building automation systems - ibcon - advantechibcon.com/catalog_website/advantech/bas...

22
Building Automation Systems Empower BA Systems with Open and Web-enabled Technologies 25-2 Advantech BAS Solution Framework 25-3 BAS-3000 I/O Module Selection Guide 25-4 WebView Selection Guide 25-5 Webaccess HMI/SCADA Software Advantech WebAccess Browser-based HMI/SCADA Software 25-6 Building Energy Management System Advantech BEMS Building Energy Management Software 25-8 Web-enabled DDC Controllers BAS-3512 BAS-3520 12-ch Web-enabled DDC Controller 20-ch Web-enabled DDC Controller 25-9 BAS-3520C (New) 20-ch Web-enabled Chiller DDC Controller 25-10 BASPro BAS-3000 DDC Programming Tool 25-11 Expansion I/O Modules BAS-3018 BAS-3024 8-ch UI Expansion Module 4-ch UI, 4-ch AO, 4-ch DO Expansion Module 25-12 BAS-3050 BAS-3051 8-ch DI, 8-ch DO Expansion Module 16-ch DI Expansion Module 25-13 BAS-3060 (New) 8-ch DO Relay Expansion Module 25-14 BACNet Remote I/O Module BAS-3018BC (New) BAS-3024BC (New) 8-ch UI BACNet MS/TP Remote I/O Module 4-ch UI, 4-ch AO, 4-ch DO BACNet MS/TP Remote I/O Module 25-15 BAS-3050BC (New) BAS-3051BC (New) 8-ch DI, 8-ch DO BACNet MS/TP Remote I/O Module 16-ch DI BACNet MS/TP Remote I/O Module 25-16 BAS-3060BC (New) 8-ch DI, 8-ch DO Relay BACNet MS/TP Remote I/O Module 25-17 WebLink & WebView Platforms WebLink-2170 Web-enabled Communication Gateway 25-18 WebView-660E 5.7" Web-enabled HMI 25-19 WebView-1070 10.4" Web-enabled HMI 25-20 WebView-1261 12.1" Web-enabled HMI with AMD LX800 25-21 WebView-1270 12.1" Web-enabled HMI with Intel Celeron M 25-22

Upload: truongxuyen

Post on 15-Feb-2019

224 views

Category:

Documents


0 download

TRANSCRIPT

��Building Automation Systems Empower BA Systems with Open and Web-enabled Technologies 25-2

Advantech BAS Solution Framework 25-3

BAS-3000 I/O Module Selection Guide 25-4

WebView Selection Guide 25-5

Webaccess HMI/SCADA SoftwareAdvantech WebAccess Browser-based HMI/SCADA Software 25-6

Building Energy Management SystemAdvantech BEMS Building Energy Management Software 25-8

Web-enabled DDC ControllersBAS-3512BAS-3520

12-ch Web-enabled DDC Controller20-ch Web-enabled DDC Controller

25-9

BAS-3520C (New) 20-ch Web-enabled Chiller DDC Controller 25-10

BASPro BAS-3000 DDC Programming Tool 25-11

Expansion I/O ModulesBAS-3018BAS-3024

8-ch UI Expansion Module4-ch UI, 4-ch AO, 4-ch DO Expansion Module

25-12

BAS-3050BAS-3051

8-ch DI, 8-ch DO Expansion Module16-ch DI Expansion Module

25-13

BAS-3060 (New) 8-ch DO Relay Expansion Module 25-14

BACNet Remote I/O ModuleBAS-3018BC (New)BAS-3024BC (New)

8-ch UI BACNet MS/TP Remote I/O Module4-ch UI, 4-ch AO, 4-ch DO BACNet MS/TP Remote I/O Module

25-15

BAS-3050BC (New)BAS-3051BC (New)

8-ch DI, 8-ch DO BACNet MS/TP Remote I/O Module16-ch DI BACNet MS/TP Remote I/O Module

25-16

BAS-3060BC (New) 8-ch DI, 8-ch DO Relay BACNet MS/TP Remote I/O Module 25-17

WebLink & WebView PlatformsWebLink-2170 Web-enabled Communication Gateway 25-18

WebView-660E 5.7" Web-enabled HMI 25-19

WebView-1070 10.4" Web-enabled HMI 25-20

WebView-1261 12.1" Web-enabled HMI with AMD LX800 25-21

WebView-1270 12.1" Web-enabled HMI with Intel Celeron M 25-22

Building Automation Systems 25-2

Empower BA Systems with Open and Web-enabled TechnologiesSystem Overview Advantech offers complete Web-enabled Building Automation Systems, ranging from Facility Monitoring & Control System and Energy Saving System to Video Surveillance Systems. Adopting open building networking standards - Modbus, BACnet, LonWorks and up to date information technology – open database management, and IE browser interface allows building facilities to be integrated to form an complete BA system. Moreover, Advantech Building Energy Management System software (BEMS) recieves, stores and analyzes energy consumption patterns to enact peak-shaving, thus saving high utility rate charges.

Advantech Web-enabled BAS Architecture

Web-enabled BAS HMI/SCADA SoftwareView, Control, Configure and Administer Software RemotelyAdvantech WebAccess enables engineers, integrators and vendors with the ability to support their systems remotely over an intranet or the Internet using an ordinary web browser.

Distributed Architecture SCADA nodes run independent of any other node. Each SCADA node communicates to automation equipment using communication driver supplied with WebAccess.

Central Database ServerThe project node is a centralized database server of configuration database and configurable process database through ODBC interface.

Redundant SCADA & COM PortsAssure continuous, reliable communications to automation equipment.

Integration with LonWorks LNS and BACnet IP DevicesWeAccess pre-built “parameters” are template to configure LonWorks, BACNet IP communications which are open standards of building automation.

Energy Management Advantech BEMS is a browser-based energy profiling tool designed to help manage Building Automation applications. Users can trend and analyze energy data and depending on the combination of values and reports selected, identify correlations between building energy consumption patterns and equipment usage to develop improved processes and profiles.

Web-enabled DDC ControllersAdvantech Web-enable DDC controllers are powerful in the industry. They provide stand-alone operation, running DDC control programs, schedules, and issuing their own alarms and events. In addition, engineers can remotely upload, download DDC programs as well as service and maintenance.

Web-enabled HMI Advantech's WebView is a web-based HMI and SCADA platform. All of the features are available through a browser, including animated graphic displays, trends, alarms, schedules and more.

Web-enabled Communication Gateways Advantech WebLink offers communication gateways with abundant device drivers for integration with third party devices such as PLC.

www.advantech.com/productsOnline Download 25-3

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

The facility management system allow control of :

� Chiller Plants � Water Pumps � Boiler � Cooling Towers � Heat Pumps � Small to large Air Handler Unit (AHU) � Makeup Air Unit (MAU) for Cleaning

room � Environment Monitoring System

(Temperature, Humidity, CO2 ...etc) � Other Facility Control/Monitoring

Applications such as Power, Lighting,...etc

For facility control applications like chiller plant control, water pump control and cooling tower control, the BAS-3000 system with BASPro programming tool can easily and flexibly tailor DDC control strategy.

PowerView is a complete advanced digital surveillance system. Designed to meet the requirements of modern security. High compression rate and image quality, real-time video plus audio recording, and monitoring, make it a dependable first choice for professionals needing an all-in-one state of the art solution that is ready for continuous 24-hour operation in large networks with centralized control.

