    BE1-IPS

    URB-9

    9-12

    ADVANTAGES Twosensitive,singleorthreephase,forwardorreverse,overorunderpowerelements fordirectionalintertiepowerowandislandingdetection.

    Twophaseover/undervoltageelementsforintertievoltagelimitsandislandingdetection. TwoneutralvoltageelementsforV

    0detection.

    Negativesequencevoltagefunctionforreversephaserotationorsinglephasingdetection. Sixover/underfrequencyelementsforoverandunderfrequencyintertielimits,islandingdetection,

    andautomaticloadshedschemes. Sixrateofchangefrequencyelementsforislandingdetectionthatcanbesetforpositive,negative,

    or"either"rateofchange.Alsousedinloadshedschemes. Multipletimeandinstantaneousovercurrentelementsthatcanbeindividuallysetforforwardor

    reversedirectionalornon-directionalcontrolformaximumexibilityinanyapplication. Sync-checkandconditionalvoltagereclosing. BESTlogicprovidestheuserwithcompleteexibilityinconguringaprotectionandcontrol

    system.Userprogrammablevariableandswitchnamesmaketheserelayscompletely

    self-documenting. ProgrammableLCDdisplayallowstherelaytoreplacelocalindicationandcontrolfunctions,such

    aspanelmetering,alarmannunciation,andcontrolswitches. Threeindependentcommunicationportsandsupportforseveralpopularprotocolsallow

    integrationwithdistributedcontrolsystems. OptionalBESTNetEthernetpackageprovidesmeteringandstatuswebpages,settingsand

    congurationviaEthernetandemailnoticationofuser-denedevents.ModbusTM/TCPalsoavailable.

    RealTimeClockwith8-hourcapacitorride-throughandoptionalbatterybackup. AvailableinfullydrawoutS1double-endedcasewithtestpaddlesforretrotapplications.TheS1

    case,withavailableadapterplates,tscutout,drillingandbehindpanelprojectiondimensionsforcommonBaslerElectric,GEandWestinghouseunitcaserelays.

    FEATURESPages2and3

    APPLICATIONSPage3

    FUNCTIONALDESCRIPTION

    Page4-6

    BESTlogicPages8and9

    SPECIFICATIONSPages7,10-11

    ORDERINGINFORMATION

    Page12

    INSTRUCTION MANUAL MODBUS INSTRUCTION MANUAL Requestpublication9365900990 Requestpublication9365900992

    DNP 3.0 INSTRUCTION MANUAL Requestpublication9365900991

    ADDITIONAL INFORMATION

    WINDOWS SOFTWAREInterfaceforsettingandcommunicatingwithBaslerprotectionproductsRequestBESTCOMSforBE1-IPS100(includes"settingscompare"feature)

    BE1-IPS100INTERTIE

    PROTECTION SYSTEM

    DEVICE FUNCTIONS

    24 25 27 32

    43 47 50

    59 60 62 67

    BF

    Opt io n Opt ion

    TheBE1-IPS100isamultifunctionnumericIntertieProtectionSystemthatprovidestheprotectionandcontrolrequirementsoutlinedinIEEEIntertieProtectionStandard1547-2003forthemajorityofapplications.TheIPS100relayprovidesthreephase,ground,andnegativesequence,directionalornon-directionaltimeandinstantaneousovercurrentprotectionwithsynccheckandconditionalvoltagereclosing.Alsoincludedaresingleorthreephase,forwardorreverse,overorunderpower,breakerfailure,over/under/rateofchangefrequency,over/undervoltage,overexcitationprotection,andbreakermonitoringandcontrol,sequence-of-eventsrecording,faultreporting,andmeteringfunctions,allinacompactintegratedsystem.

    79 81

    Ethernet

    Option

    Modbus DNP3

    101

    51

    12570 STATE ROUTE 143, HIGHLAND, ILLINOIS 62249 USA PHONE 618-654-2341 FAX 618-654-2351

  • 7/28/2019 BE1-IPS100bull9

    2/12

    E1-IPS100

    FEATURESPROTECTION2eachPhase,Neutral,andNegativeSequence

    InstantaneousOvercurrentelementswithsettabletimedelay:50TP,150TP,50TN,150TN,50TQ,150TQ

    1-Phase(see151Pnote),2-Neutral,and1-Negative

    SequenceTimeOvercurrentelements:DualMode51P,or51V(restrainedorcontrolled),51N,151N,51Q.

