bid set university of missouri teaching hospital...
TRANSCRIPT
DRAWING INDEX
UNIVERSITY OF MISSOURI TEACHING HOSPITAL
BAS UPGRADES, ED AHU-1, 2 & 3
MU PROJECT NO. CP171062
FOR THE CURATORS OF THE
UNIVERSITY OF MISSOURI
ENGINEER / ARCHITECT:
ENGINEER:
ROSS & BARUZZINI
6 SOUTH OLD ORCHARD
ST. LOUIS, MO 63119
(314) 918-8383
ARCHITECT:
bc DESIGN GROUP
200 NE MISSOURI ROAD
SUITE 200
LEE'S SUMMIT, MO 64086
DESIGN TEAM
JANUARY 31, 2019
GENERAL
G000: COVER SHEET
G001: PHASING - INFECTION CONTROL
G101: FIRST FLOOR - LIFE SAFETY PLAN
G102: SECOND FLOOR - LIFE SAFETY PLAN
MECHANICAL
M000: MECHANICAL SYMBOLS, ABBREVIATIONS & GENERAL NOTES
MD101: FIRST FLOOR - DEMOLITION
MD102: SECOND FLOOR - DEMOLITION
M101: FIRST FLOOR - NEW WORK
M102: SECOND FLOOR - NEW WORK
M101 - REF: REFERENCE FIRST FLOOR HVAC PLAN
M600: SCHEDULES AND DETAILS
M700: TEMPERATURE CONTROLS
ELECTRICAL
E001: ELECTRICAL PARTIAL FLOOR PLAN
MU AHJ CODES ENFORCED:
INTERNATIONAL BUILDING CODE 2015
INTERNATIONAL FIRE CODE 2015
INTERNATIONAL MECHANICAL CODE 2015
NATIONAL ELECTRICAL CODE 2014
NFPA 101 LIFE SAFETY CODE 2012
NFPA 72 NATIONAL FIRE ALARM CODE 2013
NFPA 99 HEALTH CARE FACILITIES CODE 2012
ASHRAE STANDARD 90.1 - 2013
G000
RAC
JPS
COVER SHEET
2012 LIFE SAFETY CODE REFERENCED STANDARDS:
NATIONAL ELECTRICAL CODE 2011
NFPA 72 NATIONAL FIRE ALARM CODE 2010
I HEREBY CERTIFY THAT DRAWING SHEET G001 HAS BEEN PREPARED
BY ME, OR UNDER MY SUPERVISION. I FURTHER CERTIFY THAT TO THE
BEST OF MY KNOWLEDGE THESE DRAWINGS AND/ OR SPECIFICATIONS
ARE AS REQUIRED BY AND IN COMPLIANCE WITH BUILDING CODES OF
THE UNIVERSITY OF MISSOURI.
I HEREBY CERTIFY THAT G000, G101, G102, M000, MD101, MD102, M101,
M102, M600, M700 AS WELL AS SPECIFICATION DIVISIONS 07 AND 23
HAVE BEEN PREPARED BY ME, OR UNDER MY SUPERVISION. I FURTHER
CERTIFY THAT TO THE BEST OF MY KNOWLEDGE THESE DRAWINGS
AND/ OR SPECIFICATIONS ARE AS REQUIRED BY AND IN COMPLIANCE
WITH BUILDING CODES OF THE UNIVERSITY OF MISSOURI.
I HEREBY CERTIFY THAT E001 AS WELL AS SPECIFICATION DIVISION 26
HAVE BEEN PREPARED BY ME, OR UNDER MY SUPERVISION. I FURTHER
CERTIFY THAT TO THE BEST OF MY KNOWLEDGE THESE DRAWINGS
AND/ OR SPECIFICATIONS ARE AS REQUIRED BY AND IN COMPLIANCE
WITH BUILDING CODES OF THE UNIVERSITY OF MISSOURI.
1.31.2019
BID SET
1.31.2019
SM SM SM
SMSM
SM SM SM
SM
SM SM
SM SM SM SM SM SM SM
SM
SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM
SMSM
SMSM
SMSM
SM
SMSM
SM
SMSM
SMSM
SMSM
SM
SM
SMSM
SMSM
SM
SMSM
SMSM
SMSM
SM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SM
SM
SMSM
SM
SM
SMSM
SM
SM
SMSM
SMSM
SMSM
SMSM
SM
SM
SM SM SM SM SM SM
SMSM
SMSM
2HR 2HR
2HR2HR
2HR
2HR2HR
2HR2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR
2HR
2HR
2HR2HR2HR2HR
2HR2HR
2HR 2HR 2HR 2HR
2HR2HR
2HR
2HR 2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR2HR2HR2HR2HR2HR
2HR2HR
2HR 2HR 2HR 2HR 2HR 2HR 2HR
2HR2HR
2HR
2HR
2HR 2HR
2HR2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR 2HR 2HR 2HR 2HR 2HR 2HR
2HR
2HR
2HR
2HR
2HR2HR2HR
2HR2HR
2HR 2HR 2HR
CODE LEGEND:
3HR 3HR 3HR 3HR
2HR 2HR 2HR 2HR
1HR 1HR 1HR 1HR
SM SM SM SM
3 HOUR FIRE BARRIER
2 HOUR FIRE WALL
1 HOUR FIRE WALL
SMOKE BARRIER
SCALE:
FIRST FLOOR - LIFE SAFETY1/8"=1'-0"1
NORTH 16'8'4'1'
SCALE: 1/8" = 1'-0"
RAC
JPS
FIRST FLOOR - LIFE SAFETY
DANIEL PHELAN
PE-2017030573
SMSMSMSM
SMSM
SMSM
SMSMSMSMSM
SMSMSM
SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM SM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SMSM
SM SM SM SM SM SM SM SM SM SM SM SM SM SM
SMSM
SMSM
SM
SMSMSM
SMSM
SM SM
SMSM
SMSM
SMSMSM
SMSM
SMSM
SMSM
SMSM
2HR
2HR2HR 2HR2HR2HR2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR
2HR2HR
2HR 2HR
2HR
2HR
2HR
2HR
2HR 2HR 2HR 2HR
2HR
2HR
2HR2HR2HR2HR2HR
2HR2HR
2HR 2HR 2HR 2HR 2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR
2HR2HR
2HR 2HR
2HR
2HR
2HR
2HR
2HR 2HR 2HR 2HR 2HR
2HR
2HR
2HR2HR2HR2HR2HR2HR
2HR 2HR 2HR
2HR2HR
2HR2HR
2HR 2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR
2HR2HR2HR
2HR2HR
2HR 2HR 2HR
2HR2HR
2HR2HR
2HR2HR
2HR
2HR 2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR 2HR 2HR
2HR2HR
2HR
2HR2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR2HR
2HR2HR
2HR 2HR
2HR
2HR
2HR2HR2HR2HR2HR
2HR2HR
2HR 2HR 2HR 2HR 2HR
2HR
2HR
2HR2HR2HR2HR2HR2HR2HR
2HR2HR
2HR 2HR 2HR 2HR 2HR 2HR 2HR
2HR
2HR
2HR2HR2HR2HR2HR2HR2HR
2HR2HR
2HR 2HR 2HR 2HR 2HR 2HR 2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
2HR
SCALE:
SECOND FLOOR - LIFE SAFETY1/8"=1'-0"1
NORTH
RAC
JPS
SECOND FLOOR - LIFE SAFETY
16'8'4'1'
SCALE: 1/8" = 1'-0"
CODE LEGEND:
3HR 3HR 3HR 3HR
2HR 2HR 2HR 2HR
1HR 1HR 1HR 1HR
SM SM SM SM
3 HOUR FIRE BARRIER
2 HOUR FIRE WALL
1 HOUR FIRE WALL
SMOKE BARRIER
DANIEL PHELAN
PE-2017030573
KEYED NOTE
GENERAL SYMBOLS
SECTION NUMBER
SHEET WHERE LOCATED
INTERFACE, EXISTING TO NEW
PITCH DOWN IN DIRECTION OF ARROW
CWS
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
PIPING SYMBOLS
HWS
HWR
HEATING WATER SUPPLY
HEATING WATER RETURN
THERMOSTAT (NIGHT)
N
THERMOSTAT
HUMIDISTAT
PIPE ANCHOR
TEE DOWN
TEE UP
ELBOW UP
ELBOW DOWN
HEAT RECOVERY UNITHRU
GAUGE COCK
FLEXIBLE PIPE COUPLING
CALIBRATED ORIFICE BALANCE VALVE
CAP
SOLENOID VALVE
PRESSURE REGULATING VALVE
PRESSURE GAUGE W/COCK
THERMOMETER
AIR VENT (M-MANUAL, A-AUTO)
FLANGE
CONCENTRIC REDUCER/INCREASER
PUMP DISCHARGE VALVE
WATER COLUMN
WET BULB
WC
WB
UC UNDERCUT DOOR
WATT OR WIDTH (PER CONTEXT)W
VOL
VOLUME DAMPER (MANUAL)VD
VOLTSV
VOLUME
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
LWT LEAVING WATER TEMPERATURE
HVAC HEATING, VENTILATING
ENTERING WATER TEMPERATUREEWT
EXISTINGEXIST, EX
EXTERNAL STATIC PRESSUREESP
BOTTOM OF PIPEBOP
APD AIR PRESSURE DROP
# x # DUCT SIZE, FIRST FIGURE IS SIDE SHOWN
ACCESS PANEL, TOP OR SIDE
TURNING VANES
CHANGE OF ELEVATION - RISE (R) OR DROP (D)
R
FLEXIBLE DUCT CONNECTION
FLEXIBLE DUCT
AFF
CONCRETECONC
CAST IRONCI
CFM
BTUH
BOD
BOB
CONDENSING UNIT
COMPUTER ROOM AIR CONDITIONING UNITCRU
CU
UNIT NUMBER
EQUIPMENT DESIGNATION
EQUIPMENT
EAT
EXHAUST AIR OR EACH (PER CONTEXT)EA
DOWNDN
DIAMETERDIA
DRY BULBDB
FEETFT
GALVANIZEDGALV
GALLONSGAL
GAUGEGA
FT-HD
EXHAUSTEXH
VAV
SUPPLY FANSF
SMOKE DAMPERSD
MD
HUMIDIFIERH
VARIABLE AIR VOLUME BOX
MOTORIZED DAMPER
HEAD IN FEET
ENTERING AIR TEMPERATURE
CUBIC FEET PER MINUTE
BRITISH THERMAL UNITS PER HOUR
BOTTOM OF DUCT
BOTTOM OF BEAM
ABOVE FINISHED FLOOR
GENERAL
STRAINER
RELIEF VALVE (TEMP/PRESS)
THREE-WAY CONTROL VALVE
TWO-WAY CONTROL VALVE
CHECK VALVE
BUTTERFLY VALVE
GLOBE VALVE
BALL VALVE
PIPE LINE EQUIPMENT
UNION
LAT
KILOWATTSKW
HORSEPOWERHP
HEADHD
GPM
OA
NTS
NIC
NO
NC
MINIMUM OR MINUTE (PER CONTEXT)MIN
MBH
MAXIMUMMAX
RH
RETURN AIRRA
PSIG
PD
TOTAL DYNAMIC HEADTDH
SP
SOLENOIDSOL
SENSIBLESENS
SANITARYSAN
STATIC PRESSURE
RELATIVE HUMIDITY
POUNDS PER SQUARE INCH GAUGE
PRESSURE DROP
OUTSIDE AIR
NOT TO SCALE
NOT IN CONTRACT
NORMALLY OPEN OR NUMBER (PER CONTEXT)
NORMALLY CLOSED OR NOISE CRITERIA (PER CONTEXT)
THOUSANDS BRITISH THERMAL UNITS PER HOUR
LEAVING AIR TEMPERATURE
GALLONS PER MINUTE
RETURN FANRF
UH UNIT HEATER
BEAM SPACEBS
GC GENERAL CONTRACTOR
JS JOIST SPACE
LS LIGHT SPACE
SUPPLY OR OUTSIDE AIR SECTION UP
RETURN AIR SECTION UP
SUPPLY OR OUTSIDE AIR DOWN OR AWAY
RETURN AIR DOWN OR AWAY
CONDENSATECOND
RM ROOM
VTR VENT THRU ROOF
DPT DIFFERENTIAL PRESSURE TRANSMITTER
BLOWER COIL UNIT
AIR HANDLING UNIT
BCU
AHU
PRESSURE REDUCING VALVE
3
PRESSURE/TEMPERATURE TEST PORT
EXPANSION JOINT
PIPE GUIDE
THERMOSTATIC EXPANSION VALVE
SIGHT GLASS
FLOW ARROW
(ACTUAL SIZE INDICATED)
AP
AUTOMATIC DAMPER
MANUAL VOLUME DAMPER
FIRE DAMPER
TYPE OF SERVICE: S = SUPPLY
R = RETURN
E = EXHAUST
T = TRANSFER
AIR QUANTITY
IN CFM
& AIR CONDITIONING
1
M
SMOKE DAMPER
FIRE/SMOKE DAMPER
EXISTING TO BE REMOVED
IN-LINE PUMP
ACC ACCESSORIES
BO BINARY SIGNAL OUTPUT
BI BINARY SIGNAL INPUT
CONN CONNECTION
CORRIDORCORR
CONTROL VALVECV
ELECTRICELEC
ELEV ELEVATION
HR HOUR
IN INCH/INCHES
PRV PRESSURE REGULATING VALVE