Facility Monitoring and Control System Energy Saving System

Video Surveillance

Advantech BEMS analyzes energy usage and analyzes, helps save energy costs. Additionally, it provides the following features:

� Receive, store and analyze metering and sensor data to optimize energy usage

� Provides powerful analysis and reporting tools for exploring cost reduction opportunities

� Automates cost allocation and supports utility bill validation

� Demand limit control

Advantech BAS Solution Framework

Building Automation Systems 25-4

BAS-3000 I/O Module Selection Guide

Model Name BAS-3018/ BAS-3018BC

BAS-3024/ BAS-3024BC

BAS-3050/ BAS-3050BC

BAS-3051/ BAS-3051BC

BAS-3060/ BAS-3060BC

Description8-ch UI Expansion

Module/ 8-ch UI BACNet MS/TP

Remote I/O Module

4-ch UI, 4-ch AO, 4-ch DO Expansion Module/ 4-ch UI, 4-ch AO, 4-ch

DO BACNet MS/TP Remote I/O Module

8-ch DI, 8-ch DO Expansion Module/ 8-ch DI, 8-ch DO BACNet MS/TP

Remote I/O Module

16-ch DI Expansion Module/

16-ch DI BACNet MS/TP Remote I/O Module

8-ch DO Relay Expansion Module/

8-ch DO Relay BACNet MS/TP Remote I/O

Module

PowerInput 24 VDC, 24 VAC 24 VDC, 24 VAC 24 VDC, 24 VAC 24 VDC, 24 VAC 24 VDC, 24 VAC

Consumption 3 W @ 24 VDC 4 W @ 24 VDC 3 W @ 24 VDC 3 W @ 24 VDC 3 W @ 24 VDC

Universal Input

Number of Inputs 8 4 - - -

Resolution 16-bit 16-bit - - -

Sampling Rate 10 Hz 10Hz - - -

Voltage Input 0~10 V 0~10 V - - -

Current Input 0~20 mA 4~20 mA

0~20 mA 4~20 mA - - -

Direct sensor input

RTD PT-100, PT-1000, Thermister 3K, 10K

PT-100, PT-1000 RTD, Thermister 3K, 10K - - -

As Digital Input Yes Yes - - -

Analog Output

Number of Outputs - 4 - - -

Resolution - 12-bit - - -

Voltage Output - 0~10 V - - -

Current Output - 0~20 mA 4~20 mA - - -

Digital Input

Number of Inputs - - 8 16 -

Logic High - - Close Close -

Logic Low - - Open Open -

As Counter input - - 2 ch, 1 KHZ 2 ch, 1 KHZ -

Digital Output

Number of Outputs - 4 8 - 8

Type - Source Source - Power relay (Form A)

Rated Load Voltage - 10 - 35 VC, 1 A

(Per Channel)10 - 35 VC, 1 A (Per Channel) - AC: 5 A @ 300 V

DC: 5 A @ 30 V

As PWM output - 2 ch 2 ch 2 ch

PWM Periodmin - 1 sec. 1 sec. - 1 sec.

PWM Pulse Widthmin - 0.1 sec. 0.1 sec. - 0.5 sec.

Isolation 3000 VDC 3000 VDC 3000 VDC 3000 VDC 500 VDC

CommunicationChannel 1 1 1 1 1

Type RS-485 RS-485 RS-485 RS-485 RS-485

Protocol

Expansion module

Local Bus (BAS-3018)

Local Bus (BAS-3024)

Local Bus (BAS-3050)

Local Bus (BAS-3051)

Local Bus (BAS-3060)

BACnet Remote IO

MS/TP server (BAS-3018BC)

MS/TP server (BAS-3024BC)

MS/TP server (BAS-3050BC)

MS/TP server (BAS-3051BC)

MS/TP server (BAS-3060BC)

Page 25-12/25-15 25-12/25-15 25-13/25-16 25-13/25-16 25-14/25-17

www.advantech.com/productsOnline Download 25-5

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

WebView Selection Guide

Model Name WebView-1270 WebView-1261 WebView-1070 WebView-660E

CPU Intel Celeron 1 GHz AMD LX800 500 MHz Intel Celeron M 1 GHz AMD Geode LX800, 500 MHZ

Memory 512 MB DDR2 SDRAM 256 MB DDR SDRAM (up to 1 GB DDR SDRAM) 512 MB DDR SDRAM 256 MB SO-DIMM DDR

SDRAM

LCD Display

Type SVGA TFT LCD SVGA TFT LCD SVGA TFT LCD TFT LCD

Size 12.1" 12.1" 10.4" 5.7"

Max. Resolution 800 × 600 800 × 600 800 × 600 640 × 480

Max. Colors 262 K 262 K 260 K 262 K

Luminance (cd/m2) 350 340 400 220

View Angle (H/V°) 140/120 100/60 140/110 140/100

Backlight Life (hrs) 50000 50000 50000 50000

Touchscreen 8-wire, analog resistive 8-wire, analog resistive 8-wire, analog resistive 4-wire, analog resistive

Network (LAN) 2 × 10/100Base-T 1 × 10/100Base-T 1 × 10/100Base-T 1 × 10/100/1000Base-T 1 × 10/100Base-T

I/O Ports

1 × PS/2 4 × Serial Ports (3 × RS-232

and 1 × RS-232/485/422) 4 × USB 2.0 1 × MIC in

1 × Line out

1 × PS/2 4 × Serial Ports (3 × RS-232

and 1 × RS-232/485/422) 1 × Parallel Port

2 × USB 2.0

1 × PS/2 3 × Serial Ports (2 × RS-232

and 1 × RS-232/485/422) 2 × USB 2.0

2 × Serial Ports (1 × RS-232 and 1 × RS-232/485/422)

CompactFlash 512 MB Compact Flash 512 MB Compact Flash 512 MB Compact Flash 512 MB Compact Flash

Power Input Voltage 18 ~ 32 VDC 18 ~ 32 VDC 18 ~ 32 VDC 18 ~ 32 VDC

Dimensions (W × H × D) 311 × 237 × 52.3 mm (12.24" × 9.33" x 2.06")

311 × 237 × 50 mm (12.24" × 9.33" x 1.97")

286 × 226 × 58 mm (11.26" × 8.9" × 2.28")

195 × 148 × 44.4 mm (7.68" × 5.83" × 1.75")

Net Weight 3.3 kg (7.28 lbs) 2.2 kg (4.85 lbs) 3.5 kg (7.72 lbs) 0.8 kg (1.76 lbs)

Front Cover Al-Mg and ABS Al-Mg and ABS Die-Casting Aluminum alloy ABS and ABS + PC

Operating Temperature 0 ~ 50° C (32 ~ 122° F) 0 ~ 50° C (32 ~ 122° F) 0 ~ 50° C (32 ~ 122° F) 0 ~ 50° C (32 ~ 122° F)

Ingress Protection (Front Panel) NEMA4, IP65 NEMA4, IP65 NEMA4, IP65 NEMA4, IP65

Certifications BSMI, CCC, CE, FCC BSMI, CCC, CE, FCC BSMI, CCC, CE, FCC BSMI, CCC, CE, FCC

Operating System Windows CE 5.0 Windows CE 5.0 Windows CE 5.0 Windows CE 5.0

Build-in WebAccess

I/O Tag Numbers 600 600 600 600

Internal Tag Numbers 600 600 600 600

Web Clients 2 2 2 2

Alarm Logging 1000 1000 1000 1000

Action Logging 1000 1000 1000 1000

Number of Graphic Pages 100 100 100 100

Macro Key Yes Yes Yes Yes

Local Script Yes Yes Yes Yes

Variables per Graphic Page 255 255 255 255

Number of data logging 50 Tags 50 Tags 50 Tags 50 Tags

Recipes per Project 100 100 100 100

Units per Recipe 100 100 100 100

Items per Unit 999 999 999 999

Holiday Configuration

Groups10 10 10 10

Time Zone Groups 99 99 99 99

Device Loop Groups 99 99 99 99

Equipment Groups 99 99 99 99

Page 25-22 25-21 25-20 25-19

WebView-1261

Building Automation Systems 25-6

Features

Browser-based HMI/SCADA Software

Advantech WebAccess

� View, control, configure system remotely over Internet using web browser � Free unlimited client licenses � Distributed SCADA architecture � Central database server � Redundant SCADA and COM ports � Supports dynamic DNS services � Acts as an OPC server and OPC client � Support LonWorks LNS and BACnet IP � Video and audio integration � Integrate flash animations with action scripts, TCL scripts and fscommand � Calendar schedule control � Global access to alarms & data � Email alarms, reports and messages

IntroductionAdvantech WebAccess is browser-based software package for human-machine interfaces (HMI), and supervisory control and data acquisition (SCADA). All the features found in conventional HMI and SCADA software packages are available in an ordinary browser including Animated Graphics Displays, Real-time Data Control, Trends, Alarms and Logs. WebAccess is based on standard internet architecture, its basic component includes:1. SCADA Node: It communicates in real-time with automation equipments and control the equipment via Serial, Ethernet or proprietary communications. The SCADA Node can

provide supervisory control and data acquisition functions, includes supplying communication driver (Modbus, PLC, and I/O systems), real-time and historical trending. It also can monitor and log alarm and event. The SCADA Node has its own run-time database and all graphics.

