bien tan danfoss vlt 5000 serie

Upload: pham-quang-duc

Post on 02-Jun-2018

238 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    1/173

    VLT5000 Series

    1M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Contents

    Safety ............................................................................................................... 4

    Introduction ..................................................................................................... 5W hy choose D anfoss? ....................................................................................6

    Available literature ...........................................................................................7

    Technical data ................................................................................................. 8G eneral technical data ....................................................................................8

    Technical data, B ookstyle IP 20 .....................................................................12

    Technical data, C om pact IP 20 and IP 54 ......................................................13

    Measurements, dimensions........................................................................ 21

    Mechanical installation ................................................................................ 25

    Electrical installation .................................................................................... 29EM C -correct electrical installation ................................................................37

    U se of EM C -correct cables..........................................................................38

    Earthing of braided screened/arm oured control cables................................39

    Installation of control cables .........................................................................44

    C onnection exam ples...................................................................................45

    Operation of the VLT frequency converter................................................ 48C ontrol panel................................................................................................48

    C ontrol keys .................................................................................................49

    D isplay M ode ................................................................................................50

    Q uick Setup via Q uick m enu .......................................................................51

    C hanging data ..............................................................................................52

    M enu structure .............................................................................................54

    Application configuration ............................................................................ 55Speed control, open loop .............................................................................55

    Speed control, closed loop (PID )..................................................................55

    Process control, closed loop (Process PID )..................................................56

    Torque control, open loop ............................................................................56

    Torque control, speed feedback...................................................................57

    Special m otor characteristics .......................................................................57

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    2/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark2

    Special functions .......................................................................................... 58Shift betw een local and rem ote control.......................................................58

    C ontrol w ith brake function ..........................................................................59

    H andling of single references........................................................................60

    H andling of m ulti-references .........................................................................61

    Autom atic M otor Adaptation ........................................................................64C ontrol of m echanical brake ........................................................................66

    PID for process control.................................................................................68

    PID for speed control....................................................................................70

    Q uick discharge ...........................................................................................71

    M ains failure/quick discharge w ith m ains failure inverse ...............................72

    Flying start....................................................................................................73

    N orm al/high overload Torque control, open loop ..........................................74

    Program m ing of Torque lim it and stop ..........................................................74

    Description of parameters........................................................................... 76O peration & D isplay .......Param eter 001 - 019 ............................................76

    Load & M otor................Param eter 100 - 131 ............................................82R eferences & Lim its ......Param eter 200 - 234 ............................................94

    Inputs & O utputs ...........Param eter 300 - 330 ..........................................102

    Special functions ...........Param eter 400 - 450 ..........................................116

    Serial com m unication ....Param eter 500 - 541 ..........................................131

    Technical functions ........Param eter 600 - 631 ..........................................140

    R elay functions ..............Param eter 700 - 711 ..........................................147

    Fault procedure .......................................................................................... 149

    Display texts ............................................................................................... 152

    Status m essages .......................................................................................152List of w arnings and alarm s........................................................................153

    W arning w ords 1 + 2 and Alarm w ord .......................................................160

    Definitions ................................................................................................... 161

    Factory settings.......................................................................................... 164

    Index ............................................................................................................ 171

    Contents

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    3/173

    VLT5000 Series

    3M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    VLT5000 Series

    Operating InstructionsS o ftw a re vers io n: 3.3x

    Software

    version

    Thes e Opera ting Instructions can be used for all VLT5000 S eriesfreq uency converters with softwa re version 3.3x. The software

    version can be seen from parameter 624.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    4/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark4

    Safety The voltage of the frequency converter

    is dangerous w henever the equipm ent

    is connected to m ains. Incorrect instal-

    lation of the m otor or the frequency converter m ay

    cause dam age to the equipm ent, serious personal

    injury or death.

    C onsequently, the instructions in this m anual, as

    w ell as national and local rules and safety

    regulations, m ust be com plied w ith.

    Safety regulations

    1. The V LT frequency converter m ust be disconnec-

    ted from m ains if rep air w ork is to be carried out.

    C heck that the m ains supply has been discon-

    nected and that the necessary tim e has passed

    before rem oving m otor and m ains plugs.

    2. The [STO P/R ESET] key on the control panel of theVLT frequency converter does not disconnect the

    equipm ent from m ains and is thus not to be used

    as a safety sw itch.

    3. C orrect protective earthing of the equipm ent m ust

    be established, the user m ust be p rotected

    against supply voltage, and the m otor m ust be

    protected against overload in accordance w ith

    applicable national and local regulations.

    4. The earth leakage currents are higher than 3.5 m A.

    5. Protection against m otor overload is not includ ed

    in the factory setting. If this function is desired, set

    param eter 128 to d ata value ETR trip ordata value

    ETR warning .

    N ote: The function is initialised at 1.16 x rated m o-

    tor current and rated m otor frequency (see page

    92).

    For the N orth A m erican m arket: The ETR functions

    provide class 20 m otor overload protection in

    accordance w ith N EC .

    Warning:Touching the electrical parts m ay be fatal - even after theequipm ent has been disconnected from m ains.Also m ake sure that other voltage inputs have beendisconnected, such as external 24 V D C , load-sharing(linkage of D C interm ediate circuit), as w ell as the m otorconnection for kinetic back-up.

    U sing VLT 5001-5006: w ait at least 4 m inutesU sing VLT 5008-5500: w ait at least 15 m inutes

    6. D o not rem ove the p lugs for the m otor and m ains

    supply w hile the V LT frequency converter is

    connected to m ains. C heck that the m ains supply

    has been disconnected and that the necessary

    tim e has passed before rem oving m otor and

    m ains plugs.

    7. Please note that the VLT frequency converter has

    m ore voltage inputs than L1, L2 and L3, w hen

    loadsharing (linking of D C interm ediate circuit) and

    external 24 V D C have been installed.

    C heck that all voltage inputs have been discon-

    nected and that the necessary tim e has passed

    before repair w ork is com m enced.

    Warning against unintended start

    1. The m otor can be brought to a stop by m eans of

    digital com m and s, bus com m ands, references ora local stop, w hile the frequency converter is

    connected to m ains.

    If personal safety considerations m ake it

    necessary to ensure that no unintended start

    occurs, these stop functions are not sufficient.

    2. W hile param eters are being changed, the m otor

    m ay start. C onsequently, the stop key [STO P/

    R ESET] m ust alw ays be activated, follow ing w hich

    data can be m odified.

    3. A m otor that has been stopped m ay start if faults

    occur in the electronics of the VLT freq uency con-

    verter, or if a tem porary overload or a fault in the

    supply m ains or the m otor connection ceases.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    5/173

    VLT5000 Series

    5M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Introduction

    These O perating Instructions are a tool intended for persons w ho are to install,

    operate and p rogram the V LT 5000 Series.

    Specific technical publications on the VLT 5000 Series: O perating Instructions,

    D esign G uide and Q uick Setup.

    Operating Instructions: G ives instructions in optim um installation, com m issio-

    ning and service.

    Design Guide: G ives all req uired inform ation for design purposes,

    and gives a good insight into the technology, pro-

    duct range, technical data, etc.

    Quick Setup: H elps the great m ajority of users to quickly get their

    VLT 5000 Series unit installed and running.

    The O perating Instructions and the Q uick Setup are delivered w ith the unit.

    W hen reading these O perating Instructions, you w ill com e across different sym bols

    that require special attention.

    The sym bols used are the follow ing:

    Indicates a general w arning

    Indicates som ething to be noted by the reader

    Indicates a high-voltage w arning

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    6/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark6

    Why choose Danfoss?

    D anfoss m anufactured the w orld's first m ass-pro-

    duced frequency converter back in 1968. W e have

    set the standard for quality drives ever since. That is

    w hy our VLT frequency converters are today sold and

    serviced in m ore than 100 countries covering six

    continents.

    W ith the new VLT 5000 Series, w e are introducing

    VVC plus. This is our new Sensorless Vector D rive S y-

    stem for torque and speed control of ind uction m otors.

    If com pared w ith a standard voltage/freq uency ratio

    control, VVC plusoffers im proved dynam ics and sta-

    bility, both w hen the speed reference and the load

    torque are changed. W e have im plem ented a fully

    digitalised protection concept, w hich ensures reliableoperation, even under the w orst possible operating

    conditions. N aturally, the VLT 5000 Series also offers

    full protection against short-circuiting, earthing fault

    and overload.

    D anfoss drives w ith the VVC pluscontrol system

    tolerate load shocks throughout their speed range

    and react sw iftly to changes in reference.

    H ow ever, it m ust also be easy to reach this perfor-

    m ance. D anfoss is convinced that high-technology

    drives can be m ade user-friendly. The V LT 5000 Se-

    ries proves us right. In order to m ake p rogram m ing

    sim ple and easy-to-grasp, w e have divided the para-

    m eters into different group s. The Q uick m enu guides

    users quickly through the program m ing of the few pa-

    ram eters that m ust be set to get started. The control

    panel is d etachable. It features a four-line alpha-

    num eric display, enab ling four m easuring values to be

    displayed at the sam e tim e. Via the detachable

    control panel, the program m ed settings can be co-

    pied from one VLT frequency converter to the next.

    This m eans that there is no tim e to b e spent onprogram m ing w hen changing drives or integrating an

    extra drive in the installation.

    The entire program m ing process is easier than ever

    before. The V LT 5000 Series m akes m ost adjust-

    m ents autom atically.

    If you have any q uestions concerning VLT frequency

    converters, please call us. W e have drive specialists

    all over the w orld ready to ad vise you on ap plications,

    program m ing, training and service.

    Whychoose

    Danfoss?

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    7/173

    VLT5000 Series

    7M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Available

    literature

    Available literature

    The chart below gives an overview of the literature

    availab le for the VLT 5000 Series.

    Please note that variations m ay occur from one coun-

    try to the next.