SA SUPPLY AIR
SQ SQUARE
TEMP TEMPERATURE
WITHW/
X
M-X
AHU
1
T
T
H
A AIR
ANALOG SIGNAL INPUTAI
AO ANALOG SIGNAL OUTPUT
AVERAGEAVG
ARCHITECTURE/ARCHITECT
APPLICATION PART LOAD VALUEAPLV
AUX AUXILIARY
ARCH
BDD BACK DRAFT DAMPER
BFC BELOW FINISHED CEILING
BHP BRAKE HORSEPOWER
CAPACITYCAP
CONTROLLED CLOSURE DEVICECCD
COOLING DUCT (COLD DUCT)CLG
DEGREESDEG
DEFL DEFLECTION
DBA A-WEIGHTED DECIBELS
DISCHARGEDISCH
DIMENSIONDIM
DIV DIVISION
DETAILDTL
DRAWING(S)DWG(S)
EFFICIENCY
ENERGY EFFICIENT RATIOEER
EFF
EQ EQUAL
DEGREES FAHRENHEITDEG F
FIN
FLR
FPM FEET PER MINUTE
FLOOR
FINISHED
HEIGHTH
HEATING DUCT (HOT DECK)HTG
HERTZ
HW
HZ
HOT WATER
LENGTHL
LINEAR FEETLF
POUND(S)LB(S)
LEVELLVL
MANUALMAN
MANUFACTURER
MECH MECHANICAL
MFR
METALMTL
NPSH
NOM
NET POSITIVE SUCTION HEAD
NOMINAL
OT OIL TRAP
OD OUTSIDE DIAMETER
PHASEPH
PENTHOUSE
PRESSURE
PENT
PPH POUNDS PER HOUR
PRESS
PSI ABSOLUTEPSIA
PSI POUNDS PER SQUARE INCH
QUANTITYQTY
RADIATEDRAD
RPM REVOLUTIONS PER MINUTE
SECTIONSEC'N
SHEETSHT
STATIC PRESSURE DIFFERENTIALSPD
STAINLESS STEELSST
STL STEEL
TOTALTOT
UNO UNLESS NOTED OTHERWISE
VE VIBRATION ELIMINATOR OR ISOLATOR
VEL VELOCITY
WITHOUTW/O
WATER GAUGEWG
WEIGHTWT
WATER PRESSURE DIFFERENTIALWPD
COMBINATION FIRE/SMOKE DAMPERFSD
EF EXHAUST FAN
HEATING COILHC
CONSTANT AIR VOLUMECAV
ENTERING AIR WET BULB TEMPERATUREEWB
FIRE DEPARTMENT CONNECTIONFDC
HORIZONTALHORIZ
INVERT ELEVATIONIE
INDIC INDICATOR
ISP INTERNAL STATIC PRESSURE
PNEUMATICPNEU
SQUARE FOOTSF
STATIC PRESSURE TRANSMITTERSPT
STEAMSTM
SW SOFTENED WATER
TEMPERATURE CONTROLTC
TEMPERATURE AND PRESSURET&P
TD THERMODYNAMIC
UNDERGROUNDUG
VACUUMVAC
VACUUM BREAKERVB
VERTICALVERT
SENSOR (T = TEMPERATURE H = HUMIDITY)
T OR H
S
GRAVITY BACKDRAFT
SUPPLY DIFFUSER, REGISTER OR
GRILLE AS SCHEDULED
RETURN GRILLE OR REGISTER
SLOT DIFFUSER AS SCHEDULED
SIDEWALL GRILLE OR REGISTER
IF NO ARROWS ARE SHOWN ON PLAN, DEFAULT
ARROWS INDICATE DIRECTION OF AIR DISCHARGE.
IS 2-WAY HORIZONTAL FOR SLOT DIFFUSERS,
4-WAY HORIZONTAL FOR SQUARE DIFFUSERS.
AS SCHEDULED
AS SCHEDULED
LUBRICATED PLUG COCK
ECCENTRIC REDUCER/INCREASER
CHILLERCH
NPLV NON-STANDARD PART LOAD VALUE
OC ON CENTER
SENSIBLE HEATSH
STEAM TRAP: IB = INVERTED BUCKET
WATER METER (FLOW TOTALIZING TYPE)M
T
FLOAT & THERMOSTATIC=FT
THERMODYNAMIC DISK=TD
S-1
100
DESIGNATION ABBREVIATIONS
GENERAL
ABBREVIATIONS
FLOW ARROW DOWNSTREAM OF FAN
FLOW ARROW UPSTREAM OF FAN
SCHEDULED
DEVICE NO
# x #
STOP CHECK VALVE
PRESSURE TEST VALVE
Y-PATTERN STRAINER WITH BLOWDOWN
BLOWDOWN VALVE
FLOW OR TEMPERATURE SWITCH
FS TS
OR
# x #
DUCT SIZE
DUCT SIZE
# x #
NEW WORK
EXISTING TO REMAIN
MERV MINIMUM EFFICIENCY REPORTING VALUE (ASHRAE 52.2)
FPF FINS PER FOOT
VALVE IN RISE
M
BUTTERFLY VALVE (MOTORIZED)
STATIC PRESSURE SENSOR
SP
GENERAL NOTES:
APPROXIMATEAPPROX
1. IF THE CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS OR IS NOT SURE OF THEIR MEANING, HE SHOULD
OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION PRIOR TO BID, SINCE THE CONTRACTOR WILL BE HELD
RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.
2. REFER TO ARCHITECTURAL SHEETS FOR THE PHASING OF THE PROJECT. THE EXISTING HVAC SYSTEMS MUST REMAIN IN
OPERATION WHILE THE SPACES REMAIN IN USE.
3. THE CONTRACTOR SHALL COORDINATE STAGING AND SCHEDULING WITH THE OWNER'S REPRESENTATIVE.
4. EXISTING CONDITIONS ARE BASED ON INFORMATION OBTAINED FROM PREVIOUS CONSTRUCTION DOCUMENTS AND
INFORMAL FIELD OBSERVATION AND SHALL NOT BE CONSTITUTED AS "AS BUILT." THE CONTRACTOR SHALL FIELD-VERIFY
EXISTING CONDITIONS BEFORE THE ONSET OF CONSTRUCTION.
5. WHERE CONTRACTOR IS REQUIRED TO CONCEAL NEW WORK, REMOVE OR MODIFY EXISTING CONSTRUCTION OR
EQUIPMENT, OR ATTACH TO EXISTING CONSTRUCTION, THE CONTRACTOR SHALL REPAIR OR REPLACE EXISTING CONSTRUCTION
MATERIALS TO MATCH CONDITIONS AT THE ONSET OF CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REMOVE AND
REPLACE EXISTING CEILINGS AND WALLS REQUIRED FOR INSTALLATION OF MECHANICAL SYSTEMS.
6. THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT AND MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED BY
THE OWNER SHALL BE REMOVED FROM THE PREMISES BY THIS CONTRACTOR.
7. PROVIDE VENTS AT ALL PIPING HIGH POINTS, AND DRAINS AT ALL PIPING LOW POINTS, REGARDLESS OF WHETHER SHOWN OR NOT.
9. THE CONTRACTOR SHALL CONNECT THE NEW HVAC SYSTEM TO THE OWNER'S EXISTING BUILDING CONTROL SYSTEM. REFER TO THE
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
10. THE WORK OF SECTION 230900 SHALL INCLUDE THE FOLLOWING ELECTRICAL WORK, COMPLYING WITH REQUIREMENTS OF DIVISION 26
SPECIFICATIONS.
A. CONTROL WIRING BETWEEN FIELD-INSTALLED CONTROLS, INDICATING DEVICES, AND UNIT CONTROL
PANELS.
B. INTERLOCK WIRING BETWEEN ELECTRONICALLY OPERATED EQUIPMENT UNITS AND BETWEEN
EQUIPMENT AND FIELD-INSTALLED CONTROL DEVICES.
C. POWER SUPPLY WIRING FOR POWER SOURCE TO POWER CONNECTION ON CONTROLS AND/OR UNIT
CONTROL PANELS, INCLUDING, BUT NOT LIMITED TO, AIR TERMINAL UNIT CONTROLLERS, DDC PANELS, DAMPER
ACTUATORS, AND VALVE ACTUATORS.
UNIT NUMBER
DAMPER TYPE DESIGNATION
FSD
1
VFD VARIABLE FREQUENCY DRIVE
RLA RUNNING LOAD AMPS
LOCKED ROTOR AMPSLRA
BRITISH THERMAL UNITBTU
F FAHRENHEIT
TEE-TYPE STRAINER
EX= EXISTING
EXHAUST GRILLE OR REGISTER
AS SCHEDULED
EXHAUST AIR SECTION UP
EXHAUST AIR DOWN OR AWAY
RAC
JPS
MECHANICAL SYMBOLS,
ABBREVIATIONS & GENERAL
NOTES
DANIEL PHELAN
PE-2017030573
2
2
5
2
5
2
2
2
2
2
22
2
2
5
2
1 3 4
1 3 4
1 3 4
1 3 4
1 3 4
1 3 4
1 3 4
1 3 4
1 3 4
1 3 4
1 3 4
1 3
41 3 4
1 3 4
1 3 4
2
5
5
5
2
2
1
2
3
4
SCALE:
FIRST FLOOR - DEMOLITION
1/8"=1'-0"
1
NORTH
RAC
JPS
FIRST FLOOR - DEMOLITION
16'8'4'1'
SCALE: 1/8" = 1'-0"
SCALE:
KEY MAP
NOT TO SCALE
5
DANIEL PHELAN
PE-2017030573
6
5
5
5
1 3 4
5
5
6
6
6
8
6
2
5
1 3 4
2
2
2
2
2
2
2
2
1 3 41 3 4
1 3 4
7
1 3 4
1 3 4
1 3 4
1 3 4
5-TON LIEBERT
UNIT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1 3 4
T 2
1
2
3
4
SCALE:
SECOND FLOOR - DEMOLITION
1/8"=1'=-0"
1
NORTH
RAC
JPS
SECOND FLOOR -
DEMOLITION
5
6
7
16'8'4'1'
SCALE: 1/8" = 1'-0"
SCALE:
KEY MAP
NOT TO SCALE
8
DANIEL PHELAN
PE-2017030573
2
2
8
2
8
2
2
2
2
2
2
2
2
2
2
8
2
1 3
4
1
3 4
1 3 4
1 3 4
1 3
4
1 3
4
1 3 4
1 3
4
1 3 4
1 3
4
1 3 4
1 3 4
1 3 4
VAV
1-143
VAV
3-101
VAV
1-141
1
3 4
VAV
1-142
VAV
3-103
VAV
3-102
VAV
1-133
VAV
3-100
VAV
1-130
VAV
1-131
1 3
4
VAV
1-136
VAV
2-100
VAV
2-101
VAV
1-140
VAV
1-139
VAV
1-132
VAV
1-138
1 3
4
2
5
5
5
5
5
5
5
5
5
8
8
5
5
5
5
5
5
5
5
6
2
1 3
4
77
7
7
8
PROVIDE A PENETRATION FIRESTOP SYSTEM AT EACH
NEW PENETRATION OF EXISTING RATED WALLS
REQUIRED FOR NEW DDC FC BUS AND 24V CONTROL
WIRING PER SPEC SECTION 078413, OR INSTALL
EZ-PATH SERIES 33 FIRE RATED PATHWAY, NO
SUBSTITUTIONS. REFER TO LIFE SAFETY PLANS G101
AND G102 FOR EXISTING RATED WALL LOCATIONS.
UTILIZE ANY EXISTING PENETRATION FIRESTOP
SYSTEM LOCATED IN AN EXISTING RATED WALL IN LIEU
OF ADDING NEW IF SUCH DEVICE HAS CAPACITY FOR
MORE CABLES. REVIEW WITH OWNER'S
REPRESENTATIVE PRIOR TO USING EXISTING
PENETRATION FIRESTOP SYSTEM.
9
10
10
7
7
2
1
2
3
4
RAC
JPS
FIRST FLOOR - NEW WORK
PLAN
NORTH
SCALE:
FIRST FLOOR - NEW WORK
1/8" = 1'-0"
1
16'8'4'1'
SCALE: 1/8" = 1'-0"
5
6
SCALE:
KEY MAP
NOT TO SCALE
7
8
9
10
DANIEL PHELAN
PE-2017030573
VAV
3-200
VAV
2-203
VAV
2-202
VAV
2-200
VAV
2-204
VAV
2-205
7
6
6
6
1 3 4
6
6
7
7
7
7
2
VAV
2-201
6
1
3 4
2
2
2
2
2
2
2
2
1 3 4
1 3 4
1 3 4
1
3
4
1 3 4
1 3 4
1 3 4
5-TON LIEBERT
UNIT
T
T
T
T
T
T
T
T
VAV
3-205
VAV
3-207
VAV
3-206
VAV
3-208
VAV
3-202
VAV
3-203
VAV
3-204
VAV
3-201
EXISTING 12"Ø
SA DOWN, AHU-2
8
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
T
9
T
T
T
T
T
10
10
PROVIDE A PENETRATION FIRESTOP SYSTEM AT EACH
NEW PENETRATION OF EXISTING RATED WALLS
REQUIRED FOR NEW DDC FC BUS AND 24V CONTROL
WIRING PER SPEC SECTION 078413, OR INSTALL
EZ-PATH SERIES 33 FIRE RATED PATHWAY, NO
SUBSTITUTIONS. REFER TO LIFE SAFETY PLANS G101
AND G102 FOR EXISTING RATED WALL LOCATIONS.
