atlas copco - total tools
TRANSCRIPT
Atlas Copco
Industrial aluminium piston compressors
LE 2, LE 3, LE 5, LE 7, LE 10, LE 15, LE 20
Instruction book
Atlas Copco
Industrial aluminium piston compressors
LE 2, LE 3, LE 5, LE 7, LE 10, LE 15, LE 20
Instruction book
Original instructions
Copyright Notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.
This instruction book is valid for CE as well as non-CE labelled machines. It meets the requirements for instructions specified by the applicable European directives as identified in the Declaration of Conformity.
2012 - 05
No. 2920 7089 82 Replaces No. 2920 7089 81
www.atlascopco.com
2 2920 7089 80
Instruction book
Table of contents
Table of contents ............................................................................................................................. 2
1 Safety precautions ................................................................................................................... 4
1.1 Safety icons ...................................................................................................................................... 4
1.2 Safety precautions, general .............................................................................................................. 4
1.3 Safety precautions during installation ............................................................................................... 4
1.4 Safety precautions during operation ................................................................................................. 6
1.5 Safety precautions during maintenance or repair ............................................................................. 7
2 General description .................................................................................................................. 9
2.1 General description ........................................................................................................................... 9
2.2 Options ........................................................................................................................................... 14
2.3 Air flow ............................................................................................................................................ 15
2.4 Regulating system .......................................................................................................................... 20
3 Installation ............................................................................................................................... 22
3.1 Dimension drawings ....................................................................................................................... 22
3.2 Installation instruction ..................................................................................................................... 39
3.3 Electrical connections ..................................................................................................................... 44
3.4 Settings of overload relay and fuses ............................................................................................... 46
3.5 Cable sizes ..................................................................................................................................... 51
3.6 Pictographs ..................................................................................................................................... 51
4 Operating instructions ........................................................................................................... 52
4.1 Initial start-up .................................................................................................................................. 52
4.2 Starting ........................................................................................................................................... 52
4.3 Stopping .......................................................................................................................................... 54
4.4 Taking out of operation ................................................................................................................... 54
4.5 Storage after installation ................................................................................................................. 55
5 Maintenance ............................................................................................................................ 56
2920 7089 80 3
Instruction book
5.1 Petrol engine maintenance ............................................................................................................. 56
5.2 Preventive maintenance schedule .................................................................................................. 56
5.3 Lubrication of compressors ............................................................................................................. 57
5.4 Service kits ..................................................................................................................................... 57
5.5 Disposal of used material ............................................................................................................... 58
6 Servicing and adjustment procedures ................................................................................. 59
6.1 Unloader or check valve ................................................................................................................. 59
6.2 Valves ............................................................................................................................................. 59
6.3 Air filter ............................................................................................................................................ 61
6.4 Adjustment MDR4 pressure switch ................................................................................................. 61
6.5 Adjustment of MDR3 pressure switch ............................................................................................. 63
6.6 Adjustment of pilot valve on Trolley ................................................................................................ 64
6.7 Safety valve .................................................................................................................................... 65
7 Problem solving ...................................................................................................................... 67
8 Technical data ......................................................................................................................... 69
8.1 Reference conditions ...................................................................................................................... 69
8.2 Limitations ....................................................................................................................................... 69
8.3 Compressor data ............................................................................................................................ 69
9 Instructions for use ................................................................................................................ 71
10 Pressure Equipment Directive (PED) ................................................................................... 72
11 Declaration of conformity ...................................................................................................... 73
4 2920 7089 80
Instruction book
1 Safety precautions
1.1 Safety icons
Explanation
Danger for life
Warning
Important note
1.2 Safety precautions, general
General precautions
1. The operator must employ safe working practices and observe all related work safety requirements and regulations.
2. If any of the following statements does not comply with the applicable legislation, the stricter of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorized, trained, specialized personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality, the compressed air must be adequately purified according to the applicable legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor, press the emergency stop button, switch off the voltage and depressurize the compressor. In addition, the power isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme caution and wear eye protection.
7. The owner is responsible for maintaining the unit in safe operating condition. Parts and accessories shall be replaced if unsuitable for safe operation.
8. It is not allowed to walk or stand on the roof of the compressor canopy.
1.3 Safety precautions during installation
All responsibility for any damage or injury resulting from neglecting these precautions, or non-observance of the normal caution and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by the manufacturer.
2920 7089 80 5
Instruction book
Precautions during installation
1. The machine must only be lifted using suitable equipment in accordance with the applicable safety regulations. Loose or pivoting parts must be securely fastened before lifting. It is strictly forbidden to dwell or stay in the risk zone under a lifted load. Lifting acceleration and deceleration must be kept within safe limits. Wear a safety helmet when working in the area of overhead or lifting equipment.
2. Place the machine where the ambient air is as cool and clean as possible. If necessary, install a suction duct. Never obstruct the air inlet. Care must be taken to minimize the entry of moisture at the inlet air.
3. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting the pipes. 4. Air hoses must be of correct size and suitable for the working pressure. Never use frayed, damaged or worn
hoses. Distribution pipes and connections must be of the correct size and suitable for the working pressure. 5. The aspirated air must be free of flammable fumes, vapors and particles, e.g. paint solvents, that can lead to
internal fire or explosion. 6. Arrange the air intake so that loose clothing cannot be sucked in. 7. Ensure that the discharge pipe from the compressor to the aftercooler or air net is free to expand under heat
and that it is not in contact with or close to flammable materials. 8. No external force may be exerted on the air outlet valve; the connected pipe must be free of strain. 9. If remote control is installed, the machine must bear a clear sign stating: DANGER: This machine is
remotely controlled and may start without warning. The operator has to make sure that the machine is stopped and that the isolating switch is open and locked before any maintenance or repair. As a further safeguard, persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the start equipment.
10. The machines must be installed in such a way that an adequate flow of cooling air is available and that the air from the exhaust does not recirculate to the compressor air inlet or cooling air inlet.
11. The electrical connections must correspond to the applicable codes. The machines must be earthed and protected against short circuits by fuses in all phases. A lockable power isolating switch must be installed near the compressor.
12. On machines with automatic start-stop system or if the automatic restart function after voltage failure is activated, a sign stating "This machine may start without warning" must be affixed near the instrument panel.
13. In multiple compressor systems, manual valves must be installed to isolate each compressor. Non-return valves (check valves) must not be relied upon for isolating pressure systems.
14. Never remove or tamper with the safety devices, guards or insulation fitted on the machine. Every pressure vessel or auxiliary installed outside the machine to contain air above atmospheric pressure must be protected by a pressure-relieving device or devices as required.
15. Pipework or other parts with a temperature in excess of 80˚C (176˚F) and which may be accidentally touched by personnel in normal operation must be guarded or insulated. Other high-temperature pipework must be clearly marked.
16. If the ground is not level or can be subject to variable inclinations, consult the manufacturer.
Also consult following safety precautions: Safety precautions during operation and Safety precautions during maintenance. These precautions apply to machinery processing or consuming air or inert gas. Processing of any other gas requires additional safety precautions typical to the application which are not included herein. Some precautions are general and cover several machine types and equipment; hence some statements may not apply to your machine.
6 2920 7089 80
Instruction book
1.4 Safety precautions during operation
All responsibility for any damage or injury resulting from neglecting these precautions, or non-observance of the normal precautions and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by the manufacturer.
Precautions during operation
1. Use only the correct type and size of hose end fittings and connections. When blowing through a hose or air line, ensure that the open end is held securely. A free end will whip and may cause injury. Make sure that a hose is fully depressurized before disconnecting it.
2. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote start equipment.
3. Never operate the machine when there is a possibility of taking in flammable or toxic fumes, vapors or particles.
4. Never operate the machine below or in excess of its limit ratings. 5. People staying in environments or rooms where the sound pressure level reaches or exceeds 90 dB(A) shall
wear ear protectors. 6. Periodically check that:
All guards are in place and securely fastened All hoses and/or pipes inside the machine are in good condition, secure and not rubbing There are no leaks All fasteners are tight All electrical leads are secure and in good order Safety valves and other pressure-relief devices are not obstructed by dirt or paint Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses etc. are in good repair, free of
wear or abuse 7. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a workroom, take
precautions against air pollution and possible contamination of the breathing air. 8. If available, do not remove any of, or tamper with, the sound-damping material. 9. Never remove or tamper with the safety devices, guards or insulations fitted on the machine. Every pressure
vessel or auxiliary installed outside the machine to contain air above atmospheric pressure shall be protected by a pressure-relieving device or devices as required.
Also consult following safety precautions: Safety precautions during installation and Safety precautions during maintenance. These precautions apply to machinery processing or consuming air or inert gas. Processing of any other gas requires additional safety precautions typical to the application which are not included herein. Some precautions are general and cover several machine types and equipment; hence some statements may not apply to your machine.
2920 7089 80 7
Instruction book
1.5 Safety precautions during maintenance or repair
All responsibility for any damage or injury resulting from neglecting these precautions, or non-observance of the normal precautions and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by the manufacturer.
Precautions during maintenance or repair
1. Always wear safety glasses. 2. Use only the correct tools for maintenance and repair work. 3. Use only genuine spare parts. 4. All maintenance work shall only be undertaken when the machine has cooled down. 5. A warning sign stating "work in progress; do not start" shall be attached to the starting equipment. 6. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no
one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote start equipment.
