Bay Protection & Control Dedicated automation controller with 4000 lines of logic Powerful math, control and boolean operators 10 stages under/over frequency protection for load shedding 4 stages of rate-of-change-of frequency for load shedding 6 stages of under-voltage elements for load shedding Dedicated protection logic at 1 msec execution rate Dedicated HMI for breaker and disconnect control Multi-breaker synchrocheck with single/three pole autoreclosing Dual breaker failure protection Direct and tele-protection elements using Inter-relay communications Bay Monitoring and Metering CT and VT monitoring Metering - current , voltage, frequency, power, energy and phasors as per IEEE C37.118 Fault recorder - 256 samples/cycle, 30 sec of storage capacity Disturbance recorder – 1 sample/cycle, 5 min of storage capacity Event recorder - 8000 time tagged events, with 0.5 ms scan of digital inputs Comprehensive display of metering, phasors, maintenance and fault information in the front panel Fast Load Shed Fast optimal load shedding executed within 20ms Intelligently sheds only necessary loads per customized priorities Highly customizable and scalable, integrating easily into most industrial plants with new or existing EMS/SCADA Optional stand-alone system with local HMI for viewing dedicated system status and reports Suitable for small or large industrial systems without re-design Easy to use system where settings and priorities can be configured within seconds Communications IEC61850, DNP3, Modbus RTU, Modbus TCP/IP, IEC 60870-5-104 Three independently configurable IP’s with fail-over features Inter-relay communication based on standard protocols Front USB for maintenance and downloading records and events Ease of Use and Security Graphical protection and automation logic programming Real time Logic Monitoring to simplify commissioning and troubleshooting EnerVista™ LaunchPad service and update notification toolset keeps documents and software up-to-date EnerVista Integrator providing easy integration of data (SCADA or DCS) into new or existing systems C90 Plus Multilin AUTOMATION CONTROL SYSTEM Powerful automation controller eliminates the need for separate substation programmable logic controller High-end load shedding with multiple stages of frequency and voltage retains system stability after disturbances Fast optimal load shedding executed within 20ms minimizes process outages and costs associated with system downtime Intelligently sheds loads to maintain system/process integrity Highly customizable and scalable, integrating easily into most industrial plants with new or existing EMS/SCADA Customizable annunciator panel capable of handling up to 288 alarms eliminates the need for a separate panel High-end fault and disturbance recording eliminates the need for digital fault or disturbance recorders Synchronized phasor information according to IEEE ® C37.118 standard for detection of system instability HMI with pre-configured and customizable displays including real time bay control, metering, fast load shed reports, equipment status, fault and event recording Advanced bay control/monitoring (6 breakers and 30 disconnects) Fast, power-balance load shed Frequency and voltage load shed Substation alarm concentrator, annunciator, and controller Advance automation schemes such as bus transfer Standalone breaker protection and monitoring FEATURES APPLICATIONS KEY BENEFITS g imagination at work

Upload: others

Post on 14-Apr-2020

20 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

Bay Protection & Control • Dedicatedautomationcontrollerwith4000linesoflogic• Powerfulmath,controlandbooleanoperators• 10stagesunder/overfrequencyprotectionforloadshedding• 4stagesofrate-of-change-offrequencyforloadshedding• 6stagesofunder-voltageelementsforloadshedding• Dedicatedprotectionlogicat1msecexecutionrate• DedicatedHMIforbreakeranddisconnectcontrol• Multi-breakersynchrocheckwithsingle/threepoleautoreclosing• Dualbreakerfailureprotection• Directandtele-protectionelementsusingInter-relay

communications

Bay Monitoring and Metering• CTandVTmonitoring• Metering-current,voltage,frequency,power,energyand

phasorsasperIEEEC37.118• Faultrecorder-256samples/cycle,30secofstoragecapacity• Disturbancerecorder–1sample/cycle,5minofstoragecapacity• Eventrecorder-8000timetaggedevents,with0.5msscanof

digitalinputs• Comprehensivedisplayofmetering,phasors,maintenanceand

faultinformationinthefrontpanel

Fast Load Shed • Fastoptimalloadsheddingexecutedwithin20ms• Intelligentlyshedsonlynecessaryloadspercustomizedpriorities• Highlycustomizableandscalable,integratingeasilyintomost

industrialplantswithneworexistingEMS/SCADA• Optionalstand-alonesystemwithlocalHMIforviewing

dedicatedsystemstatusandreports• Suitableforsmallorlargeindustrialsystemswithoutre-design• Easytousesystemwheresettingsandprioritiescanbe

configuredwithinseconds

Communications• IEC61850,DNP3,ModbusRTU,ModbusTCP/IP,IEC60870-5-104• ThreeindependentlyconfigurableIP’swithfail-overfeatures• Inter-relaycommunicationbasedonstandardprotocols• FrontUSBformaintenanceanddownloadingrecordsandevents

Ease of Use and Security• Graphicalprotectionandautomationlogicprogramming• RealtimeLogicMonitoringtosimplifycommissioningand

troubleshooting• EnerVista™LaunchPadserviceandupdatenotificationtoolset

keepsdocumentsandsoftwareup-to-date• EnerVistaIntegratorprovidingeasyintegrationofdata(SCADAor

DCS)intoneworexistingsystems

C90PlusMultilin™

AUTOMATION CONTROL SYSTEM

• Powerfulautomationcontrollereliminatestheneedforseparatesubstationprogrammablelogiccontroller

• High-endloadsheddingwithmultiplestagesoffrequencyandvoltageretainssystemstabilityafterdisturbances

• Fastoptimalloadsheddingexecutedwithin20msminimizesprocessoutagesandcostsassociatedwithsystemdowntime

• Intelligentlyshedsloadstomaintainsystem/processintegrity• Highlycustomizableandscalable,integratingeasilyintomost

industrialplantswithneworexistingEMS/SCADA

• Customizableannunciatorpanelcapableofhandlingupto288alarmseliminatestheneedforaseparatepanel

• High-endfaultanddisturbancerecordingeliminatestheneedfordigitalfaultordisturbancerecorders

• SynchronizedphasorinformationaccordingtoIEEE®C37.118standardfordetectionofsysteminstability

• HMIwithpre-configuredandcustomizabledisplaysincludingrealtimebaycontrol,metering,fastloadshedreports,equipmentstatus,faultandeventrecording

• Advancedbaycontrol/monitoring(6breakersand30disconnects)• Fast,power-balanceloadshed• Frequencyandvoltageloadshed

• Substationalarmconcentrator,annunciator,andcontroller• Advanceautomationschemessuchasbustransfer• Standalonebreakerprotectionandmonitoring

FEATURES

APPLICATIONS

KEY BENEFITS

g imagination at work

Page 2: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

FunctionalBlockDiagram

DEVICENUMBER

21G21P2527P27X50BF50DD50G50N50P50_251G51N

Ground DistancePhase DistanceSynchrocheckPhase UndervoltageAuxiliary UndervoltageBreaker FailureCurrent Disturbance DetectorGround Instantaneous OvercurrentNeutral Instantaneous OvercurrentPhase Instantaneous OvercurrentNegative Sequence Instantaneous OvercurrentGround Time OvercurrentNeutral Time Overcurrent

FUNCTION

ANSI DEVICE NUMBERS AND FUNCTIONSDEVICENUMBER

51P51_25259N59P59X59_267N67P67_2687879

Phase Time OvercurrentNegative Sequence Time OvercurrentAC Circuit BreakerNeutral OvervoltagePhase OvervoltageAuxiliary OvervoltageNegative Sequence OvervoltageNeutral Directional OvercurrentPhase Directional OvercurrentNegative Sequence Directional OvercurrentPower Swing BlockingOut-of-Step TrippingAutomatic Recloser

FUNCTION

837709AE.CDR

50N (2) 51N (2) 67N/G (2)

59P

59N

52 52

79

50P (2) 50_2 (2) 51P (2) 51_2 (2) 50BF (2) 67P (2) 67_2 (2)

59X 27X

50G (2) 51G (2)

50DD

Monitoring

C90Plus Controller System

CLOSE TRIP

25 (2)

FlexElementT M Transducer

InputsMetering

27P (2)

DeviceNumber Function25 SynchronismCheck27P PhaseUndervoltage27X AuxiliaryUndervoltage50BF BreakerFailure50DD CurrentDisturbanceDetector50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent

DeviceNumber Function50_2 NegativeSequenceInstantaneous

Overcurrent51G GroundTimeOvercurrent51N NeutralTimeOvercurrent51P PhaseTimeOvercurrent51_2 NegativeSequenceTimeOvercurrent52 ACCircuitBreaker59N NeutralOvervoltage

DeviceNumber Function59P PhaseOvervoltage59X AuxiliaryOvervoltage59_2 NegativeSequenceOvervoltage67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent67_2 NegativeSequenceDirectionalOvercurrent79 AutomaticRecloser81U/O Underandoverfrequency

ANSI® Device Numbers & Functions

AdvancedBayControlThe C90Plus Bay Control or Monitoringfunctionality is intended for high-endBay Control applications typically used inTransmission installations, where a largerquantity of I/O, advanced Protection andControl functionality and an advanced HMIisdesired.