UTILIZE ANY EXISTING PENETRATION FIRESTOP
SYSTEM LOCATED IN AN EXISTING RATED WALL IN LIEU
OF ADDING NEW IF SUCH DEVICE HAS CAPACITY FOR
MORE CABLES. REVIEW WITH OWNER'S
REPRESENTATIVE PRIOR TO USING EXISTING
PENETRATION FIRESTOP SYSTEM.
1 3 4
T 2
VAV
2-206
5
11
10
10
10
SCALE:
SECOND FLOOR - NEW WORK
1/8"=1'-0"
1
NORTH
RAC
JPS
SECOND FLOOR - NEW
WORK
16'8'4'1'
SCALE: 1/8" = 1'-0"
1
2
3
4
5
6
7
8
SCALE:
KEY MAP
NOT TO SCALE
9
10
11
DANIEL PHELAN
PE-2017030573
RAC
JPS
FIRST FLOOR REFERENCE
PLAN
NORTH
SCALE:
FIRST FLOOR REFERENCE
1/8" = 1'-0"
1
16'8'4'1'
SCALE: 1/8" = 1'-0"
SCALE:
KEY MAP
NOT TO SCALE
DANIEL PHELAN
PE-2017030573
RAC
JPS
SCHEDULES AND DETAILS
AIR TERMINAL UNIT SCHEDULE
NEW PLAN MARK
MODEL TYPE
INLET DUCT
SIZE (IN RND)
OCCUPIED FLOWS
NOTES
(CFM)
FLOW (GPM)
CONTROL
VALVE
(NOTE 2)
MFR.
LEGACY PLAN MARK
MAX. FLOW
NOTES:
AIR TERMINAL UNIT LISTED IN SCHEDULE IS EXISTING. CONTRACTOR TO FIELD VERIFY INLET SIZE NOTED IN SCHEDULE. SIZES WERE TAKEN FROM OWNER DRAWINGS DATED 06-01-1995 AND FIELD OBSERVATIONS.
EXISTING PNEUMATIC CONTROL VALVES ARE EXISTING TO REMAIN UNLESS ALTERNATE #1 OR ALTERNATE #2 IS ACCEPTED.
COOLING MAXIMUM PRIMARY AIRFLOW AND REHEAT COIL WATER FLOW NOTED IN SCHEDULE WERE TAKEN FROM OWNER DRAWINGS DATED 06-01-1995.
EXISTING HEATING HOT WATER FLOW UNKNOWN.
EXISTING COOLING MAXIMUM PRIMARY AIRFLOW, COOLING MINIMUM PRIMARY AIRFLOW, AND HEATING OCCUPIED AIRFLOW ARE UNKNOWN. EXISTING SCHEDULES INDICATING AIRFLOWS AND DRAWINGS INDICATING ROOMS SERVED BY
EXISTING AIR TERMINAL UNIT ARE NOT AVAILABLE. AIRFLOW WILL BE MEASURED BY OWNER DURING PROGRAMMING OF NEW AIR TERMINAL UNIT DDC CONTROLLER.
AIR TERMINAL UNIT IS PROVIDED IN A SEPARATE PROJECT, MU PROJECT #CP180991, UNIVERSITY OF MISSOURI TEACHING HOSPITAL ED CT SCANNER RENOVATION.
EXISTING AIR TERMINAL UNIT AIRFLOW IS TO BE RE-BALANCED IN A SEPARATE PROJECT, MU PROJECT #CP180991, UNIVERSITY OF MISSOURI TEACHING HOSPITAL / ED CT SCANNER RENOVATION.
1.
2.
3.
4.
5.
6.
7.
COOLING HEATING
(CFM)
MIN. FLOW
(CFM)
MIN. FLOW
UN-OCCUPIED FLOWS
(CFM)
MIN. FLOW
(CFM)
MIN. FLOW
HEATINGCOOLING
HOT WATER
HEATING
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
---
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
TITUS PESV
9"
9"
8"
8"
---
9"
9"
6"
7"
6"
9"
6"
10"
8"
8"
6"
8"
---
700
535
---
350
410
640
500
480
330
600
SINGLE DUCT PRESSURE INDEPENDENT
6" 380
265
660
10"
10"
10"
10"
8"
8"
10"
10"
6"
TITUS
TITUS
TITUS
TITUS
TITUS
TITUS
TITUS
TITUS
PESV
PESV
PESV
PESV
PESV
PESV
PESV
PESV
TITUS PESV
TITUS PESV
TITUS PESV
TITUS
TITUS
TITUS
PESV
PESV
PESV
TITUS PESV
TITUS
TITUS
TITUS
---
TITUS
TITUS
PESV
PESV
PESV
---
PESV
PESV
TITUS
TITUS
TITUS
TITUS
TITUS
PESV
PESV
PESV
PESV
PESV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
1-130
1-131
1-132
1-133
1-134
1-135
1-136
1-137
1-138
1-139
1-140
1-141
1-142
2-100
2-101
3-100
3-101
3-102
3-103
3-200
3-201
3-202
3-203
3-204
3-205
3-206
3-207
3-208
VAV 1-143
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
2-WAY
2-WAY
2-WAY
2-WAY
---
---
2-WAY
---
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
1.5
1.5
1.0
1.0
---
---
1.5
---
1.5
0.7
1.0
(NOTE 4)
1.5
0.7
2.0
1.0
1.0
0.7
1.0
2-WAY0.7
7
1, 3
7
6
6
7
6
7
---
--- ------ ---
---
--- ------ ---
------
--- ------
------
------
1, 3
75350
535535
615 75310
--- ------
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
------
35175 1, 3
1, 3
1, 5
1, 3
1, 3
35
45205
75320
35190
1, 3
1, 3
1, 3
1, 3
1, 3
1, 3
1, 5
1, 5
1, 5
1, 5
1, 5
1, 5
1, 5
1, 5
1, 5
(NOTE 4)
(NOTE 4)
(NOTE 4)
(NOTE 4)
(NOTE 4)
(NOTE 4)
(NOTE 4)
(NOTE 4)
(NOTE 4)
95
95
95
60
60
95
95
35
95
35
35
60
60
60
95
135
330
250
240
165
300
SINGLE DUCT PRESSURE INDEPENDENT
SINGLE DUCT PRESSURE INDEPENDENT
---
---
---
---
75
535
75
---
---
35
35
45
75
35
95
95
95
60
60
95
95
35
95
35
35
60
60
60
95
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
(NOTE 5)
---
---
---
---
350
535
310
---
---
175
205
320
190
135
330
250
240
165
300
(NOTE 5) (NOTE 5)
SINGLE DUCT PRESSURE INDEPENDENT
TITUS PESV 16"VAV 2-206 --- --- 2-WAY(NOTE 5) 1, 5(NOTE 4)235 235(NOTE 5) (NOTE 5)
DANIEL PHELAN
PE-2017030573
GENERAL:
THE CONTRACTOR SHALL SUBMIT ENGINEERED CONTROL DRAWINGS, WIRING DIAGRAMS, EQUIPMENT SCHEDULES, ETC., AS REQUIRED FOR A COMPLETE CONTROL SYSTEM.