    Note:If51Pissetdirectional,asecondpickuplevel(151P)canbeset.Tripdirectionofthe151Pisxed

    oppositethe51P.SeeIPS100instructionmanual, Section4,fordetails.

    Eachovercurrentelementcanbesetforforward, reverse,ornondirectionalcontrol(67P,67N,67Q).

    DirectionalcontrolisbyPositive(671),Negative(672),

    ZeroSequenceVoltage(670V)andZero SequenceCurrent(670I)polarizeddirectionalunits.

    AllU.S.andIECtimingcurvesplususerprogram- mablecurve

    Uniquedesignminimizestransientoverreachand

    overtravelonovercurrentelements Optionalseparategroundcurrentinputprovideszero

    sequencecurrentpolarizationand/orground overcurrentprotectionforaseparategroundCT.

    PhaseUndervoltageandOvervoltageelements:

    27P,127P,59P,159P.Elementsusea1of3,2of3,or3of3logic,andmonitoreitherline-lineorline-ground

    voltages.The27Pand127Pelementshavean undervoltageinhibitsetting.

    AuxiliaryUndervoltageandOvervoltageelements: 27X,59X,159X.Elementsmonitoreitherfundamental

    orthirdharmonicontheauxiliary4thVTinput,or

    fundamentalphaseresidual,3V0,ofthephaseinputs.The27Xelementhasanundervoltageinhibitsetting.

    Overexcitation,voltsperHertzelement:24inverseanddenitetime.

    SingleorThreephase,ForwardorReverse,Overor

    UnderPowerelements:32/132 NegativeSequenceOvervoltageelement:47

    Over/Under/RateofChangeFrequencyelements:81,181,281,381,481,581.Rateofchangecanbesetfor

    positive,negative,oreither.

    Each81elementcanbeassignedtomonitor3phaseVTinput(VP)orAuxiliaryvoltageinput(Vx).

    BreakerFailureprotectionfunction:BF Twogeneralpurposelogictimers:62,162

    ProgrammableLogicusingBESTlogic Twoprotectionsettinggroupswithexternalorautomatic

    (coldloadpickup,load,andunbalance) selectionmodes

    Synccheckwithdeadline/deadbusvoltagemonitorlogic,25,25VM

    Fuselossdetectionprotectsagainstfalsetripduetoloss

    ofvoltagesensing:60FL

    CONTROL Fourshotrecloserwithzonesequencecoordinationand

    sequencecontrolledprotectiveelementblocking

    functions Virtualbreakercontrolswitchcontrollablefromboth

    HMIandcom.ports:101 Twovirtualselectorswitchescontrollablefromboth

    HMIandcom.ports:43,143. Communicationportcontrolof101,43,and143

    switchesallowsforSCADAcontrolofrelayandbreaker

    INSTRUMENTATION RealtimeA,B,Cphasecurrent,voltage,andfrequency

    calculatedneutral,positive,andnegativesequence

    currentandvoltage,andanglesforallquantities.

    RealTimeperphaseand3phaseWatts,Vars,and

    3phasePowerFactor EnhancedDaylightSavingsTime(DST)denitions.

    REPORTS Currentdemandsforphase,neutral,andnegative

    sequencecurrents,andforwardandreversewattsand

    varsmagnitudesandtimestampsarerecordedfor

    today'speak,yesterday'speak,andpeaksincereset Optional4000pointlogofdemandreadings

    kWhandkvarh,forwardandreverse Breakeroperationscounterandcontactinterruptionduty.

    Max.torqueanglebetweenthepolarizingcurrentandvolt-ageiscontinuouslyadjustablebetween0and90.

