basic dupline basic dupline ® jens neigaard1 basic

20
Jens Neigaard 1 Basic Dupline Basic Dupline ® Basic

Upload: aidan-goynes

Post on 14-Dec-2015

236 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 1

Basic Dupline Basic Dupline ®

Basic

Page 2: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 2

Basic Dupline Basic Dupline ®

Typical Automation SystemTypical Automation System

ControllerPLC / PC

Field DevicesSensors, Switches, Valves, Contactors, Drives etc.

TraditionalInstallation

Dupline (or other Fieldbus)Installation

Page 3: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 3

Basic Dupline Basic Dupline ®

General Fieldbus AdvantagesGeneral Fieldbus Advantages

• Reduced Installation CostReduced Installation Cost

• Reduced Cable CostReduced Cable Cost

• Reduction in maintenance costReduction in maintenance cost

• Increased flexibilityIncreased flexibility

• Capacity for more signalsCapacity for more signals

Page 4: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 4

Basic Dupline Basic Dupline ®

Signal

Common

Basic Basic components: components: The twisted pairThe twisted pair

Page 5: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 5

Basic Dupline Basic Dupline ®

Channel GeneratorFM K 64

FM K 32

FM K 16

FM K 8

FM K 128

DuplineFM K 128

Carlo Gavazzi

Basic Components: Basic Components: The Channel The Channel GeneratorGenerator

Page 6: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 6

Basic Dupline Basic Dupline ®

Supply

DuplineCarlo Gavazzi

Transmitter

Basic Basic Components: The Components: The TransmitterTransmitter

Page 7: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 7

Basic Dupline Basic Dupline ®

Supply

DuplineCarlo Gavazzi

Receiver

Basic Basic Components: The Components: The ReceiverReceiver

Page 8: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 8

Basic Dupline Basic Dupline ®

I/OI/O AddressAddresseses: : A1A1, A2, A3 .. , A2, A3 .. A8, B1, B2 .. A8, B1, B2 .. P7, P8P7, P8

Gro

up

sG

rou

ps :

: A

A

...

..

. PP

Channels: 1 Channels: 1 ...... 8 8

Dupline Addressing SchemeDupline Addressing Scheme

Page 9: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 9

Basic Dupline Basic Dupline ®

A B C D E F G H

I J K L M N O P

In/Out

Group

Channel

Read/On Prog

DuplineASIC ProgrammerGAP 1605

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

Carlo Gavazzi

Dupline Address Coding Dupline Address Coding Device: GAP1605Device: GAP1605

Page 10: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 10

Basic Dupline Basic Dupline ®

A1

A1

A2

A2

A3

A3

A4

A4

A1 A2 A4

A3

A3

Channel Generator

A1 A2 A4

FMK 8

Dupline used for wire Dupline used for wire replacementreplacement

Page 11: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 11

Basic Dupline Basic Dupline ®

Transmitter

Transmitter

Channel Generator

Receiver

Transmitter

64

A1 A5

A1 A5

A1 A5

A1 A5

n-Remote Transmitters have n-Remote Transmitters have Effect on One Central ReceiverEffect on One Central Receiver

Page 12: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 12

Basic Dupline Basic Dupline ®

Receiver

Receiver

Channel Generator

Transmitter

Receiver

64

A1 A5

A1 A5

A1 A5

A1 A5

A Central Transmitter has A Central Transmitter has Effect on n-Remote ReceiversEffect on n-Remote Receivers

Page 13: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 13

Basic Dupline Basic Dupline ®

Dupline

Carlo Gavazzi

DuplineCarlo Gavazzi

Dupline Dupline Standard Standard HousingsHousings

Page 14: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 14

Basic Dupline Basic Dupline ®

Different iDifferent input Typesnput Types• Contact /NPN TransistorContact /NPN Transistor• VoltageVoltage

Different outputDifferent output Types Types• RelayRelay• NPN TransistorNPN Transistor• PNP Transistor PNP Transistor

Different Different nnumber of Iumber of I/O’s/O’s

H-HousingsH-Housings, , D-HousingsD-Housings and Open PCB and Open PCB

Different Different ssupply upply vvoltagesoltages

Dupline Digital I/O-modulesDupline Digital I/O-modules

Page 15: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 15

Basic Dupline Basic Dupline ®

A 1 - 3 - - - - 8

1 3 8

Mode Enter

7 8

4 5

1 2

6

3

DuplineTest Unit GTU 8

Select Channel-Group

Display of Channel-Status’

MODE: DIGITAL 1 GROUP

Force Channels to ON(monostable)

7

Monitoring of Channel Status’ in a Selected Channel GroupMonitoring of Channel Status’ in a Selected Channel Group

Dupline Test Unit: GTU8Dupline Test Unit: GTU8

Page 16: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 16

Basic Dupline Basic Dupline ®

Channel GeneratorFM K 128

Dupline has free TopologyDupline has free Topology

Page 17: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 17

Basic Dupline Basic Dupline ®

• Single Single (t(twistedwisted)) ppair of air of wwiresires• ShieldShield not required not required• Recommended min. cRecommended min. cross ross ssectionectionss

• Long distance:Long distance: 1.5mm 1.5mm22

• Medium distance:Medium distance: 0.8 - 0.8 - 1.1.0 0 mmmm22

• Short distance:Short distance: 0.35 0.35 mmmm22

• Low capacitance for longLow capacitance for long distancesdistances ((preferably preferably < 80 nF/km) < 80 nF/km)

Dupline CablesDupline Cables

Page 18: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 18

Basic Dupline Basic Dupline ®

• Never connect DuplineNever connect Dupline CommonCommon to Groundto Ground

• Treat the Dupline cable as a signal wireTreat the Dupline cable as a signal wire

• Use DT01 termination unit for Use DT01 termination unit for distances > 1.5 kmdistances > 1.5 km

• Check correct wiring duringCheck correct wiring during installationinstallation

Dupline InstallationDupline Installation

Page 19: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 19

Basic Dupline Basic Dupline ®

• Use soldering splicesUse soldering splices

• Splices must be water tightSplices must be water tight

• No leakage or connection between wires orNo leakage or connection between wires or fromfrom wires to groundwires to ground

Cable Splicing / IsolationCable Splicing / Isolation

Page 20: Basic Dupline Basic Dupline ® Jens Neigaard1 Basic

Jens Neigaard 20

Basic Dupline Basic Dupline ®

Rules for Dupline-powered Rules for Dupline-powered DevicesDevices

a) The total current consumption must not exceed max current output of the channel-generator:G34900000: Max. 70 mAG38000015: Max. 130 mA

b) The total current consumption in the network multiplied by the cable loop resistance must not exceed 2 V

An example: 2 km 1.0 sq.mm twisted pair is used. G50101106 is used both with input and LED

The resistance of a 1.0 sq.mm. core is app. 20 Ohms/km. With a wire length of 2 km the resistance per wire is 40 OhmsWith the 2 Dupline wires the total resistance is 2 x 40 ohms = 80 Ohms.This means that the max total current is 2 V / 80 Ohms = 25 mA.One G50101106 with LED function uses 1.2 mAMax Number of G50101106 = 25 mA / 1.2 mA = 20 units

If the LED is not used the current per G50101106 is only 0.15 mA so in this case the result is:

Max number of G50101106's = 25 mA / 0.15 mA = 166 units.