DRAWING INDEX UNIVERSITY OF MISSOURI TEACHING HOSPITAL BAS UPGRADES, ED AHU-1, 2 & 3 MU PROJECT NO. CP171062 FOR THE CURATORS OF THE UNIVERSITY OF MISSOURI ENGINEER / ARCHITECT: ENGINEER: ROSS & BARUZZINI 6 SOUTH OLD ORCHARD ST. LOUIS, MO 63119 (314) 918-8383 ARCHITECT: bc DESIGN GROUP 200 NE MISSOURI ROAD SUITE 200 LEE'S SUMMIT, MO 64086 DESIGN TEAM JANUARY 31, 2019 GENERAL G000: COVER SHEET G001: PHASING - INFECTION CONTROL G101: FIRST FLOOR - LIFE SAFETY PLAN G102: SECOND FLOOR - LIFE SAFETY PLAN MECHANICAL M000: MECHANICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES MD101: FIRST FLOOR - DEMOLITION MD102: SECOND FLOOR - DEMOLITION M101: FIRST FLOOR - NEW WORK M102: SECOND FLOOR - NEW WORK M101 - REF: REFERENCE FIRST FLOOR HVAC PLAN M600: SCHEDULES AND DETAILS M700: TEMPERATURE CONTROLS ELECTRICAL E001: ELECTRICAL PARTIAL FLOOR PLAN MU AHJ CODES ENFORCED: x INTERNATIONAL BUILDING CODE 2015 x INTERNATIONAL FIRE CODE 2015 x INTERNATIONAL MECHANICAL CODE 2015 x NATIONAL ELECTRICAL CODE 2014 x NFPA 101 LIFE SAFETY CODE 2012 x NFPA 72 NATIONAL FIRE ALARM CODE 2013 x NFPA 99 HEALTH CARE FACILITIES CODE 2012 x ASHRAE STANDARD 90.1 - 2013 G000 RAC JPS COVER SHEET 2012 LIFE SAFETY CODE REFERENCED STANDARDS: x NATIONAL ELECTRICAL CODE 2011 x NFPA 72 NATIONAL FIRE ALARM CODE 2010 I HEREBY CERTIFY THAT DRAWING SHEET G001 HAS BEEN PREPARED BY ME, OR UNDER MY SUPERVISION. I FURTHER CERTIFY THAT TO THE BEST OF MY KNOWLEDGE THESE DRAWINGS AND/ OR SPECIFICATIONS ARE AS REQUIRED BY AND IN COMPLIANCE WITH BUILDING CODES OF THE UNIVERSITY OF MISSOURI. I HEREBY CERTIFY THAT G000, G101, G102, M000, MD101, MD102, M101, M102, M600, M700 AS WELL AS SPECIFICATION DIVISIONS 07 AND 23 HAVE BEEN PREPARED BY ME, OR UNDER MY SUPERVISION. I FURTHER CERTIFY THAT TO THE BEST OF MY KNOWLEDGE THESE DRAWINGS AND/ OR SPECIFICATIONS ARE AS REQUIRED BY AND IN COMPLIANCE WITH BUILDING CODES OF THE UNIVERSITY OF MISSOURI. I HEREBY CERTIFY THAT E001 AS WELL AS SPECIFICATION DIVISION 26 HAVE BEEN PREPARED BY ME, OR UNDER MY SUPERVISION. I FURTHER CERTIFY THAT TO THE BEST OF MY KNOWLEDGE THESE DRAWINGS AND/ OR SPECIFICATIONS ARE AS REQUIRED BY AND IN COMPLIANCE WITH BUILDING CODES OF THE UNIVERSITY OF MISSOURI. 1.31.2019 BID SET

Upload: trinhthu

Post on 13-Aug-2019

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

DRAWING INDEX

UNIVERSITY OF MISSOURI TEACHING HOSPITAL

BAS UPGRADES, ED AHU-1, 2 & 3

MU PROJECT NO. CP171062

FOR THE CURATORS OF THE

UNIVERSITY OF MISSOURI

ENGINEER / ARCHITECT:

ENGINEER:

ROSS & BARUZZINI

6 SOUTH OLD ORCHARD

ST. LOUIS, MO 63119

(314) 918-8383

ARCHITECT:

bc DESIGN GROUP

200 NE MISSOURI ROAD

SUITE 200

LEE'S SUMMIT, MO 64086

DESIGN TEAM

JANUARY 31, 2019

GENERAL

G000: COVER SHEET

G001: PHASING - INFECTION CONTROL

G101: FIRST FLOOR - LIFE SAFETY PLAN

G102: SECOND FLOOR - LIFE SAFETY PLAN

MECHANICAL

M000: MECHANICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES

MD101: FIRST FLOOR - DEMOLITION

MD102: SECOND FLOOR - DEMOLITION

M101: FIRST FLOOR - NEW WORK

M102: SECOND FLOOR - NEW WORK

M101 - REF: REFERENCE FIRST FLOOR HVAC PLAN

M600: SCHEDULES AND DETAILS

M700: TEMPERATURE CONTROLS

ELECTRICAL

E001: ELECTRICAL PARTIAL FLOOR PLAN

MU AHJ CODES ENFORCED:

INTERNATIONAL BUILDING CODE 2015

INTERNATIONAL FIRE CODE 2015

INTERNATIONAL MECHANICAL CODE 2015

NATIONAL ELECTRICAL CODE 2014

NFPA 101 LIFE SAFETY CODE 2012

NFPA 72 NATIONAL FIRE ALARM CODE 2013

NFPA 99 HEALTH CARE FACILITIES CODE 2012

ASHRAE STANDARD 90.1 - 2013

G000

RAC

JPS

COVER SHEET

2012 LIFE SAFETY CODE REFERENCED STANDARDS:

NATIONAL ELECTRICAL CODE 2011

NFPA 72 NATIONAL FIRE ALARM CODE 2010

I HEREBY CERTIFY THAT DRAWING SHEET G001 HAS BEEN PREPARED

BY ME, OR UNDER MY SUPERVISION. I FURTHER CERTIFY THAT TO THE

BEST OF MY KNOWLEDGE THESE DRAWINGS AND/ OR SPECIFICATIONS

ARE AS REQUIRED BY AND IN COMPLIANCE WITH BUILDING CODES OF

THE UNIVERSITY OF MISSOURI.

I HEREBY CERTIFY THAT G000, G101, G102, M000, MD101, MD102, M101,

M102, M600, M700 AS WELL AS SPECIFICATION DIVISIONS 07 AND 23

HAVE BEEN PREPARED BY ME, OR UNDER MY SUPERVISION. I FURTHER

CERTIFY THAT TO THE BEST OF MY KNOWLEDGE THESE DRAWINGS

AND/ OR SPECIFICATIONS ARE AS REQUIRED BY AND IN COMPLIANCE

WITH BUILDING CODES OF THE UNIVERSITY OF MISSOURI.

I HEREBY CERTIFY THAT E001 AS WELL AS SPECIFICATION DIVISION 26

HAVE BEEN PREPARED BY ME, OR UNDER MY SUPERVISION. I FURTHER

CERTIFY THAT TO THE BEST OF MY KNOWLEDGE THESE DRAWINGS

AND/ OR SPECIFICATIONS ARE AS REQUIRED BY AND IN COMPLIANCE

WITH BUILDING CODES OF THE UNIVERSITY OF MISSOURI.

