automated logic corporation
TRANSCRIPT
-
7/22/2019 Automated Logic Corporation
1/9
Automated Logic Corporation - WebCTRL
ZN220; ZN253; ZN551
Primary Control UnitZN Line
Last Saved: Mar 29, 2004 4:18:18 PM
Description
Product Name(s):
ZN220 ZN253 ZN551
Product
Description:Stand-alone Zone Controllers
Product
Application(s):
The ZN253 and ZN551 are zone controllers for VAV, heat pump, unit
ventilator and other packaged HVAC applications.
The ZN220 is suitable for a variety of applications including fan coil
units, lighting, and exhaust fan control.
Automated Logics line of RS room sensors and provides local access to the system.
Control Unit Model #: AI DI UI DO AO UO Other
ZN551 5 5 1
ZN253 5 2 3
ZN220 2 2 0
A/D Converter Resolution
- 8 bit
X 10 bit
- 12 bit
- 16 bit
- Other
D/A Converter Resolution
- 6 bit
X 8 bit
- 10 bit
- No Analog Output
- Other
HOA switches provided on each output? X No
-
7/22/2019 Automated Logic Corporation
2/9
Note: These are also available as an add-on from 3rd party vendors. - Both AO and DO
- DO Only
- Other
Indicating status LED on each output?
- No
- AO and DO
- AO Only
X DO Only
- Other
Additional Features
VAV Controllers
Integral Flow Sensor? No
Integral Damper Actuator? No
Can controller accept occupant override from thermostat?Yes
Can controller accept occupancy sensor input? Yes (dry contact or 0-5Vdc)
I/O Expansion
Expander
Boards
ZN551 and ZN253 are compatible with U Line Single air Flow sensor (USF) or U
Line Dual air Flow sensor (UDF) for pressure independent VAV applications.Connects directly with cable/connector provided with USF and UDF.
Expansion Device Model # AI DI UI DO AO UO Other
USF 1
UDF 1
Network and External Communication Ports
Network Ports, Protocol(s), and
Speed(s) Supported
(Note: See 'Architecture' for network
details)
(1) EIA-485 BACnet port to primary BACnet network
(ARCNET at 156 kbps or MS/TP at 9.6, 19.2, 38.4, or76.8 kbps)
External Communication Ports,
Speeds and Access Devices
(1) Local access port for system start-up and
troubleshooting(1) Rnet port for RS room sensors
Additional Information
(Optional)
-
7/22/2019 Automated Logic Corporation
3/9
Operator Interfaces (via Controller) *
Network Accessing Capabilities via
Controller
no Access controller only
no Access controller plus additional controllers
on network segment / LAN
yes Access all controllers on system
no No access available on this controller
no Other
Controller Access Devices
yes Laptop/PC
no Local Display Panel (controller-mounted)
no Local Display Panel (zone-mounted)
no Handheld Interface Device (proprietary
device)
no PDA (3rd-Party HID)
yes Zone-Based port (details below)
no Other
Functions
Available
Through
Field
Interface**
:
View
Params
Change
Params
Change
Programs/Logi
c
O&M
Support
TAB/Cx
Support
Laptop/PC X X X X X
Zone-Based
port (detailsbelow)
X X X X X
Zone-Based Interface AccessLaptop can be connected to the RSPro andRSBasic sensor for full system access.
Zone Interface Hardware
yes Zone-Mounted touchpad (thermostat or
stand-alone display)
no HID (proprietary device)
no PDA (3rd party HID, with software)
yes Laptop/PC
no none
no Other
*Note: This section covers the capabilities for accessing the controller or other parts of thenetwork from the controller (i.e. 'bottom-up'). Standard access functionality is covered in the
Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
-
7/22/2019 Automated Logic Corporation
4/9
Processor, Memory, and Battery
Microprocessor(s)16-bit microprocessor with ARCNET communication co-
processor.
Clock Type
no Powered, battery-backed
no Battery powered
yes Powered, no battery backing
no None
no Other
Clock Synchronization
Time synchronization occurs periodically through broadcastsfrom the WebCTRL server, and from the BACnet Router on each
network segment.
Volatile Memory (RAM)
CapacityModule only contains non-volatile and flash memory.
Volatile Memory (RAM)
Uses
- RAM use unrestricted
- RAM use restricted as shown below- Information Not Provided
no Program Execution / Calculation storage
no Data / Trends / Alarms storage
no Configuration / Parameter storage
no Control Programming storage
yes Others (N.A.)
Is Volatile Memory
Supported By Battery?N.A.
Battery Type(s) N.A.Battery Life N.A.
Backup Battery Operating
TimeN.A.
Non-Volatile Memory
Capacity
(EEPROM/Flash) *
512 KByte non-volatile battery-backed RAM, 1 MByte Flash
memory, 16-bit memory bus
Non Volatile Memory Uses
yes Data / Trends / Alarms / Calculation Storage
yes Configuration / Parameter Storage
yes Control Programming Storage
yes Controller Operating System
no Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory
such as EPROM, NOVROM, etc. do not directly impact system performance.
