ashrae std 62.1-2010 update where are we now?mnashrae.org/images/meeting/101712/stanke_62.1.pdf ·...
TRANSCRIPT
ASHRAE Std 62.1-2010 Update
Where Are We Now? October 2012
Dennis A. Stanke
Trane • La Crosse, WI
© 2009 Trane 2
ASHRAE Standard 62.1
What Is It?
• Title: “Ventilation for Acceptable Indoor Air
Quality”
• Purpose: “… to specify minimum ventilation rates
and indoor air quality that will be acceptable to
human occupants and are intended to minimize
… adverse health effects.”
• Scope: All commercial, institutional, and high-rise
residential buildings
© 2009 Trane 4
ASHRAE Standard 62.1
Why Care?
• Section 6 is the basis for many ventilation codes,
include both US model codes (UMC and IMC)
• Compliance with Std 62.1-2010 (Sections 4 thru 7)
is a LEED prerequisite for any credits
• Compliance with Std 62.1-2010 (Sections 4 thru 8)
is required for compliance with:
– Std 189.1-2011 “High Performance Green Buildings”
– ENERGY STAR and bEQ energy label
© 2009 Trane 5
what does Std 62.1 require?
Must Comply With …
• (Sect 4 and 5) Mandatory general requirements
– To reduce generation of indoor contaminants and
introduction of outdoor contaminants
• (Sect 6) Ventilation requirements
– Prescribed rates to dilute indoor contaminants
– Performance rates to limit contaminant concentrations
– Natural ventilation provisions
• (Sect 7) Mandatory construction, startup reqmts
• (Sect 8) Mandatory operation, maintenance reqmts
© 2009 Trane 6
Std 62.1-2010 Section 4
Outdoor Air Quality
• 4.1.1 Regional Air Quality. Assess regional
outdoor air (OA) quality to determine NAAQS
compliance status
– Check for non-attainment for any EPA criteria
contaminants
• 4.1.2 Local Air Quality. Survey site for unusual local
sources
– Visit the site, look around
These assessments inform air cleaning
decisions
Project Team
© 2009 Trane 7
Std 62.1-2010 Section 5
Systems and Equipment
• 5.1 Ventilation Air Distribution. Design to assure that ventilation air can get to occupied zones
– Provide means to adjust (balance) airflows
– Design to assure mixing in RA/OA mixing plenums
– Document assumptions and air balancing requirements
Important in 100% OA systems – should really duct OA to zone
Mech Designer
© 2009 Trane 8
Std 62.1-2010 Section 5
Systems and Equipment
• 5.2 Exhaust Duct Location. Prevent leakage of harmful exhaust contaminants into the building
– Design exhaust ducts to operate at negative pressure
Room Duct Fan Outdoors
Mech Designer
© 2009 Trane 9
Std 62.1-2010 Section 5
Systems and Equipment
• 5.3 Ventilation System Controls. Design to assure minimum ventilation
– Provide controls to enable fan
– Provide controls to maintain minimum OA flow at any load or dynamic reset condition.
– VAV systems must include modulating dampers or injection fans
Mech Designer
© 2009 Trane 10
Std 62.1-2010 Section 5
Systems and Equipment
• 5.4 Airstream Surfaces. Reduce space contamination due to air distribution system
– Use duct materials that resist microbial growth per UL 181
– Use duct materials that resist erosion per UL 181
Most matte-face finishes meet these requirements
Mech Designer
© 2009 Trane 11
Std 62.1-2010 Section 5
Systems and Equipment
• 5.5 Outdoor Air Intakes. Reduce contamination from outdoors
– Locate intake a minimum distance from outdoor
sources, per Table 5.2. Examples sources/distances:
Loading dock 25 ft
Dumpster 15 ft
Surface below intake 1 ft
Cooling tower exhaust 25 ft
– Design to limit rain water penetration (using hood,
proper velocity, etc.) or manage water that penetrates
– Use bird screens and prevent bird nesting at intake
architect
© 2009 Trane 12
Std 62.1-2010 Section 5
Systems and Equipment
• 5.6 Local Capture of Contaminants. Reduce recirculation of indoor contaminants
– Exhaust locally captured contaminants (from printers, for instance) directly to outdoors
• 5.7 Combustion Air. Reduce pollutants from combustion appliances
– Provide sufficient combustion air
– Provide sufficient air for removal of combustion products
Mech Designer
© 2009 Trane 13
Std 62.1-2010 Section 5
Systems and Equipment
• 5.8 Particulate Matter Removal. Reduce rate of dirt accumulation on HVAC devices