    FAULT RECORDING 255eventsequenceofeventsreportwithI/Oand alarmsub-reports

    FaultReporting;1or2oscillographyrecordsper faultreport

    16faultsummaryreports;twomostrecentFault

    SummaryRecordssavedtonon-volatilememoryTotalnumberofoscillographyrecordssettablefrom

    6to16Totalof240cyclesoscillographymemory@12

    samples/cycle

    COMTRADEformat

    Loadcompensateddistancetofault

    COMMUNICATION PORTS Twoindependentgeneralpurposecommunication

    ports -FrontRS-232ASCIIcommunications

    -RearRS-485ASCII,ModbusandDNP3.0 protocols

    OptionalrearRS-232ASCIIcommunicationsIRIG-Btimesync(unmodulated)

    Optional10/100BaseTEthernetportwithBESTNet

    EasyEthernetorwithModbus/TCPprotocol

    SELF TEST AND ALARM FUNCTIONS Relayfail,majoralarm,andminoralarmLEDs,and

    fail-safealarmoutputcontact(closedoropen)

    Extensiveinternaldiagnosticsmonitorallinternal

    functionsoftherelay Morethan20additionalalarmpointsprogrammable

    formajororminorpriority

    Including:

    -Phasecurrent,andforwardandreversewattand vardemandalarm

    -Neutralandnegativesequenceunbalancedemand alarms

    -Threebreakeralarmpointsprogrammableforslow

    trip,interruptiondutythreshold,oroperationscounter -Tripcircuitvoltageandcontinuitymonitor

    -ClosecircuitmonitorviaBESTlogic

  • 7/28/2019 BE1-IPS100bull9

    3/12

    BE1-IPS

    APPLICATIONSTheBE1-IPS100IntertieProtectionSystemprovidesthreephase,ground,andnegativesequenceovercurrent,voltage

    andfrequencyprotection,includingdirectionalpower,andisintendedforuseinintertieapplicationscoveredbyIEEE1547oranydirectionalornon-directionalovercurrentprotectionapplication.Itsuniquecapabilitiesmakeitideallysuitedforapplicationswiththefollowingrequirements:

    Intertieprotectionatthepointofcommoncoupling(PCC)betweennon-utilitydistributedgeneration(DG)andtheelectricutility/AreaElectricPowerSystem(AreaEPS).

    Underfrequencyloadshedapplicationssupervised,ortrippeddirectly,by"True"RateofChangefrequency.ApplicationsthatrequirelowburdentoextendthelinearrangeofCTs. Applicationsthatrequirehighaccuracyacrossawidefrequencyrangesuchasformotor,generator,andgenerator

    step-uptransformerprotectionorinintertiefacilities. Applicationsthatrequiretheexibilityprovidedbywidesettingranges,multiplesettinggroups,andmultiple

    coordinationcurvesinoneunit. Applicationsthatrequiretheeconomyandspacesavingsprovidedbyacompactmultifunction,multiphaseunit.This

    oneunitcanprovidealloftheprotection,control,metering,andlocalandremoteindicationfunctionsrequiredonatypicalcircuit.

    Applicationsthatrequiredirectionalcontrolwithcontinuouslyadjustableangleofmaximumtorque. Applicationsthatrequirefaultlocating. Transformerbackupapplicationswhereoverexcitationprotectionisrequired. Applicationsthatrequirecommunicationsandprotocolsupport. Applicationswherethecapabilitiesofadigitalmultifunctionrelayarerequired,yetdrawoutconstructionalsois

    desirable. Applicationswherebusprotectionisprovidedbyahighspeedovercurrentblockingschemeonthetransformerbus

    mainsinsteadofadedicatedbusdifferentialcircuit. Applicationswherethesmallsizeandlimitedbehind-panelprojectionfacilitatesmodernizingprotectionandcontrol

    systemsinexistingsubstationsorequipment. ApplicationsusingEthernetcommunication,programmableemailnotications,andlivemeteringinformationviaan

    embeddedwebserver(withBESTNetoption).

    ApplicationsrequiringModbus/TCPEthernetcommunications(withModbus/TCPoption).

    FEATURES, continued

    Figure 1 - HMI (Human Machine Interface)

    PROGRAMMABLE I/O Fourprogrammableinputs

    Fiveprogrammableoutputsandonededicated

    programmablealarmoutput

    HARDWARE FEATURES Casecongurations

    -S1:Doubleended,Basler/GEstyle(withtestplugs)

    ActiveCTtechnologyforlowburdenandincreaseddynamicrange

    FlashMemoryforupgradingembeddedprogrammingwithoutchangingchips

    RealTimeClockwith8hourcapacitorridethroughandoptionalbatterybackup

    IntegralHMIwith2x16characterdisplay

    Widerangeac/dcpowersupplyoptionsprovidelongholduptimetoridethroughdipsonacpowersource.

    (100mswith4outputrelaysenergized,uponcompletelossofsource.