-
7/22/2019 Automated Logic Corporation
5/9
Trend Data Storage
Can trend data be stored in
this controller?Yes
How many total trend valuescan be stored?
The user has complete control over how trend memory is used,
including how many points are trended, how often the trend
samples are taken, how many samples are stored in the module,and whether or not the trend data will be backed up to ahistorical database on the server.
What is the controllers role in
trending?
Controller samples data either at time intervals or based on
change of value
Can controller be
programmed to 'push' data to
archive or are trends 'pulled'
from controller?
Controller can be programmed to push data to archive, or data
can be dynamically pulled from the controller for display
When full, does controller
automatically send up trenddata; overwrite data, or stop
logging data?
User defines whether controller should stop when full or beginoverwriting oldest data
Programming
Programming Method(s)
(See Also 'Software' Form)
ZN Line controllers are fully graphically
programmable using the Eikon graphical
programming software.
Resident vs. Non-Resident Program
ExecutionAll graphical programs reside in the controller.
Scheduling
(See Also 'Software' Form)
no Resident/Supervisory. This controllersupervises the scheduling of other
controllers.
yes Resident/Stand Alone. This controllercontains its own schedule.
no Non-Resident. This controller is dependent
upon another controller for its schedule.
no None. This controller has no schedulingfeatures.
no Other
Resident Energy Management
(Controller-resident energy managementfunctions/algorithms calculated and performed
by this controller. These typically require point-
sharing and can involve calculations andmultiple-loop functions. One or more of these
no Energy management algorithms for this
controller can be custom programmed
yes Pre-programmed/built-in algorithms
available, and are fully editable usingcustom programming
no Pre-Programmed/built-in with limited
editing via template-based programming
-
7/22/2019 Automated Logic Corporation
6/9
choices may be selected.) no Controller is not typically used for energymanagement functions
no Others
Specific Pre-Programmed Algorithms
Available
no None (custom programming only)
no None (not applicable)yes Optimal Start/Optimal Stop
yes Peak Demand Limiting/Load Shedding
no Economizer (enthalpy, dry-bulb, CO2,
modulating/2-position, etc.)
no Other
no Additional Energy Management functions
are resident at SI
Additional Programming Functions
A library of pre-engineered control routinesprovides solutions for most zone control
applications. Custom programs can be easilywritten in EIKON using ALCs graphic
programming language.
Controller Features
DDC Loops (P, PI, PID)Available through custom Eikon graphical
programming
Automatic PID Tuning Feature No
Automatic-Dial Alarm Support
(See 'Software' for further information) Yes
Does controller perform multiple retires and
buffer/store alarm until connection is made?Yes
Are multiple destinations possible? Yes
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and
alarm reported?Yes
DO and AO response?
- Outputs fail to a user pre-specified position
X Outputs fail to a normal (unpowered)position
- Outputs fail to last position
- Other
Volatile memory functions?- Lost
X Retained for life of backup battery (shelf life
-
7/22/2019 Automated Logic Corporation
7/9
(See 'Memory' section)10 years with 10,000 hours of continuousoperation)
- Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes
Update all monitored functions? Yes
Generate an alarm if backup battery is
dead?Yes
Upon network or communications failure:
Does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-
specified value?
User-specified default values
Do broken network segments continue to
communicate within the remaining segment?
(Note: may depend on proper termination of
segments for higher speed networks.)
Yes.
Does network automatically reconfigure
upon restoration?Yes
Does network store 'loss of communications'
alarm with time of event?Yes
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Yes
Internal hardware failure? Yes
Open/shortened sensor?
Others?
Control Enclosure Rugged GE C2950 Cycoloy plastic
Power Supply
Power Supply Required
Voltage 24 Vac 10%, 26 Vdc (25 V min, 30 V max), 50 to 60Hz,
VA 20 VA
Surge Protection
-
7/22/2019 Automated Logic Corporation
8/9
Listing, Labeling, and Compliance
Underwriters LaboratoriesUL 916(Canadian STD C 22.2 No.205-M1983)
FCC Part 15-Subpart B-Class A
CE Yes
LonMark Certified
- Yes
- No
- No - but LonWorks compatible
X Information not provided
BACnet (BTL) Certified
X Yes
- No
- Not submitted for testing
- Information not provided
Other
LGR Line
Last Saved: Feb 27, 2004 10:10:04 AM
Description
ProductName(s):
LGR-25
LGR-1000Product
Description:The LGR is a router/gateway that can connect to a BACnet/IP backbone.
Product
Application(s):
Support for BACnet/IP, BACnet-over-Ethernet, ARCNET 156 kbps,MS/TP, and BACnet PTP communications are standard. A wide range ofopen and proprietary protocol translator drivers allow the LGR to also serve
as a gateway to other
manufacturers equipment. Fully programmable, the LGR can also execute
control strategies for system integration.
Supported by the Iowa Energy Center.
-
7/22/2019 Automated Logic Corporation
9/9