2. Project Node: It is the developing platform for WebAccess, and all system configuration and project development is implemented on the Project Node. It is a web server for all Client and SCADA node to connect with.

3. Client: Through an ActiveX control inside Internet Explorer Web browser, it has the ability to monitor and control the SCADA Node simultaneously. The Client connects to the Project Node only to get the address of the SCADA Node. The Client then communicates directly with the SCADA Node using proprietary communications over a TCP/IP network connection. Data is displayed in real-time with dynamically updated graphics, and user can monitor real-time and historical trending with alarm record. Besides, user can acknowledge alarms and change setpoints, status and other data.

4. Thin Client: The Thin Client interface is intended for use with PDA, Pocket PCs and Handheld computers. Other ASP enabled web browsers can view the thin client graphics. Thin client interface supplies static snapshots of dynamic graphics as GIFs and JPEGs. No plug-in or ActiveX control is required. Real-time data, alarms and changes to data are through a text type interface. Thin client has been tested with the iPAQ series of pocket PCs. The thin client does not communicate with the SCADA node directly. The thin client communicates directly to the Project Node (Web Server).

FeaturesWeb Browser Client to View and Control Using a standard Web browser, users can view and control automation equipment used in industrial, manufacturing, process and building automation systems. Data is displayed to users in real-time with dynamically updated graphics using full-motion animation.

Powerful Remote Diagnose and Maintenance Functionality The unique feature, which distinguishes WebAccess from the competition, is that all engineering project, configuration, graphics building (DRAW) and software management (download, start and restart remote nodes) is performed using a standard Web browser. If there is any troubleshooting needed, no matter wherever the operator is located, he can use the standard internet to operate the system. This can significantly increase the efficiency of maintenance operation and reduce the maintenance cost.

Vector-based GraphicsWebAccess features Vector-based graphics. Vector-based graphics provide smaller file sizes and faster download. Because Vector-based graphics use mathematic algorithm to save image, its file size is much smaller than Bitmap graphics. Therefore it is much faster to transfer Vector-based graphics on internet. Besides, WebAccess features user interface self-adaptive adjustment technology, no matter how user adjust the screen ratio of monitor, WebAccess can ensure all the user interface will be displayed on the screen. When the resolution of screen increases, the display performance will also become better respectively.

Import BMP, JPEG and GIFExcept Vector-based graphics, WebAccess also supports the most popular BMP, JPEG and GIF Bitmap format file, and user can zoom in or zoom out these image as well as animation configurations. WebAccess also provides build-in animation image libraries.

Import AutoCAD DXFWebAccess is similar to AutoCAD, which allows engineers familiar with AutoCAD to get comfortable with WebAccess in short amount of time. Users can import DXF format files into WebAccess, and can edit imported data and choose animation configurations.

Scripts Using TCL, Java Script or VB ScriptScripts in WebAccess use the open source programming languages TCL, Java Script or VB Script and allow users to develop customized actions, calculations and reports.

Scheduler The Scheduler provides control and changes setpoint status based on time and date. Lights, Fans, and HVAC equipment are turned on and off based on the time, day of week and date. The Scheduler is also used in process control and manufacturing applications. All these schedule configurations can be modified remotely through internet.

www.advantech.com/productsOnline Download 25-7

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

WebAccess

Distributed ArchitectureSCADA nodes run independent of any other node. Each SCADA node communicates to automation equipment using communication driver supplied with WebAccess.

Central Database ServerThe project node is a centralized database server of configuration database and configurable process database through ODBC interface.

Redundant SCADA & COM PortsAssure continuous, reliable communications to automation equipment.

DDE, OPC and ODBC InterfaceMicrosoft communications standards to exchange data with your automation equipment, spreadsheets, databases or 3rd party software.

Historical and Real-time Trend, Data and Centralized LogsEach tag is logged to a separate file on the SCADA node, and user can view the real-time and historical data from the historical trend. Besides, new tags can be added to a historical trend display without losing history of other tags. User can decide the background, color and type of real-time and historical trend display. Real-time data, alarms, event from all nodes are logged to central ODBC database.

Alarm Each tag comes with multiple alarm type. Users don’t need to use extra program for the alarm, instead, users only need to configure the alarm type (HH, H, L, LL, DEV and ROC) for each tag. The alarm for analog tag also supports Deadband. WebAccess features alarm filter, alarm grade, alarm sorting, alarm historical record, and alarm value on-line adjustment.

Recipe Function Recipes provide an easy method for operators and users to change the value of hundreds of settings.

Enhanced SecurityUsing the Area of Responsibility concept to restrict changes to data, users can be assigned various privileges to restrict display and data access.

HTML ReportsGenerate HTML Reports using menu-based queries of centralized ODBC Logs based on date, time, tag, including: analog and discrete data, System Log, Alarm Log and Operator Action Log. Copy and paste these html reports to EXCEL, Word, etc.

Excel Import/ExportUsers can create and modify Tag in a spreadsheet using copy, paste, edit and other Excel tools. Databases can be imported from other HMI packages.

Email Alarms, Reports and MessagesWebAccess will e-mail alarms, reports, and logs to pagers and PCs. Alarms can be acknowledged using the reply mail.

Customized Functional ToolboxUse Microsoft Icon files to build tool bars. These can be imported from any application. Or, animate Toolbars buttons built using DRAW to provide flashing, color change, text changes or any animation.

Ordering Information � WAP-150-W70E WebAccess Win32 Professional V7.0 150 Tag (Eng.) � WAP-300-W70E WebAccess Win32 Professional V7.0 300 Tag (Eng.) � WAP-600-W70E WebAccess Win32 Professional V7.0 600 Tag (Eng.) � WAP-1200-W70E WebAccess Win32 Professional V7.0 1200 Tag (Eng.) � WAP-5000-W70E WebAccess Win32 Professional V7.0 5000 Tag (Eng.) � WAP-20K-W70E WebAccess Win32 Professional V7.0 20K Tag (Eng.) � WAP-99K-W70E WebAccess Win32 Pro V6.0 99K (Eng.) � WAP-150-T70E WebAccess Win32 Professional V7.0 150 Tag (Chn.) � WAP-300-T70E WebAccess Win32 Professional V7.0 300 Tag (Chn.) � WAP-600-T70E WebAccess Win32 Professional V7.0 600 Tag (Chn.) � WAP-1200-T70E WebAccess Win32 Professional V7.0 1200 Tag (Chn.) � WAP-5000-T70E WebAccess Win32 Professional V7.0 5000 Tag (Chn.) � WAP-20K-T70E WebAccess Win32 Professional V7.0 20K Tag (Chn.) � WAP-99K-T70E WebAccess Win32 Pro V6.0 99K (Chn.)

Building Automation Systems 25-8

Features

Advantech BEMS Building Energy Management Software

� Browser-based energy management system � Rich charts to view energy consumption from various perspectives � Supports flexible report functions � Various data analysis functions to generate energy consumption patterns � Advanced demand limit control

IntroductionAdvantech BEMS is a set of advanced Web-based energy management system aiming at helping customers with energy consumption management. This system can collect energy consumption data of different classifications and sub-items. Customers can create energy management projects and groups to manage these data according to their requirements. Various charts and its statistical analysis function can help customers to find out an optimized energy-saving strategy.

SpecificationsEnergy Profile Each management group provides energy consumption profile on a hourly, daily, monthly and yearly basis, and thus helping customers to know its own energy consumption situation and finding out the abnormal value. All kinds of related energy consumption indicators, such as Energy Use Intensity (EUI) provide data support to energy consumption statistic and energy audit. Some reference functions, such as temperature and humidity help to analyze the correlation between consumption data and environment data.

Energy RankingEnergy consumption ranking during different time periods helps to find out the energy efficiency device units.

Energy ComparisonEnergy comparison between different energy management groups during different time periods.

Average Daily ProfileAverage daily profile per 15 minutes on each day. It helps customers to know its energy consumption pattern and find out the peak requirement more than expected; therefore customers can refer to it when signing the contract with power company.

