Table of Contents 2

General Description 3 Materials 3

Areas of Applicatoin 4

Dimensions 4

Cooling Capacities 5

Heating Capacities 6

BRW Standard Slot Patterns 7

BRW Alternate Slot Patterns 8

Barcol-Air Ltd. continuously strives to optimize the construction and the quality of all products. Barcol-Air Ltd. therefore, reserves the right to undertake modifi cations in product specifi cations without notice or obligation.

©Copyright Barcol-Air Ltd. 2012

No part of this publication may be multiplied and/or made public by means of print, photocopy, microfi lm or in any other manner without the prior written authorization of Barcol-Air Ltd.

Page 3: BARCOL-AIR RADIANT WAVE (BRW)

Page 3 of 1010/09/2012 Barcol-Air Radiant Wave BRW

Barcol-Air Ltd115 Hurley RoadOxford, CT 06478P. 203-262-9900

RADIANT WAVE

General DescriptionThe BRW is a unique system that is energy effi cient, but also effective in tempering its surrounding. It has an innovative, distinctive and visually appealing design, like no other in the market. It provides thermal com-fort by radiation and acts as a heat exchanger. The assembly consists of two components; an aluminum profi le shaped as a “wave” and a seamless preci-sion drawn copper tube. The aluminum profi le also has a “C” channel embedded in the center, which holds the copper tubing. The copper tubing does not reach beyond the vertical edges of the sail, thereby, remain-ing concealed. Hot or cold water runs in the copper tubes, by which, heat is transferred via conduction to or from the sails, and via radiation to the surrounding area. The connections to the water mains are located on the top of the sail.The profi les are fi xated with top-mounted crossbars, which also serve as suspension points, typically from the ceiling. The heat exchanger assembly can be custom manufactured to accommodate various sizes. Sail lengths range from 6 feet to 12 feet, in increments of one foot. The sail width is defi ned by the number of extrusions mounted in parallel, ranging from 8 to 14 profi les, in increments of 2 (refer to page 4 for more detail). There are no restrictions in length and/or width combinations, provided the water-side pressure drop does not exceed 15 feet (recommendation Barcol-Air), or another threshold specifi ed by the engineer.The sails are available in slotted and non-slotted versions. The BRW heat exchanger is manufactured and assembled at a certifi ed location, as approved by Barcol Air Ltd. The sail is then powder coated in a color selected by the architect or client.

MaterialsThe embedded “C” channel in the “wave” profi le comes in contact with at least 55% of the outer diameter of the copper tube. Thereby, a consistent thermal contact is achieved between the profi le and the copper, without the use of any heat transfer pastes. The tolerances of the “C” channel together with the tolerances of the copper tube result in the ability to clamp or snap the tube in the profi le when it is pressed together. This enables an optimal heat transfer area and heat transfer rate.The copper tube is a precision drawn 15.0 mm (0.591”) OD, seamless and semi-hard drawn copper tube. To ensure a high precision fi t in the “C” channel, the copper is calibrated and hardened. The tolerances of the OD are within ± 0.02 mm. The copper tubing is tested with the “Eddy Current Method” and proofed for any hairline cracks.

Page 4: BARCOL-AIR RADIANT WAVE (BRW)

Page 4 of 10 10/09/2012Barcol-Air Radiant Wave BRW EN-Imperial

Barcol-Air Ltd115 Hurley RoadOxford, CT 06478P. 203-262-9900

RADIANT WAVE

DimensionsThe sail lengths range from 6 feet to 12 feet, in increments of one foot. The sail width is defi ned by the num-ber of profi les mounted in parallel, ranging from 8 to 14 pieces, in increments of 2 extrusions. This results in a combined width of 30” for 8 profi les, 36” for 10 profi les, 42” for 12 profi les and 48” for 14 profi les. Please note drawings below.

.

