DRAFT Autodesk Revit© Naming Requirements USC Nomenclature Guide for the correct naming of Families, Types, Instances, Systems and Zones 12/19/2012

Upload: phamquynh

Post on 25-Feb-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

DRAFT

Autodesk Revit© Naming Requirements

USC Nomenclature Guide for the correct naming of Families, Types, Instances, Systems and Zones

12/19/2012

DRAFT

Nomenclature | 2

SOURCESOmniClass Table 23 Products  OmniClass Table 21 

Elements (Assemblies)U.S. National CAD Standards

Module 05Terms and Abbreviations 

Legacy SourceMasterFormat©2004

Legacy SourceUniFormat™ 1992,1998

DRAFT

Nomenclature | 3

OMNICLASS

• Classification system for the construction industry 

• Developed via consensus and broad participation from the 

construction industry, individuals and organizations

• Uses existing legacy systems like MasterFormat©2004 and 

UniFormat™ 1992,1998

• 15 Tables covering everything from facilities to spaces, construction 

products, assemblies, phases, organizational roles, tools, disciplines 

etc.

DRAFT

Nomenclature | 4

U.S. NATIONAL CAD STANDARDSModule 05 Terms and Abbreviations

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for VAV BOX with TAG NUMBER “D01”

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameVariable Air Volume 

Terminal UnitsVAV Reheat 6” VAV‐D01

Type Description Instance Description

VAV with Reheat Price SDV 6”

VAV Box with Reheat 6” D01

DRAFT

Nomenclature |

FAMILY NAME

OmniClass Table 2323‐33 41 17 13

Variable Air Volume Terminal Units

23‐33 41  HVAC Air Terminals23‐ 33 41 17  Terminal Air Units23‐33 41 17 13  Variable Air Volume     

Terminal Air Units

Add  a further description here as a suffix as needed at your discretion if you need to 

differentiate between one family and another that are close in 

geometry or function. 

As long as the official OmniClassTable 23 name appears at the beginning, what you add after is 

acceptable if this extra description is necessary.

DRAFT

Nomenclature |

FAMILY NAME

OmniClass Table 2323‐33 41 17 13

Variable Air Volume Terminal Units

23‐33 41 17 13 Variable Air Volume Terminal Units

DRAFT

Nomenclature |

TYPE NAMEVAV Reheat 6”

Brief description denoting size / capacity/type as easily identified 

& understood  

(description is based on your discretion but should at minimum include sizes or dimensions for example 

2’x 2’, 6”, 8” 1.5’ x 3’, 10” etc.)

“Reheat 6” ”

U.S. National CAD Standards“VAV” +

If the abbreviation for a piece of equipment is not listed in the National CAD Standards, use the abbreviation used in your equipment/component schedules instead. For example, a “Fan Powered Box” would be abbreviated as “FPB”, Use abbreviations as universally understood in the industry

1

1

DRAFT

Nomenclature |

TYPE DESCRIPTIONVAV with Reheat Price SDV 6”

Extended description denoting manufacturer/model/size / type as easily identified & understood  

“with Reheat Price SDV 6” ”

Type Name +

“VAV” +

Inserting this parameter, “Type Description” is a requirement. Filling in the fields, however,  is up to your discretion. You may enter an added description here to supplement Type Names for the purpose of clarity or leave it blank. 

2

2

DRAFT

Nomenclature |

INSTANCE NAMEVAV‐D01

ID unique to that componentas identified in the equipment / component 

schedules or drawings (IF EXISTS)

For example, Tag Number “D01”

“D01”

U.S. National CAD Standards“VAV”

3

3 If the abbreviation for a piece of equipment is not listed in the National CAD Standards, use the abbreviation used in your equipment/component schedules instead. For example, a “Fan Powered Box” would be abbreviated as “FPB”, Use abbreviations as universally understood in the industry

DRAFT

Nomenclature |

INSTANCE DESCRIPTIONVAV Box Reheat 6 Inches D01

Extended annotative description denoting type/size/id/location unique to that component

“Reheat 6 Inches D01”+

U.S. National CAD Standards“VAV” 

4

Inserting this parameter, “Instance Description” is a requirement. Filling in the fields, however,  is up to your discretion. You may enter an added description here to supplement  Instance Names for the purpose of clarity or leave it blank. 

4

DRAFT

Nomenclature |

HOW TO RENAME FAMILIES TYPES INSTANCES

Family Name Variable Air Volume Terminal Units

Directly in theProject Browser

orDirectly in the .rfa  Family File

DRAFT

Nomenclature |

Type Name VAV Reheat 6 Inches

HOW TO RENAME FAMILIES TYPES INSTANCES

Type DescriptionVAV with Reheat Price SDV 6 

Inches

Shared Parameter“Type Name”

Allows  for the maintenance of your original office standards  while simultaneously  meeting USC’s 

requirements

Directly in Revit or the Revit Family file

Shared Parameter“Type Description”

DRAFT

Nomenclature |

HOW TO RENAME FAMILIES, TYPES, INSTANCES

Instance Name VAV‐D01

Instance DescriptionVAV Reheat 6 Inches D01

Shared Parameter“Instance Name”

