bss fire protection systemsinsulation – pyrosit® ng fire protection foam 187 insulation –...
TRANSCRIPT
-
BSS | Catalogue 2012/2013
Fire protection systems
THINK CONNECTED.
-
2 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Welcome to Customer Service
Service telephone: +49 (0)2373 89-1500
Telefax for enquiries: +49 (0)2373 89-7777
Telefax for orders: +49 (0)2373 89-7755
E-mail: [email protected]
Internet: www.obo.de
Use the direct line to OBO Customer Service! On the Service Hotline +49 (0)2373 89-1500, we are availableevery day from 7.30 a.m. to 5.00 p.m. for any questions about the OBO product range for electrical installa-tions. The newly structured OBO Customer Services can offer you the full works:• Competent contacts from your region• All the information on the OBO product range• Knowledgeable advice on special application topics• Quick, direct access to all the technical data of the OBO products – we also want to provide the best in
customer relations!
-
Gen
eral
pla
nnin
gai
ds
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
3OBOBSS
Planning aid 5
Insulation – PYROMIX® mortar insulation 177
Insulation – PYROPLATE® Fibre soft insulation 183
Insulation – PYROSIT® NG fire protection foam 187
Insulation – PYROBAG® cushion insulation 191
Insulation – PYROPLUG® foam series 195
Insulation – PYROCOMB® pipe sleeve 201
Components for small insulation and individual cable penetration acc. toMLAR
205
Escape route installations - false ceiling mounting 209
Fire protection ducts 219
Cable bandages 245
Function maintenance – cable-specific support structures 249
Function maintenance – standard support structures 273
Function maintenance – vertical ladders 285
Function maintenance – individual routing, pipes and metal duct 291
Function maintenance – junction boxes 307
Anchorings 311
Directories 317
Contents
-
Gen
eral
pla
nnin
gai
ds
4 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
OBO BSS seminars: First-handknowledgeWith a comprehensive programmeof training courses and seminarson the subject of fire protectionsystems, OBO is able to supportits customers with specialist knowl-edge from a single source. Along-side the basic theoretical princi-ples, the programme also dealswith practical implementation in ev-eryday applications. Special calcu-lation and application examplesround off the comprehensive pro-gramme of knowledge transfer.
Invitations to tender, product in-formation and datasheetsWe can make life easier for you,with our comprehensive selectionof materials designed for practicalapplications, which provide youwith effective support with theplanning and calculation of aproject. These include:• Invitations to tender• Product information• Information sheets• DatasheetsThese documents are continuallyupdated and can be downloadedat no charge at any time from theInternet download area at www-obode.
Invitations to tender on the Inter-net at www.ausschreiben.deMore than 10,000 entries from theKTS, BSS, TBS, LFS, EGS andUFS ranges can be called up freeof charge. Regular updates andextensions mean that you alwayshave a comprehensive overview ofthe OBO products. All the currentfile formats – PDF, DOC, GAEB,HTML, TEXT, XML, ÖNORM – areavailable.www.ausschreiben.de
-
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
5OBOBSS
General planning aid 5
Insulation – PYROMIX® mortar insulation 19
Insulation – PYROPLATE® Fibre soft insulation 23
Insulation – PYROSIT® NG fire protection foam 27
Insulation – PYROBAG® cushion insulation 33
Insulation – PYROPLUG® foam series 39
Insulation – PYROCOMB® pipe sleeve 57
Components for small insulation and individual cable penetration acc. toMLAR
63
Escape route installations – false ceiling mounting 69
Fire protection ducts 89
Cable bandages 99
Function maintenance – cable-specific support structures 105
Function maintenance – standard support structures 123
Function maintenance – vertical ladders 141
Function maintenance – individual routing, pipes and metal duct 151
Function maintenance – junction boxes 165
Anchorings 169
Planning aid
-
Gen
eral
pla
nnin
gai
ds
6 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Compact fire protection knowledge. The new fire protection guide
Nowadays, fire protection presentsmany planners and installation en-gineers of building equipment withalmost insurmountable obstacles.Installations run like networksthrough complex building struc-tures.
The art of the planner is to har-monise the various networks, suchas supply and disposal, heating,ventilation and air-conditioning,with the electrical installation. Thatin itself is difficult. In addition, thethought of building safety hasbeen at the forefront for severalyears now. The sensitivity towardsfire protection in buildings is grow-ing.
As soon as the first step towardsfire protection planning has beencompleted, the appropriate sys-tems and components are in-stalled. Here, too, installation engi-neers are confronted with require-ments which cannot be implement-ed without further work.
-
Gen
eral
pla
nnin
gai
ds
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
7OBOBSS
After erection, the fire protectionbuilding equipment must be readyfor acceptance. All the installationsmust be executed properly and theappropriate fire protection proofsmust be available.
In the fire protection guide, wewish to explain the interconnec-tions of fire protection in technicalbuilding equipment. Perhaps you will find some newaspects which can help you in theplanning or implementation of fireprotection systems.
Request your copy from our Cus-tomer Service department now.
-
Gen
eral
pla
nnin
gai
ds
8 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Practical: the structure of the fire protection guide
Chapter 1: General introductionHere, we can give you importantbasic principles of constructive fireprotection:• Construction law• What is fire protection?• Fire protection concepts• Building types• What happens during a fire?• Construction law protection
aims
Chapter 2: Maintenance of thefire sections - First protectionaim• Components closing rooms,
fire walls• Requirements for cable pene-
trations• Proofs of application• Tests• Insulation systems, construc-
tion types• Applications and special appli-
cations• Building in old buildings
Chapter 3: Protection of escaperoutes – Second protection aim• What is an emergency and es-
cape route?• Problem: Fire loads• Safe routing options• Proofs of application
-
Gen
eral
pla
nnin
gai
ds
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
9OBOBSS
Chapter 4: Function maintenancefor electrical systems – Third pro-tection aim• What is electrical function
maintenance?• Tasks of function maintenance• Proofs of application• Installation types• Special features of vertical
routing• Function maintenance with fire
protection ducts• Limits of function maintenance• Fastenings
Chapter 5: Additional protectionaims• Protection of property and the
environment• Industrial fire protection
Chapter 6: Fire protection fromOBO Bettermann• Insulation systems• Escape route installation sys-
tems• Function maintenance systems• Industrial fire protection sys-
tems• Engineering and support
-
Gen
eral
pla
nnin
gai
ds
10 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
The new generation is here: OBO Construct Professional and OBO Con-struct Web.
We have reinvented our Constructplanning software: we have bun-dled all the electronic planningaids under the name OBO Con-struct.
Two versionsThere are now two versions ofOBO Construct: Construct Weband Construct Professional. Theyare now aligned to the different re-quirements of our customers andoffer the following scope of ser-vice:
OBO Construct ProfessionalThe completely new tool for pro-fessional users. The new multilin-gual AutoCAD plug-in is availablein various languages and offers awealth of benefits:• Redesigned user dialogues• Simplified operation• Improved component depiction• Individual adjustment of object
display• Completely new system (runs
on 64-bit systems)• Mass determination with addi-
tional materials• Output of the mass determina-
tion in various formats (Excel,PDF, Text)
• Simple updates• Importable and editable invita-
tions to tender
OBO Construct WebThe Internet version for rapid helpnow no longer needs a CAD sys-tem and offers the following bene-fits:• Simple operation• For quick and easy application• Platform-independent• No installation required• Access possible from any-
where• Option of saving project data• Plans can be printed out as
PDFs• Exact mass determination in
an Excel file• Additional material bookable
-
Gen
eral
pla
nnin
gai
ds
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
11OBOBSS
OBO Construct KTS: Project planning, drawing, generation
Find out nowConvince yourself about the newOBO Construct: a new supportand training concept makes it easi-er than ever for you to take yourfirst steps. You can find additionalinformation on the Internet or fromour Customer Service.
