EHV CIRCUIT BREAKERS
SWITCHGEAR DIVISION, HYD - 032. 1
![Page 2: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/2.jpg)
SWITCHGEAR DIVISION, HYD - 032.
1. EHV breaker manufacturing operations Started in 1969.
2. Pioneer in high voltage breaker in the country with more
than 15,000 (including MOCBs) breakers in the grid with
more than four decades of experience.
3. About 35% ( more than 700 nos.) population of 400kV
breaker in Indian grid.
4. Complete range of manufacturing and test facilities for
breakers upto 800kV.
ABOUT SWITCHGEAR
2
![Page 3: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/3.jpg)
Product range
• SF6 gas circuit breaker– Type 3AT4/5 550kV to 800kV– Type 3AT2/3 420kV– Type 3AV1 245kV– Type 3AR1EG 145kV
SWITCHGEAR DIVISION, HYD - 032. 3
![Page 4: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/4.jpg)
CIRCUIT BREAKER
• A circuit breaker is defined as a mechanical device capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specific time and breaking currents under specific abnormal circuit conditions such as those of short circuit.
• The main functions of HV circuit-breakers can be categorized into four functions:
• Switching-off operating currents
• Switching-on operating currents
• Short-circuit current interruption
• Secure open and closed position
.
SWITCHGEAR DIVISION, HYD - 032. 4
![Page 5: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/5.jpg)
Power plant
Transformer Transformer Local distribution net work
Transmission
line
Switch
Yards
Switch
Yard
SWITCHGEAR DIVISION, HYD - 032.
Power Transmission system
5
![Page 6: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/6.jpg)
CIRCUIT BREAKER
• Physical requirements of EHV CB:
• Behave as a good conductor during a closed position.
Good isolator during an open position.
• Do not generate overvoltage's during switching.
• Keep high reliability during operation
.
SWITCHGEAR DIVISION, HYD - 032. 6
![Page 7: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/7.jpg)
CLASIFICATION OF CIRCUIT BREAKERS
Based on VoltageLow -less than 1kVMedium - 1kV to 52kVHigh/Extra High- 66kV to 765kVUltra High -above 765kV
Based on locationIndoor Outdoor
�Based on External designdead tank Live tank
�Based on Interrupting mediaAir breakAir blastBulk oilMinimum oilSF6 gas insulatedvacuum
SWITCHGEAR DIVISION, HYD - 032. 7
![Page 8: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/8.jpg)
Circuit Breakers
• Important standards
• IEC
• 62271-1General and definitions• 62271-100 Classification, Design and construction,
Type and routine testing, Selection of circuit breakers for service, Information in enquiries, tenders and orders.
SWITCHGEAR DIVISION, HYD - 032.
8
![Page 9: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/9.jpg)
Circuit Breakers
• ANSI(American National Standards Institute)
• C3704–1979 Rating structure
• C3706–1979 Preferred ratings
• C3709–1979 Test procedure
• C3710–1979 Application guide
• C3711–1979 Application guide for transient recovery voltage
• C3712–1979 Capacitance current switching
SWITCHGEAR DIVISION, HYD - 032.
9
![Page 10: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/10.jpg)
MAIN COMPONENTES 42OKV EHV CB
SWITCHGEAR DIVISION, HYD - 032.
INTERRUPTER UNIT
INSULATOR COLUMN
CONTROL UNIT
DRIVE UNIT
BELL CRANK HOUSING
10
![Page 11: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/11.jpg)
800kV Type 3AT4/5 SF6 Gas BreakerPole Assembly
SWITCHGEAR DIVISION, HYD - 032. 11
![Page 12: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/12.jpg)
CIRCUIT BREAKER
• Components of HV circuit-breakers regarding basic functions
can be divided into five groups:
a). Insulation:
Electric insulation of HV CB is Gaseous, liquid and solid
dielectric materials. Ex. Interrupter.
b). Current carrying:
The current carrying parts are significant components that
assure the flowing of current in the closed position.
The failure of these parts can lead to catastrophic events.
Ex. Guide tube.
SWITCHGEAR DIVISION, HYD - 032. 12
![Page 13: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/13.jpg)
CIRCUIT BREAKER
c). Switching:
HV circuit-breakers subjected to electrical, thermal and
mechanical stresses.
