total Air Changes - 10Outside Air Changes - 2.0Room Pressure(%) - -10Temperature (F) - Sum 75 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,0

Mechanical Notes - 8 ref pp 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 9 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M3620 Dispenser, Paper Towel 1 AP2000 Eye Wash, Hand, Wall 2 AP4700 Basin, Sink, Mop 1 A

Page 314: Army Medical Design Guide - SAFE

P6150 Sink, SVC, Wall Hung 1 AX1000 Counter Top, P.L. 1 AX1020 Cabinet, Wall, Cassette 2 AX1040 Cabinet, Wall, Storage 2 AX1050 Cabinet, Wall, Cassette 2 AX1060 Cabinet, U/C, Storage 2 AX1070 Cabinet, U/C, Waste 1 AX1080 Cabinet, U/C, Identifier 1 AX1100 Bin, Film, Loading 1 AX1600 Cabinet, Cassette, Transfer 2 AX6650 Safe Light 1 AX5325 Mixer, X-ray Chemicals 1 BX5320 Processor, X-ray Film 2 E

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

JULY 1988

Page 315: Army Medical Design Guide - SAFE
Page 316: Army Medical Design Guide - SAFE
Page 317: Army Medical Design Guide - SAFE
Page 318: Army Medical Design Guide - SAFE
Page 319: Army Medical Design Guide - SAFE

2.02.07 ACT ScannerMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Scanner - 350 (2) Control - 120 (3) Computer - 180 (4) Indep. Display - 150Finishes - Walls - (1) GW (2) GW (3)GW (4) GW - Base - (1)R (2) R (3) R (4) R - Floor - (1) VCT (2) VCT (3) VCT (4) VCT - Ceiling - (1) ACT (2) ACT (3) ACT (4) ACTCeiling Ht - (1) 10'-0" (2) 8'-0" (3) 8'-0" (4) 8'-0"Door Size & Type - (1) 36EX,48AX (2) 36G (3) Sliding Door (4)36A,.36GHardware Set - (1) H14,H15 (2) H03 (3) H22 (4) H03

Ambient Noise Level - (1) NC 35-40 (2) NC 35-40 (3) NC 35-40 (4) NC 35-40Speech Privacy Level - (1) Normal (2) Normal (3) Normal (4) NormalArchitectural Notes - (1) 17,29 (2) 27,29 (3) 27,28,29 (4) 27,29 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 0-10 (2) 0-30 (3) 50 (4) 0-30Task Illum (FC) - (1) )) (2) )- (3) )- (4) )-Luminare Type - (1) B1 (2) B1 (3) F2 (4) F1Switching - (1) Dim (2) Dim (3) Std-by-Areas (4) DimElectrical Notes - 26 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 4 (3) 4 (4) 4Outside Air Chances - (1) 1.5 (2) 1 (3) 1 (4) 1Room Pressure(%) - (1) 0 (2) 0 (3) 0 (4) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70 (3) Sum 78 Win 70 (4) Sum 78 Win 70Relative Hum(%) - (1) 30-60 (2) 30-60 (3) 30-60 (4) 30-60Exhaust Air - (1) No (2) No (3) No (4) NoReturn Air - (1) Yes (2) Yes (3) Yes (4) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0 (3) 25,0,0 (4) 25,0,0Mechanical Notes - (3) 14 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - Yes

Page 320: Army Medical Design Guide - SAFE

Treated Water - No MG-13 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 AC04JO Cabinet, U/C, Base 1 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P L. 1 AM3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3620 Dispenser, Paper Towel 1 AM5960 Coat Hook 1 AF0300 Chair, Rotary w/o Arms 3 CF2010 Waste Receptacle SS 1 CX6240 X-ray Unit, Ct 1 F A. X-Ray Unit B. Power Distribution Unit C. MPX Power Unit D. H.V. Transformer E. Main Computer Cabinet F. Aux. Computer Cabinet G. Disc Drive Unit No. 1 H. Disc Drive Unit No. 2 J. Operators Console K. Multi Format Camera L. Long Printer M. Hard Copier Imager N. Diagnostic Console

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 APAOOC Ceiling Speaker 1 APAOOM Desk Microphone 1 APAOCM Microphone, Ceiling Mounted 1 APAOLA Local Amplifier 1 APAOMO Ceiling Speaker-Music Only 1 APAOVR Volume Control w/ By-Pass Relay 5 ATLOOW Wall Outlet-54" AFF 5 ATSOOW Wall Outlet-36" AFF 5 A

JULY 1988

Page 321: Army Medical Design Guide - SAFE

JULY 1988

Page 322: Army Medical Design Guide - SAFE

JULY 1988

Page 323: Army Medical Design Guide - SAFE

JULY 1988

Page 324: Army Medical Design Guide - SAFE

JULY 1988

Page 325: Army Medical Design Guide - SAFE

2.03.01 ALinear AcceleratorMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Accelerator - 600 (2) Control - 130 (3) Entry Maze - 140Finishes - Walls - (1) GW (2) GW (3) GW - Base - (1) R (2) R (3) R - Floor - (1) VCT (2) VCT (3) VCT - Ceiling - (1) ACT (2) ACT (3) ACTCeiling Ht - (1) 10'-0" (2) 8'-0" (3) 10"-0"Door Size & Type - (3) 48AXHardware Set - (3) H15Ambient Noise Level - (1) NC 30-35 (2) )- (3) NC 30-35Speech Privacy Level - (1) Normal (2) )- (3) Normal

Architectural Notes - (1) 30 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 0-10 (2) 30 (3) 30Task Illum (FC) - (1) )) (2) )- (3) )-Luminare Type - (1) B1, H1, S (2) C1,X (3) B1Switching - (1) Dim & Std-by Area (2) Std (3) Std

Electrical Notes - 17,18,26 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 4 (3) 6Outside Air Changes - (1) 1.5 (2) 1.0 (3) 1.5Room Pressure(%) - (1) 0 (2) 0 (3) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70 (3) Sum 78 Win 70Relative Hum(%) - (1) 30-60 (2) 30-60 (3) 30-60Exhaust Air - (1) No (2) No (3) NoReturn Air - (1) Yes (2) Yes (3) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0 (3) 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1 Chilled Water - YesWaste/Vent - Yes

Page 326: Army Medical Design Guide - SAFE

Floor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 2 AC04JO Cabinet, U/C, Base 2 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AF0224 Reception Counter 1 AM3620 Dispenser, Paper Towel 1 AF0254 Chair, Secretarial 1 CF1273 Counter, Central Monitor 1 CF2000 Waste Receptacle, Off 1 CX8710 Linear Accelerator-6 mev 1 F A. Accelerator B. Control Console C. Laser Positioning Equipment D. Radiation Detection System

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CTOOC Camera Ceiling Outlet 1 ACTOOM Monitor Outlet 1 APAOOC Ceiling Speaker 1 APAOOM Desk Microphone 1 APAOCM Microphone, Ceiling Mounted 1 APAOLA Local Amplifier 1 APAOMO Ceiling Speaker-Music Only 1 APAOVR Volume Control w/ By-Pass Relay 1 ATLOOW Wall Outlet-54" AFF 2 ATSOOC Counter Outlet-6" Above 2 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 327: Army Medical Design Guide - SAFE
Page 328: Army Medical Design Guide - SAFE
Page 329: Army Medical Design Guide - SAFE
Page 330: Army Medical Design Guide - SAFE
Page 331: Army Medical Design Guide - SAFE

2.03.02 ASimulator RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Simulator - 300 (2) Control - 110 (3) Equip Room - 100Finishes - Walls - (1) GW (2) 4W (3) GW - Base - (1) R (2) R (3) R - Floor - (1) VCT (2) VCT (3) VCT - Ceiling - (1) ACT (2) ACT (3) ACTCeiling Ht - (1) 10'-0" (2) 8'-0" (3) 10'-0"Door Size & Type - (1) 36A,48AX (2) H1 (3) H15Hardware Set - (1) H15, H13 (2) H14, H13Ambient Noise Level - (1) NC 30-40 (2) NC 30-40

Speech Privacy Level - (1) Normal (2) Normal (3) NormalArchitectural Notes - 18 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 0-10 (2) 20 f(3) 10-15Task Illum (FC) - (1) 50 (2) 75 (3) 30 -Luminare Type - (1) EB (2) (3) Q1Switching - (1) Dim & Std (2) Std (3) Std

Electrical Notes - (1) 8 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 4 (3) 4Outside Air Changes - (1) 1.5 (2) 13 (3) 1Room Pressure(%) - (1) 0 (2) 0 (3) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70 (3) Sum 78 Win 70Relative Hum(%) - (1) 30-60 (2) 30-60 (3) 30-60Exhaust Air - (1) No (2) No (3) NoReturn Air - (1) Yes (2) Yes (3) YesFiltration(%) - (1) 25,0 (2) 25,0 (3) 25,0

Mechanical Notes

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - No

Page 332: Army Medical Design Guide - SAFE

Condensate - No

Piping Notes -

EQUIPMENT PROGRAMJ.S.N. LogCode Nomenclature Qty CatM3620 Paper Towel Dispenser 1 AM5960 Hook-Robe-two prong 1 AP3100 Lavatory, Wall Hung 1 AC06CO Cabinet, U/C, Base 2 AC07CO Cabinet, U/C, Base 2 AC0045 Drawer Unit, Double 2 ACT030 Countertop - P.L. 1 AX3990 Illuminator - X-Ray 2 AF0202 Chair, Rotary w/o Arms 2 CF4011 Waste Receptacle, Off 2 CX8501 Simulator-Therapy 1 F A. Simulator B. Control/Monitoring Equip C. Electrical Apparatus As Required D. Laser Positioning Equip E. Transformer F. Cable Raceway- below Finished Floor

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

PAOOC Ceiling Speaker 1 APAOOM Desk Microphone 1 APAOCM Microphone, Ceiling Mounted 1 APAOLA Local Amplifier 1 APAOMO Ceiling Speaker-Music Only 1 APAOVR Volume Control w/By-Pass Relay 1 ATLOOW Wall Outlet-54" AFF 2 ATSOOC Counter Outlet-6" Above 1 ATSOOW Wall Outlet-36" AFF 1 ATVOCW Camera Wall Outlet 1 A

JULY 1988

Page 333: Army Medical Design Guide - SAFE

JULY 1988

Page 334: Army Medical Design Guide - SAFE

JULY 1988

Page 335: Army Medical Design Guide - SAFE

JULY 1988

Page 336: Army Medical Design Guide - SAFE

JULY 1988

Page 337: Army Medical Design Guide - SAFE

2.04.01 AGamma CameraMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 600 (300 per camera)Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 9'-0"Door Size & Type - 48AHardware Set - H09Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes - 31 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 10Task Illum (FC) - ))Luminare Type - B1Switching - Std-by Area

Electrical Notes - 28 ref pp 20-23

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02QO Cabinet. U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 AC04JO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 2 ACS150 Sink, SS, Counter 1 A

Page 338: Army Medical Design Guide - SAFE

CT030 Counter Top - P.L. 1 AM3620 Dispenser, Paper Towel 1 AM7960 Track & Curtain, Cubicle 2 AF2010 Waste Receptacle SS 1 CM7400 Table, Instrument 2 CM7705 Stool, Revolving 2 CX9820 Camera, Gamma 2 C A. Large Field of View Camera B. Camera Console C. Electronic Cabinets D. Collimator Stackers

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 2 ATSOOW Wall Outlet-36" AFF 2 A

JULY 1988

Page 339: Army Medical Design Guide - SAFE

JULY 1988

Page 340: Army Medical Design Guide - SAFE

JULY 1988

Page 341: Army Medical Design Guide - SAFE

JULY 1988

Page 342: Army Medical Design Guide - SAFE

JULY 1988

Page 343: Army Medical Design Guide - SAFE

2.04.02 ASpecial ImagingMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 400Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 48AHardware Set - H09Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes - 31 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 10Task Illum (FC) - )-Luminare Type - B1Switching - Std-by Area

Electrical Notes - 28 ref pp 20-23

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02BO Cabinet, U/C, Base 1 AC0200 Cabinet, U/C, Sink 1 AC03EO Cabinet, U/C, Base 1 AC03JO Cabinet, U/C, Base 1 ACE030 Cabinet, Wall Hung 2 A

Page 344: Army Medical Design Guide - SAFE

CS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM3620 Dispenser, Paper Towel 1 AF2010 Waste Receptacle SS 1 CM0100 Data Processing Terminal 1 CM1540 Treadmill, High Speed 1 CM1560 Exerciser, Bicycle 1 CM3051 Defibrillator- w/ Cart 1 CM3500 Electrocardioscanner-EKG 1 CX9820 Camera, Gamma 1 C A. Large Field of View Camera B. Camera Console C. Electronic Cabinets D. Collimator Stackers

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 2 ATSOOC Counter Outlet-6" Above 1 ATSOOW Wall Outlet-36" AFF 2 A

JULY 1988

Page 345: Army Medical Design Guide - SAFE

JULY 1988

Page 346: Army Medical Design Guide - SAFE

JULY 1988

Page 347: Army Medical Design Guide - SAFE

JULY 1988

Page 348: Army Medical Design Guide - SAFE

JULY 1988

Page 349: Army Medical Design Guide - SAFE

2.04.03 AUptake WorkroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 120Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8-0"Door Size & Type - 36AHardware Set - H02Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - ))Luminare Type - A1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J S.N. LogCode Nomenclature Qty Cat