    X = version numberYY = language01 = Danish02 = English03 = German

    04 = French05 = Spanish06 = Italian07 = Swedish10 = Dutch20 = Finnish28 = Brazilian Portuguese51,52 = Danish, English, German

    DesignGuide

    MG.50.CX.YYOperating

    InstructionsMG.50.AX.YY

    Instructions

    for VLT

    5000 Series

    VLT SoftwareDialog

    MG.50.EX.YY

    PROFIBUSManual

    MG.10.EX.YY

    QuickSetup

    MG.50.FX.YY

    LCP remote-mounting kit

    IP 20MI.56.AX.51

    Brakeinstructions

    MI.50.DX.YY

    LC-filterVLT 5001-5011

    MI.56.DX.51

    IP 20 terminalcover

    MI.56.CX.51

    Syncron. andpositioning

    MG.10.JX.02MG.10.JX.03

    GatewayInterBus

    MG.10.G1.51

    QuickSetup

    MG.50.DX.YY

    QuickSetup

    MG.50.GX.YY

    B ookstyle IP 20 C om pact IP 20 C om pact IP 54

    VLT 5000Data sheet

    MD.50.AX.YY

    Loadsharinginstructions

    MI.50.NX.YY

    Var. literature

    for VLT 5000

    Series

    Instructions

    for VLT 5000

    Series

    Communication

    for VLT 5000

    Series

    LonWorksManual

    Device NetManual

    RCDInstructions

    MI.66.AX.YY

    Modbus

    Plus

    LC-filterVLT 5016-5250

    MI.56.FX.51

    LCP remote-mounting kit

    IP 54MI.56.GX.52

    VLT 5300-5500Installation guideMG.56.AX.YY

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    8/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark8

    General technical data

    M ains supply (L1, L2, L3):

    Supply voltage 200-240 V units ..................................................................3 x 200/208/220/230/240 V 10%

    Supply voltage 380-500 V units ...........................................................3 x 380/400/415/440/460/500 V 10%

    Supply frequency ....................................................................................................................50/60 H z + /- 1%

    M ax. im balance of supply voltage:

    VLT 5001 - 5011 / 380 - 500 V and V LT 5001 - 5006 / 200 - 240 V ................ 2.0% of rated supply voltage

    VLT 5016 - 5052 / 380 - 500 V and VLT 5008 - 5027 / 200 - 240 V .................. 1.5% of rated supply voltage

    VLT 5060 - 5500 / 380 - 500 V and VLT 5032 - 5052 / 200 - 240 V .............3.0% of rated supply voltage

    Pow er factor / cos. .............................................................................................................. 0.90/1.0 at rated loadN o. of sw itches on supply input L1, L2, L3 ......................................................................approx. 1 tim e/m in.

    M ax. shortcircuit rating ....................................................................................................................100,000 A

    See the section on special conditions in the Design Guide

    VLT output data (U , V, W ):

    O utput voltage ..........................................................................................................0-100% of supply voltageO utput frequency.........................................................................................................0 - 132 H z, 0 - 1000 H z

    R ated m otor voltage, 200-240 V units ........................................................................ 200/208/220/230/240 V

    R ated m otor voltage, 380-500 V units ..........................................................380/400/415/440/460/480/500 V

    R ated m otor frequency .......................................................................................................................50/60 H z

    Sw itching on output........................................................................................................................... U nlim ited

    R am p tim es ...............................................................................................................................0.05-3600 sec.

    Torque characteristics:

    Starting torque, VLT 5001-5027, 200 - 240 V and VLT 5001-5052, 380 - 500 V .....................160% for 1 m in.

    Starting torque, VLT 5032 - 5052, 200 - 240 V and VLT 5060-5500, 380 - 500 V ...............150% for 1 m in.

    Starting torque .....................................................................................................................180% for 0.5 sec.

    Acceleration torque .................................................................................................................................100%

    O verload torque, VLT 5001-5027, 200 - 240 V and VLT 5001 - 5052, 380 - 500 V .............................160%

    O verload torque, VLT 5032 - 5052, 200 - 240 V and VLT 5060-5500, 380 - 500 V .............................150%

    Arresting torque at 0 rpm (closed loop)..................................................................................................100%

    The torque characteristics given are for the VLT frequency converter at the high overload torque level

    (160%). At the normal overload torque (110%), the values are lower.

    C ontrol card, digital inputs:

    N um ber of program m able digital inputs ...........................................................................................................8

    Term inal nos.......................................................................................................16, 17, 18, 19, 27, 29, 32, 33

    Voltage level.....................................................................................................0-24 V D C (PN P positive logics)

    Voltage level, logical 0.......................................................................................................................< 5 V D CVoltage level, logical 1.....................................................................................................................> 10 V D C

    M axim um voltage on input...................................................................................................................28 V D C

    Input resistance, R i.......................................................................................................................approx. 2 kScanning tim e per input........................................................................................................................3 m sec.

    Reliable galvanic iso lation: All digital inputs are galvanically isolated from the sup ply voltage (PELV). In add ition,

    the digital inputs can be isolated from the other terminals on the control card by connect ing an external 24 V

    DC supply and opening switch 4. See drawing on page 45.

    Generaltechnicaldata

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    9/173

    VLT5000 Series

    9M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    General technical data

    C ontrol card, analogue inputs:

    N o. of program m able analogue voltage inputs/therm istor inputs................................................................... 2

    Term inal nos........................................................................................................................................... 53, 54

    Voltage level..................................................................................................................0 - 10 V D C (scalable)

    Input resistance, R i.....................................................................................................................approx. 10 kN o. of program m able analogue current inputs.................................................................................................1

    Term inal no....................................................................................................................................................60

    C urrent range ...............................................................................................................0/4 - 20 m A (scalable)

    Input resistance, R i ............................................................................................................................... 200 R esolution .....................................................................................................................................10 bit + sign

    Accuracy on input...................................................................................................M ax. error 1% of full scale

    Scanning tim e per input......................................................................................................................3 m sec.

    Term inal no. ground ......................................................................................................................................55

    Reliable galvanic isolation : All analogue input s are galvanically isolated from the sup ply voltage (PELV) as well

    as other inputs and outp uts.

    C ontrol card, pulse/encoder input:

    N o. of program m able pulse/encoder inputs................................................................................................... 4

    Term inal nos...............................................................................................................................17, 29, 32, 33

    M ax. frequency on term inal 17 ................................................................................................................5 kH z

    M ax. frequency on term inals 29, 32, 33 ................................................................20 kH z (PN P open collector)

    M ax. frequency on term inals 29, 32, 33 ................................................................................65 kH z (Push-pull)

    Voltage level.....................................................................................................0-24 V D C (PN P positive logics)

    Voltage level, logical 0.......................................................................................................................< 5 V D C

    Voltage level, logical 1.....................................................................................................................> 10 V D C

    M axim um voltage on input...................................................................................................................28 V D C

    Input resistance, R i.......................................................................................................................approx. 2 kScanning tim e per input........................................................................................................................3 m sec.

    R esolution ......................................................................................................................................10 bit + sign

    Accuracy (100-1 kH z), term inals 17, 29, 33 ......................................................... M ax. error: 0.5% of full scale

    Accuracy (1-5 kH z), term inal 17 ............................................................................M ax. error: 0.1% of full scale

    Accuracy (1-65 kH z), term inals 29, 33 ..................................................................M ax. error: 0.1% of full scale

    Reliable galvanic isolation: All pulse/encoder inpu ts are galvanically isolated from the supp ly voltage (PELV). In

    addition, pulse and encoder inputs can be isolated from the other terminals on the control card by connect ing

    an external 24 V DC supp ly and opening switch 4. See drawing on page 45 .

    C ontrol card, digital/pulse and analogue outputs:

    N o. of program m able digital and analogue outputs ....................................................................................... 2Term inal nos...........................................................................................................................................42, 45

    Voltage level at digital/pulse output.................................................................................................0 - 24 V D C

    M inim um load to ground (term inal 39) at digital/pulse output...................................................................600 Frequency ranges (digital output used as pulse output)......................................................................0-32 kH z

    C urrent range at analogue output...................................................................................................0/4 - 20 m A

    M axim um load to ground (term inal 39) at analogue output......................................................................500 Accuracy of analogue output................................................................................M ax. error: 1.5% of full scale

    R esolution on analogue output...................................................................................................................8 bit

    Reliable galvanic isolation: All digital and analogue outputs are galvanically isolated from the supp ly voltage

    (PELV) as well as other inpu ts and outputs.

    Generaltechnicaldata

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    10/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark10

    B rake resistor term inals (only S B and EB units):

    Term inal nos...........................................................................................................................................81, 82

    External 24 Volt D C supply:

    Term inal nos...........................................................................................................................................35, 36

    Voltage range..................................................................................24 V D C 15% (m ax. 37 V D C for 10 sec.)

    M ax. voltage ripple ................................................................................................................................2 V D C

    Pow er consum ption ....................................................................... 15 W - 50 W (50 W for start-up, 20 m sec.)

    M in. pre-fuse ..........................................................................................................................................6 Am p

    Reliable galvanic isolation: Full galvanic isolation if the external 24 V DC supp ly is also of the PELV type.

    C able lengths and cross-sections:

    M ax. m otor cable length, screened cable ...............................................................................................150 m

    M ax. m otor cable length, unscreened cable............................................................................................300 m

    M ax. m otor cable length, screened cable VLT 5011 380-500 V ..............................................................100 mM ax. brake cable length, screened cable ..................................................................................................20 m

    M ax. loadsharing cab le length, screened cable 25 m from frequency converter to D C bar.

