    PRINCIPLES OF OPERATION

    FOR ASPEN MINIPUMPS

    Imported and Distributed by 3 Kellogg Court, Unit10, Edison, NJ 08817 www.eztrap.com

    phone 732-248-8066 fax 732-248-8068 email: [email protected]

    Both types are supplied with2 incoming cables:1. A power supply cable, which alwayshas 3 conductors, color coded for differentvoltages in accordance with the NEC.Conductors for 115 volt pumps are white,black and green, and conductors for230 volt pumps are red, black and green,and these colors are standard for allmodels which operate on line voltage.2. An overflow alarm cable, which isdesigned to break the communication

    wire between the condenser and theevaporator in case the water level in thereservoir rises to an unacceptable level.This cable also has 3 conductors, gray(common), purple (normally closed) andorange (normally open), and this colorcoding is identical for all pump models.CONNECTION OF THE OVERFLOWSWITCH IS MANDATORY. FAILURETO DO SO WILL INVALIDATEMANUFACTURERS WARRANTYAND ALMOST CERTAINLY LEAD TOFLOODING AND WATER DAMAGE.NOTE: The overflow switch contacts are a

    separate volt-free circuit which operatesentirely independently from the powercircuit that automatically switches thepump on and off as the water level risesor subsides.NOTE ALSO that the overflow switchis electronic and draws its powerdirectly from the PCB in the pump,so the switch itself cannot operate

    unless the pump is powered.NOTE: The overflow switch is designedfor a maximum load of 5 amps upto 230 volts, which is normally morethan enough for most Minisplits asthe current and the voltage carried inthe communication wire are usuallywell below this.Standard wiring diagrams for mostMinisplit manufacturers are availableat WWW.EZTRAP.COM orWWW.ASPENPUMPSUSA.COM for

    download, or can be emailed or faxedon request.If the 5 amp limit is exceeded, it will benecessary to use a single pole switchingrelay to handle this current to prevent theelectronics in the pump from burning out.Specific wiring diagrams for this type ofinstallation are available from EZ-TRAPon request.Some Minisplits have communicationswires which are sensitive because theyutilize proprietary operating protocols,and these may have to be wired in adifferent way. In these cases the overflowswitch must be wired only according to awiring diagram dedicated to that partic-ular manufacturer and/or model series.Specific wiring diagrams for this typeof installation are also available fromEZ-TRAP on request.

    Some Minisplits include a dedicated set ofcontacts on the PCB in the evaporator into

    which the overflow wires can be connectedas per the specific wiring diagramsprovided by that manufacturer, and if anoverflow does occur, the unit willautomatically turn off and an alarm LEDwill flash on the control panel of the unit.If this is not the case and an externalaudio or visual alarm is required, this caneasily be done by connecting the orangewire which is energized only when thewater level in the reservoir becomesabnormally high.

    In order to connect an external alarm, itis necessary for the communication wireto carry a stable AC voltage anywherebetween 12 and 230 volts.If an external alarm is required, the orangewire would be connected to one terminalof the alarm device which must use thesame voltage as the communications wire,which will have to be determined priorto installation. If no external alarm isrequired, the orange wire is not used andthe end is taped off to isolate it.If the alarm device is powered by 12 to115 volts, it will be necessary to connect

    the other terminal of the alarm deviceto a neutral to complete the circuit.If the alarm device is powered by 230volts, it will be necessary to determinethe polarity of the communication wire(line 1 or line 2) and then to connect theother terminal of the alarm device to theother line (1 or 2) to complete the circuit.

    SEE PAGE 3 FOR DETAILED DIAGRAMS OF SEQUENCE OF OPERATION and PAGE 4 FOR PUMP SELECTION SPECIFICATIONS

    Minipumps are not designed to rundry as they are both cooled andlubricated by the water flowingthrough them. They therefore requirea float switch to detect the presence

    of water in the drain pan andactivate the pump only when wateris present.For this reason, a Minipumpalways consists of 2 elements:1. The pump body, whichincludes an electronic PCB andthe pump motor.2. The reservoir, which containsthe filter and the switching mechanismto activate the pump.This must alwaysbe kept level and clean to facilitateoperation of the float switch andthe filter must be cleaned regularly.

    When these are supplied as 2 separateitems as in the Orange or Aqua series,they are known as a SPLIT TYPE PUMPand the 2 elements are connectedtogether with a length of 1/4 vinyl tube

    and a communication cable, both ofwhich are usually around 6 feet long, butmay be extended if required.

    When these 2 elementsare combined togetherin 1 unit as in the Limeseries, they are known asa MONOBLOC PUMP in which the

    pump and reservoir share a commonbody and no connecting tubesor wires areneeded.Mini & Maxi Orange

    Pump Body

    Reservoir

    Reservoir

    ReservoirPump Body

    Pump Body

    Mini Aqua

    Mini & MaxiLime

  • 8/7/2019 Aspen Pumps Operation Manual

    2/42

    ASPEN PUMPS IMPORTED AND DISTRIBUTED BY EZTRAP EDISON,NJ 08817 PHONE 732-248-8066 [email protected] WWW.EZTRAP.COM

    CEFFECT OF DIRTY FILTER

    CONDENSATE INLET

    DRAIN PAN

    WIRE TO PUMP

    WHEN CONDENSATE STARTS FLOWING IT CANNOT PENETRATE

    FILTER TO ACTIVATE PUMP OR OVERFLOW ALARM, AND

    WATER WILL BACK UP UNTIL IT OVERFLOWS DRAIN PAN.

