bulletin 32

31
Ford Motor Company Transient Record J. Paquet (jhiggi37) SFD File No.: Bulletin 32 Bulletin 32 (2014) Corporate Security and Fire Security: Proprietary February 26, 2014 Record Retention Code: S + 5, O When printed, this becomes an uncontrolled document Verify the latest revision on the Corporate Fire Protection Website at www.security.ford.com FIRE PROTECTION ENGINEERING BULLETIN NO. 32 FIRE ALARM SYSTEMS Complete Revision: February 26, 2014

Upload: constantin-cosmin

Post on 13-Sep-2015

227 views

Category:

Documents


3 download

DESCRIPTION

FIRE PROTECTION ENGINEERINGBULLETIN NO. 32

TRANSCRIPT

  • Ford Motor Company Transient Record J. Paquet (jhiggi37) SFD File No.: Bulletin 32 Bulletin 32 (2014) Corporate Security and Fire Security: Proprietary February 26, 2014 Record Retention Code: S + 5, O

    When printed, this becomes an uncontrolled document Verify the latest revision on the Corporate Fire Protection Website at www.security.ford.com

    FIRE PROTECTION ENGINEERING BULLETIN NO. 32

    FIRE ALARM SYSTEMS

    Complete Revision: February 26, 2014

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    TABLE OF CONTENTS I. SCOPE ..................................................................................................................................... 1 II DEFINITIONS ........................................................................................................................ 2 III. SYSTEM EVALUATION...................................................................................................... 3 IV. DESIGN APPROVALS ......................................................................................................... 3 V. FACILITY TYPES AND REQUIREMENTS ..................................................................... 4

    A. Required Alarm System Types .................................................................................. 4 B. Requirements for All Facilities .................................................................................. 5 C. Fire Alarm System Requirements for Category A and B Facilities ............... 8 D. Fire Alarm System Requirements for Category C Facilities ............................ 11

    VI. EXISTING SYSTEMS ADDITIONS AND RENOVATIONS ...................................... 11 VII. ACCEPTABLE MANUFACTURERS ............................................................................... 11 VIII. PROJECT REQUIREMENTS............................................................................................ 12 A. Company (Owner) Responsibilities ......................................................................... 12 B. Contractor Responsibilities ...................................................................................... 13 IX. ACCEPTANCE TESTING REQUIREMENTS ................................................................ 18

    A. Contractor Pre-Testing ............................................................................................. 18 B. Owner Acceptance Tests ........................................................................................... 18 C. Final Acceptance Testing .......................................................................................... 19

    X. CERTIFICATION, DOCUMENTATION AND TRAINING ......................................... 19 A. Certification ............................................................................................................... 19 B. Documentation ........................................................................................................... 20 C. Operations and Maintenance Manuals ................................................................... 20 D. As Built Drawings ...................................................................................................... 20 E. Training ...................................................................................................................... 21

    APPENDICES A. Fire Alarm System Evaluation Worksheet ............................................................. 22 B. Condition/Alarm Tone/Voice Announcement/Employee Action to be Taken

    Chart ........................................................................................................................... 24 C. Sketch Nos. 1-5 ........................................................................................................... 25

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 1 of 29

    I. SCOPE A Fire Alarm System is an essential component of a facilitys fire protection system. When properly designed and operational, a fire alarm system can enhance life safety and help reduce damage due to fire by promptly identifying fire protection system alarm and trouble conditions to a constantly attended location. This communication allows prompt response by Emergency Response Teams and public fire departments/brigades. This Bulletin establishes the minimum requirements for fire alarm system installations in Ford Motor Company facilities. It applies to new construction, renovation, and for upgrading fire alarms systems in existing facilities. The Company generally references the latest edition of NFPA 72, "National Fire Alarm Code", along with the applicable portions of the latest edition of NFPA 70, National Electric Code. These codes and the Ford Fire Protection Bulletins are the basis for these requirements in all fire alarm system installations. This bulletin recognizes the NFPA concept for both Pre-signal and Positive Alarm Sequence. These features when properly utilized provide for employee safety and reduce the number of false alarms. False alarms have long been known to increase the risk to employee safety. When local, State or National fire alarm and life safety requirements are more stringent than those presented in NFPA 72 or this bulletin, those requirements shall be applied. This Bulletin also provides guidelines (System Evaluation) for determining when an alarm system can no longer be expected to provide the necessary reliability of function and should be considered for replacement. Additional Bulletins, Standards, and codes for reference are:

    Bulletin No. 7, Water Supply Systems and associated topics. Bulletin No. 8, Automatic Sprinkler System Installations. Bulletin No. 9, Carbon Dioxide (CO2) Extinguishing Systems. Bulletin No. 20, Bulletin Deviation Procedure. Bulletin No. 27, Inspection, Testing, and Maintenance Requirements for Fire

    Protection Systems and Equipment and related topics. Bulletin 29, Clean Agent Extinguishing Systems. Ford Section No. 01100, Safety Guidelines and Information for Contractors. Ford Section No. 16000, General Electrical Specifications. Ford Section No. 16400, Power Distribution Systems.

    This Bulletin and any associated topics are owned by Ford Corporate Fire Protection Engineering, Corporate Security and Fire. These requirements apply to all Company owned and leased facilities including subsidiaries of Ford Motor Company. Where NFPA, Local, State or Federal or National codes are more

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 2 of 29

    stringent than these standards, or other Company standards referenced here, the more stringent requirements shall be followed. Written approval is required from Corporate Fire Protection Engineering for deviations from the following requirements.

    II. DEFINITIONS Circuit Integrity The ability of an alarm circuit to transmit alarms during non-simultaneous single circuit fault conditions. Conceptual Design A written description of the new fire alarm and occupant notification system. Listed or Approved Products Equipment, materials, or systems included in a list published by an organization concerned with evaluation of products. The listing shall state that the equipment or material meets appropriate designated standards or has been tested and found suitable for a specified purpose. Underwriters Laboratories, Inc. (UL) listing or Factory Mutual (FM) approval are the normal means to meet requirements for listed or approved products. Where UL listed or FM approved equipment, materials, or systems are required, but not available, equipment listed by a nationally recognized laboratory in the country of use may be substituted if approved by Ford Corporate Fire Protection Engineering. Pre-signal A pre-signal feature shall meet the following conditions:

    The initial fire alarm signals sound only in department offices, control rooms, fire brigade stations, or other constantly attended central locations.

    Where there is a connection to a remote location, the transmission of the fire alarm signal to the supervising station activates upon the initial alarm signal.

    Subsequent system operation is by human action that activates the general fire alarm. Positive Alarm Sequence (PAS) An automatic sequence that results in an alarm signal, even when manually delayed for investigation, unless the system is reset. Shall Indicates a mandatory requirement. Should Indicates a recommendation or that which is advised but not required. Stand-Alone The ability of a control panel within a network to function as an independent Fire Alarm Control Panel should it be disconnected from the network.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 3 of 29

    System Evaluation A review of an alarm system to determine if it can function with the desired reliability into the future. System Survivability The ability of a fire alarm system to perform all or part of its function when in an impaired condition.

    III. SYSTEM EVALUATION When additions, remodels, or renovations are proposed, or when the reliability of the system is in question complete the Fire Alarm System Evaluation Work Sheet Appendix A.

    IV. DESIGN APPROVALS Conceptual designs for new fire alarm systems and additions or revisions to existing fire alarm systems shall be approved by Corporate Fire Protection Engineering before bidding a project. Plans for new and revised fire alarm systems shall be approved before installation begins. If work starts before receiving approvals, the installing contractor shall be responsible for any required changes. A. Corporate Approvals

    The Ford Corporate Manager of Fire Protection Engineering shall be notified prior to the development of any projected related to Fire Alarm Systems. Once the project is approved, detailed plans with equipment layout and fire protection details shall be submitted for review and approval. Plans shall indicate the specific codes, standards, and editions used to design the system. 1. Property Loss Prevention Consultant Review

    Detailed plans for fire alarm systems as described below shall be submitted for review by the Property Loss Prevention Consultant. a. All new fire alarm systems. b. Revisions or additions to existing fire alarm systems that meet any of the

    following conditions. 1) Systems that affect an area of 465 m2 (5,000 ft2) or more. 2) Projects that add 5 or more devices to a system. 3) Projects that include modifying more than one circuit.