M5080 Dispenser, Paper Towel 1 AM5145 Coat Hook 1 AM1620 Record Holder 1 AM3800 Desk, Folding, Wall Mount 1 AP3100 Lavatory, Wall Hung 1 AX4000M Illuminator, X-ray Film,2-over-2 1 AF2010 Waste Receptacle, SS 1 C

Page 350: Army Medical Design Guide - SAFE

M9050 Table, Exam., SS, 2 Section 1 CX9500 Thyroid System 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

RSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch, 3 Button 1 AMDOOW Wall Outlet-48" AFF 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 351: Army Medical Design Guide - SAFE
Page 352: Army Medical Design Guide - SAFE
Page 353: Army Medical Design Guide - SAFE
Page 354: Army Medical Design Guide - SAFE
Page 355: Army Medical Design Guide - SAFE

2.04.04 ARadioisotopeMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 140Finishes - Walls - GW-SG - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 36A,36EHardware Set - H03Ambient Noise Level - NC 30-35Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - C1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - 10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C02CO Cabinet, U/C, Sink 1 AC05LO Cabinet, U/C, Base 2 ACE050 Cabinet, Wall Hung 2 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AF2000 Waste Receptacle, Off 1 AF2010 Waste Receptacle, SS 1 A

Page 356: Army Medical Design Guide - SAFE

M3620 Dispenser, Paper Towel 1 AM5960 Coat Hook 1 AP2050 Eyewash, Hand Desk 1 AM3080 Chair, Blood Drawing 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

TLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 357: Army Medical Design Guide - SAFE

JULY 1988

Page 358: Army Medical Design Guide - SAFE

JULY 1988

Page 359: Army Medical Design Guide - SAFE

JULY 1988

Page 360: Army Medical Design Guide - SAFE

JULY 1988

Page 361: Army Medical Design Guide - SAFE

2.04.05 ARadioimmunoassayMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Lab - 400 (2) Work Area - 200Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT (2) VCT - Ceiling - (1) ACT (2) ACTCeiling Ht - (1) 8-0 (2) 8'-0"Door Size & Type - (1) 36A,36E (2) 36EHardware Set - (1) H03 (2) H03Ambient Noise Level - (1) NC 30-35 - (2) NC 30-35Speech Privacy Level - (1) Normal - (2) Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 50Task Illum (FC) - (1) 100 (2) )-

Luminare Type - (1) A1 - (2) A1 Switching - (1) Std-by Area (2) Std

Electrical Notes - 42 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 6Outside Air Changes - (1) 1.5 (2) 1.5Room Pressure(%) - (1) -10 (2) - 10Temperature (F) - (1) Sum 78 Win 68 (2) Sum 78 Win 68Relative Hum(%) - (1) 30-60 (2) 30-60Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

Page 362: Army Medical Design Guide - SAFE

J.S.N. LogCode Nomenclature Qty Cat

CS150 Sink, SS, Counter 3 ALOOOO Service Module, Lab AR AM3620 Dispenser, Paper Towel 3 AP2050 Eyewash, Hand Desk 1 AF0230 Chair, Lab 3 CF2000 Waste Receptacle, Off 1 CF2010 Waste Receptacle SS 1 CL1670 Centrifuge, Refrigerated 2 CL9840 Counter, Ria 3 CM3080 Chair, Blood Drawing 1 CM7400 Table, Instrument 1 CR6080 Freezer, 2 dr 1 CR6110 Refrigerator 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

TLOOW Wall Outlet-54" AFF 2 ATSOOC Counter Outlet-6" Above 3 A

JULY 1988

Page 363: Army Medical Design Guide - SAFE

JULY 1988

Page 364: Army Medical Design Guide - SAFE

JULY 1988

Page 365: Army Medical Design Guide - SAFE

JULY 1988

Page 366: Army Medical Design Guide - SAFE

JULY 1988

Page 367: Army Medical Design Guide - SAFE

2.04.06 ARadiopharmacy (Large)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 600Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 36EHardware Set - H03Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 100Task Illum (FC) - )-Luminare Type - A1Switching - Multi-Sw

Electrical Notes - 42 ref pp 20-23

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure (%) - -10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - YesChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0045 Drawer Unit, Double - 36" L 2 AC0047 Drawer Unit Double - 60" L 2 AC02QO Cabinet, UC, Sink 2 AC03EO Cabinet, U/C, Base 2 AC04EO Cabinet, U/C, Base 2 AC04JO Cabinet, U/C, Base 2 A

Page 368: Army Medical Design Guide - SAFE

COSLO Cabinet, U/C, Base 2 ACS150 Sink, SS, Counter 2 ACT030 Counter Top - P.L. 4 AF7035 Sink Module, LL 1 AL2270 Fume Hood, Lead Lined 1 AM3620 Dispenser, Paper Towel 2 AM5960 Coat Hook 1 AP2050 Eyewash, Hand Desk 1 AP5210 Shower Safety 1 AR6900 Refrigerator, LL 1 AX9305A Receiving Module LL 1 AX9305B Inventory Module LL 1 AX9305C Base Module, LL 1 AX9305D Generator Safe, Front 1 AX9305E Shadow Shield 3 AX9305F Counter Top, SS, LL 1 AX9305G Generator Module, LL 1 AX9305H Decay Module, LL 1 AX9305I Decay Module, LL 1 AF2000 Waste Receptacle Off 2 CF2010 Waste Receptacle SS 1 CL2290 Hood, Laminar Flow, Floor 1 CM7715 Stool, Lab 4 CR7000 Refrigerator 1 C

COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty CatTLOOW Wall Outlet-54" AFF 4 ATSOOC Counter Outlet-6" AFF 6 A

JULY 1988

Page 369: Army Medical Design Guide - SAFE

JULY 1988

Page 370: Army Medical Design Guide - SAFE

JULY 1988

Page 371: Army Medical Design Guide - SAFE

JULY 1988

Page 372: Army Medical Design Guide - SAFE

JULY 1988

Page 373: Army Medical Design Guide - SAFE

2.05.01 ACardiac CathMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Catheterization - 530 (2) Control - 100 (3) Scrub - 60Finishes - Walls - (1) GW (2) GW (3) GW-SG - Base - (1) R (2) R (3) R - Floor - (1) VCT (2) VCT (3) VCT - Ceiling - (1) ACT (2) ACT (3) ACTCeiling Ht - (1) 10'-0" (2) 8'-0" (3) 8'-0"Door Size & Type - (1) 48AX (2) 36A (3) 36AXHardware Set - (1) H15 (2) H13 (3) H14Ambient Noise Level - (1) NC 30-35 (2) NC 30-35 (3) NC 35-40Speech Privacy Level - (1) Normal (2) Normal (3) Normal

Architectural Notes - 17 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 0-50 (2) 0-50 (3) 100Task Illum (FC) - (1) )) (2) )- (3) )-Luminare Type - (1) E1 (2) C1 (3) A1Switching - (1) Dim (2) Dim (3) Multi-Sw

Electrical Notes - 5,17,26,41 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 15.0 (2) 6.0 (3) 6.0Outside Air Changes - (1) 5.0 (2) 1.5 (3) 1.5Room Pressure(%) - (1) +20 (2) 0 (3) +10Temperature (F) - (1) 68-76 (2) Sum 78 Win 70 (3) Sum 75 Win 75Relative Hum(%) - (1) 50-60 (2) 30-60 (3) 30-60Exhaust Air - (1) No (2) No (3) NoReturn Air - (1) Yes (2) Yes (3) YesFiltration(%) - (1) 25,0,90-95 (2) 25,0,90 (3) 25,0,90

Mechanical Notes - (1) 13 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-13 - 1Chilled Water - NoWaste/Vent - Yes

Page 374: Army Medical Design Guide - SAFE

Floor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CE040 Cabinet, Wall Hung 2 AC02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 AC04JO Cabinet, U/C, Base 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3620 Dispenser, Paper Towel 1 AP6980A Scrub Station-2 bay 1 AX3990 Illuminator, X-ray Film 1 AF0285 Cart, Linen 1 CF2010 Waste Receptacle SS 1 CM4500 Hamper, Linen 1 CX6190 X-ray Unit, Cardiac 1 F A. Control Console B. Table-Angiographic C. Power Unit D. Transformer E. Systems Cabinet F. Vertical Control Cabinet G. Multiformat Camera H. Storage Cabinet I. Wall Raceway J. Cable Raceway-Below K. Support System L. Video Monitor Ceiling Mounted

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOOS Staff Station 1 ANCOEL Emergency Dome Light w/ Chime 1 ANCOEW Pushbutton 1 APAOOC Ceiling Speaker 1 APAOOV Volume Control 1 APAOCM Microphone, Ceiling Mounted 1 APAOLA Local Amplifier 1 APAOMO Ceiling Speaker (Music Only) 1 ATLOOK CAPOC Outlet 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF-E.P. 2 ATVOCW Camera Outlet 1 A

Communication Notes -

JULY 1988

Page 375: Army Medical Design Guide - SAFE

JULY 1988

Page 376: Army Medical Design Guide - SAFE

JULY 1988

Page 377: Army Medical Design Guide - SAFE

JULY 1988

Page 378: Army Medical Design Guide - SAFE

JULY 1988

Page 379: Army Medical Design Guide - SAFE

2.06.01 AAutopsyMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area. Net - 280Finishes - Walls - CT - Base - ET - Floor - ET -Ceiling - ACTCeiling Ht - 8'-6"Door Size & Type - 48G,36AHardware Set - H09,H03Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes - 2 ref. pp. 5- 6

ELECTRICAL

Ambient Illum (FC) - 75Task Illum (FC) - 300Luminare Type - D1Switching - Std

Electrical Notes - 10 ref. pp. 20-23

MECHANICAL

Total Air Changes - 12Outside Air Changes - 3Room Pressure(%) - 10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,0

Mechanical Notes

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No MG-24 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CW140 Cabinet, Full Height 2 AL9715 Table, Autopsy 1 AM1530 Chalkboard 1 A

Page 380: Army Medical Design Guide - SAFE

M1860 Bulletin Board 1 AM3620 Dispenser, Paper Towel 1 AM4770 Light, Treat, Ceiling 1 AP6950 Sink, Surgeon 1 AP9320 Floor Drain w/ Primer 1 AX3990 Illuminator, X-ray Film 1 AM7705 Stool, Revolving 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

TLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 381: Army Medical Design Guide - SAFE

JULY 1988

Page 382: Army Medical Design Guide - SAFE

JULY 1988

Page 383: Army Medical Design Guide - SAFE

JULY 1988

Page 384: Army Medical Design Guide - SAFE

JULY 1988

Page 385: Army Medical Design Guide - SAFE

2.07.01 AHemodialysis CubicleMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 120Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type -Hardware Set -Ambient Noise Level - NC 30-35Speech Privacy Level - Normal

Architectural Notes

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A2Switching - Multi-Sw.

Electrical Notes -

MECHANICAL

Total Air Changes - 6.0Outside Air Changes - 1.5Room Pressure (%) - +10Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - Yes MG-3 - 2Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M3620 Dispenser, Paper Towel 2 AM7960 Track & Curtain, Cubicle 2 AM7965 Drapery Track 2 AM9900 Dialysis Console 2 AP3100 Lavatory, Wall Hung 2 AM8825 Bracket, Tv 2 B

Page 386: Army Medical Design Guide - SAFE

F0210 Chair, Visitor 2 CF2010 Waste Receptacle SS 2 CM0365 Chair, Blood Donor 2 CM1715 Dialysis Unit 2 CM8810 Television, Bedside 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC001 Single Patient Station 2 ANCOEL Dome Light w/Chime 2 ATLOOW Wall Outlet-54" AFF 2 ATSOOW Wall Outlet-36 AFF 2 ATVOOB Wall Outlet, Bedside-48" AFF 2 A

JULY 1988

Page 387: Army Medical Design Guide - SAFE

JULY 1988

Page 388: Army Medical Design Guide - SAFE

JULY 1988

Page 389: Army Medical Design Guide - SAFE

JULY 1988

Page 390: Army Medical Design Guide - SAFE

JULY 1988

Page 391: Army Medical Design Guide - SAFE

2.08.01 AGeneral ORMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 400Finishes -Walls - CT - Base - ET -Floor - ET - Coiling - GW-SGCeiling Ht - 9'-6"Door Size & Type - 36A,36G,48G/18AHardware Set - H17,H18,H16Ambient Noise Level - NC 30-35Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 200Task Illum (FC) - )-Luminare Type - D1Switching - Std-by Area

Electrical Notes - 10,29,38 ref pp 20-23

MECHANICAL

Total Air Changes - 15Outside Air Changes - 5Room Pressure(%) - +20Temperature (F) - 68-76Relative Hum(%) - 50-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,0,90-95

Mechanical Notes - 9,13,18 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG- 1 - 3Chilled Water - No M9600 - 2Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3800 Desk Folding, Wall Mount 1 AM4802 Light Surgical, Ceiling 1 A

Page 392: Army Medical Design Guide - SAFE

M9600 Surgery Gas Column 2 AM9620 Control Cabinet, Nitrogen 1 AX4010 Illuminator, X-ray Film 2 AF0355 Foot Stool 3 CM2755 Anesthesia Apparatus 1 CM7200 Cart, Case 1 CM7340 Table, Operating 1 CM7405 Pail 2 CM7410 Carriage 2 CM7415 Stand Mayo 2 CM7460 Table, Anesthesia 1 CM7510 Table Instrument 2 CM7705 Stool Revolving 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOEL Dome Light w/Chime 3 ANCOOS Staff Station 1 ANCOEW Pushbutton 1 APAOOV Volume Control 1 APAOCM Microphone, Ceiling Mounted 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOK CAPOC Outlet 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 ATVOCC Camera Ceiling Outlet 1 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 393: Army Medical Design Guide - SAFE

