 RATE OF ABSORPTION OF WATER BY LITECRETE LIGHTWEIGHT CONCRETE AND NORMAL CONCRETE ACCORDING TO THE ASTM C1585 - 04 AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Prepared for: Litecrete (NZ) Ltd PO Box 272 1386 Papakura Consultants: Mark Byrami Senior Technician Civil and Environmental Engineering The University of Auckland Date: 30 October 2006 Our Ref: 10646.04

Upload: nor-afifah-abd-halim

Post on 08-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 1/14

Page 2: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 2/14

  2

 

Reports from Auckland UniServices Limited should only be used for the purposes for 

which they were commissioned. If it is proposed to use a report prepared by

Auckland UniServices Limited for a different purpose or in a different context from

that intended at the time of commissioning the work, then UniServices should be

consulted to verify whether the report is being correctly interpreted. In particular it is

requested that, where quoted, conclusions given in UniServices reports should be

stated in full.

Page 3: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 3/14

  3

 

Table of Contents page

List of Tables, Figures and Photos 4

Method of testing 5

Specimens 5

Results and Calculations 7

Page 4: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 4/14

  4

 

Table 1: Properties of both types of concrete used in the test.

Table 2: Specimen properties.

Table 3: Absorption test results of both types of samples.

Figure 1: Schematic of testing procedure.

Figure 2: Initial Rate of Water Absorption for both types of concrete.

Figure 3: Secondary Rate of Water Absorption of normal concrete.

Figure 4: Secondary Rate of Water Absorption of lightweight concrete

Photo 1: Normal concrete sample after four hours.

Photo 2: Normal precast concrete sample after one day.

Photo 3: Lightweight concrete sample after one day.

Photo 4: Lightweight concrete sample after three days.

Page 5: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 5/14

  5

 

Method of Testing:

The test method used was ASTM C1585 – 04: “Measurement of Rate of Absorption

of Water by Hydraulic Cement Concrete”. This test method determines the rate of 

absorption (i.e. sorptivity) of water by hydraulic cement concrete by measuring the

increase in the mass of a specimen resulting from absorption of water as a function of 

time when only one surface of the specimen is exposed to water. The exposed surface

is immersed in water (the water depth is 1 to 3 mm only) and water ingress of 

unsaturated concrete dominated by capillary suction during initial contact with water.

Treating and Conditioning the Specimens:

The standard method is to cure the specimens in an oven for three days, at a

temperature of 50°C and relative humidity of 80%. The relative humidity is achieved

using potassium bromide. As an alternative to the standard test method, potassium

bromide was not used.

The specimens - three samples each of normal concrete and lightweight concrete -

were cured in the oven for three days at a temperature of 50°C. All of the samples

were kept in the same environmental condition in the laboratory during the period of 

the testing programme. Figure (1) show the schematic of the testing procedure.

Specimens:

Both sets of samples (normal concrete and lightweight concrete) were each aged 28

days and supplied by Litecrete (NZ) Ltd. The properties of each are shown in

Table(1). Lightweight concrete samples mix consist of: cement, coarse pumice, fine

Page 6: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 6/14

  6

pumice, polypropylene fibre, water and admixture. Normal concrete samples mix

consist of: cement, sand, coarse aggregate (greywacke) and water.

Table (1): Properties of both concrete mixes used in the test.

Specimen propertiesLightweight

concrete Normal concrete

Diameter (mm) 101.8 100

Thickness (mm) 51 51

Water temperature °C 18 18

Mass before sealing (grams) 536.6 915.3

Mass after sealing (grams) 544.8 921.6

Table (2): Average sample, dimensions and mass.

Figure (1) Schematic of the testing procedure.

Type of concreteStrength,

MPaDensity,kg/m3

Lightweight concrete (average for three samples) 13.3 1235

Normal concrete (average) 28.6 2341

Water 

Plastic sheet Sealing

material

Specimen

Supports1-3 mm

water 

depth

50 mm

depth

of the

sample

Exposed surface

Pan

Page 7: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 7/14

  7

Test Results and Calculations:

In table (3) the readings of the test and the value of the Absorption (I) is found using

the following equation:

I = mt / (a* d) where mt = the change in mass in grams, at

different time (t)

a = exposed area of the specimen, mm².

d = density of water in g/mm³.

Figure (2), (3) and (4) below show the Absorption (I) plotted to the square root of the

time and from the developed curve the Initial and Secondary Rate of Water 

Absorption can be determined.

Initial and Secondary Rate of Water Absorption:

•  The Initial Rate of Water Absorption is defined as the slope of the line, which

is drawn using least squares, linear regression analysis, to fit the curve of 

Absorption (I) plotted against the square root of time. The points plotted were

from one minute to six hours.