    2. Corporate Fire Protection Engineering Review Detailed plans for all fire alarm systems that do not require review by the Property Loss Prevention Consultant shall be submitted for review by Corporate Fire Protection Engineering.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 4 of 29

    B. Local Permits and/or Approvals Where Required Plans and related details shall be submitted to the local Authority Having Jurisdiction (AHJ) if required.

    C. Final Acceptance 1. As-Built Drawings

    a. Contractor shall provide detailed as-built drawings for all new systems. b. For additions or revisions to existing systems, contractor shall update

    existing as-built drawings to show as-built work for his project. This is necessary to have records of the system that are as accurate and current as possible.

    2. Contractors certificates for installed systems shall be provided as required by NFPA 72.

    3. Where approval by the Loss Prevention Service Provider is required, the appropriate acceptance form(s) shall be completed. The installing contractor shall provide 10 working days advance notice of required acceptance testing.

    4. When required by the local authority, the installing contractor shall provide advance notice of acceptance testing and all documentation needed to obtain the final acceptance. Consult the local authority to establish the required advance notice.

    V. FACILITY TYPES AND REQUIREMENTS Written approval is required from Corporate Fire Protection Engineering for deviations from the following requirements. A. Required Alarm System Types

    Facilities are considered Category A, Category B, or Category C. The type of alarm system required depends on the occupancy and value of the protected facility. 1. Category A and B Facilities

    Category A and B facilities include: Category A facilities include those whose Total Insured Value is more

    than $200,000,000 U. S. and/or having a critical BI potential. Category B facilities include those whose Total Insured Value is more

    than $100,000,000 U. S. up to $200,000,000 U.S. Note: The alarm system requirements for Category A and Category B facilities are the same.

    2. Category C Facilities Category C facilities include all other facilities.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 5 of 29

    B. Requirements for All Facilities 1. Alarm Initiating Devices

    a. Systems installed in accordance with this Bulletin shall monitor, as a minimum, the following: 1) All sprinkler system water-flow alarms and associated supervisory

    signals as required by Ford Bulletin 8 or the local authority. 2) All CO2 systems as required by Ford Fire Protection Bulletin 9. 3) All new and existing special hazards protection systems (i.e. paint

    shop, ovens, paint mix). 4) All computer center and/or telecommunication facility protection

    systems as required by Ford Bulletins 24 and 25. 5) All water supply supervisory and trouble signals as required by

    Ford Fire Protection Bulletin 7 and Topics 7.03, and 7.04. 6) Valve supervision devices (tampers) shall not be installed on any

    fire control valves. Valves shall be secured with a lock and chain. If local authorities recommend tampers contact Corporate Fire Protection.

    b. Provide manual pull stations: 1) In sprinklered areas, provide manual pull stations within 1.5 m (5

    ft.) of any designated exit. Locate at least one manual pull station on each floor. Exception: Where Positive Alarm Sequence is used, provide manual pull stations so that the maximum travel distance to a pull station does not exceed 60 m (200 ft).

    2) In unsprinklered or partially sprinklered areas, provide manual pull stations so that the travel distance does not exceed 60 m (200 ft).

    2. Alarm Notification Appliances a. Audible Appliances

    1) Audible appliances shall be installed to provide a sound level that is a minimum sound level of 75 dBA, or 15 dB above the average twenty-four ambient sound level, or 5 dB above the maximum sound level having duration of at least 60 seconds, whichever is greater.

    2) Voice communication systems shall have adequate intelligibility as determined by NFPA 72.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 6 of 29

    3) Audible appliances in manufacturing or storage areas shall be located 4.5 m (15 ft) above the floor.

    b. Visual Appliances 1) Visual appliances (strobes) shall be provided in all common use

    spaces including, but not limited to restrooms, lobbies, hallways, meeting and conference rooms, classrooms, cafeterias, filing and photocopy rooms, employee break rooms, and other spaces not used solely as employee work areas.

    2) Manufacturing plants are not defined as public areas and therefore shall not be equipped with visual appliances. Areas that are considered public areas that are within the manufacturing plant (bathrooms, conference rooms, cafeterias, etc) shall still be considered public and be provided with visual appliances.

    3) Existing plants that are being renovated and already have visual appliances in portions of the manufacturing plant shall contact Corporate Fire Protection for additional guidance. Based on individual site layout visual appliances may be required in remodeled areas.