1.31.2019

BID SET

Page 2: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

1.31.2019

Page 3: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

SM SM SM

SMSM

SM SM SM

SM

SM SM

SM SM SM SM SM SM SM

SM

SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM

SMSM

SMSM

SMSM

SM

SMSM

SM

SMSM

SMSM

SMSM

SM

SM

SMSM

SMSM

SM

SMSM

SMSM

SMSM

SM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SM

SM

SMSM

SM

SM

SMSM

SM

SM

SMSM

SMSM

SMSM

SMSM

SM

SM

SM SM SM SM SM SM

SMSM

SMSM

2HR 2HR

2HR2HR

2HR

2HR2HR

2HR2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR

2HR

2HR

2HR2HR2HR2HR

2HR2HR

2HR 2HR 2HR 2HR

2HR2HR

2HR

2HR 2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR2HR2HR2HR2HR2HR

2HR2HR

2HR 2HR 2HR 2HR 2HR 2HR 2HR

2HR2HR

2HR

2HR

2HR 2HR

2HR2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR 2HR 2HR 2HR 2HR 2HR 2HR

2HR

2HR

2HR

2HR

2HR2HR2HR

2HR2HR

2HR 2HR 2HR

CODE LEGEND:

3HR 3HR 3HR 3HR

2HR 2HR 2HR 2HR

1HR 1HR 1HR 1HR

SM SM SM SM

3 HOUR FIRE BARRIER

2 HOUR FIRE WALL

1 HOUR FIRE WALL

SMOKE BARRIER

SCALE:

FIRST FLOOR - LIFE SAFETY1/8"=1'-0"1

NORTH 16'8'4'1'

SCALE: 1/8" = 1'-0"

RAC

JPS

FIRST FLOOR - LIFE SAFETY

DANIEL PHELAN

PE-2017030573

Page 4: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

SMSMSMSM

SMSM

SMSM

SMSMSMSMSM

SMSMSM

SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SMSM

SM SM SM SM SM SM SM SM SM SM SM SM SM SM

SMSM

SMSM

SM

SMSMSM

SMSM

SM SM

SMSM

SMSM

SMSMSM

SMSM

SMSM

SMSM

SMSM

2HR

2HR2HR 2HR2HR2HR2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR

2HR2HR

2HR 2HR

2HR

2HR

2HR

2HR

2HR 2HR 2HR 2HR

2HR

2HR

2HR2HR2HR2HR2HR

2HR2HR

2HR 2HR 2HR 2HR 2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR

2HR2HR

2HR 2HR

2HR

2HR

2HR

2HR

2HR 2HR 2HR 2HR 2HR

2HR

2HR

2HR2HR2HR2HR2HR2HR

2HR 2HR 2HR

2HR2HR

2HR2HR

2HR 2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR

2HR2HR2HR

2HR2HR

2HR 2HR 2HR

2HR2HR

2HR2HR

2HR2HR

2HR

2HR 2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR 2HR 2HR

2HR2HR

2HR

2HR2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR2HR

2HR2HR

2HR 2HR

2HR

2HR

2HR2HR2HR2HR2HR

2HR2HR

2HR 2HR 2HR 2HR 2HR

2HR

2HR

2HR2HR2HR2HR2HR2HR2HR

2HR2HR

2HR 2HR 2HR 2HR 2HR 2HR 2HR

2HR

2HR

2HR2HR2HR2HR2HR2HR2HR

2HR2HR

2HR 2HR 2HR 2HR 2HR 2HR 2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

2HR

SCALE:

SECOND FLOOR - LIFE SAFETY1/8"=1'-0"1

NORTH

RAC

JPS

SECOND FLOOR - LIFE SAFETY

16'8'4'1'

SCALE: 1/8" = 1'-0"

CODE LEGEND:

3HR 3HR 3HR 3HR

2HR 2HR 2HR 2HR

1HR 1HR 1HR 1HR

SM SM SM SM

3 HOUR FIRE BARRIER

2 HOUR FIRE WALL

1 HOUR FIRE WALL

SMOKE BARRIER

DANIEL PHELAN

PE-2017030573

Page 5: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

KEYED NOTE

GENERAL SYMBOLS

SECTION NUMBER

SHEET WHERE LOCATED

INTERFACE, EXISTING TO NEW

PITCH DOWN IN DIRECTION OF ARROW

CWS

CWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

PIPING SYMBOLS

HWS

HWR

HEATING WATER SUPPLY

HEATING WATER RETURN

THERMOSTAT (NIGHT)

N

THERMOSTAT

HUMIDISTAT

PIPE ANCHOR

TEE DOWN

TEE UP

ELBOW UP

ELBOW DOWN

HEAT RECOVERY UNITHRU

GAUGE COCK

FLEXIBLE PIPE COUPLING

CALIBRATED ORIFICE BALANCE VALVE

CAP

SOLENOID VALVE

PRESSURE REGULATING VALVE

PRESSURE GAUGE W/COCK

THERMOMETER

AIR VENT (M-MANUAL, A-AUTO)

FLANGE

CONCENTRIC REDUCER/INCREASER

PUMP DISCHARGE VALVE

WATER COLUMN

WET BULB

WC

WB

UC UNDERCUT DOOR

WATT OR WIDTH (PER CONTEXT)W

VOL

VOLUME DAMPER (MANUAL)VD

VOLTSV

VOLUME

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

LWT LEAVING WATER TEMPERATURE

HVAC HEATING, VENTILATING

ENTERING WATER TEMPERATUREEWT

EXISTINGEXIST, EX

EXTERNAL STATIC PRESSUREESP

BOTTOM OF PIPEBOP

APD AIR PRESSURE DROP

# x # DUCT SIZE, FIRST FIGURE IS SIDE SHOWN

ACCESS PANEL, TOP OR SIDE

TURNING VANES

CHANGE OF ELEVATION - RISE (R) OR DROP (D)

R

FLEXIBLE DUCT CONNECTION

FLEXIBLE DUCT

AFF

CONCRETECONC

CAST IRONCI

CFM

BTUH

BOD

BOB

CONDENSING UNIT

COMPUTER ROOM AIR CONDITIONING UNITCRU

CU

UNIT NUMBER

EQUIPMENT DESIGNATION

EQUIPMENT

EAT

EXHAUST AIR OR EACH (PER CONTEXT)EA

DOWNDN

DIAMETERDIA

DRY BULBDB

FEETFT

GALVANIZEDGALV

GALLONSGAL

GAUGEGA

FT-HD

EXHAUSTEXH

VAV

SUPPLY FANSF

SMOKE DAMPERSD

MD

HUMIDIFIERH

VARIABLE AIR VOLUME BOX

MOTORIZED DAMPER

HEAD IN FEET

ENTERING AIR TEMPERATURE

CUBIC FEET PER MINUTE

BRITISH THERMAL UNITS PER HOUR

BOTTOM OF DUCT

BOTTOM OF BEAM

ABOVE FINISHED FLOOR

GENERAL

STRAINER

RELIEF VALVE (TEMP/PRESS)