    Max. cab le cross-section for mo tor, brake and loadsharing, see next section

    M ax. cable cross-section for 24 V external D C supply.......................................................... 4.0 m m 2/10 AW G

    M ax. cross-section for control cables ....................................................................................1.5 m m 2/16 AW G

    M ax. cross-section for serial com m unication .........................................................................1.5 m m 2/16 AW G

    Accuracy of display readout (param eters 009-012):

    M otor current [6] 0-140% load ..........................................................M ax. error: 2.0% of rated output current

    Torque % [7], -100 - 140% load .................................................................M ax. error: 5% of rated m otor size

    O utput [8], pow er H P [9], 0-90% load ..............................................................M ax. error: 5% of rated output

    Generaltechnicaldata General technical data

    C ontrol card, 24 V D C supply:

    Term inal nos...........................................................................................................................................12, 13

    M ax. load (short-circuit protection).......................................................................................................200 m A

    Term inal nos. ground .............................................................................................................................. 20, 39

    Reliable galvanic isolation: The 24 V DC supp ly is galvanically isolated from the supply voltage (PELV), but has

    the same po tential as the analogue outputs.

    C ontrol card, R S 485 serial com m unication:

    Term inal nos..........................................................................................................68 (TX+, R X+), 69 (TX-, R X-)

    Reliable galvanic iso lation: Full galvanic isolation.

    R elay outputs:

    N o. of program m able relay outputs .................................................................................................................2

    Term inal nos., control card ................................................................................................................4-5 (m ake)

    M ax. term inal load (AC ) on 4-5, control card......................................................................50 V AC , 1 A, 60 VAM ax. term inal load (D C ) on 4-5, control card ......................................................................75 V D C , 1 A, 30 W

    M ax. term inal load (D C ) on 4-5, control card for U L/cU L applications.................30 V AC , 1 A / 42.5 V D C , 1A

    Term inal nos., pow er card .............................................................................................1-3 (break), 1-2 (m ake)

    M ax. term inal load (AC ) on 1-3, 1-2, pow er card and relay card .................................240 V AC , 2 A, 60 VA

    M ax. term inal load on 1-3, 1-2, pow er card and relay card ......................................................50 V D C , 2 A

    M in. term inal load on 1-3, 1-2, pow er card and relay card ......................24 V D C 10 m A, 24 V AC 100 m A

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    11/173

    VLT5000 Series

    11M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    VLT 5000 S eries protection:

    Electronic m otor therm al protection against overload .

    Tem perature m onitoring of heat-sink ensures that the V LT freq uency converter cuts out if the tem perature

    reaches 90C for IP 00 and IP 20. For IP 54, the cut-out tem perature is 80C . An overtem perature can only be

    reset w hen the tem perature of the heat-sink has fallen below 60C.

    The V LT freq uency converter is protected against short-circuiting on m otor term inals U , V, W .

    The V LT frequency converter is protected against earth fault on m otor term inals U , V, W .

    M onitoring of the interm ediate circuit voltage ensures that the VLT frequency converter cuts out if the

    interm ediate circuit voltage gets too high or too low .

    If a m otor phase is m issing, the VLT frequency converter cuts out, see param eter 234 Motor phase

    monitor.

    If there is a m ains fault, the V LT frequency converter is able to carry out a controlled deram ping.

    If a m ains phase is m issing, the V LT frequency converter w ill cut out w hen a load is placed on the m otor.

    Generalt

    echnicaldata

    General technical data

    C ontrol characteristics:

    Frequency range .............................................................................................................................0 - 1000 H z

    R esolution on output frequency ........................................................................................................0.003 H z

    System response tim e ..........................................................................................................................3 m sec.

    Speed, control range (open loop)................................................................................ 1:100 of synchro. speed

    Speed, control range (closed loop)...........................................................................1:1000 of synchro. speed

    Speed, accuracy (open loop)...................................................................... < 1500 rpm : m ax. error 7.5 rpm

    > 1500 rpm : m ax. error of 0.5% of actual speed

    Speed, accuracy (closed loop)..................................................................... < 1500 rpm : m ax. error 1.5 rpm

    > 1500 rpm : m ax. error of 0.1% of actual speed

    Torque control accuracy (open loop)...........................................0- 150 rpm : m ax. error 20% of rated torque

    150-1500 rpm : m ax. error 10% of rated torque

    > 1500 rpm : m ax. error 20% of rated torque

    Torque control accuracy (speed feedback).......................................................M ax. error 5% of rated torque

    All control characteristics are based on a 4-pole asynchronous moto r

    Externals:

    Enclosure..............................................................................................................................IP 00, IP 20, IP 54

    Vibration test ............................0.7 g R M S 18-1000 H z random . 3 directions for 2 hours (IEC 68-2-34/35/36)

    M ax. relative hum idity.........................................................................93 % (IEC 68-2-3) for storage/transport

    M ax. relative hum idity ........................................95 % non condensing (IEC 721-3-3; class 3K 3) for operation

    Am bient tem perature IP 20 (high overload torque 160% )..................M ax. 45C (24-hour average m ax. 40C )

    Am bient tem perature IP 20 (norm al overload torque 110% ).............M ax. 40C (24-hour average m ax. 35C )

    Am bient tem perature IP 54 (high overload torque 160% )..................M ax. 40C (24-hour average m ax. 35C )

    Am bient tem perature IP 54 (norm al overload torque 110% ).............M ax. 40C (24-hour average m ax. 35C )

    Am bient tem perature IP 20/54 VLT 5011 500 V ................................M ax. 40C (24-hour average m ax. 35C )

    Derating for high ambient temperature, see page 96 of the Design Guide

    M in. am bient tem perature in full operation ...................................................................................................0C

    M in. am bient tem perature at reduced perform ance .................................................................................-10C

    Tem perature during storage/transport......................................................................................-25 - +65/70C

    M ax. altitude above sea level................................................................................................................1000 m

    Derating for high altitude, see page 96 o f the Design Guide

    EM C standards applied, Em ission ......................................EN 50081-1/2, EN 61800-3, EN 55011, EN 55014

    Im m unity ....................... EN 50082-2, EN 61000-4-2, IEC 1000-4-3, EN 61000-4-4

    EN 61000-4-5, EN V 50140, EN V 50141, VD E 0160/1990.12

    See section on special conditions in the Design Guide

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    12/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark12

    Technicaldata,

    Book

    styleIP20 Mains supply 3 x 200 - 240 V

    According to international req uirem ents VLVLVLVLVLT typeT typeT typeT typeT type 50015001500150015001 50025002500250025002 50035003500350035003 50045004500450045004 50055005500550055005 50065006500650065006

    O utput current IVLT,N[A] 3.7 5.4 7.8 10.6 12.5 15.2

    IVLT, M AX(60 s) [A] 5.9 8.6 12.5 17 20 24.3

    O utput (240 V) S VLT,N [kVA] 1.5 2.2 3.2 4.4 5.2 6.3Typical shaft output P VLT,N [kW ] 0.75 1.1 1.5 2.2 3.0 3.7

    Typ ical shaft outp ut P VLT,N [H P] 1 1.5 2 3 4 5

    M ax. cable cross-section to m otor,

    brake and loadsharing [m m 2]/[AW G ]2) 4/10 4/10 4/10 4/10 4/10 4/10

    R ated input current (200 V) IL,N[A] 3.4 4.8 7.1 9.5 11.5 14.5

    M ax. cable

    cross-section pow er [m m 2]/[AW G ]2) 4/10 4/10 4/10 4/10 4/10 4/10

    M ax. pre-fuses [-]/U L1)[A] 16/10 16/10 16/15 25/20 25/25 35/30

    Efficiency 3) 0.95

    W eight IP 20 EB [kg] 7 7 7 9 9 9,5

    Pow er loss at

    m ax. load. [W ] Total 58 76 95 126 172 194

    Enclosure VLT type IP 20

    1. If U L/cU L is to be com plied w ith, pre-fuses type B ussm ann K TN -R 200 V, K TS -R 500 V or sim ilar m ust be used . Pre-fuses type

    gG m ust be used for VLT 5001 - VLT 5027, 200/240 V and VLT 5001 - VLT 5052, 380/500 V. Pre-fuses type gR m ust be used

    for VLT 5032 - 5052, 200/240 V and VLT 5060 - VLT 55 00, 380/500 V. Fuses m ust be designed for protection in a circuit

    capable of supplying a m axim um of 100,000 Am ps m s (sym m etrical), 500 V m axim um .2. Am erican W ire G auge.

    3. M easured using 30 m screened m otor cables at rated load and rated frequency.

    VLVLVLVLVLT typeT typeT typeT typeT type 50015001500150015001 50025002500250025002 50035003500350035003 50045004500450045004 50055005500550055005 50065006500650065006 50085008500850085008 50115011501150115011

    O utput current IVLT,N[A] (380-440 V) 2.2 2.8 4.1 5.6 7.2 10 13 16

    IVLT, M AX(60 s) [A] (380-440 V) 3.5 4.5 6.5 9 11.5 16 20.8 25.6

    IVLT,N

    [A] (441-500 V) 1.9 2.6 3.4 4.8 6.3 8.2 11 14.5

    IVLT, M AX(60 s) [A] (441-500 V) 3 4.2 5.5 7.7 10.1 13.1 17.6 23.2

    O utput S VLT,N [kVA] (380-440 V) 1.7 2.1 3.1 4.3 5.5 7.6 9.9 12.2

    S VLT,N [kVA] (441-500 V) 1.6 2.3 2.9 4.2 5.5 7.1 9.5 12.6

    Typical shaft output P VLT,N [kW ] 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5

    Typical shaft output P VLT,N [H P] 1 1.5 2 3 4 5 7.5 10

    M ax. cable cross-section to m otor,

    brake and loadsharing [m m 2]/[AW G ]2) 4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10

    R ated input current IL,N [A] (380 V) 2.3 2.6 3.8 5.3 7 9.1 12.2 15.0

    IL,N [A] (460 V) 1.9 2.5 3.4 4.8 6 8.3 10.6 14.0

    M ax. cab le

    cross-section, p ow er [m m 2]/[AW G ]2) 4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10

