Model EAC Enclosure Air Conditioners Class I, Division 2, Group B 2,000-24,000 BTUH Capacity Units ECU Division Technical Bulletin EAC TSB-R3 08.2011 Copyright © 2011, All Rights Reserved www.okbebco.com 1.800.OKBEBCO 4725 Lawndale • La Marque, Texas 77568 Product Application Bebco Model EAC Enclosure Air Conditioners provide 2,000-24,000 BTUH of cooling and 1,000- 1,500 Watts of optional heating for enclosures, consoles or cabinets in harsh environments. The Units meet or exceed all National Electric Code requirements for use in Class I, Division 2, Group B, C & D Hazardous Locations; and they are provided with single phase 120, 230 and 480 VAC, 60 Hertz power options. Typical applications include pressurized and unpressurized enclosures containing electrical, pneumatic or analytical equipment where one or more units can work alone, in tandem or redundancy to provide required cooling force. Units may feature a commercial grade powder coated steel or industrial grade brushed stainless steel case and coated coils. These options make Bebco Model EAC Units suitable for a wide range of industrial environments, ranging from petrochemical refineries and manufacturing facilities to highly corrosive atmospheres, such as those encountered in water treatment, h 2 s sour gas units and offshore oil and gas platforms. Narrow profiles permit installation on the side of an enclosure, which is especially practical for enclosures with limited space. These units provide effective recirculating air cooling solutions in hazardous locations. They can also provide nominal heating solutions when used in conjunction with an enclosure pressurization unit that complies with all requirements of the USA National Electric Code (NEC) Standard NFPA 496 for Pressurized Enclosures. A Temperature Controller or Switch permits fast and easy adjustment of cooling, heat and alarm setpoints! See page 4 for ordering information 10,000 BTUH Unit with Stainless Steel Case, Explosion-Proof Controls & Explosion-Proof Thermostat 2,000 BTUH Unit with Powder Coated Steel Case, Encapsulated Controls & Sealed Temperature Controller LISTED 5,000, 6,000 & 8,000 BTUH Units are Room Air Conditioners For Use in Hazardous Locations UL File Number 183596 UL Control Number 8R89 Temperature Code T5 Look for the UL Label!

Upload: buinhi

Post on 21-Mar-2018

232 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Bebco Model EAC Enclosure Air Conditioners Enclosure · PDF fileModel EAC Enclosure Air Conditioners may also be specified with 1,000 BTUH or 1,500 BTUH ... 480 VAC Units feature isolated

Model EACEnclosure Air Conditioners

Class I, Division 2, Group B2,000-24,000 BTUH Capacity Units

ECU Division Technical Bulletin EAC TSB-R3 08.2011

Copyright © 2011, All Rights Reserved www.okbebco.com 1.800.OKBEBCO 4725 Lawndale • La Marque, Texas 77568

Product Application Bebco Model EAC Enclosure Air Conditioners provide 2,000-24,000 BTUH of cooling and 1,000-1,500 Watts of optional heating for enclosures, consoles or cabinets in harsh environments.

The Units meet or exceed all National Electric Code requirements for use in Class I, Division 2, Group B, C & D Hazardous Locations; and they are provided with single phase 120, 230 and 480 VAC, 60 Hertz power options.

Typical applications include pressurized and unpressurized enclosures containing electrical, pneumatic or analytical equipment where one or more units can work alone, in tandem or redundancy to provide required cooling force.

Units may feature a commercial grade powder coated steel or industrial grade brushed stainless steel case and coated coils. These options make Bebco Model EAC Units suitable for a wide range of industrial environments, ranging from petrochemical refineries and manufacturing facilities to highly corrosive atmospheres, such as those encountered in water treatment, h2s sour gas units and offshore oil and gas platforms.

Narrow profiles permit installation on the side of an enclosure, which is especially practical for enclosures with limited space.

These units provide effective recirculating air cooling solutions in hazardous locations. They can also provide nominal heating solutions when used in conjunction with an enclosure pressurization unit that complies with all requirements of the USA National Electric Code (NEC) Standard NFPA 496 for Pressurized Enclosures.