    4) Visual appliances shall be provided in egress aisles in plant areas such as stamping plant basements that have noise levels in excess of 90dBA. Typical noise levels in Ford production facilities are reported as follows: Assembly (Trim, Chassis,and Final) 75 to 82 dBA Assembly (Body) 80 to 85 dBA Stamping (Press Operations) 85 to 93 dBA Stamping (Assembly) 80 to 85 dBA Transmission 80 to 87 dBA Engine 75 to 82 dBA Office Areas 52 to 65 dBA depending on construction

    and degree of isolation from production operations. Laboratory areas are assumed similar to office areas.

    c. Notification appliances shall be capable of providing distinct signals in accordance with those outlined in Appendix B of this document for: Pre-tone (High Rise buildings only where required by local code). Evacuation. Weather alert.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 7 of 29

    All clear. d. Signals shall be synchronized throughout the building for installations

    after August 1, 2008. e. All system output (printed and text displays and pre-recorded messages)

    shall be in the local language. f. All supporting documentation associated with the fire alarm system shall

    be in the local language. 3. Pre-Signal Where a Pre-Signal feature is used the alarm shall register in a

    constantly attended location. The use of Pre-Signal is not a substitute for lack of fire alarm system maintenance. Systems designed for automatic evacuation shall be repaired and upgraded as necessary to maintain this status and shall not be converted to Pre-Signal. a. Installation of new pre-signal systems is forbidden. b. When existing systems are replaced or upgraded, pre-signal systems shall

    not be continued. c. Systems designed for automatic evacuation shall be repaired and

    upgraded as necessary to maintain this status and shall not be converted to Pre-Signal.

    4. Positive Alarm Sequence Where Positive Alarm Sequence (PAS) is used; the time for investigation may be up to a total of 5 minutes if permitted by local authorities.

    5. Equipment Requirements a. All components of the alarm system shall be listed or approved for the

    intended purpose. Products shall be of the latest design. Obsolete or discontinued models are not acceptable. 1) The Fire Alarm Control Panel (FACP) shall be completely pre-

    wired and programmed requiring only the connection of incoming field wiring and the plugging in of accessory modules such as additional memory or printer interface boards.

    2) Use UL listed wire or fiber optic devices, per the requirements of NFPA 70, Section 760, for connecting alarm initiating device circuits and alarm notification appliance circuits to the FACP.

    b. Each component of the Fire Alarm System shall be the product of a single fire alarm system manufacturer. Exception: Speakers, strobes, and explosion proof devices may be supplied by a different manufacturer; however, each shall be listed for its intended use and compatible with the FACP and other equipment.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 8 of 29

    C. Fire Alarm System Requirements for Category A and B Facilities All fire alarm control panels shall be: Listed per UL 864, 9th Edition. Modular in design. Microprocessor based and point addressable. Capable of alarm verification to avoid unwanted alarms and positive alarm

    sequence (PAS) as outlined in NFPA 72 and this Bulletin. Programmable control-by-event of outputs for individual alarm or supervisory

    point addressable devices. Be multiplex capable of networking with additional fire alarm control panels

    (nodes) for large applications. Each Node panel shall be capable of degrade operations in the event of communication loss with the main FACP.

    All initiating devices and control devices shall be point addressable and capable of multiplex operation.

    1. System Coverage Fire alarm panels shall only monitor fire alarm systems or conditions that adversely affect fire protection systems.

    2. System Performance, Circuit Integrity, and System Survivability a. Devices shall be point addressable. b. Signal transmission (where provided) from a monitored facility to the

    Ford Global Communication Center (GCC), shall use circuitry as described in NFPA 72. See Appendix B, Sketch #1.

    c. Networked panels in a protected facility shall communicate by Class X (formerly Class A, Style 7) as described in NFPA 72. See Appendix B, Sketch #1.

    d. All Class A circuits shall maintain 1.3 m (4 ft) horizontal and 0.3 m (1 ft) vertical separation. The intent of this requirement is to protect the cables from physical damage that would affect both the outgoing and return circuits.

    e. Notification circuits and initiating circuits shall originate from the zone they cover.

    f. Addressable initiating device loop wiring shall be Class A, as described in NFPA 72. See Appendix B, Sketch #2.

    g. Initiating Device Circuits (IDC) with more than one (1) initiating device connected to the circuit shall be Class A as described in NFPA 72. See Appendix B, Sketch #2.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 9 of 29

    h. An IDC with only one (1) initiating device connected to the circuit shall be Class B as described in NFPA 72. See Appendix B, Sketch #2.

    i. Notification Appliance Circuits (NAC) shall be Class B as described in NFPA 72. See Appendix B, Sketch #3.