    M ax. pre-fuses [-]/U L1)[A ] 16/6 16/6 16/10 16/10 16/15 25/20 25/25 35/30

    Efficiency3) 0.96

    W eight IP 20 EB [kg] 7 7 7 7.5 7.5 9.5 9.5 9.5

    Pow er loss at

    m ax. load. [W ] Total 55 67 92 110 139 198 250 295

    Enclosure VLT type IP 20

    Mains supply 3 x 380 - 500 VAccording to international req uirem ents

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    13/173

    VLT5000 Series

    13M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Technica

    ldata,CompactIP20and

    IP54

    VLVLVLVLVLT typeT typeT typeT typeT type 50015001500150015001 50025002500250025002 50035003500350035003 50045004500450045004 50055005500550055005 50065006500650065006

    H igh overload torH igh overload torH igh overload torH igh overload torH igh overload torquequequequeque (160 % ):::::

    O utput current IVLT,N[A] 3.7 5.4 7.8 10.6 12.5 15.2

    IVLT, M AX(60 s) [A] 5.9 8.6 12.5 17 20 24.3

    O utput (240 V) S VLT,N [kVA] 1.5 2.2 3.2 4.4 5.2 6.3Typical shaft output P VLT,N [kW ] 0.75 1.1 1.5 2.2 3.0 3.7

    Typ ical shaft outp ut P VLT,N [H P] 1 1.5 2 3 4 5

    M ax. cable cross-section to m otor,

    brake and loadsharing [m m 2]/[AW G ]2) 4/10 4/10 4/10 4/10 4/10 4/10

    R ated input current (200 V) IL,N[A] 3.4 4.8 7.1 9.5 11.5 14.5M ax. cable cross-section,

    pow er [m m 2]/[AW G ]2) 4/10 4/10 4/10 4/10 4/10 4/10

    M ax. pre-fuses [-]/U L 1 )[A] 16/10 16/10 16/15 25/20 25/25 35/30

    Efficiency 3) 0.95

    W eight IP 20 EB [kg] 8 8 8 10 10 10

    W eight IP 54 [kg] 11.5 11.5 11.5 13.5 13.5 13.5

    Pow er loss at

    m ax. load. [W ] Total 58 76 95 126 172 194

    Enclosure IP 20/IP 54

    Mains supply 3 x 200 - 240 VAccording to international requirem ents

    Mains supply 3 x 200 - 240 V

    According to international requirem ents

    1. If U L/cU L is to be com plied w ith, pre-fuses type B ussm ann K TN -R or sim ilar m ust be used. Pre-fuses type gG m ust be usedfor VLT 5001 - VLT 5027, 200/240 V and VLT 5001 - VLT 5052, 380/500 V. Pre-fuses type gR m ust be used for VLT 5032 -

    5052, 200/240 V and VLT 5060 - VLT 5500, 380/500 V. Fuses m ust be designed for protection in a circuit capable ofsupplying a m axim um of 100,000 Am ps m s (sym m etrical), 500 V m axim um .

    2. Am erican W ire G auge.

    3. M easured using 30 m screened m otor cables at rated load and rated frequency.4. M in. cable cross-section is the sm allest cab le cross-section allow ed to be fitted on the term inals.

    Alw ays com ply w ith national and local regulations on m in. cable cross-section.

    VLVLVLVLVLT typeT typeT typeT typeT type 50085008500850085008 50115011501150115011 50165016501650165016 50225022502250225022 50275027502750275027

    N orm al overload torqueN orm al overload torqueN orm al overload torqueN orm al overload torqueN orm al overload torque (110 % ):

    O utput current IVLT,N[A] 32 46 61.2 73 88

    IVLT, M AX(60 s) [A] 35.2 50.6 67.3 80.3 96.8

    O utput (240 V) S VLT,N [kVA] 13.3 19.1 25.4 30.3 36.6

    Typical shaft output P VLT,N [kW ] 7.5 11 15 18.5 22

    Typ ical shaft outp ut P VLT,N [H P] 10 15 20 25 30

    H igh overload torqueH igh overload torqueH igh overload torqueH igh overload torqueH igh overload torque (160 % ):

    O utput current IVLT,N[A] 25 32 46 61,2 73

    IVLT, M AX(60 s) [A] 40 51.2 73.6 97.9 116.8

    O utput (240 V) S VLT,N [kVA ] 10 13 19 25 30

    Typical shaft output P VLT,N [kW ] 5.5 7.5 11 15 18.5

    Typ ical shaft outp ut P VLT,N [H P] 7,5 10 15 20 25

    M ax. cable cross-section to m otor, IP 54 16/6 16/6 35/2 35/2 50/0

    brake and loadsharing [m m 2/A W G ]2) IP 20 16/6 35/2 35/2 35/2 50/0

    M in. cable cross-section to m otor,brake and loadsharing 4)[m m 2/A W G ]2) 10/8 10/8 10/8 10/8 16/6

    R ated input current (200 V) IL,N[A] 32 46 61 73 88

    M ax. cable cross-section, IP 54 16/6 16/6 35/2 35/2 50/0

    pow er [m m 2]/[AW G ]2) IP 20 16/6 35/2 35/2 35/2 50/0

    M ax. pre-fuses [-]/U L 1 )[A] 50 60 80 125 125

    Pre-fuse SM P S [-]/U L 1 )[A] 4.0/4.0

    Efficiency 3) 0.95

    W eight IP 00 [kg]

    W eight IP 20 EB [kg] 23 23 30 30 48

    W eight IP 54 [kg] 35 38 49 50 55

    Pow er loss at m ax. load.

    - high overload torque (160 % ) [W ] 340 426 626 833 994

    - norm al overload torque (110 % ) [W ] 426 545 783 1042 1243

    Enclosure IP 20+N EM A 1 kit, IP 54/N EM A 12

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    14/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark14

    Technicaldata,

    CompactIP20andIP54 Mains supply 3 x 380 - 500 V

    According to international req uirem ents VLVLVLVLVLT typeT typeT typeT typeT type 50015001500150015001 50025002500250025002 50035003500350035003 50045004500450045004 50055005500550055005 50065006500650065006 50085008500850085008 50115011501150115011

    H igh overload torH igh overload torH igh overload torH igh overload torH igh overload torquequequequeque (160 % ):::::

    O utput current IVLT,N[A] (380-440 V) 2.2 2.8 4.1 5.6 7.2 10 13 16

    IVLT, M AX(60 s) [A] (380-440 V) 3.5 4.5 6.5 9 11.5 16 20.8 25.6

    IVLT,N[A] (441-500 V) 1.9 2.6 3.4 4.8 6.3 8.2 11 14.5

    IVLT, M AX (60 s) [A] (441-500 V) 3 4.2 5.5 7.7 10.1 13.1 17.6 23.2

    O utput S VLT,N [kVA] (380-440 V) 1.7 2.1 3.1 4.3 5.5 7.6 9.9 12.2

    S VLT,N [kVA] (441-500 V) 1.6 2.3 2.9 4.2 5.5 7.1 9.5 12.6

    Typical shaft output P VLT,N [kW ] 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5

    Typ ical shaft outp ut P VLT,N [H P] 1 1.5 2 3 4 5 7.5 10

    M ax. cable cross-section to m otor,

    brake and loadsharing [m m 2]/[AW G ]2) 4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10

    Rated input current IL,N [A] (380 V) 2.3 2.6 3.8 5.3 7 9.1 12.2 15.0

    IL,N [A] (460 V) 1.9 2.5 3.4 4.8 6 8.3 10.6 14.0

    M ax. cable cross-section, 4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10pow er [m m 2]/[AW G ]2)

    M ax. pre-fuses [-]/U L 1 )[A ] 16/6 16/6 16/10 16/10 16/15 25/20 25/25 35/30

    Efficiency 3) 0.96

    W eight IP 20 EB [kg] 8 8 8 8.5 8.5 10.5 10.5 10.5

    W eight IP 54 [kg] 11.5 11.5 11.5 12 12 14 14 14

    Pow er loss at

    load [W ] Total 55 67 92 110 139 198 250 295

    Enclosure IP 20/IP 54

    1. If U L/cU L is to be com plied w ith, pre-fuses type B ussm ann K TS -R or sim ilar m ust be used . Pre-fuses type gG m ust be used for

    VLT 5001 - 5027, 200/240 V and VLT 5001 - 5052, 380/500 V. Pre-fuses type gR m ust be used for VLT 5032 - 5052, 200/240

    V and VLT 5060 - 5500, 380/500 V. Fuses m ust be designed for protection in a circuit capable of supplying a m axim um of

    100,000 Am ps m s (sym m etrical), 500 V m axim um .

