august 17, 2012 solar pv inverters anuj dixit planning engineer resource integration rpg meeting

11
August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

Upload: roberta-wilkerson

Post on 03-Jan-2016

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

August 17, 2012

Solar PV Inverters

Anuj DixitPlanning Engineer Resource Integration

RPG Meeting

Page 2: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

2

Definition and Purpose

• Definition: Intermittent Renewable Resource (IRR)

- A Generation Resource that can only produce energy from variable uncontrollable resources such as wind, solar or run-of-the-river hydroelectricity.

• Purpose

- ERCOT is encountering some projects in which the inverter designs limit the capability of the solar plant because all of the protocol requirements were not considered in the design.

- So far, these limitations have been on reactive capability across operating range.

November 14, 2011

Page 3: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

3

Outline

• Solar projects in ERCOT

• Example

• Modeling requirements

• Protocol requirements

• Summary

• Questions / Discussion

August 17, 2012

Page 4: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

4August 17, 2012

Example - Reactive capability

P

Operating Area

Reactive curve for a sample inverter, 0.95 pf lead/lag requirement

0.750 MW

0.250 -0.250

MW

MVAr

Page 5: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

5August 17, 2012

• 506 MW solar projects in the Study Phase• Majority of the projects are solar PV

Solar PV projects

Page 6: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

6August 17, 2012

• Steady state– Active/Reactive Power Capability– Voltage control settings– Generator step up transformer

• Short circuit– Equivalenced collector system model

• Dynamic– Compatible PSS/E standard model or a user defined model

• PSCAD Model for SSCI Studies ?

Modeling requirements – FIS perspective

Page 7: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

7August 17, 2012

• Voltage ride through capability (Operating Guide 2.9.1)

ERCOT Protocols and other binding documents

Page 8: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

8August 17, 2012

• Frequency Control (Protocol 8.5 Primary Frequency Response Requirements and Monitoring)

- At all times an All-Inclusive Generation Resource is On-Line, its Governor must remain in service and be allowed to respond to all changes in system frequency except during startup, shutdown, or testing. …All Generation Resources that have capacity available to either increase output or decrease output in Real-Time must provide Primary Frequency Response, which may make use of that available capacity. Only Generation Resources providing Regulation Up (Reg-Up), Regulation Down (Reg-Down), Responsive Reserve (RRS), or Non-Spinning Reserve (Non-Spin) from On-Line Resources, as specified in Section 8.1.1, QSE Ancillary Service Performance Standards, shall be required to reserve capacity that may also be used to provide Primary Frequency Response.

ERCOT Protocols and other binding documents

Page 9: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

9August 17, 2012

ERCOT Protocols and other binding documents

• Voltage Control : Reactive Capability 0.95 lead lag capability over the entire range (Protocol 3.15)

-Reactive Power Requirements: an over-excited (lagging) power factor capability of 0.95 or less and an under-excited (leading) power factor capability of 0.95 or less, both determined at the generating unit's maximum net power to be supplied to the ERCOT Transmission Grid and at the transmission system Voltage Profile established by ERCOT, and both measured at the POI.

– The Reactive Power requirements shall be available at all MW output levels and may be met through a combination of the Generation Resource’s Unit Reactive Limit (URL), which is the generating unit’s dynamic leading and lagging operating capability, and/or dynamic VArcapable devices.

– Generation Entities may submit to ERCOT specific proposals to meet the Reactive Power requirements established in paragraph (3) above by employing a combination of the URL and added VArcapability, provided that the added VArcapability shall be automatically switchable static and/or dynamic VArdevices. ERCOT may, at its sole discretion, either approve or deny a specific proposal, provided that in either case, ERCOT shall provide the submitter an explanation of its decision.

Page 10: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

10August 17, 2012

• Inverter selection must consider how the design will meet ERCOT protocols and other binding document (grid code)

• Inverter characteristics may be improved with design modifications (i.e. it may be possible that an inverter who’s published specifications do not meet the ERCOT requirements can be modified to meet these requirements)

Summary

Page 11: August 17, 2012 Solar PV Inverters Anuj Dixit Planning Engineer Resource Integration RPG Meeting

11August 17, 2012

Questions ?