THREE-WAY CONTROL VALVE

TWO-WAY CONTROL VALVE

CHECK VALVE

BUTTERFLY VALVE

GLOBE VALVE

BALL VALVE

PIPE LINE EQUIPMENT

UNION

LAT

KILOWATTSKW

HORSEPOWERHP

HEADHD

GPM

OA

NTS

NIC

NO

NC

MINIMUM OR MINUTE (PER CONTEXT)MIN

MBH

MAXIMUMMAX

RH

RETURN AIRRA

PSIG

PD

TOTAL DYNAMIC HEADTDH

SP

SOLENOIDSOL

SENSIBLESENS

SANITARYSAN

STATIC PRESSURE

RELATIVE HUMIDITY

POUNDS PER SQUARE INCH GAUGE

PRESSURE DROP

OUTSIDE AIR

NOT TO SCALE

NOT IN CONTRACT

NORMALLY OPEN OR NUMBER (PER CONTEXT)

NORMALLY CLOSED OR NOISE CRITERIA (PER CONTEXT)

THOUSANDS BRITISH THERMAL UNITS PER HOUR

LEAVING AIR TEMPERATURE

GALLONS PER MINUTE

RETURN FANRF

UH UNIT HEATER

BEAM SPACEBS

GC GENERAL CONTRACTOR

JS JOIST SPACE

LS LIGHT SPACE

SUPPLY OR OUTSIDE AIR SECTION UP

RETURN AIR SECTION UP

SUPPLY OR OUTSIDE AIR DOWN OR AWAY

RETURN AIR DOWN OR AWAY

CONDENSATECOND

RM ROOM

VTR VENT THRU ROOF

DPT DIFFERENTIAL PRESSURE TRANSMITTER

BLOWER COIL UNIT

AIR HANDLING UNIT

BCU

AHU

PRESSURE REDUCING VALVE

3

PRESSURE/TEMPERATURE TEST PORT

EXPANSION JOINT

PIPE GUIDE

THERMOSTATIC EXPANSION VALVE

SIGHT GLASS

FLOW ARROW

(ACTUAL SIZE INDICATED)

AP

AUTOMATIC DAMPER

MANUAL VOLUME DAMPER

FIRE DAMPER

TYPE OF SERVICE: S = SUPPLY

R = RETURN

E = EXHAUST

T = TRANSFER

AIR QUANTITY

IN CFM

& AIR CONDITIONING

1

M

SMOKE DAMPER

FIRE/SMOKE DAMPER

EXISTING TO BE REMOVED

IN-LINE PUMP

ACC ACCESSORIES

BO BINARY SIGNAL OUTPUT

BI BINARY SIGNAL INPUT

CONN CONNECTION

CORRIDORCORR

CONTROL VALVECV

ELECTRICELEC

ELEV ELEVATION

HR HOUR

IN INCH/INCHES

PRV PRESSURE REGULATING VALVE

SA SUPPLY AIR

SQ SQUARE

TEMP TEMPERATURE

WITHW/

X

M-X

AHU

1

T

T

H

A AIR

ANALOG SIGNAL INPUTAI

AO ANALOG SIGNAL OUTPUT

AVERAGEAVG

ARCHITECTURE/ARCHITECT

APPLICATION PART LOAD VALUEAPLV

AUX AUXILIARY

ARCH

BDD BACK DRAFT DAMPER

BFC BELOW FINISHED CEILING

BHP BRAKE HORSEPOWER

CAPACITYCAP

CONTROLLED CLOSURE DEVICECCD

COOLING DUCT (COLD DUCT)CLG

DEGREESDEG

DEFL DEFLECTION

DBA A-WEIGHTED DECIBELS

DISCHARGEDISCH

DIMENSIONDIM

DIV DIVISION

DETAILDTL

DRAWING(S)DWG(S)

EFFICIENCY

ENERGY EFFICIENT RATIOEER

EFF

EQ EQUAL

DEGREES FAHRENHEITDEG F

FIN

FLR

FPM FEET PER MINUTE

FLOOR

FINISHED

HEIGHTH

HEATING DUCT (HOT DECK)HTG

HERTZ

HW

HZ

HOT WATER

LENGTHL

LINEAR FEETLF

POUND(S)LB(S)

LEVELLVL

MANUALMAN

MANUFACTURER

MECH MECHANICAL

MFR

METALMTL

NPSH

NOM

NET POSITIVE SUCTION HEAD

NOMINAL

OT OIL TRAP

OD OUTSIDE DIAMETER

PHASEPH

PENTHOUSE

PRESSURE

PENT

PPH POUNDS PER HOUR

PRESS

PSI ABSOLUTEPSIA

PSI POUNDS PER SQUARE INCH

QUANTITYQTY

RADIATEDRAD

RPM REVOLUTIONS PER MINUTE

SECTIONSEC'N

SHEETSHT

STATIC PRESSURE DIFFERENTIALSPD

STAINLESS STEELSST

STL STEEL

TOTALTOT

UNO UNLESS NOTED OTHERWISE

VE VIBRATION ELIMINATOR OR ISOLATOR

VEL VELOCITY

WITHOUTW/O

WATER GAUGEWG

WEIGHTWT

WATER PRESSURE DIFFERENTIALWPD

COMBINATION FIRE/SMOKE DAMPERFSD

EF EXHAUST FAN

HEATING COILHC

CONSTANT AIR VOLUMECAV

ENTERING AIR WET BULB TEMPERATUREEWB

FIRE DEPARTMENT CONNECTIONFDC

HORIZONTALHORIZ

INVERT ELEVATIONIE

INDIC INDICATOR

ISP INTERNAL STATIC PRESSURE

PNEUMATICPNEU

SQUARE FOOTSF

STATIC PRESSURE TRANSMITTERSPT

STEAMSTM

SW SOFTENED WATER

TEMPERATURE CONTROLTC

TEMPERATURE AND PRESSURET&P

TD THERMODYNAMIC

UNDERGROUNDUG

VACUUMVAC

VACUUM BREAKERVB

VERTICALVERT

SENSOR (T = TEMPERATURE H = HUMIDITY)

T OR H

S

GRAVITY BACKDRAFT

SUPPLY DIFFUSER, REGISTER OR

GRILLE AS SCHEDULED

RETURN GRILLE OR REGISTER

SLOT DIFFUSER AS SCHEDULED

SIDEWALL GRILLE OR REGISTER

IF NO ARROWS ARE SHOWN ON PLAN, DEFAULT

ARROWS INDICATE DIRECTION OF AIR DISCHARGE.

IS 2-WAY HORIZONTAL FOR SLOT DIFFUSERS,

4-WAY HORIZONTAL FOR SQUARE DIFFUSERS.

AS SCHEDULED

AS SCHEDULED

LUBRICATED PLUG COCK

ECCENTRIC REDUCER/INCREASER

CHILLERCH

NPLV NON-STANDARD PART LOAD VALUE

OC ON CENTER

SENSIBLE HEATSH

STEAM TRAP: IB = INVERTED BUCKET

WATER METER (FLOW TOTALIZING TYPE)M

T

FLOAT & THERMOSTATIC=FT

THERMODYNAMIC DISK=TD

S-1

100

DESIGNATION ABBREVIATIONS

GENERAL

ABBREVIATIONS

FLOW ARROW DOWNSTREAM OF FAN

FLOW ARROW UPSTREAM OF FAN

SCHEDULED

DEVICE NO

# x #

STOP CHECK VALVE

PRESSURE TEST VALVE

Y-PATTERN STRAINER WITH BLOWDOWN

BLOWDOWN VALVE

FLOW OR TEMPERATURE SWITCH

FS TS

OR

# x #

DUCT SIZE

DUCT SIZE

# x #

NEW WORK

EXISTING TO REMAIN

MERV MINIMUM EFFICIENCY REPORTING VALUE (ASHRAE 52.2)

FPF FINS PER FOOT

VALVE IN RISE

M

BUTTERFLY VALVE (MOTORIZED)

STATIC PRESSURE SENSOR

SP

GENERAL NOTES:

APPROXIMATEAPPROX

1. IF THE CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS OR IS NOT SURE OF THEIR MEANING, HE SHOULD

OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION PRIOR TO BID, SINCE THE CONTRACTOR WILL BE HELD

RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.