BayControlProtectionFunctionsOvercurrent:

The C90Plus provides multiple stages ofovercurrent functions for phase, neutral andground.Overcurrentfunctionsinclude:

• Instantaneousandtimedovercurrentelementsforphase,neutral,groundandnegativesequenceprotection

• Directionalsupervisionisavailableforphaseneutralandnegativesequenceelements

• TimeO/CelementscanindividuallybesettouseIEEE,IEC®orcustomFlexCurves™

Over and Under Voltage Protection

Long lines under lightly loaded conditionsor no-load or sudden loss of power mayexperiencevoltagesexceeding the ratedperunit voltage level of the line. Use the phaseovervoltage element of the C90Plus to initiatea local trip as well as a remote trip usingdirect transfer trip. The C90Plus also provides

additionalvoltagefunctionsincludingneutralovervoltage, negative sequence overvoltageand phase undervoltage. The phaseundervoltagecanbeprogrammedasdefinitetimeorinversetime.

Over and Under Frequency Protection

The multiple stages of under and overfrequency elements can be used to initiateload shedding or remedial actions schemesorfrequency-basedloadrestorationschemesduring lack of generation in the network ordue to sudden load drops. Combined withtheadvancedautomation capabilities of theC90Plus flexible, special protection schemes,advancedloadsheddingandloadrestorationschemescanbebuilt .

2

C90Plus Automation Control System

GEDigitalEnergy.com

Page 3: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

SmallSignalOscillationFunctionalityA new protection element called the smallsignal oscillation detection is added to theproduct.Modernpowersystemsarebecomingincreasingly interconnected toeachother forthe benefits of increased reliability, reducedoperation cost, improved power quality andreduced necessary spinning reserve. Withthe increasingly large interconnected powersystems some technical challenges alsobecome apparent. One of these challengesis the inter-area low frequency oscillationsthatareamajor threat to reliableoperationsof large-scale power systems. Inter-areaoscillationsnotonlylimittheamountofpowertransfer,butalsothreatenthesystemsecurityand equilibrium, as theymay lead to systeminstabilityandcascadingoutages.

Therefore, it is essential to identify thecharacteristics of the inter-area oscillations,including oscillation frequency and dampingratio, so that proper actions can be takenbased on the results. This is required toimprove the system damping and maintain

stability in the power system. The C90Pluscan detect these inter-area oscillations andprovide an alarm or even a trip signal topreventalarge-scalesystemdisturbance.

BayConfigurationsTheC90Plushas12pre-configuredbaysingle-linediagramsandcorrespondingcontrolsforeach of the bay equipment. Users can alsoprogramtheirownsinglelinediagramsusingthe ANSI/IEC library symbols provided in theEnerVistaset-upprogram.

PowerSystemTroubleshootingThe C90Plus contains tools that allow for early detection of impending breaker problems and allow for maintenance to be performed before serious damage occurs.

Breaker Latch Release Time:

Indicates how long it took for the breaker latch to release

from the time the Trip Coil was energized by the relay

Arc Extinguish Time:

Indicates the length of time that was required for the

breaker to extinguish the arc and finally clear the fault

Breaker Mechanism Travel Time:

Indicates time interval required for the breaker mechanism

to travel to its rest position

Triggering a waveform on each breaker operation can identify changes in the length of time each part or mechanism in the breaker takes to perform its function.

Two-Main and Transfer Bus configuration

Double Bus configuration

Breaker-and-half configuration

3

C90Plus Automation Control System

GEDigitalEnergy.com

Page 4: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

FastLoadShed

WhyFastLoadShed?Conventional Frequency and Voltage loadsheddingschemesoperatetypicallyin250mstoseconds.

Contingency based load shedding schemesare typically faster at 160 – 400 msdepending on both system architecture andcommunicationsemployed.

Both these scheme types are too slow forIndustrial Cogeneration applications such asOilandGasorManufacturing,whereveryfastload shedding is required to ensure powersystemandcriticalprocessesintegrity.

WhatisFastLoadShed?FastLoadShedisaSystemconsistingofoneor more C90Plus, IEC61850-Ethernet network,UR, URPlus or IEC61850-8-1-capable enddevices that provides fast load shedding, tore-establish power balance when source/loadsbalancewasdisrupted.Enddevicesareof UR, URPlus, SR or IED’swith IEC 61850-8-1support(othervendorIEDinteroperabilitynotproven/tested). It is possible to use existingdevices which do not support IEC 61850.In those cases the D25 RTU can be used tocommunicatebetweenthoseexistingdevicesand the Fast Load Shed Controller, howeverthis will slow the scheme down. The C90PlusController checks if generation lost exceedsremaininggenerationreserveper:

Δ(Pgen)+Preserve≥0

IncaseofgenerationlossorpowerunbalanceGOOSE messages are sent to shed enoughloadperpre-definedprioritiesaboveavailablegeneration reserve (Dynamic Mode). LoadPriorities can be changed/updated via HMIwithin a second. Alternatively, a predefinedshedding scenario can be executed uponeachdefinedcontingency(StaticMode).

Upto16automaticreportsaregeneratedforany scheme operation containing Fast LoadShed Controller (FLSC) relay name, firmwarerevision,contingencydate/timeandduration,steady-state power flows, in-feeds lost ,scenarios encountered, load groups shed,settingslastchangeddate.

Speed of Fast Load Shed Scheme:

ThespeedofFastLoadSheddingincludinginternalprocessingisasfollows:

origin UR end device detects trip/breaker operation

3000µs URGOOSEmessagewithchangeofonlinestate

200µs MessagepassedthroughmultipleLANswitches

3000µs FLSCProcessingandcalculations

1000µs ShedcommandGOOSEmessagecomposed

500µs FLSCGOOSEmessageissentthroughLANswitches

3000µs ShedcommandGOOSEmessageparsedbyloadURs

4000µs URenddevicecalculationsandprocessing

2000µs Tripcontactoutputcloses

16.7ms Total

End-to-end execution made under 20m

C90PlusLoadShedSchemeDevices

C90Plus Fast Load Shed Controller (FLSC)

The controller is the main decision pointof the system where all the calculationsand intelligent commands are sent. It is asubstation-hardened devicewith a real-timeoperating system that is highly reliableand accurate. It is also equipped with alocal annunciator panel and HMI screen(optional) for ease-of-use for maintenanceandoperation.Thecontrollerreceivessourcedata from end devices, load data from enddevicesorAggregators viaanalogGOOSE. Ithandlesupto64loadsorin-feedsaswellas6localin-feeds,andmakesthefinaldecisionto shed load. The load shed commands areissuedviaGOOSEtoenddevices.

C90Plus Fast Load Shed Aggregator (FLSA)

This is an extension of the system allowingfor aggregation of load data and is a loadshed data concentrator – combines LoadData fromenddevicesand sendsasanalogGOOSE to the Controller. It does not makeloadsheddecisions.Itallowsthecontrollertohandlemorethan64loads.Byconnectingtheaggregatorsinatree-likematrix,thenumberofloadscontrolledwiththisschemecanreachover2500.

Load Shed Controller Design

The FLSC can interface or aggregatemeasurements into32 sources/in-feeds;and32loads/loadgroups(manyloads/group).

User-defined shed priorities of the loadgroups are fixed or user-selectable through

Enddevice(SourceorGeneratorProtection)detectsachange/trip

ShedcommandcomposedandsentfromC90Pluscontrollertoloadrelays

Tripcommandissenttocontactinloadrelay

GOOSEmessageiscreatedinSource/GeneratorProtection

Shedcommandgoesthrough20Ethernetswitches

Loadtripcontactcloses

GOOSEmessageisparsedintheC90Pluscontroller

17 milliseconds

Shedcommandparsedbyenddevices/loadrelays

4

C90Plus Automation Control System

GEDigitalEnergy.com

Page 5: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

anHMI.Loadscanbetakenoutofscanifitisdeterminedthatsheddingisnotrequired.TheFLSC has an auto-compute solution option(AdaptiveMode)where loads to be shedarecalculated based on priorities, generationlost and generation reserve; and a manualscenarioexecutionoption(StaticMode)whereload shedding is pre-determined for eachpowerlosscontingency.

Scalability of the Fast Load Shed Scheme

Thecontroller canhandleup to64 in-feeds/loads or aggregators plus 6 local devices(in-feedsorloads).

Adding another C90Plus as an aggregator,extendsthesystembyanadditional70loads.With12 in-feeds,18 loads&40aggregators

(64 loads each), the system can support 12in-feeds and 2578 sheddable loads.Minimalre-configuration is required in the case ofsystemexpansion.

Interoperability

AllcommunicationsarebasedonGOOSEandIEC61850-8-1.

G60

Aggregator

Loads, infeedsLoads Loads

32 load group powers32 infeed powers

32 reserve powers

Priorities or trip masks

C90Plus Fast LoadShed Controller (FLSC)

ML3000 Ethernet Switch

T60

End DevicesEnd Devices End Devices

Infeed data units(power, offline)

F60

Aggregator data message(32 load power groups)

Shed commands, digital GOOSE messages

Load data units, analog GOOSE messages(power, unavailable)

F35 F60 SR350

GOOSE

Legend

Modbus over TCP/IP

Aggregator

External computer(optional)

ML3000 Ethernet Switch

ML3000Ethernet Switch

SR350 F35 F60 SR350

TheSystemOverviewandArchitectureBelow is a typical Fast Load Shed scheme, consisting of:

• 1 x C90Plus FLSC

• IEC 61850-Ethernet network

• 2 x C90Plus FLSA’s (optional based on system size)

• IEC 61850-8-1 capable end-devices

The above system architecture can be expanded to cater for non-IEC 61850 end devices by adding a D25 Substation Controller.

