Ascom Energy Systems Product Specification Ascom_Motorola_Product_Specs_FE2000_system_kits_07 CGDS40071138681 FE2000 48V / 160A Cabinet System Kit 1000mm (expandable to 320A max.) ASCOM ENERGY SYSTEMS PN: D 0021691 Electrical Specification: Input voltage range: 88...264VAC Input current nom.: 44A @ 110Vac / 40A @ 230Vac Frequency range: 45...66Hz Output voltage range: 40...59VDC Output current max.: 168A (336A w/expansion) Output power max.: 9.9kW (19.8kW w/expansion) Grounding: Plus grounding Mechanical Specification: Dimensions(HxWxD): 1000 x 600 x 450 mm Weight: app. 50 kg Color: light grey, RAL7032 Packing size(HxWxD): 1200 x 800 x 600 mm Shipping weight: app. 60 kg Installed Standard Equipment: One (1) FE2000 AC/DC Rectifier Rack @ 48V/160A Two (2) FE2000 AC/DC Rectifier 48V/40A One (1) System Controller – PSC1000 One (1) LVBD Contactors @48V/300A Eight (8) CKT BKR DIN 20A for AC input One (1) Distribution CB DIN rails Two (2) CKT BKR DIN 80A CGDS40043053296 Two (2) CKT BKR DIN 63A CDGS40043053426 Two (2) CKT BKR DIN 25A CGDS40043053486 Two (2) CKT BKR DIN 6A CDGS40043053540 One (1) AC Surge Arrester CGDSC0024011 Two (2) Battery Disconnect EFEN NH2 (400A) DC Copper Busbars/Cables, Load Shunt, Battery Shunt, Additional Equipment: Part Number: *FE2000 Rectifier 48V/40A CGDS40071088930 *Distribution Circuit Breaker (DIN rail CB version up to 125A) Up to 26 DIN rail MCBs (<80A) can be installed. Each installed CB (>80A) reduces the number of CBs (<80A) that can be installed by 1.5. Optional Equipment: *One (1) additional FE2000 AC/DC Rectifier Shelf 48V/160A CGDS40071138480 *See separate Product Specification for more details. Notice: Above Cabinet System is not seismic Zone 4 approved. Field Replaceable Units: CGDS40071138480 *FE2000 AC/DC Rectifier Shelf 48V/160A CGDS40071088930 *FE2000 AC/DC Rectifier 48V/40A CGDS5CPD45500399 * -48V PSC1000 Controller CGD40043053xxx * Distribution Circuit Breaker CGDSC0024011 * AC Multipole Surge Arrester

Upload: ahmed-helmy-hegazy

Post on 28-Nov-2015

274 views

Category:

Documents


11 download

DESCRIPTION

ASCOM Rectifier Catalog

TRANSCRIPT

Page 1: ASCOM Rectifier Catalog

Ascom Energy Systems – Product Specification

Ascom_Motorola_Product_Specs_FE2000_system_kits_07

CGDS40071138681FE2000 48V / 160A Cabinet System Kit 1000mm(expandable to 320A max.)ASCOM ENERGY SYSTEMS PN: D 0021691

Electrical Specification:Input voltage range: 88...264VACInput current nom.: 44A @ 110Vac /

40A @ 230VacFrequency range: 45...66HzOutput voltage range: 40...59VDCOutput current max.: 168A (336A w/expansion)Output power max.: 9.9kW (19.8kW w/expansion)Grounding: Plus grounding

Mechanical Specification:Dimensions(HxWxD): 1000 x 600 x 450 mmWeight: app. 50 kgColor: light grey, RAL7032Packing size(HxWxD): 1200 x 800 x 600 mmShipping weight: app. 60 kg

Installed Standard Equipment:One (1) FE2000 AC/DC Rectifier Rack @ 48V/160ATwo (2) FE2000 AC/DC Rectifier 48V/40AOne (1) System Controller – PSC1000One (1) LVBD Contactors @48V/300AEight (8) CKT BKR DIN 20A for AC inputOne (1) Distribution CB DIN railsTwo (2) CKT BKR DIN 80A CGDS40043053296Two (2) CKT BKR DIN 63A CDGS40043053426Two (2) CKT BKR DIN 25A CGDS40043053486Two (2) CKT BKR DIN 6A CDGS40043053540One (1) AC Surge Arrester CGDSC0024011Two (2) Battery Disconnect EFEN NH2 (400A)DC Copper Busbars/Cables, Load Shunt, Battery Shunt,

Additional Equipment: Part Number:*FE2000 Rectifier 48V/40A CGDS40071088930*Distribution Circuit Breaker (DIN rail CB version upto 125A)Up to 26 DIN rail MCBs (<80A) can be installed.Each installed CB (>80A) reduces the number of CBs(<80A) that can be installed by 1.5.

Optional Equipment:*One (1) additional FE2000 AC/DC Rectifier Shelf 48V/160ACGDS40071138480

*See separate Product Specification for more details.Notice: Above Cabinet System is not seismic Zone 4 approved.

Field Replaceable Units:CGDS40071138480*FE2000 AC/DC Rectifier Shelf 48V/160ACGDS40071088930*FE2000 AC/DC Rectifier 48V/40ACGDS5CPD45500399* -48V PSC1000 ControllerCGD40043053xxx* Distribution Circuit BreakerCGDSC0024011* AC Multipole Surge Arrester