Deviation ReportDeviation between energy consumption value and set value during different time periods on any day. The red value represents the increment trend of energy consumption.

Max/Min Value AnalysisMax/Min value during different time periods helps to analyze the relations between energy consumption and time.

Primary Energy ProfileConverts energy consumption to heat (MJ), standard coal, crude oil and coal as well as other primary energy consumption value and their relative CO2 emission value.

Cost ProfileEach management group provides cost profile on a daily, monthly and yearly basis. It calculates the cost based on the data in the energy table and rate structure in order to manage the energy cost. Customers can set an energy consumption benchmark. Set the budget based on the deviation from the actual cost will contribute to the decreasing of the risk in the process of purchasing.

Cost RankingEnergy consumption cost ranking during different time periods helps to find out the max./min. energy efficiency device units.

Statistical ReportStatistics report (Y/M/D) with classification and sub-items allows customers to view clearly the energy consumption and helps them to make a reasonable allocation and use of energy.

Ordering Information � WAP-BEMS-W70E WebAccess Building Energy Management System

Software V7.0 (Eng.) � WAP-BEMS-T70E WebAccess Building Energy Management System

Software V7.0 (Chn.) � WAP-DC-W70E WebAccess Demand Control Software V7.0 (Eng.) � WAP-DC-T70E WebAccess Demand Control Software V7.0 (Chn.)

www.advantech.com/productsOnline Download 25-9

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

Features

BAS-3512BAS-3520

12-ch Web-enabled DDC Controller

20-ch Web-enabled DDC Controller

SpecificationsGeneral � Dimension (W x H x D) 176 x 120 x 44 mm (6.93" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 10 W @ 24 VDC

� Real-time Clock Yes � Watchdog Timer Yes � I/O Isolation Protection 3,000 VDC

Hardware � CPU 32-bit CPU 312 MHz � Flash Memory 32 MB � RAM 64 MB SDRAM � Battery Backup SRAM 512 KB

Communication � LAN 1 x 10/100Base-T (RJ-45) � RS-485 1 (isolated) � Communication Modbus/TCP, Modbus/RTU

Protocol

Universal Input (BAS-3520 only) � Channels 4 � Resolution 16-bit � Sample Rate 10 Hz (Total) � Accuracy ±0.1% of FSR (Voltage, Current) � Type and Range

Analog Input 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA, Pt-100 RTD, Pt-1000 RTD, Thermistor (3 k, 10 k) Digital Input Logic High: Close (Dry Contact) Logic Low: Open

� Over Voltage Protection ±35 V � Span Drift ±25 ppm/° C � Zero Drift ±6 μV/° C

Analog Output (BAS-3520 only) � Channels 4 � Resolution 12-bit � Accuracy ±0.1% of FSR � Range 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA

Digital Input � Channels 8 � Dry Contact Logic High: Close

Logic Low: Open � Supports 1 kHz Counter Input (2 channels) � Supports 1 kHz Frequency Input (2 channels)

Digital Output � Channels 4 (Source Type) � Vcc: 10 ~ 35 VDC, Current: 1 A (per channel) � PWM output (2 channels)

Minimum Period 1 second (for PWM output)Minimum Pulse Width 0.1 second (for PWM output)

LCM Operation Unit (Optional) � 2 line x 8 char, backlit LCD � 5 button keypad � Hot swap capable

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) (with airflow) � Storage Temperature -20 ~ 80° C (-4 ~ 176° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3512-AE 12-ch Web-enabled DDC Controller � BAS-3520-AE 20-ch Web-enabled DDC Controller � BAS-3595-AE LCM operation unit (Optional)

� Standalone programmable controller � BASPro programming software provides BA domain function (scheduler,

HVAC calculation, sequence…) � Auto-tuning PID control � Calendar schedule control � Alarm and event notifications � Provides RS-485 to connect with remote I/O devices � Up to 3 local I/O expansion modules � Remote programming and maintenance through Ethernet � LCM display (optional)

IntroductionBAS-3512/3520 is a standalone programmable controller specially designed for building automation (BA) applications. Designed as a typical DDC (Direct Digital Controller), BAS-3512/3520 delivers various of onboard I/O including universal input, analog output, digital input and digital output, providing flexible options to satisfy versatile application requirements. It also features powerful BASPro programming tool for engineers to quickly develop their application. BASPro delivers many function blocks suitable for BA application, such as scheduler, HVAC calculation, sequential control, PID control, alarm, and event. Its compact size makes it an ideal solution to fulfill BA installation environment. The I/O expansion modules (BAS-3018, BAS-3024, BAS-3050, BAS-3051 and BAS-3060) provide more I/O points and make the system a scalable solution.

BAS-3512 BAS-3520����COMPLIANT

����������

Building Automation Systems 25-10

Features

BAS-3520C 20-ch Web-enabled Chiller DDC Controller

SpecificationsGeneral � Dimension (W x H x D) 176 x 120 x 44 mm (6.93" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 10 W @ 24 VDC

� Real-time Clock Yes � Watchdog Timer Yes � I/O Isolation Protection 500 VDC For Relay Digital Output

3000 VDC For Universal InputHardware � CPU 32-bit CPU 312 MHz � Flash Memory 32 MB � RAM 64 MB SDRAM � Battery Backup SRAM 512 KB

Communication � LAN 1 x 10/100Base-T (RJ-45) � RS-485 1 (isolated) � Communication Modbus/TCP, Modbus/RTU

Protocol

Universal Input � Channels 12 � Resolution 16-bit � Sample Rate 10 Hz (Total) � Accuracy ±0.1% of FSR (Voltage, Current) � Type and Range

Analog Input 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA, Pt-100 RTD, Pt-1000 RTD, Thermistor (3 k, 10 k) Digital Input Logic High: Close (Dry Contact) Logic Low: Open

� Over Voltage Protection ±35 V � Span Drift ±25 ppm/° C � Zero Drift ±6 μV/° C

Digital Output � Channels 8 ( Form A) � Breakdown Voltage 1000 VAC (50/60 Hz) � Contact Rating AC: 5 A @ 250 V

(Resistive) DC: 5 A @ 30 V � Initial Insulation 1G ohm min @ 500 VDC

Resistance � Relay Off Time 5.6ms (Typical) � Relay On Time 5.6ms (Typical) � Maximum Operating 6 operations/min (@ related load)

Speed � PWM Output (2 channels)

Minimum Period 1 second (for PWM output)Minimum Pulse Width 0.5 second (for PWM output)

LCM Operation Unit (Optional) � 2 line x 8 char, backlit LCD � 5 button keypad � Hot swap capable

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) (with airflow) � Storage Temperature -20 ~ 75° C (-4 ~ 167° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3520C-AE 20-ch Web-enabled Chiller DDC Controller � BAS-3595-AE LCM operation unit (Optional)

� Standalone programmable controller � BASPro programming software provides BA domain function (scheduler,

HVAC calculation, sequence…) � Auto-tuning PID control � Calendar schedule control � Alarm and event notifications � Provides RS-485 to connect with remote I/O devices � Up to 3 local I/O expansion modules � Remote programming and maintenance through Ethernet � LCM display (optional)

IntroductionBAS-3520C is a standalone programmable controller specially designed for HVAC Chiller Control applications. Designed as a typical DDC (Direct Digital Controller), BAS-3520C delivers various of onboard I/O including universal input, and digital output, providing flexible options to satisfy versatile application requirements. It also features powerful BASPro programming tool for engineers to quickly develop their application. BASPro delivers many function blocks suitable for BA application, such as scheduler, HVAC calculation, sequential control, PID control, alarm, and event. Its compact size makes it an ideal solution to fulfill chiller plant control applications. The I/O expansion modules (BAS-3018, BAS-3024, BAS-3050, BAS-3051 and BAS-3060) provide more I/O points and make the system a scalable solution.