– Use at least a MERV 6 filter upstream of dehumidifying coils and other wet-surface devices (about 20% to 30% Dust Spot)
Mech Designer
© 2009 Trane 14
Std 62.1-2010 Section 5
Systems and Equipment
• 5.9 Dehumidification Systems. Design to reduce
dampness in buildings during mechanical cooling
– By analysis, limit RH to 65% or less at design dew
point condition without solar load
– Design so that intake exceeds exhaust airflow
Basic constant volume systems with sensible-only thermostat might not comply with 65% limit
Mech Designer
© 2009 Trane 15
Std 62.1-2010 Section 5
Systems and Equipment
• 5.10 Drain Pans. Assure condensate drainage without flooding or carryover
– Slope drain pan at least 1/8 “ per foot
– Locate drain opening at lowest point of drain pan and size to prevent overflow under normal conditions
– Use P-trap or other seal to prevent ingestion of air while allowing complete drainage with fan on or off
– Size drain pan to limit carryover
Proper P-trap design helps avoid common water carryover problems
Mech Designer
© 2009 Trane 16
total trap height T = D + H
where … H = air-handler casing pressure + 1 in. wg D = trap depth = ½ H + d d = drain pipe diameter
Drain Seals Mech Designer
© 2009 Trane 17
Std 62.1-2010 Section 5
Systems and Equipment
• 5.11 Finned Tube Coils and Heat Exchangers. Select to reduce water droplet carryover
– Limit coil pressure drop to 0.75 in.wc.@ 500 fpm
– Exception: No pressure drop limit when design provides access to both faces for cleaning
• 5.12 Humidifiers and Water Spray Systems. Reduce water-borne contaminants and design to reduce carryover
– Use potable water
– No downstream devices within absorption distance
Mech Designer
© 2009 Trane 18
Std 62.1-2010 Section 5
Systems and Equipment
• 5.13 Access for Inspection, Cleaning and Maintenance. Reduce dirt accumulation in air distribution system
– Design system with adequate clearance around ventilation equipment
– Provide access doors/panels for ventilation equipment (air handlers, terminal units)
– Provide access doors/panels for devices in air distribution system (air plenums, coils, air cleaners, drain pans, fans, humidifiers)
Mech Designer
© 2009 Trane 19
Std 62.1-2010 Section 5
Systems and Equipment
• 5.14 Building Envelope and Interior Surfaces.
Reduce intrusion of water and water vapor and
uncontrolled condensation
– Use a weather barrier within the building envelope
– Use a vapor retarder within the building envelope
(typically on the warm side, but it really depends on
wall design)
– Seal all envelope seams, joints and penetrations
– Insulate pipes, ducts and other cold surfaces
Architect
© 2009 Trane 20
Std 62.1-2010 Section 5
Systems and Equipment
• 5.15 Buildings with Attached Parking Garages.
Reduce infiltration of vehicular exhaust
– Maintain garage pressure below adjacent occupied
space
– Or, use a vestibule
– Or, otherwise design to minimize air migration from
garage to occupied space
Architect
© 2009 Trane 21
Std 62.1-2010 Section 5
Systems and Equipment
• 5.16 Air Classification and Recirculation. Reduce
recirculation of “dirty” air to “cleaner” spaces
– Designate air from each space/location (see Table 6.1)
Class 1: Low contaminant concentration (office)
Class 2: Mild concentration (dining room)
Class 3: Significant concentration (daycare sick room)
Class 4: Highly objectionable/potentially harmful
– Design to limit air recirculation as follows:
Class 1 to any space or location
Class 2 to self, other Class 2 or Class 3
Class 3 to self
Class 4 to outdoors only
Mech Designer
© 2009 Trane 22
Std 62.1-2010 Section 5
Systems and Equipment
• 5.17 Buildings Containing ETS Areas and ETS-Free
Areas. Reduce level of ETS in ETS-free areas
– Classify each area as ETS or ETS-free
– Pressurize ETS-free areas with respect to ETS areas
– Separate ETS/ETS-free areas with solid walls, doors, etc
(or engineer to assure airflow into ETS areas
– Maintain transfer airflow paths
– Don’t recirculate from ETS to ETS-free at air handler
– Exhaust from ETS areas
– Post sign: “This area may contain ETS”
Project Team
© 2009 Trane 23
what does Std 62.1 require?