JULY 1988

Page 394: Army Medical Design Guide - SAFE

JULY 1988

Page 395: Army Medical Design Guide - SAFE

JULY 1988

Page 396: Army Medical Design Guide - SAFE

JULY 1988

Page 397: Army Medical Design Guide - SAFE

2.08.02 ASpecial ORMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 600Finishes -Walls - CT - Base - ET - Floor - ET - Ceiling - GW-SGCeiling Ht - 9'-6"Door Size & Type - 36A,36G,48G/18AHardware Set - H17,H18,H16Ambient Noise Level - NC 30-35Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 200Task Illum (FC) - )-Luminare Type - D1Switching - Std-by Area

Electrical Note - 10,29,38 ref pp 20-23

MECHANICAL

Total Air Changes - 15Outside Air Changes - 5Room Pressure(%) - +20Temperature (F) - 68-76Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,99.97

Mechanical Notes - 9,13,18 ref PP 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-1 - 3Chilled Water - No M9600 - 2Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAMJ.S.N. LogCode Nomenclature Qty Cat

M3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3800 Desk, Folding, Wall Mount 1 AM4803 Light, Surgical, Ceiling 1 AM9600 Surgery Gas Column 2 A

Page 398: Army Medical Design Guide - SAFE

M9620 Control Cabinet, Nitrogen 1 AX4010 Illuminator, X-ray Film 2 AF0355 Foot Stool 4 CM2755 Anesthesia Apparatus 1 CM7200 Cart, Case 1 CM7340 Table, Operating 1 CM7405 Pail 2 CM7410 Carriage 2 CM7415 Stand Mayo 2 CM7460 Table, Anesthesia 2 CM7510 Table, Instrument 4 CM7705 Stool, Revolving 2 C

COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOEL Dome Light w/ Chime 3 ANCOOS Staff Station 1 ANCOEW Pushbutton 1 APAOCM Microphone, Ceiling Mounted 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOK CAPOC Outlet 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-18" AFF 1 ARVOCC Camera Ceiling Outlet 1 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 399: Army Medical Design Guide - SAFE

JULY 1988

Page 400: Army Medical Design Guide - SAFE

JULY 1988

Page 401: Army Medical Design Guide - SAFE

JULY 1988

Page 402: Army Medical Design Guide - SAFE

JULY 1988

Page 403: Army Medical Design Guide - SAFE

2.08.03 AScrub AreaMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 144Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 36A,36GHardware Set - H17,H18Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 100Task Illum (FC) - )-Luminare Type - A1Switching - Multi-SW

Electrical Notes -

MECHANICAL

Total Air Changes - 6.0Outside Air Changes - 1.5Room Pressure(%) - +10Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,90,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

P690B Scrub Station-3 bay 2 A

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

Page 404: Army Medical Design Guide - SAFE

NCOEL Dome Light w/ Chime 2 A

JULY 1988

Page 405: Army Medical Design Guide - SAFE

JULY 1988

Page 406: Army Medical Design Guide - SAFE

JULY 1988

Page 407: Army Medical Design Guide - SAFE

JULY 1988

Page 408: Army Medical Design Guide - SAFE

JULY 1988

Page 409: Army Medical Design Guide - SAFE

2.08.04 ADecontamination - ORMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 150Finishes - Walls - GW-SG - Base - ET - Floor - ET - Ceiling - GW-SGCeiling Ht - 8'-0"Door Size & Type - 36GHardware Set - H18Ambient Noise Level - NC 35-40Speech Privacy Level - Not Critical

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 30Task Illum (FC) - )-Luminare Type - C1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 6.0Outside Air Changes - 1.5Room Pressure (%) - -20Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25.90.0

Mechanical Notes -8 ref pp 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - YesCondensate - Yes

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CE040 Cabinet, Wall Hung 2 AC02QO Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 2 ACS150 Sink, SS, Counter 1 ACT050 Counter Top - SS 1 AL2337 Canopy Exhaust Hood 1 A

Page 410: Army Medical Design Guide - SAFE

M3620 Dispenser, Paper Towel 1 AP6350 Sink, SVC, Wall Hung 1 AF2010 Waste Receptacle SS 1 CS7550 Washer-Sterilizer 1 E

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOOS Staff Station 1 ATLOOW Wall Outlet-54" AFF 1 A

JULY 1988

Page 411: Army Medical Design Guide - SAFE

JULY 1988

Page 412: Army Medical Design Guide - SAFE

JULY 1988

Page 413: Army Medical Design Guide - SAFE

JULY 1988

Page 414: Army Medical Design Guide - SAFE
Page 415: Army Medical Design Guide - SAFE

2.08.05 AOR Prep/HoldMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) General - 120 (2) ICU - 120Finishes - Walls - (1) GW-SG (2) GW-SG - Base - (1) IV (2) IV - Floor - (1) SV (2) SV - Ceiling - (1) ACT (2) ACTCeiling Ht - (1) 9'-0" (2) 9'-0"Door Size Type -Hardware Set -Ambient Noise Level - (1) NC 30-35 (2) NC 30-35Speech Privacy Level - (1) Normal (2) Normal

Architectural Nates - 32 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 30 (2) 30Task Illum (FC) - (1) 100 (2) 100Luminare Type - (1) A2,C2,J1 - (2) A2,C2,J1Switching - (1) Std-by Area (2) Std-by Area

Electrical-Notes - 13,38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 6Outside Air Changes - (1) 1.5 (2) 1.5Room Pressure(%) - (1) +10 (2) +10Temperature (F) - (1) Sum 75 Win 75 (2) Sum 75 Win 75Relative Hum(%) - (1) 50-60 (2) 50-60Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,90,0 (2) 25,90,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5541 - 1Chilled Water - No M5542H - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

J.S.N. Log

Page 416: Army Medical Design Guide - SAFE

Code Nomenclature Qty Cat

CO2QO Cabinet, U/C, Sink 1 A C04E0 Cabinet, U/C, Base 1 AC04HO Cabinet, U/C, Base 1 ACEO4O Cabinet, Wall Hung 2 ACS150 Sink, SS, Counter 1 ACT050 Counter Top - SS 1 ACTO3O Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 2 AM315O Clock, Elapsed Time 1 AM3162 Clock 1 AM362O Dispenser, Paper Towel 1 AM4740 Light, Exam, Ceiling 1 AM5542B Patient SVC Console - M/S 2 AM796O Track & Curtain, Cubicle 2 AM8000 IV Track 2 AF2010 Waste Receptacle SS 3 CM74OO Table, Instrument 1 CM7415 Stand Mayo 1 CM835O Stretcher, Transport 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOC Ceiling Outlet 1 ANCOO1 Single Patient Station 2 ANCOOD Duty Station 1 ANCODL Dome Light-3 Lamp 2 ATLOOH Wall Outlet-54" A.F.F. 2 ATSOOH Wall Outlet-54" A.F.F. 2 ATSOOW Wall Outlet-36" A.F.F. 1 A

JULY 1988

Page 417: Army Medical Design Guide - SAFE

JULY 1988

Page 418: Army Medical Design Guide - SAFE

JULY 1988

Page 419: Army Medical Design Guide - SAFE

JULY 1988

Page 420: Army Medical Design Guide - SAFE

JULY 1988

Page 421: Army Medical Design Guide - SAFE

2.08.06 ARecovery ModuleMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) General - 120 (2) ICU - 120Finishes - Walls - (1) GW-SG (2) GW-SG - Base - (1) IV (2) IV -Floor - (1) SV (2) SV -Ceiling - (1) ACT (2) ACTCeiling Ht - (1) 9'-0" (2) 9'-0"Door Size & Type -Hardware Set -Ambient Noise Level - (1) NC 30-35 (2) NC 30-35Speech Privacy Level - (1) Normal (2) Normal

Architectural Nates - 32 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 30 (2) 30Task Illum (FC) - (1) 100 (2) 100Luminare Type - (1) A2,C2,J1 - (2) A2,C2,J1Switching - (1) Std-by Area (2) Std-by Area

Electrical Notes - 13,38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 6Outside Air Changes - (1) 1.5 (2) 1.5Room Pressure(%) - (1) +10 (2) +10Temperature (F) - (1) Sum 75 Win 75 (2) Sum 75 Win 75Relative Hum(%) - (1) 50-60 (2) 50-60Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,90,0 (2) 25,90,0

Mechanical Notes - 13 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5541 - 1Chilled Water - No M5542H - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

Page 422: Army Medical Design Guide - SAFE

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

F6010 Bumper, Hospital Bed 2 AM3620 Dispenser, Paper Towel 1 AM5541 Patient SVC Console-ICU 1 AM5542H Patient SVC Console-Recovery 1 AM7960 Track & Curtain, Cubicle 2 AM8000 IV Track 1 AM8015 IV Track ICU 1 AP3100 Lavatory, Wall Hung 1 AF2010 Waste Receptacle SS 2 CM0850 Bed, Recovery 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 2 ANCOOD Duty Station 1 ANCODL Dome Light - 3 Lamp 2 ATLOOH Wall Outlet-54" A.F.F. 2 ATLOHK CAPOC Outlet 2 ATSOOH Wall Outlet 2 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 423: Army Medical Design Guide - SAFE

JULY 1988

Page 424: Army Medical Design Guide - SAFE

JULY 1988

Page 425: Army Medical Design Guide - SAFE

JULY 1988

Page 426: Army Medical Design Guide - SAFE

JULY 1988

Page 427: Army Medical Design Guide - SAFE

2.09.01 ALabor RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Labor - 150 (2) Toilet - 40Finishes - Walls - (1) GW-SG (2) GW-SG - Base - (1) R (2) R - Floor - (1) VCT (2) VCT - Ceiling - (1) ACT (2) GWCeiling Ht (1) 8'-0" (2) 8'-0"Door Size & Type - (1) 36A 48AHardware Set - (1) H13 H10Ambient Noise Level - (1) NC 30-35 (2) NC 30-40Speech Privacy Level - (1) Confidential (2) Normal

Architectural Notes - (1) 5 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 30 (2) 20Task Illum (FC) - (1) 100 (2) )-Luminare Type - (2) A2,C2,J1,K,R2

Switching - (1) Std-by Areas (2) Std

Electrical Notes - 13,14,15,16,38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6.0 (2) 10.0Outside Air Changes - (1) 1.5 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 75 Win 75 (2) Sum )- Win )-Relative Hum(%) - (1) 30-60 (2) )-Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,90,0 (2) ))

Mechanical Notes - 6 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHotWater - YesTreated Water - No M5542G - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

Page 428: Army Medical Design Guide - SAFE

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A1110G Patient SVC Console-Labor 1 AA1160 IV Track 1 AA5080 Dispenser, Paper Towel 2 AA4600M Grab Bar, 36 X 48 1 AA5300 Mirror 18 X 30 1 AA5145 Coat Hook 1 AA5180 Track & Curtain, Cubicle 1 AA5185 Drapery Track 1 AA5190 Toilet Paper Holder, Recessed 1 AA6010 Bumper, Hospital Bed 1 AC0023 Wardrobe, Single 1 AM1620 Record Holder 1 AP3000 Lavatory, Wall Hung 1 AP3450 Lavatory, Wall Hung 1 AP9050 Water Closet 1 AA5220 Bracket, TV , Wall Mounted 1 BF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 2 CM0500 Television Set 1 CM7000 Bed, Birthing 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOET Pullcord Station 1 AMDOOH Service Console Outlet 1 AMDOOW Wall Outlet-48" AFF 1 ATVOOW Wall Outlet-12" below Ceiling 1 A

Communications Notes - 17 ref pp 29-30

JULY 1988REVISED SEPTEMBER 1994

Page 429: Army Medical Design Guide - SAFE
Page 430: Army Medical Design Guide - SAFE

2.09.02 ABirthing RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Birthing - 250 (2) Toilet - 60Finishes - Walls - (1) GW-SG (2) GW-SG - Base - (1) IV (2) CT - Floor - (1) SV (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"Door Size & Type - 36A,48AHardware Set - (1) H13,H10Ambient Noise Level - (1) NC 30-35 (2) NC 30-40Speech Privacy Level - (1) Confidential (2) Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - (1) 30 (2) 20Task Illum (FC) - (1) 100 (2) )-Luminare Type - (1) A2,C2,J1,J2,K,T,R2

Switching - (1) Multi-Sw & Std-by Area (2) Std

Electrical Notes - 13,14,15,16,38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 10Outside Air Changes - (1) 1.5 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 75 Win 75 (2) Sum )- Win ))Relative Hum(%) - (1) 30-60 (2) ))Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,90,0 (2) 0,0,0

Mechanical Notes - (2) 6 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5541 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5