2. REFER TO ARCHITECTURAL SHEETS FOR THE PHASING OF THE PROJECT. THE EXISTING HVAC SYSTEMS MUST REMAIN IN

OPERATION WHILE THE SPACES REMAIN IN USE.

3. THE CONTRACTOR SHALL COORDINATE STAGING AND SCHEDULING WITH THE OWNER'S REPRESENTATIVE.

4. EXISTING CONDITIONS ARE BASED ON INFORMATION OBTAINED FROM PREVIOUS CONSTRUCTION DOCUMENTS AND

INFORMAL FIELD OBSERVATION AND SHALL NOT BE CONSTITUTED AS "AS BUILT." THE CONTRACTOR SHALL FIELD-VERIFY

EXISTING CONDITIONS BEFORE THE ONSET OF CONSTRUCTION.

5. WHERE CONTRACTOR IS REQUIRED TO CONCEAL NEW WORK, REMOVE OR MODIFY EXISTING CONSTRUCTION OR

EQUIPMENT, OR ATTACH TO EXISTING CONSTRUCTION, THE CONTRACTOR SHALL REPAIR OR REPLACE EXISTING CONSTRUCTION

MATERIALS TO MATCH CONDITIONS AT THE ONSET OF CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REMOVE AND

REPLACE EXISTING CEILINGS AND WALLS REQUIRED FOR INSTALLATION OF MECHANICAL SYSTEMS.

6. THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT AND MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED BY

THE OWNER SHALL BE REMOVED FROM THE PREMISES BY THIS CONTRACTOR.

7. PROVIDE VENTS AT ALL PIPING HIGH POINTS, AND DRAINS AT ALL PIPING LOW POINTS, REGARDLESS OF WHETHER SHOWN OR NOT.

9. THE CONTRACTOR SHALL CONNECT THE NEW HVAC SYSTEM TO THE OWNER'S EXISTING BUILDING CONTROL SYSTEM. REFER TO THE

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

10. THE WORK OF SECTION 230900 SHALL INCLUDE THE FOLLOWING ELECTRICAL WORK, COMPLYING WITH REQUIREMENTS OF DIVISION 26

SPECIFICATIONS.

A. CONTROL WIRING BETWEEN FIELD-INSTALLED CONTROLS, INDICATING DEVICES, AND UNIT CONTROL

PANELS.

B. INTERLOCK WIRING BETWEEN ELECTRONICALLY OPERATED EQUIPMENT UNITS AND BETWEEN

EQUIPMENT AND FIELD-INSTALLED CONTROL DEVICES.

C. POWER SUPPLY WIRING FOR POWER SOURCE TO POWER CONNECTION ON CONTROLS AND/OR UNIT

CONTROL PANELS, INCLUDING, BUT NOT LIMITED TO, AIR TERMINAL UNIT CONTROLLERS, DDC PANELS, DAMPER

ACTUATORS, AND VALVE ACTUATORS.

UNIT NUMBER

DAMPER TYPE DESIGNATION

FSD

1

VFD VARIABLE FREQUENCY DRIVE

RLA RUNNING LOAD AMPS

LOCKED ROTOR AMPSLRA

BRITISH THERMAL UNITBTU

F FAHRENHEIT

TEE-TYPE STRAINER

EX= EXISTING

EXHAUST GRILLE OR REGISTER

AS SCHEDULED

EXHAUST AIR SECTION UP

EXHAUST AIR DOWN OR AWAY

RAC

JPS

MECHANICAL SYMBOLS,

ABBREVIATIONS & GENERAL

NOTES

DANIEL PHELAN

PE-2017030573

Page 6: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

2

2

5

2

5

2

2

2

2

2

22

2

2

5

2

1 3 4

1 3 4

1 3 4

1 3 4

1 3 4

1 3 4

1 3 4

1 3 4

1 3 4

1 3 4

1 3 4

1 3

41 3 4

1 3 4

1 3 4

2

5

5

5

2

2

1

2

3

4

SCALE:

FIRST FLOOR - DEMOLITION

1/8"=1'-0"

1

NORTH

RAC

JPS

FIRST FLOOR - DEMOLITION

16'8'4'1'

SCALE: 1/8" = 1'-0"

SCALE:

KEY MAP

NOT TO SCALE

5

DANIEL PHELAN

PE-2017030573

Page 7: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

6

5

5

5

1 3 4

5

5

6

6

6

8

6

2

5

1 3 4

2

2

2

2

2

2

2

2

1 3 41 3 4

1 3 4

7

1 3 4

1 3 4

1 3 4

1 3 4

5-TON LIEBERT

UNIT

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

1 3 4

T 2

1

2

3

4

SCALE:

SECOND FLOOR - DEMOLITION

1/8"=1'=-0"

1

NORTH

RAC

JPS

SECOND FLOOR -

DEMOLITION

5

6

7

16'8'4'1'

SCALE: 1/8" = 1'-0"

SCALE:

KEY MAP

NOT TO SCALE

8

DANIEL PHELAN

PE-2017030573

Page 8: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

2

2

8

2

8

2

2

2

2

2

2

2

2

2

2

8

2

1 3

4

1

3 4

1 3 4

1 3 4

1 3

4

1 3

4

1 3 4

1 3

4

1 3 4

1 3

4

1 3 4

1 3 4

1 3 4

VAV

1-143

VAV

3-101

VAV

1-141

1

3 4

VAV

1-142

VAV

3-103

VAV

3-102

VAV

1-133

VAV

3-100

VAV

1-130

VAV

1-131

1 3

4

VAV

1-136

VAV

2-100

VAV

2-101

VAV

1-140

VAV

1-139

VAV

1-132

VAV

1-138

1 3

4

2

5

5

5

5

5

5

5

5

5

8

8

5

5

5

5

5

5

5

5

6

2

1 3

4

77

7

7

8

PROVIDE A PENETRATION FIRESTOP SYSTEM AT EACH

NEW PENETRATION OF EXISTING RATED WALLS

REQUIRED FOR NEW DDC FC BUS AND 24V CONTROL

WIRING PER SPEC SECTION 078413, OR INSTALL

EZ-PATH SERIES 33 FIRE RATED PATHWAY, NO

SUBSTITUTIONS. REFER TO LIFE SAFETY PLANS G101

AND G102 FOR EXISTING RATED WALL LOCATIONS.

UTILIZE ANY EXISTING PENETRATION FIRESTOP

SYSTEM LOCATED IN AN EXISTING RATED WALL IN LIEU

OF ADDING NEW IF SUCH DEVICE HAS CAPACITY FOR

MORE CABLES. REVIEW WITH OWNER'S

REPRESENTATIVE PRIOR TO USING EXISTING

PENETRATION FIRESTOP SYSTEM.