THE CONTRACTOR WILL BE EXPECTED TO WORK OUT THE DETAILS OF NORMALLY OPEN/NORMALLY CLOSED CONNECTIONS, EXACT EQUIPMENT REQUIREMENTS, ETC., TO
PROVIDE A WORKING CONTROL SYSTEM TO ACHIEVE THE SEQUENCES OF OPERATION BELOW AND NOTED ELSEWHERE ON THE TEMPERATURE CONTROL DRAWINGS. THE
WRITTEN SEQUENCE OF OPERATION SHALL BE THE CRITERION USED TO JUDGE THE FINAL PERFORMANCE OF THE CONTROL SYSTEM. ALL FUNCTIONS IN THE SEQUENCE
WILL BE REQUIRED EVEN IF THE REQUIRED EQUIPMENT AND CONNECTIONS ARE NOT DEPICTED ON THESE DRAWINGS.
CONTRACTOR SHALL PROVIDE AS-BUILT DIAGRAM OF NETWORK BUS ROUTING PER SPEC SECTION 23 0900.
THE UNIVERSITY OF MISSOURI - COLUMBIA UTILIZES JOHNSON CONTROLS EQUIPMENT FOR THEIR CAMPUS ENERGY MANAGEMENT CONTROL SYSTEM (EMCS). NEW DDC
CONTROL SYSTEM SHALL FULLY INTERFACE WITH THE CAMPUS JOHNSON CONTROLS METASYS SYSTEM.
AIR TERMINAL (VAV) UNITS: CONTRACTOR IS RESPONSIBLE FOR ENTERING THE AIRFLOW SETPOINTS AS NOTED IN THE SCHEDULE ON SHEET M600 INTO EACH VAV BOX
PROGRAM. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE CORECT VAV BOX INLET DIAMETER AND ENTERING THE CORRESPONDING AREA INTO THE VAV BOX
PROGRAM. THE CONTRACTOR IS RESPONSIBLE FOR ENTERING THE DEFAULT GAIN OF 2.0 INTO THE VAV BOX PROGRAM FOR EACH VAV BOX.
SEQUENCE OF OPERATION
RAC
JPS
TEMPERATURE CONTROLS
FC COMMUNICATION BUS
WIRE DAISY CHAINED TO
PREVIOUS VMA CNTRLR
LOW VOLTAGE
WIRE
7
AIR FLOW
MEASURING
TAPS
FC COMMUNICATION BUS
WIRE DAISY CHAINED TO
NEXT VMA CONTROLLER
1
SUPPLY AIR
SENSOR
6
AIR VALVE
DAMPER
NETWORK
SENSOR
T
M
2
CONTROLLER WILL BE OWNER FURNISHED AND CONTRACTOR INSTALLED. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES.
PROGRAMMING WILL BE DONE BY OWNER. COMMISSIONING WILL BE DONE BY CONTRACTOR.
NETWORK SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. NETWORK SENSOR WILL BE JCI NS SERIES.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED
AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.
NOT USED.
CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.
VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE. PROVIDED, INSTALLED, & WIRED TO
CONTROLLER BY CONTRACTOR.
FUSE LOCATED WITHIN 3 FT. OF VMA CONTROLLER.
LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.
VALVE WITH PROPORTIONAL 0-10 VOLT ACTUATOR OR EQUIVALENT.
SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.
1
2
3
4
5
6
7
8
9
10
3
5
3
ELECTRIC
ACTUATOR
9
8
VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE NOTED, ALL
CONTROL WORK SHALL BE BY CONTRACTOR.
CAPS FOR VAV DP TEST PORTS MUST BE 1/4" BRASS PLUGS.
1.
2.
SA BUS
WIRE
10
AIR IN AIR OUT
NC
HWS HWR
DDC VMA
CONTROLLER
SECONDARY LINE CAN BE RAN IN SAME CONDUIT AS FC BUS
ENCLOSED POWER SUPPLY MUST BE LOCATED IN EXISTING ELECTRICAL ROOMS AS INDICATED ON THE PLANS AND BE
ACCESSIBLE. ANY OTHER LOCATION MUST BE APPROVED BY THE OWNER'S REPRESENTATIVE.
1.
2.
EACH SECONDARY OUTPUT LINE CAN POWER 3-5 VAV CONTROLLERS MAXIMUM (100 VA) BY MECHANICAL CONTRACTOR.
PRIMARY LINE INFO: 480/277/240/120 Vac, #12 AWG MINIMUM BY ELECTRICAL CONTRACTOR.
SECONDARY LINE INFO: 24 Vac, #12-26 AWG, 100 VA. MAX LENGTH 175 FEET USING #14 AWG BY MECHANICAL CONTRACTOR.
DISCONNECT SWITCH REQUIRED, EXTERNALLY MOUNTED WITHIN 12 INCHES OF RIB POWER SUPPLY BY ELECTRICAL CONTRACTOR.
500VA POWER SUPPLY - INCLUDED IN RIB MODEL# PSH500A OR APPROVED EQUIVALENT. POWER SUPPLY TO BE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. SEE PLANS FOR LOCATIONS.
ALL SECONDARY LINES MUST BE LABELED IN ENCLOSURE AS TO WHICH VAV'S THEY POWER PRIOR TO ENERGIZING POWER SUPPLY BY MECHANICAL CONTRACTOR.
A SEPARATE 3 AMP FUSE IS REQUIRED WITHIN 3 FEET OF EACH VAV BY MECHANICAL CONTRACTOR.
1
2
3
4
5
24V
COM
24V
COM
24V
COM
24V
COM
24V
COM
480
277
240
120
COM
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
RIB AC
BREAKER
SWITCH
POWER
SUPPLY/
TRANSFORMER
(FUSE)
6
7
100 VA
100 VA
100 VA
100 VA
100 VA
DISCONNECT
SWITCH
PSH500A
ENCLOSED AC POWER SUPPLY
FC COMMUNICATION BUS
WIRE DAISY CHAINED TO
PREVIOUS VMA CNTRLR
FC COMMUNICATION BUS
WIRE DAISY CHAINED TO
NEXT VMA CONTROLLER
1
SUPPLY AIR
SENSOR
6
AIR VALVE
DAMPER
NETWORK SENSOR
T
M
2
CONTROLLER WILL BE OWNER FURNISHED AND CONTRACTOR INSTALLED. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES.