5

C90Plus Automation Control System

GEDigitalEnergy.com

Page 6: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

SimplifiedSource-LoadExampleBelow is a simplified system illustrating the load shed priorities and how shedding is determined:

The Total System Load = PGrp1 + PGrp2 + PGrp3 + PGrp4 + PGrp5

Total Source/Generation = PG1 + PG2 + PMA + PMB

The C90Pluscalculates:Δ(Pgen)+Preserve≥0

LOAD PRIORITIZATION: (AS SET BY END-USER)

Asset Value Priority/Status (User set)

Group1 10MW 5

Group2 10MW 0(Don’tShed)

Group3 5MW 1

Group4 20MW 4

Group5 5MW 2

Example: For a loss of 9MW of Generation with no generation reserve, the scheme will trip Load Groups 3 and 5 for a total of 10MW.

Actual Load Shed Performance Results (System Islanded)

Belowaresometestresults fromaC90PlusFastLoadShedSchemeoperation inconjunctionwithbackupdf/dtandunderfrequencyloadshedding,illustratingoperatingspeedofeachsystemataPetrochemicalfacilitythatgotIslandedasa4.5MWunderpoweredIsland.Inthiscasetheschemeoperatedin13ms,includingtripcommandtosheddingloadbreakers.

TIME(MS) EVENT

0 BreakerMBOpenedmanually

8 BreakerOpenDe-bouncedIslandDetectedPriorities1,2and,3LoadShedsent

10 Shedmessagereceivedatloadrelays

13 Tripcoilsenergized

50 ShedBreakerOpen–loadshed

64 ROCOF(df/dt)Trigger

106 UnderfrequencyLoadShedTrigger

G1

GA

Grp1 Grp2 Grp3 Grp4 Grp5

G2

GBMA MB

230 kVFeed 1

230 kVFeed 2

TIE

G1 G2

PositivePower

PositivePower

C90PlusAutomationControlSystemThe C90Plus is a powerful logic controllerand protection product designed for therequirements of industrial and utility powersystems.ItsunparalleledlistoffeaturesmaketheC90Plusoneofthemostagileandadvancedproducts, allowing it to perform severalfunctions and be used in many scenariosbased on the needs of each customer. TheC90Plus provides unmatched logic processingability combined with a powerful mathengine with deterministic execution of logicequations, regardlessof the configurationofthenumberoflinesoflogic.

TheC90Plusprovidesthetoolsandfunctionalitynecessaryforcreatingcustomizedautomationandcontrolschemesthatinclude:

• Advancedbaycontrolandinterlocking

• Breakermonitoringandcontrol

• AutomaticBusTransferschemes

• Loadsheddingandloadrestorationschemes

• UltraFastLoadsheddinginindustrialplants

Automation Logic

TheC90Plus incorporatesadvancedautomationfeatures including powerful FlexLogic™ (userprogrammable logic) for its protection andadvanced automation schemes. Combinedwith the communication capabilities, C90Plusautomationfeaturesfarsurpasswhatisfoundinaveragerelayswithprogrammablelogic.TheC90PlusintegratesseamlesslywithURandURPlusrelaysforcompletesystemprotection,includinginterlockingandspecialprotectionschemes.

FlexLogic

FlexLogicisthepowerfuluserprogrammablelogic engine that provides the ability tocreate customized protection and controlschemes thereby minimizing the need, andtheassociatedcosts,ofauxiliarycomponentsand wiring. The independent automationFlexLogicfeaturesmath,Booleanandcontrolfunctions which can be used for advancedloadshedding, loadrestorationanddynamicvolt/var control schemes. More than 4000linesoflogicareprovidedwithadeterministicexecutionrateof50msec,irrespectiveofthenumberoflinesoflogic.

6

C90Plus Automation Control System

GEDigitalEnergy.com

Page 7: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

AutomationFlexLogicoperatorsinclude:

• Math:EXP,ACOS,ATAN2,ATAN,ASIN,FLOOR,CEIL,LOG,LOG10,POW,SIN,COS,TAN,NEG,ABS,SQRT,ADD,SUB,MUL,DIV,CONSTANT

• Boolean:AND,NAND,NOR,NOT,OR,XOR

• Control:=,<=,!=,>=,>,Latch,Positive/Negative/Dualoneshot,Timers,Counters

Deterministic Automation

Apowersystemisareal-timesysteminwhichtime and accuracy of every control shouldbe considered critical. The C90Plus operatingsystemensuresthateveryactionandcontrolis scheduled properly and beforehand toguaranteethatnothingismissednordelayed.This intelligence inside the C90Plus handlesboth protection trip commands as well asany other logic written for execution as perits programmed timeline.Nomoredelays ormissed timelines when it comes to controlbecauseprocessoris‘busy’orotherwise.

CommunicationsTheC90Plussupportsthemostpopularindustrystandard protocols enabling easy, directintegration into DCS and SCADA systemsincluding:

• IEC61850

• DNP3

• EthernetGlobalData(EGD)

• IEC60870-5-104

• ModbusRTU,ModbusTCP/IP

• ThreeindependentlyconfigurableIP’swithfail-overfeatures

• Inter-relaycommunicationcardtoenableimplementationofpilot-schemesbasedonstandardcommunicationprotocols

• FrontUSBformaintenance&downloadingrecordsandevents

Interoperability with Embedded IEC 61850

Use the C90Pluswith integrated IEC 61850 tolowercostsassociatedwithprotection,controland automation. GE Multilin’s leadershipin IEC 61850 comes from thousands ofinstalleddevices and followsonmany yearsof development and operational experiencewithUCA2.0.

• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging

• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVistaViewpointEngineer

• IntegrateGEMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVistaViewpointMonitoring

Extreme Communication

• Highreliablecommunicationcardwithautomaticfailoverandextremelyfastredundantschemes

• Inter-relaycommunicationcardtoenableimplementationofpilot-schemesthatarebasedonstandardcommunicationprotocols,andboth“Direct”and“Tele-Protection”inputandoutputelementsavailable

Ease-of-use, Security Ease-of-use and quicksetups are considered throughout everyapplication and configuration parameterrequiring virtually no training for thoseworking in thepower industry.TheEnerVistaSuite is an industry-leading set of softwareprograms that simplifies every aspect ofusing the C90Plus relay. The EnerVista suiteprovides all the tools to monitor the status

of the protected asset, maintain the relay,and integrate information measured by theC90PlusintoDCSorSCADAmonitoringsystems.Convenient COMTRADE and Sequence ofEvents viewers are an integral part of theURPlus Setup software included with everyURPlus relay, to carry out postmortem eventanalysis to ensure proper protection systemoperation.

Security and NERC/CIP

• AuditTrail

• Passwordprotectionandauthentication

• Supportforalphanumericpasswords

• Role-basedaccesscontroltomanagemultiplepersonnelrightsasperANSIINCITS359-2004

EnerVista Launchpad

EnerVista Launchpad is a powerful softwarepackage that provides users with all ofthe setup and support tools needed forconfiguring and maintaining GE’s Multilinproducts. The setup software withinLaunchpad allows configuring of devicesin real-time by communicating using serial,Ethernet, or modem connections, or offlinebycreatingsettingfilestobesenttodevicesat a later time. Included in Launchpad is adocumentarchivingandmanagementsystem

CustomProgrammableLogicDesigner

The C90Plus supports an advanced automation logic engine that supports Boolean operators, analog comparisons, and advanced mathematical operations.

7

C90Plus Automation Control System

GEDigitalEnergy.com

Page 8: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

thatensurescriticaldocumentation isup-to-dateandavailablewhenneeded.Documentsmadeavailableinclude:

• Manuals

• ApplicationNotes

• GuideformSpecifications

• Brochures

• WiringDiagrams

• FAQ’s

• ServiceBulletins

Viewpoint Engineer

ViewpointEngineer isasetofpowerful toolsthat will allow you to configure and testyour relays at a system level in an easy-to-use, graphical drag-and-drop environment.Viewpoint Engineer provides the followingconfigurationandcommissioningutilities:

• GraphicalLogicDesigner

• GraphicalSystemDesigner

• GraphicalLogicMonitor

• GraphicalSystemMonitor

UserInterfaceandHMIThe C90Plus provides extensive local HMIcapability through two dedicated displaypanels. One serves as a digital annunciatorandtheotheroptionalHMIisfordisplayandcontrolfunctions.

Annunciator

Enhanced HMI and Annouciator panels onthe front of the C90Plus make it one of themostpowerfulhumanmachineinterfacesonlocalunits.TheC90Plusprovidesanembedded,configurable color LCD annunciator on thefrontpanelofthedevice,eliminatingtheneedfor LED labels and separate annunciators intherelaypanel.

• Anycontact/direct/remoteinputorinternallygeneratedFlexLogicoperandcanbeassignedtobedisplayedontheannunciator.