A Temperature Controller or Switch permits fast and easy adjustment of cooling, heat

and alarm setpoints!See page 4 for ordering information

10,000 BTUH Unit withStainless Steel Case,

Explosion-Proof Controls & Explosion-Proof Thermostat

2,000 BTUH Unit withPowder Coated Steel Case,Encapsulated Controls &

Sealed Temperature Controller

LISTED

5,000, 6,000 & 8,000 BTUH Units are

Room Air Conditioners ForUse in Hazardous Locations

UL File Number 183596UL Control Number 8R89

Temperature Code T5

Look for theUL Label!

Page 2: Bebco Model EAC Enclosure Air Conditioners Enclosure · PDF fileModel EAC Enclosure Air Conditioners may also be specified with 1,000 BTUH or 1,500 BTUH ... 480 VAC Units feature isolated

ECU EAC TSB-R3 Page 2

Model EAC Units are constructed to be easily serviceable and extremely robust...

Unit Features & OptionsUnit cases are available in 14 gauge powder coated carbon steel or brushed 316 stainless steel. The case supports the electrical and temperature controls, forms a corrosion resistant shroud, insulates the evaporator compartment, and ventilates the condenser compartment.

All cases feature an externally mounted standard 1” thick or severe duty 2” thick air filter to prevent contamination of the condenser coil.

Chassis are fabricated from galvanized steel and aluminum sheet metal. They form a sealed barrier between the evaporator and condenser compartments, and also provide a mounting surface for attachment to the cooled enclosure.

The refrigerant coils and all refrigerant tubing may be fully coated for maximum corrosion resistance upon specification.

All 2,000 to 15,000 BTUH units utilize R422d Refrigerant and 20,000 & 24,000 BTUH units utilize R438a Refrigerant for CFC free operation.

The evaporator coil drain pan and the heated condensate evaporation pan at the unit base are formed from seal-welded aluminum. The evaporation pan removes all condensate water within the unit housing.

All evaporator and condenser fan blades are formed from corrosion resistant thermoplastic or aluminum to provide spark-free operation in accordance with NEC Hazardous Location ventilation fan design requirements.

As required, the coil fan motors are protected by hermetically sealed thermal overloads, and all electrical equipment meets all requirements for Class I, Division 2, Group B, C & D Hazardous Locations.

Electrical controls are housed in an encapsulated enclosure or NEMA 7 explosion proof enclosure. Temperature control is achieved by a sealed temperature transmitter or switch.

Model EAC Enclosure Air Conditioners may also be specified with 1,000 BTUH or 1,500 BTUH Heating Elements to provide enclosure heating.

SPECIAL NOTICE When heating elements are specified, the cooled enclosure must be protected by a

pressurization system that complies with all requirements of NFPA 496.

1 Air Conditioner Chassis 2 Evaporator Coil 3 Thermal Expansion Valve 4 Evaporator Coil Drain Pan 5 Condensate Drain Tubing 6 Wiring Harness Connectors 7 Compartment Barrier 8 Condenser Coil 9 Condenser Coil Fan 10 Sealed Pressure Sensors 11 Rotary Compressor & Capacitor 12 Heated Condensate Evaporation Pan 13 Evaporator Coil Fan & Power Wiring 14 Return Air Duct 15 Condenser Coil Air Filter

Bebco Industries, Incorporated © 2011

1

2

34

5

6

7

9

10

11

12

Control wiring connectors allow case removal for

full service access!

Rear Views

13

14

8

15

8

Page 3: Bebco Model EAC Enclosure Air Conditioners Enclosure · PDF fileModel EAC Enclosure Air Conditioners may also be specified with 1,000 BTUH or 1,500 BTUH ... 480 VAC Units feature isolated

Model EAC Units are manufactured with superior materials and components...