AutoCAD is a registered trademarkof Autodesk Incorporation, USA.
-
Gen
eral
pla
nnin
gai
ds
12 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Selection aid, insulation in solid components
This overview is intended to helpyou choose the suitable insulationsystem for the installations madein solid walls and ceilings. In thecase of ceiling insulation, it shouldbe noted that some systems must
be secured on the underside ofthe ceiling against falling out. Inaddition, people must be prevent-ed from walking on the insulationmeasures in ceilings.
Cable Cable bundle Hollow shaft conductor Kupa pipes
PYROMIX Yes Yes Yes Yes
PYROPLATE Fibre Yes Yes - -
PYROSIT NG Yes Yes - Yes
PYROBAG Yes Yes - -
PYROPLUG blocks andplugs
Yes Yes - Yes
PYROPLUG drill crownand small insulation
Yes - - -
PYROCOMB Yes - - Yes
Insulation layer creator Yes - - -
-
Gen
eral
pla
nnin
gai
ds
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
13OBOBSS
Selection aid, insulation in solid components
Stapa pipes Kupa pipe bundle Cable support systems Plastic pipes Metal pipes Combination
Yes - Yes Yes Yes Yes
- - Yes Yes Yes Yes
- - Yes Yes Yes Yes
- - Yes - - -
- - Yes Yes Yes Yes
- - - - - -
- Yes - Yes - -
- - - - - -
-
Gen
eral
pla
nnin
gai
ds
14 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Selection aid, insulation in light-duty partitions
This overview is intended to helpyou choose the suitable insulationsystem for the installations madein light-duty partitions with mois-ture resistance. The subconstruc-tion of the light-duty partitions isusually made of metal stands andbolts, which are surrounded on
each side by fire protection plates,fastened in two layers. Light-dutypartitions are not supporting com-ponents, meaning that fire protec-tion fastening, e.g. for functionmaintenance, cannot be imple-mented.
Cable Cable bundle Hollow shaft conductor Kupa pipes
PYROPLATE Fibre Yes Yes - -
PYROSIT NG Yes Yes - Yes
PYROBAG Yes Yes - -
PYROPLUG blocks andplugs
Yes Yes - Yes
PYROPLUG drill crownand small insulation
Yes - - -
PYROCOMB Yes - - Yes
Insulation layer creator Yes - - -
-
Gen
eral
pla
nnin
gai
ds
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
15OBOBSS
Selection aid, insulation in light-duty partitions
Stapa pipes Kupa pipe bundle Cable support systems Plastic pipes Metal pipes Combination
- - Yes Yes Yes Yes
- - Yes Yes Yes Yes
- - Yes - - -
- - Yes Yes Yes Yes
- - - - - -
- Yes - Yes - -
- - - - - -
-
Gen
eral
pla
nnin
gai
ds
16 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Selection aid, insulation, special applications
This overview is intended to helpyou find the suitable insulation sys-tem for the special electrical instal-lation applications in the field of
cable routing ducts, underfloorsystems and case lining pipes.
Underfloor ductsscreed-covered
Underfloor ductsscreed-flush
Metal ducts Plastic ducts PVC lining pipes
PYROSIT NG Yes Yes - - Yes
PYROBAG - - Yes Yes Yes
PYROPLUG blocks Yes Yes - - -
-
Gen
eral
pla
nnin
gai
ds
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
17OBOBSS
Special application for refurbishment of buildings (building in existingbuildings)
The following applies to all oldbuilding ceilings and wall construc-tions made of special components(sandwich elements): mounting ofinsulation systems is approvedwhen this kind of application is in-cluded in the approval. In conjunc-tion with the construction authori-ties, insulation systems can beused, which, according to the ap-proval, are approved for a similarapplication, e.g. within a layer ofnon-combustible materials.
Important note: Before mounting,always obtain the approval fromthe client, e.g. construction su-pervision or fire brigade. Get intouch with us, we'd be glad tohelp you!
Wooden beam ceiling
Wooden beam ceiling with fire protection ceil-ing
Ribbed ceiling
Cavity chamber ceiling
Cap cover
Beamed ceiling
-
18 OBO BSS
-
19OBOBSS
Planning aid, PYROMIX® mortar insulation
System description, PYROMIX® mortar insulation 20
Installation principle, PYROMIX® mortar insulation 21
-
Pla
nnin
g a
id, P
YR
OM
IX®
mor
tar
insu
latio
n
20 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROMIX® mortar insulation
Stir the mortar with water toachieve the desired consistency
Apply mortar to the opening, uselining as necessary
Use approved section insulationfor metal pipes
Section insulation should also beapplied to steel electrical installa-tion pipes
Mount pipe sleeves for com-bustible pipes on both sides of thewall
Combination insulation for variousstructures with labelling
PYROMIX® is a special mortar,free of mineral fibres, for the cre-ation of cable and combinationinsulation. Depending on theamount of water added, the fin-ished compound can be appliedto the openings by hand, withpumps or with presses. The highlevel of substrate adhesion makelining unnecessary for small in-sulation sizes. A porous consis-tency makes retroinstallationeasy.
System benefits• Combination of multiple installations possible• Many approved section insulations, even Armaflex or Foamglas• Free of mineral fibres• Hollow shaft conductors permitted• Good substrate adhesion• Can even be used with small component thicknesses• Required consistency can be achieved by adding water• Easy retroinstallation
-
Pla
nnin
g a
id, P
YR
OM
IX®
mor
tar
insu
latio
n
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
21OBOBSS
Installation principle, PYROMIX® mortar insulation
Mineral special mortar, hard insulation
Fire resistance class S90
Proof of application General construction approvalof DIBt, Berlin
Approval number Z-19.15-2046
Testing standard DIN 4102 Part 9
Insulation dimensions in cm
Component Solid wall Solid ceiling
Min. component strength 10 15
Min. insulation thickness 15 15
Opening width, max. 100 (200) 100
Opening height, max. 200 (100) -
Max. length - Unlimited
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
22 OBO BSS
-
23OBOBSS
Planning aid, PYROPLATE® Fibre soft insulation
System description, PYROPLATE® Fibre soft insulation 24
Installation principle, soft insulation, PYROPLATE® Fibre 25
-
Pla
nnin
g a
id, P
YR
OPLA
TE®
Fib
re s
oft
insu
latio
n
24 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROPLATE® Fibre soft insulation
Moisten the component layer andapply the coating to the cut edgesfor adhesion
Use approved section insulationfor metal pipes
Apply the final coating to the sur-face and the installations
Fix pipe sleeves for combustiblepipes with threaded rods on bothsides
Combination insulation for variousstructures with labelling
Secure soft insulation in ceilingsagainst footfall
OBO PYROPLATE® Fibre is amineral fibre or soft insulation.The core of the system is themineral fibre plate coated with amoisture-resistant ablation coat-ing. When there is a fire, the fireprotection coating forms an insu-lating carbon foam. Together withthe mineral fibre plates, this pro-vides effective prevention of thespread of fire and smoke. Ac-cording to the construction ap-proval, in addition to the cables,pipes made of steel, copper orvarious plastics may also be runthrough the same insulation.Therefore, the OBO PYROPLATE®Fibre is combination insulationfor various structures. For pipeli-nes, additional fire protectionmeasures (section insulation andpipe sleeves) are required.