7. Close the compressor air outlet valve before connecting or disconnecting a pipe. 8. Before removing any pressurized component, effectively isolate the machine from all sources of pressure and
relieve the entire system of pressure. 9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety precautions against toxic
vapors of cleaning liquids. 10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by covering the parts and
exposed openings with a clean cloth, paper or tape. 11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be completely purged,
e.g. by steam-cleaning, before carrying out such operations. Never weld on, or in any way modify, pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the machine shall be stopped but no inspection covers shall be opened before sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil vapor when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel etc. 14. Make sure that no tools, loose parts or rags are left in or on the machine. 15. All regulating and safety devices shall be maintained with due care to ensure that they function properly. They
may not be put out of action. 16. Before clearing the machine for use after maintenance or overhaul, check that operating pressures, temperatures
and time settings are correct. Check that all control and shut-down devices are fitted and that they function correctly. If removed, check that the coupling guard of the compressor drive shaft has been reinstalled.
17. Protect the motor, air filter, electrical and regulating components etc. to prevent moisture from entering them, e.g. when steam-cleaning.
18. Make sure that all sound-damping material and vibration dampers, e.g. damping material on the bodywork and in the air inlet and outlet systems of the compressor, are in good condition. If damaged, replace it by genuine material from the manufacturer to prevent the sound pressure level from increasing.
19. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls. 20. The following safety precautions are stressed when handling refrigerant:
Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if required, use breathing protection.
Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If liquid refrigerant contacts the skin through clothing, never tear off or remove the latter; flush abundantly with fresh water over the clothing until all refrigerant is flushed away; then seek medical first aid.
21. Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.
8 2920 7089 80
Instruction book
Also consult the following safety precautions: Safety precautions during installation and Safety precautions during operation. These precautions apply to machinery processing or consuming air or inert gas. Processing of any other gas requires additional safety precautions typical to the application which are not included herein. Some precautions are general and cover several machine types and equipment; hence some statements may not apply to your machine.
2920 7089 80 9
Instruction book
2 General description
2.1 General description
Introduction
LE are air-cooled, two cylinder, single-stage, lubricated piston compressors, built for effective working pressures up to 10 bar.
Compressor block with unloading valve
Power pack
10 2920 7089 80
Instruction book
Power pack with unloading valve
Base mounted
2920 7089 80 11
Instruction book
Tank-mounted, LE 2 up to LE 3, horizontal receiver
Tank-mounted, horizontal receiver
12 2920 7089 80
Instruction book
Tank-mounted, Full-Feature unit, 475 l receiver
LE Trolley Petrol/Electric
Reference Description AF Air filter AR Air receiver AV Air outlet valve CV Check valve Dm Condensate drain valve Dp Oil drain plug FC Filler cap FN Fan
2920 7089 80 13
Instruction book
Reference Description Gp Air pressure gauge M Motor MDR Air pressure switch Me Electric motor Mp Petrol engine P1 Hourmeter, running time PD Pulsation damper RV Pilot valve S1 On/off switch S2 On/off switch dryer SG Oil sight glass SV Safety valve
UA Unloader US Blow-off silencer Y1 Loading solenoid valve
Reference Description 1 Cover 2 Air inlet silencer 3 Crankcase 4 Cooling pipe 5 Left cylinder 6 Right cylinder 7 Pictograph, see Pictographs 8 Electric cabinet 9 Dewpoint indicator 10 Refrigerant dryer 11 Lifting yoke 12 Towing handle 13 Fuel tank
Compressor variants
The compressor block includes: Crankcase (3) and cylinders (5) and (6) Air inlet filter (AF) and inlet silencer (2) Fan (FN) Air cooler piping Check valve (CV) or Unloader (UA) Safety valve (SV)
The Power Pack comprises:
14 2920 7089 80
Instruction book
For LE 2 up to LE 3: The Compressor Block as described above, with flanged-on electric motor (M),
check valve (CV) and safety valve (SV) For LE 5 up to LE 20: The Compressor Block as described above, with flanged-on electric motor (M)
and safety valve (SV)
The tank-mounted unit comprises:
For LE 2 up to LE 3: The Power pack mounted on a horizontal or vertical air receiver (AR) with air outlet valve (AV), pressure gauge (Gp), safety valve (SV), air pressure switch with an on/off button (MDR) and condensate drain valve (Dm).
For LE 5 up to LE 20: The power pack mounted on an air receiver (AR) with air outlet valve (AV), pressure gauge (Gp), safety valve (SV), and condensate drain valve (Dm). An electric cubicle (8) includes the motor starter. A separate air pressure switch (MDR) is provided.
The base-mounted unit is a fully operational unit with air pressure switch and on/off switches mounted on a frame (no air receiver).
LE Trolley units are mobile compressors. They are equipped with either a directly flanged electric motor or a petrol engine. The compressors have two outlet connections:
A connection for compressed air at working pressure. A connection for compressed air at reduced pressure via a pressure regulator.
The Full-Feature compressor is a tank-mounted compressor provided with a Refrigerant dryer with DD & PD filter. They remove moisture from compressed air by cooling the air to near freezing point. This causes water to condense. The condensate is automatically drained. The air is warmed up before leaving the dryer.
2.2 Options
The compressors are extendible with the following options. For detailed information consult Atlas Copco.
Silencing hood For 90 / 250 /475 Tank Mounted and Base Mounted Units LE15 and LE20 are not available with hood. Not as Tankmounted, Base Mounted or Sales Version
Receiver upgrade
Receiver size upgrade 90 to 250 Standard Receiver.Vertical Receiver upgrade 90 or 250 to 250. Only for 2 and 3hp 475 Receiver upgrade 90 or 250 to 475
Pneumatic drain Not available for Trolley versions
Interstage drain Not available
Transformer 100VA (for cubicle control voltage 400/3/50) YD only
2920 7089 80 15
Instruction book
Motor anti-condensation heaters and thermistor protection
Used with LE 2-20 with 400V/50Hz and 460V/60Hz
CD adsorption dryer LE 2-3 on 90 and 250 receiver
Heavy duty air inlet filter For PP-BM-TM-FF versions
Oil level switch make contact (NO) break contact (NC)
Receiver wheel set Wheelset for 90/250 receiver
Power supply cable (3 m)
with red CEE 3-pole plug 16A L = 3 mtr
Auto restart offload valve (solenoid valve to make sure unit will start after power failure)
Timer drain (solenoid operated)
all Receiver Mounted units
Used For DOL 230v/50hz and 400v/50hz Units
Invalid Combinations for Any other voltages or frequencies and YD units
2.3 Air flow
LE 2 up to LE 20
Air drawn through air filter (AF) and inlet silencer (1) into cylinders (2 and 3) is compressed, then discharged through cooler piping (4) and (5)”and check valve (CV) / unloader valve (UA)” into air receiver (AR).
16 2920 7089 80
Instruction book
Air flow and regulating system with DOL starter
2920 7089 80 17
Instruction book
Air flow and regulating system with Y/D starter
18 2920 7089 80
Instruction book
Air flow and regulating system of trolley
2920 7089 80 19
Instruction book
Full-Feature
Air flow and regulating system, Full- Feature
References on flow diagrams
Reference Description AF Air filter AR Air receiver AV Air outlet valve AV1/AV2 Air outlet valves CV Check valve Dm Condensate drain valve FC Oil filler cap FN Fan Gp Air pressure gauge M Motor MDR Air pressure switch PD Pulsation damper S1 On/off switch
20 2920 7089 80
Instruction book
Reference Description RV Pilot valve SV Safety valve UA Unloader UV Unloading valve US Blow-off silencer Y1 Loading solenoid valve
DP Oil drain plug SG Oil level sight-glass
Reference Description 1 Air inlet silencer 2 Left cylinder 3 Right cylinder 4 Cooler 5 Cooling pipe 6 Pressure release valve 7 Electrical cubicle 8 Plunger 9 Spring 10 Pressure regulator 11 Refrigerant dryer
2.4 Regulating system
LE 2 up to LE 20 with DOL starter
The regulating system includes:
Check valve (CV) Air pressure switch (MDR) with pressure release valve (6) and on/off button (S1). For 10 to 20 Hp also Sol valve (for quicker discharge of head)
Operation
Air pressure switch (MDR) opens and closes its contacts at pre-set pressures. During loaded operation, the contacts are closed: the motor is running.
When the pressure in the air receiver reaches the pre-set maximum pressure, the contacts as well as pressure release valve (6) are opened. The motor stops, the air at the delivery side of the compressor is vented to atmosphere and check valve (CV) closes to prevent venting of the receiver.
When the pressure in the air receiver decreases to the pre-set minimum pressure, the contacts of the air pressure switch close and pressure release valve (6) closes. The motor restarts and compressed air is supplied to the receiver again.
LE 5 up to LE 20 each with Y/D starter
The regulating system includes:
2920 7089 80 21
Instruction book
Electric cubicle Air pressure switch (MDR) On/off switch (S1) Solenoid valve (Y1) Unloader (UA) with integrated check valve (CV)
Operation
Air pressure switch (MDR) opens and closes its contacts at pre-set pressures. During loaded operation, the contacts are closed: the motor is running and solenoid valve (Y1) is energized preventing the compressed air from flowing to unloader (UA).
When the pressure in the air receiver reaches the pre-set maximum pressure, the contacts of pressure switch (MDR) open. The motor stops and solenoid valve (Y1) is de-energized. Compressed air from the receiver will flow via the solenoid valve to plunger (8) which causes unloading valve (UV) to open. The air at the delivery side of the compressor is blown through silencer (US) to atmosphere and check valve (CV) closes to prevent venting of the receiver.
When the pressure in the air receiver decreases to the pre-set minimum pressure, the contacts of the pressure switch close. The motor restarts and, after switching over from star to delta, solenoid valve (Y1) is energized. Control air from the unloader plunger chamber is vented to the atmosphere. Unloading valve (UV) closes and compressed air is supplied to the receiver again.
LE Trolley
The regulating system includes:
Pilot valve (RV) Unloader (UA) with integrated check valve (CV) Electric cabinet (only on electric motor driven Trolley compressors)
Operation
Pilot valve (RV) opens and closes at pre-set pressures. During loaded operation, pilot valve (RV) is closed preventing the compressed air from flowing to unloader (UA).