Page 431: Army Medical Design Guide - SAFE

ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 1 ACT030 Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 1 AM3150 Clock, Elapsed Time 2 AM3162 Clock 1 AM3620 Dispenser, Paper Towel 2 AM4600C Grab Bar, Toilet-36" x 48" 1 AM5300 Mirror 14 X 20 1 AM5541 Patient SVC Console-ICU 2 AM5960 Coat Hook 1 AM6880 Shower Curtain Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 3 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AM8000 IV Track 1 AP3070 Lavatory, Counter 1 AP3450 Lavatory, Wall Hung 1 AP5100 Shower, 36" X 36" 1 AP9050H Water Closet 1 AM8825 Bracket, Tv 1 9F0110 Bassinet 1 CF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 2 CM0845 Bed, Birthing 1 CM2755 Anesthesia Apparatus 1 CM4500 Hamper, Linen 1 CM7415 Stand Mayo 1 CM7460 Table Anesthesia 1 CM7705 Stool Revolving 2 CM8810 Television, Bedside 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANC001 Single Patient Station 1 ANCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station 1 ANCOEW Pushbutton 1 ATLOHK CAPOC Outlet 1 ATLOOH Wall Outlet-54" AFF 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 ATSOOH Wall Outlet 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communications Note - 17 ref pp 29-30

JULY 1988

Page 432: Army Medical Design Guide - SAFE

JULY 1988

Page 433: Army Medical Design Guide - SAFE

JULY 1988

Page 434: Army Medical Design Guide - SAFE

JULY 1988

Page 435: Army Medical Design Guide - SAFE

JULY 1988

Page 436: Army Medical Design Guide - SAFE

2.09.03 AStress TestingMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Stress Testing - 150 (2) Toilet - 60Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"Door Size & Type - (1) 36A,48AHardware Set - (1) H13,H10Ambient Noise Level - (1) NC 30-35 (2) NC 35-40Speech Privacy Level - (1) Confidential (2) Normal

Architectural Notes - (2) 19 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 20Task Illum (FC) - (1) 100 (2) )-Luminare Type - (1) A2,J1,K (2) R1Switching - (1) Multi-Sw & Std-by Area (2) Std

Electrical Notes - 12,13,14,15,16, 38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6.0 (2) 10.0Outside Air Changes - (1) 1.5 (2) 0Room Pressure(%) - (1) 0 (2) 100Temperature (F) - (1) Sum 75 Win 75 (2) Sum )) Win )-Relative Hum(%) - (1) 30-60 (2) ))Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,90,0 (2) 0,0,0

Mechanical Notes - (2) 6 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No A110G - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 437: Army Medical Design Guide - SAFE

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A1100G Patient SVC Console - M/S 1 AA1160 IV Track 1 AA5080 Dispenser, Paper Towel 2 AA5110C Grab Bar, Toilet 36" X 48" 1 AA5110H Grab Bar, Shower, 24"X57"X24" 1 AM5115 Mirror 18 X 30 1 AM5145 Coat Hook 2 AA5170 Shower Curtain Rod 1 AA5175 Soap Dish w/Grab Bar 1 AA5180 Track & Curtain, Cubicle 1 AA5190 Toilet Paper Holder, Recessed 1 AA5205 Towel Bar, 1" Dia. 1 AA6010 Bumper, Hospital Bed 1 ACE030 Cabinet, Wall Hung 2 AC0023 Wardrobe, Single 1 AC02QO Cabinet, U/C, Sink 1 AC03EO Cabinet, U/C, Base 1 AC03JO Cabinet, U/C, Base 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L 2 AM1620 Record Holder 1 AP3070 Lavatory, Counter 1 AP5100 Shower 2'-6"X5'-0" 1 AP9050H Water Closet 1 AA5220 Bracket, TV, Wall Mounted 1 BF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 2 CM7000 Bed, Birthing 1 CM0500 Television Set 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC001 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station 1 AMDOOW Wall Outlet-48"AFF 1 AMDOOH Wall Outlet 1 ATVOOW Wall Outlet-12" Below Ceiling 1 A

Communication Notes - 17 ref pp 29-30

JULY 1988REVISED SEPTEMBER 1994

Page 438: Army Medical Design Guide - SAFE
Page 439: Army Medical Design Guide - SAFE
Page 440: Army Medical Design Guide - SAFE
Page 441: Army Medical Design Guide - SAFE
Page 442: Army Medical Design Guide - SAFE

2.09.04 AOB Exam/PrepMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Patient Exam/Prep - 150 (2) Toilet - 60Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-6" (2) 8'-0" Door Size & Type - (1) 36A,48AHardware Set - (1) H13,H10Ambient Noise Level - (1) NC 30-35 (2) NC 35-40Speech Privacy Level - (1) Confidential (2) NormalArchitectural Notes - (2) 19 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 20Task Illum (FC) - (1) 100 (2) ))Luminare Type - (1) A2,J1,K (2) R1Switching - (1) Std-by Area (2) Std

Electrical Notes - 12,13,14,15,16,38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6.0 (2) 10.0Outside Air Changes - (1) 1.5 (2) 0Roam Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 75 Win 75 (2) Sum )- Win )-Relative Hum(%) (1) 30-60 (2) -Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,90,0 (2) 0,0,0

Mechanical Notes - (2) 6 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No A1110G - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 443: Army Medical Design Guide - SAFE

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A1100G Patient SVC Console - M/S 1 AA1160 IV Track 1 AA5080 Dispenser, Paper Towel 2 AA5110C Grab Bar, Toilet 36" X 48" 1 AA5110H Grab Bar, Shower, 24"X57"X24" 1 AM5115 Mirror 18 X 30 1 AM5145 Coat Hook 2 AA5170 Shower Curtain Rod 1 AA5175 Soap Dish w/Grab Bar 1 AA5180 Track & Curtain, Cubicle 1 AA5190 Toilet Paper Holder, Recessed 1 AA5205 Towel Bar, 1" Dia. 1 AA6010 Bumper, Hospital Bed 1 ACE030 Cabinet, Wall Hung 2 AC0023 Wardrobe, Single 1 AC02QO Cabinet, U/C, Sink 1 AC03EO Cabinet, U/C, Base 1 AC03JO Cabinet, U/C, Base 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L 2 AM1620 Record Holder 1 AM7405 Light, Exam, Ceiling 1 AP3070 Lavatory, Counter 1 AP5100 Shower 2'-6"X6'-0" 1 AP9050H Water Closet 1 AA5220 Bracket, TV, Wall Mounted 1 BF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 2 CM0845 Bed, Birthing 1 CM7000 Television Set 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC001 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station 1 AMDOOW Wall Outlet-48" AFF 1 AMDOOH Service Console Outlet 1 ATVOOW Wall Outlet-12" Below Ceiling 1 A

Communication Note - 17 ref pp 29-30

JULY 1994

Page 444: Army Medical Design Guide - SAFE

JULY 1994

Page 445: Army Medical Design Guide - SAFE

JULY 1994

Page 446: Army Medical Design Guide - SAFE

JULY 1994

Page 447: Army Medical Design Guide - SAFE

JULY 1994

Page 448: Army Medical Design Guide - SAFE

2.09.05 ADelivery RoomMatrix Data

Architectural/Acoustics

Square Foot Area Net - 400Finishes - Walls - CT - Base - ET - Floor - ET - Ceiling - GW-SGCeiling Ht - 9'-6"Door Size & Type - 36G,48G/18GHardware Set - H17,H16/H09Ambient Noise Level - NC 30-35Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 200Task Illum (FC) -Luminare Type - D1Switching - Std-by Area

Electrical Notes - 10,29,38 ref pp 20-23

MECHANICAL

Total Air Changes - 15Outside Air Changes - 5Room Pressure(%) - +20Temperature (F) - 68-76Relative Hum(%) - 50-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,80,90-95

Mechanical Notes - 9,13,18 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1Chilled Water - No M9600 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CWO90 Cabinet, Full Height 1 AM3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3800 Desk, Folding, Wall Mount 2 A

Page 449: Army Medical Design Guide - SAFE

M4801 Light, Surgical, Ceiling 1 AM8500 Cabinet, Warming 1 AM9600 Surgery Gas Column 1 AP6980A Scrub Station-2bay 1 AX4010 Illuminator, X-ray Film 1 AF0355 Foot Stool 1 CF2010 Waste Receptacle SS 2 CM1265 Fetal Monitor, Bedside 1 CM2640 Infant Care Center 1 CM2755 Anesthesia Apparatus 1 CM7150 Table, OB 1 CM7200 Cart, Case 1 CM7400 Table, Instrument 1 CM7405 Pail 1 CM7410 Carriage 1 CM7705 Stool, Revolving 3 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOOS Staff Station 1 ANCOEL Dome Light w/ Chime 2 ANCOEW Pushbutton 1 APAOOV Volume Control 1 APAOCM Microphone, Ceiling Mounted 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 2 ATLOOK CAPOC Outlet 1 ATSOOW Wall Outlet-36" AFF 2 ATVOCW Camera Wall Outlet 1 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 450: Army Medical Design Guide - SAFE

JULY 1988

Page 451: Army Medical Design Guide - SAFE

JULY 1988

Page 452: Army Medical Design Guide - SAFE

JULY 1988

Page 453: Army Medical Design Guide - SAFE

JULY 1988

Page 454: Army Medical Design Guide - SAFE

2.10.01 ACystoscopy SuiteMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Cystoscopy/IVP - 250 (2) Decont - 100 (3) Toilet - 30Finishes - Walls - (1) CT (2) GW-SG (3) GW-SG - Base - (1) ET (2) ET (3) CT - Floor - (1) ET (2) ET (3) CT - Ceiling - (1) GW (2) ACT (3) GWCeiling Ht - (1) 9'-6" (2) 8'-0" (3) 8'-0"Door Size & Type - (1) 36AX,48AX (2) 36A,36AX (3) 36AXHardware Set (1) H15,H15 (2) H06,H14 (3) H14Ambient Noise Level - (1) NC 30-35 (2) NC 35-40 (3) NC 35-40Speech Privacy Level (1) Normal (2) Normal (3) Normal

Architectural Notes - 17,19 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 0-70 (2) 30 (3) 20Task Illum (FC) - (1) 100 (2) )- (3) )-Luminare Type - (1) A2 (2) B1 (3) R1Switching - (1) Dim (2) Multi-Sw (3) Std

Electrical Notes - (1) 8,17 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 15 (2) 6 (3) 10Outside Air Changes - (1) 5 (2) 1.5 (3) 0Room Pressure(%) - (1) + 20 (2) -20 (3) -100Temperature (F) - (1) 68-76 (2) Sum 75 Win 75 (3) Sum - Win -Relative Hum(%) - (1) 50-60 (2) 30-60 (3) ))Exhaust Air - (1) Yes (2) Yes (3) YesReturn Air - (1) No (2) No (3) NoFiltration(%) - (1) 25,80,90-95 (2) 25,90,0

Mechanical Notes - (1) 13 (3) 6 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-13 - 1Chilled Water - NoWaste/Vent - Yes

Page 455: Army Medical Design Guide - SAFE

Floor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A1160 IV Track 1 AA4015 Clock, Elapsed Time 1 AA4020 Clock 1 AA5080 Dispenser, Paper Towel 2 AA5110C Grab Bar 1 AA5115 Mirror 18 X 30 1 AA5195 Toilet Paper Holder 1 ACE030 Cabinet, Wall Hung 1 ACC02CO Cabinet, Wall Hung 1 AC02QO Cabinet, U/C, Sink 1 AC03JO Cabinet, U/C, Base 1 AC02CO Cabinet, U/C, Base 1 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM3800 Desk, Folding, Wall Mount 1 AM7405 Light, Exam, Ceiling 1 AP3000 Lavatory, Wall Hung 1 AP6350 Sink, SVC, Wall Hung 1 AP6980A Scrub Station- 2bay 1 AP9050 Water Closet 1 AP9320 Floor Drain w/Primer 1 AX3150 Rack Apron & Glove 1 AX3990 Illuminator, X-ray Film 1 AF2010 Waste Receptacle SS 2 CM8830 Table, Instrument 1 CM8905 Pail 1 CM8900 Carriage 1 CM8810 Stand Mayo 1 CM8945 Stool, Revolving 2 CX6530 X-ray Unit-Urology 1 F A. Control Console 8. Urological Table C. Control Cabinet D. Transformer E. Wall Raceway F. Cable Raceway - Below Finish Floor

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ACCOET Elapsed Clock with Control 1 ANCOOS Staff Station 2 ANCOEL Dome Light w/ Chime 3 ANCOET Pullcord Station 1 ANCOEW Pushbutton 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet-54" AFF 2 AMDOOW Wall Outlet-48" AFF 1 ATVOCC Camera Outlet 1 A

Page 456: Army Medical Design Guide - SAFE

JULY 1988REVISED SEPTEMBER 1994

Page 457: Army Medical Design Guide - SAFE
Page 458: Army Medical Design Guide - SAFE
Page 459: Army Medical Design Guide - SAFE
Page 460: Army Medical Design Guide - SAFE
Page 461: Army Medical Design Guide - SAFE

2.10.02 AUrodynamics RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 100Finishes - Walls - GWB - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 36AHardware Set - H01Ambient Noise Level - NC 30-35Speech Privacy Level - Confidential

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A2Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - +10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

A5080 Dispenser, Paper Towel 1 AA5145 Coat Hook 1 AC02QO Cabinet, U/C, Sink 1 AC03JO Cabinet, U/C, Base 1 AC03LO Cabinet, U/C, Base 1 ACE030 Cabinet, Wall Hung 2 ACS150 Sink, SS, Counter 1 A

Page 462: Army Medical Design Guide - SAFE

CT030 Counter Top - P.L. 1 AM1160 Record Holder 1 AM5180 Track & Curtain, Cubicle 1 AF0075 Analyzer-urodynamics 1 CF0355 Foot Stool 1 CF2010 Waste Receptacle SS 1 CM3075 Cabinet, Exam Rm 1 CM9050 Table, Exam, SS 1 CM8945 Stool, Revolving 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ARSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch, 3 Button 1 AMDOOC Counter Outlet-6" Above CT 1 A