    3. Fire Alarm Control Panel (FACP) and Intermediate Control Panels (ICP) a. All FACPs for greenfield sites shall be a minimum of 20% oversized.

    ICPs shall be a minimum of 10% oversized to accommodate future system expansion of input and output needs. Replacement FACPs and ICPs on fire alarm systems shall be a minimum of 10% oversized to accommodate any future changes to the system.

    b. The following hardware shall be provided in all control panels: 1) A CPU/LCD Display unit that will display system messages,

    status information, and programming means. 2) Audio control module with built-in hand-held microphone to

    provide voice messages (instructions) to building occupants. 3) Standby batteries sized as needed with fused battery outlets.

    c. FACP Cabinet(s) shall be lockable painted steel enclosure(s). 1) Arrange unit so all operations required for testing or for normal

    care and maintenance of the system is performed from the front of the enclosure.

    2) If more than a single unit is required to form a complete control unit, provide matching modular unit enclosures.

    3) Wiring shall be through the sides or bottom of the cabinet. d. Cabinets in normal office areas and substations shall be NEMA Type 1a.

    Cabinets not installed in a normal office or substation environment shall be NEMA 4 rated enclosures.

    e. Alphanumeric Display and System Controls: Panel shall include an LCD (Liquid Crystal Display) display to indicate alarm, supervisory, and component status messages and shall include a keypad for use in entering and executing control commands.

    f. In the event that any control panel should lose communications with the network, that panel shall operate in a degrade mode as a stand-alone FACP.

    g. Locate the FACP in cooperation with local Fire Department officials. The preferred location is at a constantly attended location or within 6 m (20 ft) of the main building entrance.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 10 of 29

    h. FACPs shall not be located in locked rooms. ICPs shall be lockable or located in a locked room.

    i. Heat detectors shall be located above all control panels. In office areas, smoke detectors shall be located above all control panels.

    4. Other System Components a. Printer

    A printer compatible with the fire alarm system shall be provided for management of the system.

    b. Duct Smoke Detectors Duct smoke detectors should be avoided whenever possible. These units

    are designed to be installed within HVAC air transfer units to detect and prevent smoke transfer between rooms in a subdivided space such as an office environment. In general they are not required in open spaces such as plants or warehouses. 1) Duct detectors should not be installed for air systems that only

    supply plant areas. 2) For all other areas duct smoke detectors should be avoided unless

    required by local code. Feel free to contact Corporate Fire Protection Engineering to verify code actually requires installation if requested by local officials.

    3) Where duct detectors are required by local code, provide the following. a) A keyed test switch, with LED alarm light within 2 m (80

    in) of the finished floor level. b) A permanent label, adjacent to the test switch, describing

    the function of the switch. c) A label to show the location of the duct detector.

    c. Remote Power Supplies 1) Remote power supplies installed to provide power for notification

    appliances shall be supervised by the main fire alarm system for trouble conditions.

    2) Each power supply shall be activated by an individual notification circuit originating at the FACP or ICP or an individual control module.

    3) Activation of remote strobe power supplies by cascading of strobe power supplies or circuits shall not be acceptable.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 11 of 29

    Execption: If remote strobe power supplies are located in the same location, it is acceptable to activate the group with a single control module and monitor the group with an addressable monitor module.

    d. Graphic Display System Although not recommended, there is often an option to provide a graphic display system, complete with high-resolution color monitor, keyboard, and Microsoft-compatible computer. These systems have an advantage when there is a high turnover in personnel responsible for monitoring the fire alarm system. These systems are expensive to keep updated and are considered to be not cost-effective.