NEW

����COMPLIANT

����������

www.advantech.com/productsOnline Download 25-11

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

Features

BASPro BAS-3000 DDC Programming Tool

� Graphical programming environment � Supports remote download and maintenance by Ethernet � Pre-defined function blocks to save development time � Scheduler and sequential control � BA HVAC calculation � Auto-tuning PID and RAMP/SOAK control algorithm � Local alarms and event notifications

IntroductionBASPro is a programming software package suitable for building automation application, perfectly integrating with BAS-3500 Series DDC Controller (Direct Digital Controller). BASPro features rich function blocks like mathematical calculation, data conversion, logic operation, alarm, event and timer, and control algorithm (PID, Ramp, ON/OFF switch control). Moreover, BASPro also provides many BA domain function blocks, such as scheduler, HVAC calculation and sequential control, which are commonly used in building applications. Developers can benefit from saving development time by the function blocks. Engineers can develop applications on their computer. After the application program is complete, it can be download to the BAS-3500 series through Ethernet. Then BAS-3500 series becomes a standalone controller since it can execute the program by itself. Besides, BASPro delivers simulation function that you can observe the program execution situation before the program is downloaded to the BAS-3500 series.

FeaturesGraphical Programming EnvironmentBASPro features completely graphical programming environment, making the programming for variety of control applications become very easy and convenient. It takes a very short time for the developers to learn the software tool. Developers can benefit not only the short time of developing program also the convenience of troubleshooting and debugging, so the development and maintenance cost can be reduced.

Supports Remote Download and MaintenanceBASPro supports Ethernet communication, which can deliver remotely downloading and uploading control logic programs. After the program is downloaded to the remote target (BAS-3500 DDC controller), engineers can easily use another computer to maintain the system by Ethernet. Engineers are able to control and monitor the project program running on the target device, and even can modify the program remotely.

Powerful and Flexible Function BlocksThere can be up to 30 control pages per controller, each page supports up to 50 function blocks (max.4 PID blocks per page, total 16 PID per controller). BASPro delivers plenty of built-in function blocks, integrating many control and calculation functions into one simple block. Developers don't need to write program code for the control function blocks by themselves, and simply uses these function blocks to complete their applications. It helps greatly decreasing the development time. Below are some lists of the function blocks:

� Mathematical CalculationAddition, subtraction, multiplication, division, exponentiation, square root operation, logarithm operation, natural logarithm operation, absolute operation, maximum number, minimum number, scale conversion.

� Logic OperationBoolean calculation (such as AND, OR, NOT, NAND, NOR, XOR, ...), value comparison, trigger function, etc.

� Timer/CounterCreate time delay, count event, timing measurement, pulse, etc.

� Data ConversionConversion for various data type, such as convert float type data to integer data type, convert boolean data to numeric data, combine byte to word, unpack byte to bit, etc.

� Control and AlarmPID control, Ramp/Soak, ON/OFF switch control, alarm setting (H, L, HH, LL alarm), etc.

� ScheduleProvide schedule control blocks to implement multiple purpose scheduling task controls with the very friendly configuration edit page, such as Holiday, Weekly and Device Group.

� HVAC Calculation Dew Point, Vapor Pressure, WetBulb, and Enthalpy Calculation.

� Sequential ControlProvide the multiple stage control function for 4 or 8 stage control units. It will turn on or turn off the unit device according to PV, SP, deadband and control mode paramters. The sequential order includes first in last out, first in first out, depending on the time length of operation, etc.

� Communication with External Device by Modbus Protocol

Note: This software is only available as a bundle with BAS-3512, BAS-3520, and BAS-3520C

Building Automation Systems 25-12

Features

SpecificationsGeneral � Dimension (W x H x D) 120 x 120 x 44 mm (4.72" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 3 W @ 24 VDC (BAS-3018)/4 W @ 24 VDC (BAS-3024) � Watchdog Timer Yes � Communication Local Bus (Connect to BAS-3520/3512/3520C)

RS-485 (Standalone as Remote IO Device)

Universal Input � Channels 8 (BAS-3018)/4 (BAS-3024) � Resolution 16-bit � Sample Rate 10 Hz (Total) � Accuracy ±0.1% of FSR (Voltage, Current) � Type and Range Analog Input: 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA,

Pt-100/1000, RTD, Thermistor (3 k, 10 k) Digital Input Logic High: Close (Dry Contact) Logic Low: Open

� Over Voltage Protection ±35 V

Analog Output (BAS-3024 only) � Channels 4 � Resolution 12-bit � Accuracy ± 0.1% of FSR � Range 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA

Digital Output (BAS-3024 only) � Channels 4 (Source Type) � Vcc 10 ~ 35 VDC, Current: 1 A (per channel) � PWM Output (2 channels)

Minimum Period 1 second (for PWM output)Minimum Pulse Width 0.1 second (for PWM output)

BAS-3018BAS-3024

8-ch UI Expansion Module

4-ch UI, 4-ch AO, 4-ch DO Expansion Module

����COMPLIANT

����������

BAS-3018 BAS-3024

� 24 VDC or 24 VAC input � Universal input supports 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA, RTD, Thermistor

(3K, 10K), and digital input � Analog output supports 0 ~ 10 V, 0 ~ 20 mA, and 4 ~ 20 mA (BAS-3024 only) � Supports PWM output (BAS-3024 only)

IntroductionBAS-3018/BAS-3024 expansion I/O modules can be stacked on the DDC controller, or can serve as remote standalone I/O modules through an RS-485 network. These expansion I/O modules add both scalability and flexibility to Advantech BAS-3000 solutions. Like the DDC, I/O expansion modules can be programmed using the BASPro programming tool.

Protection � Isolation Voltage 3,000 VDC

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) � Storage Temperature -20 ~ 80° C (-4 ~ 176° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3018-AE 8-ch UI Expansion Module � BAS-3024-AE 4-ch UI, 4-ch AO, 4-ch DO Expansion Module

www.advantech.com/productsOnline Download 25-13

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

Features

BAS-3050 BAS-3051

BAS-3050BAS-3051

8-ch DI, 8-ch DO Expansion Module

16-ch DI Expansion Module

����COMPLIANT

����������

� 24 VDC or 24 VAC input � 3000 VDC isolation protection � Supports 1 kHz counter input and 1 kHz frequency input (2 channels) � Supports PWM output (2 channels) (BAS-3050 only)

IntroductionBAS-3050/BAS-3051 expansion I/O modules can be stacked on the DDC controller, or can serve as remote standalone I/O modules through an RS-485 network. These expansion I/O modules add both scalability and flexibility to Advantech BAS-3000 solutions. Like the DDC, I/O expansion modules can be programmed using the BASPro programming tool.

SpecificationsGeneral � Dimension (W x H x D) 120 x 120 x 44 mm (4.72" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 3 W @ 24 VDC

� Watchdog Timer Yes � Communication Local Bus (Connect to BAS-3520/3512/3520C)

RS-485 (Standalone as Remote IO Device)

Digital Input � Channels 8 (BAS-3050)/16 (BAS-3051) � Dry Contact Logic High Close

Logic Low Open Support 1 kHz Counter Input (2 channels) Support 1 kHz Frequency Input (2 channels)

Digital Output (BAS-3050 only) � Channels 8 (Source Type) � Vcc 10 ~ 35 VDC, Current: 1 A (per channel) � Supports PWM Output (2 channels)

Minimum Period 1 second (for PWM output) Minimum Pulse Width 0.1 second (for PWM output)

Protection � Isolation Voltage 3,000 VDC

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) � Storage Temperature -20 ~ 80° C (-4 ~ 17° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3050-AE 8-ch DI, 8-ch DO Expansion Module � BAS-3051-AE 16-ch DI Expansion Module

Building Automation Systems 25-14

Features

BAS-3060 8-ch DO Relay Expansion Module

NEW

����COMPLIANT

����������

� 24 VDC or 24 VAC input � 500 VDC isolation protection � Power relay output � Supports PWM output (2 channels)

IntroductionBAS-3060 expansion I/O modules can be stacked on the DDC controller, or can serve as remote standalone I/O modules through an RS-485 network. These expansion I/O modules add both scalability and flexibility to Advantech BAS-3000 solutions. Like the DDC, I/O expansion modules can be programmed using the BASPro programming tool.