•  Secondary Rate of Water Absorption is calculated in the same manner, with

the points of time plotted from one day to seven days.

Note: To achieve the initial or secondary rate of water absorption using this method

there should be a correlation coefficient of more than 0.98. This is calculated using a

spreadsheet programme:

Page 8: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 8/14

  8

•  Initial Rate of Water Absorption for lightweight concrete = 107 x 10-4

mm/√sec. R = 0.99.

•  Initial Rate of Water Absorption for normal concrete = 215 x 10-4 mm/√sec.

R=0.99.

•  Secondary Rate of Water Absorption for lightweight concrete = 29 x 10-4

mm/√sec. R=0.98.

•  Secondary Rate of Water Absorption for the normal concrete = 4 x 10-4

mm/√sec. R=0.98.

Page 9: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 9/14

  9

Test Data:

Lightweight concrete Normal concrete

Testingtime,(Sec)

√Time,(Sec

1/2)

m, (gram) I, (mm)m

(gram)I, (mm)

60 7.7 1.10 0.14 2.65 0.34

300 17.3 2.33 0.29 5.15 0.66

600 24.5 3.21 0.39 6.73 0.86

1200 34.6 4.30 0.53 8.66 1.10

1800 42.4 5.05 0.62 10.22 1.30

3600 60.0 6.63 0.81 13.35 1.70

7200 84.9 8.70 1.07 17.59 2.24

10800 103.9 10.27 1.26 20.59 2.62

14400 120.0 11.53 1.42 22.98 2.92

18000 134.2 12.57 1.55 24.88 3.16

21600 147.0 13.54 1.67 26.48 3.37

86400 293.9 19.71 2.36 40.12 5.10

172800 415.7 23.82 2.85 40.81 5.19

266400 516.1 26.60 3.18 41.23 5.24

345600 587.9 28.54 3.41 41.49 5.28

604800 777.7 32.13 3.84 41.99 5.34

691200 831.4 33.12 3.96 42.13 5.36

Table (3): Average absorption of normal concrete and lightweight concrete samples.

Page 10: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 10/14

  10

 

Figure (2): The absorption plotted against square root of time, for both concrete

types, plotted from one minute to six hours.

Figure (3): the absorption plotted against square root of time, for lightweight concretespecimens, plotted from one day to eight days.

Secondary Rate of Water Absorption, Litecrete

y = 0.0029x + 1.6104

R2

= 0.9829

2.000

2.500

3.000

3.500

4.000

4.500

200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0

Square Root time (sec^0.5)

Absorption I, (mm

)

Initial rate of water absorption

y = 0.0215x + 0.3231

R2

= 0.9944

y = 0.0107x + 0.1265

R2

= 0.9952

0.000

0.500

1.000

1.500

2.000

2.500

3.000

3.500

4.000

0.0 20.0 40.0 60.0 80.0 100.0 120.0 140.0 160.0

SQRT Time, (sec)^0.5

Absorption, I, mm

Litecrete

Normal Concrete

Linear (Normal Concrete)

Linear (Litecrete)

Initial Rate of Water 

absorption:

Litecrete = 10.7E-3

Normal concrete = 21.5E-3

Page 11: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 11/14

  11

Figure (4): the absorption plotted against square root of time, for normal concrete

specimens, plotted from one day to eight days.

Secondary Rate of Water Absorption Normal Concrete

y = 0.0004x + 5.0363R

2= 0.9883

5.180

5.200

5.220

5.240

5.260

5.280

5.300

5.320

5.340

5.360

5.380

300.0 400.0 500.0 600.0 700.0 800.0 900.0

SQRT time (s^0.5)

I , (mm)

Page 12: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 12/14

  12

Water Ponding

The tests results showed that the water penetrated through the samples, ponding on

the top surface at varying volumes for each type of concrete. Water penetration was

evident by ponding on the surface of the normal concrete in less than five hours,

whereas for the lightweight concrete samples this ponding phenomenon was not

evident until after three days. Photos (1) and (2) show the amount of water on top of 

each sample of normal concrete and photos (3) and (4) show the results for the

lightweight concrete.

Photo (1): Normal concrete sample shows traces of water saturating 25% of the

surface area after less than five hours from the start of the test.

Page 13: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 13/14

  13

 

Photo (2): Normal concrete sample after one day; the top surface area is fully

saturated.

Photo (3): Lightweight concrete sample after one day’s testing shows no trace of 

water on the top surface.

Page 14: Auck Uni Sorp Test report

8/7/2019 Auck Uni Sorp Test report

http://slidepdf.com/reader/full/auck-uni-sorp-test-report 14/14

  14

 

Photo (4): Lightweight concrete sample after three days from the start of the test,

showing 10% saturation of the top surface area.