When the pressure in the pulsation dampers (PD) reaches the pre-set maximum pressure, pilot valve (RV) will open. Compressed air from the pulsation dampers will flow to plunger (8) which causes unloading valve (UV) to open. The air at the delivery side of the compressor is blown through silencer (US) to atmosphere and check valve (CV) closes to prevent venting of the pulsation dampers. The compressor runs unloaded.
When the pressure in the pulsation dampers decreases to the pre-set minimum pressure, the pilot valve closes. Control air from the unloader plunger chamber is vented to the atmosphere. Unloading valve (UV) closes and compressed air is supplied to the pulsation dampers again.
22 2920 7089 80
Instruction book
3 Installation
3.1 Dimension drawings
Dimension drawings
B B
A
496
40
For Dismantling Air filter
254
202
X
VIEW F G-G
Cooling Air Inlet
Compressor Air Inlet
LE/LF/LT 2-3:WITHOUT VIBRATION DAMPERLE/LF/LT 5 :WITH VIBRATION DAMPER
G
G112 20
157
100
91
30
141
368
Compressed Air outletG1/2"
26
167
Pitc
h Ø
154
H7
Ø
21
8 p9
Ø 5k 52
M8(4x)
VIEW F
M10
N e t M a s s B lo c k ( K g )
N e t M a s s P o w e r p a c k ( K g )
A B C D E
542 6 1 5943155542 6 1 5943155
T y p e
5 0 4 2 5 2
L T
3 0
3 0 5 3 3 2 7 9
L E / L F
3 6 5 7 76 8 7
6 8 7
Cooling Air Inlet
Cooling Air inlet
157
615
Compressed Air outletG1/2"
26
74 � 0,5
167
506
E
C
40
For dismantling Air filter
71
Compressed Air OutletG1/2"
VIEW H
VIEW H
D
Y
Z
9820 2239 01/0881448D
LE 2 up to LE 5, Power Pack
2920 7089 80 23
Instruction book
F-F
Cooling Air Inlet
Compressor Air Inlet
LE/LT/LF 7-10
F
F
VIEW E
A
300 B
H
K
457
49,5
135
173
290
221
601
40
For Dismantling Air inlet
8,5
� hctiP 041
154
H7
Ø
M8(4x)
M10
X
VIEW E
J
10 p9
30
Ø 5K 53
25
Compressor Air OutletG1/2"
VIEW H Cooling Air inlet
C
D74 � 0,5
E
VIEW H
G
Z
Y
F
Compressor Air OutletG 1/2"
Net Mass Block (Kg)
Net Mass Power pack (Kg)
A B C D E F G H J K
06821409710 102 932
10 (60Hz) 102 929 225 109 23*7 90 412 860
10 102 453 9327 90 412 860
10 102 453 932
25
Type
LE
45
600 300453
LT 610 310
LF 600 300
187
187
71
71
15
15
177 619820 2239 02/08
81449D
LE 7 up to LE 10, Power Pack
24 2920 7089 80
Instruction book
9820 2239 07/0281450D
Z ( 1:2 )
VIEW Y
Z
COOLING AIRINLET
AIR INLETFOR DISMANTLING AIR FILTER
B
A
394
244
60
25,5
266
99
74
228
293COMPRESSED AIROUTLET G1/2" 42
589
� 14(4x)
VIEW Y
� 270
14pg
� 45 k5M16
39,5
- 0,20
+
667
VIEW X
COOLING AIR
C
D
277
36,5
678
110
COMPRESSED AIROUTLET G1/2"
VIEW X
395 � 0,5
TYPE FRAME SIZE NET MASS BLOCK NET MASS POWERPACK A B C DLE 15 O 98 164 719 359.5 545 1067LE 20 O 98 198 719 359.5 545 1094LT 15 O 98 166 682 353 545 1067LT 20 O 98 194 713 353 545 1094
LE 10 up to LE 20, Power Pack
2920 7089 80 25
Instruction book
9820 2239 42/0681452D
Type Net Mass (Kg) A B C D E FLE/LF 2 47 613LE/LF 3 51LE/LF 5 53 205 641 506
LT 2 47 613LT 3 51LT 5 53 205 641 506
504 252
533 279
496
496
631682
682
195
195 631
BM LE/LT/LF 2-3-5 DOL
252 B
A
10
D40
125
555
4198
395
E40
F
For dismantling Air filter
Compressor Cooling Air inlet
Cooling Air outlet
MotorCooling Air inlet
Compressor air Inlet
C
540166
Compressed Air ouletG 1/2"
6
LE 2 up to LE 5, Base-mounted
26 2920 7089 80
Instruction book
9820 2239 43/0581453D
Type Net mass (Kg) A B C D
LE/LT/LF 7 92 860 322 205 721
LE/LT/LF 10 104 932 322 205 721
LE 10 (60 Hz) 104 929 360 243 759
Compressor cooling Air inlet
Cooling Air outlet
Motor cooling Air inlet
Compressor Air inlet
BM LE/LT/LF 7-10 YD300300
600
154 555
198
395
24
10
C C
D40
For dismantling Air filter
B
125
248 541
A
244Compressed Air outletG1/2"
LE 7 up to LE 10, Base-mounted
2920 7089 80 27
Instruction book
9820 2239 41/0881454D
B
MN
K L MIN. 280
E
DA
B
COOLING AIROUTLET
COOLING AIR OUTLET
MOTOR COOLINGAIR INLET
COMPRESSOR AIR+COOLING AIR INLET
G 130 39525 540 F
TYPE SIZE NET MASS A B D E F G K L M N
LE 10 (50 Hz) 171 740 816 1180 1395 185 42.5 191.5 155 296.5 123.5
LF 10 (50 Hz) 171 740 816 1180 1395 185 42.5 191.5 155 296.5 123.5
LT 10 (50 Hz) 171 740 816 1180 1395 185 42.5 191.5 155 296.5 123.5
LE 10 (60 Hz) 240 830 880 1360 1410 369 87.5 322 194 330 82
LT 10 (60 Hz) 171 830 880 1360 1410 369 87.5 322 194 330 82
TYPE NET MASS A B D E F G K L M N
LE/LT/LF 2 101 680 731 890 1254 130 12.5 191.5 100 229.5 85.5
LE/LT/LF 3 105 680 731 890 1254 130 12.5 191.5 100 229.5 85.5
LE/LT/LF 5 107 680 731 890 1254 130 12.5 191.5 100 229.5 85.5
LE/LT/LF 7 159 740 816 1180 1395 185 42.5 191.5 155 296.5 123.5
LE/LT/LF 10 171 740 816 1180 1395 185 42.5 191.5 155 296.5 123.5
LE 2 up to LE 20, Pack with silencing hood
28 2920 7089 80
Instruction book
9820 2239 21/0781455D
Receiver (L) Netmass (Kg) A B2 853 892 933 97
504
533 279
252LE/LF
Type
LT
90
90
TM 90L LE/LT/LF 2-3
Cooling air inlet
Cooling air outlet
Compressor air inlet
181
982
640
191600
979
� 370
40
For dismantling air filter
A
252 B
10
615
529
483
364
318
Compressed air outletG 1/2"
Manual drainG 1/4"
Slot Hole 15x25 (4x)
LE 2 up to LE 3, Tank-mounted, receiver 90 l
2920 7089 80 29
Instruction book
9820 2239 23/0581456D
Cooling Air inlet
Cooling Air outlet
Compressor Air inlet
1149
1645
40
For DismantlingAir filter
A
252 B
2
C
140
81 Ø 006
� 500
10
Manual drainG 1/4"
Compressed Air Outlet G1/2"
622
D
Type Receiver (L) Net Mass(kg) A B C D2 2653 2695 271 687 3432 2853 2895 291 687 343
533 279
615
615
271
271
LE/LF
LT
504 252250
250
LE 2 up to LE 5, Tank-mounted, receiver 250 l
30 2920 7089 80
Instruction book
9820 2239 22/0781457D
R e c e i v e r ( L ) N e t M a s s ( K g ) A B C D E F G H E K2 1 4 73 1 4 95 1 5 02 1 6 73 1 6 95 1 7 02 1 4 73 1 4 95 1 5 0
1 0 8 2L T 5 3 3 2 7 9
L F 5 0 4 2 5 2
3 3 6 3 8 2 5 7 5 4 5 0
2 5 2
4 1 8 1 8 5 2 3 1 0
T y p e
L E
2 5 0
5 0 4
Type Receiver (L) Net Mass (Kg) A B C D E F G H J KLE 5 185 504 252LT 5 245 533 279LF 5 185 504 252
1261455 1926 395 476475 530 754 600
Cooling air Outlet
Cooling air Inlet
Compressor air inlet
LE/LT/LF 5
OPTIONAL LARGER VESSEL ON LE/LT/LF 2-3-5
C 960
Dmax
687
E
Ø J
H
G
40K
252 B
A
F
For dismantling air filter
60
Compressed Air outlet G 1/2"
365
Manual drainG 1/4"
10
LE 2 up to LE 5, Tank-mounted, horizontal receiver 250/475 l
2920 7089 80 31
Instruction book
LE/LT/LF 7-10
D
M40
C
E 960
10
62F max.
