AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: [email protected] www.bihl-wiedemann.de We reserve the right to change any data Mannheim, 14.5.13 page 1 AS-i 3.0 Gateways, PROFIsafe via PROFINET or PROFIBUS 22 / 1 Master, PROFINET / PROFIBUS Slave AS-i Safety input slaves report via PROFIsafe AS-i Safety output slaves switch via PROFIsafe Up to 32 release circuits up to 6 CAT4, SIL 3 safe output circuits on the Monitor safe relays or fast electronic safe outputs Safe AS-i outputs are supported up to 32 independent AS-i outputs Multiple safe AS-i outputs possible via a single AS-i address 1 Safety Monitor for 2 AS-i networks Operation using a single Monitor configuration! Monitor processes safety slaves on two AS-i networks Coupling between the two networks superfluous Monitor configuration can be „arbitrarily“ large 256 devices (previously 48) Identical reaction time due to artificial limitation to 256 devices Applications up to category 4/PLe/SIL 3 Chip card for storage of configuration data (Figure similar) Figure Type Inputs safety, expandable to Outputs Safety, SIL 3, cat. 4 Safety outputs, independent according to SIL 3, expandable to Safety communication Number of AS-i networks, number of AS-i Master 1 power supply, 1 gateway for 2 AS-i networks, inexpensive power supplies Diagnostic and configuration interface Article No. PROFIs- afe, PROFI- BUS max. 62 x 2 channels 4 release circuits; 2 x relay, 2 x fast electronic safe outputs max. 16 PROFIsafe (F-CPU) + ASIMON 256 Devices 2 AS-i networks, 2 AS-i Masters yes, max. 4A/ AS-i network Ethernet BWU2615 PROFIs- afe, PROFI- BUS max. 62 x 2 channels 4 release circuits; 2 x relay, 2 x fast electronic safe outputs max. 16 PROFIsafe (F-CPU) + ASIMON 256 Devices 2 AS-i networks, 1 AS-i Master yes, max. 4A/ AS-i network Ethernet BWU2598 PROFIs- afe, PROFI- BUS max. 62 x 2 channels 4 release circuits; 2 x relay, 2 x fast electronic safe outputs max. 16 PROFIsafe (F-CPU) 2 AS-i networks, 2 AS-i Masters yes, max. 4A/ AS-i network RS 232 BWU2215 PROFIs- afe, PROFI- BUS max. 62 x 2 channels 4 release circuits; 2 x relay, 2 x fast electronic safe outputs max. 16 PROFIsafe (F-CPU) 2 AS-i networks, 2 AS-i Masters no, max. 8A/ AS-i network, redundant supply RS 232 BWU2214 PROFIs- afe, PROFI- BUS max. 62 x 2 channels - max. 16 PROFIsafe (F-CPU) 1 AS-i network, 1 AS-i Masters yes, max. 4A/ AS-i network RS 232 BWU2479

Upload: others

Post on 22-Sep-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

AS-i 3.0 Gateways, PROFIsafe via PROFINET or PROFIBUS

22 / 1 Master, PROFINET / PROFIBUS Slave• AS-i Safety input slaves report via PROFIsafe

• AS-i Safety output slaves switch via PROFIsafe

Up to 32 release circuits• up to 6 CAT4, SIL 3 safe output circuits on the Monitor

safe relays or fast electronic safe outputs

Safe AS-i outputs are supported• up to 32 independent AS-i outputs

Multiple safe AS-i outputs possible via a single AS-i address

1 Safety Monitor for 2 AS-i networks• Operation using a single Monitor configuration!

Monitor processes safety slaves on two AS-i networksCoupling between the two networks superfluous

Monitor configuration can be „arbitrarily“ large• 256 devices (previously 48)

Identical reaction time due to artificial limitation to 256 devices

Applications up to category 4/PLe/SIL 3

Chip card for storage of configuration data

(Figure similar)

Figure TypeInputs safety, expandable to

Outputs Safety, SIL 3, cat. 4

Safety outputs,independent according to SIL 3, expandable to

Safetycommunication

Number of AS-i networks, number of AS-i Master

1 power supply, 1 gateway for 2 AS-i networks, inexpensive power supplies

Diagnostic and configuration interface

Article No.