JULY 1988REVISED SEPTEMBER 1994

Page 463: Army Medical Design Guide - SAFE
Page 464: Army Medical Design Guide - SAFE
Page 465: Army Medical Design Guide - SAFE
Page 466: Army Medical Design Guide - SAFE
Page 467: Army Medical Design Guide - SAFE

Department of the Army Volume 3

Medical Design Guide

Office of the Surgeon General Office of the Chief of EngineersHealth Facility Planning Agency Medical Facilities Design Office

JULY 1988REVISED SEPTEMBER 1994

Page 468: Army Medical Design Guide - SAFE

3.01.01 ACCU BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 220Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 48EHardware Set - H10Ambient Noise Level - NC 25-30Speech Privacy Level - Normal

Architectural Notes - 20,24 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 30Task Illum (FC) - 30 (Reading) 100 (Exam)Luminare Type - A2,J1,K,M1Switching - Multi & Std-by Area

Electrical Notes - 12,13,14,15,16, 38 ref pp 20-23

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - +10Temperature (F) - 70-78Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80.0

Mechanical Notes -13,15 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5541 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CT030 Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 1 AM1980 Nurse Server U/C 1 A

Page 469: Army Medical Design Guide - SAFE

U3620 Dispenser, Paper Towel 2 AM4600D Grab Bar, Outrigger-Left 1 AM5300 Mirror 14 X 20 1 AM5541 Patient SVC Console-ICU 1 AM5960 Coat Hook 1 AM7960 Track & Curtain, Cubicle 1 AM7965 Drapery Track 1 AM8015 IV Track ICU 1 AP3100 Lavatory, Wall Hung 1 AP9150 Cabinet, Toil/Lav 1 AM8836 Wall Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 2 CM0355 Table, Overbed 1 CM0375 Bed, Hospital, ICU 1 CM8830 Television Set 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCODL Dome Light - 3 Lamp t ANCOET Emergency Pullcord Station 1 ATLOOH Wall Outlet 1 ATLOHK CAPOC Outlet 1 ATSOOH Service Console Outlet 1 ATSOOW Wall Outlet-36" AFF 1 ATVOOW Wall Outlet-12" Below Ceiling 1 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 470: Army Medical Design Guide - SAFE

JULY 1988

Page 471: Army Medical Design Guide - SAFE
Page 472: Army Medical Design Guide - SAFE

JULY 1988

Page 473: Army Medical Design Guide - SAFE

JULY 1988

Page 474: Army Medical Design Guide - SAFE

3.01.02 AICU BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 220Finishes - Walls - GW - Base - R - Floor - VCT -Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 48EHardware Set - H10Ambient Noise Level - NC 25-30Speech Privacy Level - Normal

Architectural Notes - 20,24 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 30Task Illum (FC) - 30 (Reading), 100 (Exam)Luminare Type - A2,J1,K,M1Switching - Multi-Sw & Std-by Area

Electrical Notes - 12,13,14,15,16,38 ref pp 20-23

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - +10Temperature (F) - 70-78Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,0

Mechanical Notes -13,15 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5541 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CT030 Counter Top - P.L 1 AF6010 Bumper, Hospital Bed 1 AM1980 Nurse Server U/C, 1 A

Page 475: Army Medical Design Guide - SAFE

M3620 Dispenser, Paper Towel 1 AM5541 Patient SVC Console-ICU 1 AM5960 Coat Hook 1 AM7965 Drapery Track 1 AM8015 IV Track ICU 1 AP3100 Lavatory, Wall Hung 1 AM8836 Wall Bracket, Tv 1 AF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 1 CM0355 Table, Overbed 1 CM0375 Bed, Hospital, ICU 1 CM8830 Television Set 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ATLOHK CAPOC Outlet 1 ATLOOH Wall Outlet-54" AFF 1 ATSOOH Service Console Outlet 1 ATSOOW Wall Outlet-36" AFF 1 ATVOOW Wall Outlet-12" Below Ceiling 1 A

Communication Notes - 17 ref pp 27-28

JULY 1988

Page 476: Army Medical Design Guide - SAFE

JULY 1988

Page 477: Army Medical Design Guide - SAFE

JULY 1988

Page 478: Army Medical Design Guide - SAFE

JULY 1988

Page 479: Army Medical Design Guide - SAFE

JULY 1988

Page 480: Army Medical Design Guide - SAFE

3.01.03 AICU Isolation BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) ICU 220 (2) Anteroom 50Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT (2) VCT - Ceiling - (1) ACT-2 (2) ACT-2Ceiling Height - (1) 8'-0" (2) 8'-0"Door Size & Type - (1) 48E (2) 36E,36G

Hardware Set - (1) H11 (2) H11Ambient Noise Level - (1) NC 25-30 (2) NC 35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 24 (2) 20 ref pp 5- 6

ELECTRICAL

Ambient Illum (FC) - (1) 30 (2) 30Task Illum (FC) - (1) 30 (Reading) (1) 100 (Exam)Luminare Type - (1) A2,J1,K,M1 (2) C1Switching - (1) Multi-Sw & Std-by Area (2) Std

Electrical Notes - (1) 12,13,14,15,16,38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 4Outside Air Changes - (1) 1.5 (2) 1Room Pressure(%) - (1)+20/-20 (2)-10Temperature (F) - (1) 70-78 (2) 70-78

Relative Hum(%) - (1) 50-60 (2) 30-60

Exhaust Air - (1) Yes (2) YesReturn Air - (1) No (2) NoFiltration(%) - (1) 25,80,90-95 (2) 25,80,90-95

Mechanical Notes - (1) 4,11,13 (2) 11,15 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5541 - 1Chilled Water - NoWaste Vent - YesFloor Drain - NoSteam - No

Page 481: Army Medical Design Guide - SAFE

Condensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0036 Apron Frame 22"D x 30" L 1 AC03EO Cabinet, U/C, Base 1 ACA040 Cabinet, Wall, Hung 1 ACT030 Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 1 AM1970 Nurse Server 1 AM3620 Dispenser, Paper Towel 3 AM3800 Desk, Folding, Wall Mount 1 AM4600D Grab Bar, Outrigger-Left 1 AM5300 Mirror 14 X 20 1 AM5541 Patient SVC Console-ICU 1 AM5960 Coat Hook 1 AM7960 Track & Curtain, Cubicle 1 AM7965 Drapery Track 1 AM8015 IV Track ICU 1 AP3070 Lavatory, Counter 1 AP3100 Lavatory, Wall Hung 1 AP9150 Cabinet Toil/Lav 1 AM8836 Wall Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 3 CM0355 Table, Overbed 1 CM0375 Bed, Hospital, ICU 1 CM4500 Hamper, Linen 1 CM8830 Television Set 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC001 Single Patient StationNCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOET Pullcord Station - Toilet 1 ATLOOH Wall Outlet 1 ATLOHK CAPOC Outlet 1 ATSOOH Wall Outlet 1 ATSOOW Wall Outlet-36" AFF 1 ATVOOW Wall Outlet-12" Below Ceiling 1 A

Communication Note - 17 ref pp 29-30

JULY 1988

Page 482: Army Medical Design Guide - SAFE
Page 483: Army Medical Design Guide - SAFE
Page 484: Army Medical Design Guide - SAFE
Page 485: Army Medical Design Guide - SAFE
Page 486: Army Medical Design Guide - SAFE

3.02.01 AOne Bedroom (Mob)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 170 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 4,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Exam-100, Reading-30Luminare Type - (1) A2,B2,J1,M1,P3 (2) R1Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,13,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) )

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2) -

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542A - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 487: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 1 AC0037 Apron Frame 22" D x 36" L 1 ACT030 Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 2 AM1970 Nurse Server 1 AM3620 Dispenser, Paper Towel 1 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542A Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 2 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 1 AP51OOC Shower 3'-6" X 5' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0260 Chair, Patient, Posture 1 CF0400 Cabinet, Bedside 1 CM0355 Table, Overbed 1 CM0375 Bed, Hosp., Electric 1 CM8810 Television, Bedside 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ANC002 Dual Patient Station 1 ATLOOH Service Console Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communication Notes - 17 ref. pp. 29-30

AUGUST 1989

Page 488: Army Medical Design Guide - SAFE

AUGUST 1989

Page 489: Army Medical Design Guide - SAFE
Page 490: Army Medical Design Guide - SAFE

AUGUST 1989

Page 491: Army Medical Design Guide - SAFE

AUGUST 1989

Page 492: Army Medical Design Guide - SAFE

3.02.02 ATwo Bedroom (Mob)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 250 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 7,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B2,J1,M2,K,P3 (2) R1Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,14,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) )

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2) -

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542A - 1Waste/Vent - Yes M5542B - 1Floor Drain - NoSteam - NoCondensate - No

Piping Notes - (1) 5

Page 493: Army Medical Design Guide - SAFE

ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 2 AC0037 Apron Frame 22" D x 36" L 1 ACT030 Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 3 AM1970 Nurse Server 2 AM3620 Dispenser, Paper Towel 1 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542A Patient SVC Console - M/S 1 AM5542B Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 4 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 1 AP51OOA Shower 3'-6" X 3' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 2 BF0210 Chair, Visitor 2 CF0400 Cabinet, Bedside 2 CM0355 Table, Overbed 2 CM0375 Bed, Hosp., Electric 2 CM8810 Television, Bedside 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCOO2 Dual Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 3 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 2 A

Communication Notes - 17 ref. pp. 29-30

JULY 1988

Page 494: Army Medical Design Guide - SAFE
Page 495: Army Medical Design Guide - SAFE
Page 496: Army Medical Design Guide - SAFE
Page 497: Army Medical Design Guide - SAFE

3.02.03 AFour Bedroom (Mob)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 440 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 8,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B2,J1,K,M1,P3,R2 (2) R1Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) )

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2) -

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542A - 2Waste/Vent - Yes M5542B - 2Floor Drain - NoSteam - NoCondensate - No

Piping Notes - (1) 5

Page 498: Army Medical Design Guide - SAFE

ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 4 AC0039 Apron Frame 22" D x 36" L 2 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 6 AM1970 Nurse Server 4 AM3620 Dispenser, Paper Towel 1 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 2 AM5542A Patient SVC Console - M/S 2 AM5542B Patient SVC Console - M/S 2 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 8 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 2 AP51OOA Shower 3'-6" X 4' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 4 BF0210 Chair, Visitor 4 CF0400 Cabinet, Bedside 2 CM0355 Table, Overbed 4 CM0375 Bed, Hosp., Electric 4 CM8810 Television, Bedside 4 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 2 ANCOO2 Dual Patient Station 2 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 6 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 4 A

Communication Notes - 17 ref. pp. 29-30

JULY 1988

Page 499: Army Medical Design Guide - SAFE
Page 500: Army Medical Design Guide - SAFE
Page 501: Army Medical Design Guide - SAFE
Page 502: Army Medical Design Guide - SAFE
Page 503: Army Medical Design Guide - SAFE

3.02.04 AFour Bedroom ALT (Mob)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 440 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 8,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B2,J1,K,M2,P3 (2) R1Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) )

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2) -

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542A - 2Waste/Vent - Yes M5542B - 2Floor Drain - NoSteam - NoCondensate - No

Piping Notes - (1) 5

Page 504: Army Medical Design Guide - SAFE

ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 4 AC0036 Apron Frame 22" D x 30" L 1 AC0038 Apron Frame 22" D x 42" L 1 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 6 AM1970 Nurse Server 4 AM3620 Dispenser, Paper Towel 2 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 2 AM5542A Patient SVC Console - M/S 2 AM5542B Patient SVC Console - M/S 2 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 8 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 2 AP5100A Shower 3'-6" X 4' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 4 BF0210 Chair, Visitor 4 CF0400 Cabinet, Bedside 2 CM0355 Table, Overbed 4 CM0375 Bed, Hosp., Electric 4 CM8810 Television, Bedside 4 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 2 ANCOO2 Dual Patient Station 2 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet 4 ATSOOW Wall Outlet-36" AFF-N.P. 1 ATVOOB Wall Outlet, Bedside-48" AFF 4 A

Communication Notes - 17 ref. pp. 29-30

JULY 1988

Page 505: Army Medical Design Guide - SAFE
Page 506: Army Medical Design Guide - SAFE
Page 507: Army Medical Design Guide - SAFE
Page 508: Army Medical Design Guide - SAFE
Page 509: Army Medical Design Guide - SAFE

3.02.05 AIsolation BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 140 (2) Toilet - 60 (3) Ante Rm - 60Finishes - Walls - (1) GW (2) GW-SG (3) GW - Base - (1) R (2) CT (3) R - Floor - (1) VCT (2) CT (3) VCT - Ceiling - (1) ACT (2) GW (3) ACTCeiling Ht - (1) 8'-0" (2) 8'-0" (3) 8'-0"Door Size & Type - (1) 48A (2) 36A (3) 48EHardware Set - (1) H10 (2) H13 Ambient Noise Level - (1) NC30-35 (2) (3) NC35-40Speech Privacy Level - (1) Normal (2) (3) Normal

Architectural Notes - (1) 14,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20 (3) 30Task Illum (FC) - (1) Exam-100, Reading-30Luminare Type - (1) A2,J1,M1,P1,P3 (2) R1 (3) C1,P3Switching - (1) Multi-Sw & Std by Area (2) Std (3) Std by Area

Electrical Notes - (1) 12,13,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 10 (3) 4Outside Air Changes - (1) 1.5 (2) 0 (3) 1Room Pressure(%) - (1) +20/-20 (2) -100 (3) -10 Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win - (3) Sum 78 Win 70