• Upto288targetsmaybeassigned.Thedisplaycanbeconfiguredfor12/24/48alarmsperpagetoamax.of24pagesusinga16-colorpalletforbettervisualizationandcustomization.

• Aseparateself-testmessagepageontheannunciatorpanelshowsclearerrormessagesaboutthedevicehealth,greatlyassistinginidentifying,andcorrectingdevicerelatedissues.

• ForeasymaintenanceandassetmanagementproductinformationsuchasIPaddressesandserialnumbersofeachmodulearealsoaccessiblewithouttheneedtoconnecttotheunit.

HMI

• Comprehensivedatavisualization.

• UserprogrammablesinglelinediagramsupportedbyANSI/IECsymbols.Pre-programmedsinglelinediagramsforbaymonitoringandcontrolforcommonbusconfigurations,includingring-bus,doublebreakerandbreaker-and-halfconfigurations.

• Multipleprogrammablecontrolpushbuttons,tenpushbuttonsperpagewithmultiplelevelsofcontrol.

• Local/RemoteControl.

• Pre-programmedcomprehensivedisplaysfor:

- Metering

- BayControl

- FaultReports

- SequenceofEventReports

- FaultRecords

- DeviceDiagnostics

- EquipmentManager

- FastLoadShedStatusandReports

RealTimePhasorDisplaysofVoltage,CurrentandSequencecomponents.

Front Panel USB

The frontpanelof theC90PlusprovidesaUSB2.0hostforfieldlaptopconnectionsforhigh-speeddatatransfer,makingdownloadinganduploading faster than a conventional RS232connection.

12 to 48 user configurable alarms per page eliminates the need for a separate annunciator.

Easy to read large display of metering values.

Single Bus Configuration

Sequence of event records with the ability to view time difference between two events for troubleshooting and analysis.

Phasor display of sequence components showing the standing unbalance in the line.

8

C90Plus Automation Control System

GEDigitalEnergy.com

Page 9: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

Digital Alarm Annunciator• 288customizablealarmsinmultiplepages

usingapalletof16colors• Eliminatestheneedforseparate

annunciator• Descriptiveself-testmessages

Intuitive HMI• Userconfigurablesinglelinediagrams

usingIEC/ANSIlibrarysymbols• Localcontrolandstatusindicationof

breakers&disconnectswitches,20userprogrammablepushbuttons

• Local/Remotecontrol• Fault,event,disturbanceandtransient

reports

Bay Protection• Overcurrent,over/undervoltage,over/

underfrequency• Breakerfailure,autoreclose,synchcheck• 512linesofProtectionFlexLogic

@1msecexecution

Automation Controller• Built-inindustryhardenedlogiccontroller• 4096linesofindependentuser

programmablelogic,50msecexecutionrate

• AdvancedMath,BooleanandControloperations

Communication Capabilities• UptothreeindependentEthernetports

withredundantfast-over• IEC61850,DNP3,MODBUSTCP/IP,IEC

60870-5-104protocols• FrontUSBportforhighspeeddatatransfer

Recorders• Eliminatestheneedforstand-alone

disturbancerecorders• Configurableandupto256samples/cycle,

1mindurationrecorder• Dedicateddisturbancerecorderfor

recordinglongtermevents• SynchrophasorsoverEthernet

C90PlusAutomationControlSystem

Disturbance recorder eliminates stand-alone DFR and Phasor Measurement Unit

Digital fault recorder summary with the latest information on the events, faults, transients and disturbances.

Real time display of the fundamental phasors of voltage and current in the front panel HMI.

Real time phasor information of fundamental and sequence components

9

C90Plus Automation Control System

GEDigitalEnergy.com

Page 10: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

mm

mm

mm

mm

mm

mm

mm

mm

mmmm

mm

mm

mm

mm

mm

mm

mm

mm

mm

mmmm

mm

Dimensions

g Multilin C90PlusController

TypicalWiringDiagram

10

C90Plus Automation Control System

GEDigitalEnergy.com

Page 11: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

TechnicalSpecificationsAUTORECLOSUREApplications: twobreakersTrippingschemes: single-poleandthree-poleRecloseattempts: upto4beforelockoutReclosingmode: selectableBreakersequence: selectable

AUXILIARY OVERVOLTAGEPickuplevel: 0.000to1.100puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracy: ±0.5%ofreadingfrom10to208VPickupdelay: 0.00to600.00secondsinstepsof0.01Resetdelay: 0.00to600.00secondsinstepsof0.01Timingaccuracy: ±3%ofoperatetimeor±4ms

(whicheverisgreater)Operatetime: <2cyclesat1.10×pickupat60Hz

AUXILIARY UNDERVOLTAGEPickuplevel: 0.000to1.100puinstepsof0.001Dropoutlevel: >102%ofpickupLevelaccuracy: ±0.5%ofreadingfrom10to208VCurveshapes: GEIAVinverse,definitetimeCurvemultiplier: 0.00to600.00instepsof0.01Timingaccuracy: ±3%ofoperatetimeor±4ms

(whicheverisgreater)

BREAKER FAILUREMode: single-pole,three-poleCurrentsupervision: phasecurrent,neutralcurrentSupervisionpickup: 0.001to30.000puinstepsof0.001Supervisiondropout: <98%ofpickupSupervisionaccuracyat0.1to2.0×CT: ±2%ofratedSupervisionaccuracyat>2.0×CT: ±2.5%ofreadingTimeaccuracy: ±3%or4ms(whicheverisgreater)

BREAKER FLASHOVEROperatingquantity: phasecurrent,voltage,andvoltage

differencePickuplevelvoltage: 0.000to1.500puinstepsof0.001Dropoutlevelvoltage: 97to98%ofpickupPickuplevelcurrent: 0.000to1.500puinstepsof0.001Dropoutlevelcurrent: 97to98%ofpickupLevelaccuracy: ±0.5%or±0.1%ofrated

(whicheverisgreater)Pickupdelay: 0.000to65.535secondsinstepsof

0.001Timeaccuracy: ±3%or±42ms

(whicheverisgreater)Operatetime: <42msat1.10×pickupat60Hz

CONTACT INPUTSInputrating: 300VDCmaximumOnthreshold: 70%ofnominalvoltagesettingor20V

(whicheverisgreater)Offthreshold: 30%ofnominalvoltagesettingor15V

(whicheverisgreater)Bouncethreshold: 50%ofnominalvoltagesettingor20V

(whicheverisgreater)AZthreshold: 80%ofnominalvoltagesettingOvervoltagethreshold: 130%ofnominalvoltagesettingor285

VmaximumMaximumcurrent: 10mAduringturnon,0.5mAsteady-

stateNominalvoltage: 24to250VInputimpedance: activeRecognitiontime: <1msDebouncetimer: 1.50to16.00msinstepsof0.25Chatterdetectiontimer: 1to100secondsChatterstatechanges: 10to100

DISTURBANCE DETECTOR (50DD)Type: sensitivecurrentdisturbancedetectorRange: 0.004to0.04pu(twicethecurrentcut-

offlevelthreshold)

FLEXCURVESNumber: 4(AthroughD)Resetpoints: 40(0through1ofpickup)Operatepoints: 80(1through20ofpickup)Timedelay: 0to65535msinstepsof1

FLEXELEMENTSElements: 8Operatingsignal: anyanalogactualvalue,ortwovalues

indifferentialmodeOperatingsignalmode: signedorabsolutevalueOperatingmode: level,deltaComparatordetection: over,underPickuplevel: –90.000to90.000puinstepsof0.001Hysteresis: 0.1to50.0%instepsof0.1Deltadt: 20msto60daysPickupdelay: 0.000to65.535secondsinstepsof

0.001Dropoutdelay: 0.000to65.535secondsinstepsof

0.001

FLEXMATRIXPrinciple: aggregatesandconditionssignalsfor

trippingandauxiliaryfunctionsTimingaccuracy: ±1ms

FLEX STATESNumber: upto256logicalvariablesgrouped

under16ModbusaddressesProgrammability: anylogicalvariable,contact,orvirtual

input

GROUND INSTANTANEOUS OVERCURRENTPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingOverreach: <2%Pickupdelay: 0.00to600.00secondsinstepsof0.01Resetdelay: 0.00to600.00secondsinstepsof0.01Operatetime: <16msat3×pickupat60HzTimingaccuracyforoperationat1.5×pickup: ±3%or±4ms(whicheverisgreater)

GROUND TIME OVERCURRENTCurrent: phasororRMSPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingCurveshapes: IEEEModeratelyInverse,IEEEVery

Inverse,IEEEExtremelyInverse,IEC(BS)A,IEC(BS)B,IEC(BS)C,IECShortInverse,IACInverse,IACShortInverse,IACVeryInverse,IACExtremelyInverse,I2t,FlexCurves™(programmable),definitetime(0.01secondbasecurve)

Curvemultiplier: 0.01to600.00instepsof0.01Resettype: instantaneous/timed(perIEEE)Timingaccuracyfor1.03to20×pickup: ±3.5%ofoperatingtimeor±1cycle

(whicheverisgreater)

NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENTDirectionality: co-existingforwardandreversePolarizing: voltagePolarizingvoltage: V_2Operatingcurrent: I_2Levelsensing(zero-sequence): |I_0|–K×|I_1|Levelsensing(negative-sequence): |I_2|–K×|I_1|Restraint,K: 0.000to0.500instepsof0.001Characteristicangle: 0to90°instepsof1Limitangle: 40to90°instepsof1,independentfor

forwardandreverseAngleaccuracy: ±2°Offsetimpedance: 0.00to250.00ohmsinstepsof0.01Pickuplevel: 0.05to30.00puinstepsof0.01Dropoutlevel: <98%Operationtime: <16msat3×pickupat60Hz

NEGATIVE-SEQUENCE INSTANTANEOUS OVERCURRENTPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingOverreach: <2%Pickupdelay: 0.00to600.00secondsinstepsof0.01Resetdelay: 0.00to600.00secondsinstepsof0.01Operatetime: <20msat3×pickupat60HzTimingaccuracyforoperationat1.5×pickup: ±3%or±4ms(whicheverisgreater)

NEGATIVE-SEQUENCE OVERVOLTAGEPickuplevel: 0.000to1.250puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracy: ±0.5%ofreadingfrom10to208VPickupdelay: 0.00to600.00secondsinstepsof0.01Resetdelay: 0.00to600.00secondsinstepsof0.01Timingaccuracy: ±3%or±20ms(whicheverisgreater)Operatetime: <30msat1.10×pickupat60Hz

NEGATIVE-SEQUENCE TIME OVERCURRENTPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingCurveshapes: IEEEModeratelyInverse,IEEEVery

Inverse,IEEEExtremelyInverse,IEC(BS)A,IEC(BS)B,IEC(BS)C,IECShortInverse,IACInverse,IACShortInverse,IACVeryInverse,IACExtremelyInverse,I2t,FlexCurves™(programmable),definitetime(0.01secondbasecurve)

Curvemultiplier: 0.01to600.00instepsof0.01Resettype: instantaneous/timed(perIEEE)and

linearTimingaccuracyfor1.03to20×pickup: ±3.5%ofoperatingtimeor±1cycle

(whicheverisgreater)

NEUTRAL DIRECTIONAL OVERCURRENTDirectionality: co-existingforwardandreversePolarizing: voltage,current,dualPolarizingvoltage: V_0orVXPolarizingcurrent: IGOperatingcurrent: I_0Levelsensing: 3×(|I_0|–K×|I_1|),IG;independentfor

forwardandreverseRestraint(K): 0.000to0.500instepsof0.001Characteristicangle: –90to90°instepsof1Limitangle: 40to90°instepsof1,independentfor

forwardandreverseAngleaccuracy: ±2°Offsetimpedance: 0.00to250.00ohmsinstepsof0.01Pickuplevel: 0.002to30.000puinstepsof0.01Dropoutlevel: <98%Operationtime: <16msat3×pickupat60Hz

NEUTRAL INSTANTANEOUS OVERCURRENTPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingOverreach: <2%Pickupdelay: 0.00to600.00secondsinstepsof0.01Resetdelay: 0.00to600.00secondsinstepsof0.01Operatetime: <20msat3×pickupat60HzTimingaccuracyforoperationat1.5×pickup: ±3%or±4ms(whicheverisgreater)

NEUTRAL OVERVOLTAGEPickuplevel: 0.000to1.250puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracy: ±0.5%ofreadingfrom10to208VPickupdelay: 0.00to600.00secondsinstepsof0.01

(definitetime)oruser-definedcurveResetdelay: 0.00to600.00secondsinstepsof0.01Timingaccuracy: ±3%or±20ms(whicheverisgreater)Operatetime: <3cyclesat1.10×pickup

NEUTRAL TIME OVERCURRENTCurrent: phasororRMSPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingCurveshapes: IEEEModeratelyInverse,IEEEVery

Inverse,IEEEExtremelyInverse,IEC(BS)A,IEC(BS)B,IEC(BS)C,IECShortInverse,IACInverse,IACShortInverse,IACVeryInverse,IACExtremelyInverse,I2t,FlexCurves™(programmable),definitetime(0.01secondbasecurve)

Curvemultiplier: 0.01to600.00instepsof0.01Resettype: instantaneous/timed(perIEEE)Timingaccuracyat1.03to20×pickup: ±3.5%ofoperatingtimeor±1cycle

(whicheverisgreater)

NON-VOLATILE LATCHESType: set-dominantorreset-dominantNumber: 16(individuallyprogrammed)Output: storedinnon-volatilememoryExecutionsequence: asinputpriortoprotection,control,and

FlexLogic

11

C90Plus Automation Control System

GEDigitalEnergy.com

Page 12: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

TechnicalSpecifications(cont’d)PHASE DIRECTIONAL OVERCURRENTRelayconnection: 90°(quadrature)Quadraturevoltage: phaseA(VBC),phaseB(VCA),phaseC

(VAB)forABCphasesequence;phaseA(VCB),phaseB(VAC),phaseC(VBA)forACB

phasesequencePolarizingvoltagethreshold: 0.000to3.000puinstepsof0.001Currentsensitivitythreshold: 0.05puCharacteristicangle: 0to359°instepsof1Angleaccuracy: ±2°Trippingoperationtime: <12ms,typically(reverseload,forward

fault)Blockingoperationtime:<8ms,typically(forwardload,reverse

fault)

PHASE INSTANTANEOUS OVERCURRENTPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingOverreach: <2%Pickupdelay: 0.00to600.00secondsinstepsof0.01Resetdelay: 0.00to600.00secondsinstepsof0.01Operatetime: <16msat3×pickupat60HzTimingaccuracyforoperationat1.5×pickup: ±3%or±4ms(whicheverisgreater)

PHASE OVERVOLTAGEVoltage: phasoronlyPickuplevel: 0.000to3.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracy: ±0.5%ofreadingfrom10to208VPickupdelay: 0.00to600.00secondsinstepsof0.01Operatetime: <3cyclesat1.10×pickupTimingaccuracy: ±3%or±4ms(whicheverisgreater)

PHASE TIME OVERCURRENTCurrent: phasororRMSPickuplevel: 0.000to30.000puinstepsof0.001Dropoutlevel: <98%ofpickupLevelaccuracyat0.1to2.0×CT: ±0.5%ofreadingor±1%ofrated

(whicheverisgreater)Levelaccuracyat>2.0×CT: ±1.5%ofreadingCurveshapes: IEEEModeratelyInverse,IEEEVery

Inverse,IEEEExtremelyInverse,IEC(BS)A,IEC(BS)B,IEC(BS)C,IECShortInverse,IACInverse,IACShortInverse,IACVeryInverse,IACExtremelyInverse,I2t,FlexCurves™(programmable),definitetime(0.01secondbasecurve)

Curvemultiplier: 0.01to600.00instepsof0.01Resettype: instantaneous/timed(perIEEE)Timingaccuracyat1.03to20×pickup: ±3.5%ofoperatingtimeor±1cycle

(whicheverisgreater)

PHASE UNDERVOLTAGEPickuplevel: 0.000to1.100puinstepsof0.001Dropoutlevel: >102%ofpickupLevelaccuracy: ±0.5%ofreadingfrom10to208VCurveshapes: GEIAVInverse;DefiniteTime(0.1

secondbasecurve)Curvemultiplier: 0.00to600.00instepsof0.01Timingaccuracyforoperationat<0.90×pickup: ±3.5%ofoperatetimeor±4ms

(whicheverisgreater)

PROTECTION FLEXLOGICProgramming: ReversePolishNotationwithgraphical

visualization(keypadprogrammable)Linesofcode: 512Internalvariables: 64Supportedoperations: NOT,XOR,OR(2to16inputs),AND(2to

16inputs),NOR(2to16inputs),NAND(2to16inputs),latch(reset-dominant),edgedetectors,timers

Inputs: anylogicalvariable,contact,orvirtualinput

Numberoftimers: 32Pickupdelay: 0to60000(ms,seconds,orminutes)in

stepsof1Dropoutdelay: 0to60000(ms,seconds,orminutes)in

stepsof1

PROTECTION VIRTUAL INPUTSInputpoints: 64Programmability: self-resetorlatched

PROTECTION VIRTUAL OUTPUTSOutputpoints: 96Programmability: outputofaprotectionFlexLogic

equationorinputtoaprotectionFlexLogicequation

REMOTE INPUTS (IEC 61850 GSSE/GOOSE)Inputpoints: 64Remotedevices: 32Defaultstatesonlossofcommunications: on,off,latest/off,latest/onRemotedouble-pointsstatusinputs: 16

REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)Standardoutputpoints: 32Useroutputpoints: 32

SENSITIVE DIRECTIONAL POWERMeasuredpower: three-phase,trueRMSStages: 2Characteristicangle: 0to359°instepsof1Calibrationangle: 0.00to0.95°instepsof0.05Minimumpower: –1.200to1.200puinstepsof0.001Pickuplevelaccuracy: ±1%or±0.001pu(whicheverisgreater)Hysteresis: 2%or0.001pu(whicheverisgreater)Pickupdelay: 0.00to600.00secondsinstepsof0.01Timeaccuracy: ±3%or±4ms(whicheverisgreater)Operatetime: 50ms