PROFIs-afe, PROFI-BUS

max. 62 x 2 channels

4 release circuits; 2 x relay, 2 x fast electronic safe outputs

max. 16

PROFIsafe (F-CPU) + ASIMON 256 Devices

2 AS-i networks, 2 AS-i Masters

yes, max. 4A/AS-i network

Ethernet BWU2615

PROFIs-afe, PROFI-BUS

max. 62 x 2 channels

4 release circuits; 2 x relay, 2 x fast electronic safe outputs

max. 16

PROFIsafe (F-CPU) + ASIMON 256 Devices

2 AS-i networks, 1 AS-i Master

yes, max. 4A/AS-i network

Ethernet BWU2598

PROFIs-afe, PROFI-BUS

max. 62 x 2 channels

4 release circuits; 2 x relay, 2 x fast electronic safe outputs

max. 16PROFIsafe (F-CPU)

2 AS-i networks, 2 AS-i Masters

yes, max. 4A/AS-i network

RS 232 BWU2215

PROFIs-afe, PROFI-BUS

max. 62 x 2 channels

4 release circuits; 2 x relay, 2 x fast electronic safe outputs

max. 16PROFIsafe (F-CPU)

2 AS-i networks, 2 AS-i Masters

no, max. 8A/AS-i network,redundant supply

RS 232 BWU2214

PROFIs-afe, PROFI-BUS

max. 62 x 2 channels

- max. 16PROFIsafe (F-CPU)

1 AS-i network,1 AS-i Masters

yes, max. 4A/AS-i network

RS 232 BWU2479

Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: [email protected]

www.bihl-wiedemann.de We reserve the right to change any data Mannheim, 14.5.13 page 1

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

PROFIs-afe, PROF-INET

max. 62 x 2 channels

4 release circuits; 2 x relay, 2 x fast electronic safe outputs

max. 16

PROFIsafe (F-CPU) + ASIMON 256 Devices

2 AS-i networks, 2 AS-i Masters

yes, max. 4A/AS-i network

RS 232 +

Ethernet1BWU2647

PROFIs-afe, PROF-INET

max. 62 x 2 channels

4 release circuits; 2 x relay, 2 x fast electronic safe outputs

max. 16PROFIsafe (F-CPU)

2 AS-i networks, 2 AS-i Masters

yes, max. 4A/AS-i network

RS 232 +

Ethernet1BWU2383

PROFIs-afe, PROF-INET

max. 62 x 2 channels

4 release circuits; 2 x relay, 2 x fast electronic safe outputs

max. 16PROFIsafe (F-CPU)

2 AS-i networks, 2 AS-i Masters

no, max. 8A/AS-i network,redundant supply

RS 232 +

Ethernet1BWU2421

PROFI-safe, PROF-INET

max. 31 x 2 channels

6 release circuits; fast electronic safe outputs

max. 31

PROFIsafe (F-CPU) + ASIMON 256 Devices

1 AS-i network, 1 AS-i Master

yes, max. 4A/AS-i network

Ethernet BWU2794

1 ASIMON, AS-i Control Tools via RS-232 and Ethernet (RJ-45 PROFINET-Interface)

Article no. BWU2479 BWU2214 /BWU2215

BWU2598 /BWU2615

BWU2383 / BWU2421 / BWU2647

BWU2794

Interface

PROFIBUS

Baud rates 9,6 kBaud up to 12 000 kBaud, automatic recognition

DP functions imaging of the AS-i slaves as I/O data of the PROFIBUS

complete diagnosis and configuration via the PROFIBUS DP

PROFINET

PROFINET interface – RJ-45

Conformance Class – B

Baud rates – 10/100MBaud

AS-i

Cycle time 150 μs * (number of slaves + 2)

Operating voltage AS-i voltage 30V DC

Display

LCD indication of slave addresses and error messages in plain text

LED PROFINET – green: PROFINET-Master recognizedred: PROFINET-Master not recognized

LED PROFIBUS PROFIBUS master recognized –

LED power power on

LED config error configuration error

LED U AS-i AS-i voltage OK

LED AS-i active AS-i normal operation active

LED prg enable automatic addresses programming enabled

LED prj mode configuration mode active

LED AUX – auxiliary power

LED 1.Y1, 1.Y2, 2.Y1, 2.Y2(EDM/Start)

– state of inputs:off: openon: close

LED K1 ... K4 – state of outputs:off: openon: close

LEDs SI1 ... SI6 – state of inputs:off: openon: close

LEDs SO1 ... SO6 – state of outputs:off: openon: close

Figure TypeInputs safety, expandable to

Outputs Safety, SIL 3, cat. 4

Safety outputs,independent according to SIL 3, expandable to

Safetycommunication

Number of AS-i networks, number of AS-i Master

1 power supply, 1 gateway for 2 AS-i networks, inexpensive power supplies

Diagnostic and configuration interface

Article No.

Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: [email protected]

page 2 Mannheim, 14.5.13 We reserve the right to change any data www.bihl-wiedemann.de

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

UL-specifications (UL508)

External Protection an isolated source with a secondary open circuit voltage of ≤ 30V DC with a 3A maximum over current protection.Over current protection is not required when a Class 2 source is employed.

In general UL mark does not provide UL certification for any functional safety rating or aspects of the above devices.

cTÜVus the devices• BWU2214• BWU2215• BWU2383• BWU2421• BWU2479• BWU2598• BWU2615• BWU2647from Bihl + Wiedemann GmbH were safety certified by TÜV Rheinland of North America, Inc. according to UL-standards and meet the safety requirements for the North American market.

Norms EN 50 295EN 61 000-6-2EN 61 000-6-4

EN 62 061:2005, SIL 3EN 61 508:2006, SIL 3

EN ISO 13 849-1:2008/AC:2009, Performance-Level eEN ISO 13 849-2:2008

Environment

Housing stainless steel

Ambient operating temperature

0°C +55°C

Storage temperature -25°C +85°C

Protection category IEC 60 529

IP20

Tolerable loading referring to impacts and vibrations

according EN 61 131-2

Voltage of insulation ≥ 500V

Weight 800 g

Dimensions (B / H / T in mm) 75 / 120 / 87 100 / 120 / 96 100 / 120 / 106 109 / 120 / 96 109 / 120 / 106

Article no. BWU2479 BWU2214 /BWU2215

BWU2598 /BWU2615

BWU2383 / BWU2421 / BWU2647

BWU2794

Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: [email protected]

www.bihl-wiedemann.de We reserve the right to change any data Mannheim, 14.5.13 page 3

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

Article no. BWU2479 BWU2214 /BWU2215

BWU2598 /BWU2615

BWU2383 / BWU2421 / BWU2647

BWU2794

Safety monitor

Start delay – < 10 ms

Max. turn-off time < 40 ms

Card slot Chip card for storage of configuration data

Input

Inputs Safety – 3 x 2 channels or 6 standard inputsInputs digital, EDM – 4

switching current – statical 4mA at 24V, dynamic 30mA at 24V (T=100 μs)

statical 4mA at 24V, dynamic 15mA at 24V (T=100μs)

power supply – out of AUX

tolerated test pulse – adjustable

Output

Number of release circuits on the monitor

– 4 6

Outputs – relay outputs (output circuits 1 and 2)max. contact load: 3A AC-15 at 30V,

3A DC-13 at 30V

semiconductor output max. contact load:

1,2A DC-13 at 30V, ∑= 7,2A in sum1

1

– semiconductor outputs (output circuits 3 and 4):

max. contact load: 0,5A DC-13 at 30V

power supply(semiconductor outputs)

– out of AUX

Test pulse(semiconductor outputs)

– if output is on: minimum interval between 2 test pulses:

250ms (as from Safety Version 4.3); maximum pulse width 1ms

if output is on: minimum interval between

2 test pulses: 250ms; maximum pulse width 1ms

BWU2794Derating output current

I AUX, max [A]

5A

7,2A

40 55

Tamb [°C]

Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: [email protected]

page 4 Mannheim, 14.5.13 We reserve the right to change any data www.bihl-wiedemann.de

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

Safety outputs block diagramBWU2214, BWU2215, BWU2383, BWU2421, BWU2598, BWU2615, BWU2647:

Safety outputs block diagramBWU2794

Article no.