Relative Hum(%) - (1) 30-60 (2) ) (3) 30-60Exhaust Air - (1) Yes (2) Yes (3) YesReturn Air - (1) No (2) No (3) NoFiltration(%) - (1) 25,80,0 (2) - (3) 25,80,0

Mechanical Notes - (1) 11,4 (2) 6,11 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542 - 1Waste/Vent - YesFloor Drain - NoSteam - No

Page 510: Army Medical Design Guide - SAFE

Condensate - No

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 1 AC0035 Apron Frame 22" D x 24" L 1 AC0036 Apron Frame 22" D x 30" L 1 ACA020 Cabinet, Wall Hung 1 ACT030 Counter Top - P.L. 2 AF6010 Bed Bumper 1 AM1970 Nurse Server 1 AM3620 Dispenser, Paper Towel 1 AM3800 Desk, Folding, Wall Mount 1 AM4600C Grab Bar, Toilet 36" x 48" 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542 Patient SVC Console - Isol 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1150 Rinse Valve, Bedpan 1 AP3070 Lavatory, Counter 2 AP5100C Shower 3'-6" X 5' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0297 Shower Curtain 1 CF0400 Cabinet, Bedside 1 CF2010 Waste Receptacle SS 1 CM0355 Table, Overbed 1 CM0375 Bed, Hosp., Electric 1 CM4500 Hamper Linen 1 CM8810 Television, Bedside 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communication Notes - 17 ref. pp. 29-30

Page 511: Army Medical Design Guide - SAFE

JULY 1988

Page 512: Army Medical Design Guide - SAFE
Page 513: Army Medical Design Guide - SAFE
Page 514: Army Medical Design Guide - SAFE

3.02.06 APed-One Bedroom (Mob)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 170 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48E (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 10,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FCC) - (1) Exam-100, Reading-30Luminare Type - (1) A2,J1,K,M1,P3,R2 (2) R1

Switching - (1) Std by Area (2) Std

Electrical Notes - (1) 12,13,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration - (1) 25,8,0 (2) -

Mechanical Notes - (1) 15 (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542A - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 515: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 2 AC0036 Apron Frame 22" D x 30" L 1 AC0038 Apron Frame 22" D x 42" L 1 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 3 AM1980 Nurse Server U/C 1 AM3620 Dispenser, Paper Towel 2 AM4600H Grab Bar, Shower 1 AM4600J Grab Bar, Tub 1 AM5300A Mirror 24 X 30 1 AM5542B Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM69OO Soap Dish w/ Grab Bar 1 AM7560 Track & Curtain, Cubicle 3 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1060 Bath Tub, Childs 1 AP3070 Lavatory, Counter 1 AP9050 Water Closet 1 AP9130 Bath Sink, Infant 1 AM8825 Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0400 Cabinet, Bedside 1 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 1 CM0375 Bed, Hospital, Electric 1 CM8810 Television, Bedside 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC002 Dual Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 2 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communication Notes - 17 ref. pp. 29-30

FEBRUARY 1990

Page 516: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 517: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 518: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 519: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 520: Army Medical Design Guide - SAFE

3.02.07 APed-Two Bedroom (Mob)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 250 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48E (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 11,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) J1,K,M2,P3,R2 (2) R1

Switching - (1) Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration - (1) 25,8,0 (2) -

Mechanical Notes - (1) 15 (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542A - 1Waste/Vent - Yes M5542B - 1Floor Drain - NoSteam - NoCondensate - No

Page 521: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 1 AC0038 Apron Frame 22" D x 42" L 1 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 2 AM1970 Nurse Server 1 AM1980 Nurse Server U/C, 1 AM3620 Dispenser, Paper Towel 2 AM4600J Grab Bar, Tub 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542A Patient SVC Console - M/S 1 AM5542B Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7560 Track & Curtain, Cubicle 4 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1060 Bath Tub, Childs 1 AP3070 Lavatory, Counter 1 AP9050 Water Closet 1 AP9130 Bath Sink, Infant 1 AM8825 Bracket, Tv 2 BF0210 Chair, Visitor 2 CF0400 Cabinet, Bedside 2 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 2 CM0375 Bed, Hospital, Electric 2 CM8810 Television, Bedside 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC001 Single Patient Station 1 ANC002 Dual Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-36" AFF 2 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communication Notes - 17 ref. pp. 29-30

JULY 1988

Page 522: Army Medical Design Guide - SAFE
Page 523: Army Medical Design Guide - SAFE
Page 524: Army Medical Design Guide - SAFE
Page 525: Army Medical Design Guide - SAFE
Page 526: Army Medical Design Guide - SAFE

3.02.08 APed-Four Bedroom (Mob)Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 440 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48E (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 12,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B2,J1,K,M2,R2 (2) P3,R1

Switching - (1) Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration - (1) 25,8,0 (2) -

Mechanical Notes - (1) 15 (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542A - 2Waste/Vent - Yes M5542B - 2Floor Drain - NoSteam - NoCondensate - No

Page 527: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 4 AC0037 Apron Frame 22" D x 36" L 1 AC0038 Apron Frame 22" D x 48" L 2 ACT030 Counter Top - P.L. 3 AF6010 Bumper, Hospital Bed 6 AM1970 Nurse Server 2 AM1980 Nurse Server U/C, 2 AM3620 Dispenser, Paper Towel 2 AM4600J Grab Bar, Tub 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542A Patient SVC Console - M/S 2 AM5542B Patient SVC Console - M/S 2 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6CJOO Soap Dish w/ Grab Bar 1 AM7560 Track & Curtain, Cubicle 8 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1060 Bath Tub, Childs 1 AP3070 Lavatory, Counter 1 AP9050 Water Closet 1 AP9130 Bath Sink, Infant 1 AM8825 Bracket, Tv 4 BF0210 Chair, Side 6 CF0220 Chair, Converta-Bed 2 CF0400 Cabinet, Bedside 4 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 4 CM0375 Bed, Hospital, Electric 4 CM8810 Television, Bedside 4 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC001 Single Patient Station 2 ANC002 Dual Patient Station 2 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 6 ATSOOC Counter Outlet-6" Above 1 ATVOOB Wall Outlet, Bedside-48" AFF 4 A

Communication Notes - 17 ref. pp. 29-30

FEBRUARY 1990

Page 528: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 529: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 530: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 531: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 532: Army Medical Design Guide - SAFE

3.02.09 APed-Isolation Bedroom Matrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 140 (2) Toilet - 60 (3) Ante Rm - 60Finishes - Walls - (1) GW (2) GW-SG (3) GW - Base (1) R (2) CT (3) R - Floor - (1) VCT (2) CT (3) VCT - Ceiling - (1) ACT (2) GW (3) ACTCeiling Ht - (1) 8'-0" (2) 8'-0" (3) 8'-0"Door Size & Type - (1)(3)48A (2) 36AHardware Set - (1)(3)H11 (2) H13Ambient Noise Level - (1)(3)NC30-35 (2) NC35-40Speech Privacy Level - (1)(2)(3) Normal

Architectural Notes - (1) 13,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20 (3) 30Task Illum (FC) - (1) Exam-100, Reading-30Luminare Type - (1) A2,J1,K,M1 (2) P3,R1 (3) B1Switching - (1) Multi-Sw by Area (2) Std (3) Std by Area

Electrical Notes - (1) 12,13,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 10 (3) 4Outside Air Changes - (1) 1.5 (2) 0 (3) 1Room Pressure(%) - (1) 0 (2) -100 (3) -10 Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win - (3) Sum 78 Win 70Relative Hum(%) - (1) 30-60 (2) - (3) 30-60Exhaust Air - (1) Yes (2) Yes (3) YesReturn Air - (1) No (2) No (3) NoFiltration - (1) 25,8,0 (2) - (3) 25,8,0

Mechanical Notes - (1) 11,4 (2) 6 (3) 11,15 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 533: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 1 AC0037 Apron Frame 22" D x 36" L 2 AC02QO Cabinet, U/C, Sink 1 AC05EO Cabinet, U/C, Base 1 ACA020 Cabinet, Wall Hung 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 3 AF6010 Bed Bumper 1 AM1980 Nurse Server U/C 1 AM3620 Dispenser, Paper Towel 2 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5S42 Patient SVC Console - Isol 1 AM5960 Coat Hook 1 AM6880 Shower Curtain Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1060 Bath Tub, Childs 1 AP1150 Rinse Valve, Bedpan 1 AP9050 Water Closet 1 AP9130 Bath Sink, Infant 1 AM8825 Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0297 Shower Curtain 1 CF0400 Cabinet, Bedside 1 CF2000 Waste Receptacle, Off 1 CF2310 Waste Receptacle, SS 1 CM0355 Table, Overbed 1 CM0375 Bed, Hosp., Electric 1 CM4500 Hamper, Linen 1 CM8810 Television, Bedside 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 1 ATSOOC Counter Outlet-6" Above 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communication Notes - 17 ref. pp.28-30 FEBRUARY 1990

Page 534: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 535: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 536: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 537: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 538: Army Medical Design Guide - SAFE

3.03.01 ASeclusion RoomMatrix Room

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 140 (2) Toilet - 60 (3) Ante Rm - 60Finishes - Walls - (1) GW (2) GW-SG (3) GW - Base (1) R (2) CT (3) R - Floor - (1) VCT (2) CT (3) VCT - Ceiling - (1) GW (2) GW (3) GW Ceiling Ht - (1) 8'-0" (2) 8'-0" (3) 8'-0"Door Size & Type - (1) 48A (2) 36A (3) 48GHardware Set - (1) H11 (2) H13 (3) H10 Ambient Noise Level - (1) NC30-35 (2)(3) NC35-40Speech Privacy Level - (1)(2)(3) Normal

Architectural Notes - (1) 9,15,19 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20 (3) 30Task Illum (FC) - (1) - (2) - (3) - Luminare Type - (1) U,V (2) R1 (3) P3,R1Switching - (1) Std (2) Std (3) Std

Electrical Notes - (1) 16 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 10 (3) 4Outside Air Changes - (1) 1.5 (2) 0 (3) 1Room Pressure(%) - (1) 0 (2) -100 (3) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win - (3) Sum 78 Win 70Relative Hum(%) - (1) 30-60 (2) - (3) 30-60Exhaust Air - (1) No (2) Yes (3) No Return Air - (1) Yes (2) No (3) YesFiltration - (1) 25,8,0 (2) - (3) 25,8,0

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 539: Army Medical Design Guide - SAFE

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 1 AC0035 Apron Frame 22" D x 24" L 1 ACT030 Counter Top - P.L. 2 AM1970 Nurse Server 1 AM3620 Dispenser, Paper Towel 1 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5400 Mirror, Acrylic 24 X 30 1 AM5960 Coat Hook 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 2 AP5100A Shower 3'-6" x 3' 1 AP9050 Water Closet 1 AF0105 Bed, Hospital, Manual 1 CF2000 Waste Receptacle, Off 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOCS Ceiling Speaker/Microphone 1 ANCOEL Dome Light W/ Chime 1 ANCOEW Pushbutton 3 ANCOKS Key Switch 1 ATSOOW Wall Outlet-36" AFF 1 A

Communication Notes - 17 ref. pp. 29-30

AUGUST 1989

Page 540: Army Medical Design Guide - SAFE

AUGUST 1989

Page 541: Army Medical Design Guide - SAFE

AUGUST 1989

Page 542: Army Medical Design Guide - SAFE

AUGUST 1989

Page 543: Army Medical Design Guide - SAFE

AUGUST 1989

Page 544: Army Medical Design Guide - SAFE

3.04.01 AOne BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 150 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 4,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Exam-100, Reading-30Luminare Type - (1) A2,F2,J1,K,P3 (2) R1

Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,13,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2) -

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542E - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 545: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 1 AC0037 Apron Frame 22" D x 36" L 1 ACT030 Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 1 AM1970 Nurse Server 1 AM3620 Dispenser, Paper Towel 1 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542E Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 1 AP5100C Shower 3'-6" X 5' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0260 Chair, Patient, Posture 1 CF0400 Cabinet, Bedside 1 CF2000 Waste Receptacle, Off 1 CM0355 Table, Overbed 1 CM0375 Bed, Hosp., Electric 1 CM8810 Television, Bedside 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communication Notes - 17ref. pp. 29-30

AUGUST 1989

Page 546: Army Medical Design Guide - SAFE

AUGUST 1989

Page 547: Army Medical Design Guide - SAFE

AUGUST 1989

Page 548: Army Medical Design Guide - SAFE

AUGUST 1989

Page 549: Army Medical Design Guide - SAFE

AUGUST 1989

Page 550: Army Medical Design Guide - SAFE

3.04.02 ATwo BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 220 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 7,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B2,J1,K,P3 (2) R1

Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2) -

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542F - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 551: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 2 AC0037 Apron Frame 22" D x 36" L 1 ACT030 Counter Top - P.L. 1 AF6010 Bumper, Hospital Bed 2 AM1970 Nurse Server 2 AM3620 Dispenser, Paper Towel 1 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542E Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 2 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 1 AP5100C Shower 3'-6" X 3' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 2 BF0210 Chair, Visitor 2 CF0260 Chair, Patient, Posture 2 CF0400 Cabinet, Bedside 2 CF2000 Waste Receptacle, Off 1 CM0355 Table, Overbed 2 CM0375 Bed, Hosp., Electric 2 CM8810 Television, Bedside 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 2 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 2 A