Must Comply With …
• (Sect 4 and 5) Mandatory general requirements
– To reduce generation of indoor contaminants and
introduction of outdoor contaminants
• (Sect 6) Ventilation requirements
– Prescribed rates to dilute indoor contaminants
– Performance rates to limit contaminant concentrations
– Natural ventilation provisions
• (Sect 7) Mandatory construction, startup reqmts
• (Sect 8) Mandatory operation, maintenance reqmts
© 2009 Trane 24
Std 62.1-2010 Section 6.0
Procedures
• 6.1 General. Find minimum zone and intake OA flow using either the VRP, the IAQP, or the NVP
– 6.1.1 Ventilation Rate Procedure (VRP). Prescribes procedures and OA rates, assuming typical space contaminant sources and source strengths
– 6.1.2 IAQ Procedure (IAQP). Requires analysis of contaminants (“performance”) based on sources and target concentrations to find minimum OA rates
– 6.1.3 Natural Ventilation Procedure (NVP). Prescribes opening areas, and requires mechanical ventilation in most climates (mixed-mode ventilation)
Mech Designer
© 2009 Trane 25
• 6.2 Ventilation Rate Procedure. Find OA intake flow (Vot) using prescribed zone OA rates & system intake calculation procedures in this section
Std 62.1-2010 Section 6.2
Ventilation Rate Procedure Mech Designer
© 2009 Trane 26
• 6.2.1 Outdoor Air Treatment. If OA is unacceptable per Section 4.1 assessment, must use air cleaning
– 6.2.1.1 PM10. Where PM10 exceeds the NAAQS (non-
attainment areas), use MERV 6 filter
– 6.2.1.2 PM2.5. Where PM2.5 exceeds the NAAQS
(non-attainment areas) use MERV 11 filter
– 6.2.1.3 Ozone. Where ozone greatly exceeds the
NAAQS (very high non-attainment area) use 40%
efficient ozone air cleaner
Std 62.1-2010 Section 6.2
Ventilation Rate Procedure Mech Designer
NAAQS: “… the most recent three-year average annual fourth-
highest daily maximum eight-hour average ozone
concentration exceeds 0.107 ppm (209 μg/m3) …”
© 2009 Trane 30
Std 62.1-2010 Section 6.2
VRP – Zone Calculaitons
• 6.2.2 Zone Calculations. To assure reasonable breathing-zone dilution for each zone:
– Use Table 6.1 rates (cfm/per and cfm/sf) and Equation 6-1 to find breathing zone outdoor airflow: Vbz = Rp*Pz + Ra*Az
– Use Table 6.2 defaults to find zone air distribution effectiveness, Ez (typically 1.0 for cooling)
– Use Equation 6-2 to find zone outdoor airflow: Voz = Vbz/Ez
Mech Designer
© 2009 Trane 31
ventilation rate procedure
Minimum Ventilation Rates
Table 6-1: Minimum breathing-zone rates for 63 categories
Office 20 0.0 5.0 0.06
Classroom (ages 5-8) 15 0.0 10.0 0.12
Lecture classroom 15 0.0 7.5 0.06
Retail sales 0 0.3 7.5 0.12
Auditorium 15 0.0 5.0 0.06
Std 62-2001 Std 62.1-2010
Rp Ra Rp Ra Occupancy category cfm/p cfm/ft² cfm/p cfm/ft²
Prescribes both per-person and per-area rates
Mech Designer
© 2009 Trane 32
Office (5p) 100 20.0 85 17.0
Classroom (ages 5-8) (25p) 375 15.0 370 15.0
Lecture classroom (65p) 975 15.0 550 8.5
Retail sales (20p) 300 15.0 270 14.0
Auditorium (150p) 2250 15.0 810 5.4
Occupancy category (default density/1000 ft²)
Std 62-2001
Vbz cfm
Effective
cfm/p
ventilation rate procedure
Effective Minimum Rates
Std 62.1-2010
70% of OA rates drop; 30% stay same or rise
Comparison of breathing-zone OA flow
Vbz cfm
Effective
cfm/p
Mech Designer
© 2009 Trane 33
• 6.2.3 Single-Zone Systems. For ventilation systems with one air handler per zone:
– Find system-level outdoor air intake flow: Vot = Voz
• 6.2.4 100% Outdoor Air Systems. For ventilation systems with one air handler supplying only outdoor air to many zones.