SpecificationsGeneral � Dimension (W x H x D) 120 x 120 x 44 mm (4.72" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 3 W @ 24 VDC

� Watchdog Timer Yes � Communication Local Bus (Connect to BAS-3520/3512/3520C)

RS-485 (Standalone as Remote IO Device)

Digital Output (Relay Output) � Channels 8 � Digital Output (Relay) Isolation Voltage: 500 VDC

Universal Input Isolation Voltage: 3000 VDC

� Supports PWM Output (2 channels) Minimum Period 1 second (for PWM output) Minimum Pulse Width 0.5 second (for PWM output)

� Breakdown Voltage 1000 VAC (50/60 Hz) � Contact Rating AC: 5 A @ 250 V

(Resistive) DC: 5 A @ 30 V � Initial Insulation 1G ohm min @ 500 VDC

Resistance � Relay Off Time 5.6 ms

(Typical) � Relay On Time 5 ms

(Typical) � Maximum Operating 6 operations/min (@ related load)

Speed

Protection � Isolation Voltage 500 VDC

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) � Storage Temperature -20 ~ 80° C (-4 ~ 176° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3060-AE 8-ch DO Relay Expansion Module

www.advantech.com/productsOnline Download 25-15

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

Features

SpecificationsGeneral � Dimension (W x H x D) 120 x 120 x 44 mm (4.72" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 3 W @ 24 VDC (BAS-3018BC)/4 W @ 24 VDC (BAS-3024BC)

� Watchdog Timer Yes � Communication RS-485

Universal Input � Channels 8 (BAS-3018BC)/4 (BAS-3024BC) � Resolution 16-bit � Sample Rate 10 Hz (Total) � Accuracy ±0.1% of FSR (Voltage, Current) � Type and Range Analog Input: 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA,

Pt-100/1000, RTD, Thermistor (3 k, 10 k) Digital Input Logic High: Close (Dry Contact) Logic Low: Open

� Over Voltage Protection ±35 V

Analog Output (BAS-3024BC only) � Channels 4 � Resolution 12-bit � Accuracy ± 0.1% of FSR � Range 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA

Digital Output (BAS-3024BC only) � Channels 4 (Source Type) � Vcc 10 ~ 35 VDC, Current: 1 A (per channel) � PWM Output (2 channels)

Minimum Period 1 second (for PWM output)Minimum Pulse Width 0.1 second (for PWM output)

BAS-3018BCBAS-3024BC

8-ch UI BACNet MS/TP Remote I/O Module4-ch UI, 4-ch AO, 4-ch DO BACNet MS/TP Remote I/O Module

NEW

����COMPLIANT

����������

BAS-3018BC BAS-3024BC

� 24 VDC or 24 VAC input � 3000 VDC isolation protection � Universal input supports 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA, RTD, Thermistor

(3K, 10K), and digital input (Dry contact) � Analog output supports 0 ~ 10 V, 0 ~ 20 mA, and 4 ~ 20 mA

(BAS-3024BC only) � Supports PWM output (BAS-3024BC only) � BACNet MS/TP Server � Supports Master and Slave mode

IntroductionBAS-3018BC/BAS-3024BC can serve as BACNet MS/TP remote I/O modules through an RS-485 network to be integrated with worldclass BACNet DDC Controller such as Johnson Controls, Honeywell, ... etc.

Protection � Isolation Voltage 3,000 VDC

BACNet Profile � Protocol BACNet MS/TP Server � Mode Master and Slave � Device Profile BACnet Smart Sensor (B-SS) � Interoperability DS-RP-B,DS-WP-B,DS-RPM-B,DS-WPM-B Building

Blocks � Objects AI, AO, BO and Device

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) � Storage Temperature -20 ~ 80° C (-4 ~ 176° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3018BC-AE 8-ch UI BACNet MS/TP Remote I/O Module � BAS-3024BC-AE 4-ch UI, 4-ch AO, 4-ch DO BACNet MS/TP Remote I/O

Module

Building Automation Systems 25-16

Features

BAS-3050BC BAS-3051BC

BAS-3050BCBAS-3051BC

8-ch DI, 8-ch DO BACNet MS/TP Remote I/O Module16-ch DI BACNet MS/TP Remote I/O Module

NEW

����COMPLIANT

����������

� 24 VDC or 24 VAC input � 3000 VDC isolation protection � Supports 1 kHz counter input and 1 kHz frequency input (2 channels) � Supports PWM output (2 channels) (BAS-3050BC only) � BACNet MS/TP Server � Supports Master and Slave mode

Introduction BAS-3050BC/BAS-3051BC can serve as BACNet MS/TP remote I/O modules through an RS-485 network to be integrated with worldclass BACNet DDC Controllers such as Johnson Controls, Honeywell, ... etc.

SpecificationsGeneral � Dimension (W x H x D) 120 x 120 x 44 mm (4.72" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 3 W @ 24 VDC

� Watchdog Timer Yes � Communication RS-485

Digital Input � Channels 8 (BAS-3050BC)/16 (BAS-3051BC) � Dry Contact Logic High Close

Logic Low Open Support 1 kHz Counter Input (2 channels) Support 1 kHz Frequency Input (2 channels)

Digital Output (BAS-3050BC only) � Channels 8 (Source Type) � Vcc 10 ~ 35 VDC, Current: 1 A (per channel) � Supports PWM Output (2 channels)

Minimum Period 1 second (for PWM output) Minimum Pulse Width 0.1 second (for PWM output)

Protection � Isolation Voltage 3,000 VDC

BACNet Profile � Protocol BACnet MS/TP Server � Mode Master and Slave � Device Profile BACnet Smart Sensor (B-SS) � Interoperability DS-RP-B,DS-WP-B,DS-RPM-B,DS-WPM-B Building

Blocks � Objects BI, BO, and Device

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) � Storage Temperature -20 ~ 80° C (-4 ~ 176° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3050BC-AE 8-ch DI, 8-ch DO BACNet MS/TP Remote I/O Module � BAS-3051BC-AE 16-ch DI BACNet MS/TP Remote I/O Module

www.advantech.com/productsOnline Download 25-17

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

Features

BAS-3060BC 8-ch DO Relay BACNet MS/TP Remote I/O Module

NEW � 24 VDC or 24 VAC input � 500 VDC Isolation Protection � Power Relay Output � Supports PWM output (2 channels) � BACNet MS/TP Server � Supports Master and Slave mode

Introduction BAS-3060BC can serve asBACNet MS/TP remote I/O modules through an RS-485 nnetwork to be integrated with worldclass BACNet DDC Controllers such as Johnson Controls, Honeywell, ... etc.

SpecificationsGeneral � Dimension (W x H x D) 120 x 120 x 44 mm (4.72" x 4.72" x 1.73") � Enclosure ABS + PC � Power Input 24 VDC/24 VAC

� Power Consumption 3 W @ 24 VDC

� Watchdog Timer Yes � Communication RS-485

Digital Output (Relay Output) � Channels 8 � Supports PWM Output (2 channels)

Minimum Period 1 second (for PWM output) Minimum Pulse Width 0.5 second (for PWM output)

� Breakdown Voltage 1000 VAC (50/60 Hz) � Contact Rating AC: 5 A @ 250 V

(Resistive) DC: 5 A @ 30 V � Initial Insulation 1 G ohm min @ 500 VDC

Resistance � Relay Off Time 5.6 ms

(Typical) � Relay On Time 5 ms

(Typical) � Maximum Operating 6 operations/min (@ related load)

Speed

Protection � Isolation Voltage 500 VDC

BACNet Profile � Protocol BACnet MS/TP Server � Mode Master and Slave � Device Profile BACnet Smart Sensor (B-SS) � Interoperability DS-RP-B,DS-WP-B,DS-RPM-B,DS-WPM-B Building

Blocks � Objects BO and Device

Environment � Operating Temperature -10 ~ 60° C (14 ~ 140° F) � Storage Temperature -20 ~ 80° C (-4 ~ 176° F) � Operating Humidity 20 ~ 95% (Non-condensing) � Storage Humidity 0 ~ 95% (Non-condensing)

Ordering Information � BAS-3060BC-AE 8-ch DO Relay BACNet MS/TP Remote I/O Module

Building Automation Systems 25-18

Features

WebLink-2170 Web-enabled Communication Gateway

Software Specifications � Operating System Windows CE 5.0 � Advantech WinCE WebAccess Communication Gateway:

I/O Tag Number 600Internal Tag Number 600 Web Client 2

� Number of I/O device 64 (max)