    2. Am erican W ire G auge.

    3. M easured using 30 m screened m otor cables at rated load and rated frequency.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    15/173

    VLT5000 Series

    15M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Technicaldata,CompactIP20and

    IP54

    VLVLVLVLVLT typeT typeT typeT typeT type 50165016501650165016 50225022502250225022 50275027502750275027 50325032503250325032 50425042504250425042 50525052505250525052

    N orm al overload torN orm al overload torN orm al overload torN orm al overload torN orm al overload torquequequequeque (110 % ):

    O utput current IVLT,N[A] (380-440 V) 32 37.5 44 61 73 90

    IVLT, M AX(60 s) [A] (380-440 V) 35.2 41.3 48.4 67.1 80.3 99

    IVLT,N[A] (441-500 V) 27.9 34 41.4 54 65 78IVLT, M AX(60 s) [A] (441-500 V) 30.7 37.4 45.5 59.4 71.5 85.8

    O utput S VLT,N[kVA] (380-440 V) 24.4 28.6 33.5 46.5 55.6 68.6

    S VLT,N[kVA] (441-500 V) 24.2 29.4 35.8 46.8 56.3 67.5

    Typical shaft output P VLT,N[kW ] 15 18.5 22 30 37 45

    Typ ical shaft outp ut P VLT,N[H P] 20 25 30 40 50 60

    H igh o verload torH igh overload torH igh o verload torH igh overload torH igh overload torquequequequeque (160 % ):::::

    O utput current IVLT,N[A] (380-440 V) 24 32 37.5 44 61 73

    IVLT, M AX (60 s) [A] (380-440 V) 38.4 51.2 60 70.7 97.6 116.8

    IVLT,N[A] (441-500 V) 21.7 27.9 34 41.4 54 65

    IVLT, M AX (60 s) [A] (441-500 V) 34.7 44.6 54.4 66.2 86 104

    O utput S VLT,N [kVA] (380-440 V) 18.3 24.4 28.6 33.5 46.5 55.6

    S VLT,N [kVA] (441-500 V) 18.8 24.2 29.4 35.9 46.8 56.3Typical shaft output P VLT,N [kW ] 11 15 18.5 22 30 37

    Typ ical shaft outp ut P VLT,N [H P] 15 20 25 30 40 50

    M ax. cable cross-section to m otor, IP 54 16/6 16/6 16/6 35/2 35/2 50/0

    brake and loadsharing [m m 2]/[AW G ]2) IP 20 16/6 16/6 35/2 35/2 35/2 50/0

    M in. cable cross-section to m otor,

    brake and loadsharing [m m 2]/[AW G ] 10/8 10/8 10/8 10/8 10/8 16/6

    Rated input current IL,N [A] (380 V) 32 37.5 44 60 72 89

    IL,N [A] (460 V) 27.6 34 41 53 64 77

    M ax. cable cross-section, IP 54 16/6 16/6 16/6 35/2 35/2 50/0

    pow er [m m 2]/[AW G ] IP 20 16/6 16/6 35/2 35/2 35/2 50/0

    M ax. pre-fuses [-]/U L 1 )[A] 63/40 63/50 63/60 80/80 100/100 125/125Pre-fuse SM P S [-]/U L 1 )[A] 4.0/4.0

    Efficiency 0.96

    W eight IP 20 EB [kg] 23 23 30 30 48 48

    W eight IP 54 [kg] 48 48 51 61 67 70

    Pow er loss at m ax. load.

    - high overload torque (160 % ) [W ] 419 559 655 768 1065 1275

    - norm al overload torque (110 % ) [W ] 559 655 768 1065 1275 1571

    Enclosure IP 20/IP 54

    Mains supply 3 x 380 - 500 VAccording to international requirem ents

    1. If U L/cU L is to be com plied w ith, pre-fuses type B ussm ann K TS -R or sim ilar m ust be used . Pre-fuses type gG m ust be used for

    VLT 5001 - 5027, 200/240 V and VLT 5001 - 5052, 380/500 V. Pre-fuses type gR m ust be used for VLT 5032 - 5052, 200/240V and VLT 5060 - 5500, 380/500 V. Fuses m ust be designed for protection in a circuit cap able of supplying a m axim um of

    100,000 Am ps m s (sym m etrical), 500 V m axim um .

    2. Am erican W ire G auge.

    3. M easured using 30 m screened m otor cables at rated load and rated frequency.

    4. M in. cable cross-section is the sm allest cab le cross-section allow ed to be fitted on the term inals.

    Alw ays com ply w ith national and local regulations on m in. cable cross-section.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    16/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark16

    Technical

    data,

    CompactIP00,

    IP20andIP54

    VLVLVLVLVLT typeT typeT typeT typeT type 50325032503250325032 50425042504250425042 50525052505250525052

    N orm al overload torN orm al overload torN orm al overload torN orm al overload torN orm al overload torquequequequeque (110 % ):::::

    O utput current IVLT,N[A] (200-230 V) 115 143 170

    IVLT, M AX

    (60 s) [A] (200-230 V) 127 158 187IVLT,N[A] (231-240 V) 104 130 154

    IVLT, M AX(60 s) [A] (231-240 V) 115 143 170

    O utput S VLT,N [kVA] (200-230 V) 41 52 61

    S VLT,N [kVA] (231-240 V) 41 52 61

    Typical shaft output (200-240 V) P VLT,N [kW ] 30 37 45

    Typical shaft output (200-240 V) P VLT,N [H P] 40 50 60

    H igh overload torH igh overload torH igh overload torH igh overload torH igh overload torquequequequeque (150 % ):::::

    O utput current IVLT,N[A] (200-230 V) 88 115 143

    IVLT, M AX(60 s) [A] (200-230 V) 132 173 215

    IVLT,N[A] (231-240 V) 80 104 130

    IVLT, M AX (60 s) [A] (231-240 V) 120 156 195

    O utput S VLT,N [kVA] (200-230 V) 32 41 52

    S VLT,N [kVA] (231-240 V) 32 41 52

    Typical shaft output (200-240 V) P VLT,N [kW ] 22 30 37

    Typical shaft output (200-240 V)P VLT,N [H P] 30 40 50

    M ax. cross-section of copper cable to m otor, brake

    and loadsharing (200-240 V) [m m 2]5) 70 90 120

    M ax. cross-section of alum inium cable to m otor, brake

    and loadsharing (200-240 V) [m m 2]5) 95 95 120

    M ax. cross-section of copper cable to m otor, brake

    and loadsharing (200-240 V) [AW G ]2) 5) 1/0 3/0 4/0

    M ax. cross-section of alum inium cable to m otor, brake

    and loadsharing (200-240 V) [AW G ]2) 5) 3/0 250m cm 300m cm

    M in. cable cross-section to m otor,

    brake and loadsharing 4) [m m 2/AW G ]2) 5) 10/8 10/8 10/8

    Mains supply 3 x 200 - 240 V

    According to international req uirem ents

    1. If U L/cU L is to b e com plied w ith, pre-fuses type B ussm ann FW H and FW X or sim ilar m ust be used. Pre-fuses type gG m ust beused for VLT 500 1 - 5027, 200/240 V and VLT 5001 - 5052, 380/500 V. Pre-fuses type gR m ust be used for VLT 5032 - 5052,20 0/240 V and V LT 506 0 - 5500, 380/500 V. Fuses m ust be designed for protection in a circuit capable of sup plying am axim um of 100,000 Am ps m s (sym m etrical), 500 V m axim um .

    2. Am erican W ire G auge.3. M easured using 30 m screened m otor cables at rated load and rated frequency.4. M in. cable cross-section is the sm allest cable cross-section allow ed to be fitted on the term inals.

    Alw ays com ply w ith national and local regulations on m in. cable cross-section.

    5. C onnection stud 1 x M 8/2 x M 8.

    R ated input current IL,N [A] (230 V) 101.3 126.6 149.9

    M ax. cross-section of copper cable

    to pow er (200-240 V) [m m 2]5) 70 90 120

    M ax. cross-section of alum inium cable

    to pow er (200-240 V) [m m 2]5) 95 95 120

    M ax. cross-section of copper cable

    to pow er (200-240 V) [AW G ]2) 5) 1/0 3/0 4/0

    M ax. cross-section of alum inium cable

    to pow er (200-240 V) [AW G ]2) 5) 3/0 250m cm 300m cm

    M in. cable cross-section to m otor,

    brake and loadsharing 4) [m m 2/AW G ]2) 5) 10/8 10/8 10/8

    M ax. pre-fuses (m ains) [-]/U L 1 )[A] 150 200 250

    Integral pre-fuses

    (softcharge circuit) [-]/UL 1 )[A] 15/15 15/15 15/15Integral pre-fuses

    (softcharge resistors) [-]/U L 1 )[A] 12/12 12/12 12/12

    Integral pre-fuses (SM PS) [-]/U L 1 )[A] 12/12

    Efficiency 3) 0.96-0.97

    W eight IP 00 [kg] 90 90 90

    W eight IP 20 EB [kg] 101 101 101

    W eight IP 54 [kg] 104 104 104

    Pow er loss at m ax. load [W ] 1089 1361 1613

    Enclosure IP 00 / IP 20/ IP 54

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    17/173

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    18/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark18

    Technical

    data,

    CompactIP00,

    IP20andIP54

    VLVLVLVLVLT typeT typeT typeT typeT type 50605060506050605060 50755075507550755075 51005100510051005100 51255125512551255125 51505150515051505150 52005200520052005200 52505250525052505250

    R ated input current IL,N [A] (400 V) 87.6 103 145 174 206 256 318

    IL,N [A] (460 V) 77.9 103 128 158 185 236 304

    M ax. cross-section ofcopp er cab le

    to pow er (380-440 V) [m m 2]5) 70 95 120 2x70 2x70 2x95 2x120

    M ax. cross-section of

    copp er cab le

    to pow er (441-500 V) [m m 2]5) 70 70 95 2x70 2x70 2x95 2x120

    M ax. cross-section of

    alum inium cable

    to pow er (380-440 V) [m m 2]5) 95 120 150 2x70 2x120 2x120 2x150

    M ax. cross-section of

    alum inium cable

    to pow er (441-500 V) [m m 2]5) 70 90 120 2x70 2x95 2x120 2x150

    M ax. cross-section of

    copp er cab le

    to pow er (380-440 V) [AW G ]2) 5) 1/0 3/0 4/0 2x1/0 2x2/0 2x3/0 2x250m cm

    M ax. cross-section of

    copp er cab le

    to pow er (441-500 V) [AW G ]2) 5) 1/0 2/0 3/0 2x1/0 2x1/0 2x3/0 2x4/0

    M ax. cross-section of

    alum inium cable

    to pow er (380-440 V) [AW G ]2) 5) 3/0 250m cm 300m cm 2x2/0 2x4/0 2x250m cm 2x350m cm

    M ax. cross-section of

    alum inium cable

    to pow er (441-500 V) [AW G ]2) 5) 3/0 4/0 250m cm 2x2/0 2x3/0 2x250m cm 2x300m cm