  • 7/28/2019 BE1-IPS100bull9

    4/12

    E1-IPS100

    FUNCTIONAL DESCRIPTIONTheBE1-IPS100isamultifunction,numericrelaysystemthatprovidesacomprehensivemixofprotectivefunctions(IEEE1547compliant)todetectfaultsandabnormaloperatingconditionsattheintertiepoint(PCC)betweenaDGandanelectric

    utility,alongwithcontrolandmeteringfunctions,inanintegratedsystem.Additionalfeaturessuchassingleorthreephasedualforward/reverseover/underpower(32/132),dualover/undervoltage(27/59P,127/159P),sixover/under/rateofchangefrequencyelements(81,181...581),alongwithdualmodedirectionaltimeovercurrent,directionalinstantaneousovercurrentprotection,andsynccheckreclosewithvoltageconditionsmakethisproductidealforintertieapplicationsondistributionandsubtrans-missionsystems.Otherprotectionapplicationswouldincludefeeder,transformer,generator,bus,andloadshedding.Twelvesamplepercycledigitalsignalpro-cessingwithfrequencycompensationextractsthefun-damental

    componentforhighaccuracywithdistortedwaveformsandatoff-nominalfrequencyoperation.

    Theunithasonesetofthreephasecurrentandvoltagesensinginputstoprovideallcommonpro-tectivefunctionsforsubstationandfeederapplications.Thevoltagesensingcircuitsareconguredinternallyfor1phase,3phase3wire,or3phase4wireVTcircuits.

    TheBE1-IPS100alsocanbeorderedwithanoptionalindependentgroundcurrentinput,typicallyusedforapplicationwithaseparategroundCTsuchasauxbalancingwindowCT,ortoprovidegroundbackup

    protectionfortheneutralortertiaryofatransformer.

    ThefourthAuxiliaryVoltageinputcanbeconnectedtolinesidepotentialforsynccheck(25)anddeadline(25VM)closingsupervisionortoagroundsensingVTconnectionforgroundfaultprotectiononthedeltasideofacogenerationintertietransformer.

    Fordirectionalapplications,allovercurrentelementscanbeindependentlysetforforward,reverse,ornon-directionalcontrol.Fordirectionalapplications,allovercurrentelementscanbeindependentlysetforforward,reverse,ornondirectionalcontrol.Note:If51Pissetdirectional,asecondpickuplevel(151P)canbe

    set.The151PincludesseparateusersettingsforPU,TD,andcurve,buttripdirectionisxedoppositethe51P.SeetheIPS100instructionmanual,Section4,fordetails.ThetargetreportingfunctionintheBE1-IPS100automaticallyadaptsthetargetsasappropriate.Forexample,ifthe150TPandthe51Pfunctionsaresetfordirectionalcontrol,theyposttargetsforanAphasefaultas167Afordirectionalinstantaneoustripor"67TA"fordirectionaltimetriprespectively.Directionalcontrolisbysequencedirectionalelements.Thezerosequencecurrentpolarizedelementusestheoptionalindependentgroundinputforitspolarizationsignal.ThezerosequencevoltagepolarizedelementrequiresthattheVTconnectionbe4W.Thepositivesequence

    directionalelementhasmemoryvoltagetoprovidereliabledirectionalcontrolforcloseinbalancedthreephasefaults.Themaximumtorqueangles,normallyderivedfromthepositive/negativeandzerosequencelineimpedances,arecontinuouslyadjustablebetween

    0and90degrees.

    Threeindependentcommunicationsportsprovideeasyaccesstointegratingtheprotection,control,metering,andstatusmonitoringfunctionsintoasubstationautomationsystem.COM1isfrontRS-232ASCII;COM2isRS-485withModbusTMorDNP;COM3isRS-232orethernetwithBESTNetorModbusTM/TCP.ThestandardIRIG-Bportcanprovidetimesynchronizationfromamasterclock.

    RealtimemeteringprovidesWatt,Watt-hour,VAR,VAR-hour,voltage,amp,andunbalanceloadingtelemetryfortheprotectedcircuit.Contactsensing

    inputsandalarmmonitoringfunctionsproviderealtimestatusinformation.Remotecontrolisprovidedbyvirtualcontrolandselectorswitcheswithselect-before-operatecontrolofprogrammableoutputs.