System benefits• Combination of multiple installations possible• Many approved section insulations• Low insulation thickness - "Plate to plate"• Pre-coated plate with final coating is visually tidy• Moisture-resistant coating• Easy retroinstallation
-
Pla
nnin
g a
id, P
YR
OPLA
TE®
Fib
re s
oft
insu
latio
n
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
25OBOBSS
Installation principle, soft insulation, PYROPLATE® Fibre
Mineral fibre plate with ablation coating, soft insulation
Fire resistance class S90
Proof of application General construction approvalof DIBt, Berlin
Testing standard DIN 4102 Part 9
Insulation dimensions in cm
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 10 10 15
Opening width, max. 120 120 125
Opening height, max. 200 200 -
Max. length - - Unlimited
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
26 OBO BSS
-
27OBOBSS
Planning aid, PYROSIT® NG fire protection foam
System description, PYROSIT® NG fire protection foam 28
Installation principle, PYROSIT® NG fire protection foam 29
System description, PYROSIT® NG underfloor fire protectionfoam
30
Installation principle, PYROSIT® NG underfloor fire protec-tion foam
31
-
Pla
nnin
g a
id, P
YR
OSIT
® N
G fire
pro
tect
ion
foam
28 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROSIT® NG fire protection foam
Clean the layer and attach the lin-ing aids, e.g. adhesive tape
Apply the foam from the rear tothe front, and remove residues asnecessary
Use approved section insulationfor metal pipes
Electrical installation pipes up toM40, filled with cables or empty
Combustible pipes up to Ø 50 mmcan be run through without addi-tional measures
Combination insulation for variousstructures with labelling
The PYROSIT® NG fire protectionfoam can offer many benefits inapplication and handling. Its par-ticular recipe means that the two-component material can offervery homogeneous localisedfoam insulation. The chemical re-action is perfectly matched toany requirements. The good sub-strate adhesion prevents thefoam from running out of theopening. Work can easily be in-terrupted to carry out checks.After the reaction process hasbeen completed, PYROSIT® NGhas a soft consistency, meaningthat retroinstallations are veryeasy.In addition to the cables, pipesmade of steel, copper or variousplastics may also be run throughthe same insulation. OBOPYROSIT® NG is therefore combi-nation insulation for variousstructures.
System benefits• Simple working, even with brief interruptions• Good substrate adhesion• Foam volume per cartridge up to 2.1 litres• Soft consistency - easy retroinstallation• No surface coatings required• Dust and fibre-free installation• Combination of multiple installations possible• Many approved section insulations• Battery pressing gun for large-scale use
-
Pla
nnin
g a
id, P
YR
OSIT
® N
G fire
pro
tect
ion
foam
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
29OBOBSS
Installation principle, PYROSIT® NG fire protection foam
2-component fire protection foam, localised foam
Fire resistance class To EI120 To EI120
Proof of application European technical approval of OIB, Vienna
Association of Cantonal Fire Insurers VKF, Berne
Approval number ETA-11/0527 VKF 22552, 22553, 22554, 22555
Testing standard EN 1366 Part 3 EN 1366 Part 3
Additive properties
Heat penetration Fraunhofer IBP Stuttgart P1-001/2012; P1-002/2012
Air permeation/pressure resistance ift Rosenheim 11-003694-PR01/02/03
Noise insulation HfT Stuttgart 122-007-04P-186a
Insulation dimensions in cm
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness (EI90/EI120) 20/25 20/25 20/25
Opening size, max. 45 x 45; Ø 30 45 x 45; Ø 30 45 x 45; Ø 30
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OSIT
® N
G fire
pro
tect
ion
foam
30 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROSIT® NG underfloor fire protection foam
Invisible insulation in screed-cov-ered underfloor ducts
Use of the mixing tube with exten-sion to apply the fire protectionfoam
Labelled underfloor insulation withreserve empty pipe
Invisible insulation in screed-flushunderfloor ducts
Application of the fire protectionfoam directly under the wall
Empty pipes with tension wirescan be foamed in for assignmentat a later date
OBO's PYROSIT® NG fire protec-tion foam is a quick and simpletype of cable insulation for use inunderfloor ducts. If, during anelectrical installation, underfloorducts pass below walls classifiedfor fire protection, then the ductsmust be closed against smokegas penetration and fire.With an open duct system, theduct lid is removed on both sidesof the wall and the foam insertedon both sides. PYROSIT® NG isthe ideal solution for use inscreed-covered underfloor ducts:mounting is carried out, startingfrom the underfloor boxes onboth sides of the wall. Plastic in-stallation pipes can also befoamed in for later retroinstalla-tions.
System benefits• Applications covered by surveyor's comments• Simple working, even with brief interruptions• Good substrate adhesion, even on metal ducts• Foam volume per cartridge up to 2.1 litres• Soft consistency - easy retroinstallation• Empty pipes may also be foamed in as a reserve opening• No surface coatings required• Dust and fibre-free installation
-
Pla
nnin
g a
id, P
YR
OSIT
® N
G fire
pro
tect
ion
foam
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
31OBOBSS
Installation principle, PYROSIT® NG underfloor fire protection foam
2-component fire protection foam, localised foam
Fire resistance class To EI120 To EI120
Proof of application
European technical approvalof the OIB, Viennain conjunction with surveyor's report
Association of Cantonal Fire Insurers VKF, Berne
Approval number ETA-11/0527 VKF 22552, 22553, 22554, 22555
Testing standard EN 1366 Part 3 EN 1366 Part 3
Insulation dimensions in cm
Screed-covered Screed-flush (open)
Min. insulation thickness 30 (2 x 15) 20
Max. duct size 35 x 5 60 x 16
Min. screed thickness 3.5 -
Underfloor socket distance Unlimited -
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
32 OBO BSS
-
33OBOBSS
Planning aid, PYROBAG® cushion insulation
System description, PYROBAG® cushion insulation 34
Installation principle, PYROBAG® cushion insulation 35
System description, cable routing duct, PYROBAG® cushioninsulation
36
Installation principle, PYROBAG® cable routing duct cushioninsulation
37
-
Pla
nnin
g a
id, P
YR
OB
AG
® c
ushi
on in
sula
tion
34 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROBAG® cushion insulation
Closing of the opening with cush-ions - without filler or coating
Panels as mounting aid for the lastcushion layer
Lock against falling out during ceil-ing mounting
Lock against slippage above thefloor
The OBO KBK cable fire protec-tion cushions, which can adoptany shape, are ideal for simple,quick, absolutely tidy and dust-free mounting of the PYROBAG®cable insulation. The cushionscan be used for permanent ortemporary insulations in wallsand ceilings, e.g. during recon-struction. Additional cables canbe installed quickly, tidily andeconomically at a later date, asthe cushions can be used severaltimes over.The cushions consist of a close-knit, dense and mechanically sol-id glass fabric with a special fill-ing. The shell and the filling arefree of mineral fibres and are alsoweatherproof and waterproof.
