AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing the excitation current to the Generator field. The AVR supplies the required D.C. to the Generator field depending on the load, power factor etc. to maintain a constant terminal voltage. 1

Upload: amaya-hunter

Post on 30-Dec-2015

81 views

Category:

Documents


3 download

DESCRIPTION

AUTOMATIC VOLTAGE REGULATOR(AVR). Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing the excitation current to the Generator field. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

AUTOMATIC VOLTAGE REGULATOR(AVR)

Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing the excitation current to the Generator field.

The AVR supplies the required D.C. to the Generator field depending on the load, power factor etc. to maintain a constant terminal voltage.

1

Page 2: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

CONTROL SYSTEMS OF AVR

1. Auto control

2. Manual control

2

Page 3: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

TYPES OF AVR

1.Single channel AVR

Two controllers one is automatic and the other is manual

Both the controllers are fed from the same supply

3

Page 4: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

2. Dual channel AVR system One automatic voltage controller

and one manual controller Different power supply, gate

control and pulse amplifier units for each of the controllers

4

Page 5: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

3.Twin channel AVR system

Two automatic voltage regulators

5

Page 6: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

Function of AVR compares the Generator terminal

voltage with a preset reference voltage.

If the Generator terminal voltage is less than the reference voltage, the AVR increases D.C. voltage across the Generator field.

Maintaining the constant voltage as per the setting.

6

Page 7: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

The automatic voltage control system

EXCITATION AS A CLOSED LOOP CONTROL SYSTEM

Grid

If Vg Synchronous

Generator

Excitation

System

Page 8: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

2

3

4

7

6

GAIN

INPUT OUTPUT

OP AMP

REF

FEED BACK

OPERATIONAL AMPLIFIER

Page 9: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

Block diagram of AVR

9

Page 10: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

AVR inputs Generator voltage feedback signal Generator voltage reference AVR provides the following

functions and signals Summing and amplification of signals to

provide the exciter rectifier firing angle control signal.

A signal for manual follow up.

10

Page 11: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

AVR Action Two inputs are of opposite polarity. When the magnitudes are equal,

the net input is zero. When unequal-the error is

amplified and reversed to obtain a correction signal which goes to the

GPG(gate pulse generator)

11

Page 12: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

AVR CIRCUIT

12

Page 13: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

+-50 V SUPPLY To power the regulator amplifier as

well as the optional accessories such as manual follow up and power integral stabilizer

13

Page 14: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

Regulator auxiliary card 3 phase voltage from the generator

PT’s are stepped down and applied to the regulator auxiliary card which converts it to ripple free dc voltage suitable for the input of regulator amplifier.

Page 15: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

Balance Voltmeter

A 30-0-30 V dc voltmeter is connected across the output of regulator amplifier to read the magnitude and polarity of the output voltage of OP-AMP at any instant.

Page 16: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

AVR Voltage Setting

From the +-50 V source ,-50 V is applied and taken across a motorized potentiometer which can be operated from the control bench board. The variable output from the pot. is applied to the input of the regulator OP-AMP.

Page 17: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

Manual Voltage Control In the absence of AVR the voltage

can be manually controlled. The stabilized 15 V from the MPS is

applied across a second potentiometer. The variable output goes to the GPG together with output of the regulator

OP-AMP.

Page 18: AUTOMATIC  VOLTAGE  REGULATOR(AVR)

MANUAL FOLLOW UP

When there is a noticeable output from the regulator OP-AMP, depending on its polarity, either of a pair of relays is automatically closed to drive the manual potentiometer motor in the required direction.