H
J
G
K
296 B
A
290
Ø L
21161
FOR DISMANTLING AIR FILTER
COMPRESSORCOOLINGAIR INLET
COOLINGAIR OUTLET
MOTORCOOLINGAIR INLET
COMPRESSEDAIR OUTLET
G 1/2"
COMPRESSORAIR INLET
COMPRESSORAIR INLET
MANUAL DRAINOUTLET G 1/4"
SLOT HOLE15x25 (4x)
TYPE
LE/LT/LF 7
LE /LT/LF 10
NET MASS A B C
411,5
452,5
D
859,5
931,5
E
418
F
1852
G
310
H
336
J
382
K
575
L
450
M
116208
189
201
592 296
606 310
452,5 931,5455 1926 395 476 530 754 600 1341
224
236 606 310
WITH 250L RECEIVER
TYPE
LE/LT/LF 7
LE /LT/LF 10
NET MASS A B C D E F G H J K L M
08
WITH 475L RECEIVER
411,5 859,5592 296
LE 10 (60Hz) 201 600 300 453 929
LE 10 (60Hz) 236 600 300 453 929
418 1852 310 336 382 575 450 1200
455 1926 395 476 530 754 600 1379
9820 2239 25/0881737D
LE 7 up to LE 10, Tank-mounted, horizontal receiver 250/475 l
32 2920 7089 80
Instruction book
9821 1041 00/1081738D
Receiver(L) Net Mass(Kg) A B BB C D E F G H J K L M N250 - 390 1793 310 336 382 554 450 1250475 - 427 1867 395 476 530 729 600 1425250 - 390 1793 310 336 382 554 450 1250475 - 427 1867 395 476 530 729 600 1425250 - 390 1793 310 336 382 554 450 1250475 - 427 1867 395 476 530 729 600 1425250 - 390 1793 310 336 382 554 450 1250475 - 427 1867 395 476 530 729 600 1425
960
Type
68715
20
LE
718
1062.5
1089.5LT
353 540
334
365
15 687 334 1062.5
20 718 365 1089.5
Air Inlet
Cooling air Inlet Electrical cable entry
(pg 21on rear side)
Gmax 60
E F
N60
BB B
A
ØM
J
K
395
H
D
Compressed AirOutlet G1/2"C
10
SLOT HOLE 15x25(4x)
L
For Dismantling Air Filter
Manual drainG 1/4"
LE/LT 15-20
LE 15 up to LE 20, Tank-mounted, horizontal receiver 250/475 l
2920 7089 80 33
Instruction book
9820 4496 00/0181458D
Compressor Air inlet
960 384
1782
� 450
1390
60
310�
3
10
605�
6
H �
6
Manual drain outlet G 1/4"
Compressed air outlet G 1/2"
Dryed compressed air outlet G 1/2"
402 � 5
352 � 585
0�
6
76For dismantlingair filter
Cooling air inlet
Cooling air outlet
40A
B C
748
28 495
1090
�6
485
326
286
Dryer cooling air outlet
Dryer cooling air inlet
D
Type Net Mass A B C D HLE/LF 2 504 252
LT2 533 279LE/LF 3 504 252
LT3 533 279LE5 504 252LT5 533 279
1072175 kg
1082
171 kg
177 kg
252 686
LE 2 up to LE 7, Tank-mounted, Full-Feature, receiver 250 l
34 2920 7089 80
Instruction book
9820 4497 00/0181459D
Compressor Air inlet
476 � 5
10
1888
395�
3
767�
6
1012
�6
H �
6
Compressed air outlet G 1/2"
Manual drain outlet G 1/4"
Dryed compressed air outlet G 1/2"
60
75For dismantlingair filter
Cooling air inlet
Cooling air outlet
530 � 5
� 600
1398
960 437
A
B C
40
1
1
27 495
748
1252
�6
485
327 1
287
Dryer cooling air outlet
Dryer cooling air inlet
D
Type Net Mass A B C D HLE5 225 kg 510 255 255 686 1261LT5 225 kg 533 255 279 686 1261LF5 / LE7 265 kg 592 296 296 860 1341LT/LF 7 265 kg 606 296 310 860 1341LE 10 (50Hz) 282 kg 592 296 296 932 1341LT 10 (50Hz) 277 kg 606 296 310 932 1341LF 10 / LE 15 320 kg 790 418 372 1000 1379
LE 5 up to LE 20, Tank-mounted, Full-Feature, receiver 475 l
2920 7089 80 35
Instruction book
9820 2239 24/0881460D
COOLING AIR OUTLET
COOLING AIR OUTLET
COMPRESSED AIR OUTLET G1/2"
COOLING AIR INLET
L 890
100191,5680
A
B
ØK
H
G
C
254
D M
Emax 60
F
J22
9,5
N
10
Manual drain outlet G1/4"
SLOT HOLE 15x25 (4x)
Receiver Net Mass
(Kg)A B C D E F G H J K L M N
2 1933 1955 197
LF/LE 5 475 232 1340 754 1872 455 1926 395 476 530 1025 600 2302 2013 2035 205
LT 5 475 240 1340 754 1872 455 1926 395 476 530 1025 600 2302 1333 1355 1372 1413 1435 145
1852 310 336
Type
1161 1694250LF/LE 418575 846382 450 193
LT 250 1161 575 1694 418 1852 310 193336 382 846 450
960 115
LF/LE 90 1076 483 1603 191 1034 370275 318 368 761
LT 90 1076 483 1603 191 1034 275 45
600 155
318 368 761 370
45
LE 2 up to LE 5, Tank-mounted with silencing hood
36 2920 7089 80
Instruction book
9820 2239 26/0981461D
LE 7 up to LE 10, Tank-mounted with silencing hood
2920 7089 80 37
Instruction book
9820 2239 71/0781462D
1569
1131
795
A
Compressed air outlet
40 (For dismantling air filter)
AirInlet
363
220
10
311,5
375
438
1104
776
TYPERECEIVER
(lit.)NET MASS
(Kg) A
LE/LT/LF 235
LE/LT/LF
15107
LE/LT20
2 x 10 ltr.
2 x 10 ltr.
2 x 10 ltr.
9599
101140152216248
812
891
1024
LE Trolley with electrical motor
38 2920 7089 80
Instruction book
9820 2239 91/0581463D
LE Trolley with petrol engine
References of figures on dimension drawings.
Reference Description 1 Air inlet 2 Hole, 15 x 25 (4X) 3 Cooling air inlet 4 Net mass 5 Compressed air outlet, G1/2
2920 7089 80 39
Instruction book
Reference Description 6 Manual condensate drain 7 Hole, 15 x 25 (3X) 8 Receiver 9 Cooling air inlet 10 Motor cooling air inlet 11 Compressed air outlet 13 Compressor cooling air and air inlet 14 For dismantling air filter 15 Compressor air outlet with flexible (2 meters) 16 Electric cable entry (on rear side) 19 Air outlet
3.2 Installation instruction
Install the unit in an area where the noise levels do not cause inconvenience and adequate ventilation is available for cooling purposes.
Before commencing installation, check that the electrical data on the compressor specification plate/s are compatible with the local power supply. Before connecting, the electricity, ensure that the power supply is off and correctly isolated. The electrical power supplied to the compressor unit must be connected by a qualified electrician in accordance with the wiring diagram supplied with the plant. All wiring must be in accordance with IEE regulations. Cable sizes given in section. Electric data are recommendations only.
Installation proposal for tank-mounted unit (90 l receiver)
40 2920 7089 80
Instruction book
Installation proposal for tank-mounted unit (250/475 l receiver)
2920 7089 80 41
Instruction book
Installation proposal for tank-mounted unit (vertical 250 l receiver)
42 2920 7089 80
Instruction book
Installation proposal for base-mounted unit with optional silencing hood
2920 7089 80 43
Instruction book
Installation proposal for tank mounted compressors with silencing hood
References of figures on installation drawings.
Reference Description 1 Cooling air outlet 2 Compressor air and cooling air inlet
LE
Install the compressor horizontally, in a cool but frost-free and well-ventilated room. Place the compressor as level as possible; however, LE can be operated with a maximum inclination of 40% (22.5 degrees) in any direction. The air should be clean.
A Base mounted unit with hood option must be installed away from walls to allow easy maintenance. Keep the ventilation openings free.
It is recommended to install an automatic condensate drain (available as an option) on the air receiver to ensure continuous condensate removal.
LE trolley
44 2920 7089 80
Instruction book
The compressors are equipped with a lifting eye or yoke. When running, the compressor must be installed as level as possible; however, it can be operated temporarily in an inclined plane of maximum 25% (or 20 degrees). Keep the compressor in a frost-free and well-ventilated place.
3.3 Electrical connections
Warning
The electrical connection must be carried out by an electrician and corresponds to the local codes. The indications on the motor data plate must correspond to the power supply voltage and frequency. The installation must include an isolating switch in the power line near to the unit and be protected against short-circuits by fuses for each phase refer section Overload relays and fuses or Cable sizes. The power supply and earthing lines must be of suitable size. refer section Overload relays and fuses or Cable sizes. For DOL starters, connect the power supply cables as shown in the electrical diagrams. For Y/D starters, connect the power supply cables to terminal board (X1) as shown in the picture. Check the setting of the overload relay. refer section Overload relays and fuses or Cable sizes.