It is required that they should be able to make and break large
amount of power without causing failures.
.
SWITCHGEAR DIVISION, HYD - 032. 13
![Page 14: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/14.jpg)
CIRCUIT BREAKER
d). Operating mechanism:
The operating mechanism is a part used to move contacts
from open to closed position or inversely.
Ex. Hydraulic Mechanism.
e). Control and auxiliary functions: The signal is sent to the coil to move a latch or open a valve leading to energy release of a mechanical drive.
.
SWITCHGEAR DIVISION, HYD - 032. 14
![Page 15: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/15.jpg)
Classification of BreakersClassification of Breakers
SWITCHGEAR DIVISION, HYD - 032.
DEAD TANK TYPE LIVE TANK TYPE
15
![Page 16: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/16.jpg)
Classification of BreakersClassification of Breakers
Indoor Switchgear (GIS) Outdoor breakers (AIS)
SWITCHGEAR DIVISION, HYD - 032. 16
![Page 17: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/17.jpg)
SF6 GAS PROPERTIESSF6 GAS PROPERTIES
SWITCHGEAR DIVISION, HYD - 032. 17
![Page 18: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/18.jpg)
ARC INTERRUPTION
SWITCHGEAR DIVISION, HYD - 032. 18
![Page 19: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/19.jpg)
SWITCHGEAR DIVISION, HYD - 032. 19
![Page 20: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/20.jpg)
BREAKER'S OPERATION TIMES
• Basic oprns of the CB is "CLOSE" when joining, and "TRIP" when parting the contacts.• In most of the cases it has to execute on demand a combination of the basic operations, called cycles. The most popular are the following:
1."TRIP FREE", (C-O): simulates a trip on short circuit after a "CLOSE". 2."RECLOSE", (O-C): simulates a fast close after short circuit trip to reestablish the current.3."RECLOSE-OPEN", (O-0.3s-C-O): Simulates a "RECLOSE" on short circuit. The breaker should clear the fault successfully.
SWITCHGEAR DIVISION, HYD - 032.
20
![Page 21: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/21.jpg)
BREAKER'S OPERATION TIMES
4. (C-O)-15 sec-(C-O)-15-sec-(C-O): simulates a multiple close after short circuit trips in purpose of re-establishing the current, hoping that the short circuit is disappeared. This cycle is mostly used in the Medium voltage appls.
5. The times measured, for the different cycles starting from the coil energizing until the switching of the main contacts are called the Breaker's mechanical times of operations.
SWITCHGEAR DIVISION, HYD - 032.
21
![Page 22: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/22.jpg)
Arc interruption in duel flow conducting nozzle interrupter
SWITCHGEAR DIVISION, HYD - 032. 22
![Page 23: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/23.jpg)
Arc-quenching in duel flow conducting nozzle interrupter
SWITCHGEAR DIVISION, HYD - 032. 23
![Page 24: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/24.jpg)
Arc-quenching in insulated nozzle interrupter
1. Terminal plate 5. Nozzle2. Contact carrier 6. Contact cylinder3. Main contact 7. Base4. Arcing contact 8. Terminal plate
SWITCHGEAR DIVISION, HYD - 032.
24
![Page 25: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/25.jpg)
SWITCHGEAR DIVISION, HYD - 032. 25
![Page 26: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/26.jpg)
Blast cylinder assemblySWITCHGEAR DIVISION, HYD - 032.
26
![Page 27: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/27.jpg)
SWITCHGEAR DIVISION, HYD - 032. 27
![Page 28: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/28.jpg)
OPERATION OF CLOSING RESISTOROPERATION OF CLOSING RESISTOR
SWITCHGEAR DIVISION, HYD - 032. 28
![Page 29: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/29.jpg)
SWITCHGEAR DIVISION, HYD - 032. 29
![Page 30: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/30.jpg)
Spring operated mechanisms
SWITCHGEAR DIVISION, HYD - 032. 30
![Page 31: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/31.jpg)
Pneumatic mechanism
SWITCHGEAR DIVISION, HYD - 032. 31
![Page 32: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/32.jpg)
COMPARISON OF ELECTROHYDRAULIC - PNEUMATIC - SPRING MECHANISMS
Electro Hydraulic Pneumatic Spring
1. No compressor is required – Hydraulic pump ismaintenance free and directly coupled to motor.
Compressor is required, which needs routinemaintenance (at least once a year). Compressors arenormally coupled to motor by belt, which is a weaklink. Also intake air filters of compressors requirefrequent change (Every Six months in pollutedatmosphere)
No compressor is required – Hence no associatedmaintenance problems.