Communication Notes - 17 ref. pp. 29-30

FEBRUARY 1990

Page 552: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 553: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 554: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 555: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 556: Army Medical Design Guide - SAFE

3.04.03 AFour BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 440 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 8,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B2,J1,K,P3,R2 (2) R1

Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2) -

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542F - 2Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 557: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 4 AC0037 Apron Frame 22" D x 36" L 2 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 4 AM1970 Nurse Server 4 AM3620 Dispenser, Paper Towel 1 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 2 AM5542E Patient SVC Console - M/S 2 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 4 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 2 AP5100C Shower 4'-0" X 3'-6" 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 4 BF0210 Chair, Visitor 4 CF0260 Chair, Patient, Posture 4 CF0400 Cabinet, Bedside 4 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 4 CM0375 Bed, Hosp., Electric 4 CM8810 Television, Bedside 4 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO2 Single Patient Station 2 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 4 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 4 A

Communication Notes - 17 ref. pp. 29-30

FEBRUARY 1990

Page 558: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 559: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 560: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 561: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 562: Army Medical Design Guide - SAFE

3.04.04 AFour Bedroom, ALTMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 440 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 8,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B2,J1,J2,K,P3 (2) R1

Switching - (1) Multi-Sw & Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1) 25,80,0 (2)

Mechanical Notes - (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542F - 2Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 563: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 4 AC0036 Apron Frame 22" D x 30" L 1 AC0038 Apron Frame 22" D x 42" L 1 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 4 AM1970 Nurse Server 4 AM3620 Dispenser, Paper Towel 2 AM4600H Grab Bar, Shower 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 2 AM5542E Patient SVC Console - M/S 2 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 4 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP3070 Lavatory, Counter 2 AP5100C Shower 3'-6" X 4' 1 AP9050 Water Closet 1 AM8825 Bracket, Tv 4 BF0210 Chair, Visitor 4 CF0260 Chair, Patient, Posture 4 CF0400 Cabinet, Bedside 4 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 4 CM0375 Bed, Hosp., Electric 4 CM8810 Television, Bedside 4 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO2 Single Patient Station 2 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 4 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 4 A

Communication Notes - 17 ref. pp. 29-30

FEBRUARY 1990

Page 564: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 565: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 566: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 567: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 568: Army Medical Design Guide - SAFE

3.04.05 APed-One BedroomMatrix Data

Square Foot Area Net - (1) Bedroom - 150 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48E (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 10,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Exam-100, Reading-30Luminare Type - (1) A2,J1,K,P3,R2 (2) R1

Switching - (1) Multi Sw & Std by Area (2) Std

Electrical Notes - (1) 12,13,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration - (1) 25,8,0 (2) -

Mechanical Notes - (1) 15 (2) 6 ref. pp. 13-15

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542E - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - (1) 5 ref. pp. 16

Page 569: Army Medical Design Guide - SAFE

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cot

C0023 Wardrobe, Single 1 AC0036 Apron Frame 22" D x 30" L 1 AC0038 Apron Frame 22" D x 42" L 1 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 1 AM1980 Nurse Server U/C, 1 AM3620 Dispenser, Paper Towel 2 AM4600J Grab Bar, Tub 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542E Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain & Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1060 Bath Tub, Child 1 AP3070 Lavatory, Counter 1 AP9050 Water Closet 1 AP9130 Bath Sink, Infant 1 AM8825 Bracket, Tv 1 BF0210 Chair, Visitor 1 CF0220 Chair, Converta-Bed 1 CF040D Cabinet, Bedside 1 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 1 CM0375 Bed, Hosp, Electric 1 CM8810 Television, Bedside 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcard Station, Emer 1 ATLOOH Service Console Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 1 A

Communication Notes - 17 ref. pp. 29- C

JULY 1988

Page 570: Army Medical Design Guide - SAFE
Page 571: Army Medical Design Guide - SAFE
Page 572: Army Medical Design Guide - SAFE
Page 573: Army Medical Design Guide - SAFE
Page 574: Army Medical Design Guide - SAFE

3.04.06 APed-Two BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 220 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48E (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 11,25 ref pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) J1,K,P3,R2 (2) R1

Switching - (1) Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration(%) - (1)25,80,0 (2) -

Mechanical Notes - (1) 15 (2) 6 ref. pp. 13-1

MECHANICAL PIPING

Cold Water - YesHotWater - Yes QtyTreated Water - NoChilled Water - No M5542F - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 575: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 2 AC0037 Apron Frame 22" D x 36" L 1 ACT030 Counter Top - P.L. 2 AF6010 Bumper, Hospital Bed 2 A M1970 Nurse Server 1 AM1980 Nurse Server U/C, 1 AM3620 Dispenser, Paper Towel 2 AM4600J Grab Bar, Tub 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542F Patient SVC Console - M/S 1 AM5960 Coat Hook 1 AM6880 Shower Curtain and Rod 1 AM6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 2 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1060 Bath Tub, Childs 1 AP3070 Lavatory, Counter 1 AP9050 Water Closet 1 AP9130 Bath Sink, Infant 1 AM8825 Bracket, TV 2 BF0210 Chair, Visitor 2 CF0400 Cabinet, Bedside 2 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 2 CM0375 Bed, Hospital, Electric 2 CM8810 Television, Bedside 2 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NC002 Dual Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ATLOOH Service Console outlet-54" AFF 2 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 2 A

Communication Notes - 17 ref. pp. 29- 30

FEBRUARY 1990

Page 576: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 577: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 578: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 579: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 580: Army Medical Design Guide - SAFE

3.04.07 APed-Four BedroomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Bedroom - 440 (2) Toilet - 60

Finishes - Walls - (1) GW (2) GW-SG - Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-0" (2) 8'-0"

Door Size & Type - (1) 48E (2) 36AHardware Set - (1) H10 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - (1) 12,25 ref. pp. 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 10 (2) 20Task Illum (FC) - (1) Reading-30Luminare Type - (1) B1,J2,K,R2 (2) P3,R1

Switching - (1) Std by Area (2) Std

Electrical Notes - (1) 12,14,15,16,38 ref. pp. 20-23

MECHANICAL

Total Air Changes - (1) 4 (2) 10Outside Air Changes - (1) 1 (2) 0Room Pressure(%) - (1) 0 (2) -100Temperature (F) - (1) Sum 78 Win 70 (2) Sum - Win -

Relative Hum(%) - (1) 30-60 (2) -

Exhaust Air - (1) No (2) YesReturn Air - (1) Yes (2) NoFiltration - (1) 25,80,0 (2) -

Mechanical Notes - (1) 15 (2) 6 ref. pp. 13-1

MECHANICAL PIPING

Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No M5542F - 2Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Page 581: Army Medical Design Guide - SAFE

Piping Notes - (1) 5 ref. pp. 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0023 Wardrobe, Single 4 AC0037 Apron Frame 22" D x 36" L 1 AC0039 Apron Frame 22" D x 48" L 2 ACT030 Counter Top - P.L 3 AF6010 Bumper, Hospital Bed 4 AM1970 Nurse Server 2 AM1980 Nurse Server U/C 2 AM3620 Dispenser, Paper Towel 2 AM4600J Grab Bar, Tub 1 AM4600M Grab Bar, Straddle 1 AM5300A Mirror 24 X 30 1 AM5542F Patient SVC Console - M/S 2 AM5960 Coat Hook 1 AM6880 Shower Curtain and Rod 1 AM6900 Soap Dish w, Grab Bar 1 AM7960 Track & Curtain, Cubicle 4 AM7965 Drapery Track 1 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 1 AP1060 Bath Tub, Childs 1 AP3070 Lavatory, Counter 1 AP9050 Water Closet 1 AP9130 Bath Sink, Infant 1 AM8825 Bracket, Tv 4 BF0210 Chair, Visitor 4 CF0220 Chair, Converta-Bed 2 CF0400 Cabinet, Bedside 4 CF2000 Waste Receptacle, Off 2 CM0355 Table, Overbed 4 CM0375 Bed, Hosp., Electric 4 CM8810 Television, Bedside 4 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Cat

NCOO1 Single Patient Station 1 ANC002 Dual Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station. Emer 1 ATLOOH Service Console outlet-36" AFF 2 ATSOOW Wall Outlet-36" AFF 1 ATVOOB Wall Outlet, Bedside-48" AFF 2 A

Communication Notes - 17 ref .pp. 29-30

FEBRUARY 1990

Page 582: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 583: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 584: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 585: Army Medical Design Guide - SAFE

FEBRUARY 1990

Page 586: Army Medical Design Guide - SAFE

3.05.01 ANormal Newborn NurseryMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 30 per bassinetFinishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - ACTCeiling Ht - 9'-0"Door Size & Type - 36E,48EHardware Set - H07,H10Ambient Noise Level - NC 25-30Speech Privacy Level - Normal

Architectural Notes - 21,24 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 70 Color CorrectedTask Illum (FC) - -Luminare Typo - R3Switching - Ext, Multi-Sw

Electrical Notes - 30 ref pp 20-23

MECHANICAL

Total Air Changes - 12Outside Air Chances - 3Room Pressure(%) - +20Temperature (F) - 75-80Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,90-95

Mechanical Notes - 13 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 6 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0045 Drawer Unit, Double - 36" L 1 AC06DO Cabinet, U/C, Base 1 AC06MO Cabinet, U/C, Base 1 A

Page 587: Army Medical Design Guide - SAFE

CT030 Counter Top - P.L 1 AM3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3620 Dispenser, Paper Towel 1 AP3100 Lavatory, Wall Hung 1 AF2010 Waste Receptacle SS 1 CM2705 Bassinet 6 CM4500 Hamper, Linen 1 CM4700 Light, Exam, Mobile 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOOS Staff Station 1 ANCOEL Dome Light w/ Chime 2 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOC Counter Outlet-6" Above 1 A

JULY 1988

Page 588: Army Medical Design Guide - SAFE

JULY 1988

Page 589: Army Medical Design Guide - SAFE

JULY 1988

Page 590: Army Medical Design Guide - SAFE

JULY 1988

Page 591: Army Medical Design Guide - SAFE

JULY 1988

Page 592: Army Medical Design Guide - SAFE

3.05.02 AAdm/Obs/Cont Care NurseryMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 30 per bassinetFinishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - ACTCeiling Ht - 9'-0"Door Size & Type - 36E,48EHardware Set - H19,H10Ambient Noise Level - NC 25-30Speech Privacy Level - Normal

Architectural Notes - 22 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 70 Color CorrectedTask Illum (FC) - -Luminare Typo - R3Switching - Ext, Multi-Sw

Electrical Notes - 31 ref pp 20-23

MECHANICAL

Total Air Changes - 12Outside Air Chances - 3Room Pressure(%) - +20Temperature (F) - 75-80Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,90-95

Mechanical Notes - 13 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No MG-3 - 3Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 7 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C0045 Drawer Unit, Double - 36" L 1 A

Page 593: Army Medical Design Guide - SAFE

C06DO Cabinet, U/C, Base 1 AC06MO Cabinet, U/C, Base 1 ACT030 Counter Top - P.L 1 AM3150 Clock, Elapsed Time 1 AM3162 Clock 1 AM3620 Dispenser, Paper Towel 1 AP3100 Lavatory, Wall Hung 1 AF2010 Waste Receptacle SS 1 CM2705 Bassinet 6 CM4500 Hamper, Linen 1 CM4700 Light, Exam, Mobile 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

CCOOW Wall Outlet 1 ANCOOS Staff Station 1 ANCOEL Dome Light w/ Chime 2 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOC Counter Outlet-6" Above 1 A

JULY 1988

Page 594: Army Medical Design Guide - SAFE

JULY 1988

Page 595: Army Medical Design Guide - SAFE

JULY 1988

Page 596: Army Medical Design Guide - SAFE

JULY 1988

Page 597: Army Medical Design Guide - SAFE

JULY 1988

Page 598: Army Medical Design Guide - SAFE

3.05.03 AIntermed Care NurseryMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 50 per bassinetFinishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - GW-SGCeiling Ht - 9'-0"Door Size & Type - 48EHardware Set - H10Ambient Noise Level - NC 25-30Speech Privacy Level - Normal

Architectural Notes - 22,24,33 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 70 Task Illum (FC) - -Luminare Typo - A2Switching - Ext & Multi-Sw

Electrical Notes - 38,40,41,44 ref pp 20-23

MECHANICAL

Total Air Changes - 12Outside Air Chances - 3Room Pressure(%) - +20Temperature (F) - 75-80Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,90-95

Mechanical Notes - 13,19 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5543 - 6Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M3620 Dispenser, Paper Towel 2 AM5543 Service Console ICU - Nursery 6 AP3100 Lavatory, Wall Hung 2 A

Page 599: Army Medical Design Guide - SAFE

F2010 Waste Receptacle SS 1 CM2560 Incubator, Infant 6 CM4500 Hamper, Linen 1 CM4700 Light, Exam, Mobile 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOOS Staff Station 1 ANCOEL Dome Light w/ Chime 3 ANCOEW Pushbutton, Emergency 6 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 3 ATLOOW Wall Outlet-54" AFF 1 ATSOOD Wall Outlet-18" AFF 1 ATSOOH Service Console Outlet 6 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 600: Army Medical Design Guide - SAFE

JULY 1988

Page 601: Army Medical Design Guide - SAFE

JULY 1988

Page 602: Army Medical Design Guide - SAFE

JULY 1988

Page 603: Army Medical Design Guide - SAFE

JULY 1988

Page 604: Army Medical Design Guide - SAFE

3.05.04 AICU NurseryMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 80 per bassinetFinishes - Walls - GW-SG - Base - IV - Floor - SV - Ceiling - ACTCeiling Ht - 9'-0"Door Size & Type - 36G,48EHardware Set - H20,H10Ambient Noise Level - NC 25-30Speech Privacy Level - Normal