2920 7089 80 45
Instruction book
Electric cabinet
Example of an electrical cubicle
Reference Description F1 Fuse
46 2920 7089 80
Instruction book
Reference Description F4 Overload relay K1 Line contactor with integrated Y-D timer K2 Star contactor K3 Delta contactor P Hourmeter, running hours X1 Terminal board S1 On/off switch
Electrical diagram with direct-on-line starter
3.4 Settings of overload relay and fuses
Settings of overload relay - fuses of compressors with DOL starter
50 Hz
Type Voltage (V)
Overload relay (A)
Fuses (A)
LE 2 230 MONO 10 16
LE 2 230 7 10
LE 2 400 4 6
LE 2 500 3 6
2920 7089 80 47
Instruction book
Type Voltage
(V) Overload relay (A)
Fuses (A)
LE 3 230 MONO 14 20
LE 3 230 10 16
LE 3 400 5.2 10
LE 3 440 5 10
LE 3 500 4 6
LE 3 550 3 6
LE 3 660 2.8 6
LE 3 1000 2 4
LE 5 230 16 25
LE 5 400 10 16
LE 5 690 5 10
LE 5 1000 4 6
LE 7 230 22 32
LE 7 400 14 20
LE 7 550 9 16
LE 7 690 6 10
LE10 400 15 20
LE10 690 9 16
LE15 400 21.5 32
LE20 400 30 50
60 Hz
Type voltage (V)
overload relay (A)
fuses (A)
LE2 230 MONO 10 16
LE2 230 7 10
LE2 380 4 6
LE2 460 3.4 6
LE2 575 3 6
LE2 690 2 4
LE3 230 MONO 14 20
LE3 230 10 16
LE3 380 6.5 10
LE3 460 5.5 10
48 2920 7089 80
Instruction book
Type voltage (V)
overload relay (A)
fuses (A)
LE3 575
LE5 230 MONO 29 40
LE5 230 16 25
LE5 380 11 16
LE5 460 9 16
LE5 575
LE7 230 22 32
LE7 380 15 20
LE7 460 12 20
LE7 575 10 16
LE10 230 30 50
LE10 380 18 32
LE10 460 15 25
LE10 575 11 20
LE15 230 47 63
LE15 460 23 40
LE15 575 18 32
LE20 230 58 80
LE20 460 29 50
LE20 575 23 32
Settings of overload relay and fuses of compressors with Y-D starter
50 Hz
Type voltage
(V) overload relay (A)
fuses (A)
LE5 230 10.5 25
LE5 400 6 16
LE5 500 4 10
LE5 550 5 10
LE7 230 14 32
LE7 400 8 20
LE7 440 7 16
LE7 500 6 16
2920 7089 80 49
Instruction book
Type voltage (V)
overload relay (A)
fuses (A)
LE7 550 5 16
LE7 575 4.8 12
LE7 660 4 12
LE7 1000 2.5 6
LE10 230 16 40
LE10 400 10.5 25
LE10 440 9 25
LE10 500 7 20
LE10 550 6 16
LE10 660 5 16
LE10 690 5 16
LE10 1000 4 10
LE15 230 25 63
LE15 400 15 40
LE15 500 12 32
LE15 550 10 25
LE20 230 34 80
LE20 400 20 50
LE20 500 14 32
LE20 550 13 32
60 Hz
Type voltage (V)
overload relay (A)
fuses (A)
LE5 230 10.5 25
LE5 380 6.5 16
LE5 460 5.5 16
LE7 230 14 32
LE7 380 8.5 20
LE7 460 7 16
LE7 575 5.5 16
LE10 230 16 40
LE10 380 10.5 25
LE10 460 9 20
LE10 575 7 20
50 2920 7089 80
Instruction book
Type voltage (V)
overload relay (A)
fuses (A)
LE15 230 25 50
LE15 380 15 40
LE15 460 13 32
LE20 230 31 80
LE20 380 20 50
LE20 460 15 40
2920 7089 80 51
Instruction book
3.5 Cable sizes
Starter Cable size
mm² LE 2 and LE 3 DOL 2.5 LE 5 and LE 7 DOL 4 LE 10 DOL 6 LE 5 Y/D 2.5 LE 7 Y/D 4 LE 10 and LE 15 Y/D 6 LE 20 Y/D 10
3.6 Pictographs
10
Reference Description 1 Temperature 2 Pressure 3 On 4 Off 5 Warning: voltage 6 Switch off voltage and depressurize before maintenance or repair 7 Read Instruction book before starting 8 Consult Instruction book for correct rotation direction 9 Do not adjust switch if it is depressurized
10 Drain label - drain out the tank daily - annually have the thickness of the tank walls checked by a competent body, recording the date of the service task on the label.
52 2920 7089 80
Instruction book
4 Operating instructions
4.1 Initial start-up
If the compressor has not run for the past 6 months (at initial start-up check the date on the data plate), it is strongly recommended to improve the lubrication of the compressor element: drain the oil, refill the compressor with the same oil while turning the crankshaft.
1. For Tank-mounted and base mounted units, remove the RED transport brackets from underneath the compressor.
2. Check the electrical installation, which must be in accordance with the instructions given in Electrical connection.
3. LE are filled with Piston Fluid compressor oil. Check that the oil level is still at the top of the red circle of sight-glass (SG).
4. Switch on the voltage. Start the motor. 5. Check the operation of the air pressure switch. See section Adjustment of pressure switch Check the
operation of pilot valve (RV) on LE Trolley. See section Adjustment of pilot valve. 6. On LE 15 and 20 compressors, check for correct direction of rotation, as indicated by the arrow on the fan
housing
4.2 Starting
LE
1. On LE check the oil level, which must be at the top of the red circle of sight-glass (SG). The minimum level is the lower part of the red circle.
2. Switch on the voltage. 3. Turn the switch to position I (Auto), or turn switch (S1) to position I.
4. For the full feature units, also push the switch to position I to start up the refrigerant dryer. Approximately 10 minutes later, the nominal dewpoint will be reached.
2920 7089 80 53
Instruction book
To ensure optimum operational efficiency, do not use dryer on/switch repeatedly within a short time period. Wait at least 5 minutes to start the dryer again after stopping to allow pressure equalization.
5. Open the air outlet valve (AV).
Regularly drain condensate
LE Trolley with electrical motor
1. On LE check the oil level, which must be near the top of the red circle of sight-glass (SG). The minimum level is the lower part of the red circle.
2. Set pilot valve (RV) in the unload position by turning the red handle 90 degrees. See section Adjustment of pilot valve.
3. Attach the air lines to the air outlets. 4. Plug in and switch on the voltage at the main circuit breaker.
Warning: Never move the compressor after plugging it in.
5. Move switch to position I or push switch (S1) to position I. 6. Open the outlet valves (AV1 and AV2). 7. Set pilot valve (RV) in the load position by turning the red handle 90 degrees. See section Adjustment of
pilot valve. 8. Turn the regulating knob of the pressure regulator (10) clockwise or counter-clockwise to increase or
decrease the pressure at the outlet of the pressure regulator.
Regularly drain condensate (Dm).
LE Trolley with petrol engine
1. On LE check the oil level, which must be near the top of the red circle of sight-glass (SG). The minimum level is the lower part of the red circle.
2. Check the engine oil level as follows: Remove the oil filler cap and wipe the dipstick clean. Insert the dipstick into the filler neck, but do not screw it in. The oil level must show between the minimum and maximum marks on the dipstick.
3. Fill the fuel tank with unleaded or low-leaded petrol (gasoline).
54 2920 7089 80
Instruction book
4. Start the engine, consult the engine "Owner's manual". 5. Attach the air lines to the air outlets. 6. Open the outlet valves (AV1/2). 7. Set pilot valve (RV) in the load position by turning the red handle 90 degrees. See section Adjustment of
pilot valve. 8. Turn the regulating knob of the pressure regulator (10) clockwise or counter-clockwise to increase or
decrease the pressure at the outlet of the pressure regulator.
Regularly drain condensate (Dm)
4.3 Stopping
LE
1. Turn the switch to position 0 (Off), or push switch (S1) to position 0. 2. Close air outlet valve (AV) 3. Switch off the voltage.
If a compressor with pressure switch stops during operation because of a power failure, the pressure from the air outlet pipe must be released by moving the switch on top of the air pressure switch to 0 to prevent the compressor from restarting against back-pressure when the power becomes live again.
LE Trolley
1. Set pilot valve (RV) in the unload position by turning the red handle 90 degrees. See section Adjustment of pilot valve.
2. On LE Trolley with electrical motor, move switch to position 0 or push switch (S1) to position 0.If the compressor is not required for immediate further use, switch off the voltage at the main circuit breaker and unplug.
3. On LE Trolley with petrol engine Stop the engine, consult the engine "Owner's manual". 4. Close the air outlet valves (AV1 and AV2). Depressurize and disconnect the air lines from the outlet valves.
4.4 Taking out of operation
At the end of the service life of the compressor, proceed as follows:
1. Stop the compressor and close the air outlet valve(s). 2. Switch off the voltage and disconnect the compressor from the mains. 3. Depressurize the compressor. 4. Shut off and depressurize the part of the air net which is connected to the outlet valve. Disconnect the
compressor from the air net. 5. Drain the oil.
2920 7089 80 55
Instruction book
4.5 Storage after installation
Procedure
If the compressor is going to be stored without running from time to time, protective measures must be taken.
Protect the machine against dust and moisture, if possible in a clean, cool, dry and well ventilated area. Make sure that the machine is not subject to vibration. If the machine is stored in packing, put some vapor corrosion inhibitor (VCI) paper into the packing. Store the machine in its normal position, not upside down or on its side. If the machine is stored for 1 year or more, rotate the bearings once a month to change the position of the
roller balls in the bearings. Consult Atlas Copco Service.
56 2920 7089 80
Instruction book
5 Maintenance
5.1 Petrol engine maintenance
Consult the engine "Owner's manual".
5.2 Preventive maintenance schedule
The schedule contains a summary of the maintenance instructions. Read the respective section before taking maintenance measures. When servicing, replace all disengaged packing components, e.g. gaskets, O-rings, washers. The "longer interval" checks must also include the "shorter interval" checks.
Period Running hours
Operation Consult section See notes below table
Preventive maintenance kit
Weekly Check oil level. Starting 1 - Daily
Drain condensate from air receiver or pulsation damper.
Air receiver instructions
- -
6-monthly
Test safety valve.
Safety valve Relief valve
1 -
6-monthly
Inspect air filter. Air filter 3/4 2
Yearly 500 On LE 15 and LE 20, replace air filter.
Air filter 3/4 2
Yearly 600 On LE 5 and LE 7, replace air filter.
Air filter 3/4 2
Yearly 800 On LE 2 and LE 3, replace air filter.
Air filter 3/4 2
Yearly 2000 Change blow-off silencer, if provided.