    BESTlogicBESTlogicprogrammablelogicprovidestheuserwithhighexibilityinconguringaprotectionandcontrolsystem.

    EachoftheprotectionandcontrolfunctionsintheBE1-IPS100isimplementedasanindependentfunctionblockthatisequivalenttoitssinglefunction,

    discretedevicecounterpart.Eachindependentfunctionblockhasalltheinputsandoutputsthatthediscretecomponentcounterpartmighthave.Figures6Aand6BshoweachoftheindependentfunctionblocksavailableforuseintheBE1-IPS100.ProgrammingBESTlogicisequivalenttochoosingthedevicesrequiredbyyourprotectionandcontrolschemeanddrawingschematicdiagramstoconnecttheinputsandoutputstoobtainthedesiredoperationallogic.

    TheBE1-IPS100relaycanstore,asusersettings,oneuserprogrammable,customlogicscheme.Tosaveyoutime,apreprogrammedintertielogicschemehasalsobeenprovided.Thepreprogrammedschememay

    becopiedintothelogicsettingwithoutmakinganyadditionalBESTlogicsettingsorcanbemodiedtomeettheuser'sneeds.

    BESTlogicprovidestheprotectionengineerwiththeexibilitytosetupthispowerfulmultifunctionsystemwiththesamefreedomthatwasonceenjoyedwithsinglefunction,discretedevices.Itisnolongernecessarytocompromiseyourstandardprotectionandoperatingpracticestodealwiththelimitationsinprogrammabilityofpreviousmultifunctiondevices.

    Figures2A,2Band3showtypicalexternalconnections,andFigure5showsrearpanelconnections.

  • 7/28/2019 BE1-IPS100bull9

    5/12

    BE1-IPS

    Figure 2A - Typical External Sensing Connections - Intertie Protection Application

    FUNCTIONAL DESCRIPTION, continued

    Figure 2B - Typical Alternate Connections for Vx

    and IG

    Figure 3 - Typical External Connections

  • 7/28/2019 BE1-IPS100bull9

    6/12

    E1-IPS100

    FUNCTIONAL DESCRIPTION, continued

    Figure 4 - Typical Application Single Line Figure 5 - S1 Double-ended Case,Rear Panel Connections (shown with Ethernet port)

  • 7/28/2019 BE1-IPS100bull9

    7/12

    BE1-IPS

    GENERAL SPECIFICATIONS5 Amp CURRENT INPUTS

    Continuousrating: 20A OneSec.Rating: 400A

    Saturationlimit: 150A Burden:

  • 7/28/2019 BE1-IPS100bull9

    8/12

    E1-IPS100

    Figure 6A - BESTlogic Function Blocks

  • 7/28/2019 BE1-IPS100bull9

    9/12

    BE1-IPS

    Figure 6B - BESTlogic Function Blocks

  • 7/28/2019 BE1-IPS100bull9

    10/12

    E1-IPS100

    0

    PERFORMANCE SPECIFICATIONS

    INSTANTANEOUS OVERCURRENT WITH

    SETTABLE DELAY (50TP, 150TP, 50TN, 150TN,50TQ, 150TQ)

    Pickup: 5ACT 0.5-150.0A 1ACT 0.1-30.0A

    PUtimewithTD=0.000Sec 2cycforP,NandG@5xPU

    3cycforQ@5xPU Delaytime: 0.00-60sec TimeAccuracy: 0.5%or cycforPandN

    0.5%or1cycforQ

    TIME OVERCURRENT (51P, 151P, 51N, 151N, 51Q)

    Note:151Pisnotaphaseovercurrentelement.It

    isasecondsettingforthe51Pelement,whensetdirectional.Tripdirectionofthe151Pisxedoppositethe51P.SeeInstructionManualfordetails.

    Pickup: 5ACT 0.5-16.0A 1ACT 0.1-3.20A

    Timedial: TD=K=0-99for46curve TD=0.0-9.9forallothercurves

    Time-CurrentCharacteristics: Thefollowingexpressiondescribestheinverse timecurrentcharacteristicforeachcurve:

    TT=AD+BD+K=Timetotrip

    MN-C

    TR

    =RD=TimefordecayingresetM2-1

    whereD=Timedial,M=MultipleofPUandA,B,

    C,N,KandRareconstantsthatgoverntheshape ofeachcurve.Theprotectionengineercansetthe

    constantsfortheP(programmable)curveto achievevirtuallyanycharacteristic.