    M in. cable cross-section to m otor,

    brake and loadsharing 4) [m m 2/AW G ]2) 5) 10/8 10/8 10/8 10/8 10/8 16/6

    M ax. pre-fuses (m ains) [-]/U L 1 )[A] 150/150 250/220 250/250 300/300 350/350 450/400 500/500

    Integral pre-fuses(softcharge circuit) [-]/UL 1 )[A] 15/15 15/15 15/15 30/30 30/30 30/30 30/30

    Integral pre-fuses

    (softcharge resistors) [-]/U L 1 )[A] 12/12 12/12 12/12 12/12 12/12 12/12 12/12

    Integral pre-fuses (SM PS) [-]/U L 1 )[A] 5.0/5.0

    Efficiency 0.96-0.97

    W eight IP 00 [kg] 109 109 109 146 146 146 146

    W eight IP 20 EB [kg] 121 121 121 161 161 161 161

    W eight IP 54 [kg] 124 124 124 177 177 177 177

    Pow er loss at m ax. load [W ] 1430 1970 2380 2860 3810 4770 5720

    Enclosure IP 00 / IP 20/ IP 54

    Mains supply 3 x 380-500 VAccording to international req uirem ents

    1. If U L/cU L is to b e com plied w ith, pre-fuses type B ussm ann FW H and FW X or sim ilar m ust be used. Pre-fuses type gG m ust be

    used for VLT 500 1 - 5027, 200/240 V and VLT 5001 - 5052, 380/500 V. Pre-fuses type gR m ust be used for VLT 5032 - 5052,

    20 0/240 V and V LT 506 0 - 5500, 380/500 V. Fuses m ust be designed for protection in a circuit capable of sup plying a

    m axim um of 100,000 Am ps m s (sym m etrical), 500 V m axim um .

    2. Am erican W ire G auge.

    3. M easured using 30 m screened m otor cables at rated load and rated frequency.

    4. M in. cable cross-section is the sm allest cab le cross-section allow ed to be fitted on the term inals.

    Alw ays com ply w ith national and local regulations on m in. cable cross-section.

    5. C onnection stud 1 x M 8/2 x M 8.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    19/173

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    20/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark20

    VLVLVLVLVLT typeT typeT typeT typeT type 53005300530053005300 53505350535053505350 54505450545054505450 55005500550055005500

    Rated input current IL,M AX [A] (400 V) 389 467 584 648

    IL,M AX [A] (460 V) 356 431 526 581

    M ax. cross-section ofcopper cable 2 x 150 2 x 185 2 x 240 2 x 300

    to pow er (380-440 V) [m m 2]5) 3 x 70 3 x 95 3 x 120 3 x 150

    M ax. cross-section of

    copper cable 2 x 120 2 x 150 2 x 185 2 x 300

    to pow er (460-500 V) [m m 2]5) 3 x 70 3 x 95 3 x 95 3 x 120

    M ax. cross-section of

    alum inium cable 2 x 185 2 x 240 2 x 300

    to pow er (380-440 V) [m m 2]5) 3 x 120 3 x 150 3 x 185 3 x 185

    M ax. cross-section of

    alum inium cable 2 x 150 2 x 185 2 x 240

    to pow er (460-500 V) [m m 2]5) 3 x 95 3 x 120 3 x 150 3 x 185

    M ax. cross-section of

    copper cable 2 x 250m cm 2 x 350m cm 2 x 400m cm 2 x 500m cm

    to pow er (380-440 V) [AW G ]2) 5) 3 x 2/0 3 x 3/0 3 x 4/0 3 x 250m cm

    M ax. cross-section of

    copper cable 2 x 4/0 2 x 300m cm 2 x 350m cm 2 x 500m cm

    to pow er (460-500 V) [AW G ]2) 5) 3 1/0 3 x 3/0 3 x 3/0 3 x 4/0

    M ax. cross-section of

    alum inium cable 2 x 350m cm 2 x 500m cm 2 x 600m cm 2 x 700m cm

    to pow er (380-440 V) [AW G ]2) 5) 3 x 4/0 3 x 250m cm 3 x 300m cm 3 x 350m cm

    M ax. cross-section of

    alum inium cable 2 x 300m cm 2 x 400m cm 2 x 500m cm 2 x 600m cm

    to pow er (460-500 V) [AW G ]2) 5) 3 x 3/0 3 x 4/0 3 x 250m cm 3 x 300m cm

    M ax. pre-fuses (m ains) [-]/U L 1 )[A] 630/600 700/700 800/800 800/800

    Integral pre-fuses

    (softcharge circuit) [-]/UL 1 )[A ] 15/15 15/15 15/15 30/30

    Integral pre-fuses(softcharge resistors) [-]/U L 1 )[A ] 12/12 12/12 12/12 12/12

    Integral pre-fuses (SM PS) [-]/U L 1 )[A ] 5 .0 /5 .0

    Efficiency 0.97

    W eight IP 00 [kg] 480 515 560 585

    W eight IP 20 [kg] 595 630 675 700

    W eight IP 54 [kg] 605 640 685 710

    Pow er loss at m ax. load [W ] 7500 9450 10650 12000

    Enclosure IP 00 / IP 20/ IP 54

    Mains supply 3 x 380-500 V

    According to international req uirem ents

    1. If U L/cU L is to be com plied w ith, pre-fuses type B ussm ann FW H and FW X or sim ilar m ust be used. Pre-fuses type gG m ust be

    used for VLT 5001 - VLT 5027, 200/240 V and VLT 5001 - VLT 5052, 380/500 V. Pre-fuses type gR m ust be used for VLT

    5032 - 5052, 200/240 V and VLT 5060 - VLT 5500 , 380/500 V. Fuses m ust be designed for protection in a circuit capable of

    supplying a m axim um of 100,000 Am ps m s (sym m etrical), 500 V m axim um .

    2. Am erican W ire G auge.

    3. M easured using 30 m screened m otor cables at rated load and rated frequency.

    4. M in. cable cross-section is the sm allest cable cross-section allow ed to be fitted on the term inals.

    Alw ays com ply w ith national and local regulations o n m in. cable cross-section.

    5. C onnection stud 2 x M 12 / 3 x M 12.

    Technicaldata,CompactIP00,I

    P20

    andIP54

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    21/173

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    22/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark22

    Measurements,d

    imensions Compact IP 00

    IP 00 enclosure 200-240 V

    VLT type A (mm) B (mm) C (mm) a (mm) b (mm) a b/be (mm) l/r (mm)

    5032 - 5052 800 370 335 780 270 225 0

    IP 00 enclosure 380-500 V

    VLT type A (mm) B (mm) C (mm) a (mm) b (mm) ab/be (mm) l/r (mm)

    5060 - 5100 800 370 335 780 270 225 0

    5125 - 5250 1400 420 400 1380 350 225 0

    5300 - 5500 1896 1099 490 - - 400 0

    ab:M in. space above enclosure. be: M in. space below enclosure.

    l/r:M in. distance betw een VLT frequency converter and other plant com ponents, left and right sides.

    VLT 5060 - 5250/380-500 V

    IP 20 bottom cover

    VLT type A1 (mm) B 1 (mm) C1 (mm)

    5060 - 5100 175 370 335

    5125 - 5250 175 420 400

    VLT 5300 - 5500/380-500 V

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    23/173

    VLT5000 Series

    23M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Measurements,dimensions

    Compact IP 20

    IP 20 enclosure 200-240 V

    VLT type A (mm) B (mm) C (mm) a (mm) b (mm) ab/be (mm) l/r (mm)

    5001 - 5003 395 220 160 384 200 100 0

    5004 - 5006 395 220 200 384 200 100 0

    5008 560 242 260 540 200 200 0

    5011 - 5016 700 242 260 680 200 200 0

    5022 - 5027 800 308 296 780 270 200 0

    5032 - 5052 954 370 335 780 270 225 0

    IP 20 enclosure 380-500 V

    VLT type A (mm) B (mm) C (mm) a (mm) b (mm) ab/be (mm) l/r (mm)

    5001 - 5005 395 220 160 384 200 100 0

    5006 - 5011 395 220 200 384 200 100 0

    5016 - 5022 560 242 260 540 200 200 0

    5027 - 5032 700 242 260 680 200 200 0

    5042 - 5052 800 308 296 780 270 200 0

    5060 - 5100 975 370 335 780 270 225 0

    5125 - 5250 1575 420 400 1380 350 225 0

    5300 - 5500 2010 1200 600 - - 400 0

    ab:M in. space above enclosure. be: M in. space below enclosure.

    l/r:M in. distance betw een VLT frequency converter and other plant com ponents, left and right sides.

    VLT 5008 - 5027/200-240 V

    VLT 5016 - 5052/380-500 V

    VLT 5001 - 5006/200-240 V

    VLT 5001 - 5011/380-500 V

    VLT 5032 - 5052/200-240 V

    VLT 5060 - 5250/380-500 V

    VLT 5300 - 5500/380-500 V

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    24/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark24

    Measurements,d

    imensions Compact IP 54

    IP 54 enclosure 200-240 V

    VLT type A (mm) B (mm) C (mm) D (mm) a (mm) b (mm) ab/be (mm) l/r (mm)5001 - 5003 460 282 195 85 260 258 100 0

    5004 - 5006 530 282 195 85 330 258 100 0

    5008 - 5011 810 355 280 70 560 330 200 0

    5016 - 5027 940 400 280 70 690 375 200 0

    5032 - 5052 937 495 421 - 830 374 225 50

    IP 54 enclosure 380-500 V

    VLT type A (mm) B (mm) C (mm) D (mm) a (mm) b (mm) ab/be (mm) l/r (mm)

    5001 - 5005 460 282 195 85 260 258 100 0

    5006 - 5011 530 282 195 85 330 258 100 0

    5016 - 5027 810 355 280 70 560 330 200 0

    5032 - 5052 940 400 280 70 690 375 200 0

    5060 - 5100 937 495 421 - 830 374 225 50

    5125 - 5250 1572 495 425 - 1465 445 225 0

    5300 - 5500 2010 1200 600 - - - 400 0

    ab:M in. space above enclosure. be: M in. space below enclosure.

    l/r:M in. distance betw een VLT frequency converter and other plant com ponents, left and right sides.