2. All parts permanently immersed in oil - No scope forinternal corrosion or rusting.
All parts exposed to atmosphere. In addition,atmospheric air is compressed and releasedduring closing / opening operation. Duringexpansion, traces of moisture present in air inspiteof purification / drying of air, condense on metalparts of the mechanism causing corrosion andrusting.
All parts exposed to atmosphere Heaters providedto prevent condensation of moisture on parts ofmechanism
3. Minimal piping – Oil flow is through ducts in valveblock assembly – No scope for external leakage –Internal leakage, if any, would only cause morefrequent operation of motor at worst.
Piping is involved - Scope for leakage. No piping - No leakage.
4. No mechanical latches.The differential piston principle used clearly definesthe switching condition and ensures that this ismaintained should there be a fall in pressure and that"creeping" trip out is prevented.
Latches are to be checked for disturbances in settingsafter specified no. of operations
Latches are to be checked for disturbances in settingsafter specified no. of operations.
5. Small in size, compact and robust construction.Reliability very high.
Complex construction with many componentsand moving parts - Reliability very low.
Simple in design and construction. Less componentsand moving parts, hence reliable.
6. Two Close-Open operations are possible after failureof supply to motor.
One Open-Close-Open or Close-Open-Closeoperation is possible after failure of supply to motor.
One Open-Close-Open operation is possible afterfailure of supply to the motor.
SWITCHGEAR DIVISION, HYD - 032. 32
![Page 33: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/33.jpg)
COMPARISON OF ELECTROHYDRAULIC - PNEUMATIC - SPRING MECHANISMS
Electro Hydraulic Pneumatic Spring
7 No additional damping system The damping requiredfor both closing and opening is provided by thehydraulics of the operating mechanism.
Additional damping system is required which is to beroutinely checked and maintained.
Additional damping system is required which is to beroutinely checked and maintained.
8 No inter-posing mechanism. The piston systemtransmits the operating energy direct to the operatingrod.
Inter-posing mechanism with linkages is required fortransmission of operating energy to the movingcontact system.
Inter-posing mechanism with linkages is required fortransmission of operating energy to the movingcontact system.
9 Low noise level High noise level Low noise level
SWITCHGEAR DIVISION, HYD - 032. 33
![Page 34: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/34.jpg)
145 kV TYPE 3AR1EG BREAKER
SWITCHGEAR DIVISION, HYD - 032. 34
![Page 35: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/35.jpg)
145kV hydraulic mechanism operated SF6 gas breaker
SWITCHGEAR DIVISION, HYD - 032. 35
![Page 36: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/36.jpg)
245kV TYPE 3AV1 BREAKER
SWITCHGEAR DIVISION, HYD - 032. 36
![Page 37: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/37.jpg)
SWITCHGEAR DIVISION, HYD - 032. 37
![Page 38: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/38.jpg)
800kV Type 3AT4/5
SF6 gas circuit breaker
SWITCHGEAR DIVISION, HYD - 032. 38
![Page 39: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/39.jpg)
Testing of circuit breaker• Type tests
– High power tests• Direct tests• synthetic tests
– Short circuit tests
– Switching performance tests
– High voltage tests
– Mechanical and environmental tests
– Temperature rise test
• Routine tests– Mechanical operations test
– Measurement of contact resistance
– Voltage withstand test on control circuit
– Power frequency withstand test on main circuit
– High pressure test on Hydraulic mechanism
– SF6 gas tightness test
– Pump charging time for operations
– Leak testing hydraulic mechanism
– N2 leak test on accumulatorSWITCHGEAR DIVISION, HYD - 032.
39
![Page 40: BHEL Breaker presentation](https://reader035.vdocuments.net/reader035/viewer/2022062221/55cf99e1550346d0339f9f4e/html5/thumbnails/40.jpg)
Thank youThank you
40SWITCHGEAR DIVISION, HYD - 032.