building regulations update · change of use •calculation required before completion certificate...

47
Building Regulations Update Joe Campion BSc (Hons) MBEng ACIOB MIFireE

Upload: others

Post on 18-Jul-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Building Regulations Update

Joe CampionBSc (Hons) MBEng ACIOB MIFireE

Page 2: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

2010 Changes to The Building Regulations

• Part G – April 2010

• Water efficiency & sanitary • Water efficiency & sanitary provision

• Part L & F – October 2010

• Conservation of Fuel & Power

• Ventilation

Page 3: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Part G

• G1 – Water Quality

• G2 – Water Efficiency

• G3 - Hot Water Supply• G3 - Hot Water Supply

• G4 – Sanitary Provisions

• G5 – Bathrooms

• G6 – Food Preparation Areas

Page 4: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Part G1 – Provision of Cold Water Services

• Definition of wholesome and non-wholesome water

• Allows recycled or rainwater to be used for non wholesome useused for non wholesome use

Page 5: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

G2 Water Efficiency

• Maximum water use per person per day

• 125 litres maximum of wholesome waterwholesome water

• Calculated by formula

• Allows additional non wholesome water use

Page 6: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Regulations 17K & 20E

• Only Applies to dwellings

• New build dwellings

• New Dwellings formed by material change of usechange of use

• Calculation required before Completion Certificate issued

The Water Efficiency Calculator for New Dwellings

Available from Planning Portal

www.wrcplc.co.uk/PartGCalculator/Calculator.aspx

Page 7: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction
Page 8: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Water Use

• Low flush WC

• Aerated taps & showers

• Smaller baths• Smaller baths

• Low water use appliances

Page 9: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

G3 – Hot Water Services

• Requires hot water supply to sinks within toilet accommodation

• Specifically includes food prep areas

• Vented Hot Water Storage systems require additional energy cut out to require additional energy cut out to prevent boiling the water

• Pressurised systems require two independent safety devices

Page 10: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Prevention of Scalding

• In line hot water tempering valves required where DHW store can exceed 80oC

• In line blending valve to baths• In line blending valve to baths

• Thermostatic mixing valves

• Limiting temperature to 48oC

• Only applies to dwellings

Page 11: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

G4 – Sanitary Provision

• Follow Guidance within Workplace Regs 1992

• or BS 6465: Part 1 2006• or BS 6465: Part 1 2006

• ‘Adequate and Suitable’ provision now part of Building Regulations

Page 12: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Workplace Scale of Provision

Page 13: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Non Domestic Buildings

• Separate sinks for hand washing required within commercial kitchens

• Single door between WC • Single door between WC and kitchen – but beware Environmental Health Officers Requirements

Page 14: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

General Items

• Hot taps should always be on the left

• All new dwellings to have WC with integrated washing facilityintegrated washing facility

• Must also have a bath or shower

• Single door required between WC and kitchens

Page 15: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Part L Conservation of Fuel & Power

• Moving towards “Carbon Neutral”

• 2016 Zero Carbon • 2016 Zero Carbon Building Regulations for domestic

• 2019 for Commercial

Page 16: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

‘Timetable for Change’

2010 25% reduction Code level 3

2013 44% reduction Code level 4

2016 100% reduction Code level 5

Taken from 2006 Part L Baseline

Non Domestic Buildings move to 100% by 2019

Page 17: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction
Page 18: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Non Domestic

• 25% CO2 improvement required over 2006 Part L

• Submit a design stage SBEM

• Submit list of key design features• Submit list of key design features

• New Regulation to require a commissioning plan at submission stage

Page 19: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Solar Gain

• Solar gain must be considered on all building types

• Including Air • Including Air conditioned buildings

• More than 40% of external wall glazed could cause potential problems

Page 20: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

25% Improvement

• Improvement is likely to be averaged over different categories of buildings

Page 21: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Why?