    VLT 5060 - 5250/380-500 V

    VLT 5032 - 5052/200-240 V

    VLT 5001 - 5027/200-240 V

    VLT 5001 - 5052/380-500 V

    VLT 5300 - 5500/380-500 V

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    25/173

    VLT5000 Series

    25M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Mechanicalinstallation

    Mechanical installation

    Please pay attention to the requirem ents

    that apply to integration and field

    m ounting kit, see the b elow list. The

    inform ation given in the list m ust be observed to avoid

    serious dam age or injury, especially w hen installing

    large units.

    The V LT frequency convertermust be installed

    vertically.

    The V LT frequency converter is cooled by m eans of

    air circulation. For the unit to be able to release its

    cooling air, the minimumdistance over and below the

    unit m ust be as show n in the illustration below .

    To protect the unit from overheating, it m ust be

    ensured that the am bient tem perature does not riseabove the max.temperature stated for the VLT

    frequency converterand that the 24-hour average

    tem perature is not exceeded.The m ax. tem perature

    and 24-hour average can b e seen from the G eneral

    Technical D ata on page 11.

    If the am bient tem perature is in the range of 45 C -

    55 C , derating of the VLT frequency converter w ill be

    required in accordance w ith the diagram on page

    96 of the D esign G uide. The service life of the VLT

    frequency converter w ill be red uced if no allow ance is

    m ade for the derating for am bient tem perature.

    Installation of VLT 5001-5006 200-240 V, VLT 5001-5011 380-500 V Bookstyle IP 20

    Cooling

    All B ookstyle units require a m inim um space of

    100 m m above and below the enclosure.

    Side-by-side

    All B ookstyle units can be installed side by side

    w ithout any space betw een them , since the units do

    not require any cooling on the sides.

    Enclosure protection

    IP 00 IP 20 IP 54

    B ookstyle - O K -

    C om pact

    VLT 5001-5027 200-240 V - O K O K

    VLT 5001-5250 380-500 V O K O K O K

    VLT 5300-5500 380-500 V O K O K O K

    Field mounting

    IP 00 IP 20 IP 54

    B ookstyle - N o -

    C om pact

    VLT 5001-5027 200-240 V - N o O K

    VLT 5001-5250 380-500 V N o N o O KVLT 5300-5500 380-500 V N o N o O K

    C om pact w /IP 4x top cover

    VLT 5001-5006 200 V - O K O K

    VLT 5001-5011 500 V - O K O K

    C om pact w /IP 20 term inal cover

    VLT 5008-5027 200 V - O K O K

    VLT 5016-5052 500 V - O K O K

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    26/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark26

    Mechanicalinstallation

    Installation of VLT 5008-5027 200-240 V, VLT 5016-5052 380-500 V Compact IP 20 and IP 54

    Cooling

    All C om pact units in the above-m entioned series

    require a m inim um space of 200 m m above and

    below the enclosure and m ust be installed on a plane,

    vertical surface (no spacers). This applies to both IP

    20 and IP 54 units.

    Side-by-side

    C om pact IP 20

    C om pact IP 54 (flange-by-flange)

    All IP 20 and IP 54 units in the above-m entioned

    series can be installed side by side w ithout any space

    betw een them , since these units do not require

    cooling on the sides.

    Installation of VLT 5001-5006 200-240 V, VLT 5001-5011 380-500 V Compact IP 20 and IP 54

    Cooling

    All C om pact units require a m inim um space of 100

    m m above and below the enclosure and m ust be

    installed on a plane, vertical surface (no spacers). This

    applies to both IP 20 and IP 54 units.

    Side-by-side

    All C om pact units can be installed side-by-side

    w ithout any space betw een them , since the units do

    not require any cooling on the sides.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    27/173

    VLT5000 Series

    27M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Installation of VLT 5125-5250 380-500 V Compact IP 00, IP 20 and IP 54

    Cooling

    All C om pact units in the above-m entioned series

    require a m inim um space of 225 m m above and

    below the enclosure and m ust be installed on a p lane,

    vertical surface (no spacers). This applies to both IP

    00, IP 20 and IP 54 units.

    Side-by-side

    C om pact IP 00 and IP 20

    C om pact IP 54

    All IP 00, IP 20 and IP 54 units in the above-m entioned series can be installed side by side w ithout

    any space betw een them , since these units do not

    require cooling on the sides.

    Mechanicalinstallation

    Installation of VLT 5060-5100 380-500 V, VLT 5032-5052 200-240 V Compact IP 00, IP 20 and IP 54

    Cooling

    All C om pact units in the above-m entioned series

    require a m inim um space of 225 m m above and

    below the enclosure and m ust be installed on a p lane,

    vertical surface (no spacers). This applies to both IP

    00, IP 20 and IP 54 units.

    Side-by-side

    C om pact IP 00 and IP 20

    C om pact IP 54

    All IP 00 and IP 20 units in the above-m entioned

    series can be installed side by side w ithout any space

    betw een them .

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    28/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark28

    Side-by-side

    C om pact IP 00, IP 20 and IP 54

    All IP 00, IP 20 and IP 54 units in the above-

    m entioned series can be installed side b y side

    w ithout any space betw een them , since these units

    do not req uire cooling on the sides.

    Installation of VLT 5300-5500 380-500 V Compact IP 00, IP 20 and IP 54

    Cooling

    All units in the above-m entioned series require a

    m inim um space of 400 m m above the enclosure

    and m ust be installed on a plane floor. This appliesto both IP 00, IP 20 and IP 54 units.

    G aining access to the VLT 5300-5500 requires a

    m inim um space of 605 m m in front of the V LT

    freq uency converter.

    Mechanicalinstallation

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    29/173

    VLT5000 Series

    29M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Electrical installation

    The voltage on the frequency converter is

    dangerous w hen the unit is connected to

    m ains. Incorrect installation of the m otor

    or VLT frequency converter m ay lead to

    m aterial dam age or serious injury or it m ay be fatal.

    C onsequently, the instructions in this m anual as w ell

    as national and local rules and safety regulations m ust

    be com plied w ith.

    Touching the electrical parts m ay be fatal, even after

    the m ains sup ply has been disconnected.

    W ait at least 4 m inutes if using VLT 5001-5006 and at

    least 15 m inutes if using VLT 5008-5500.

    NB!

    It is the user's or certified electrician'sresponsibility to ensure correct earthing and

    protection in accordance w ith ap plicable national and

    local norm s and standards.

    All term inals for the control cables are located under

    the protective cover of the VLT freq uency converter.

    The protective cover (see draw ing) can b e rem oved

    by m eans of a pointed ob ject - a screw driver or

    sim ilar.

    O nce the p rotective cover has been rem oved, the

    actual EM C -correct installation can start.

    See draw ings on pages 30-32.

    Electricalinstallation,Bookstyle/Compact

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    30/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark30

    Bookstyle

    0.75 - 7.5kW

    Compact IP 20/IP 54

    0.75 - 7.5kW

    Compact IP 20

    11 - 37kW

    Compact IP 54

    11 - 37kW

    Electricalinstallation

    Electrical installation, power cables

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    31/173

    VLT5000 Series

    31M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Compact IP 54

    90 - 160kW

    Compact IP 00/IP 20

    90 - 160kW

    Compact IP 00/IP 20

    45 - 75 kW

    Compact IP 54

    45 - 75kW

    Electrical installation, power cables Electricalinstallation

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    32/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark32

    Compact IP 20/IP 54

    with disconnector and mains fuses

    200 - 500kW

    Compact IP 20/IP 54

    without disconnector and mains fuses

    200 kW - 500kW

    Electricalinstallation Electrical installation, power cables

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    33/173

    VLT5000 Series

    33M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Electricalinstallation,enclosures

    Electrical installation, enclosures

    Bookstyle IP 20

    VLT 5001-5006, 200-240 V

    VLT 5001-5011, 380-500 V

    Compact IP 20

    VLT 5001-5006, 200-240 V

    VLT 5001-5011, 380-500 V

    Compact IP 20

    VLT 5008-5027, 200-240 V

    VLT 5016-5052, 380-500 V

    Compact IP 54

    VLT 5001-5006, 200-240 V

    VLT 5001-5011, 380-500 V

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    34/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark34

    Electrical installation, enclosures

    Electricalinstallation,enclosures

    Compact IP 54

    VLT 5008-5027, 200-240 V

    VLT 5016-5052, 380-500 V

    Compact IP 00

    VLT 5032-5052, 200-240 V

    VLT 5060-5100, 380-500 V

    Compact IP 00

    VLT 5125-5250, 380-500 V

    Compact IP 20

    VLT 5032-5052, 200-240 V

    VLT 5060-5100, 380-500 V

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    35/173

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    36/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark36

    Electricalinstallation,e

    nclosures

    Compact IP 20 / IP 54

    VLT 5300-5500, 380-500 V

    Electrical installation, enclosures

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    37/173

    VLT5000 Series

    37M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Electrica

    linstallation

    EMC-correct electrical installation

    G eneral points to be observed to ensure EM C -correct

    electrical installation:

    - U se only braided screened/arm oured m otor

    cables and braided screened/arm oured control

    cables.

    - C onnect the screen to earth at both end s.

    - Avoid installation w ith tw isted screen ends

    (pigtails), since this ruins the screening effect at

    high frequencies. U se cable clam ps instead.