PROGRAMMING WILL BE DONE BY OWNER. COMMISSIONING WILL BE DONE BY CONTRACTOR.
NETWORK SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. NETWORK SENSOR WILL BE JCI NS SERIES.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED
AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.
NOT USED.
CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.
VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE. PROVIDED, INSTALLED, & WIRED TO
CONTROLLER BY CONTRACTOR.
FUSE LOCATED WITHIN 3 FT. OF VMA CONTROLLER.
LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.
EP TRANSDUCER SHALL HAVE 0-10 VDC INPUT, 0-20 PSI HIGH VOLUME OUTPUT (500 SCIM MIN. AIR
CAPACITY). JCI MODEL EP-8000-2 OR EQUAL. CONTRACTOR FURNISHED AND INSTALLED.
SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.
IN-LINE FILTER AND PRESSURE GAUGES PROVIDED BY CONTRACTOR.
1
2
3
4
5
6
7
8
9
10
11
3
10
5
3
8
VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE NOTED, ALL
CONTROL WORK SHALL BE BY CONTRACTOR.
IF VAV HAS DP TEST PORTS AND RUBBER CAPS, CAPS MUST BE REPLACED WITH 1/4" BRASS PLUGS.
1.
2.
IN-LINE FILTER
CONTROL AIR
TUBING (TYP.)
MAIN
AIR
M
9
VALVE EP
TRANSDUCER
9
SA BUS
WIRE
11
7
AIR OUT
DDC VMA
CONTROLLER
NC
EP
HWS HWR
LOW VOLTAGE
WIRE
AIR FLOW
MEASURING
TAPS
AIR IN
1
4
2
3
6
5
7
SCALE:
VAV BOX CONTROL DIAGRAM WITH REHEAT - ALTERNATE #1 AND #2
N.T.S.
B
2
SCALE:
500 VA POWER SUPPLY DIAGRAM
N.T.S.
C
SCALE:
VAV BOX CONTROL DIAGRAM WITH PNEUMATIC CONTROL VALVE - BASE BID
N.T.S.
A
FC BUS TO BE CONTINUOUS DAISY CHAIN WITHOUT SPLICES.
CONNECTIONS CAN ONLY BE MADE AT CONTROLLERS. SEE PLANS FOR
QUANTITY AND LOCATIONS OF VAV CONTROLLERS.
CONTRACTOR WILL MAKE TERMINATION CONNECTIONS AT PANELS.
LOCATE PANELS IN SAME ROOM AS EQUIPMENT SERVED.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED,
TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING,
DESCRIPTED AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY
WINDY CITY WIRE, CONSTRUCTED BY CABLE-TEK, OR APPROVED
EQUIVALENT.
COORDINATE FIELD ROUTING WITH OWNERS REPRESENTATIVE.
EXTEND FC BUS FROM EITHER EXISTING VAV 1-127 OR VAV 1-128, REFER
TO SHEET M101. FIELD VERIFY WHICH EXISTING AIR TERMINAL UNIT CAN
BE UTILIZED. COORDINATE WITH OWNERS REPRESENTATIVE.
VAV VAVVAV
EXIST
VAV
VAV VAVVAV
SCALE:
FC BUS SCHEMATIC DIAGRAM
N.T.S.
D
5
5
1.
2.
3.
4.
DANIEL PHELAN
PE-2017030573
E
E
2
EXISTING
PANEL LQ1ER
LQ1ER-29 3
1
4
5
5
5
5
E
2
LQ1ER-313
4
1
5
5
KFM
GMC
ELECTRICAL PARTIAL FLOOR
PLANS
GENERAL SHEET NOTES:
1. VERIFY POWER SUPPLY LOCATIONS WITH OWNER'S REPRESETATIVE PRIOR
TO COMMENCEMENT OF WORK.
2. REFER TO MECHANICAL DETAIL C/M700 500VA POWER SUPPLY DIAGRAM FOR
ADDITIONAL INFORMATION.
3. UPDATE PANEL DIRECTORIES WITH NEW LOADS BEING SERVED BY EXISTING
PANELS.
SCALE:
ELECTRICAL PARTIAL SECOND FLOOR PLAN
1/8" = 1' - 0"
2
NORTH
SCALE:
ELECTRICAL PARTIAL FIRST FLOOR PLAN
1/8" = 1' - 0"
1
NORTH
SCALE:
KEY MAP - 1ST FLOOR
NOT TO SCALE
SCALE:
KEY MAP - 2ND FLOOR
NOT TO SCALE
KEYED NOTES:
FURNISH AND INSTALL NEW POWER SUPPLIES TO SERVE NEW MECHANICAL
VAV BOXES. REFER TO MECHANICAL DETAIL C/M700 FOR SPECIFIC MODEL
NUMBER TO BE PROVIDED AND ADDITIONAL INFORMATION REGARDING
INSTALLATION. MOUNT 7'-0" A.F.F. IN APPROXIMATE LOCATION. COORDINATE
FINAL LOCATION WITH OWNER'S REPRESENTATIVE PRIOR TO
COMMENCEMENT OF WORK AND COORDINATE WITH EXISTING CONDITIONS
IN THE ROOM.
PROVIDE LEVITON #1221-2, HUBBELL #HBL1221, OR APPROVED EQUAL 120V,
20A TOGGLE TYPE DISCONNECT SWITCH AND MOUNT ON THE WALL
ADJACENT TO POWER SUPPLIES.
PROVIDE 120V, 20A CIRCUIT TO NEW POWER SUPPLIES FURNISHED AND
INSTALLED BY CONTRACTOR. CONNECT TO NEXT AVAILABLE SPARE 120V,
20A, 1-POLE CIRCUIT BREAKER IN PANEL INDICATED. CIRCUIT NUMBER
INDICATED ON PLAN IS PROVIDED FOR REFERENCE BASED ON PREVIOUS
FIELD INVESTIGATIONS.
UTILIZE THE EXISTING SHAFT FOR CIRCUIT INSTALLATION BETWEEN FIRST
FLOOR PANEL AND POWER SUPPLIES ON THE SECOND FLOOR.
TEMPORARILY REMOVE OR SUPPORT ALL CEILING MOUNTED DEVICES AND
LUMINAIRES IN APPROXIMATE SPACE AS REQUIRED FOR CIRCUIT
INSTALLATION. COORDINATE THIS SCOPE WITH FINAL CIRCUIT PATH
DETERMINED IN THE FIELD.