Component SpecificationsUnit Cases: Powder Coated Carbon Steel or 316 Brushed Stainless SteelCase Insulation: Closed Cell UrethaneChassis & Brackets: Galvanized Steel & AluminumChassis Gaskets: Neoprene & Butyl RubberCondensation Pans: Seal-Welded AluminumCondensation Drains: Polyurethane & NylonRefrigerant Coils: Copper Tubing w/ Aluminum FinsRefrigerant Lines: Copper TubingService Ports: BrassCoil & Tube Coating: PPG Power Crown 8000Tubing Insulation: ASTM E-84 Elastometric2-8K Unit Motors: TENV Cast Aluminum10-24K Unit Motors: ODP Steel w/ Aluminum End Plate2-8K Unit Fan Blades: Thermoplastic Axial Blade10-24K Unit Fan Blades: Aluminum Tangential Blade Compressor Cases: Seal Welded Carbon SteelCompressor Construction: Rotary StyleNameplates: Stainless Steel & Lexan ®Electrical Control NEMA 7 Cast Aluminum orEnclosures: Encapsulated Polyurethane EnclosureTemperature NEMA 4 Epoxy Coated Aluminum CaseSwitch Housings: w/ Polycarbonate Face PlateTemperature NEMA 4 Polyurethane CaseController Housings: & Retainer w/ Lexan ® Face PlateFasteners: Stainless Steel & Zinc Plated SteelAir Filters: PVC Media w/ Anodized Aluminum FrameMotor & Compressor Finishes: Epoxy Paint

Lexan® is a registered trademark of the General Electric Corporation

Basic Electrical SpecificationsAlarm Contacts: Form C 10 Amps @ 250 VAC480 VAC Transformers: 0.75-3 KVA w/ Copper WindingsPressure Switches: Copper Body w/ Stainless ContactsUnit Wiring: THHN & TWN 600 VAC RatedMotor & CompressorThermal Overloads: Hermetically Sealed

Documentation & HardwareAll Units are furnished with the following materials:One (1) Installation, Operation & Maintenance ManualOne (1) Full Size Unit Installation Cutout TemplateOne (1) Unit Wiring Diagram One (1) Set of Zinc-Plated Enclosure Fastener Bolts

Please see our Installation & Operation Manual for more information!

Bebco Industries, Incorporated © 2011 ECU EAC TSB-R3 Page 3

Unit Ampacity Requirements All Units Require Single Phase 60 Hertz Power

Size BTUH 120 VAC 230 VAC 480 VAC020 2,000 3.76 3.07 0.93030 3,000 5.15 3.07 1.51040 4,000 5.53 3.07 1.51050 5,000 7.26 3.76 1.50060 6,000 7.83 4.80 1.44080 8,000 7.83 4.80 1.80100 10,000 16.3 8.90 4.12120 12,000 16.3 8.90 4.12155 15,000 n/a * 8.5 5.08200 20,000 n/a * 11.3 5.85240 24,000 n/a * 14.4 7.20

* 155, 200 & 240 Units not available with 120 VAC Power

Maximum Temperatures Dimensions & Weights (in lbs)

Minimum Operating Temperature: -40°FSize Voltage Temp H x W X D* Weight020 120 & 230 131°F 32" x 11.8" x 9.5" 86.5020 480 131°F 37.71" x 11.8" x 9.5" 126.5030 120 & 230 131°F 32" x 11.8" x 9.5" 86.5030 480 131°F 37.71" x 11.8" x 9.5" 126.5040 120 & 230 131°F 32" x 11.8" x 9.5" 86.5040 480 125°F 37.71" x 11.8" x 9.5" 126.5050 120 & 230 125°F 36" x 11.8" x 15.1" 116.5050 480 125°F 44.63" x 11.8" x 15.1" 156.5060 120 & 230 125°F 36" x 11.8" x 15.1" 116.5060 480 125°F 44.63" x 11.8" x 15.1" 156.5080 120 & 230 125°F 36” x 11.8” x 15.1” 116.5080 480 125°F 44.63" x 11.8" x 15.1" 156.5100 120 & 230 125°F 48" x 15.86" x 15.03" 161.5100 480 125°F 57.62" x 15.86" x 15.03" 221.5120 120 & 230 125°F 48" x 15. 86" x 15.03" 161.5120 480 125°F 57.62" x 15.86" x 15.03" 221.5155 230 125°F 48" x 15.86" x 15.03" 161.5155 480 125°F 57.62" x 15.86" x 15.03" 221.5200 230 125°F 56.09" x 23" x 15" 202.5200 480 125°F 65.72" x 23" x 15.03" 251.5240 230 125°F 56.09" x 23" x 15" 202.5240 480 125°F 65.72" x 23" x 15.03" 251.5* Dimensions above indicate width and depth of Unit Case

Add 2.5” to Width dimension for 2 Inch Thick Filter. Add 4.5" to Depth dimension for Encapsulated Controls.