    51P VOLTAGE CONTROL (27R) ControlModes: Uncontrolled,voltage

    controlled,voltagerestrained. Control/RestraintRange: 30-250V

    RestrainedModeCharacteristic:(seebelow)

    CurveType

    Constants

    A B C N K RS1 0.2663 0.03393 1.000 1.2969 0.028 0.5000

    S2 0.0286 0.02080 1.000 0.9844 0.028 0.0940

    L1 5.6143 2.18592 1.000 1.000 0.028 15.750

    L2 2.3955 0.00000 1.000 0.3125 0.028 7.8001D 0.4797 0.21359 1.000 1.5625 0.028 0.8750

    M 0.3022 0.12840 1.000 0.5000 0.028 1.7500

    I1 8.9341 0.17966 1.000 2.0938 0.028 9.0000

    I2 0.2747 0.1042 1.000 0.4375 0.028 0.8868

    V1 5.4678 0.10814 1.000 2.0469 0.028 5.5000

    V2 4.4309 0.0991 1.000 1.9531 0.028 5.8231

    E1 7.7624 0.02758 1.000 2.0938 0.028 7.7500

    E2 4.9883 0.0129 1.000 2.0469 0.028 4.7742

    A 0.01414 0.00000 1.000 0.0200 0.028 2.0000

    B 1.4636 0.00000 1.000 1.0469 0.028 3.2500

    C 8.2506 0.00000 1.000 2.0469 0.028 8.0000

    G 12.1212 0.00000 1.000 1.0000 0.028 29.0000

    F 0.0000 1.00000 0.000 0.0000 0.028 1.0000

    46 * 0.00000 0.000 2.0000 0.028 100.0000

    P 0to600 0 to25 0to1 0.5to2.5 0.028 0to30

    S1, S2 =COShortInv,IACShortInv A=IECStandardInverse

    L1, L2 =COLongInv,IACLongInv B=IECVeryInverse

    D=CODeniteTime C =IECExtremelyInverse

    M=COModeratelyInverse G=IECLongTimeInverse

    I1, I2=COInverse,IACInverse F=FixedTime

    V1, V2=COVeryInv,IACVeryInv 46=NegativeSequenceOvercurrent

    E1, E2=COExtInverse,IACExt.Inverse P=Programmable

    * ConstantAisvariableforthe46curveandisdeterminedasnecessarybasedonsystem fullloadcurrentsetting,minimumpickup,andKfactorsettings.

    DIRECTIONAL CONTROL (ALL OVERCURRENT)

    Mode: Forward,Reverse, Nondirectional 67PPolarization: PositiveSequencew/Memory

    NegativeSequence 67QPolarization: NegativeSequence

    67NPolarization: Selectableanycombination: ZeroSequenceVoltage

    NegativeSequenceVoltageZeroSequenceCurrent

    (RequiresIG) BREAKER FAILURE (BF)

    Time: 50-999mSec Dropout: 5ACT 0.5A

    1ACT 0.1A

    TimeAccuracy: 0.5%or+1cyc/- cyc

    VOLTS/HZ (24)

    Inverse Time: Range:0.5to6V/Hz

    Accuracy:2% InverseTimeCurves:(M-1)2,(M-1)1,(M-1)0.5

    TimeDial:0.0to9.9V/Hz IntegratingTimeDelayReset

    ResetDial:0.0to9.9V/Hz Accuracy:5%or4cycles,whicheverisgreater Defnite Time #1 and #2, and Alarm:

    Range:0.5to6V/Hz TimeDelay:0.05secondto600seconds

    Accuracy:0.5%or3cycles,whicheverisgreater

  • 7/28/2019 BE1-IPS100bull9

    11/12

    BE1-IPS

    PERFORMANCE SPECIFICATIONS, continued

    Sync Check (25) DeltaPhaseAngle: 1-99degrees DeltaVoltageMagnitude: 1-20V DeltaFrequency: 0.01-0.50Hz

    Sync Check, Voltage Monitor (25VM) DeadThreshold: 10-150V LiveThreshold: 10-150V DropoutTimeDelay: 0.05-60.0sec Logic: DeadPhase/DeadAux.

    DeadPhase/LiveAux. LivePhase/DeadAux.