Architectural Notes - 22,24,33 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 70 Color CorrectedTask Illum (FC) - -Luminare Typo - A2Switching - Ext & Multi-Sw

Electrical Notes - 32,38,41,44 ref pp 20-23

MECHANICAL

Total Air Changes - 12Outside Air Chances - 3Room Pressure(%) - +20Temperature (F) - 75-80Relative Hum(%) - 50-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,90-95

Mechanical Notes - 13,19 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5543A - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M3620 Dispenser, Paper Towel 2 AM5543A Service Console - Nursery 6 AP3100 Lavatory, Wall Hung 2 A

Page 605: Army Medical Design Guide - SAFE

F2010 Waste Receptacle SS 1 CM2640 Infant Care Center 6 CM4500 Hamper, Linen 1 CM4700 Light, Exam, Mobile 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOOS Staff Station 1 ANCOEL Dome Light w/ Chime 4 ANCOEW Pushbutton, Emergency 6 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 3 ATLOOW Wall Outlet-54" AFF 1 ATLOOW Wall Outlet-18" AFF 1 ATSOOH Service Console Outlet 6 A

Communications Notes - 17 ref pp 29-30

JULY 1988

Page 606: Army Medical Design Guide - SAFE

Figure 67

JULY 1988

Page 607: Army Medical Design Guide - SAFE

JULY 1988

Page 608: Army Medical Design Guide - SAFE

JULY 1988

Page 609: Army Medical Design Guide - SAFE

JULY 1988

Page 610: Army Medical Design Guide - SAFE

3.05.05 AIsolation NurseryMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Isolation - 10 (2) Ante - 50Finishes - Walls - (1) GW-SG (2) GW-SG - Base - (1) IV (2) IV - Floor - (1) SV (2) SV - Ceiling - (1) ACT-2 (2) ACT-2Ceiling Ht (1) 8'-0" (2) 8'-0"Door Size & Type - (1) 36E,48A (2) 36GHardware Set - (1) H10,H11 (2) H10Ambient Noise Level - (1) NC 25-30 (2) NC 35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - 24 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - (1) 70 (2) 30Task Illum FC - (1) - (2) -Luminare Type - (1) D2 (2) C1

Switching - (1) Multi-Sw (2) Std

Electrical Notes - 29,38 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 12 (2) 12Outside Air Changes - (1) 3 (2) 3Room Pressure(%) - (1) +20 /-20 (2) -10Temperature (F) - (1) 75-80 (2) 75-80Relative Hum(%) - (1) 50-60 (2) 50-60Exhaust Air - (1) Yes (2) YesReturn Air - (1) No (2) NoFiltration(%) - (1) 25,80,90-95 (2) 25 80,90-95

Mechanical Notes - (1) 11,13 ref pp 13-15

MECHANICAL PIPING

Cold Water - Yes QtyHot Water - YesTreated Water - No M5543 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes - 5 ref pp 16

Page 611: Army Medical Design Guide - SAFE

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

CA020 Cabinet, WAll Hung 1 AC01DO Cabinet, U/C, Base 1 AC02CO Cabinet, U/C, Base 1 ACTO3O Counter Top - P.L. 1 AM3620 Dispenser, Paper Towel 2 AM5543 Service Console ICU - Nursery 1 AP3100 Lavatory, Wall Hung 2 AF2010 Waste Receptacle SS 2 CM2560 Incubator, Infant 1 CM4500 Hamper, Linen 1 CM7400 Table, Instrument 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOO1 Single Patient Station 1 ANCOOS Staff Station 1 ANCOEL Dome Light w/o Chime 1 ANCOEW Pushbutton 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet-54" AFF 2 ATSOOC Counter Outlet 1 ATSOOH Service Console Outlet 1 A

Communication Notes - 17 ref pp 29-30

JULY 1988

Page 612: Army Medical Design Guide - SAFE
Page 613: Army Medical Design Guide - SAFE
Page 614: Army Medical Design Guide - SAFE
Page 615: Army Medical Design Guide - SAFE
Page 616: Army Medical Design Guide - SAFE

3.06.01 ANurses StationMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - (1) Workroom - 150 (2) Team Center - 200Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT (2) VCT - Ceiling - (1) ACT (2) ACTCeiling Ht - (1) 8'-0" (2) 8'-0"Door Size & Type - (1) 36AHardware Set - (1) H10Ambient Noise Level - (1) NC 35-40 (2) NC 35-40Speech Privacy Level - (1) Normal (2) Normal

Architectural Notes - 23,24 ref pp 5- 6

ELECTRICAL

Ambient Illum (FC) - (1) 50 (2) 30 Task Illum (FC) - (1) - (2) 70Luminare Type - (1) B1 (2) C1,L1,Q1Switching - (1) Std (2) Ext, Multi-Sw & Std-by Area

Electrical Notes - 33 ref pp 20-23

MECHANICAL

Total Air Changes - (1) 6 (2) 6Outside Air Changes - (1) 1.5 (2) 1.5Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70Relative Hum(%) - (1) 30-60 - (2) 30-60Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,80,0 (2) 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - NoHot Water - NoTreated Water - NoChilled Water - NoWaste/Vent - NoFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

Page 617: Army Medical Design Guide - SAFE

M1860 Bulletin Board 1 AM1870 Magnetic Scheduling Board 1 AM3160 Clock 1 AX3930 Illuminator, X-ray Film 1 AFO115 Bookcase 1 CF0280 Chair, Rotary w/Arms 6 CF0300 Chair, Rotary w/o Arms 3 CF0405 Cabinet, Filing 1 CF0750 Table, Conference 1 CF2000 Waste Receptacle, Off 2 CM2800 Cart, Chart Holder 1 CE2500 Nurses Station, Modular 1 E

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOOD Duty Station 1 ANCOOM Master Control Station 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOC Counter Outlet-6" Above CT 3 ATLOOK CAPOC Outlet 1 ATLOOW Wall Outlet-54" AFF 1 ATLOFX Facsimile Outlet-18" AFF 1 ATSOOC Counter Outlet-6" Above 3 ATSOOD Wall Outlet-18" AFF 1 A

JULY 1988

Page 618: Army Medical Design Guide - SAFE
Page 619: Army Medical Design Guide - SAFE
Page 620: Army Medical Design Guide - SAFE
Page 621: Army Medical Design Guide - SAFE
Page 622: Army Medical Design Guide - SAFE

3.06.02 ANurses Station-CCU/ICUMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 250Finishes - Walls - GW - Base - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type -Hardware Set -Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes - 23,24 ref pp 5-6

ELECTRICAL

Ambient Illum (FC) - 30Task Illum (FC) - 70Luminare Type - B1,L1,Q1Switching - Std-by Area

Electrical Notes - 33,34 ref pp 20-23

MECHANICAL

Total Air Changes - 6.0Outside Air Changes - 1.5Room Pressure(%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - NoHot Water - NoTreated Water - NoChilled Water - NoWaste/Vent - NoFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M1860 Bulletin Board 1 AM3160 Clock, Electric 1 AF0300 Chair, Rotary w/o Arms 4 CF1273 Counter, Central Monitors 1 CF2000 Waste Receptacle, Off 1 C

Page 623: Army Medical Design Guide - SAFE

M2800 Cart, Chart Holder 1 CM3051 Defibrillator w/Cart 1 CE2500 Nurses Station, Modular 2 E

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOOM Master Control Station 1 APAOOC Ceiling Speaker 1 ATLOOC Counter Outlet-6" Above CT 4 ATLOOF Floor Outlet-Flush 1 ATLOOK CAPOC Outlet 1 ATLOFX Facsimile Outlet 1 ATSOOC Counter Outlet-6" Above 4 A

JULY 1988

Page 624: Army Medical Design Guide - SAFE
Page 625: Army Medical Design Guide - SAFE
Page 626: Army Medical Design Guide - SAFE
Page 627: Army Medical Design Guide - SAFE
Page 628: Army Medical Design Guide - SAFE

3.06.03 AMedi PrepMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 90Finishes -Walls - GW-SG - Base - R -Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 36GHardware Set - H20Ambient Noise Level - NC 30-35Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 100Task Illum (FC) - -Luminare Type - D3Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M3620 Dispenser, Paper Towel 1 AM5250 Medicine, SVC Center 1 AP3100 Lavatory, Wall Hung 1 AF2010 Waste Receptacle SS 1 CM2960 Cart, Unit Dose 2 C

COMMUNICATION PROGRAM

Page 629: Army Medical Design Guide - SAFE

Commo LogCode Nomenclature Qty Cat

NCOOD Duty Station 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 630: Army Medical Design Guide - SAFE

JULY 1988

Page 631: Army Medical Design Guide - SAFE

JULY 1988

Page 632: Army Medical Design Guide - SAFE

JULY 1988

Page 633: Army Medical Design Guide - SAFE

JULY 1988

Page 634: Army Medical Design Guide - SAFE

3.06.04 ASoiled Utility-NUMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 120Finishes - Walls - GW - 8ase - R - Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 36DHardware Set - H19Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 20Task Illum (FC) -Luminare Type - B1Switching - Std

Electrical Notes -

MECHANICAL

Total Air Changes - 10Outside Air Changes - 1Room Pressure(%) - -10Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,80.0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - YesCondensate - Yes

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

C01CO Cabinet, U/C, Base 1 ACO1QO Cabinet, U/C, Sink 1 ACC010 Cabinet, Wall Hung 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM3620 Dispenser, Paper Towel 1 AP6350 Sink, SVC Wall Hung 1 A

Page 635: Army Medical Design Guide - SAFE

S6700 Washer, Bedpan 1 AM2020 Trashcan, Mobile 1 CM4500 Hamper, Linen 1 CR6200 Refrigerator, U/C, Lab 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOOD Duty Station 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 636: Army Medical Design Guide - SAFE

JULY 1988

Page 637: Army Medical Design Guide - SAFE

JULY 1988

Page 638: Army Medical Design Guide - SAFE

JULY 1988

Page 639: Army Medical Design Guide - SAFE

3.06.05 ATub Shower RoomMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 180Finishes - Walls - CT - Base - CT - Floor - CT - Ceiling - GW-SGCeiling Ht - 8'-0"Door Size & Type - 48AHardware Set - H12Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 20Task Illum (FC) - -Luminare Type - N1,P3Switching - Std by Area

Electrical Notes -

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - 10Temperature (F) - Sum 78 Win 75Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration(%) - 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M1291 Bath, Hydraulic Lift 1 AM3620 Dispenser, Paper Towel 1 AM4600J Grab Bar, Tub/Shower 1 AM4600M Grab Bar, Straddle 1 AM5300 Mirror 14 X 20 1 AM5960 Coat Hook 2 AM6880 Shower Curtain & Rod 1 A

Page 640: Army Medical Design Guide - SAFE

M6900 Soap Dish w/ Grab Bar 1 AM7960 Track & Curtain, Cubicle 3 AM7970 Toilet Paper Holder, Recessed 1 AM7980 Towel Bar, 18" 2 AP5040 Shower, Wheelchair 1 AP9050 Water Closet 1 AP9180 Lavatory, Wheelchair 1 AF2000 Waste Receptacle, Off 1 C

COMMUNICATION PROGRAM

Commo LogCode Nomenclature Qty Cat

NCOEC Pullcord Station, Ceiling 1 ANCOEL Dome Light W/ Chime 1 ANCOES Pullcord Station-WP, Shower 1 ANCOET Pullcord Station, Emer 1 ANCOOD Duty Station 1 ATLOOW Wall Outlet-54" AFF 1 A

JULY 1988

Page 641: Army Medical Design Guide - SAFE
Page 642: Army Medical Design Guide - SAFE
Page 643: Army Medical Design Guide - SAFE
Page 644: Army Medical Design Guide - SAFE
Page 645: Army Medical Design Guide - SAFE

3.06.06 ANourishment PantryMatrix Data

ARCHITECTURAL/ACOUSTICS

Square Foot Area Net - 200Finishes - Walls - GW-SG - Base - R -Floor - VCT - Ceiling - ACTCeiling Ht - 8'-0"Door Size & Type - 48AHardware Set - H06Ambient Noise Level - NC 35-40Speech Privacy Level - Normal

Architectural Notes -

ELECTRICAL

Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A1Switching - Std by Area

Electrical Notes - 27 ref. pp. 20-23

MECHANICAL

Total Air Changes - 6Outside Air Changes - 1Room Pressure(%) - -10Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,80,0

Mechanical Notes -

MECHANICAL PIPING

Cold Water - YesHot Water - YesTreated Water - NoChilled Water - NoWater/Vent - YesFloor Drain - NoSteam - NoCondensate - No

Piping Notes -

EQUIPMENT PROGRAM

J.S.N. LogCode Nomenclature Qty Cat

M5552 Nourishment Station 1 AK1250 Cart, Food 2 C

COMMUNICATION PROGRAM

Commo Log

Page 646: Army Medical Design Guide - SAFE

Code Nomenclature Qty Cat

TLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A

JULY 1988

Page 647: Army Medical Design Guide - SAFE

JULY 1988

Page 648: Army Medical Design Guide - SAFE

JULY 1988

Page 649: Army Medical Design Guide - SAFE

JULY 1988

Page 650: Army Medical Design Guide - SAFE

JULY 1988