- - 2
Yearly 2000 If mineral oil is used, change oil.
Lubrication of compressor
- -
2-yearly 3000 If Piston Fluid oil is used, change oil.
Lubrication of compressor
- -
3000 to 4000 Replace check valve or unloader.
Valves - 3/4
4000 On LE 2 up to 5 and LE 15 up to 20 replace valve discs.
Valves - 1
5000 On LE 7 up to 10 replace valve discs.
Valves - 1
2920 7089 80 57
Instruction book
Notes:
1. Maintain the level in the red circle of the sight-glass. 2. Wear gloves and safety glasses. 3. For normal operation in clean surroundings. More frequently when operating in a dusty environment. 4. In a dusty environment, a heavy-duty filter (available as an option) is essential.
Preventive maintenance schedule Full Feature units
Only applicable on the refrigerant dryer.
Period Operation Daily Inspect and clean the filter of the steam trap. Weekly Brush or blow off the finned surface of the condensor.
Note (Full Feature units):
Regularly check that the condensate is discharged via the condensate outlet of the refrigerant dryer. The amount depends on the operation conditions.
5.3 Lubrication of compressors
It is strongly recommended to use the Piston Fluid compressor oil to keep the compressor in excellent operating condition.
Traditional lubricants cannot cope with the extreme conditions of piston compressors, resulting in a fast oil degradation, overheating and potentially irreversible damage and high repair costs. Therefore, high performing lubricants increase the equipment lifetime.
Considering the low oil content in piston compressors, often less than 2 liters, the economy of lesser quality oils simply is not worth the risk.
Piston Fluid oil can be ordered in different quantities: a 1-liter can and 5-liter can.
5.4 Service kits
Service kits are available, offering the benefits of genuine Atlas Copco parts while keeping the maintenance budget low. The kits comprise all parts needed for servicing. Consult the Parts list for the contents of all kits.
58 2920 7089 80
Instruction book
Reference Description 1 Valve kit 2 Filter kit 3 Check valve 4 Unloader 5 Piston Fluid
Notes:
1. Use only authorized parts. Any damage or malfunction caused by the use of unauthorized
parts is not covered by Warranty or Product Liability. 2. Whichever interval comes first. The local Sales Company may overrule the maintenance
schedule, especially the service intervals, depending upon the environmental and working conditions of the compressor.
3. For the contents of all kits, consult the Parts list.
5.5 Disposal of used material
Used filters or any other used material (e.g. desiccant, lubricants, cleaning rags, machine parts, etc.) must be disposed of in an environmentally friendly and safe manner, and in line with the local recommendations and environmental legislation.
2920 7089 80 59
Instruction book
6 Servicing and adjustment procedures
6.1 Unloader or check valve
Warning
Release the pressure from the compressor before starting repair or maintenance works. Switch off the voltage and isolate the compressor from the mains.
Unloader or check valve
It is recommended to replace the unloader or check valve as indicated in section Preventive maintenance schedule.
Dirt, condensate, coke formation and oxidation influence the proper operation of the valve. Depending on the environmental and working conditions (ambient temperature, working pressure, load cycle, oil type), the local Atlas Copco customer center or authorized distributor may overrule the maintenance schedule (consult Atlas Copco).
6.2 Valves
A faulty valve must be replaced immediately. A faulty valve can be discovered as stated in section Problem solving Consult Atlas Copco.
60 2920 7089 80
Instruction book
It is highly recommended to replace the valve discs, O-rings and gaskets if disassembling the cylinder heads.
Cylinder heads, low pressure variants
10 97
654
3
2
11 1213 1
16
15
17
1820
1921
8
1414
81615D
Reference Description
1 Pin
2 Suction disc
3 Seat
4 O-ring
5 Delivery disc
6 Valve guard
7 Spring
8 Head
9 Bolt
10 Washer
11 Stud
12 Washer
13 Nut
14 O-ring
15 Cylinder
16 O-ring
17 Gasket
18 Bolt
19 Washer
20 Washer
21 Nut
2920 7089 80 61
Instruction book
Replacement of valve discs
Operation sequence
Remove the fan guard, unscrew the cap and remove the cover, air filter and cover of the air inlet silencer(1).
Disconnect cylinder head cover (12) from the inlet and outlet pipe flanges. Remove cylinder head cover.
Remove spring (3), outlet valve guard (4) and outlet valve disc (5). Lift off valve seat (6) and remove inlet valve disc (7). Do not remove guide pins (8). Remove and discard all O-rings. If necessary, remove the carbon deposits from the inlet valve guard at the cylinder top. Take care that
no dirt drops into the cylinder. Clean and inspect all parts. Fit a new O-ring (11). Do not stretch the cord while inserting it in its groove; the ends should meet. Put a new inlet valve disc (7) into place and install valve seat (6). Fit new O-rings (9) and (10). Install a new outlet valve disc (5), guard (4) and spring (3). Reinstall cylinder head cover (12). Fit new O-rings/gaskets (2) for the pipe flanges. Fit the flange and
cylinder head bolts and tighten them alternately. Reinstall the fan guard, cover of the air inlet silencer, air filter, cover (1).and cap.
Torque value Torque value Torque value M6: 10 Nm ±2 M8: 23 Nm ±2 M10: 46 Nm ±5
6.3 Air filter
To replace the air filter, follow these steps:
1. Stop the compressor. 2. Unscrew the cap on top of the cover. Lift off the cover and the filter element. Take care that no dirt
drops inside the suction silencer. 3. Using a damp cloth, clean the filter chamber and cover. Discard damaged elements. 4. Install the new element, cover and cap.
6.4 Adjustment MDR4 pressure switch
Views of air pressure switch MDR4
62 2920 7089 80
Instruction book
Ref Name 1 Air pressure switch 2 Solenoid valve 3 Pressure release valve 4 Adjusting screw, stopping pressure 5 Adjusting screw, pressure difference
Function
The adjustment of the maximum or stopping pressure of the compressor is effected by means of the air pressure switch. The switch also controls the pressure difference between the maximum pressure (stopping pressure) and the pressure at which compression is resumed (starting pressure).
Adjustment
• Adjust the air pressure switch while it is pressurized. • Switch off the voltage before removing the cover of the switch; reinstall it
after an adjustment has been made and before the voltage is switched on again.
The maximum pressure is controlled by adjusting screw (4). Turn the screw clockwise to raise the maximum or stopping pressure, counter-clockwise to lower it.
The pressure difference is adjusted by means of screw (5). To reduce the difference between the stopping and starting pressures, i.e. to increase the starting pressure, turn the screw counter-clockwise. To increase the pressure difference, turn the screw clockwise. The adjustment range is shown on the pressure difference diagram below.
Pressure difference diagram MDR4 - 11 bar
Ref Name (1) Starting pressure - bar(e) (2) Stopping pressure - bar(e)
2920 7089 80 63
Instruction book
Example: Stopping pressure: 7 bar(e) Starting pressure: adjustable between 3 and 5.7 bar(e)
6.5 Adjustment of MDR3 pressure switch
Views of air pressure switch MDR3 with ON/OFF switch
This pressure switch has a cover with rotary knob (4) for manual On/Off (Auto/Off).
Reference Description 1 Dial, overload relay 2 Adjusting screw, stopping pressure 3 Adjusting screw, pressure difference 4 On/off switch (Auto/Off)
Function
The switch allows the operator to select the stopping pressure and the pressure difference between stopping and starting pressures. The stopping and starting pressures are the opening and closing pressures of the switch.
Adjustment
• Adjust the air pressure switch while it is pressurized. • Switch off the voltage before removing the cover of the switch; reinstall it after an
adjustment has been made and before the voltage is switched on again.
The stopping pressure is controlled by adjusting screw (2). Turn the screw clockwise to raise the stopping pressure, counter-clockwise to lower it.
The pressure difference between starting and stopping is adjusted by means of adjusting screw (3). The adjustment range is shown in the graph below. Turn the screw counter-clockwise to reduce the pressure difference, clockwise to increase it.
64 2920 7089 80
Instruction book
Pressure difference diagram, MDR3/11 (10 bar units)
Example:
Stopping pressure: 7 bar(e) Starting pressure: adjustable between 3 and 5.7 bar(e)
Ref Name (1) Starting pressure - bar(e) (2) Stopping pressure - bar(e)
6.6 Adjustment of pilot valve on Trolley
The adjustment of the maximum or unloading pressure of the compressor is effected by means of pilot valve (RV) The valve also controls the difference between the preset maximum pressure and that at which compression is resumed.
Pilot valve on Trolley
2920 7089 80 65
Instruction book
Reference Description A Control air to unloader R Vent hole 1 Unloading handle 2 Pressure adjusting screw 3 Nuts 4 Shims
Unload mechanism
The pilot valve is equipped with a hand-operated unload mechanism: by turning the red handle (1) 90 degrees, the plunger of the valve will be lifted, releasing the spring force. The air pressure from the pulsation dampers will force down unloader plunger (8) and the compressor will run unloaded. By turning handle (1) 90 degrees further, the plunger returns to its original position so that the pilot valve will again unload and load the compressor at the pre-set pressures.
Setting of the pilot valve
The maximum pressure is controlled by adjusting screw (2): 1. Loosen handle (1) and the two nuts (3) 2. Turn the adjusting screw (2) clockwise to increase the maximum pressure. 3. The pressure difference can be increased by removing one or more shims (4). 4. Fit the two nuts (3) and handle (1) in their original position.
6.7 Safety valve
Replace the valve if it does not open at the correct pressure. No adjustment is allowed. Testing: Testing as described below shall only be carried out by competent personnel.
If safety valve is not used for longer than 6 months, pressurize for 4h to have working pressure.
Testing
1. Close the air outlet valve, depressurize and disconnect the hose or pipe from the valve 2. Start the compressor and run it until it stops automatically. 3. Switch off the voltage.
