Page 1: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Psychrometrics 101

Tony deFrancescoBE Mech (Hons)Technical DirectorP.U.E. Pty Ltd

Page 2: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

1. Psychrometric basicsi. Dry & wet bulb temperatureii. Psychrometric chartiii. The heating & cooling process

2. The data centre environmenti. Data centre exampleii. What can alter the moisture leveliii. Why is precise control important

3. ASHRAE recommended guidelines4. Effect of moisture on free-cooling

i. Free-cooling according to ASHRAE indoor limitsii. How to increase free-cooling hours

5. Summary

Topics

Page 3: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Psychrometric basics

Page 4: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Psychrometrics

Psychrometrics or psychrometry are terms usedto describe the study of gas-vapour mixtures, inparticular the mixture of water vapour and air

Page 5: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Dry bulbtemperature

(Tdb)

Wet bulbtemperature

(Twb)

• Wet bulb temperature isan indication of theamount of moisture inthe air

• Wet bulb temperature isthe lowest temperaturethat can be reached bythe evaporation of wateronly

• Dry bulb temperature isthe temperature that isusually thought of asthe “air temperature”

• Dry bulb temperatureprovides no indicationof the amount ofmoisture in the air

Dry & wet bulb temperature

Page 6: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Wet bulbtemperature

Dry bulbtemperature

Moisturecontent

Relativehumidity

Psychrometric chart

Page 7: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Heating airCooling air

Addingmoisture

Drying air

Saturation line(i.e. maximummoisture content)

Psychrometric chart

Page 8: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

1kg of air

15g moisture

20°C

100%RH

1kg of air

15g moisture

32°C

50%RH

+12°C

Note: No change in the amountof moisture, but a change in

relative humidity!!

Heating example

Page 9: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

ΔTdb = 12°C

Heating example

Page 10: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

1kg of air

20g moisture

25°C

100%RH

1kg of air

15g moisture

20°C

100%RH

-5°C

5g water

Note: No change in relative humidityand no change in the total amount ofmoisture, but a change in its state!!

Cooling example

Page 11: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

ΔW = 5g

ΔTdb = 5°C

NOTE: When air is at 100%RH,any cooling will result inprecipitation (i.e. rain)

Cooling example

Page 12: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

The data centre environment

Page 13: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

13°C @ 90%RH

22°C @ 50%RH35°C @ 23%RH

Temperature & relative humidity changes throughout theroom, but the amount of moisture in the air does not change!

8.4g/kg

8.4 g/kg8.4 g/kg

Data centre example

Page 14: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

W = 8.4g

Data centre example

Page 15: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

In increase in the air’s moisture can occur due to:

1. Introduction of moist outside air (typically summer)

2. People

3. Humidification

A decrease in the air’s moisture can occur due to:

1. Introduction of dry outside air (typically winter)

2. Cooling the air

What changes the room’s moisture?

Page 16: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

If the supply air cools from 13°C@50%RH to <11.5°C,water would be present in the data centre!!

13°C @ 90%RH

22°C @ 50%RH

11.5°C @ 100%RH!!!!

20.5°C @ 55%RH

Why is precise control important?

Page 17: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

ASHRAE recommendedguidelines

Page 18: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Allowable Operating Environment

Revised 2008 RecommendedOperating Environment Limits

Existing 2004 RecommendedOperating Environment Limits

Class 1 & 2 Operating Environments

NOTE: The Recommended range is a statement on reliability,the Allowable range is not.

ASHRAE environmental guidelines

Page 19: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Effect of moisture onfree-cooling

Page 20: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Outside air inwhen temperature

and moisturelevels within limits

20°C

32°C

Free-cooling: Direct

Page 21: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Upper limit: 8.7g/kg

Lower limit: 5.6g/kg

20°C

Free-cooling: ASHRAE guidelines

Page 22: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Moisture must be:

> 5.6 g/kg

< 8.7g/kg

20°C

32°C

Free-cooling: ASHRAE guidelines

Page 23: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

BRISBANEBRISBANE

NO FC

SYDNEYSYDNEY

NO FC

CANBERRACANBERRA

NO FC

Free-cooling: ASHRAE guidelines

MELBOURNEMELBOURNE

NO FC

Page 24: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Indirect FCIndirect free-cooling a function of:

• Ambient Temperature

Direct free-cooling a function of:

• Ambient Temperature

• Ambient Moisture (%RH)

• Ambient Air Quality

Direct FCHow to increase free-cooling hours

Page 25: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Sydney temperature levels basedon a 20°C S/A and 32°C R/A

Direct FC Indirect FC

FC54.1%

MIX45.7%

DX0.3%

FC49.4%

MIX49.6%

DX1.0%

Ambient temperature

Page 26: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Sydney moisture levels with limits shown according to ASHRAE EnvironmentalGuidelines (2008) for 20°C room setpoint temperature

FC30%

FC100%

Direct FC Indirect FC

Ambient moisture

Page 27: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Sydney temperature levels based on a 20°C S/Aand 32°C R/A and moisture levels according toASHRAE Environmental Guidelines (2008)

Direct FC Indirect FC

Ambient temperature & moisture

Page 28: BICSI South Pacific 2011 - PUE Psychrometrics 101hvaceducationaustralia.com/Resources/PDF/Psychrometrics_101-PUE.… · The heating & cooling process ... Psychrometrics or psychrometry

Summary1. Relative humidity is not an absolute measure of the moisture in the air.

It is an indication of the level of saturation of the air.

2. A change in relative humidity does not necessarily mean a change inthe air’s absolute moisture content.

3. The amount of moisture in the air is best measured by determining theair’s moisture content from a psychrometric chart.

4. In most of Australia’s cities, the use of outside air to directly cool adata centre is heavily restricted due to the very high and low levels ofmoisture typically present

5. The amount of free-cooling hours in a year can be greatly increasedby introducing a heat exchanger to separate the indoor and outdoor airstreams.