    FILTER

    BREATHERTUBE

    PUMP INTAKE TUBE

    WIRENUT

    GREY

    N.O.

    N.C.PURPLE

    ORANGE

    COMMUNICATIONTERMINAL INEVAPORATOR

    COMMUNICATION WIREFROM CONDENSER

    LIGHT OR BUZZER24V, 115V OR 230VACCORDING TO VOLTAGEIN COMMUNICATION WIRE

    FOR 24V OR 115V THIS MUST BE

    WIRED TO A NEUTRALFOR 230V IT MUST BE WIRED TOOTHER LEG OF INCOMING POWER

    ADIAGRAM TO HOOK UP AN EXTERNAL ALARM

    MAX 5 AMPS

    DWHY BREATHER TUBE IS REQUIRED

    CONDENSATE INLET

    DRAIN PAN

    WIRE TO PUMP

    FILTER

    BREATHERTUBE

    AIR INTAKEPREVENTS

    VACUUM

    PUMP INTAKE TUBE

    MIN 1

    WHEN PUMP STARTS AND BEGINS SUCKING WATER OUT OF RESERVOIR, AN AIRLOCK WILL BE CREATEDUNLESS AN AIR INTAKE OPENING IS PROVIDED ON TOP OF RESERVOIR. BECAUSE CONDENSATE FLOWFROM DRAIN PAN INTO RESERVOIR RELIES ON GRAVITY, RESERVOIR MUST ALWAYS BE BELOW DRAINPAN AND IT IS POSSIBLE THAT A BLOCKAGE MAY CAUSE THE WATER LEVEL INTHE CONDENSATE DRAIN INLET HOSE BETWEEN PAN AND RESERVOIR TO BACK UPUNTIL IT GETS HIGHER THAN THE TOP OF THE RESERVOIR. IF THIS HAPPENS,THE WATER WILL BLEED OUT OF THE AIR INTAKE OPENING AND TO PREVENTTHIS FROM OCCURRING, A 6 x1/4 BREATHER TUBE IS FITTED ONTO THEAIR INTAKE OPENING TO EXTEND IT SO THE TOP IS A MINIMUMOF 1ABOVE THE TOP OF THE DRAIN PAN.

    B CORRECT POWER WIRING FOR PUMPIF DISCONNECT IS REQUIRED BY LOCAL CODE

    PUMP115V

    115 VOLTS

    EVAPORATOR115V

    GREEN

    DISCONNECT

    DO NOT WIRE PUMPFROM INCOMING SIDEOF DISCONNECT

    BLACK

    WHITE

    G

    L

    N

    NEUTRAL

    LIVE

    GROUND

    PUMP230V

    230 VOLTS

    EVAPORATOR230V

    GREEN

    DISCONNECT

    DO NOT WIRE PUMPFROM INCOMING SIDEOF DISCONNECT

    BLACK

    RED

    G

    L1

    L2

    LINE2

    LINE1

    GROUND

    All pump models incorporate a filter in thereservoir which must be cleaned regularly.A detailed explanation of this will befound in diagram C below.

    All pump models require a mandatorybreather tube to prevent an airlock in thereservoir while the pump is operating.A detailed explanation of this will befound in diagram D below.

    ASPEN Mini models are available in24V, 115V and 230V AC.ASPEN Maxi models are available in115V & 230V AC only.

    If the current in the communication wireis low voltage electronic or DC, it willgenerally be difficult or impossible toisolate the other leg required to operatean alarm, and in this case, the orangewire is simply taped up and not used.Connection details for an externalalarm will be found in diagram Abelow.Generally, most installers do not connectup an external alarm and this is why ourwiring diagrams show the orange wirebeing taped off and not used.

    NOTE THAT THE OVERFLOW ALARMCIRCUIT NEVER DEACTIVATES THEPUMP WHICH REMAINS LIVE ATALL TIMES.The power supply to the pump shouldalways be connected to the incomingpower terminal block on the evaporatorto ensure that the pump is poweredwhenever the evaporator is powered.

    It is not a good idea to hard wire thepump from a separate circuit, or to powerit from a receptacle like a conventionaltank pump because either of these can beinadvertently isolated or the plug could beaccidentally removed.In either case the evaporator wouldcontinue to produce water, but therewould be no power to operate the pumpor the overflow switch, so a flood would

    occur and this is unacceptable.In spite of this, some local codes actuallycall for this type of wiring connection andif local code officials insist, thisrequirement will have to be met eventhough it may contradict the Aspen wiringinstructions.Some codes also require a disconnectclose to the evaporator and, if this isinstalled, sometimes the pump is powereddirectly from the disconnect. In this case,it is vital that the pump is powered

    from the outgoing terminals on thedisconnect, not the incoming ones,to ensure that if the evaporator isisolated, the pump will be isolatedas well.Details of this will be found indiagram B below.All manufacturers of Minisplit airconditioners use different wiring protocols,so the communications wire varies from

    one unit to another, as well as from onemodel to another, and for this reason, allwiring diagrams in the installationmanuals are generic.Consult EZ-TRAP for factoryapproved wiring diagrams for allthe major manufacturers. Thesecan be found on WWW.EZTRAP.COMor WWW.ASPENPUMPSUSA.COM orcan be emailed or faxed on request.

