borri rcb - unitek rcb.e.pdf · 2010. 8. 14. · borri s.p.a. head offi ce & factory via 8...
TRANSCRIPT
Robust and reliable layout for
industrial applications
Standard confi gurations for cost
effective, short lead time solutions
Input isolation transformer
protected by MCCB
Microprocessor control
Full set of battery charging
methods
Expertise in battery selection,
dimensioning and testing
Extensive range of options and
customised solutions
Easy accessibility and maintenance
Block diode for parallel operation
Built-in battery breaker
Battery on racks or inside cabinets
Battery voltage temperature
compensation
Dedicated buttons and selectors for
battery charge functions
Earth fault monitoring and alarm
Fan monitoring and alarm
Remote relay alarms
Serial ports, RS232 and RS485
Modbus
Control logic redundant supply
Additional matching cabinets
for batteries and distribution and
dropping cells
Power Stations and Substations
Oil & Gas and Petrochemical
Plants
Water Treatment Plants
Manufacturing Plants
Transportation
The RCB.e is a robust and reliable industrial rectifi er-battery charger, designed to supply critical dc loads and to charge any type of battery (Ni-Cd, vented and sealed lead-acid).
Development of the system took into account the requirements of our customers and the experience acquired by Borri over more than 75 years of activity in the area of power conversion technology.
The RCB.e relies on standard DC system confi gurations to provide cost-effective, short lead time solutions. The RCB.e system is thyristor-controlled rectifi er and it is based on a fully digital
control to ensure the required fl exibility.The high level of standardisation makes the product particularly compact, even though it is designed for industrial applications.
Customer’s requirements are fully met with the availability of a wide set of basic options, such as dropping diodes, breakers, extensive battery, communication and alarm functions. Special customer’s requirements can be complied with on demand.
The system is provided with a digital control panel and mimic, displaying the operational status of the equipment (signals, alarms, meters, history events).
LCD Multifunctional Mimic Panel
Main Options ApplicationsMain Features
Product SnapshotTechnology: Isolated Thyristor-controlled
bridge
Current Rating: 50-100-150 Amps
Voltage: 400Vac 3ph Input,24-48-110-220Vdc Output
BORRI RCB.eCompact Rectifi er Battery Charger
A compact industrial DC system specifi cally designed for Power Stations and Substations
RCB.e Compact Rectifi er Battery Charger Technical characteristics
One Line Diagram
BORRI S.p.A.Head Offi ce & FactoryVia 8 Marzo, 252012 Bibbiena (Arezzo)Tel. +39-0575-5351Fax +39-0575-561438www.borri.it
Printed in Italy - 2009 - Borri s.p.a.rev. 2.04.09The information contained in this publication is subject to variations without notice.
Rating 50 A 100 A 150 A
Input
Nominal voltage 400 Vac three phase ±10%
Frequency 50÷60 Hz ± 5 Hz
Output
Nominal voltage 24-48-110-220 Vdc
Operating Voltages Floating 2,27 (VRLA). 2.2+2.3 (VLA), 1.4+1.5 (Ni-Cd)V/cell adjustableBoost 2.4+2.45 (VLA), 1.5+1.65 (Ni-Cd)V/cell adjustable
Equalizing upto 2.35 (VRLA), upto 2.7 (VLA), upto 1.7 (Ni-Cd) V/cell adjustable
Static voltage regulation ±1%
Voltage ripple <=1%
Overload capacity <120% for 20 min; <150% for 2 min; >150% for 20 sec.
Charging characteristic IU (according to DIN41773), I1I2U, U1U2I
System and Environmental
Isolation Input/output
Dimensions WxHxD (mm) 550x1300x550
Weight (kg) 150 180 240
Cooling Forced ventilation
Colour RAL7035
Protection degree (IEC60529) IP21 (Option IP31)
Operating temperature -10°C – +40°C
Storage temperature -20°C – +70°C
Altitude <2000 m (derating according to EN62040-3)
Audible noise at 1 meter (dBA) <65
Options External battery cabinets; external cabinet for distribution and dropping cells; built-in battery breaker; battery thermal probe; block diode for parallel; earth
fault alarm; fan monitoring and alarm; control logic redundant supply
User Interface
Front panel LCD display with 4x LED’s and keyboard
Optional RS232 and/or RS485 Modbus serial port, 1 or 2 relay card(s)
Standards and Certifi cation
Marking CE
Safety IEC EN 50178, IEC EN62040-1
EMC IEC EN 61000-6-2, IEC EN 61000-6-4
Test and Performance IEC EN 62040-3
Quality ISO9001 :2000
TAB1
TATOT
V
Option
V
On front panel display
On front panel display
A
V A
On front panel display
FRONT PANEL:
16 Alarms+4 Status on LCD display
REMOTE CONNECTION
REMOTE ALARMS
UP to 12 remote alarms
MODBUS ADAPTER
9
6
5
1
Option
D1F1...3 R64RECTIFIER
Option
RICB
BCB
ROCB
X02X01
X03
T1
RS232
FLOW DIAGRAM
10 alarms on leds (Settable)
Option
Option
Option
L1,L2,L3,N +R,-R
+B,-B