System benefits• Simple, quick, tidy, dust-free mounting• No coating or fillers required• Ideal solution for frequent retroinstallation• For permanent and temporary insulation• Weatherproof and waterproof• Free of mineral fibres
-
Pla
nnin
g a
id, P
YR
OB
AG
® c
ushi
on in
sula
tion
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
35OBOBSS
Installation principle, PYROBAG® cushion insulation
Glass mesh cushion with special fire protection filling
Fire resistance class S90
Proof of application General construction approvalof DIBt, Berlin
Approval number Z-19.15-1115
Testing standard DIN 4102 Part 9
Insulation dimensions in cm
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 35 35 35
Opening width, max. 100 100 60
Opening height, max. 150 100 -
Max. length - - Unlimited
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OB
AG
® c
ushi
on in
sula
tion
36 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, cable routing duct, PYROBAG® cushion insulation
Cushions arranged in the duct Retaining profile to prevent slip-page in vertical arrangements
Discreet attachment of the identifi-cation plate
The PYROBAG® cable insulation,together with the OBO KBK cablefire protection cushion, is the ide-al solution for insulation in PVCand metal cable routing ducts. In-sulation with the cable fire pro-tection cushions, which can beturned into any shape, can bemounted in a manner which isvery easy, quick, clean and dust-free.As the cushions are only mount-ed within the ducts, the cable in-sulation cannot be seen from theoutside – this is the preconditionfor a perfect cable duct installa-tion, which is usually subjectedto particular optical require-ments. The cushions can be usedfor permanent or temporary insu-lations in walls and ceilings. Ad-ditional cables can be installedquickly, tidily and economicallyat a later date, as the cushionscan be used several times over.
System benefits• Ideal solution for insulation in plastic and metal cable routing ducts• Insulation in the interior of the duct invisible on the outside• No visual impairment of the duct installation• Simple, quick, tidy, dust-free mounting• No coating or fillers required• Retroinstallations possible at any time
-
Pla
nnin
g a
id, P
YR
OB
AG
® c
ushi
on in
sula
tion
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
37OBOBSS
Installation principle, PYROBAG® cable routing duct cushion insulation
Glass mesh cushion with special fire protection filling
Fire resistance class S90
Proof of application General construction approvalof DIBt, Berlin
Approval number Z-19.15-1119
Testing standard DIN 4102 Part 9
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 35 35 35
Max. metal duct size 21 x 10 21 x 10 21 x 10
Max. plastic duct size 21 x 8 21 x 8 21 x 8
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
38 OBO BSS
-
39OBOBSS
Contents: planning aid, PYROPLUG® foam series
PYROPLUG® Block 200 stones 40
PYROPLUG® Block 200 stones, underfloor 42
PYROPLUG® Block 220 stones 44
PYROPLUG® Block 120 stones 46
PYROPLUG® Peg plugs 48
PYROPLUG® Box box insulation 50
PYROPLUG® Shell pipe shells 52
PYROMIX® Mini small insulation 54
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
40 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROPLUG® Block 200 stones
Mounting of the cut blocks Vacuum blocks for simple residualgap closing
Simple retroinstallation through re-moval of individual blocks
Running of combustible pipes with-out additional measures
Run-through, non-combustiblepipes with section insulation
Tight-fitting installation of theblocks in the ceiling penetration
The OBO PYROPLUG® Block 200combination insulation is createdfrom foam blocks, which, if thereis a fire, expand without any no-ticeable pressure creation. In sodoing, they form an insulatingcarbon foam. This reliably pre-vents the penetration of fire andsmoke through the cable insula-tion.Combustible pipes can be run inthis insulation without an addi-tional sleeve. Copper and steelpipes can be insulated either withor without section insulation.All the PYROPLUG® Block 200 in-sulation is completely dust andfibre-free. This also applies toany installations at a later date.This is an aspect, which is partic-ularly important for installation inIT and laboratory rooms.
System benefits• Combination insulation• Running of combustible pipes without additional measures• Running of non-combustible pipes with section insulation• Simple, dust and fibre-free mounting• Simple retroinstallation• Residual joints closed with PYROPLUG® Screed filler (type FBA-SP)
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
41OBOBSS
Installation principle, stones PYROPLUG® Block 200
Foam rubber fitting with fire protection additives
Fire resistance class S90 S90
Proof of application General construction approvalof DIBt, Berlin
Association of Cantonal Fire Insurers VKF, Berne
Approval number Z-19.15-1849 VKF 18140, 18141, 18142
Testing standard DIN 4102 Part 9 DIN 4102 Part 9
Additive properties
Heat penetration Fraunhofer IBP Stuttgart P1-001/2012; P1-002/2012
Air permeation/pressure resistance ift Rosenheim 11-003694-PR01/02/03
Noise insulation HfT Stuttgart 122-007-04P-186a
Insulation dimensions in cm
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 20 20 20
Opening width, max. 100 84 (57) 70
Opening height, max. 100 57 (84) -
Max. length - - Unlimited
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
42 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROPLUG® Block 200 underfloor stones
Invisible insulation in screed-flushunderfloor ducts
Adjustment of the foam blockswith a knife
Closing of residual joints with thefiller FBA-SP
Invisible insulation in screed-cov-ered underfloor ducts
Cutting of thin strips for the ductcompartments
Close the joints between cablesand blocks with the FBA-SP filler
The OBO PYROPLUG® Block200 cable insulation is the idealcable insulation for use in under-floor ducts. If, during an electricalinstallation, underfloor ductspass below walls classified forfire protection, then the ductsmust be closed against smokegas penetration and fire.With an open duct system, theduct lid is removed on both sidesof the wall and the blocks insert-ed on both sides. ThePYROPLUG® Block 200 cable in-sulation can only be mounted onscreed-covered underfloor ductsfrom the underfloor boxes onboth sides of the wall. Retroin-stallations can be carried outvery easily by removing individu-al blocks.
System benefits• Mounting directly in underfloor duct• Invisible cable insulation• Mounting of empty pipes to prepare for retroinstallations• Dust and fibre-free mounting• Residual joints closed with PYROPLUG® Screed filler (type FBA-SP)
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
43OBOBSS
Installation principle, underfloor stones PYROPLUG® Block 200
Foam rubber fitting with fire protection additives
Fire resistance class S90 S90
Proof of application
General construction approvalof DIBt, Berlinin conjunction withsurveyor's report
Association of Cantonal Fire Insurers VKF, Berne
Approval number Z-19.15-1849 VKF 18140, 18141, 18142
Testing standard DIN 4102 Part 9 DIN 4102 Part 9
Insulation dimensions in cm
Screed-covered Screed-flush (open)
Min. insulation thickness 40 (2 x 20) 20
Max. duct size 35 x 5 60 x 16
Min. screed thickness 3.5 -
Underfloor socket distance Unlimited -
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
44 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROPLUG® Block 220 stones
Mounting of the cut blocks Cable reels according to the cablediameter and the fire resistanceclass
Vacuum blocks for simple residualgap closing
Simple retroinstallation through re-moval of individual blocks
Tight-fitting installation of theblocks in the ceiling penetration
The OBO PYROPLUG® Block 220cable insulation system is creat-ed from special foam blocks. Theinsulation system is particularlysuitable for regular retroinstalla-tions, e.g. in the fields oftelecommunications and dataprocessing. Here, it is primarilysmaller cable cross-sectionswhich are used. According to theETA approval, a special coil isadditionally required for the ca-bles with a larger diameter andaccording to the fire resistanceclass. If there is a fire, this foamsup and provides the appropriateheat insulation.The PYROPLUG® Block 220 cableinsulation can be created withoutany dust or fibres. This also ap-plies to any installations at a laterdate. This is an aspect which isparticularly important for installa-tion in data processing and labo-ratory rooms.