    Phase Over/Undervoltage (27P, 59P, 127P, 159) Mode: 1of3;2of3;3of3 Pickup: 10.0-300V

    L-Lor10.0-300V

    L-N

    DelayTime: 0.050-600sec.

    27P/127PUVInhibit:10-300VAC

    Negative Sequence Overvoltage(47) Pickup: 1.0-300V

    L-N

    DelayTime: 0.05-600sec.

    Auxiliary / 3V0 Over/Undervoltage(27X, 59X, 159X)

    Mode: FundamentalVX,

    3phaseResidual(3V0), 3rdHarmonicV

    X

    Pickup: 1.0-150V DelayTime: 0.05-600Sec.

    27XUVInhibit: 1.0-150VAC

    Power (32/132) Mode: 1of3;2of3;3of3;Total Operationdirection: ForwardorReverse,Overor Under Pickup: 5A:1.0-6000Watts,3ph 1A:1.0-1200Watts,3ph PickupAccuracy: 3%

    DelayTime: 0.05-600Sec.

    General Purpose Logic Timers (62, 162) Mode: PU/DO,1Shot,Non-Retrig. 1Shot,Retrig. IntegratingLatch T1andT2DelayTime:0.00-9999Sec.

    TimeAccuracy: 0.5%orcyc

    Recloser (79) Mode: Poweruptoclose, Poweruptolockout RecloseShots: 0-4 Reclose,Reset,Fail, Max.CycleTimers: 0.100-600Sec.

    TimeAccuracy: 0.5%or+1cyc/-0cyc

    Current Pickup Accuracy (All 50 and 51) PhaseandGround: 5A 2%or50mA 1A2%or10mA

    NeutralandNegative 5A3%or75mA Sequence: 1A3%or75mA

    Voltage Pickup Accuracy (All 27, 47 and 59) Phase(V

    L-LorV

    L-N): 2%or1Volt

    Phase3V0andV2: 2%or1Volt

    Defnite Time Accuracy Unless Otherwise Stated

    (All 27, 47 and 59) DeniteTimeAccuracy: 0.5%or+3.6/-1.9 cycles,whichever isgreater

    Setting Groups SettingGroups: 2 ControlModes: Automatic:CLP;Dynamicload orunbalance.External:Discrete

    inputlogic;Binary:InputLogic

    Metering CurrentRange: 5A 0.5to15.0 1A 0.1to3.0

    CurrentAccuracy: 1% PhaseVoltageRange:3W 0-300V

    L-L

    4W 0-300VL-L

    PhaseVoltage

    Accuracy: 0.5%for50V

  • 7/28/2019 BE1-IPS100bull9

    12/12

    E1-IPS100

    ORDERINGSAMPLE STYLE NUMBER

    Thestylenumberidenticationchartdenestheelectricalcharacteristicsandoperationfeaturesincludedin

    BE1-IPS100relays.Forexample,ifthestylenumberwereBE1-IPS100E4A1C0Y,thedevicewouldhavethe

    following: BE1-IPS100

    (E) - 5Ampnominalsystemwith5AmpIndependentGroundInput

    (4) - Threephasevoltagesensingwithindependentaux.input (A) - S1coverwithopeningforHMIaccess

    (1) - 48/125Vac/Vdcpowersupply (C) - DoubleendedS1drawoutcase,normallyopenalarm

    (0) - ASCIIoverRS-485,noEthernet (Y) - 4000pointDataArray

    STANDARD ACCESSORIES9334818100 BatteryBackupReplacementKit(if"U"or"W"ischosenforOption1).

    Figure 7BCover option B.

    www.basler.com

    12570 State Route 143, Highland, Illinois 62249-1074 USATel +1 618.654.2341 Fax +1 618.654.2351

    e-mail: [email protected]

    No. 59 Heshun Road Loufeng District (N),Suzhou Industrial Park, 215122, Suzhou, P.R.China

    Tel +86(0)512 8227 2888 Fax +86(0)512 8227 2887e-mail: [email protected]

    P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCETel +33 3.88.87.1010 Fax +33 3.88.87.0808

    e-mail: [email protected]

    111 North Bridge Road #15-06 Peninsula PlazaSingapore 179098

    Tel +65 68.44.6445 Fax +65 65.68.44.8902il i i f @b l

    Figure 7ACover option A.