Remove the cover from the air pressure switch and, with the air receiver now under pressure, turn the adjusting screw one turn clockwise to increase the stopping pressure Adjustment of MDR4S pressure switch and Adjustment of MRD3 pressure switch. Reinstall the cover.
4. Switch on the voltage, slightly open the outlet valve and start the compressor 5. Gradually close the outlet valve while checking the air pressure gauge. If the safety valve has not
opened at the pressure specified in Compressor data, it must be replaced by a new one. If the compressor unloads before the specified opening pressure is reached, repeat the procedure as mentioned from step 3.
6. Readjust the unloading pressure as described in sections Adjustment of MDR4S pressure switch and Adjustment of MRD3 pressure switch
7. Reconnect the hose or pipe to the closed air outlet valve
66 2920 7089 80
Instruction book
Testing on Trolley
1. Close the air outlet valves, depressurize and disconnect the hoses from the valves. 2. Loosen the red handle of the pilot valve (1) and the two nuts (3) 3. Open outlet valve (AV1) a fraction. Start the compressor. 4. Gradually turn adjusting screw (2) clockwise while checking pressure gauge (Gp). If the safety
valve has not opened at the pressure specified in Compressor data, it must be replaced by a new one.
5. Readjust the normal working pressure after testing. Consult section Adjustment of pilot valve 6. Fit nuts (3) and handle (1) in their original positions.
2920 7089 80 67
Instruction book
7 Problem solving
Condition Fault Remedy Insufficient air pressure Air leak Check and correct as
necessary Air filter choked Replace filter Air pressure switch incorrectly
set Adjust switch
Air consumption exceeds maximum output of compressor
Check equipment connected
Damaged valve Inspect valves and replace parts where necessary
Unloader malfunctioning Inspect and replace parts where necessary
Solenoid valve out of order Remove and check. Replace if necessary
Unit does not speed up Voltage drop at motor terminals Consult power supplier. Use correct size of cable
Unloader malfunctioning Inspect and replace parts where necessary
Solenoid valve out of order Remove and check. Replace if necessary
Blow-off silencer choked Replace Air receiver pressure rises above maximum and causes safety valve to blow
Air pressure switch or pilot valve incorrectly set or out of order
Check. Replace switch or valve, if necessary
Solenoid valve defective Remove and check. Replace if necessary
Unloader malfunctioning Inspect and replace parts where necessary
Blow-off silencer choked Replace Receiver does not hold pressure Check valve leaks Check for broken valve and
springs Air leaks Check and correct as
necessary Too frequent starting/too short operating periods
Air pressure switch or pilot valve incorrectly set
Increase pressure difference
Check valve leaks Check for broken valve and springs
High oil consumption on LE/LT compressors
Oil level too high Do not overfill crankcase. Keep level in red circle of sight-glass
Piston ring(s) worn or broken Have condition of piston rings checked
Unit does not start Electrical failure Have electrical system checked. Check fuses and line terminals for tightness
68 2920 7089 80
Instruction book
Condition Fault Remedy Overload relay cut out Reset overload relay. If the
relay cuts out again after starting, see "Overload relay cuts out"
Air pressure above pre-set starting pressure
Compressor will start when air pressure is lower than pre-set starting pressure of air pressure switch
Overload relay cuts out Overload relay incorrectly set Check and adjust. Reset relay Solenoid valve out of order Remove and check. Replace if
necessary Unloader plunger jammed Inspect and replace parts
where necessary Blow-off silencer choked Replace Ambient temperature too high Improve ventilation of room Motor stops and starts too
frequently See "Too frequent starting/too short operating periods"
Overcurrent due to motor or compressor failure
Consult Atlas Copco
2920 7089 80 69
Instruction book
8 Technical data
8.1 Reference conditions
Inlet pressure (absolute) bar 1 Relative air humidity % 0 Air inlet temperature ºC 20 Working pressure: for LE 10 bar bar(e) 7
8.2 Limitations
Minimum inlet temperature °C 0 Maximum inlet temperature ºC 40 Maximum working pressure bar(e) See below Only applicable for Full Feature variants. (with refrigerant dryer) Minimum ambient air temperature °C 5
8.3 Compressor data
50 Hz (10 bar)
Compressor type LE 2 LE 3 LE 5 LE 7 LE 10 LE 15 LE 20 Maximum working pressure
bar(e) 10 10 10 10 10 10 10
Maximum working pressure for Trolley
bar(e) 9.5 9.5 9.5 9.5 9.5 9.5 9.5
Pre-set pressure difference for Trolley
bar 1 1 1 1 1 1 1
Temperature at outlet valve, approx. - Unsilenced compressor
ºC 40 44 66 59 80 70 89
- Silenced compressor ºC 48 52 74 67 88 78 97 Power input at max. working pressure
kw 1.82 2.54 4.57 6.11 8.28 12.14 16.02
Motor shaft speed r/min 1500 1500 1500 1500 1500 1500 1500 Free air delivery (Note 1)
l/s 3.4 4.4 8.4 11.7 15.7 23.9 31.7
Oil capacity l 0.8 0.8 0.8 1.4 1.4 5.4 5.4 Opening pressure of safety valve
bar(e) 11 11 11 11 11 11 11
Maximum sound pressure level (Note 2)
70 2920 7089 80
Instruction book
Compressor type LE 2 LE 3 LE 5 LE 7 LE 10 LE 15 LE 20 - Tank-mounted dB(A) 78 79 79 80 81 84 85 - Tank-mounted with hood
dB(A) 65 66 66 70 70 73 73
- Base-mounted with hood
dB(A) 63 64 64 68 68 70 70
60 Hz (10 bar)
Compressor type LE 2 LE 3 LE 5 LE 7 LE 10 LE 15 LE 20 Maximum working pressure
bar(e) 10 10 10 10 10 10 10
Maximum working pressure for Trolley
bar(e) 9.5 9.5 9.5 9.5 9.5 9.5 9.5
Pre-set pressure difference for Trolley
bar 1 1 1 1 1 1 1
Temperature at outlet valve, approx. - Unsilenced compressor
ºC 49 54 80 74 80 70 89
- Silenced compressor ºC 57 62 88 82 88 78 97 - Power input at max. working pressure
kw 2.36 3.38 6.36 7.57 10.81 14.32 18.98
Motor shaft speed r/min 1800 1800 1800 1800 1800 1800 1800 Free air delivery (Note 1)
l/s 3.9 5.1 9.7 13.6 18.2 28.7 37.2
Oil capacity L 0.8 0.8 0.8 1.4 1.4 5.4 5.4 Opening pressure of safety valve
bar(e) 11 11 11 11 11 11 11
Maximum sound pressure level (Note 2) - Tank-mounted dB(A) 80 81 81 82 83 84 85 - Tank-mounted with hood
dB(A) 67 68 68 72 74 75 75
- Base-mounted with hood
dB(A) 65 66 66 70 70 72 73
Notes:
1) At reference conditions 2) According to ISO 2151 and Pneurop/Cagi PN8NTC2; tolerance 3dB(A)
2920 7089 80 71
Instruction book
9 Instructions for use
Air receiver (tank-mounted units)
1 Corrosion must be prevented: depending on the conditions of use, condensate may accumulate inside the tank and must be drained every day. This may be done manually, by opening the drain valve, or by means of the automatic drain, if fitted to the tank. Nevertheless, a weekly check of correct functioning of the automatic valve is needed. This has to be done by opening the manual drain valve and checking for condensate.
2 Periodical service inspection of the air receiver is needed, as internal corrosion can reduce the steel wall thickness with the consequent risk of bursting. Local rules need to be respected, if applicable. The use of the air receiver is forbidden once the wall thickness reaches the minimum value as indicated in the service manual of the air receiver (part of the documentation delivered with the unit).
3 Lifetime of the air receiver mainly depends on the working environment. Avoid installing the compressor in a dirty and corrosive environment, as this can reduce the vessel lifetime dramatically.
4 Do not anchor the vessel or attached components directly to the ground or fixed structures. Fit the pressure vessel with vibration dampers to avoid possible fatigue failure caused by vibration of the vessel during use.
5 Use the vessel within the pressure and temperature limits stated on the nameplate and the testing report.
6 No alterations must be made to this vessel by welding, drilling or other mechanical methods.
72 2920 7089 80
Instruction book
10 Pressure Equipment Directive (PED)
Components subject to the 97/23/EC Pressure Equipment Directive
The following table contains the necessary information for the inspection of all pressure equipment of category II and higher according to the Pressure Equipment Directive 97/23/EC and all pressure equipment according to the Simple Pressure Vessel Directive 2009/105/EC.
Part number Description PED Class 0830 1007 42 Safety valve IV 0830 1010 34 Safety valve IV 0830 1010 17 Safety valve IV 0830 1010 18 Safety valve IV 0830 1007 70 Safety valve IV 0830 1010 19 Safety valve IV 0830 1010 32 Safety valve IV 0830 1007 73 Safety valve IV 0830 1010 33 Safety valve IV 0830 1009 54 Safety valve IV 0832 1001 10 Safety valve IV
Overall rating
The compressors conform to PED smaller than category II.
2920 7089 80 73
Instruction book
11 Declaration of conformity
1 EC DECLARATION OF CONFORMITY2 We, Atlas Copco Airpower n.v., declare under our sole responsibility, that the product
3 Machine name
4 Machine type
5 Serial number
Which falls under the provisions of article 12.2 of the EC Directive 2006/42/EC on the approximation of the laws of the Member States relating to machinery, is in conformity with the relevant Essential Health and Safety Requirements of this directive.
The machinery complies also with the requirements of the following directives and their amendments as indicated.