  • 8/7/2019 Aspen Pumps Operation Manual

    3/4

  • 8/7/2019 Aspen Pumps Operation Manual

    4/44

    ASPENLIMESERIESEXTERNALLYMOUNTEDMONOBLOCPUMPSFOR

    SIDEENTRYEVAPORATORINSTALLATIONS

    COLUM

    N1

    COLUMN2

    UPTO30,000

    BTUs/HOUR

    30,000TO60,000BTUs/HOUR

    LINESET

    U

    PTO

    UPT

    O

    NOELBOW

    AND

    UPTO

    UPTO

    NOELBOWAND

    SIZE

    3/8

    &5/8

    1/2&

    3/4

    LINESETC

    OVER

    3/8&5/8

    1/2&3/4

    LINESETCOVER

    HEAD

    0-26feet

    26-49feet

    0-26feet

    26-49feet

    0-26feet

    26-49feet

    0-49feet

    0-49feet

    0-49feet

    115VOLT

    ASP-ML-115

    ASP-MAXLS-115

    ASP-MLS-115

    ASP-MAXLS-115

    ASP-MLOEM-115

    AS

    P-MAXOEM-115

    ASP-MAXLS-115

    ASP-MAXLS-115

    ASP-MAXOEM-115

    230VOLT

    ASP-ML-230

    ASP-MAXLS-230

    ASP-MLS-230

    ASP-MAXLS-230

    ASP-MLOEM-230

    AS

    P-MAXOEM-230

    ASP-MAXLS-230

    A

    SP-MAXLS-230

    ASP-MAXOEM-230

    24VOLT

    ASP-ML-LG24

    N/A

    ASP-MLS-LG24

    N/A

    ASP-MLOEM-LG24

    N/A

    N/A

    N/A

    N/A

    ASP

    ENPUMP

    SELECTION

    SPE

    CIFICATIONS

    1aboveceiling

    2insidelinesetcover

    3insideevaporatorcasingwhereaccesspermits

    VINYLTUBE

    FALSECEILING

    LINESETCOVER

    MINI&MAXIOR

    ANGESYSTEMLOCATION

    INLINERE

    SERVOIR

    EVAPORATOR

    COIL

    CONDENSATE

    DRAINTRAY

    BREATHERTUBE

    1insideevaporator

    2insidelinesetcover

    VINYL

    DISCHARGE

    TUBE

    FALSECEILING

    LINESETCOVER

    CONDENSATE

    DRAINTRAY

    EVAPORATOR

    COIL

    MINIAQUASYSTEMLOCATION

    RESERVO

    IR

    INLET

    TUBE

    BREATHER

    TUBE

    ASPEN

    ORANGE&AQUASERIESSPLITTYPE

    PUMPS

    COLUMN1

    COLUMN2

    UPTO24,000BTUs/HOUR

    24

    ,000-60,000BTUs/HOUR

    HEAD

    0

    -26feet

    26-65feet

    0-26feet

    26-65feet

    ORANGE115VOLT

    AS

    P-MO-115

    ASP-MAXO-115

    ASP-MAXO-115

    ASP-MAXO-115

    ORANGE230VOLT

    ASP-MO-230

    ASP-MAXO-230

    ASP-MAXO-230

    ASP-MAXO-230

    ORANGE24VOLT

    ASP

    -MO-LG24

    N/A

    N

    /A

    N/A

    AQUA115VOLT

    AS

    P-MA-115

    N/A

    N

    /A

    N/A

    AQUA230VOLT

    ASP-MA-230

    N/A

    N

    /A

    N/A

    AQUA24VOLT

    ASP

    -MA-LG24

    N/A

    N

    /A

    N/A

    Mini&

    MaxiLime

    Lefthand

    Mini&MaxiLime

    Righthand

    Mini&MaxiLime

    OEMKitPumpOnly

    Mini&MaxiLime

    KitInstalled

    MiniAqua

    NOTE:Pumpcapacityiscalculatedatfulldesignvoltage.Operationat

    reducedvoltagewillaffectpumpperfo

    rmance.Whenselecting

    pumpcapacityascertain

    actualinputvoltage

    andA

    LWAYSDESIGN

    FORW

    ORSTCASE

    SCENA

    RIO!

    Mini&Maxi

    Orange

    ImportedandDistributedby

    3KelloggCourt,Unit10,Ed

    ison,NJ08817

    www.eztrap.com

    phone732-248-8066

    fa

    x732-248-8068

    email:[email protected]

    EZT-ASP-POO/SEL/9/07