GeniSys™ 7505 120V Oil Burner ControlPart 2

September 2, 2020

Beckett Online Training | Series 3: Beckett Controls | Session 2

Page 2: Beckett Online Training | Series 3: Beckett Controls

OilPrimaries

OilIgniters

Gas Ignition & Control

AquaSmart

12 VDC

24 VDC

120 Potted

240 Potted

120 Volt

12 VDC24 VDC

240 Volt

120 Volt 120/24 Volt

Outdoor Reset

7590 Gas Control

120 Volt Gas ignitor

Beckett Family of Controls

7586 Intermittent Pilot Gas Control

Page 3: Beckett Online Training | Series 3: Beckett Controls

Series Overview

• Basic Features of the GeniSys 7505 Primary Control.• Model Designation, Installation and Wiring for

Proper Operation.• Understanding the Sequence of Operation.• Resetting the Control from a Safety Lock-out Condition.• The 4 Minute Pump Prime Feature.• Viewing and Reading the 15 cycles of History for

Advanced Diagnostics.

• Field wiring of the 7505 Oil Burner Primary Control for Pre- Purge and Post Purge.

• Why a CleanCut Fuel Pump or solenoid valve is required when programming for Pre-Purge and Post Purge.

• Learn how to set the purge features using the 4 keys on the Contractor tool.

• 7610 Features and Benefits.• Warm and Cold Start Boiler Operation.• Freeze Up Protection.• Easy Programming of the Aquasmart Control.• Reset Information Including:• Heat Manager (Indoor Reset)• Circulators On and Off Delays for Purging the system• Outdoor Temperature Reset

• 7590 Features and Benefits• Various Models Available• Status and Diagnostics LED’S• Flame Supervision• Air Pressure Switch Monitoring• 7590 Important Terms• Auto Retry Feature• Beckett Link Configuration and Diagnostics Tool

Module 1

Module 2

Module 3

Module 4

Page 4: Beckett Online Training | Series 3: Beckett Controls

Class OverviewUpon completion of this web-based instruction module you should be able to:

Set the pre-purge and post-purge on the Genisys Control utilizing the Contractor Tool

Please feel free to submit questions after the end of each session

Page 5: Beckett Online Training | Series 3: Beckett Controls

GeniSys Electronic Primary

Finally-a universal control that saves time, control inventory and delivers on the promise of:

GeniSys Control

“Technology made simple”

Page 6: Beckett Online Training | Series 3: Beckett Controls

GeniSys Display Service Tool

52082 display provides a sealed pushbutton keypad for control interface:• Customizable pre-time • (valve on delay)

• Customizable post-time • (motor off delay)

• Allows navigation through current & historical data • 32-character backlit alphanumeric display

Page 7: Beckett Online Training | Series 3: Beckett Controls

• Low voltage operation

• Continuous real-time cycle monitoring

• Continuous cad cell resistance reading

• Continuous AC line voltage readout

• Real-time error notification

• 15 cycle history monitoring

• 18- month warranty

• Customizable lockout service message

CALL FOR SERVICE1 800 645 2876

CALL FOR SERVICE1 800 645 2876

GeniSys Display Service Tool

Page 8: Beckett Online Training | Series 3: Beckett Controls

Two communication ports for add-on modules.

GeniSys Control

Page 9: Beckett Online Training | Series 3: Beckett Controls

Basic FeaturesRecessed wiring terminals

• Saves room in wiring box

• Fewer pinched wires

• Easy removal

• Shipped with pigtails and spade flag terminals

• Room to use typical straight insulated spade terminals

Wiring terminals recessed inside case

Page 10: Beckett Online Training | Series 3: Beckett Controls

Color coded recessed wiring terminals

• Same colors as legacy controls

• Matches wire colors of Beckett components

• Reduces wiring mistakes

• Separate L2 terminals to aid trouble shooting

Basic Features

Page 11: Beckett Online Training | Series 3: Beckett Controls

Wiring / Installation

L1/Limit jumper

• For A and B model GeniSys controls programed without motor-off delay (postpurge), the L1 and Limit terminals must be jumpered.

• L1/Limit jumper is supplied with the control.

• The control will not work if 120VAC is not present at L1 or Limit

• If no jumper is available simply add a wire to Limit and connect to line input

Page 12: Beckett Online Training | Series 3: Beckett Controls

Universal Applications Replace 3 wire control with 7505A0000Or simply reprogram an existing GeniSys and rewire

Page 13: Beckett Online Training | Series 3: Beckett Controls

Burner has pump with valve. Program control for Pre-Time valve on delay and wire the valve to the valve terminalUniversal Applications

Page 14: Beckett Online Training | Series 3: Beckett Controls

Need motor off delay?One control does it all. Remove jumper, wire as shown, then program “Pre” and “Post” time

GeniSys Control

Page 15: Beckett Online Training | Series 3: Beckett Controls

7505A • No delays (purge)

7505B• Valve-on delay (prepurge) only

7505P• Valve on delay (prepurge) and motor-off delay (postpurge)

Model Designation

Page 16: Beckett Online Training | Series 3: Beckett Controls

Part Number Valve-On Delay Motor-Off Delay

7505A 0000 None None

7505B 1500 15 seconds None

7505P 1515 15 seconds 15 seconds

7505P 1530 15 seconds 30 seconds

7505P 152M 15 seconds 2 minutes

STOCK 1 AND YOU’RE DONE

PICK A CONTROL MODEL NUMBER

Model Designation

Page 17: Beckett Online Training | Series 3: Beckett Controls

UP

Begin by plugging in the Contractors Tool.