System benefits• Large dimensions require less blocks per insulation• Routing of steel cable support systems permitted• Ideal solution for use in the field of telecommunications and data pro-
cessing• Very suitable for regular retroinstallation of small cables• Simple, dust and fibre-free mounting• Simple retroinstallation• Residual joints closed with PYROPLUG® Screed filler (type FBA-SP)
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
45OBOBSS
Installation principle, stones PYROPLUG® Block 220
Foam rubber fitting with fire protection additives
Fire resistance class To EI120
Proof of application European technical approval of OIB, Vienna
Approval number ETA-11/0237
Testing standard EN 1366 Part 3
Insulation dimensions in cm
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 22 22 22
Opening width, max. 100* 100* 41
Opening height, max. 100* 100* -
Max. length - - Unlimited* Maximum area may not exceed 0.6 m².
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
46 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, stones, PYROPLUG® Block 120
Cable reels for cables with a diam-eter of more than 18 mm and forsupport systems
Mounting of the cut blocks Vacuum blocks for simple residualgap closing
Simple retroinstallation through re-moval or cutting of individualblocks
Tight-fitting installation of theblocks in the ceiling penetration
The OBO PYROPLUG® Block 120cable insulation system is creat-ed from special foam blocks. Theinsulation system is particularlysuitable for regular retroinstalla-tions, e.g. in the fields oftelecommunications and dataprocessing. Here, it is primarilysmaller cable cross-sectionswhich are used. An additionalspecial coil is required for cablesof a diameter of more than 18 mmand for support systems runthrough the insulation. If there isa fire, this foams up and providesthe appropriate heat insulation.The PYROPLUG® Block 120 cableinsulation can be created withoutany dust or fibres. This also ap-plies to any installations at a laterdate. This is an aspect which isparticularly important for installa-tion in data processing and labo-ratory rooms.
System benefits• Routing of steel cable support systems permitted• Ideal solution for use in the field of telecommunications and data pro-
cessing• Very suitable for regular retroinstallation of small cables• Simple, dust and fibre-free mounting• Simple retroinstallation• Residual joints closed with PYROPLUG® Screed filler (type FBA-SP)
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
47OBOBSS
Installation principle, stones PYROPLUG® Block 120
Foam rubber fitting with fire protection additives
Fire resistance class S90 S90
Proof of application General construction approvalof DIBt, Berlin
Association of Cantonal Fire Insurers VKF, Berne
Approval number Z-19.15-1850 VKF 18139
Testing standard DIN 4102 Part 9 DIN 4102 Part 9
Insulation dimensions in cm
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 12 12 12
Opening width, max. 100 87.5 70
Opening height, max. 100 57.5 -
Max. length - - Unlimited
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
48 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROPLUG® Peg plugs
Cutting of the plugs for cable as-signment on the edge of the corehole
Push cut plugs into the core hole Mounting of the pipe shell in light-duty partition
Cutting and mounting of the plugsin the pipe shell
In case of full assignment, closeoff the residual joints with the FBA-SP filler
With retroinstallations, careful cut-ting and drilling of the plugs
The FBA plug is available in 8 dif-ferent sizes for creation of theOBO PYROPLUG® Peg cable in-sulation. They consist of a per-manently elastic, closed-porefoam. The FBA plugs are the ide-al solution for closing core holes.The pipe shell FBA-SR is also re-quired to create round cable in-sulation in lightweight partitionwalls. This variant of thePYROPLUG® Peg cable insulationconsists of a two part, fixed pipeshell and two matching FBAplugs. The PYROPLUG® Peg insu-lation system can be used with-out difficulty in areas of data pro-cessing and in laboratories, asmounting is completely clean andis free or dust and fibres. This al-so applies to any necessary ca-ble installations at a later date.Special tools are not required forprocessing, a knife is sufficient.
System benefits• Ideal solution for core drill holes in solid walls and concrete ceilings• Mounting also possible in light-duty partitions in combination with the
FBA-SR pipe shell• Full assignment of the pipe shell possible• Group formation possible• Simple, dust and fibre-free mounting• Simple retroinstallation• Residual joints closed with PYROPLUG® Screed filler (type FBA-SP)
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
49OBOBSS
Installation principle, PYROPLUG® Peg plug
Foam rubber fitting with fire protection additives
Fire resistance class S30/S90 S30/S90
Proof of application General construction approvalof DIBt, Berlin
Association of Cantonal Fire Insurers VKF, Berne
Approval number Z-19.15-1558 VKF 18816
Testing standard DIN 4102 Part 9 DIN 4102 Part 9
Additive properties
Heat penetration Fraunhofer IBP Stuttgart P1-001/2012; P1-002/2012
Air permeation/pressure resistance ift Rosenheim 11-003694-PR01/02/03
Noise insulation HfT Stuttgart 122-007-04P-186a
Insulation dimensions in cm
Component F30 Solid wall Light-duty partition wall Solid ceiling
Min. component strength 5 7.5 15
Min. insulation thickness 12 12 12
Core drill hole Ø max. 25 25 25
Component F90 Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 15 15 15
Core drill hole Ø max. 25 25 25
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
50 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROPLUG® Box box insulation
Insertion of the split frame in light-duty partitions
Mounting of the frame with previ-ously installed cables
Exact cutting of the internal piecesand then insertion in the frame
Closing joint component on full as-signment with cables
Grouped arrangement of the box-es
The OBO PYROPLUG® Box cableinsulation is a special system forsimple mounting of cable insula-tion in light-duty partitions. In-stallation in solid walls and ceil-ings is also possible and ap-proved.The insulation system consists ofa two-part frame and two match-ing internal pieces. As the inter-nal area of the boxes is exactly60% of the external area, it is im-possible to over assign it with ca-bles. This usable area corre-sponds to the maximum approvalcable assignment.
System benefits• Ideal solution for cable insulation in light-duty partition walls• Full cable assignment possible• Grouped arrangement of the frames approved• Simple, dust and fibre-free mounting• Simple retroinstallation• Residual joints closed with PYROPLUG® Screed filler (type FBA-SP)
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
51OBOBSS
Installation principle, PYROPLUG® Box box insulation
Foam rubber fitting with fire protection additives
Fire resistance class S30/S90 S30/S90
Proof of application General construction approvalof DIBt, Berlin
Association of Cantonal Fire Insurers VKF, Berne
Approval number Z-19.15-1557 VKF 18817
Testing standard DIN 4102 Part 9 DIN 4102 Part 9
Insulation dimensions in cm
Component F30 Solid wall Light-duty partition wall Solid ceiling
Min. component strength 5 7.5 15
Min. insulation thickness 12 12 12
Opening width, max. 50 50 50
Opening height, max. 50 50 -
Max. length - - 50
Component F90 Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 20 20 20
Opening width, max. 50 50 50
Opening height, max. 50 50 -
Max. length - - 50
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
52 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROPLUG® Shell pipe shells
Drilling of a hole with a drill crown Grouped arrangement of the drillholes
Insertion of the pipe shell in thelight-duty partition
For previously installed cables, cut-ting of the pipe shell
Cutting and insertion of the plugsin the pipe shell
Full assignment of the pipe shell
The OBO PYROPLUG® Shell ca-ble insulation is the ideal solutionfor installing small round cableinsulation quickly and simply, es-pecially in light-duty partitionwalls.The insulation system consists ofa pipe shell and two matchingplugs. The ratio of the external di-ameter to the internal diameter ofthe pipe shell ensures that overassignment with cables is notpossible, even at full assignment.