9

10

10

7

7

2

1

2

3

4

RAC

JPS

FIRST FLOOR - NEW WORK

PLAN

NORTH

SCALE:

FIRST FLOOR - NEW WORK

1/8" = 1'-0"

1

16'8'4'1'

SCALE: 1/8" = 1'-0"

5

6

SCALE:

KEY MAP

NOT TO SCALE

7

8

9

10

DANIEL PHELAN

PE-2017030573

Page 9: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

VAV

3-200

VAV

2-203

VAV

2-202

VAV

2-200

VAV

2-204

VAV

2-205

7

6

6

6

1 3 4

6

6

7

7

7

7

2

VAV

2-201

6

1

3 4

2

2

2

2

2

2

2

2

1 3 4

1 3 4

1 3 4

1

3

4

1 3 4

1 3 4

1 3 4

5-TON LIEBERT

UNIT

T

T

T

T

T

T

T

T

VAV

3-205

VAV

3-207

VAV

3-206

VAV

3-208

VAV

3-202

VAV

3-203

VAV

3-204

VAV

3-201

EXISTING 12"Ø

SA DOWN, AHU-2

8

5

5

5

5

5

5

5

5

5

5

5

5

5

5

5

T

9

T

T

T

T

T

10

10

PROVIDE A PENETRATION FIRESTOP SYSTEM AT EACH

NEW PENETRATION OF EXISTING RATED WALLS

REQUIRED FOR NEW DDC FC BUS AND 24V CONTROL

WIRING PER SPEC SECTION 078413, OR INSTALL

EZ-PATH SERIES 33 FIRE RATED PATHWAY, NO

SUBSTITUTIONS. REFER TO LIFE SAFETY PLANS G101

AND G102 FOR EXISTING RATED WALL LOCATIONS.

UTILIZE ANY EXISTING PENETRATION FIRESTOP

SYSTEM LOCATED IN AN EXISTING RATED WALL IN LIEU

OF ADDING NEW IF SUCH DEVICE HAS CAPACITY FOR

MORE CABLES. REVIEW WITH OWNER'S

REPRESENTATIVE PRIOR TO USING EXISTING

PENETRATION FIRESTOP SYSTEM.

1 3 4

T 2

VAV

2-206

5

11

10

10

10

SCALE:

SECOND FLOOR - NEW WORK

1/8"=1'-0"

1

NORTH

RAC

JPS

SECOND FLOOR - NEW

WORK

16'8'4'1'

SCALE: 1/8" = 1'-0"

1

2

3

4

5

6

7

8

SCALE:

KEY MAP

NOT TO SCALE

9

10

11

DANIEL PHELAN

PE-2017030573

Page 10: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

RAC

JPS

FIRST FLOOR REFERENCE

PLAN

NORTH

SCALE:

FIRST FLOOR REFERENCE

1/8" = 1'-0"

1

16'8'4'1'

SCALE: 1/8" = 1'-0"

SCALE:

KEY MAP

NOT TO SCALE

DANIEL PHELAN

PE-2017030573

Page 11: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

RAC

JPS

SCHEDULES AND DETAILS

AIR TERMINAL UNIT SCHEDULE

NEW PLAN MARK

MODEL TYPE

INLET DUCT

SIZE (IN RND)

OCCUPIED FLOWS

NOTES

(CFM)

FLOW (GPM)

CONTROL

VALVE

(NOTE 2)

MFR.

LEGACY PLAN MARK

MAX. FLOW

NOTES:

AIR TERMINAL UNIT LISTED IN SCHEDULE IS EXISTING. CONTRACTOR TO FIELD VERIFY INLET SIZE NOTED IN SCHEDULE. SIZES WERE TAKEN FROM OWNER DRAWINGS DATED 06-01-1995 AND FIELD OBSERVATIONS.

EXISTING PNEUMATIC CONTROL VALVES ARE EXISTING TO REMAIN UNLESS ALTERNATE #1 OR ALTERNATE #2 IS ACCEPTED.

COOLING MAXIMUM PRIMARY AIRFLOW AND REHEAT COIL WATER FLOW NOTED IN SCHEDULE WERE TAKEN FROM OWNER DRAWINGS DATED 06-01-1995.

EXISTING HEATING HOT WATER FLOW UNKNOWN.

EXISTING COOLING MAXIMUM PRIMARY AIRFLOW, COOLING MINIMUM PRIMARY AIRFLOW, AND HEATING OCCUPIED AIRFLOW ARE UNKNOWN. EXISTING SCHEDULES INDICATING AIRFLOWS AND DRAWINGS INDICATING ROOMS SERVED BY

EXISTING AIR TERMINAL UNIT ARE NOT AVAILABLE. AIRFLOW WILL BE MEASURED BY OWNER DURING PROGRAMMING OF NEW AIR TERMINAL UNIT DDC CONTROLLER.

AIR TERMINAL UNIT IS PROVIDED IN A SEPARATE PROJECT, MU PROJECT #CP180991, UNIVERSITY OF MISSOURI TEACHING HOSPITAL ED CT SCANNER RENOVATION.

EXISTING AIR TERMINAL UNIT AIRFLOW IS TO BE RE-BALANCED IN A SEPARATE PROJECT, MU PROJECT #CP180991, UNIVERSITY OF MISSOURI TEACHING HOSPITAL / ED CT SCANNER RENOVATION.

1.

2.

3.

4.

5.

6.

7.

COOLING HEATING

(CFM)

MIN. FLOW

(CFM)

MIN. FLOW

UN-OCCUPIED FLOWS

(CFM)

MIN. FLOW

(CFM)

MIN. FLOW

HEATINGCOOLING

HOT WATER

HEATING

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

---

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

TITUS PESV

9"

9"

8"

8"

---

9"

9"

6"

7"

6"

9"

6"

10"

8"

8"

6"

8"

---

700

535

---

350

410

640

500

480

330

600

SINGLE DUCT PRESSURE INDEPENDENT

6" 380

265

660

10"

10"

10"

10"

8"

8"

10"

10"

6"

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

PESV

PESV

PESV

PESV

PESV

PESV

PESV

PESV

TITUS PESV

TITUS PESV

TITUS PESV

TITUS

TITUS

TITUS

PESV

PESV

PESV

TITUS PESV

TITUS

TITUS

TITUS

---

TITUS

TITUS

PESV

PESV

PESV

---

PESV

PESV

TITUS

TITUS

TITUS

TITUS

TITUS

PESV

PESV

PESV

PESV

PESV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

1-130

1-131

1-132

1-133

1-134

1-135

1-136

1-137

1-138

1-139

1-140

1-141

1-142

2-100

2-101

3-100

3-101

3-102

3-103

3-200

3-201

3-202

3-203

3-204

3-205

3-206

3-207

3-208

VAV 1-143

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

2-WAY

2-WAY

2-WAY

2-WAY

---

---

2-WAY

---

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

2-WAY

1.5

1.5

1.0

1.0

---

---

1.5

---

1.5

0.7

1.0

(NOTE 4)