SMALL SIGNAL OSCILLATION DETECTORMeasuredvalue: anyanalogvalueElements: 2Inputs: 6Minimumpickup: 0.02to10.00puinstepsof0.01for

alarm;0.05to10.00puinstepsof0.01fortrip

Pickuplevelaccuracy: ±5%or±0.1pu(whicheverisgreater)Pickupdelay: definitetime,0.00to600.00secondsin

stepsof0.01Timeaccuracy: ±3%or±20ms(whicheverisgreater)Operatetime: 3/(4×fs)to1/fs,wherefsisthesignal

frequency

VT FUSE FAILURE SUPERVISIONElements: 1persourceMonitoredparameters: V_2,V_1,I_1

AutomationAUTOMATION LOGICNumberoflinesoflogic:4096Numberofblocks: 1Editandviewcapability:yesLogictype: cyclicProgramminglanguage:proprietaryExecutionrate: 50msVariabletypes: Boolean,IEEEfloatingpointBooleanoperations: NOT,XOR,OR,AND,NOR,NAND,any

contactinput,anydirectinput,anyteleprotectioninput,anyremoteinput,anyvirtualinput,anyautomationlogicoperand

Arithmeticoperations: add,subtract,multiply,divide,negation,absolutevalue,squareroot,exponent,logarithm,sine,cosine,tangent,arcsine,arccosine,arctangent,naturallogarithm,base10algorithm,modulo,ceiling,floor

Controloperations: latch,timer,comparator,absolutetimerfunctions

Booleaninputs: anycontactinput,directinput,teleprotectioninput,remoteinput,virtualinput,orautomationlogicoperand

Analoginputs: anyFlexAnalog™quantityVirtualinputs: 128Virtualoutputs: 255Remoteinputs: 64Remoteoutputs: 64Remotedevices: 32

AUTOMATION VIRTUAL INPUTSInputpoints: 128Programmability: self-resetorlatched

AUTOMATION VIRTUAL OUTPUTSOutputpoints: 255Programmability: outputofanautomationlogicequation

orinputtoanautomationlogicequation

BREAKER CONTROLMode: single-pole,three-poleControl: open/close,local/SCADAControlseal-in: 0to2000msinstepsof1

BREAKER INTERLOCKINGInterlockinginputs: 6

DISCONNECT CONTROLMode: single-pole,three-poleControl: open/close,local/SCADAControlseal-in: 0to2000msinstepsof1

DISCONNECT INTERLOCKINGInterlockinginputs: 3

FAST LOAD SHEDDING (FLS)Elements: 1Algorithm: adaptive(usingpriorities)orstatic

(usingtripmasks)Staticmodescenarios: upto32Adaptivemodepriorities:upto128Totalofinfeeds,loads,andaggregatorsmonitoredperC90Plus: upto64viacommunicationsplus6

localinfeedsorloadsInfeeds: upto32Loadsperenddevice: upto6perGOOSEdatamessageLoadsperC90Plus: upto70(upto64fromenddevice,plus

upto6fromlocalcontactinput/outputcards)

Loadgroups: upto32Operatetime: 1/8powersystemcycle(exclusiveof

communicationsandenddevicedelays)Powermeasurementupdating: 250ms

FREQUENCY RATE OF CHANGE LOAD SHEDDINGElements: 4Minimumvoltage: 0.10to1.25puinstepsof0.01Pickuplevel: 0.10to15.00Hz/sinstepsof0.01Dropoutlevel: pickup–0.02Hz/sPickupdelay: 0.00to99.99secondsinstepsof0.001Dropoutdelay: 0.00to99.99secondsinstepsof0.001Levelaccuracy: 30mHz/sor3.5%(whicheverisgreater)Timeaccuracy: ±3%or±4ms(whicheverisgreater)95%settlingtimefordf/dt: <24cyclesOperatetime(typical): 6cyclesat2×pickup;5cyclesat3×

pickup;4cyclesat5×pickup

LOAD SHEDDING SOURCEMinimumvoltagepickup: 0.00to1.25puinstepsof0.01Minimumvoltagedropout: pickup+0.20puMaximumnegative-sequencevoltagepickup: 0.00to1.25puinstepsof0.01Maximumnegative-sequencevoltagedropout: pickup–0.20pu

SELECTOR SWITCHUpperpositionlimit: 1to7instepsof1Selectingmode: time-outoracknowledgeTime-outtimer: 3.0to60.0secondsinstepsof0.1Controlinputs: step-upandthree-bitPower-upmode: restorefromnon-volatilememoryor

synchronizetoathreebitcontrolinputorsynchronize/restoremode

SYNCHROCHECKElements: 2Maximumvoltagedifference: 0to100000voltsinstepsof1Maximumangledifference: 0to100°instepsof1Maximumfrequencydifference: 0.00to2.00Hzinstepsof0.01Hysteresisformaximumfrequencydifference: 0.00to0.10Hzinstepsof0.01Deadsourcefunction: none,LV1&DV2,DV1&LV2,DV1or

DV2,DV1xorDV2,DV1&DV2(L=live,D=dead)

UNDERFREQUENCY LOAD SHEDDINGElements: 10Pickuplevel: 45.00to65.00Hzinstepsof0.01Dropoutlevel: pickuplevel+0.03HzPickupdelay: 0.00to99.99secondsinstepsof0.01Dropoutdelay: 0.00to99.99secondsinstepsof0.01Levelaccuracy: ±0.01HzTimeaccuracy: ±3%or4ms(whicheverisgreater)Operatetime(typical): 4cyclesat–0.1Hz/schange;3.5cycles

at–0.3Hz/schange;3cyclesat–0.5Hz/schange

UNDERVOLTAGE LOAD SHEDDINGElements: 6Pickuplevel: 0.10to1.25puinstepsof0.01Dropoutlevel: pickuplevel+0.20puPickupdelay: 0.00to99.99secondsinstepsof0.01Dropoutdelay: 0.00to99.99secondsinstepsof0.01Levelaccuracy: ±0.5%ofreadingfrom10to208voltsTimeaccuracy: ±3%or4ms(whicheverisgreater)Operatetime(typical): 2cyclesat0.90×pickup

12

C90Plus Automation Control System

GEDigitalEnergy.com

Page 13: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

EquipmentManagerBATTERY MONITORPrinciple: monitorsbatteryvoltageandauxiliaryalarmsHysteresis: 5%Timingaccuracy: 1cycle

BREAKER ARCING CURRENTElements: 1perbreaker(toamaximumof2)Principle: accumulatescontactwear(Ixt),

measuresfaultmagnitudeanddurationAuxiliarycontactcompensation: 0to50msinstepsof1Alarmthreshold: 0to50000kA2-cycleinstepsof1Faultdurationaccuracy: 0.25ofpowercycle

MeteringCURRENT METERINGType: phaseandgroundRMScurrentAccuracyat0.1to2.0×CT: ±0.25%ofreadingor±0.1%ofrated

(whicheverisgreater)at50/60Hznominalfrequency

Accuracyat>2.0×CT: ±1.0%ofreading,at50/60Hznominalfrequency

DATA LOGGERChannels: 1to16Parameters: anyFlexAnalogvalueStatistics: maximumandtimeofmaximum,

minimumandtimeofminimum,average

Alarms: high,high-high,low,low-low

ENERGY METERINGType: positiveandnegativewatt-hoursand

var-hoursAccuracy: ±2.0%ofreadingRange: –2.0×109to2.0×109MWh/MvarhParameters: three-phaseonlyUpdaterate: 50ms

FREQUENCY METERINGAccuracyatV=0.8to1.2pu: ±0.001Hz(whenvoltagesignalisused

forfrequencymeasurement)AccuracyatI=0.1to0.25pu: ±0.05Hz(whencurrentsignalisused

forfrequencymeasurement)AccuracyatI>0.25pu: ±0.001Hz(whencurrentsignalisused

forfrequencymeasurement)

PHASOR MEASUREMENT UNITOutputformat: perIEEEC37.118standardChannels: 14synchrophasors,8analogs,16

digitalsTVE(totalvectorerror): <1%Triggering: frequency,voltage,current,power,rate

ofchangeoffrequency,user-definedReportingrate: 1,2,5,10,12,15,20,25,30,50,or60

timespersecondNumberofclients: OneoverTCP/IPport,twooverUDP/IP

portsACranges: asindicatedinappropriate

specificationssectionsNetworkreportingformat: 16-bitintegeror32-bitIEEEfloating

pointnumbersNetworkreportingstyle: rectangular(realandimaginary)

orpolar(magnitudeandangle)coordinates

Post-filtering: none,3-point,5-point,7-pointCalibration: ±5°

POWER METERINGRealpoweraccuracy: ±1.0%ofreadingat–1.0≤PF<0.8and

0.8<PF≤1.0Reactivepoweraccuracy: ±1.0%ofreadingat–0.2≤PF≤0.2Apparentpoweraccuracy: ±1.0%ofreading