• Aim is to maximise all efficiency savings possible

• Reduce maximum amount of CO2with minimum cost across building with minimum cost across building types

• CO2 savings have different costs in different types of buildings

Page 22: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Quality of Construction

• Increased sample of air testing for dwelling

• All non domestic buildings require testingtesting

• Improved thermal bridging

• Testing of heating ductwork

• Improved commissioning

Page 23: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Linier Thermal Bridging

Three Proposed Options

Page 24: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Ψ-Value Calculation

• Accreditation Scheme Proposed

• CA, Kingspan or Eurobond may produce standard details

• Traditional details should be freely • Traditional details should be freely available (ACD)

Page 25: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

On Site Assessment

• On site inspection of details

• Checking for buildability

• Reporting of defects

• Continuous improvement of details

• Someone must pay for this

• Traditional details bigger problem

Page 26: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Un Accredited Details

• No added costs

• May not have big effect on SBEM

• Buildings with high heating • Buildings with high heating loads would be more effected

• Care homes, schools, leisure centres, distribution warehouses little effect

Page 27: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Air Testing of Ductwork• Ductwork leakage testing to low pressure ductwork

• Required when SBEM • Required when SBEM assumes low air leakage to improve calculation

• Not required for ventilation only

Page 28: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

SBEM Example - School

• Currently TER 35.96 BER 34.97

• Standard Spec for new School

• Gas central heating• Gas central heating

• Natural ventilation

• Good natural daylight

Page 29: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

2010 SBEM

• U-values 0.15w/m2k Floor & Roof

• U-values 0.20w/m2k Wall

• U-values 1.50w/m2k Windows

• Air leakage 5m3/(m2.h)@50Pa• Air leakage 5m3/(m2.h)@50Pa

• Boiler 98% Efficient with controls

• Very good lighting

TER 20.68 - BER 22.17 - FAILS

Page 30: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Suggestions?

• LED Lighting to corridors toilets etc

• Daylight sensing –Schools OfficesSchools Offices

• Go air conditioning

• Renewables

Page 31: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Energy Use - Office

LightingHeating

Page 32: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Offices – Natural Ventilation

• Lighting has high carbon load

• Auto Switching and daylight dimming provide a big saving

• LED’s to circulation spaces & toilets• LED’s to circulation spaces & toilets

• Low installed power loads

• Automatic monitoring & targeting to energy meters

Page 33: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Heating Systems

• Thermal Mass can provide 10% improvement (5% with aircon)

• High efficiency condensing boilers

• 95% efficient or better• 95% efficient or better

• Use underfloor heating with heat pump boilers

Page 34: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Other Features

• Power Factor Correction

• aM&T to Energy Meters

• Maximise areas of South Glazing

• But beware of Overheating!!• But beware of Overheating!!

• Renewables

Page 35: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Energy Use – Leisure Centre

Page 36: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Domestic Hot water

• Any showering facility increases DHW demand significantly

• Super efficient DHW boilers 98%+

• Direct rather than large storage • Direct rather than large storage capacity – Reduces standing losses

• Limit the boilers to showering areas – Reduces distribution losses

Page 37: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Storage & Industrial

Page 38: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Storage & Industrial

• LED Floodlights rather than Metal Halide box lighting

• Improve U-values to walls 0.25w/m2k

• Floor & Roof U-values 0.20w/m2k• Floor & Roof U-values 0.20w/m k

• Air leakage 5m3/(m2/h)@50Pa

• Good thermal bridging details

• Efficient Warm Air Heaters 95%+

Page 39: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Retail - Supermarket

• Build to current standards they should PASS

• Why?

Page 40: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Low & Zero Carbon Systems

• Solar Thermal

• Combined Heat & Power

• Wind Turbines• Wind Turbines

• Photovoltaic

• Heat Pumps

Page 41: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Feed in Tariffs (FiT)

• Payment received for renewable energy generation

• Regardless of end use

• MCS Accreditation • MCS Accreditation required for Installers

Page 42: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Renewable Heat Incentives (RHI)

• Similar to FiT

• Heat Pumps

• Solar thermal

• CHP• CHP

• Aerobic Digestion

• Biomass/Bio fuel

Page 43: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Part F - Ventilation

• Only real changes to dwellings

• Commissioning of ventilation systems

• Visual inspection for natural • Visual inspection for natural ventilation

• Testing of extract and whole house ventilation systems

Page 44: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Part L Summary• Heat pump boilers replacing gas boilers

• LED lighting for non-domestic may provide benefits to get a pass

• Solar shading and thermal mass important, not enough alone

• Solar shading and thermal mass important, not enough alone

• Low and Zero Carbon Systems can help

• U values and air permeability will require improvements

Page 45: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Questions

Page 46: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction
Page 47: Building Regulations Update · change of use •Calculation required before Completion Certificate issued The Water Efficiency Calculator for New Dwellings ... 2010 25% reduction

Thank You

Joe CampionBSc (Hons) MBEng ACIOB MIFireE