1.5

0.7

2.0

1.0

1.0

0.7

1.0

2-WAY0.7

7

1, 3

7

6

6

7

6

7

---

--- ------ ---

---

--- ------ ---

------

--- ------

------

------

1, 3

75350

535535

615 75310

--- ------

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

------

35175 1, 3

1, 3

1, 5

1, 3

1, 3

35

45205

75320

35190

1, 3

1, 3

1, 3

1, 3

1, 3

1, 3

1, 5

1, 5

1, 5

1, 5

1, 5

1, 5

1, 5

1, 5

1, 5

(NOTE 4)

(NOTE 4)

(NOTE 4)

(NOTE 4)

(NOTE 4)

(NOTE 4)

(NOTE 4)

(NOTE 4)

(NOTE 4)

95

95

95

60

60

95

95

35

95

35

35

60

60

60

95

135

330

250

240

165

300

SINGLE DUCT PRESSURE INDEPENDENT

SINGLE DUCT PRESSURE INDEPENDENT

---

---

---

---

75

535

75

---

---

35

35

45

75

35

95

95

95

60

60

95

95

35

95

35

35

60

60

60

95

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

(NOTE 5)

---

---

---

---

350

535

310

---

---

175

205

320

190

135

330

250

240

165

300

(NOTE 5) (NOTE 5)

SINGLE DUCT PRESSURE INDEPENDENT

TITUS PESV 16"VAV 2-206 --- --- 2-WAY(NOTE 5) 1, 5(NOTE 4)235 235(NOTE 5) (NOTE 5)

DANIEL PHELAN

PE-2017030573

Page 12: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

GENERAL:

THE CONTRACTOR SHALL SUBMIT ENGINEERED CONTROL DRAWINGS, WIRING DIAGRAMS, EQUIPMENT SCHEDULES, ETC., AS REQUIRED FOR A COMPLETE CONTROL SYSTEM.

THE CONTRACTOR WILL BE EXPECTED TO WORK OUT THE DETAILS OF NORMALLY OPEN/NORMALLY CLOSED CONNECTIONS, EXACT EQUIPMENT REQUIREMENTS, ETC., TO

PROVIDE A WORKING CONTROL SYSTEM TO ACHIEVE THE SEQUENCES OF OPERATION BELOW AND NOTED ELSEWHERE ON THE TEMPERATURE CONTROL DRAWINGS. THE

WRITTEN SEQUENCE OF OPERATION SHALL BE THE CRITERION USED TO JUDGE THE FINAL PERFORMANCE OF THE CONTROL SYSTEM. ALL FUNCTIONS IN THE SEQUENCE

WILL BE REQUIRED EVEN IF THE REQUIRED EQUIPMENT AND CONNECTIONS ARE NOT DEPICTED ON THESE DRAWINGS.

CONTRACTOR SHALL PROVIDE AS-BUILT DIAGRAM OF NETWORK BUS ROUTING PER SPEC SECTION 23 0900.

THE UNIVERSITY OF MISSOURI - COLUMBIA UTILIZES JOHNSON CONTROLS EQUIPMENT FOR THEIR CAMPUS ENERGY MANAGEMENT CONTROL SYSTEM (EMCS). NEW DDC

CONTROL SYSTEM SHALL FULLY INTERFACE WITH THE CAMPUS JOHNSON CONTROLS METASYS SYSTEM.

AIR TERMINAL (VAV) UNITS: CONTRACTOR IS RESPONSIBLE FOR ENTERING THE AIRFLOW SETPOINTS AS NOTED IN THE SCHEDULE ON SHEET M600 INTO EACH VAV BOX

PROGRAM. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE CORECT VAV BOX INLET DIAMETER AND ENTERING THE CORRESPONDING AREA INTO THE VAV BOX

PROGRAM. THE CONTRACTOR IS RESPONSIBLE FOR ENTERING THE DEFAULT GAIN OF 2.0 INTO THE VAV BOX PROGRAM FOR EACH VAV BOX.

SEQUENCE OF OPERATION

RAC

JPS

TEMPERATURE CONTROLS

FC COMMUNICATION BUS

WIRE DAISY CHAINED TO

PREVIOUS VMA CNTRLR

LOW VOLTAGE

WIRE

7

AIR FLOW

MEASURING

TAPS

FC COMMUNICATION BUS

WIRE DAISY CHAINED TO

NEXT VMA CONTROLLER

1

SUPPLY AIR

SENSOR

6

AIR VALVE

DAMPER

NETWORK

SENSOR

T

M

2

CONTROLLER WILL BE OWNER FURNISHED AND CONTRACTOR INSTALLED. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES.

PROGRAMMING WILL BE DONE BY OWNER. COMMISSIONING WILL BE DONE BY CONTRACTOR.

NETWORK SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. NETWORK SENSOR WILL BE JCI NS SERIES.

FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED

AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.

NOT USED.

CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.

VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE. PROVIDED, INSTALLED, & WIRED TO

CONTROLLER BY CONTRACTOR.

FUSE LOCATED WITHIN 3 FT. OF VMA CONTROLLER.

LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.

VALVE WITH PROPORTIONAL 0-10 VOLT ACTUATOR OR EQUIVALENT.

SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.

1

2

3

4

5

6

7

8

9

10

3

5

3

ELECTRIC

ACTUATOR

9

8

VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE NOTED, ALL

CONTROL WORK SHALL BE BY CONTRACTOR.

CAPS FOR VAV DP TEST PORTS MUST BE 1/4" BRASS PLUGS.

1.

2.

SA BUS

WIRE

10

AIR IN AIR OUT

NC

HWS HWR

DDC VMA

CONTROLLER

SECONDARY LINE CAN BE RAN IN SAME CONDUIT AS FC BUS

ENCLOSED POWER SUPPLY MUST BE LOCATED IN EXISTING ELECTRICAL ROOMS AS INDICATED ON THE PLANS AND BE

ACCESSIBLE. ANY OTHER LOCATION MUST BE APPROVED BY THE OWNER'S REPRESENTATIVE.

1.

2.

EACH SECONDARY OUTPUT LINE CAN POWER 3-5 VAV CONTROLLERS MAXIMUM (100 VA) BY MECHANICAL CONTRACTOR.

PRIMARY LINE INFO: 480/277/240/120 Vac, #12 AWG MINIMUM BY ELECTRICAL CONTRACTOR.

SECONDARY LINE INFO: 24 Vac, #12-26 AWG, 100 VA. MAX LENGTH 175 FEET USING #14 AWG BY MECHANICAL CONTRACTOR.

DISCONNECT SWITCH REQUIRED, EXTERNALLY MOUNTED WITHIN 12 INCHES OF RIB POWER SUPPLY BY ELECTRICAL CONTRACTOR.

500VA POWER SUPPLY - INCLUDED IN RIB MODEL# PSH500A OR APPROVED EQUIVALENT. POWER SUPPLY TO BE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. SEE PLANS FOR LOCATIONS.

ALL SECONDARY LINES MUST BE LABELED IN ENCLOSURE AS TO WHICH VAV'S THEY POWER PRIOR TO ENERGIZING POWER SUPPLY BY MECHANICAL CONTRACTOR.

A SEPARATE 3 AMP FUSE IS REQUIRED WITHIN 3 FEET OF EACH VAV BY MECHANICAL CONTRACTOR.