System benefits• Ideal solution for small, round cable insulation in light-duty partition
walls• Grouped arrangement of the pipe shells permitted• Full cable assignment possible• Simple, dust and fibre-free mounting• Simple retroinstallation• Residual joints closed with PYROPLUG® Screed filler (type FBA-SP)
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
53OBOBSS
Installation principle, PYROPLUG® Shell pipe shells
Foam rubber fitting with fire protection additives
Fire resistance class S30/S90 S30/S90
Proof of application General construction approvalof DIBt, Berlin
Association of Cantonal Fire Insurers VKF, Berne
Approval number Z-19.15-1559 VKF 18815
Testing standard DIN 4102 Part 9 DIN 4102 Part 9
Insulation dimensions in cm
Component F30 Solid wall Light-duty partition wall Solid ceiling
Min. component strength 5 7.5 15
Min. insulation thickness 10 10 10
Component F90 Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 10 10 10
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
54 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROMIX® Mini small insulation
Closing of the opening with thefiller FBA-SP
In light-duty partitions, use of themini pipe shell FBA-DR
Complete assignment of the minipipe shell
The OBO PYROPLUG® Mini cableinsulation is a quick and simpleoption for creating small roundcable insulations. It only consistsof the one-component fillerPYROPLUG® Screed (type FBA-SP).The insulation may also be in-stalled in light-duty partitions.The empty mini pipe shells FBA-DR are used to create the layers.The interior of these pipe shellsmay be completely assigned. On-ly the residual joints must befilled with the filler.
System benefits• Only one component: PYROPLUG® Screed filler (type FBA-SP)• Simple solution for small round cable insulation in walls and ceilings• Mounting approved in combination with the mini pipe shell in light-
weight partitions• Simple, dust and fibre-free mounting• Simple retroinstallation
-
Pla
nnin
g a
id, P
YR
OPLU
G®
foa
m s
erie
s
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
55OBOBSS
Installation principle, PYROPLUG® Mini small insulation
1-component fire protection compound, dispersion-based
Fire resistance class S90 S90
Proof of application General construction approvalof DIBt, Berlin
Association of Cantonal Fire Insurers VKF, Berne
Approval number Z-19.15-1851 VKF 18143
Testing standard DIN 4102 Part 9 DIN 4102 Part 9
Insulation dimensions in cm
Component Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Min. insulation thickness 10 10 15
Core drill hole Ø max. 8 8 8
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
56 OBO BSS
-
57OBOBSS
Planning aid, PYROCOMB® pipe sleeve
System description, PYROCOMB® Tubes cable insulation 58
Installation principle, PYROCOMB® Tubes cable insulation 59
System description, PYROCOMB® pipe insulation 60
Installation principle, PYROCOMB® pipe insulation 61
-
Pla
nnin
g a
id, P
YR
OC
OM
B®
pip
e sl
eeve
58 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROCOMB® Tubes cable insulation
Two-sided arrangement of the pipesleeves for wall mounting
Mounting on the underside of theceiling with metal anchors
Closing of the ring gap with the in-sulation layer creator DSX
Combination of the sleeve halvesand fastening on the wall
Closing of the pipe ends with theinsulation layer creator DSX
Labelled insulation of installationpipe bundles
The PYROCOMB® Tubes cable in-sulation consists of multiplesizes of the pipe sleeve, typeTCX, of the PYROCOMB® system.This allows simple insulation ofbundles of plastic electrical in-stallation pipes, rigid or flexible.It is irrelevant whether the pipesare filled with cables or are emp-ty.In case of fire, the fire protectionmaterial inserted within the sealfoams up after a few minutes un-der high pressure, closing thesoftened bundles at a high pres-sure. This safely prevents thespread of fire and smoke, shoulda fire occur.
System benefits• Simple solution for electrical installation pipe bundle• Bundle diameter up to 125 mm• Maximum pipe diameter in bundle M63• Rigid and flexible pipes• Pipes filled with cables (max. Ø 21 mm) or empty• Pipe and ring gap closure with insulation layer creator DSX
-
Pla
nnin
g a
id, P
YR
OC
OM
B®
pip
e sl
eeve
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
59OBOBSS
Installation principle, PYROCOMB® Tubes cable insulation
Sleeve with metal housing and fire protection inlays
Fire resistance class S90 To EI120
Proof of application General construction approvalof DIBt, Berlin
European technical approval of OIB, Vienna
Approval number Z-19.15-2031 ETA-12/0207
Testing standard DIN 4102 Part 9 EN 1366 Part 3
Insulation dimensions in cm
S90 data Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Max. pipe bundle Ø 12.5 12.5 12.5
EI120 data Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Max. pipe bundle Ø 12.5 12.5 12.5
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, P
YR
OC
OM
B®
pip
e sl
eeve
60 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROCOMB® pipe insulation
Two-sided arrangement of the pipesleeves for wall mounting
Mounting on the underside of theceiling with metal anchors
Sloping pipe penetration up to anangle of 39°
Pipe sleeves in the area of thepenetration
Eccentric arrangement with max. 3levels of larger pipe sleeves
Pipe post systems with 2 accom-panying cables
The pipe sleeves, type TCX of thePYROCOMB® system, can beused as independent pipe sealingfor combustible pipes (e.g. sani-tary wastewater pipes). Mountingtakes place with metal anchorson each side of the wall. Ceilingpenetrations only have a tubeseal from the underside. Thread-ed rods are mounted using thepush-through method in dry par-tition walls.In case of fire, the fire protectionmaterial inserted within the sealfoams up after a few minutes un-der high pressure, closing thesoft plastic pipes. This safely pre-vents the spread of fire andsmoke, should a fire occur.The PYROCOMB® pipe sleevesmay only be used to insulateplastic pipes in the PYROMIX®and PYROPLATE® Fibre systems.
System benefits• Many approved pipe materials• Sloping penetration (up to 39°) possible• Noise insulation on pipes need not be removed• Slender pipe sleeve structure• The size of the pipe sleeve may be three levels greater than the di-
ameter of the run-through pipe• Versatile application in various systems
-
Pla
nnin
g a
id, P
YR
OC
OM
B®
pip
e sl
eeve
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
61OBOBSS
Installation principle, PYROCOMB® pipe insulation
Sleeve with metal housing and fire protection inlays
Fire resistance class R90 To EI240
Proof of application General construction approvalof DIBt, Berlin
European technical approval of DIBt, Berlin
Approval number Z-19.17-2036 ETA-12/0182
Testing standard DIN 4102 Part 11 EN 1366 Part 3
Insulation dimensions in cm
S90 data Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Max. pipe Ø 20 16 20
EI120 data Solid wall Light-duty partition wall Solid ceiling
Min. component strength 10 10 15
Max. pipe Ø 20 16 20
The data in the named proofs of applicability apply.