1
2
PLAN
NORTH
ABBREVIATIONS
LINE TYPE LEGEND
DRAWING REFERENCES ELECTRICAL GENERAL NOTES
NEW WORK BY THIS CONTRACTOR
(DARK, SOLID LINE)
EXISTING TO REMAIN OR NEW WORK BY OTHERS
(LIGHT, SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK, DASHED LINE, DEMOLITION PLANS)
NEW WORK BY THIS CONTRACTOR TO BE
INSTALLED UNDERGROUND, OR BELOW FLOOR
(DARK, LONG DASHED LINE)
NORTH ARROW
PLAN DETAIL REFERENCE TITLE
KEYED NOTE DESIGNATION
#
AHU
1
PLAN MARK
EQUIPMENT NUMBER
EQUIPMENT DESIGNATION REFER TO MEP
SCHEDULE FOR CIRCUITING AND DEVICE
REQUIREMENTS AND FLOOR PLANS FOR
LOCATIONS
#
ENLARGED PLAN REFERENCE
E100
1
PLAN MARK
SHEET NUMBER
1. MAKE ALL INSTALLATIONS IN ACCORDANCE WITH THE AMERICANS WITH
DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG) AND/OR ARCHITECTURAL
BARRIERS ACT (ABA).
2. MOUNTING HEIGHTS INDICATED WITHIN PLANS AND SCHEDULES ARE
DIMENSIONED TO THE CENTER LINE OF THE DEVICE, EQUIPMENT, LUMINAIRE,
ETC. UNLESS OTHERWISE NOTED.
3. COORDINATE EXACT EQUIPMENT LOCATIONS WITH OTHER TRADES. EQUIPMENT
LOCATIONS SHOWN ON ELECTRICAL PLANS ARE DIAGRAMMATICAL ONLY AND
MIGHT NOT BE EXACT.
4. CIRCUIT IDENTIFICATION NUMBERS BESIDE ELECTRICAL DEVICES AND
CONNECTION POINTS ON PLANS CORRESPOND TO AN OVERCURRENT DEVICE IN
THE DESIGNATED PANELBOARD. NOTE ALL CIRCUIT NUMBER CHANGES MADE IN
THE FIELD AT EACH ELECTRICAL DEVICE AND CONNECTION POINT. ALSO
CORRECT THE DIRECTORIES AND DEVICE MARKINGS AT PANELBOARDS,
SWITCHBOARDS AND SWITCHGEAR TO ACCURATELY REFLECT THE AS-BUILT
CONDITIONS.
5. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILINGS, ETC. UNLESS
OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT
ROUTED IN MECHANICAL ROOMS, ELECTRICAL ROOMS, AND STORAGE ROOMS
WITHOUT CEILINGS MAY BE ROUTED EXPOSED.
6. COORDINATE VERTICAL CONDUIT ROUTING TO WALL MOUNTED DEVICES TO
ENSURE DEVICES LOCATED WITHIN AN 18-INCH HORIZONTAL DIMENSION WILL BE
CENTER-ALIGNED VERTICALLY.
7. FIELD COORDINATE ALL ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT
MOUNTING LOCATIONS TO AVOID ENCROACHMENT OF OPERATION AND ACCESS
TO EQUIPMENT FROM OTHER TRADES. COORDINATE THE APPROPRIATE
MOUNTING LOCATION WITH THE AFFECTED DISCIPLINES WHEN EQUIPMENT IS
SPECIFIED TO BE MOUNTED ONTO THE SURFACE OF ANOTHER DISCIPLINE'S
EQUIPMENT.
8. REPAIR ALL OPENINGS MADE IN EXISTING WALLS, PARTITIONS, ETC TO
ACCOMMODATE WORK OF THIS DISCIPLINE TO MATCH THE SURROUNDING
CONDITIONS, USING WORKERS QUALIFIED IN THE APPROPRIATE TRADE.
APPROPRIATELY GROUT OR SEAL ALL CONDUITS THROUGH WALLS.
9. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND
FLOORS MUST HAVE BEEN TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814
STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS.
10. REPLACE OR REINSTALL ALL PORTIONS OF THE BUILDING (CEILING TILES, WALLS,
ETC) REMOVED TO ACCOMMODATE THE INSTALLATION OF ANY ELECTRICAL
DEVICE, EQUIPMENT, ETC., USING WORKERS QUALIFIED IN THE APPROPRIATE
TRADE.
A.F.F : ABOVE FINISHED FLOOR
C : CONDUIT
E.C. : ELECTRICAL CONTRACTOR
ER : EXISTING RELOCATED
ETR : EXISTING TO REMAIN
EWC : ELECTRIC WATER COOLER
G.C. : GENERAL CONTRACTOR
GND : GROUND
TYP. : TYPICAL
U.O.N. : UNLESS OTHERWISE NOTED
3
WIRING PLANS
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT CAPPED FOR FUTURE.
HOMERUN TO PANEL OR DESTINATION NOTED
PROVIDE WIRING REQUIRED BY THE CIRCUITING AND SWITCHING
REQUIREMENTS FOR THE PARTICULAR CIRCUITS INVOLVED. TYPICAL
120V HOMERUNS SHALL CONSIST OF #12 AWG CONDUCTORS IN 3/4"
CONDUIT MINIMUM UNLESS INDICATED OTHERWISE. NO SHARED
NEUTRALS SHALL BE ALLOWED. A MAXIMUM OF NINE CURRENT-
CARRYING CONDUCTORS ARE ALLOWED IN A RACEWAY. NEUTRAL
CONDUCTORS ARE ALSO CONSIDERED CURRENT-CARRYING
CONDUCTORS. FOR CIRCUITS EXCEEDING 75'-0" IN LENGTH, PROVIDE
THE NEXT LARGER WIRE SIZE FOR THE CIRCUIT AMPACITY.
WHERE NUMBER OF CURRENT-CARRYING CONDUCTORS IN A RACEWAY
EXCEEDS THREE, THE ALLOWABLE AMPACITY OF EACH CONDUCTOR
SHALL BE REDUCED AS SHOWN IN THE ADJUSTMENT FACTOR TABLE IN
THE NATIONAL ELECTRIC CODE. LOAD DIVERSITY FACTORS SHALL NOT
BE USED IN SIZING CONDUCTORS. NEUTRAL CONDUCTORS SHALL BE
COUNTED AS CURRENT-CARRYING CONDUCTORS.
1.
2.
POWER EQUIPMENT
PANELBOARD (SURFACE)
PANELBOARD (FLUSH)
WIRING DEVICES, RECEPTACLES - MISC.
ELECTRICAL CONNECTION: CEILING MOUNTED
ELECTRICAL CONNECTION: WALL MOUNTED
E
E
J
JUNCTION AND PULL BOXES
PULL BOX
JUNCTION BOX : CEILING OR FLOOR MOUNTED. SIZE
PER N.E.C. REQUIREMENTS.
JUNCTION BOX : WALL MOUNTED. SIZE PER N.E.C.
REQUIREMENTS.
J
P
TOGGLE TYPE DISCONNECT SWITCH
4
5
MICHAEL D. SWANSON
PE-2013000637