    BOILER & STEAM UTILITYSYSTEM

  • 7/30/2019 Boiler specification with mountings

    2/9

    Boiler Construction

    As per IBR regulations 1950.

    Heating surface area- 148 m2

    Water holding capacity- 12 m2

    Overall length- 5.5 m

    Shell diameter- 2.4 m

    Corrugated furnace diameter- 1.12 m

  • 7/30/2019 Boiler specification with mountings

    3/9

    Material of construction

    Shell & furnace plates- SA 515/516 Gr 70 CS

    pressure vessel plates for medium & high

    temperature service.

    Plain & stay tubes- confirming to BS 3059

    Valve body _ carbon steel WCB with flanged

    end connections.

    Fusible plug- Alloy comprising of Tin, Lead &

    antimony

  • 7/30/2019 Boiler specification with mountings

    4/9

    Boiler mountings

    Water gauge glasses mountings- consists ofsteam side cock & water side cock, levelglass, protector & drain lines.

    Pressure gauge- Bourdon pressure gauge10 dia. dial with a range: 0-25 Kg/cm2

    Safety valves 40 x 80: spring loaded fulllift safety relief valve- 2 Nos.

    Feed check valve- plate type mounted onfeed pump discharge

    Main steam stop valve- Globe typemounted on boiler drum

  • 7/30/2019 Boiler specification with mountings

    5/9

    Mountings Continued .

    Blow down valveParallel sliding type

    mounted at bottom line from boiler

    Air vent valve- Globe type mounted on top ofboiler drum

    Fusible plug- 2 Nos. of small welded fitting

    filled with low melting temperature alloy, onemounted on reverting chamber another at end

    plate on top of smoke tubes at 2nd 3rd passjunction chamber.

    Man hole- mounted on top of shell

    Mud hole- at bottom of shell.

  • 7/30/2019 Boiler specification with mountings

    6/9

    Accessories continued . Oil preheating unit- Dual operated

    with electrical & steam oil pre_heaterwith shell & tube type heat exchanger

    Oil pre_filter- Bucket type filter witha standby

    Burner assembly- pressure jet typeburner with auto regulatingarrangement to meet loadrequirement.

    Modulating unit- Step less modulatingunit with a turn down ratio of 4:1regulating the air fuel requirement ofvarious load requirement

  • 7/30/2019 Boiler specification with mountings

    7/9

    Instrumentation & safety cut

    offs

    Extra low water level in drumcut offby Mobrey unit

    High pressure switch- Sensing the steampressure inside the boiler and trips thefiring at the set pressure.

    Flame failure sensor- a photo cell unitmounted on the burner assembly, cut offthe fuel supply in absence of no flame

    High flu gas temperature- cut off

    Low oil temperature- cut off Flue gas outlet damper closed- cut off

    by limit switch

  • 7/30/2019 Boiler specification with mountings

    8/9

    Fuel oil Specification

    Furnace oil confirming to IS 1593-1988 grade MV-2

    Calorific value9600 Kcal/ Kg (approx)

    Kinematic viscosity @ 15o C -125180 cSt.

    Kinematic viscosity @ 100o C

  • 7/30/2019 Boiler specification with mountings

    9/9

    Water Quality RequirementAs per IS 10392-1982Feed water requirement:-

    Total hardness 10 mg/l max

    pH value- 8.5 to 9.5

    Dissolved oxygen- .1 mg/l max.

    Boiler water requirement:- Total hardness Not detectable

    pH value- 11.0 to 12.0

    Total alkalinity- 700 mg/l max.

    Caustic alkalinity- 350 mg/l max. Residual sodium sulphite 3050 mg/l

    Phosphates as (PO4)20-40 mg/l