VOLTAGE METERINGType: RMSvoltageAccuracy: ±0.5%ofreadingfrom30to208volts

at50/60Hznominalfrequency

DigitalFaultRecorderDISTURBANCE RECORDERStoragecapacity: onerecordwithallavailablechannels

at60samplespersecondfor40seconds

Maximumrecords: 64Samplingrate: 1samplepercycleSamplingaccuracy: <1mspersecondofrecordingAnalogchannels: 64Analogchanneldata: anyFlexAnalog™quantityDigitalchannels: 32Digitalchanneldata: anycontactinput,directinput,remote

input,virtualinput,automationlogicoperand,orFlexLogicoperand

Triggers: anydigitalchangeofstate(user-programmable),undervoltage,overvoltage,undercurrent,overcurrent,underfrequency,overfrequency,rateofchangeoffrequency,1user-programmabletrigger,1lock

Storagemodes: automaticoverwrite,protectedTriggeringmodes: timewindowfromrisingedgeoftrigger,

continuousrecordingaslongastriggerisactive

Pre-triggerwindow: 0to100%Datastorage: non-volatilememory

EVENT RECORDERStoragecapacity: 8192eventsTimetag: to1msTriggers: anycontactinput,directinput,remote

input,virtualinput,logicoperand,orself-testevent

Datastorage: non-volatilememory

FAULT REPORTRecords: 5Data: stationandcircuitID,dateandtimeoftrip,faulttype,activesettinggroupattimeoftrigger,pre-faultcurrentandvoltagephasors(2cyclesbefore50DDassociatedwithfaultreportsource),faultcurrentandvoltagephasors(1cycleaftertrigger),protectionelementsoperatedattimeoftrigger,firmwarerevisionTriggers: user-selectedoperandDatastorage: non-volatilememory

FAULT LOCATORMethod: single-endedAccuracy: 2%oflinelengthUnits: milesorkilometersTrigger: fromfaultreportDatastorage: non-volatilememory

FAST LOAD SHED REPORTRecords: 16Data: FLSCrelayname,firmwarerevision,

contingencydate/timeandduration,steady-statepowerflows,infeedslost,scenariosencountered,loadgroupsshed,settingslastchangedate

Triggers: anyFLScontingencyDatastorage: non-volatilememory

TRANSIENT RECORDERStoragecapacity: onerecordwithallavailablechannels

at32samplespercyclefor1minuteNumberofrecords: 1to64Samplingrate: 16to256samplesperpowercycleTimestampaccuracy: <10μspersecondofrecordingAnalogchannels: uptotwelve16-bit,unprocessed,AC

inputchannelsAnalogchanneldata: anyFlexAnalogquantityDigitalchannels: upto128Digitalchanneldata: anycontactinput,directinput,remote

input,virtualinput,automationlogicoperand,orFlexLogicoperand

Sampledchannels: upto24Sampledchanneldata: 16-bit,unprocessedsampledchannelsTriggers: anydigitalchannelchangeof

state,undervoltage,overvoltage,undercurrent,overcurrent,underfrequency,overfrequency,rateofchangeoffrequency,oneuserprogrammable,oneblock

Storagemodes: automaticoverwrite,protectedTriggeringmodes: timewindowfromrisingedgeoftrigger,

continuousrecordingaslongastriggerisactive

Pre-triggerwindow: 0to100%Datastorage: non-volatilememory

FrontPanelInterfaceANNUNCIATORInputs: 288Windowsperpage: 12to48Pages: upto24Sequence: manualreset,lockingOffindication: alarminactiveandresetFlashingindication: alarmactiveandnotacknowledged,

alarminactiveandnotacknowledgedOnindication: alarmactiveandacknowledged,alarm

inactiveandnotresetPriority: byactivewindowandpagenumberDatastorage: non-volatilememory

CONTROL DISPLAYDevices: statusandcontrolofupto8power

systemdevicesPushbuttons: 30dedicateduser-programmable

pushbuttonsFunctionality: supportsselect-before-operate

functionality

DIGITAL FAULT RECORDER DISPLAYSequenceofevents: displaysthestoredsequenceofevents

recordFaultreports: displayandretrievalofthecritical

metricsofastoredfaultreportTransientrecords: retrievalofastoredtransientrecordDisturbancerecords: retrievalofastoreddisturbancerecordFastloadshedding(FLS)records: retrievalofastoredFLSrecord

EQUIPMENT MANAGER DISPLAYBatterymonitoring: displaysthecurrentbatteryvoltageand

alarmstates

METERING DISPLAYSummary: displayspresentvaluesofvoltage,

current,realpower,reactivepower,powerfactor,andfrequencyonaper-phaseandtotalbasis

Phasors: digitalandgraphicaldisplayofpresentvoltageandcurrentmagnitudesandangles

Sequencecomponents: displayspresentmagnitudesandanglesofcurrentandvoltagesequencecomponents

Energy: four-quadrantdisplayofaccumulatedenergy

Demand: presentandpeakdemandvaluesforcurrentandreal,reactive,andapparentpower

MAINTENANCE DISPLAYInputandoutputstatus:displaysthecurrentstatusofallcontactinputsandoutputs

HardwareAC CURRENTCTratedprimary: 1to50000ACTratedsecondary: 1Aor5ANominalfrequency: 50or60HzRelayburden: <0.2VAsecondaryConversionrange: 0.02to46×CTratingRMSsymmetricalCurrentwithstand: 20msat250×rated,1secondat100×

rated,continuousat3×rated

AC VOLTAGEVTratedsecondary: 50.0to240.0VVTratio: 1.00to24000.0Nominalfrequency: 50or60HzRelayburden: <0.25VAat120VConversionrange: 1to275VVoltagewithstand: continuousat260Vtoneutral,1

minuteperhourat420Vneutral

CONTACT INPUTSInputrating: 300VDCmaximumSelectablethresholds: 24to250VMaximumcurrent: 10mAduringturnon,0.5mAsteady-

stateRecognitiontime: <1msDebouncetimer: 1.50to16.00msinstepsof0.25

CONTACT OUTPUTS: CRITICAL FAILURE RELAYMakeandcarryfor0.2s: 10:00AMContinuouscarry: 6:00AMBreakatL/Rof40ms: 0.250Aat125VDC;0.125Aat250VDCOperatetime: <8msContactmaterial: silveralloy

13

C90Plus Automation Control System

GEDigitalEnergy.com

Page 14: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

Hardware(cont’d)CONTACT OUTPUTS: FORM-A RELAYMakeandcarryfor0.2s: 30AasperANSIC37.90Continuouscarry: 6:00AMBreakatL/Rof40ms: 0.250Aat125VDC;0.125Aat250VDCOperatetime: <4msContactmaterial: silveralloy

CONTACT OUTPUTS: SOLID-STATE RELAYMakeandcarryfor0.2s: 30AasperANSIC37.90Continuouscarry: 6:00AMBreakatL/Rof40ms: 10Aat250VDCOperatetime: <100μsContactmaterial: silveralloy

CONTROL POWER EXTERNAL OUTPUTCapacity: 100mADCat48VDCIsolation: 2kV

CRITICAL FAILURE RELAYMakeandcarryfor0.2s: 30AasperANSIC37.90Carrycontinuous: 6:00AMBreakatL/Rof40ms: 0.250ADCat125VDC;0.125ADCat

250VDC;0.10ADCmaximumat125VOperatetime: <8msContactmaterial: silveralloy

ETHERNET PORTSStandard: 1portsupportingModbusTCPOptional: 2portssupportingDNP3.0,IEC

60870-5-104,orIEC61850locatedoncommunicationsmodule

100Base-FXmediatype:1300nm,multi-mode,half/full-duplex,fiberopticwithSTconnector

10/100Base-TXmediatype: RJ45connectorPowerbudget: 10dBMaximumopticalinputpower: –14dBmReceiversensitivity: –30dBmTypicaldistance: 2.0kmSNTPclocksynchronization: <10mstypical

FORM-A RELAYMakeandcarryfor0.2s: 30AperANSIC37.90Carrycontinuous: 6ABreakatL/Rof40ms: 0.250ADCat125VDC;0.125ADCat

250VDCOperatetime: <4msContactmaterial: silveralloy

IRIG-B INPUTAmplitudemodulation: 1to10Vpk-pkDCshift: TTLInputimpedance: 50kΩIsolation: 2kV

POWER SUPPLYNominalDCvoltage: 125to250VMinimumDCvoltage: 80VMaximumDCvoltage: 300VNominalACvoltage: 100to240Vat50/60HzMinimumACvoltage: 80Vat48to62HzMaximumACvoltage: 275Vat48to62HzVoltagewithstand: 2×highestnominalvoltagefor10msVoltagelosshold-up: 200msdurationatnominalPowerconsumption: 30VAtypical,65VAmaximum

RS485 PORTBaudrates: 300,600,1200,2400,4800,9600,

19200,38400,57600,115200Protocol: ModbusRTUandDNP3.0Distance: 1200mIsolation: 2kV

SOLID-STATE RELAYMakeandcarryfor0.2s: 30AasperANSIC37.90Carrycontinuous: 6ABreakatL/Rof40ms: 10.0ADCat250VDCOperatetime: <100μs

