boiler prot.ppt
DESCRIPTION
boiler protectionsTRANSCRIPT
![Page 1: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/1.jpg)
![Page 2: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/2.jpg)
TYPES OF PROTECTIONS
-PROTECTIONS CAUSING UNIT
SHUTDOWN
-PROTECTIONS CAUSING LOAD
REDUCTION
-PROTECTIONS CAUSING ANNUNCIATION
ONLY
![Page 3: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/3.jpg)
REASONS FOR PROTECTIONS
-Deviation from normal condition,
which can not be easily
controlled automatically
-Hence, it calls for human
intervention.
-Can cause loss of generation,
property and / or life
![Page 4: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/4.jpg)
Protections causing unit shutdown
-Failure of all BFPs.
-Boiler shutdown due to both ID fan tripping, both FD fans tripping, loss of all fuel etc.
-Reheater protection to ensure continuous steam flow through reheater.
![Page 5: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/5.jpg)
Protections causing load reduction
-One ID Fan tripping
-One FD fan tripping
-One PA fan tripping( tripping can be avoided only when air gates close quickly.)
-Mills or feeders tripping.
![Page 6: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/6.jpg)
Furnace safeguard supervisory system
-This system takes care of interlocks required for starting, supervision and safe shutdown of the equipments.
Basically, FSSS prevents any firing till safe purging of boiler is complete.
It prevents ignition of fuel firing instruments till certain interlocks are satisfied.
It effects master fuel trip in certain conditions.
![Page 7: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/7.jpg)
Conditions for purging(FSSS)
1. No Boiler trip conditions2. HOTV and LOTV closed.3. HONVs and LONVs closed.4. All PA fans off.5. All feeders off.6. All Hot air gates closed.7. All aux.air dampers modulating.8. Air flow >30% and <40%9.All scanners no flame..
![Page 8: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/8.jpg)
ID fan start permissives
1. IGV in minimum position.
2. I/L and O/L gates closed.
3. Bearing temperatures not high.
4. One SAH running with its i/l and o/l gates open.
5. One of the two VFD channels ready.
6. Lube oil supply healthy.
-Once one of the two channels is taken i/s, i/l and o/l gates are opened in auto. Then the other channel can be taken i/s.
![Page 9: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/9.jpg)
ID fan tripping
ID fan can trip on protections like bearing temp. very high, fan/motor vibration very high or fault from VFD channels( only the faulty channel trips).
-when ID fan-A trips and ID fan-B is not i/s-: 1.I/D fan-B i/l and o/l gates open. 2.Auto control system is disconnected. 3.Both IGVs open to wide open position. 4.Working FD fans trip. 5. Boiler trips through FSSS. 6.ID Fan A i/l and o/l gates remain wide open.
![Page 10: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/10.jpg)
-When both ID fans are in service and one of them trips.
1. Corresponding FD fan trips. 2. Runback operates and load is reduced to 60
% of full load. 3.IGV and VFD get disconnected from auto
control loop and come to minimum position. 4.I/L and O/L gates closed.
![Page 11: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/11.jpg)
FD fan start permissives
Blade pitch in minimum position.O/L damper closed.Bearing temperatures not high.One ID fan i/s.Lube oil system healthy.
-For the second FD fan to start, two ID fans should be i/s; other conditions will remain as above.
![Page 12: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/12.jpg)
FD fan trippings--When one FD fan is in service-
1.Dampers of both the fans open to wide open position.
2.Blade pitch of both the fans go to maximum positions.
3. Emergency scanner air damper opens.
4. Boiler trips.
![Page 13: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/13.jpg)
When both FD fans are in service and one of them trips.
Apart from the conditions like high bearing temp., high winding temp., high vibration etc., one FD fan will trip also when one ID fan trips.
1. Blade pitch control of running fan comes to manual.
2. Blade pitch of tripped fan comes to minimum and o/l damper gets closed
3. Runback operates and load is reduced to 60 % of BMCR.
![Page 14: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/14.jpg)
One PA Fan trips and other is in service.
REASONS:-
-Fan/motor bearing temp. is high.
- Winding temp. very high.
-Lube oil flow low.
-Fan vibration very high.
![Page 15: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/15.jpg)
Effect of one PA Fan tripping
- Runback will operate It is very difficult to save the unit because- There is sudden drop in PA header
pressure. (Alarm at 625 mm which starts top mills’ tripping).
At 500mm, mills trip on PA header pressure very low(2/3 logic).
Time Delay is very less (Approx. 6 sec) Air gates closing and PA fan o/l gate
closing takes more than 10 sec.