– Find system-level outdoor air intake flow: Vot = S Voz
Std 62.1-2010 Section 6.2
VRP – System Calculations Mech Designer
© 2009 Trane 34
• 6.2.5 Multiple-Zone Recirculating Systems. For ventilation systems with one AHU serving many zones: – Find outdoor air intake flow (Vot) using prescribed
equations and procedure to account for system ventilation efficiency (Ev):
Vot = Vou/Ev … outdoor air intake flow Vou = D* S Rp*Pz + S Ra*Az … OA used in zones D = Ps/ S Pz … population diversity factor Ev = min(Evz) … system vent efficiency
Evz = 1 + Xs – Zpz … zone vent efficiency
Xs = Vou/Vps … average OA fraction
Zpz = Voz/Vpz … zone primary OA fraction
Std 62.1-2010 Section 6.2
VRP – System Calculations Mech Designer
© 2009 Trane 35
• 6.2.5 Multiple-Zone Recirculating Systems. For ventilation systems with one AHU serving many zones: – Find outdoor air intake flow (Vot) using prescribed
equations and procedure to account for system ventilation efficiency (Ev):
Vot = Vou/Ev … outdoor air intake flow Vou = D* S Rp*Pz + S Ra*Az … OA used in zones D = Ps/ S Pz … population diversity factor Ev = min(Evz) … system vent efficiency
Evz = 1 + Xs – Zpz … zone vent efficiency
Xs = Vou/Vps … average OA fraction
Zpz = Voz/Vpz … zone primary OA fraction
Std 62.1-2010 Section 6.2
VRP – System Calculations Mech Designer
For design, Vpz = Vpz-exp, where Vpz-exp is the lowest expected primary airflow at the design condition. I use the reheat minimum airflow setting, Vpzm; it’s easy but very conservative.
For design, Vps = Vps-exp, where Vps-exp is the highest expected system primary airflow value at the design condition. I use fan block airflow Vps-des: it’s easy and usually worst-case.
© 2009 Trane 36
Std 62.1-2010 Section 6.2
OA Calculation Example
Do we have time for an example?
– No
– But, I found total OA intake for a 6-zone school,
using different systems and methods:
One RTU per zone (six single-zone systems), both in
cooling and heating
One FC per zone, and a 100% OA system, with both
CV and VAV ventilation airflow
A reheat VAV (single-path multiple-zone) system
using both default Ev and calculated Ev
A series fan-powered VAV (dual-path multiple-zone)
system using calculated Ev
© 2009 Trane 41
VRP 6-zone school example
OA Intake Flow Summary
Ventilation System OA Intake (2001 Vot)
OA Intake (2010 Vot)
% Chg
Single-Zone Clg 12,600 8,900 -29
Single-Zone Htg 15,800 11,100 -30
100% OA – CV 12,600 8,900 -29
100% OA – VAV 8,800 7,000 -20
MZS-VAV Default Ev 10,900 10,800 -1
MZS-VAV Calc Ev 10,900 8,400 -23
MZS-VAV Series FP 10,900 7,800 -28
© 2009 Trane 43
• 6.2.7 Dynamic Reset. To assure outdoor airflow meets requirement for ventilation load, without over-ventilating, optional controls may:
– Reset zone minimum OA flow based on variations in occupancy, i.e., demand controlled ventilation (DCV)
– Reset OA intake flow based on variations in ventilation efficiency (ventilation reset control)
– Reset VAV zone minimum airflow based on variations in outdoor air fraction due to free cooling or exhaust-air make-up operation
Std 62.1-2010 Section 6.2
VRP – Dynamic Reset
This Section includes operating control options, (rather than design requirements)
Mech Designer
© 2009 Trane 44
• 6.3. Indoor Air Quality (IAQ) Procedure
– Find breathing zone OA flow (Vbz) and system OA intake flow (Vot) based on “performance”
– Compliance addresses
Contaminant sources
Contaminant concentration
Perceived indoor air quality
Design approach
Combined IAQP and VRP
Documentation
Std 62.1-2010 Section 6.3
IAQ Procedure Mech Designer
© 2009 Trane 45
• 6.3.1 Contaminant Sources. Must identify contaminants of concern including mixtures, sources, source strengths
• 6.3.2 Contaminant Concentration. Must specify
target concentration, for each C of C
• 6.3.3 Perceived IAQ. Must specify target perceived
air quality in terms of percent satisfied
Std 62.1-2010 Section 6.3
IAQ Procedure
Requires designer judgment to identify contaminants/mixtures of concern, source and source strength for each, targets concentrations.