Shared Parameter“Instance Description”

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a ROUND CONED SUPPLY DIFFUSER Type RC-1

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameSupply Air Ventilation Diffusers Round Coned

SA DIFF Round Coned 24" Face 8 Connection

SA DIFF Type RC‐1

Type Description Instance Description

Round Coned Diffuser Supply Air Diffuser Type RC‐1

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a STANDARD ROUND VOLUME DAMPER

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance Nameno tag number needed if not scheduled or 

not tagged in drawings

Volume ControlDamper Round

VD Standard RoundSupply

VD RND SPLY

Type Description Instance Description

Standard Round Volume Damper on Supply Ducts

Standard Round Volume Damper on

Supply Ducts

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for MAIN SERVICE TRANSFORMER ‘C’

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameTransformer Liquid Filled Substation

XFMR 500kVA, 4.8 kV –480/277V

XFMR  T‐MSC

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for PANELBOARD 208V

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NamePanelboards 208V MLO

SurfacePB 208/120V, 225A PB EL1A

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a DUPLEX RECEPTACLE

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance Nameno tag number needed if not scheduled or 

not tagged in drawings

Electrical Receptacle Duplex

ELEC RECPT GFCI Duplex ELEC RECPT

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a 4” SQUARE 120V JUNCTION BOX

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance Nameno tag number needed if not scheduled or 

not tagged in drawings

Electrical Junction Box Loaded

J‐BOX 4" Square 120 J‐BOX

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a LOW VOLTAGE LIGHT SWITCH

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance Nameno tag number needed if not scheduled or 

not tagged in drawings

Lighting Switches LT SW Low Voltage LT SW

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a WALL MOUNTED OCCUPANCY SENSOR

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance Nameno tag number needed if not scheduled or 

not tagged in drawings

Occupancy Sensor Wall Low Voltage

OCCUPANCY SNSR Dual Technology

OCCUPANCY SNSR 

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a 2’ x 2’ Indirect Light Fixture

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameLighting Fixtures 2’ x 2’ 

IndirectLTNG FIXT 24"(2 Lamp) 

277VLTNG FIXT Type D01

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a GATE VALVE

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameGate Valve 2‐12 Inches GTV Gate Valve 1" GTV‐40

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a WATER CLOSET 1.6gpf

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameWater Closet Flush Valve Floor Mounted

WC 1.6gpf WC Type WC‐1

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a STEEL SINGLE FLUSH 12 GLASS PANEL DOOR

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameDoor Steel Single Flush 

Glass 12 PanelDR 3‐0x9‐4x1‐3/4 Type J DR 100.B

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a SOLID CORE WOOD SINGLE FLUSH DOOR (1hr)

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameDoor Solid Core Wood 

Single FlushDR 3‐0x7‐0x1 3/4 60Min 

Type ADR S2.1‐A

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a STEEL OVERHEAD ROLLING DOOR

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameDoor Steel Overhead 

Rolling DR 12‐0x15‐0x3 Type M DR 105.B

Type Description Instance Description

DRAFT

Nomenclature |

example FAMILY, TYPE & INSTANCE NAMES for a CAST STONE FIXED GLASS WINDOW

DRAFT

Nomenclature |

FAMILY, TYPE & INSTANCE

Family Name  Type Name Instance NameWindow Cast Stone 

Fixed GlassWDW 2'‐10 3/4" x 2'‐6 3/4" Cast Stone Trim

WDW Type J

Type Description Instance Description

DRAFT

Nomenclature |

SYSTEMSMechanical Supply Air AHU‐D1

OmniClass Table 2121‐04 30 60 10

HVAC – Ventilation – Supply Air

Abbreviation : U.S. National CAD Standards

Air Handling Unit

+“Supply Air” “AHU”

Identification that further 

defines a piece of equipmentfrom others

(usually a tag number or mark 

from the schedules)

+ “D1”

DRAFT

Nomenclature |

DUCTLESS SYSTEMSMechanical Return Air RG‐1  2nd Floor 214A Office

Ductless return air system consisting of pieces of ductwork and a return air grille marked as “RG‐1”, whose grille is physically located in room 214A Office on the 2nd Floor

OmniClass Table 2121‐04 30 60 20

HVAC – Ventilation – Return Air

Tag number of the Return Grill “RG‐1”

+“Return Air” “RG‐1”

Floor + USC Official Room Name & Number

+“2nd Floor 

214A Office”

Room :  214A Office

RG‐1

DRAFT

Nomenclature |

ZONESexample: HVAC Zone associated with VAV Box D01 serving Offices 100,101,102

National CAD StandardNCS 3.1  Module 5 abbreviation for Air 

Handling Unit is "VAV"+

Description denoting ‘size/type as easily identified "D01"

VAV‐D01

USC Official Room Names and Numbers for Rooms contained in that Zone

Office "100", "101", "102"Office 100, 101, 102

ZONE NAMEVAV‐D01 Offices 100, 101, 102

VAV‐D01 Offices 100, 101, 102