    - It is im portant to ensure good electrical contact

    from the installation plate through the installation

    screw s to the m etal cabinet of the VLT frequency

    converter.

    - U se starw ashers and galvanically conductiveinstallation plates.

    - D o not use unscreened/unarm oured m otor cables

    in the installation cabinets.

    The illustration below show s EM C -correct electrical

    installation; the VLT frequency converter has been

    fitted in an installation cabinet and connected to a

    PLC.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    38/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark38

    Electricalinstallation Use of EMC-correct cables

    B raided screened/arm oured cables are

    recom m ended to optim ise EM C im m unity of the

    control cables and the EM C em ission from the m otor

    cables.

    The ab ility of a cable to reduce the in- and outgoing

    radiation of electric noise dep ends on the transfer

    im pedance (ZT). The screen of a cable is norm ally

    designed to reduce the transfer of electric noise;

    how ever, a screen w ith a low er transfer im pedance

    (ZT) value is m ore effective than a screen w ith a higher

    transfer im pedance (ZT).

    Transfer im pedance (ZT) is rarely stated by cable

    m anufacturers, but it is often possible to estim ate

    transfer im pedance (ZT) by assessing the physical

    design of the cable.

    Transfer im pedance (ZT) can be assessed on the

    basis of the follow ing factors:

    - The cond uctibility of the screen m aterial.

    - The contact resistance b etw een the individual

    screen conductors.

    - The screen coverage, i.e. the physical area of the

    cable covered by the screen - often stated as a

    percentage value.

    - Screen type, i.e. braided or tw isted pattern.

    Alum inium -clad w ith

    copper w ire.

    Tw isted copper w ire or

    arm oured steel w ire cable.

    Single-layer braided copperw ire w ith varying percentage

    screen coverage.

    D ouble-layer braided

    copper w ire.

    Tw in layer of braided copper w ire

    w ith a m agnetic, screened/

    arm oured interm ed iate layer.

    C able that runs in copper

    tube or steel tube.

    Lead cable w ith 1.1 m m w all

    thickness w ith full coverage.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    39/173

    VLT5000 Series

    39M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    Earthing of braided screened/armoured control

    cables

    G enerally speaking, control cables m ust be braided

    screened/arm oured and the screen m ust be

    connected by m eans of a cable clam p at both ends

    to the m etal cabinet of the unit.

    The draw ing below ind icates how correct earthing is

    carried out and w hat to be done if in doub t.

    Correct earthing

    C ontrol cables and cables for serial com m unication

    m ust be fitted w ith cable clam ps at both ends to

    ensure the best possible electrical contact.

    Wrong earthing

    D o not use tw isted cable ends (pigtails), since these

    increase the screen im pedance at high frequencies.

    Protection with respect to earth potential

    between PLC and VLTIf the earth potential betw een the V LT freq uency

    converter and the PLC (etc.) is different, electric noise

    m ay occur that w ill disturb the w hole system . This

    problem can be solved by fitting an eq ualising cable,

    to be placed next to the control cable. M inim um cable

    cross-section: 16 m m 2.

    For 50/60 Hz earth loops

    If very long control cables are used, 50/60 H z earth

    loops m ay occur. This prob lem can be solved by

    connecting one end of the screen to earth via a

    100nF cap acitor (keep ing leads short).

    Cables for serial communication

    Low -frequency noise currents betw een tw o VLT

    frequency converters can be elim inated by connect-

    ing one end of the screen to term inal 61. This term inal

    is connected to earth via an internal R C link. It is

    recom m ended to use tw isted-pair cables to reduce

    the differential m ode interference betw een theconductors.

    Electricalinstallation

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    40/173

    VLT5000 Series

    M G .50.A8.02 - VLT is a registered D anfoss tradem ark40

    Electricalinstallation Tightening-up torques and screw sizes

    The table show s the torque required w hen fitting

    term inals to the V LT frequency converter. For VLT

    5001-5027 200-240 V, VLT 5001-5052 380-500 V

    the cables m ust be fastened w ith screw s. For VLT

    5032 - 5052 200-240 V, VLT 5060-5500 380-500 V

    the cables m ust be fastened w ith bolts.

    These figures apply to the follow ing term inals:

    Mains terminals

    Motor terminals

    Earth terminal

    Brake resistor

    terminals

    Loadsharing

    Nos 91, 92, 93

    L1, L2,

    L3

    Nos 96, 97, 98

    U, V, W

    No 95

    81, 82

    88, 89

    VLT type Tightening-up Screw

    3 x 200-240 V torque size

    VLT 5001-5006 0.5 - 0.6 N m M 3

    VLT 5008-5011 1.8 N m M 4

    VLT 5016-5022 3.0 N m M 5

    VLT 5027 4.0 N m M 6

    VLT type Tightening-up Screw

    3 x 200-240 V torque size

    VLT 5032-5052 1) 11.3 N m M 8

    VLT type Tightening-up Screw

    3 x 380-500 V torque size

    VLT 5001-5011 0.5 - 0.6 N m M 3

    VLT 5016-5027 1.8 N m M 4

    VLT 5032-5042 3.0 N m M 5

    VLT 5052 4.0 N m M 6

    VLT type Tightening-up B olt3 x 380-500 V torque size

    VLT 5060-5100 1) 11.3 N m M 8

    VLT 5125-5250 11.3 N m M 8

    VLT 5300-5500 2) 42 N m M 12

    1) For the brake term inals, the tightening-up torque

    is 3.0 N m and the bolt size M 6.2) For the brake term inals, the tightening-up torque

    is 42 N m and the bolt size M 8.

    Connection of mains

    C onnect the three m ains phases to term inals

    L1, L2, L3.

    High voltage test

    A high voltage test can b e carried out by short-

    circuiting term inals U , V, W , L1, L2and L3and ener-

    gizing by m ax. 2.15 kV D C for one second betw een

    this short-circuit and the chassis.

    NB!

    The R FI sw itch m ust be closed (position O N )

    w hen high voltage tests are carried out (seepages 33-36, R FI sw itch).

    The m ains and m otor connection m ust be interrupted

    in the case of high voltage tests of the total installa-

    tion if the leakage currents are too high.

    Safety earthing:

    NB!

    The VLT frequency converter has a high

    leakage current and m ust be earthed

    ap propriately for safety reasons. U se earth term inal

    (see d raw ing pages 30-32), w hich enables

    reinforced earthing.

    Apply national safety regulations.

    Motor thermal protection

    The electronic therm al relay in U L-approved VLT

    frequency converters has received the U L-approval

    for single m otor protection w hen param eter 128 has

    been set forETR Tripand param eter 105 has been

    program m ed to the rated m otor current (see m otor

    nam eplate).

    Extra protection (RCD)

    ELC B relays, m ultiple protective earthing or earthing

    can be used as extra protection, provided that local

    safety regulations are com plied w ith.

    In the case of an earth fault, a D C content m ay deve-

    lop in the faulty current.

    If ELC B relays are used, local regulations m ust be

    observed. R elays m ust be suitable for protection of 3-

    phase equipm ent w ith a bridge rectifier and for a brief

    discharge on pow er-up.

    See also the section S pecial C onditions in the D esign

    G uide.

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    41/173

    VLT5000 Series

    41M G .50.A8.02 - VLT is a registered D anfoss tradem ark

    RFI switch

    M ains supply isolated from earth:

    If the VLT frequency converter is supplied from an

    isolated m ains source (IT m ains), the R FI sw itch can

    be turned off (O FF). In O FF position, the internal R FI

    capacities (filter capacitors) betw een the chassis and

    the interm ediate circuit are cut off to avoid dam age to

    the interm ediate circuit and to red uce the earth

    capacity (according to IEC 1800-3).

    See position of R FI sw itch on pages 33-36.

    NB!

    The R FI sw itch is not to be operated w ith

    m ains connected to the unit. C heck that the

    m ains supply has been disconnected before

    operating the R FI sw itch.

    NB!

    O pen R FI sw itch is only allow ed at factory set

    sw itching freq uencies.

    NB!

    The R FI sw itch disconnects the capacitors

    galvanically; how ever, transients higher than

    approx. 1,000 V w ill be bypassed by a spark gap.

    M ains supply connected to earth:

    The R FI sw itch m ust be in O N position in order for the

    frequency converter to com ply w ith the E M C -

    standard.

    Installation of motor cables

    NB!

    If an unscreened cable is used, som e EM C

    requirem ents are not com plied w ith, see the

    D esign G uide chapter 11: Special cond itions.

    If the E M C specifications regarding em ission are to be

    com plied w ith, the m otor cab le m ust be screened,

    unless otherw ise stated for the R FI filter in question. It

    is im portant to keep the m otor cable as short as

    possible so as to reduce the noise level and leakage

    currents to a m inim um .

    The m otor cable screen m ust be connected to the

    m etal cabinet of the frequency converter and to the

    m etal cabinet of the m otor. The screen connectionsare to be m ade w ith the biggest possible surface

    (cable clam p). This is enabled by different installation

    devices in the different VLT frequency converters.

    M ounting w ith tw isted screen ends (pigtails) is to be

    avoided, since these spoil the screening effect at

    higher freq uencies.

    If it is necessary to break the screen to install a m otor

    isolator or m otor contactor, the screen m ust be

    continued at the low est possible H F im pedance.

    The frequency converter has been tested w ith a given

    length of cable and a given cross-section of that

    cable. If the cross-section is increased, the cable

    capacitance - and thus the leakage current -

    increases, and the cable length m ust be reduced

    correspondingly.

    Connection of motor

    All types of 3-phased asynchronous standard m otors

    can be used w ith the V LT 5000 Series.

    N orm ally, sm all m otors are star-connected

    (200/400 V,/).Large m otors are delta-connected (400/690 V,/).

    Electrica

    linstallation

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    42/173

  • 8/10/2019 Bien Tan Danfoss VLT 5000 Serie

    43/173

    VLT5000 Series

    43M