Judgment = Risk
Mech Designer
© 2009 Trane 46
• 6.3.4 Design Approaches. Find highest required
zone and system OA flow rates using:
– Mass balance analysis AND
– Subjective evaluation, either after construction, OR
using OA needed in a substantially similar zone
• 6.3.5 Combined IAQP and VRP. May use VRP to
find minimum OA and IAQP to find additional OA (or
air cleaning required)
• 6.3.6 Documentation. Must document assumptions
and calculations.
Std 62.1-2010 Section 6.3
IAQ Procedure
IAQP meets Std 62.1 but does NOT meet Std 189.1 or LEED requirements
Mech Designer
© 2009 Trane 47
Std 62.1-2010 Section 6
Natural Ventilation
• 6.4 Natural Ventilation Procedure. Use NV with mechanical ventilation in most climates:
– Perimeter areas must be within defined distance from OA opening with free area at least 4% of floor area
– Interior areas must be within defined distance from OA opening, and interior-perimeter opening with free area at least 8% of interior floor area, but not less than 25 ft2
Defined distance depends on window location and ceiling height (2H for single-side, 5H for double-side)
– “Mixed mode” controls must coordinate operation of NV and MV systems
Project Team
© 2009 Trane 48
• 6.2.8 Exhaust Ventilation. To assure minimum removal of local contaminants, some zones require exhaust rates prescribed in Table 6.4.
• Examples of more than 20 zones listed: Art classroom 0.70 cfm/ft2
Beauty and nail salons 0.60
Kitchenettes 0.30
Locker/dressing rooms 0.25
Copy, printing rooms 0.50
Toilet – public 50 (cont.) or 70 (cyc.) cfm/wtr closet
Std 62.1-2010 Section 6.5
Exhaust Ventilation Mech Designer
© 2009 Trane 49
what does Std 62.1 require?
Must Comply With …
• (Sect 4 and 5) Mandatory general requirements
– To reduce generation of indoor contaminants and
introduction of outdoor contaminants
• (Sect 6) Ventilation requirements
– Prescribed rates to dilute indoor contaminants
– Performance rates to limit contaminant concentrations
• (Sect 7) Mandatory construction, startup reqmts
• (Sect 8) Mandatory operation, maintenance reqmts
© 2009 Trane 50
Std 62.1-2010 Section 7
Construction/Start-Up
• 7.1 Construction Phase. Must reduce IAQ problems
introduced during construction. For example:
– 7.1.2. Install unit filters before operating fans
– 7.1.3. Protect materials from rain and moisture. Don’t
install materials with visible microbial growth
– 7.1.4. Reduce transfer of construction contaminants
into occupied areas
– 7.1.5. Construct ducts per SMACNA standards
Project Team
© 2009 Trane 51
Std 62.1-2010 Section 7
Construction/Start-Up
• 7.2 System Start-Up. Must reduce potential for IAQ
problems prior to occupancy. For example:
– Balance air flows
– Test (or certify) drain pan drainage
– Clean air distribution system before start up
– Test OA dampers for proper operation
– Provide ventilation system documentation (HVAC
controls information, air balance report, design criteria
and assumptions, drawings, etc.) to owner or owner’s
agent
Project Team
© 2009 Trane 52
Std 62.1-2010 Section 8
8.0 Operation & Maintenance
• 8.2 Operations and Maintenance Manual. Develop
a building operations and maintenance manual
• 8.3 Ventilation System Operation. Operate it
whenever spaces are expected to be occupied
• 8.4 Ventilation System Maintenance.
Maintain it in accordance with Manual
Compliance with Section 8 is required by Std 189.1-2010 but
not by LEED
Project Team
© 2009 Trane 53
Std 62.1-2010
Summary
• The 2010 version has a few new requirements
• It’s continually improved (next version in 2013)
• It’s VRP rates and procedures are required by
IMC and UMC and by LEED
• It’s required by reference in Std 189.1, which is
one of two IgCC project compliance paths
• We’re out of time!
Questions? ASHRAE 62.1 update:
Where are we now?