Ordering Information � WLINK2170-600-W50E Web-enabled Communication Gateway w/600 I/O tags

� Two RS-232 and two RS-232/422/485 ports with automatic flow control � Two 10/100Base-T RJ-45 ports � Two USB ports � Built-in Windows® CE with Advantech WinCE WebAccess Communication

Gateway � Supports various protocol drivers to communicate with different devices � Multi-thread communication, response time is fast � Configured through web browser � Easy to diagnose and maintain, which helps to reduce maintenance costs � Point transfer between communication devices within one WebLink

SpecificationsGeneral � Dimensions (W x D x H) 255 x 152 x 50 mm (10.04" x 5.98" x 1.97") � Enclosure Aluminum � Mounting Wall � Power Consumption 24 W (Typical) � Power Input Min. 48 W (9 ~ 36 VDC) (e.g +24 V @ 2 A) � Weight 1.6 kg

System Hardware � CPU Celeron M 1 GHz � Keyboard/Mouse 1 x PS/2 � Memory 512 MB DDR DRAM � VGA DB15 VGA connector

Communications � Serial Ports 2 x RS-232, 2 x RS-232/422/485 with DB9 connectors

Automatic RS-485 data flow control � Serial Port Speed RS-232: 50 ~ 115.2 kbps

RS-422/485: 50 ~ 921.6 kbps (Max.) � LAN 2 x 10/100 Base-T RJ-45 ports � USB Ports 2 x USB, UHCI, Rev. 2.0 compliant � Parallel Ports 1 x Parallel Port

Environment � Humidity 95% @ 40° C (non-condensing) � Operating Temperature -10 ~ 50° C (14 ~ 122° F) @ 5 ~ 85% RH. � Shock Protection IEC 68 2-27

50 G @ wall mount, half sine, 11 ms � Vibration Protection IEC 68 2-64 (Random 1 Oct./min, 1hr/axis.)

2 Grms @ 5 ~ 500 Hz

IntroductionAdvantech WebLink-2170 is fanless communication gateway, featuring Celeron® M 1 GHz and rich interfaces (such as serial, USB and LAN). Installed Advantech WinCE WebAccess, WebLink-2170 is a browser-based communication gateway, whose Web Server function increases the flexibility and convenience, and makes the user easy to configure and maintain the system via Internet. With built-in driver, WebLink-2170 can connect with variety of Automation equipment and devices, and get data from them.

����COMPLIANT

����������

www.advantech.com/productsOnline Download 25-19

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

Features

WebView-660E � AMD Geode LX800 processor � 5.7" TFT LCD � Super slim and compact design with plastic housing � Fanless cooling system � NEMA4/IP65 compliant front panel � Built-in Windows® CE 5.0 with Advantech WinCE WebAccess � One CompactFlash® slot � Supports Vector-based graphics � Supports 2 Web Clients � Remote control and monitor by Ordinary IE Browser � 50 tags real time trend and historical trend � Supports calendar scheduler � Import BMP, JPEG, GIF, ACAD DXF

IntroductionAdvantech's WebView-660E is a web-based human-machine interface (HMI) and supervisory control and data acquisition (SCADA) platform. All the features are available in an ordinary Web browser including Animated Graphics Displays, Real-time Data Control, Trends, Alarms and Logs, Scheduler, and more.

5.7" Web-enabled HMI

SpecificationsGeneral � BIOS Award® 4 MB � Certifications BSMI, CCC, CE, FCC � Cooling System Fanless design � Dimensions (W x H x D) 195 x 148 x 44.4 mm (7.68" x 5.83" x 1.75") � Enclosure ABS and ABS + PC � Mounting Panel Mount � Power Consumption 24.5 W (typical) � Power Input 18 ~ 32 VDC

� Watchdog Timer Programmable as 250 ms, 500 ms, 1 second � Weight (Net) 0.8 kg (1.76 lb)

System Hardware � CPU AMD Geode LX800, 500 MHZ � Expansion Slots 1 x CompactFlash slot � LAN 1 x 10/100Base-T � Memory 256 MB SO-DIMM DDR SDRAM � Serial Ports RS232 x 1 (COM1)

RS232/422/485 *1 (COM2) with auto data flow control � Storage 512 MB Compact Flash

LCD Display � Display Type TFT LCD � Display Size 5.7" � Max. Resolution 640 x 480 � Max. Colors 262 K � Luminance cd/m2 220 � Viewing Angle (H/V°) 140/100 � Backlight Life 50,000 hrs � Contrast Ratio 300 : 1

Touchscreen � Lifespan 10 millions times with a silicone rubber of 8 mm

diameter finger � Light Transmission Above 75% � Resolution Linearity � Type 4-wire, analog resistive

Environment � Humidity 10 ~ 95% RH @ 40° C, non-condensing � Ingress Protection Front panel: NEMA4, IP65 � Operating Temperature 0 ~ 50° C (32 ~ 122° F) � Storage Temperature -20 ~ 60° C (-4 ~ 140° F) � Vibration Protection 1 Grms (Random, Operating)

Software Specifications � Operating System Windows CE 5.0 � Advantech WinCE WebAccess specifications:

I/O Tag Number 600 Internal Tag Number 600 Web Client 2 Alarm Logging 1,000 Action Logging 1,000 Message Characters 50

� Graphics No. of Graphic Pages 100 Macro Key Macro Key Yes Script Yes Per Graphic Page 255

� Data Trend Log No. of data logging 50 Tags

� Recipe Recipes per Project 100Unit per Recipe 100 Item per Unit 999

� Scheduler Holiday Configuration 10 groupsTime Zone Group 99 Device Loop Group 99 Equipment Group 99

Ordering Information � WView660E-600-W50E 5.7" Web-enabled HMI w/600 I/O tags

����COMPLIANT

����������

Building Automation Systems 25-20

Features

WebView-1070

SpecificationsGeneral � BIOS Award® 4 MB � Certifications BSMI, CCC, CE, FCC � Cooling System Fanless design � Dimensions (W x H x D) 286 x 226 x 58 mm (11.26" x 8.9" x 2.28") � Enclosure Die-Casting Aluminum alloy � Mounting Desktop, Wall or Panel Mount � Power Consumption 60 W � Power Input 18 ~ 32 VDC

� Watchdog Timer 1 sec (system) � Weight (Net) 3.5 kg (7.72 lbs)

System Hardware � CPU Intel Celeron M 1 GHz � Expansion Slots 1 x CompactFlash slot

1 x PCI-104 slot � Graphics Controller Intel 855 GME � Keyboard/Mouse Ports 1 x PS/2 � LAN 1 x 10/100Base-T, 1 x 10/100/1000Base-T � Memory 512 MB DDR SDRAM � Serial Ports 2 x RS-232 and 1 x RS-232/485/422 � Storage 1 x CompactFlash card (optional), or

1 x 2.5" HDD (optional) � USB Ports 2 x USB 2.0

LCD Display � Backlight Life 50,000 � Contrast Ratio 500:1 � Display Size 10.4" � Display Type SVGA TFT LCD � Luminance cd/m2 400 � Max. Colors 260 K � Max. Resolution 800 x 600 � Viewing Angle (H/V) 140/110

Touchscreen � Lifespan 1 million touches at single point � Light Transmission Above 75% � Pixel Pitch (H x V) 0.3075 x 0.3075 mm � Resolution 1,024 x 1,024 � Type 8-wire, analog resistive

Environment � Humidity 10 ~ 95% RH @ 40° C, non-condensing � Ingress Protection Front panel: NEMA4, IP65 � Operating Temperature 0 ~ 50° C (32 ~ 122° F) � Storage Temperature -20 ~ 70° C (-4 ~ 158° F) � Vibration Protection With CompactFlash: 2 grms (5 ~ 500 Hz)

With HDD: 1 grms

Software Specifications � Operating System Windows CE 5.0 � Advantech WinCE WebAccess specifications:

I/O Tag Number 600Internal Tag Number 600 Web Client 2 Alarm Logging 1,000 Action Logging 1,000 Message Characters 50

� Graphics No. of Graphic Pages 100Macro Key Yes Script Yes Per Graphic Page 255

� Data Trend Log No. of data logging 50 Tags

� Recipe Recipes per Project 100 Unit per Recipe 100 Item per Unit 999

� Scheduler Holiday Configuration 10 groupsTime Zone Group 99 Device Loop Group 99 Equipment Group 99

Ordering Information � WView1070-600-W50E 10.4" Web-enabled HMI w/600 I/O tags

� Compact design with Die-Casting � Fanless cooling system � NEMA4/IP65 compliant front panel � Automatic data flow control RS-485 � Dual fast Ethernet supported � Built-in Windows® CE 5.0 with Advantech WinCE WebAccess � Supports Vector-based graphics � Remote control and monitor by Ordinary IE Browser � Supports calendar scheduler � Import BMP, JPEG, GIF, ACAD DXF � Supports 2 web clients � 50 real-time and historical trend tags

IntroductionAdvantech's WebView-1070 is a web-based human-machine interface (HMI) and supervisory control and data acquisition (SCADA) platform. All the features are available in an ordinary web browser including Animated Graphics Displays, Real-time Data Control, Trends, Alarms and Logs, Scheduler, Recipes, and more.