    D. Fire Alarm Requirements for Category C Facilities In lieu of the requirements for Category A and B facilities provide the following: 1. Signal transmission may be non-addressable. External alarm communication

    shall be via a supervised digital dialer. 2. Initiating device circuits as defined in NFPA 72 for connecting initiating

    devices to the FACP shall be Class B. 3. Notification appliance circuits as defined by NFPA 72 for connecting

    notification appliances to the FACP shall be Class B. 4. Program digital dialer so that it is compatible with the Ford Global

    Communication Center (GCC) Station in Dearborn, Michigan or local approved supervising station.

    5. Provide alarm horns (with strobe lights as required by applicable codes), for evacuation in accordance with the requirements of NFPA 72 and NFPA 101.

    VI. EXISTING SYSTEMS ADDITIONS AND RENOVATIONS A. For projects where there is presently a fire alarm system in existence, the switchover to

    the new system shall be carefully coordinated, such that: 1. No alarm points are out of service beyond a single 8-hour period. 2. Full system operability is achieved prior to the daily departure of installation

    personnel from the job site. B. If it becomes necessary to leave the protected premises while parts, sections, zones, or

    components are out of service, a full time trained security guard service shall be provided, at the contractors expense, subject to the approval of the Corporate Fire Protection Engineer.

    VII. ACCEPTABLE MANUFACTURERS

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 12 of 29

    A. Manufacturers All system components shall only be purchased from one of the approved manufacturers listed below: 1. Category A and Category B Facilities

    Notifier/Honeywell Simplex/Grinnell

    2. Category C Facilities Notifier/Honeywell Simplex/Grinnell Silent Knight

    B. Manufacturers Obligations 1. Being listed as an acceptable manufacturer in no way relieves the obligation to

    provide all equipment and features in accordance with these specifications. 2. The manufacturer shall be a nationally recognized company specializing in fire

    alarm and detection systems. This organization shall employ factory trained (and NICET certified technicians for U.S. facilities) and shall maintain a service organization within 200 km (125 mi) of the project location. The manufacturer and service organization shall have a minimum of ten (10) years experience in the fire protective signaling systems industry.

    3. Each manufacturer shall designate one (1) single point of contact or Ford Account Manager. All proposals/submittals shall be prepared/reviewed by this Account Manager to assure compliance with Ford standards and procedures.

    VIII. PROJECT REQUIREMENTS A. Company (Owner) Responsibilities

    See Section III. 1. Prior to requesting funding for the project, contact Corporate Fire Protection

    Engineering and the local purchasing activity. 2. Existing facilities shall provide current and accurate CAD drawings of the

    facility. Failure to do so will result in increased cost and longer project duration. Plans shall include the following: Current point list Appropriate existing power distribution panels System designer Component supplier

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 13 of 29

    Installing contractor 3. Prior to putting the project out for bid, have a job site meeting with Corporate

    Fire Protection Engineering or their designee and the Loss Prevention Service Provider.

    4. Construction reviews shall be scheduled with the same professional (see 3 above) during the course of the project.

    B. Contractor Responsibilities 1. Plans and Approvals

    a. The contractor shall visit the site, examine and verify the conditions under which his work shall be conducted before submitting a proposal. The submitting of a proposal implies that the contractor has visited the site and is conversant with all site conditions.

    b. The Fire Alarm System supplier shall submit to Ford Corporate Fire Protection Engineering a preliminary design and equipment cut sheets with the proposal for approval. Equipment cut sheets shall identify all system components and U.L. listings.

    c. DO NOT START installation of the fire alarm system until detailed plans and specifications have been approved and documented by the Corporate Fire Protection Engineering, the Property Loss Prevention Consultant, the Local Authority Having Jurisdiction, and the appropriate Building Officials and installation permits have been obtained from local officials. It is the contractors responsibility to notify Corporate Fire Protection Engineering, and the Property Loss Prevention Consultant when conflicts between the local code and this bulletin occur. Equipment submissions shall include the following as a minimum: 1) Complete and accurate Scope of Work. For renovations or

    modifications to existing systems the areas of work shall be clearly identified on submitted documents.

    2) Complete description data indicating listed or approved products for all system components.

    3) Complete sequence of operations of all functions of the system. 4) Details of system security levels and access methodology. 5) Detailed description of the functions and displays of the main

    operators console. 6) A list of every system address provided for purposes of alarm

    initiation, status monitoring, supervised signaling, and auxiliary

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 14 of 29

    controls shall be provided to the local site activity responsible for the alarm system.