Operating current

Master power supply, ca. 300mA out of AS-i circuits

Master power supply,max. 300mA out of AS-i circuit 1

(approx. 70mA ... 300mA),max. 300mA out of AS-i circuit 2

(approx. 70mA ... 300mA);in sum max. 370mA

Version „1 gateway, 1 power supply, for 2 AS-i networks“,

approx. 300mA (PELV voltage)

BWU2214 – ● –

BWU2215 – – ●

BWU2383 – – ●

BWU2421 – ● –

BWU2479 ● – –

BWU2598 – ● –

BWU2615 – – ●

BWU2647 – – ●

BWU2794 – – ●

BWU2214 /BWU2421

BWU2479 / BWU2598

BWU2215 / BWU2383 / BWU2615 / BWU2647 / BWU2794

Redundant power supply out of AS-i:all fundamental functions of the deviceremain available even in case of powerfailure in one of the two AS-i networks

● – –

Current measurement of the AS-i circuits – – ●

Self-resetting adjustable fuses – – ●

AS-i earth fault monitor distinguishes between AS-i cable and sensor cable

– – ●

In version „1 gateway, 1 power supply for 2 AS-i circuits“: only 1 gateway + 1 AS-i power supply is needed for both 2 AS-i circuits

– ● ●

24V

0V

1.13

2.13

3.14

4.14

1.14

2.14

0 VSO2

24 V SO1

SO4

SO3

SO6

SO5

Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: [email protected]

www.bihl-wiedemann.de We reserve the right to change any data Mannheim, 14.5.13 page 5

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

Possibilities of terminal configurationBWU2794

Connections: Gateway + Safety Monitor:

Terminal Safe output Safe input for mechanical contacts in

combination withT1, T2

Safe antivalent input

Safe electronic input

Standard input

SI1,2 ‒ ● ● ● ●

SI3,4 ‒ ● ● ● ●

SI5,6 ‒ ● ● ● ●

SO1,21

1 If outputs are configured as inputs, the input current has to be limited by an external element at ≤ 100mA

● ● ● ‒ ●

SO3,41 ● ● ● ‒ ●

SO5,61 ● ● ● ‒ ●

BWU2214, BWU2421 BWU2598

1.Y22.14

+ 24.14

+ 11.14

1.Y13.14

2.13+ 3

24V2.Y1

0V+ 4

1.132.Y2

+ ASI 2–

+ASI 1–

ASI 1 +PWR- (max. 8A)

ASI 2 +PWR- (max. 8A)

output switching elements

EDM/Start inputs

EDM/Start inputs

output switching elements

1.Y22.14

+ 24.14

+ 11.14

1.Y13.14

2.13+ 3

24V2.Y1

0V+ 4

1.132.Y2

nc

+ASI 1–

+ASI 1–

ASI 1 +PWR- (max. 4A)

EDM/Start inputs

output switching elements

output switching elements

EDM/Start inputs

Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: [email protected]

page 6 Mannheim, 14.5.13 We reserve the right to change any data www.bihl-wiedemann.de

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

Accessories:• Safe contact expander, 1 or 2 independent channels (art. no. BWU2548 / BWU2539)

• ASIMON 3 G2 and AS-i Control Tools with serial cable for AS-i Master/Monitors in Stainless Steel (art. no. BW2071)

• AS-i Power Supply 4A (art. no. BW1649) / AS-i Power Supply 8A (art. no. BW1997

For devices with PROFIBUS interface:

• Serial PROFIBUS Master (art. no. BW1258)

• PROFIBUS-DP Master simulator (art. no. BW1257)

BWU2215, BWU2383, BWU2615, BWU2647 BWU2479

BWU2794

Connection Description

SI1, SI3, SI5 Safe input terminal (T1)

SI2, SI4, SI6 Safe input terminal (T2)

T1 Clock output 1

T2 Clock output 2

SO1 ... SO6 Safe semiconductor outputs 1 ... 6

24V, 0V Power supply for local I/Os

+ASI 1- Connection of AS-i circuit

ASI +PWR- Power supply for Gateway and AS-i networks

1.Y22.14

+ 24.14

+ 11.14

1.Y13.14

2.13+ 3

24V2.Y1

0V+ 4

1.132.Y2

+ASI 2–

+ASI 1–

+ASI 1–

ASI +PWR- (max. 8A)

output switching elements

EDM/Start inputs

EDM/Start inputs

output switching elements24V ext.

+ASI 1–

+ASI 1–

ASI 1 +PWR- (max. 4A)

+ ASI 1 –

+ASI 1–

+ASI 1–

ASI +PWR- (max. 8A)

SO6SO4

0VSO3

SO5SO1

24VSO2

SI6SI5

SI4SI3

SI2SI1

T2T1

Safe inputs /

Standard inputs

Safe outputs