Add 6.6" to Depth dimension for Explosion Proof Controls.480 VAC Units feature isolated compartment for power transformer.

Quality components assure years of maintenance-free operation!

To back it up, Bebco offers the Industry’s best Two Year Service Warranty!Please contact Bebco now for more information!

Page 4: Bebco Model EAC Enclosure Air Conditioners Enclosure · PDF fileModel EAC Enclosure Air Conditioners may also be specified with 1,000 BTUH or 1,500 BTUH ... 480 VAC Units feature isolated

A wide range of options make Model EAC Units the most innovative solution on the market...

4725 Lawndale, La Marque, Texas 77568Phone: 409.935.5743 or 1.800.OKBEBCO (1.800.652.3226)

Fax: 409.938.4189 e-mail: [email protected]

ECU EAC TSB-R3 Page 4 Bebco Industries, Incorporated © 2011

Local Area Representative

Model Number DesignationsCX - EAC - 040 - A - 22 - EA - 1T - X1 - XX

1 - CASE STYLECX Commercial Grade Powder Coated Carbon SteelIX Industrial Grade Brushed Stainless Steel

2 - PRODUCT SERIESEAC Enclosure Air Conditioner

3 - BTUH RATING 020 2,000 060 6,000 155 15,000 * 030 3,000 080 8,000 200 20,000 * 040 4,000 100 10,000 240 24,000 *050 5,000 120 12,000

4 - OPERATING VOLTAGE A 120 VAC B 230 VAC C 480 VAC

5 - COMPARTMENT CLASSIFICATION RATING ** 1st Digit - Evaporator 2nd Digit - CondenserG General Purpose G General Purpose2 Division 2 2 Division 2 050, 060 & 080 BTUH Rated Units with "22" Compartment Classification Ratings are UL Listed, w/ exception to 050 BTUH Rated Units w/ 120 VAC Operating Voltage.

* 155, 200 & 240 BTUH Rated Units are not available with 120 VAC Operating Voltage.

** Compartment Classification Ratings denote Hazardous Location suitability. Evaporator compartment is sealed to the enclosure and condenser compartment is vented to the surrounding atmosphere.

Please see SPECIAL NOTICE on Page 2 for more information.

6 - CONTROL HOUSING & CONTROLLER SETPOINTS 1st Digit - Housing 2nd Digit - Setpoints *** N NEMA 7 X Cooling Setpoint OnlyE Encapsulated A Cooling & High Temp Alarm H Cooling & Heating Element

7 - LOW AMBIENT CONTROL, COIL & TUBE COATING 1st Digit - Control 2nd Digit - Coating 0 No Control X No Coating 1 Low Ambient Control C Coil Coating T Coil & Tube Coating

8 - UNIT VIBRATION & CONDENSER COIL INLET AIR FILTER 1st Digit - Vibration 2nd Digit - Filter X No Resistance 1 Standard V Full Resistance 2 High Capacity

9 - GRILL STYLE & CASE FINISH 1st Digit - Filter Grill 2nd Digit - Finish X Standard (open) X Standard (see case style)A Armored (indoor) C Custom Finish **** L Louvered (outdoor) *** "H" denotes output to activate auxiliary heater units which mount in enclosure and may be purchase separately at time of order.

Heaters provide 500, 1,000 or 1,500 Watts of convection heat and require separate 120 VAC or 240 VAC Power Source.

**** Please specify custom finish in writing at time of order.

1 2 3 4 5 6 7 8 9Typical Model Number:Applicable Segment:

2,000 to 4,000 BTU 5,000 to 8,000 BTU 10,000 to 24,000 BTU Remote UnitConfigurations UnitConfigurations UnitConfigurations AlarmDevices

America’s most versatile, compact, well-engineered and fully warranted hazardous location enclosure air conditioners, from a name you trust.Call now to learn more!

See all Accessories on our Website!

High Temperature Warning Nameplates

All rights reserved. All specifications subject to change without notice. Product Warranty & Liability policies available upon request.

Disconnect&AlarmSwitches