USB PORTStandard: typeBUSBconnectorforEnerVista

software

CommunicationsDIRECT INPUTSInputpoints: 96perchannelRemotedevices: 16Defaultstatesonlossofcommunications: On,Off,Latest/On,Latest/OffRingconfiguration: yes,noDatarate: 64or128kbpsCRC: 32-bitCRCalarm: respondingtorateofmessagesfailing

theCRCCRCalarmmonitoringmessagecount: 10to10000instepsof1CRCalarmthreshold: 1to1000instepsof1Unreturnedmessagesalarm: respondingtorateofunreturned

messagesintheringUnreturnedmessagesalarmmonitoringmessagecount: 10to10000instepsof1Unreturnedmessagesalarmthreshold: 1to1000instepsof1

DIRECT OUTPUTSOutputpoints: 96perchannel

FAST LOAD SHEDDING (FLS) END DEVICE DATA UNITS (IEC 61850 GOOSE)Number: 64

MODBUS USER MAPNumber: upto256ModbusaddressesProgrammability: anysettingoractualvalueindecimal

REMOTE INPUTS (IEC 61850 GSSE/GOOSE)Inputpoints: 64Remotedevices: 32Defaultstatesonlossofcommunications: On,Off,Latest/Off,Latest/OnRemotedouble-pointstatusinputs: 16

REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)Standardoutputpoints: 12AUseroutputpoints: 32

TELEPROTECTIONInputpoints: 16perchannelRemotedevices: 3Defaultstatesonlossofcommunications: On,Off,Latest/On,Latest/OffRingconfiguration: NoDatarate: 64or128kbpsCRC: 32-bit

Inter-relayCommunicationsTYPICAL DISTANCERS422interface: 1200m(basedontransmitterpower;

doesnottakeintoconsiderationtheclocksourceprovidedbytheuser)

G.703interface: 100m850nmlaser(multimode)interface: 2.0km(50/125μmcablewithST

connector);2.9km(62.5/125μmcablewithSTconnector)

NOTE: Thetypicaldistancesshownarebasedontheassumptionsforsystemlossshownbelow.Asactuallossesvaryfromoneinstallationtoanother,thedistancecoveredbyyoursystemmayvary.

LINK LOSSES (850 NM LASER, MULTIMODE MODULE)STconnectorlosses: 2dB(totalofbothends)50/125μmfiberloss: 2.5dB/km62.5/125μmfiberloss: 3.0dB/kmSpliceloss: onespliceevery2km,at0.05dBloss

perspliceSystemmargin: 3dBofadditionallosswasaddedto

calculationstocompensateforallotherlosses,includingageandtemperature

LINK POWER BUDGET (850 NM LASER, MULTIMODE MODULE)Maximumopticalinputpower: –9dBmMinimumtransmitpower: –22dBm(into50μmfiber),–18dBm

(into62.5μmfiber)Maximumreceiversensitivity: –32dBmPowerbudget: 10dBm(for50μmfiber),14dBm(for

62.5μmfiber)NOTE: Thesepowerbudgetsarecalculated

fromthemanufacturer’sworst-casetransmitterpowerandworst-casereceiversensitivity.

TestsPRODUCTION TESTSThermal: productsgothrougha12hourburn-in

processat60°C

TYPE TESTSVibration: IEC60255-21-1,1G(classBm)Shock/bump: IEC60255-21-2,10G(classBm)Seismic(singleaxis): IEC60255-21-3,1G/3.5mm(class1)Makeandcarry(30A): IEEEC37.90Conductedimmunity: IEC61000-4-6/IEC60255-22-6,class3

(10VRMS)Surge: IEC61000-4-5orIEC60225-22-5,

1.2/50testuptolevel4(4kV)Burstdisturbance(1MHzoscillatory): IEC60255-22-1upto2.5kVat1MHz

dampedFasttransients: ANSI/IEEEC37.90.1,EC61000-4-4class

4,(2kV,5kHz/4kV,2.5kHz,2kVondatacontrolportsandinputs/outputs),IEC60255-22-4

Radiatedimmunity: IEC61000-4-3/IEC60255-22-3class3(10V/m)orIEEEC37.90.2radiatedRFI(35V/m)

Powerfrequencydisturbance: IEC61000-4-8(30A/m)class4Radiated/conductedemissions: IEC60255-25/CISPR11/22classAInsulationresistance: IEC60255-5Dielectricstrength: IEC60255-5,ANSI/IEEEC37.90Dielectricacrossrelaycontacts: IEEEC37.90(1.6kV)Electrostaticdischarge: EN61000-4-2,IEC60255-22-28kVC,

15kVA,L4Voltagedips/interruptions/variations: IEC61000-4-11(30%1cycle),IEC

60255-11ACripple: IEC61000-4-17(standard)InterruptionsonDCpower: IEC61000-4-29Dampedmagneticimmunity: IEC61000-4-10(level5,100A/m)Impulsevoltagewithstand: EN/IEC60255-5(5kV)Humiditycyclic: IEC60068-2-30,6days55°C,95%RH

(variant1)

EnvironmentalOPERATING TEMPERATURECold: IEC60068-2-1,16hoursat–40°CDryheat: IEC60068-2-2,16hoursat80°C

OTHER ENVIRONMENTAL SPECIFICATIONSAltitude: upto2000mInstallationcategory: IIIPrating: IP30forfront,IP10forback

ApprovalsandCertificationAPPROVALSUL50817theditionandC22.2No.14-05: ULlistedfortheUSAandCanada

CERTIFICATIONCELVD2006/95/EC: EN/IEC61010-1:2001/EN60255-5:2000CEEMC89/336/EEC: EN60255-26:2004-08

14

C90Plus Automation Control System

GEDigitalEnergy.com

Page 15: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

OrderingC90P * E * * ** * * * X H * * * * * * ** * Description

Base Unit C90P BaseUnitFrontPanel A Annunciator

H Annunciator&HMILanguage E EnglishProtection X None

P BasicProtectionandProtectionFlexLogicO Basicprotection,protectionFlexLogic,small-signaloscillationdetection

Automation S BreakerControl&SynchrocheckE BreakerControl,Synchrocheck,&AutomationControllerL BreakerControl,Synchrocheck,AutomationController,&LoadSheddingC Fastloadshedding(controller)A Fastloadshedding(aggregator)

Communications 01 ModBusTCP/IP,DNP3.0Serial,andSerialModbus02 ModBusTCP/IP&IEC6185003 ModBusTCP/IP,IEC61850,&DNP3.0TCP/IP04 ModBusTCP/IP,IEC61850,&IEC60870-5-104

Metering D NoACmetering;dataloggerfornon-meteringdataS BasicMeteringP BasicMetering&SynchrophasorsL BasicMetering&DataLoggerU BasicMetering,DataLogger,&Synchrophasors

DigitalFaultRecorder S FaultRecorder&SequenceofEventsD FaultRecorder,SequenceofEvents,&DisturbanceRecorder

EquipmentManager X NoequipmentmanagerfeaturesS Circuitbreaker,communicationsstatistics,andbatterymonitor

Reserved XPowerSupply H High(88-275VAC/80-300VDCI)Inter-relayCommunications X Reserved

B G.703,64/128kbps,twochannelsC RS422,64/128kbps,twochannels,twoclockinputsD 850nm,64/128kbps,STmulti-modelaser,twochannelswithDDMI

CommunicationsModule X NoneA DualSTfiberandcoppermodule

I/OModule X X X X X NoneA A A A A 8Inputs,4Form-AOutputswithVoltage&CurrentMonitoringB B B B B 8Inputs,4SolidStateOutputswithVoltage&CurrentMonitoringC C C C C 8Inputs,4Form-AOutputsD D D D D 4Inputs,8Form-AOutputsE E E E E 23InputsF F F F F 12Form-AOutputs

ACModule X NoACmodule01 5VT&7CT(5Ampcurrent)02 5VT&7CT(1Ampcurrent)

Notes for Fast Load Shedding:

Front Panel: Can be either A or H (HMI is an option)

Automation: C or A for Controller or Aggregator

Communication Module: Only option A available

AC Module: X – none only option

TypicalC90PlusFastLoadShedOrderCodes:Controller Aggregator

• MultiLinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1

• ViewpointEngineer VPE-1

• ViewpointMaintenance VPM-1

• ViewpointMonitoringIEC61850 VP-1-61850

AccessoriesfortheC90Plus

15

C90Plus Automation Control System

GEDigitalEnergy.com

Page 16: AUTOMATION CONTROL SYSTEM - GE Grid Solutions · 2013-02-12 · AUTOMATION CONTROL SYSTEM • Powerful automation controller eliminates the need for separate substation programmable

g imagination at work GEA-12653A(E)English130212

DigitalEnergy650MarklandSt.Markham,ONCanadaL6C0M1TollFree(NAOnly):1-800-547-8629Tel:905-927-7070Fax:905-927-5098

GEDigitalEnergy.com©Copyright2013.GeneralElectricCompany.AllRightsReserved.GE reserves the right tomakechanges to specificationsofproductsdescribedatany timewithoutnoticeandwithoutobligationtonotifyanypersonofsuchchanges.GE, theGEmonogram,Multilin, EnerVista, FlexCurves and FlexLogic are trademarks of theGeneralElectricCompany.ANSIisaregisteredtrademarkofAmericanNationalStandardsInstitute,Incorporated.IECisaregisteredtrademarkofCommissionElectrotechniqueInternationale.IEEEisaregisteredtrademarkoftheInstituteofElectricalElectronicsEngineers,Inc.