Auto Mains Failure AMF Controller AE10113

Page 2: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

Auto Mains Failure

DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which acti-vates the generator during power failure & vice versa. The panel includes mC based controller. The operation is controlled automatically in “Auto Mode” as well as manually in the “Manual Mode”. Apart from the activating & deactivating, AMF10113 can control the GENSET according to the engine side parameters like Water Temp., Lub oil pressure etc. And alternator side parameter like under voltage, over voltage, under frequency etc. Also it gives us various indications & power measurement. It’s having LCD dis-play & user friendly setting parameter. Software also provides inbuilt help menu.

SPECIFICATIONS

• DC supply: 12V DC (Battery supply) • Starter output: Signal for relay coil • Fuel start/stop output: Signal for relay coil (In CCPL case controls ECU supply) • Over all dimensions: (for controller) : 196mm x 96mm x 100mm • Approx. weight or controller : 750 gms.

Page 3: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

Auto Mains Failure

FEATURES • Microprocessor based design • Automatic engine start and stop • LCD Display with key pad • Solid state fuel stop & crank outputs • LED indication for few operations.

OPERATION Auto mode: In this mode panel monitors the mains supply (3 phase or single phase). As the incoming mains supply either fail or drops below preset limit i.e. 180V (by default) the generator will be started and load will be transferred to genset, panel will indicate that load is transferred to genset with LED indication. When the AC mains supply returns within limit, the panel will wait for preset time & will transfer the load to mains (indication through LED). The engine will be instructed to stop after preset time. Manual mode: ‘Manual’ mode is used to start & run the engine with start push button. And it can be stopped by pressing the stop push button. Off mode: ‘Off’ mode is used to keep the Genset off condition in case of mains fail. Nor AMF controller will transfer the Load on DG. Night mode: ‘Night’ mode is the special mode in which the Genset will be kept in ‘Off’ Mode in the specific period of the day. This period is settable. Test mode: Test mode will be active in AUTO / MANUAL mode while mains present. To enter into test mode, press test key, and observe the indications on LCD display.

Page 4: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

Auto Mains Failure

Indication • Remote start • Charging fail • Warning (any warning fault) • Shut down fault (any) • Mains present • DG on • Mains CB close • DG CB close

Indications on LCD display • Battery voltage • Alternator voltage (for three phases i.e.PH1, PH2, PH3) • Load current (for three phases i.e.PH1, PH2, PH3) • Alternator power in kw • Alternator power in KVA • Alternator KwH • Alternator KVAH • Power factor (pf) for three phases • Alternator supply frequency

Page 5: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

Auto Mains Failure

Key switches • F1 • F2 • PROG • ESC • Increment • Decrement • Enter • Left • Right • ACK. • Start • Stop Sensor / switches required • Lop switch • Fuel level switch 25% • Charge Fail • Water in Fuel • Remote Start • Remote Stop Apart from this there will be 2 PF contacts that can be programmed as per our requirement. No need to have separate relay card. Every warning fault / shutdown fault will be displayed on the LCD display. Also we can program the parameters as per or requirement with the help of keys provided on the controller. This will b totally user friendly. No need to have separate energy meter, as controller displayed all the required readings.

Page 6: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

No. Parameter Range Standard if not set

1 Start delay 0-59sec 5 sec

2 Mains restore time 1-59 sec 5 sec

3 Mains under voltage 70-500V 190V

4 Mains Over voltage 70-500V 250V

5 Warm up time 1-59 sec 5 sec

6 Cool down time 1-59 sec

30 sec

7 Generator under voltage 70-500V 190V

8 Generator over voltage 70-500V 250V

9 CT ratio 10-1000A 50:5

10 Generator over load 0 - disable or value

11 Low frequency 0-99Hz 47Hz

12 High frequency 0-99Hz 53Hz

13 Generator fail Alarm

14 Crank Time 1-20sec 5 sec

15 Charge Fail Level 3-24 volts 8 volt

16 Rest time 1-59 sec 5 sec

17 Crank attempt 1-10 attempt 3 attempt

18 LLOP bypass time 0-59 sec 5sec

19 Stop Time 0-59 sec

10 sec

Programmable Parameters

Page 7: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

No. Parameter Range Standard if not set

20 Horn time 0-59 sec 20 sec

21 Fuel type 1 – pull to stop 2 – pull to start

1

22 Faults for programmable relay-1 1-12 faults (table) 1

23 Faults for programmable relay-2 1-12 faults (table) 2

24 Faults for programmable relay-3 1-12 faults (table) 3

25 Faults for programmable relay-4 1-12 faults (table) 4

26 Single / three phase single phase three phase

1

27 Low fuel programmable 1-Shut down fault 0 – only LED indi.

1

28 Alarm 1 Time for shut down 1-59 sec 1 sec

29 Alarm 2 Time for shut down 1-59 sec 1 sec

30 Low Fuel Time for shut down 3-15 min 10 min

31 R.P.M. selection; Frequency = 50 Hz

1 = 1500 RPM 2 = 3000 RPM

1

32 Remote signal Enable/ Disable for Single phase

Disable Enable

0

33 Continuous On time Min 480 min

Programmable Parameters

Page 8: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

List of Faults

Fault no. Faults

1

Start Fail

2 LLOP

3 Over speed

4 Low Battery

5 Charge fail

6 HWT

7 Low fuel

8 Over load

9 Alarm 1

10 Alarm 2

11 Fail to Stop

12 Generator voltage fail

Page 9: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which

TERMINAL DETAILS

Page 10: Auto Mains Failure AMF Controller AE10113 - Arya Electronics … Mains... · Auto Mains Failure DESCRIPTION AMF Controller AE10113 is an Automatic Mains Failure controller, which