![Page 16: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/16.jpg)
RUNBACK OPERATION1. Top mills will trip with 2sec delay till
4 mills from bottom remain.2.Turbine comes in pressure control
mode.3.Fuel master will take command from
unit capability.4. Load will start reducing after 30-45
sec.5. Fuel will not reduce below 150 TPH.
![Page 17: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/17.jpg)
Other effects-
PA header pressure will increase due to mill trippings.
Furnace pressure fluctuation. Drum level (+/-100mm)
In case of BFP tripping our aim should be to reduce steam flow. Pressure set point should be on the higher side. Oil gun should not be taken i/s.
![Page 18: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/18.jpg)
MASTER FUEL TRIP
-There are 3 channels for MFT. Boiler trips on 2/3 logic.
1. All ID fans off.
2. All FD fans off.
3. Flame failure
4. Loss of all fuel
5. Less than Fireball and loss of 110 V AC.
6. Waterwall circulation incorrect
7. Reheater protection.
8. Furnace pressure very high>150mm
9. Furnace pressure very low <-175mm
![Page 19: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/19.jpg)
10. Drum level very high>250mm11. Drum level very low <-375mm12. Loss of FSSS 220V AC.13.Low Air flow (<30 %).14. All BFPs off.15. Both SAH off.16.2/3 MFT both networks fail.17.2/3MFT DPU outputs frozen
![Page 20: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/20.jpg)
Water wall circulation incorrect-: 1. All 3 BCW on AND each
dP<10psi(2/3) 2. Any two BCW pps. On AND both
dP <10 psi 3.Any one BCW on AND its dP<10
psi 4.Boiler on AND all BCW pps off
(TD=5s)
![Page 21: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/21.jpg)
Loss of all fuel trip
Loss of all fuel trip arming AND All feeders off AND[LOTV not open OR elevation AB all LONVs closed ]
AND [HOTV not open OR {In all HO elevations all HONVs
closed } Loss of all fuel trip arming:- Any elev. any nozzle valve not closed.
![Page 22: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/22.jpg)
Unit Flame failure trip
Unit flame failure trip arming AND all elevation A-K voted no flame.
Unit flame failure trip arming:- Any feeder proven for 2s.
![Page 23: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/23.jpg)
Ee
No flame voting (For elev. A)1.Feeder A not proven for more than 2s.
2. Elevation AA ¾ FB scanner no flame AND
[{Elev. AB started AND loss of 110 V AC (TD=2s)} OR {Elev. AB 2/4 nozzle v/v not proven AND elev. AB ¾ FB scanner no flame}]
![Page 24: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/24.jpg)
Loss of reheat protection:
1.Reheater protection enabled ANDGenerator CB opened AND[Both HPBP closed(<2%) OR { Either
LPBP stop v/v OR LPBP CV in both LPBP lines closed}]
2. Reheater Protection enabled AND [{Turbine HP v/vs and HPBP closed}OR{ Turbine IP v/vs and LPBP closed}]
![Page 25: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/25.jpg)
Reheater Protection enabling
Drum pressure > 8Ksc AND {Any feeder ON OR Boiler firing ON}
AND{ Any LPBP stop v/v open AND
corresponding LPBP CV>2% open}AND [Any HPBP v/v >2% open] AND No MFT.
![Page 26: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/26.jpg)
Turbine HP v/v and HPBP closed
[Either HP stop v/v OR HP control v/v in both HP lines closed]
ANDBoth HPBP closed(<2%)Similarly for IP v/v & LPBP closed[Either IP stop v/v OR IP control v/v in both IP lines closed]
AND[Either LPBP stop v/v OR LPBP control
closed(<2%) in both LPBP lines closed.]
![Page 27: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/27.jpg)
BOILER TRIPWhen the boiler trips the following events takes place
Boiler trip red lamp comes on. MFT A & B trip lamp comes on and reset lamp goes off. Cause of trip memory can not be reset till the furnace purge is
completed. F D Fans Control is transferred to manual. I D fans vane position is transferred to manual. Pulverizers are tripped. Coal feeders are tripped. P A Fans are tripped. Cold air dampers opens 100 %. HFO trip valve closes. All HFO Nozzle valves closes. Upper and Lower Fuel air damper opens. Auxiliary air damper opens and control is transferred to manual. Loss of all fuel trip protection disarms. S/H and R/H spray block valves S-82 & R-31 closes and can not be
opened unless furnace purge is completed. Turbine Trips
![Page 28: Boiler Prot.ppt](https://reader033.vdocuments.net/reader033/viewer/2022042522/55cf997e550346d0339da880/html5/thumbnails/28.jpg)