COM port 1

GeniSys Control

Page 18: Beckett Online Training | Series 3: Beckett Controls

The keysGeniSys Control

Page 19: Beckett Online Training | Series 3: Beckett Controls

GeniSys Control

STANDBY 8:15> 50 K OHMS 115 V

Press the NEXT key

Page 20: Beckett Online Training | Series 3: Beckett Controls

VIEWHISTORY

Press and hold the NEXT key for 3 secondsGeniSys Control

Page 21: Beckett Online Training | Series 3: Beckett Controls

PRE-TIME 0:00SEL TO CHANGE

Press the SEL key GeniSys Control

Page 22: Beckett Online Training | Series 3: Beckett Controls

VALVE INSTALLED?NO YES

Notice: To continue the burner must have an oil valve or CleanCut pump to add purgesGeniSys Control

Page 23: Beckett Online Training | Series 3: Beckett Controls

The GeniSys Control requires an oil valve to program both the valve on delay (pre purge) and motor off delay (post purge) features.

GeniSys Control

Page 24: Beckett Online Training | Series 3: Beckett Controls

LOCK OUT 0:45 PRE-TIME FLAME

The cad cell detected flame at theend of the Valve On Delay state.GeniSys Control

Page 25: Beckett Online Training | Series 3: Beckett Controls

VALVE NEEDEDSEE IO MANUAL

Press the BACK (NO) key if an oil valve is not available and see messageGeniSys Control

Page 26: Beckett Online Training | Series 3: Beckett Controls

CHANGED CANCELLED

The changed cancelled message will be displayedGeniSys Control

Page 27: Beckett Online Training | Series 3: Beckett Controls

PRE-TIME 0:00SEL TO CHANGE

Press the SEL key GeniSys Control

Page 28: Beckett Online Training | Series 3: Beckett Controls

VALVE INSTALLED?NO YES

Press the SEL (YES) key GeniSys Control

Page 29: Beckett Online Training | Series 3: Beckett Controls

PRE-TIME 0:30NO YES

Press the next key to set the timing 0, 5, 10, 15, 30 OR 45 SecondsGeniSys Control

Page 30: Beckett Online Training | Series 3: Beckett Controls

ACCEPT 0:30NO YES

Press SEL(YES) to acceptGeniSys Control

Page 31: Beckett Online Training | Series 3: Beckett Controls

PRE-TIME 0:30SEL TO CHANGE

The Pre-Time is now setPress the NEXT key to set the post time GeniSys Control

Page 32: Beckett Online Training | Series 3: Beckett Controls

POST-TIME 0:00SEL TO CHANGE

Press the SEL key GeniSys Control

Page 33: Beckett Online Training | Series 3: Beckett Controls

VALVE INSTALLED?NO YES

Press the SEL (YES) key GeniSys Control

Page 34: Beckett Online Training | Series 3: Beckett Controls

POST TIME 0:30NO YES

Press the next key to set the timing 0, 5, 15, 30, 1, 2, 4 or 8 minutesGeniSys Control

Page 35: Beckett Online Training | Series 3: Beckett Controls

ACCEPT 0:30NO YES

Press SEL (YES) to acceptGeniSys Control

Page 36: Beckett Online Training | Series 3: Beckett Controls

POST TIME 0:30SELECT TO CHANGE

The Post Time is now set.Press the BACK key to exit GeniSys Control

Page 37: Beckett Online Training | Series 3: Beckett Controls

STANDBY 1:15> 50 K OHMS 115 V

You just set the Pre-Time and Post TimeGeniSys Control

Page 38: Beckett Online Training | Series 3: Beckett Controls

THIS QUICK TUTORIALWILL GUIDE YOU

THROUGH THE STEPSON SETTING THE PRE

PURGE AND POST PURGE ON A GENISYS CONTROL

Download right to yoursmart phone or tabletTutorials

Page 39: Beckett Online Training | Series 3: Beckett Controls

www.beckettcorp.com

Beckett Website

Page 40: Beckett Online Training | Series 3: Beckett Controls

Any questions?Thank You!

[email protected]

Jeff Rozga Jim Todd

If you have any questions that weren’t answered – Email at