Areas of Application1. Commericial or residential buildings2. Offi ce buildings3. Schools4. Manufacturing facilities5. Other

Page 5: BARCOL-AIR RADIANT WAVE (BRW)

Page 5 of 1010/09/2012 Barcol-Air Radiant Wave BRW

Barcol-Air Ltd115 Hurley RoadOxford, CT 06478P. 203-262-9900

RADIANT WAVE

Cooling Capacities

The mean temperature difference (Δtm ºF) for cooling is calculated as follows:Δtm (ºF) = Room Temp. (ºF) - [(Supply Water Temp. (ºF) + Return Water Temp. (ºF))/2]

BRW Cooling CapacetiesBRW Cooling Capaceties140

BRW Cooling Capaceties140

BRW Cooling Capaceties140

- Interior Full Slotted130 E i P i l Sl d F d 97ºF

- Interior Full Slotted130 - Exterior Partial Slotted Facade 97ºF

- Interior Full Slotted130 - Exterior Partial Slotted Facade 97ºF

I t i P ti l Sl tt d

130 - Exterior Partial Slotted Facade 97ºF- Interior Partial Slotted

120

- Interior Partial Slotted- Interior Non Slotted120 - Interior Non Slotted120 - Interior Non Slotted

110110110

100100100100

909090

a

80rea

80

ve a

rea

80

Wav

e ar

70Wav

e

70

ft W

av

70

sqft

W 70

UH

/sqf

t W

60TUH

/s

60

BTU

H

60

BTU

BT

5050

404040

30

40

303030

2020

101010

000 5 10 15 20 25

00 5 10 15 20 25

00 5 10 15 20 25

Mean Temperature Difference tm ºF0 5 10 15 20 25

Mean Temperature Difference tm ºFMean Temperature Difference tm F

Page 6: BARCOL-AIR RADIANT WAVE (BRW)

Page 6 of 10 10/09/2012Barcol-Air Radiant Wave BRW EN-Imperial

Barcol-Air Ltd115 Hurley RoadOxford, CT 06478P. 203-262-9900

RADIANT WAVE

Heating Capacities

The mean temperature difference (Δtm ºF) for heating is calculated as follows:Δtm (ºF) = [(Supply Water Temp. (ºF) + Return Water Temp. (ºF))/2] - Room Tempe. (ºF)

140

160

180

BRW Heating Capaceties

- Exterior Partial Slotted Facade 55ºF- Interior Partial Slotted- Interior Non Slotted

- Interior Full Slotted

100

120

ft W

ave

area

40

60

80

BTU

H/s

qf

0

20

0 5 10 15 20 25 30 35 40

Mean Temperature Difference tm ºF

Page 7: BARCOL-AIR RADIANT WAVE (BRW)

Page 7 of 1010/09/2012 Barcol-Air Radiant Wave BRW

Barcol-Air Ltd115 Hurley RoadOxford, CT 06478P. 203-262-9900

RADIANT WAVE

BRW with Standard SlotsThe BRW comes in three standard slot patterns: 1. None slotted, 2. Partial slotted 3. Fully slotted.

Note: The partially slotted wave will have partially slotted profi les in the interier part of the wave and fully slotted profi les at the perimeter of the wave.

Standard No Slots Standard Partial Slots Standard Full Slots

Standard Partial Slots, perimeter profi les are fully slotted and interior profi les are partly slotted

Page 8: BARCOL-AIR RADIANT WAVE (BRW)

Page 8 of 10 10/09/2012Barcol-Air Radiant Wave BRW EN-Imperial

Barcol-Air Ltd115 Hurley RoadOxford, CT 06478P. 203-262-9900

RADIANT WAVE

BRW Alternate Slot Patterns (possible on request)

Page 9: BARCOL-AIR RADIANT WAVE (BRW)

Page 9 of 1010/09/2012 Barcol-Air Radiant Wave BRW

Barcol-Air Ltd115 Hurley RoadOxford, CT 06478P. 203-262-9900

RADIANT WAVE

Federal Center South in Seattle WA

Page 10: BARCOL-AIR RADIANT WAVE (BRW)

RADIANT WAVE

Contacts

Headquarters

Your partner for radiant cooling and heating,chilled beams and VAV systems.

Barcol-Air Ltd.115 Hurley Road Oxford, CT 06478Phone: (203) 262-9900Fax: (203) 262-9906Email: [email protected]: www.barcolairusa.com

Barcol-Air Ltd.Georgetown Center, Building B5963 Coreson Avenue SouthSeattle, WA 98108Email: [email protected]: www.barcolairusa.com