1

2

3

4

5

24V

COM

24V

COM

24V

COM

24V

COM

24V

COM

480

277

240

120

COM

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

RIB AC

BREAKER

SWITCH

POWER

SUPPLY/

TRANSFORMER

(FUSE)

6

7

100 VA

100 VA

100 VA

100 VA

100 VA

DISCONNECT

SWITCH

PSH500A

ENCLOSED AC POWER SUPPLY

FC COMMUNICATION BUS

WIRE DAISY CHAINED TO

PREVIOUS VMA CNTRLR

FC COMMUNICATION BUS

WIRE DAISY CHAINED TO

NEXT VMA CONTROLLER

1

SUPPLY AIR

SENSOR

6

AIR VALVE

DAMPER

NETWORK SENSOR

T

M

2

CONTROLLER WILL BE OWNER FURNISHED AND CONTRACTOR INSTALLED. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES.

PROGRAMMING WILL BE DONE BY OWNER. COMMISSIONING WILL BE DONE BY CONTRACTOR.

NETWORK SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. NETWORK SENSOR WILL BE JCI NS SERIES.

FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED

AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.

NOT USED.

CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.

VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE. PROVIDED, INSTALLED, & WIRED TO

CONTROLLER BY CONTRACTOR.

FUSE LOCATED WITHIN 3 FT. OF VMA CONTROLLER.

LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.

EP TRANSDUCER SHALL HAVE 0-10 VDC INPUT, 0-20 PSI HIGH VOLUME OUTPUT (500 SCIM MIN. AIR

CAPACITY). JCI MODEL EP-8000-2 OR EQUAL. CONTRACTOR FURNISHED AND INSTALLED.

SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.

IN-LINE FILTER AND PRESSURE GAUGES PROVIDED BY CONTRACTOR.

1

2

3

4

5

6

7

8

9

10

11

3

10

5

3

8

VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE NOTED, ALL

CONTROL WORK SHALL BE BY CONTRACTOR.

IF VAV HAS DP TEST PORTS AND RUBBER CAPS, CAPS MUST BE REPLACED WITH 1/4" BRASS PLUGS.

1.

2.

IN-LINE FILTER

CONTROL AIR

TUBING (TYP.)

MAIN

AIR

M

9

VALVE EP

TRANSDUCER

9

SA BUS

WIRE

11

7

AIR OUT

DDC VMA

CONTROLLER

NC

EP

HWS HWR

LOW VOLTAGE

WIRE

AIR FLOW

MEASURING

TAPS

AIR IN

1

4

2

3

6

5

7

SCALE:

VAV BOX CONTROL DIAGRAM WITH REHEAT - ALTERNATE #1 AND #2

N.T.S.

B

2

SCALE:

500 VA POWER SUPPLY DIAGRAM

N.T.S.

C

SCALE:

VAV BOX CONTROL DIAGRAM WITH PNEUMATIC CONTROL VALVE - BASE BID

N.T.S.

A

FC BUS TO BE CONTINUOUS DAISY CHAIN WITHOUT SPLICES.

CONNECTIONS CAN ONLY BE MADE AT CONTROLLERS. SEE PLANS FOR

QUANTITY AND LOCATIONS OF VAV CONTROLLERS.

CONTRACTOR WILL MAKE TERMINATION CONNECTIONS AT PANELS.

LOCATE PANELS IN SAME ROOM AS EQUIPMENT SERVED.

FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED,

TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING,

DESCRIPTED AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY

WINDY CITY WIRE, CONSTRUCTED BY CABLE-TEK, OR APPROVED

EQUIVALENT.

COORDINATE FIELD ROUTING WITH OWNERS REPRESENTATIVE.

EXTEND FC BUS FROM EITHER EXISTING VAV 1-127 OR VAV 1-128, REFER

TO SHEET M101. FIELD VERIFY WHICH EXISTING AIR TERMINAL UNIT CAN

BE UTILIZED. COORDINATE WITH OWNERS REPRESENTATIVE.

VAV VAVVAV

EXIST

VAV

VAV VAVVAV

SCALE:

FC BUS SCHEMATIC DIAGRAM

N.T.S.

D

5

5

1.

2.

3.

4.

DANIEL PHELAN

PE-2017030573

Page 13: BID SET UNIVERSITY OF MISSOURI TEACHING HOSPITAL …operations-webapps.missouri.edu/pdc/adsite/projects/cp171062/plans/CP... · npsh nom net positive suction head nominal ot oil trap

E

E

2

EXISTING

PANEL LQ1ER

LQ1ER-29 3

1

4

5

5

5

5

E

2

LQ1ER-313

4

1

5

5

KFM

GMC

ELECTRICAL PARTIAL FLOOR

PLANS

GENERAL SHEET NOTES:

1. VERIFY POWER SUPPLY LOCATIONS WITH OWNER'S REPRESETATIVE PRIOR

TO COMMENCEMENT OF WORK.

2. REFER TO MECHANICAL DETAIL C/M700 500VA POWER SUPPLY DIAGRAM FOR

ADDITIONAL INFORMATION.

3. UPDATE PANEL DIRECTORIES WITH NEW LOADS BEING SERVED BY EXISTING

PANELS.

SCALE:

ELECTRICAL PARTIAL SECOND FLOOR PLAN

1/8" = 1' - 0"

2

NORTH

SCALE:

ELECTRICAL PARTIAL FIRST FLOOR PLAN

1/8" = 1' - 0"

1

NORTH

SCALE:

KEY MAP - 1ST FLOOR

NOT TO SCALE

SCALE:

KEY MAP - 2ND FLOOR

NOT TO SCALE

KEYED NOTES:

FURNISH AND INSTALL NEW POWER SUPPLIES TO SERVE NEW MECHANICAL

VAV BOXES. REFER TO MECHANICAL DETAIL C/M700 FOR SPECIFIC MODEL

NUMBER TO BE PROVIDED AND ADDITIONAL INFORMATION REGARDING

INSTALLATION. MOUNT 7'-0" A.F.F. IN APPROXIMATE LOCATION. COORDINATE

FINAL LOCATION WITH OWNER'S REPRESENTATIVE PRIOR TO

COMMENCEMENT OF WORK AND COORDINATE WITH EXISTING CONDITIONS

IN THE ROOM.

PROVIDE LEVITON #1221-2, HUBBELL #HBL1221, OR APPROVED EQUAL 120V,

20A TOGGLE TYPE DISCONNECT SWITCH AND MOUNT ON THE WALL

ADJACENT TO POWER SUPPLIES.

PROVIDE 120V, 20A CIRCUIT TO NEW POWER SUPPLIES FURNISHED AND

INSTALLED BY CONTRACTOR. CONNECT TO NEXT AVAILABLE SPARE 120V,

20A, 1-POLE CIRCUIT BREAKER IN PANEL INDICATED. CIRCUIT NUMBER

INDICATED ON PLAN IS PROVIDED FOR REFERENCE BASED ON PREVIOUS

FIELD INVESTIGATIONS.

UTILIZE THE EXISTING SHAFT FOR CIRCUIT INSTALLATION BETWEEN FIRST

FLOOR PANEL AND POWER SUPPLIES ON THE SECOND FLOOR.

TEMPORARILY REMOVE OR SUPPORT ALL CEILING MOUNTED DEVICES AND

LUMINAIRES IN APPROXIMATE SPACE AS REQUIRED FOR CIRCUIT

INSTALLATION. COORDINATE THIS SCOPE WITH FINAL CIRCUIT PATH

DETERMINED IN THE FIELD.