-
62 OBO BSS
-
63OBOBSS
Planning aid, materials for small insulation and individual cables acc. toMLAR
System description, PYROMIX® Screed small insulation 64
Installation principle, PYROMIX® Screed small insulation 65
System description, individual cables according to MLARwith insulating layer forming agent
66
Installation principle, individual cables according to MLARwith insulating layer forming agent
67
-
Pla
nnin
g a
id, m
ater
ials
for
sm
all i
nsul
atio
n an
d in
divi
dual
cab
les
acc.
to
MLA
R
64 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, PYROMIX® Screed small insulation
Mineral wool with melting point ≥1,000 °C to plug the opening
2 cm-deep closure of the surfaceson both sides with the DSX insula-tion layer creator
Labelling of the small insulation
The PYROMIX® Screed small in-sulation only consists of twocomponents: OBO's insulationcreating material, type DSX, andthe MIW mineral wool. The non-combustible mineral wool has amelting point ≥ 1,000 °C andserves as a basis for the cable in-sulation. When the opening hasbeen plugged, both sides of theopening are sealed with the DSXinsulation creator.If there is a fire, the filler foamsup, preventing penetration by fireand smoke. The foaming actionalso draws heat from the cables,thus considerably reducing thetransfer of heat via the coppercores.
System benefits• Very simple assembly• Only two components required• Low-cost, approved components• In cartridges or in a bucket• Components can be used in other systems• Fulfils the requirements of the MLAR regarding so-called aids
-
Pla
nnin
g a
id, m
ater
ials
for
sm
all i
nsul
atio
n an
d in
divi
dual
cab
les
acc.
to
MLA
R
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
65OBOBSS
Installation principle, PYROMIX® Screed small insulation
Small insulation made of mineral fibres and fire protection filler
Fire resistance class S90
Proof of application General construction approvalof DIBt, Berlin
Approval number Z-19.15-2044
Testing standard DIN 4102 Part 9
Insulation dimensions in cm
Component Solid wall Solid ceiling
Min. component strength 15 15
Min. insulation thickness 15 15
Opening size, max. 10x10; Ø 10 10x10; Ø 10
Maximum approved assignment of the opening area with installations: 60%. The data in the named proofs of applicability apply.
-
Pla
nnin
g a
id, m
ater
ials
for
sm
all i
nsul
atio
n an
d in
divi
dual
cab
les
acc.
to
MLA
R
66 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, individual cables according to MLAR with insulatinglayer forming agent
DSX insulation layer creator, suit-able for full-wall ring gap closure insolid walls and ceilings
With light-duty partitions, filling thedouble plates to both sides is suffi-cient
The OBO insulation layer cre-ation material, type DSX, can beused to fill drill holes for penetra-tions with a single cable or multi-ple cables of a small cross-sec-tion, routed next to each other,through walls and ceilings mark-ing the end of fire sections, in ac-cordance with the cable systemsdirective.The ring gap around the cablemust be completely closed withfire protection filler. If there is afire, the filler foams up, prevent-ing penetration by fire andsmoke. The foaming action alsodraws heat from the cables, thusconsiderably reducing the trans-fer of heat via the copper cores.
System benefits• Low-cost, approved material• Simple handling• In cartridges or in a bucket• Components for other systems
-
Pla
nnin
g a
id, m
ater
ials
for
sm
all i
nsul
atio
n an
d in
divi
dual
cab
les
acc.
to
MLA
R
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
67OBOBSS
Installation principle, individual cables according to MLAR with insulat-ing layer forming agent
Insulation forming material on dispersion basis
Material class B2 – normally flammable
Proof of application General construction approvalof DIBt, Berlin
Approval number Z-19.11-1991
Testing standard DIN 4102
Minimum dimensions of components and their fire resistance period
Min. solid component strength 60 70 80
Fire resistance class F30 F60 F90
Ring gap max. 15 15 15
All data in mm. The data in the named proofs of applicability apply.
-
68 OBO BSS
-
69OBOBSS
Planning aid, escape route installations, false ceiling
Grip M grouped support 70
Metal pressure clip 72
Cable tray RKS-Magic® 74
Cable tray SKS 78
Mesh cable tray GR-Magic® 82
G mesh cable tray G-GRM 86
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
70 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, Grip M grouped support
Wall and ceiling mounting abovesuspended fire protection ceiling
Required minimum spacing to thefire protection ceiling
Simple insertion the cables in theopened grouped support
The mechanical stability of thegrouped supports in case of firehas been proved for wall and ceil-ing mounting for fire loads of 90minutes.The grouped supports are madeof galvanised sheet steel and canbe opened and closed easilywithout the use of tools. To allowsimple cable insertion, thegrouped supports can remainopen during cable routing. Thegrouped supports are onlyclosed when cable installation iscomplete. The construction of thegrouped support and weight ofthe installed cables automaticallyensures that the lock does notopen itself unintentionally.
System benefits• Tested routing variant• Proof of minimum spacing to the fire protection ceiling• Horizontal wall and ceiling mounting• Can be closed and reopened without tools• Various dimensions of the grouped supports• Full assignment with cables possible
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
71OBOBSS
Installation principle, Grip M grouped support
Fire-proof fastenings above fire protection ceilings
Fire load 30 and 90 minutes
Testing proof Materials' testing institute iBMB MPA Braunschweig
Document no. 3054/1495-Mu
Testing principles In accordance with DIN 4102
Carrying capacity under fire load and mounting parameters
Fire load 30 min. Fire load 90 min. Max. fastening spacing Distance "a" min.
2031 M15 - 2.0 kg 60 cm 100 mm
2031 M30 - 3.5 kg 60 cm 100 mm
2031 M70 12 kg 8.0 kg 80 cm 250 mm
Caution!No electrical function maintenance according to DIN 4102 Part 12!
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
72 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, metal pressure clip
Ceiling mounting above suspend-ed fire protection ceiling
Required minimum spacing to thefire protection ceiling
Simple cable installation throughside insertion of the cables
The mechanical stability of thepressure clips in case of fire hasbeen proved for ceiling mountingfor fire loads of 30 minutes.The pressure clips are made ofsprung, rust-proof steel. Cableassignment is possible from bothsides, and the cables simplyneed be pushed under the hips ofthe clip. A tool is not required tomount the cables. The edges ofthe clip are sloping, excludingthe possibility of damage to thecables.
System benefits• Tested routing variant• Proof of minimum spacing to the fire protection ceiling• Space-saving mounting directly under the ceiling• Simple pushing in of the cable from the side• No tool required for cable installation• 2 different sizes
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
73OBOBSS
Installation principle, metal pressure clip
Fire-proof fastenings above fire protection ceilings
Fire load 30 minutes
Testing proof Materials' testing institute iBMB MPA Braunschweig
Document no. 3094/2093-CM
Testing principles In accordance with DIN 4102
Carrying capacity under fire load and mounting parameters
Fire load 30 min. Cable filling max. Max. fastening spacing Distance "a" min.
2033M 0.23 kg/m 16 (2 x 8) 0.5 m 70 mm
2034M 0.23 kg/m 10 (2 x 5) 0.6 m 50 mm
Caution!No electrical function maintenance according to DIN 4102 Part 12!
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
74 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, cable tray RKS-Magic®
Single-layer ceiling mountingabove suspended fire protectionceiling
Two-layer ceiling mounting abovesuspended fire protection ceiling
Required minimum spacing to thefire protection ceiling
Clamp fastening for high load ca-pacities
Screwless joint connection, onlythe base lugs need to be bent
The mechanical stability of theRKS-Magic® cable trays in case offire has been proved for fireloads of 30 minutes.The mounting system consists ofthe MS41 mounting rail withthreaded rod suspension fromthe ceiling on both sides. A two-layer arrangement of the cabletrays up to a width of 300 mm ispossible, providing that the ap-proved tensile stress in thethreaded rods is maintained incase of fire. Due to the varyingdeformations in case of fire, se-lect the cable trays according tothe space available to the falseceiling. These characteristic de-formation values of the appropri-ate cable trays are documentedappropriately.