Directive on the approximation of laws of the Member States relating to
Harmonized and/or Technical Standards used
Att’mnt
a. CE/32/79 tnempiuqe erusserP
b. CE/24/6002 ytefas yrenihcaMEN ISO 12100 – 1 EN ISO 12100 – 2
EN 1012 – 1 c. CE/501/9002 lessev erusserp elpmiS
d. Electromagnetic compatibility 2004/108/EC EN 61000-6-2 EN 61000-6-4
e. Low voltage equipment 2006/95/EC EN 60034
EN 60204-1 EN 60439
f. CE/41/0002 noissime esion roodtuO
6
7
8.a The harmonized and the technical standards used are identified in the attachments hereafter
8.b Atlas Copco Airpower n.v. is authorized to compile the technical file. 9
10 Conformity of the specification to the directives
Conformity of the product to the specification and by implication to the
directives11
12
13
gnirutcafunaM gnireenignE yb deussI
14 Name Ferdinando MARCHETTI
RikVAN DE VELDE
15 Signature
16 Date
Typical example of a Declaration of Conformity document
(1): Contact address:
Atlas Copco Airpower n.v.
P.O. Box 100
B-2610 Wilrijk (Antwerp)
Belgium
74 2920 7089 80
Instruction book
DECLARATION OF INCORPORATION
2 We, Atlas Copco Airpower n.v., declare under our sole responsibility, that the product
3 Machine name
4 Machine type
5 Serial number
6
7
must not be put into service until the machine in which it is intended to be incorporated into or assembled with, is in conformity with the relevant Essential Health and Safety Requirements of the EC-Directive 2006/42/EC and its amendments on the approximation of the laws of the Member States relating to Machinery.
EC DECLARATION OF CONFORMITY
We, Atlas Copco Airpower n.v., hereby declare that the product which falls under the provisions of article 12.2 of the EC Directive 2006/42/EC on the approximation of the laws of the Member States relating to machinery, as a component/quasi machine is in conformity with the relevant Essential Health and Safety Requirements of this directive.We, Atlas Copco Airpower n.v., undertakes, in response to a reasoned request by the national authorities, to transmit the relevant information on the partly completed machinery. The information on the relevant parts can be obtained prejudice to the intellectual property rights of Atlas Copco Airpower N.V.
The machinery complies also with the requirements of the following directives and their amendments as indicated.
Directive on the approximation of laws of the Member States relating to
Harmonized and/or Technical Standards used
Att’mnt
a. Pressure equipment 97/23/EC
b. Machinery safety 2006/42/EC EN ISO 12100 – 1 EN ISO 12100 – 2
EN 1012 – 1 EN 60204-11
c. Simple pressure vessel 2009/105/EC d. Electromagnetic compatibility 2004/108/EC EN 61000-6-2
EN 61000-6-4
e. Low voltage equipment 2006/95/EC EN 60034
EN 60204-1 EN 60439
f. Outdoor noise emission 2000/14/EC
8
9
10
11.a The harmonized and the technical standards used are identified in the attachments hereafter
11.b Atlas Copco Airpower n.v. is authorized to compile the technical file. 12
13 Conformity of the specification to the directives
Conformity of the product to the specification and by implication to the
directives14
15
16
Issued by Engineering Manufacturing
17 Name Ferdinando MARCHETTI
RikVAN DE VELDE
18 Signature
19 Date
Typical example of a Declaration of incorporation for block document
(1): Contact address:
Atlas Copco Airpower n.v.
P.O. Box 100
B-2610 Wilrijk (Antwerp)
Belgium
2920 7089 80 75
Instruction book
1 EC DECLARATION OF CONFORMITY2 We, Atlas Copco Airpower n.v., declare under our sole responsibility, that the product
3 Machine name
4 Machine type
5 Serial number
Which falls under the provisions of article 12.2 of the EC Directive 2006/42/EC on the approximation of the laws of the Member States relating to machinery, is in conformity with the relevant Essential Health and Safety Requirements of this directive.
The machinery complies also with the requirements of the following directives and their amendments as indicated.
Directive on the approximation of laws of the Member States relating to
Harmonized and/or Technical Standards used
Att’mnt
a. Pressure equipment 97/23/EC
b. CE/24/6002 ytefas yrenihcaMEN ISO 12100 – 1 EN ISO 12100 – 2
EN 1012 – 1 c. Simple pressure vessel 2009/105/EC
d. Electromagnetic compatibility 2004/108/EC EN 61000-6-2 EN 61000-6-4
e. Low voltage equipment 2006/95/EC EN 60034
EN 60204-1 EN 60439
6
7
8.a The harmonized and the technical standards used are identified in the attachments hereafter
8.b Atlas Copco Airpower n.v. is authorized to compile the technical file. 9
10 Conformity of the specification to the directives
Conformity of the product to the specification and by implication to the
directives11
12
13
Issued by Engineering Manufacturing
14 Name Ferdinando MARCHETTI
RikVAN DE VELDE
15 Signature
16 Date
Typical example of a Declaration of conformity for petrol document
(1): Contact address:
Atlas Copco Airpower n.v.
P.O. Box 100
B-2610 Wilrijk (Antwerp)
Belgium
76 2920 7089 80
Instruction book
WO
RK
ING
PR
ESSU
RE:
7 ba
r10
bar
7 ba
r10
bar
7 ba
r7
bar
10 b
ar7
bar
10 b
ar7
bar
LE 2
-3-5
-7-1
010
0%10
0%10
0%85
-15
70-3
010
0%85
-15
100%
85-1
570
-30
-04-06
03-0703-07
51-58C
A tlusnoC
03-0751-58
5 1-58% 001
02-51 E L
0 5-0 50 3-0 7
51-5851-58
5 1- 5805-0 5
03 -0751 -5 8
51- 5851-58
*** *D
EC
NELI
S EL
03 -0751- 58
%001% 001
%00103-07
51 -58%00 1
%001% 001
FL05- 05
03- 075 1-5 8
51 -5851 -58
05-050 3- 07
51 -5 851- 58
51-58D
EC
NE LI
S FL05-05
04-0604-06
03-0704 -06
03- 0704-0 6
0 3-07K
COL
B R
EW
OP xFL
06-0405-05
04-060 3-0 7
05 -0504 -06
0 4-0603- 07
DE
CN
ELIS xFL
WO
RK
ING
PR
ESSU
RE:
14 b
a r20
bar
14 b
ar20
bar
12 b
ar*
15ba
r**
20ba
r***
14 b
ar20
bar
14 b
ar20
bar
12 b
ar*
15ba
r**
20ba
r*** 0 5-0 5
05 -0 503 -07
03-07%00 1
51 -58%0 01
05- 0505 -05
03-0751- 58
%001%001
%001TL LT
SIL
EN
CIN
G H
OO
D10
0%85
-15
85-1
570
-30
50-5
030
-70
30-7
010
0%85
-15
81-1
570
-30
50-5
030
-70
30-7
0
WO
RK
ING
PR
ESSU
RE:
30 b
a r30
bar
30 b
ar30
bar
30 b
ar30
bar
LT 3
0bar
85-1
585
-15
Con
sult
AC
85-1
570
-30
Con
sult
AC
LOA
D C
YC
LE IN
DIC
IATI
ON
A -
BA
= M
AX
. LO
AD
TIM
E%
B =
MIN
. STO
P T
IME
%M
AX
MO
TOR
STA
RTS
PE
R H
OU
R:2
0
ME
AS
UR
ED
DU
RIN
G M
AX
. 1H
R
Exa
mpl
e: L
DC
70-
30 m
eans
dur
ing
1 ho
ur, t
he c
ompr
esso
r mot
or m
ay h
ave
run
max
imiu
m 4
2 m
in, a
nd m
ust s
tand
stil
l at l
east
18
min
utes
, with
out m
ore
than
20
mot
or s
tarts
*LT
15
bar u
sed
at m
ax w
orki
ng p
ress
ure
12 b
ar**
LT 2
0 ba
r use
d at
max
wor
king
pre
ssur
e 15
bar
***
LT 3
0 ba
r use
d at
max
wor
king
pre
ssur
e 20
bar
****
LE15
-20
Not
Ava
ilabl
e w
ith S
ilenc
ing
Hoo
d
ed01
: Tri
Cyl
inde
r rep
lace
d by
O-F
ram
e si
ngle
sta
ge L
E15
-20
CO
ND
EN
SA
TIO
N: I
T IS
RE
CO
MM
EN
DE
D T
O A
VO
ID G
EN
ER
AL
LOA
D C
YC
LES
LE
SS
TH
EN
5%
, A S
MA
LLE
R U
NIT
SH
OU
LD B
E P
RO
PO
SE
D IN
SU
CH
CA
SE
S
TO A
LLO
W T
HE
UN
IT T
O A
CH
IEV
E G
OO
D W
OR
KIN
G T
EM
PE
RA
TUR
E. (
OC
CA
SIO
NA
L S
HO
RT
LOA
D C
YC
LES
AR
E N
O P
RO
BLE
M)
NO
RM
AL
AM
BIE
NT
(0 -
30°C
)H
IGH
AM
BIE
NT
(+30
°C)
NO
RM
AL
AM
BIE
NT
(0 -
30°C
)H
IGH
AM
BIE
NT
(+30
°C)
REC
OM
MEN
DED
LO
AD
DU
TY -
LE-L
F-LT
-LFx
50Hz
TRO
PIC
AL
(4
0-50
°C)
TRO
PIC
AL
(40
-50
°C)
60Hz
No.
292
0 70
89 8
0 / 2
012
- 05
- P
rint
ed in
Bel
gium
In order to be First in Mind-First in Choice® for all your quality compressed air needs, Atlas Copco delivers the products and services that help to increase your business’ efficiency and profitability.
Atlas Copco's pursuit of innovation never ceases, driven by our need for reliability and efficiency. Always working with you, we are committed to providing you the customized quality air solution that is the driving force behind your business.
www.atlascopco.com