1

2

PLAN

NORTH

ABBREVIATIONS

LINE TYPE LEGEND

DRAWING REFERENCES ELECTRICAL GENERAL NOTES

NEW WORK BY THIS CONTRACTOR

(DARK, SOLID LINE)

EXISTING TO REMAIN OR NEW WORK BY OTHERS

(LIGHT, SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR

(DARK, DASHED LINE, DEMOLITION PLANS)

NEW WORK BY THIS CONTRACTOR TO BE

INSTALLED UNDERGROUND, OR BELOW FLOOR

(DARK, LONG DASHED LINE)

NORTH ARROW

PLAN DETAIL REFERENCE TITLE

KEYED NOTE DESIGNATION

#

AHU

1

PLAN MARK

EQUIPMENT NUMBER

EQUIPMENT DESIGNATION REFER TO MEP

SCHEDULE FOR CIRCUITING AND DEVICE

REQUIREMENTS AND FLOOR PLANS FOR

LOCATIONS

#

ENLARGED PLAN REFERENCE

E100

1

PLAN MARK

SHEET NUMBER

1. MAKE ALL INSTALLATIONS IN ACCORDANCE WITH THE AMERICANS WITH

DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG) AND/OR ARCHITECTURAL

BARRIERS ACT (ABA).

2. MOUNTING HEIGHTS INDICATED WITHIN PLANS AND SCHEDULES ARE

DIMENSIONED TO THE CENTER LINE OF THE DEVICE, EQUIPMENT, LUMINAIRE,

ETC. UNLESS OTHERWISE NOTED.

3. COORDINATE EXACT EQUIPMENT LOCATIONS WITH OTHER TRADES. EQUIPMENT

LOCATIONS SHOWN ON ELECTRICAL PLANS ARE DIAGRAMMATICAL ONLY AND

MIGHT NOT BE EXACT.

4. CIRCUIT IDENTIFICATION NUMBERS BESIDE ELECTRICAL DEVICES AND

CONNECTION POINTS ON PLANS CORRESPOND TO AN OVERCURRENT DEVICE IN

THE DESIGNATED PANELBOARD. NOTE ALL CIRCUIT NUMBER CHANGES MADE IN

THE FIELD AT EACH ELECTRICAL DEVICE AND CONNECTION POINT. ALSO

CORRECT THE DIRECTORIES AND DEVICE MARKINGS AT PANELBOARDS,

SWITCHBOARDS AND SWITCHGEAR TO ACCURATELY REFLECT THE AS-BUILT

CONDITIONS.

5. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILINGS, ETC. UNLESS

OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT

ROUTED IN MECHANICAL ROOMS, ELECTRICAL ROOMS, AND STORAGE ROOMS

WITHOUT CEILINGS MAY BE ROUTED EXPOSED.

6. COORDINATE VERTICAL CONDUIT ROUTING TO WALL MOUNTED DEVICES TO

ENSURE DEVICES LOCATED WITHIN AN 18-INCH HORIZONTAL DIMENSION WILL BE

CENTER-ALIGNED VERTICALLY.

7. FIELD COORDINATE ALL ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT

MOUNTING LOCATIONS TO AVOID ENCROACHMENT OF OPERATION AND ACCESS

TO EQUIPMENT FROM OTHER TRADES. COORDINATE THE APPROPRIATE

MOUNTING LOCATION WITH THE AFFECTED DISCIPLINES WHEN EQUIPMENT IS

SPECIFIED TO BE MOUNTED ONTO THE SURFACE OF ANOTHER DISCIPLINE'S

EQUIPMENT.

8. REPAIR ALL OPENINGS MADE IN EXISTING WALLS, PARTITIONS, ETC TO

ACCOMMODATE WORK OF THIS DISCIPLINE TO MATCH THE SURROUNDING

CONDITIONS, USING WORKERS QUALIFIED IN THE APPROPRIATE TRADE.

APPROPRIATELY GROUT OR SEAL ALL CONDUITS THROUGH WALLS.

9. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND

FLOORS MUST HAVE BEEN TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814

STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS.

10. REPLACE OR REINSTALL ALL PORTIONS OF THE BUILDING (CEILING TILES, WALLS,

ETC) REMOVED TO ACCOMMODATE THE INSTALLATION OF ANY ELECTRICAL

DEVICE, EQUIPMENT, ETC., USING WORKERS QUALIFIED IN THE APPROPRIATE

TRADE.

A.F.F : ABOVE FINISHED FLOOR

C : CONDUIT

E.C. : ELECTRICAL CONTRACTOR

ER : EXISTING RELOCATED

ETR : EXISTING TO REMAIN

EWC : ELECTRIC WATER COOLER

G.C. : GENERAL CONTRACTOR

GND : GROUND

TYP. : TYPICAL

U.O.N. : UNLESS OTHERWISE NOTED

3

WIRING PLANS

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT CAPPED FOR FUTURE.

HOMERUN TO PANEL OR DESTINATION NOTED

PROVIDE WIRING REQUIRED BY THE CIRCUITING AND SWITCHING

REQUIREMENTS FOR THE PARTICULAR CIRCUITS INVOLVED. TYPICAL

120V HOMERUNS SHALL CONSIST OF #12 AWG CONDUCTORS IN 3/4"

CONDUIT MINIMUM UNLESS INDICATED OTHERWISE. NO SHARED

NEUTRALS SHALL BE ALLOWED. A MAXIMUM OF NINE CURRENT-

CARRYING CONDUCTORS ARE ALLOWED IN A RACEWAY. NEUTRAL

CONDUCTORS ARE ALSO CONSIDERED CURRENT-CARRYING

CONDUCTORS. FOR CIRCUITS EXCEEDING 75'-0" IN LENGTH, PROVIDE

THE NEXT LARGER WIRE SIZE FOR THE CIRCUIT AMPACITY.

WHERE NUMBER OF CURRENT-CARRYING CONDUCTORS IN A RACEWAY

EXCEEDS THREE, THE ALLOWABLE AMPACITY OF EACH CONDUCTOR

SHALL BE REDUCED AS SHOWN IN THE ADJUSTMENT FACTOR TABLE IN

THE NATIONAL ELECTRIC CODE. LOAD DIVERSITY FACTORS SHALL NOT

BE USED IN SIZING CONDUCTORS. NEUTRAL CONDUCTORS SHALL BE

COUNTED AS CURRENT-CARRYING CONDUCTORS.

1.

2.

POWER EQUIPMENT

PANELBOARD (SURFACE)

PANELBOARD (FLUSH)

WIRING DEVICES, RECEPTACLES - MISC.

ELECTRICAL CONNECTION: CEILING MOUNTED

ELECTRICAL CONNECTION: WALL MOUNTED

E

E

J

JUNCTION AND PULL BOXES

PULL BOX

JUNCTION BOX : CEILING OR FLOOR MOUNTED. SIZE

PER N.E.C. REQUIREMENTS.

JUNCTION BOX : WALL MOUNTED. SIZE PER N.E.C.

REQUIREMENTS.

J

P

TOGGLE TYPE DISCONNECT SWITCH

4

5

MICHAEL D. SWANSON

PE-2013000637