System benefits• Tested routing system• Space-saving mounting under the ceiling• Two-layer mounting up to tray width 300 mm possible• Proof of minimum spacing to the fire protection ceiling• Full assignment of cable trays possible• Various widths of the cable tray
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
75OBOBSS
Installation principle, RKS-Magic® cable tray
Fire-proof fastenings above fire protection ceilings
Fire load 30 minutes
Testing proof BET, Menden
Document no. 05130/111108-01
Testing principles In accordance with DIN 4102
Carrying capacity under fire load and mounting parameters
Cable tray width in mm Cable load in kg/m Max. support spacing in m Distance "a" in mm
100 15 1.5 70
200 30 1.5 180
300 45 1.5 180
400 60 1.5 180
Caution!No electrical function maintenance according to DIN 4102 Part 12!
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
76 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Components used: cable tray RKS-Magic®
False ceiling routing system formounting under the raw ceiling onU transverse profile with threadedrod pendulum suspension.
Parameters:• Span: max. 1.5 m• Tray width max. 400 mm• Max. number of layers 2• Max. cable load 15 kg/m per
100 mm of tray width
Components used
Cable tray RKSM 6… FS 1 2
Truss-head bolt FRSB 6x15 F 2 4
Large washer DIN440 7 F 2 4
Mounting rail MS 41 L … FS 1 2
Protective cap MS 41 SK OR 2 4
Threaded rod 2078 M12 1m G 2 4
Connection sleeve 12005 M12 G 0 2Two layers limited to maximum 300 mm width; fastening anchors should be chosen according to the substrate. The appropriate amount of hexagonalnuts and washers are required.
-
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
77OBOBSS
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
78 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, cable tray SKS
Single-layer ceiling suspension Two-layer ceiling suspension withbracket arrangement on one side
Two-layer ceiling suspension withbracket arrangement on bothsides
Wall mounting, one and two-layerpossible
Required minimum spacing to thefire protection ceiling
Mounting of the threaded rod lockthrough the connection bracket onthe tip of the bracket
The mechanical stability of therouting system with SKS cabletrays in case of fire has beenproved for fire loads of 30 min-utes. The tested routing systemcan be mounted on the wall orunder the ceiling. To preventbending of the brackets in caseof fire, a threaded rod lock mustbe mounted at the bracket tip.Due to the varying deformationsin case of fire, select the cabletrays according to the spaceavailable to the false ceiling. Thefire protection survey documentsthese spacings. When appliedlogically, the parameters visiblethere allow the implementation ofmulti-layer variants.
System benefits• Tested routing system• Wall and ceiling mounting• Two-layer mounting up to tray width 300 mm possible• Proof of minimum spacing to the fire protection ceiling• Full assignment of cable trays possible• Various widths of the cable tray
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
79OBOBSS
Installation principle, SKS cable tray
Fire-proof fastenings above fire protection ceilings
Fire load 30 minutes
Testing proof Materials' testing institute iBMB MPA Braunschweig
Document no. 3059/3644-AR/Mu
Testing principles In accordance with DIN 4102
Carrying capacity under fire load and mounting parameters
Cable tray width in mm Cable load in kg/m Max. support spacing in m Distance "a" in mm
200 30 1.5 65
300 45 1.5 95
400 60 1.5 130
500 75 1.5 160
600 90 1.5 190
Caution!No electrical function maintenance according to DIN 4102 Part 12!
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
80 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
Components used: cable tray SKS
False ceiling routing system formounting under the raw ceilingwith U suspended support, AWFbracket and threaded rod locking.
Parameters:• Span: max. 1.5 m• Tray width max. 600 mm• Max. number of layers 2• Max. cable load 15 kg/m per
100 mm of tray width
Components used
Cable tray SKS 6… FS 1 2 2
Connector RWVL 60 FS 2 4 4
Joint plate SSLB… FS 1 2 2
Truss-head bolt FRSB 6x 12 F 1 2 2
Truss-head bolt FRSB 6x 20 F 1 2 2
US 5 suspended support US 5 K … FT 1 1 1
Protective cap US 5 KS OR 1 1 1
Wall and support brackets AW30F… FT 1 2 2
Spacer DSK 45 FT 1 2 1
Hexagonal bolt SKS 10x 90 F 1 2 1
Threaded rod 2078 M12 1m G 1 2 2
Connection sleeve 12005 M12 G 0 1 0
Fire protection clamp* BSB FT 1 1 2* Alternatively, directly with internal thread anchor; two layers limited to maximum 300 mm width; fastening anchors should be chosen according to thesubstrate. The appropriate amount of hexagonal nuts and washers are required.
False ceiling routing system formounting on the wall with AWFbracket and threaded rod locking.
Parameters:• Span: max. 1.5 m• Tray width max. 600 mm• Max. number of layers 2• Max. cable load 15 kg/m per
100 mm of tray width
Components used
Cable tray SKS 6… FS 1 2
Connector RWVL 60 FS 2 4
Joint plate SSLB… FS 1 2
Truss-head bolt FRSB 6x 12 F 1 2
Truss-head bolt FRSB 6x 20 F 1 2
Wall and support brackets AW30F… FT 1 2
Threaded rod 2078 M12 1m G 1 2
Connection sleeve 12005 M12 G 0 1
Fire protection clamp* BSB FT 1 1* Alternatively, directly with internal thread anchor; two layers limited to maximum 300 mm width; fastening anchors should be chosen according to thesubstrate. The appropriate amount of hexagonal nuts and washers are required.
-
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
81OBOBSS
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
82 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
System description, mesh cable tray GR-Magic®
Single-layer ceiling mountingabove suspended fire protectionceiling
Two-layer ceiling mounting abovesuspended fire protection ceiling
Required minimum spacing to thefire protection ceiling
Clamp fastening for high load ca-pacities
Screwless joint connection
The mechanical stability of therouting system with GR-Magic®mesh cable trays in case of firehas been proved for fire loads of30 minutes.The routing system consists ofthe mounting rails MS21 and/orMS41 in a pendulum suspensionfrom the ceiling. A two-layer ar-rangement of the mesh cabletrays up to a width of 400 mm ispossible, providing that the ap-proved tensile stress in thethreaded rods is maintained incase of fire.Due to the varying deformationsin case of fire, select the meshcable trays according to thespace available to the false ceil-ing. These characteristic defor-mation values of the appropriatemesh cable trays are document-ed appropriately.
System benefits• Tested routing system• Space-saving mounting under the ceiling• Two-layer mounting• Proof of minimum spacing to the fire protection ceiling• Various widths of the mesh cable tray
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /
18/0
7/20
12
83OBOBSS
Installation principle, GR-Magic® mesh cable tray
Fire-proof fastenings above fire protection ceilings
Fire load 30 minutes
Testing proof BET, Menden
Document no. 05130/111110-01
Testing principles In accordance with DIN 4102
Carrying capacity under fire load and mounting parameters
Mesh cable tray width in mm Cable load in kg/m Max. support spacing in m Distance "a" in mm
100 10 1.5 150
200 20 1.5 155
300 30 1.5 160
400 40 1.5 165
Caution!No electrical function maintenance according to DIN 4102 Part 12!
-
Pla
nnin
g a
id, e
scap
e ro
ute
inst
alla
tions
, fal
se c
eilin
g
84 OBO BSS
05_B
SS
_Mas
terk
atal
og_L
ände
r_20
12 /
en /
17/0
7/20
12 (L
LExp
ort_
0400
3) /