10.4" Web-enabled HMI

����COMPLIANT

����������

www.advantech.com/productsOnline Download 25-21

19PC-based Controllers

Embedded Controllers

20PAC21

Motion Control22

RS-485 I/O23

Ethernet I/O24

Building Automation25

Self-service Terminals26

eHome Platforms27

Features

WebView-1261

SpecificationsGeneral � BIOS Award® 4 MB � Certifications BSMI, CCC, CE, FCC � Cooling System Fanless design � Dimensions (W x H x D) 311 x 237 x 50 mm (12.24" x 9.33" x 1.97") � Enclosure Al-Mg and ABS � Mounting Desktop, swing arm or wall (with mounting kit) � Power Consumption 60 W � Power Input 18 ~ 32 VDC

� Weight (Net) 2.2 kg (4.85 lb)

System Hardware � CPU AMD LX800 500 MHz � Expansion Slots 1 x CompactFlash® slot � Graphics Controller LX800 � Keyboard/Mouse Ports 1 x PS/2 � LAN 1 x 10/100Base-T � Memory 256 MB DDR SDRAM (up to 1 GB DDR SDRAM) � Parallel Ports 1 x Parallel Port � Serial Ports 3 x RS-232 and 1 x RS-232/485/422 � USB Ports 2 x USB 2.0

LCD Display � Backlight Life 50,000 hrs � Contrast Ratio 1 : 300 � Display Size 12.1" � Display Type SVGA TFT LCD � Luminance cd/m2 340 � Max. Colors 262 K � Max. Resolution 800 x 600 � Viewing Angle (H/V°) 100/60

Touchscreen � Lifespan 1 million touches at single point � Light Transmission Above 75% � Pixel Pitch (H x V) 0.3075 x 0.3075 mm � Resolution 1024 x 1024 � Type 8-wire, analog resistive

12.1" Web-enabled HMI with AMD LX800

IntroductionAdvantech WebView-1261 is a web browser-based human-machine interfaces (HMI) and supervisory control and data acquisition (SCADA). All the features are available in an ordinary Web browser including Animated Graphics Displays, Real-time Data Control, Trends, Alarms and Logs, Scheduler, Recipe ...etc.

Environment � Humidity 10 ~ 95% RH @ 40° C, non-condensing � Ingress Protection Front panel: NEMA4, IP65 � Operating Temperature 0 ~ 50° C (32 ~ 122° F) � Storage Temperature -20 ~ 70° C (-4 ~ 158° F) � Vibration Protection 2 grms (5 ~ 500 Hz) (Operating, random vibration)

Software Specifications � Operating System Windows CE 5.0 � Installed Advantech WinCE WebAccess with specification listed below:

I/O Tag Number 600Internal Tag Number 600 Web Client 2 Alarm Logging 1,000 Action Logging 1,000 Message Characters 50

� Graphics No. of Graphic Pages 100Macro Key Yes Local Script Yes Variable per Graphic Page 255

� Data Trend Log No. of data logging 50 Tags

� Recipe Recipes per Project 100Unit per Recipe 100 Item per Unit 999

� Scheduler Holiday Configuration group 10 groupsTime Zone Group 99 Device Loop Group 99 Equipment Group 99

Ordering Information � WVIEW1261-600-W50E 12.1" Web-enabled HMI w/LX800 and 600 I/O tags

� 12.1" SVGA TFT LCD � Super slim and compact design with Al-Mg housing � NEMA4/IP65 compliant front panel � Built-in Windows® CE 5.0 with Advantech WinCE WebAccess � Supports Vector-based graphics � Supports 2 Web clients � Remote control and monitor by Ordinary IE Browser � 50 tags real time trend and historical trend � Supports calendar scheduler � Import BMP, JPEG, GIF, ACAD DXF

����COMPLIANT

����������

Building Automation Systems 25-22

Features

WebView-1270

SpecificationsGeneral � BIOS Award® 4 MB � Certifications BSMI, CCC, CE, FCC � Cooling System Fanless design � Dimensions (W x H x D) 311 x 237 x 52.3 mm (12.24" x 9.33" x 2.06") � Enclosure Al-Mg and ABS � Mounting Desktop, Panel Mount or Wallmount � Power Consumption 40 W � Power Input 18 ~ 32 VDC

� Weight (Net) 3.3 kg (7.28 lb)

System Hardware � CPU Intel Celeron 1 GHz � Expansion Slots 1 x CompactFlash® slot, 1 x PCI-104 slot � Graphics Controller Intel 915 GME � Keyboard/Mouse Ports 1 x PS/2 � LAN 2 x 10/100Base-T � Memory 512 MB DDR2 SDRAM on board � Serial Ports 3 x RS-232 (COM1,2,3) and 1 x RS-232/485/422

(COM4) � USB Ports 4 x USB 2.0 � Audio Ports 1 x MIC-in, 1 x Line-out

LCD Display � Backlight Life 50,000 hrs � Contrast Ratio 500:1 � Display Size 12.1" � Display Type SVGA TFT LCD � Luminance cd/m2 350 � Max. Colors 262 K � Max. Resolution 800 x 600 � Viewing Angle (H/V°) 140/120

Touchscreen � Lifespan 1 million touches at single point � Light Transmission Above 75% � Resolution Linearity � Type 8-wire, analog resistive

12.1" Web-enabled HMI with Intel® Celeron® M

IntroductionAdvantech WebView-1270 is a web browser-based human-machine interfaces (HMI) and supervisory control and data acquisition (SCADA). All the features are available in an ordinary Web browser including Animated Graphics Displays, Real-time Data Control, Trends, Alarms and Logs, Scheduler, and more.

Environment � Humidity 10 ~ 95% RH @ 40° C, non-condensing � Ingress Protection Front panel: NEMA4, IP65 � Operating Temperature 0 ~ 50° C (32 ~ 122° F) � Storage Temperature -20 ~ 60° C (-4 ~ 140° F) � Vibration Protection With HDD: 1 grms (5 ~ 500 Hz)

(Operating, random vibration)

Software Specifications � Operating System Windows CE 5.0 � Installed Advantech WinCE WebAccess with specification listed below:

I/O Tag Number 600Internal Tag Number 600 Web Client 2 Alarm Logging 1,000 Action Logging 1,000 Message Characters 50

� Graphics No. of Graphic Pages 100Macro Key Yes Local Script Yes Variable per Graphic Page 255

� Data Trend Log No. of data logging 50 Tags

� Recipe Recipes per Project 100Unit per Recipe 100 Item per Unit 999

� Scheduler Holiday Configuration group 10 groupsTime Zone Group 99 Device Loop Group 99 Equipment Group 99

Ordering Information � WVIEW1270-600-W50E 12.1" Web-enabled HMI w/Celeron M and 600 I/O tags

� 12.1" SVGA TFT LCD � Super slim and compact design with Al-Mg housing � NEMA4/IP65 compliant front panel � Built-in Windows® CE 5.0 with Advantech WinCE WebAccess � Supports Vector-based graphics � Supports 2 web clients � Remote control and monitor through an ordinary IE browser � 50 tags real time trend and historical trend � Supports calendar scheduler � Import BMP, JPEG, GIF, ACAD DXF

����COMPLIANT

����������