    7) Detailed description of alarm functioning and hard copy print out log of trouble and alarm conditions.

    8) Detailed operational description of the audible evacuation system including built-in tones, messages, and main console microphone unit.

    9) Complete system-wiring diagrams for all components and interfaces to equipment supplied by others.

    10) Completed building plan view showing location of all devices and wiring runs.

    11) A listing of the manufacturers representatives for installation, coordination and service.

    12) Standby battery, voltage drop, and current load calculations. d. The installation shall be in accordance with:

    1) Approved submittals. 2) Contract drawings and specifications. 3) All applicable requirements of the referenced codes and standards. 4) Current recommendations of the equipment manufacturer.

    e. Systems that are connected to a Ford Global Communication Center (GCC) Station shall have all device labeling approved in writing by GCC and local plant personnel prior to system programming. DO NOT connect any points to GCC Station without their approval. The installing contractor will bear any cost, time, or funding associated with any system label reprogramming due to failure to provide approved labels.

    f. Non-central station system descriptors only need to be approved by the local plant personnel.

    g. Only certified technicians (NICET, national or state license, or certified by the alarm system manufacturer) skilled in this type of work shall be used to perform installation work.

    h. Factory trained technicians shall be used for the supervision of installation and all required system software additions/changes.

    i. The contractor shall hold timely (recommended weekly) site meetings to address and resolve any issues that arise during installation. Review of compliance to design specifications and approved drawings, along with

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 15 of 29

    all revisions to drawings, is required during these meetings. The contractor shall provide meeting minutes to all attendees within 72 hours.

    2. System Power Requirements a. All fire alarm equipment supplied from plant power shall be served by a

    dedicated branch circuit. Non-fire alarm system equipment shall not be permitted on the same branch circuit.

    b. The breaker shall be clearly labeled Fire Alarm System and mechanically protected against unauthorized switching.

    c. The contractor shall be responsible for all necessary 120 volt (or 220 volt) wiring. The contractor shall utilize a spare breaker or supply a new circuit breaker of the correct type and size if no spares are available. The contractor shall verify the circuit breaker is not switchable by the energy management system.

    d. All 120 volt (or 220 volt) wiring shall comply with Fords Sections 16000 and 16400 requirements, and shall be provided and installed as recommended by the equipment manufacturer.

    e. Emergency Power 1) The secondary (back up) power supply shall be capable of a

    minimum 24 hours of standby power for all system components, followed by 5 minutes (15 minutes for voice systems) of full fire mode operation. Full fire mode operation includes: a general alarm audible signal, alarm strobe light activation, and any auxiliary alarm functions. The system shall automatically transfer to the standby batteries upon power failure. All battery charging and recharging operations shall be automatic.

    2) All fire alarm equipment shall be supplied by emergency power circuits when available.

    3. System Wiring Requirements a. All wiring for this system shall be separate and distinct from all other

    wiring in the facility. It shall not share raceways or cable trays and shall not be bundled with other cables.

    b. All raceway fittings, conduit fittings, pull boxes and similar items containing wiring for this system, where exposed, shall be painted red per Ford Specifications. It is not intended to paint the entire raceway or conduit.

    c. All boxes in other than office space shall be NEMA 12 (or, in Canada, Code gauge galvanized steel, EEMAC Type 12) without holes inside the building and NEMA 4X outside the building.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 16 of 29

    d. Any new underground and exposed exterior wiring shall be in rigid galvanized steel conduit, per Ford Section 16400.

    e. All wiring shall be appropriately color-coded and permanent wire markers shall be used for identification at each termination. The color-coding shall be maintained consistent throughout the project.

    f. All wires shall be continuous and there shall be no splices. Terminations shall utilize terminal blocks or insulated crimp connectors. T-taps are not permitted.

    g. All wiring in hazardous areas shall be in rigid, galvanized steel conduit using explosion proof fittings, boxes, devices, etc. rated for Class I Division I ( E.U. Class 0) environments.

    4. Wiring a. All wiring and cable shall be UL listed for use in fire alarm and occupant

    notification systems. b. All devices shall be labeled with a marking that will not fade or wash off.

    This label shall include the system program address of the device. c. All system wiring shall be copper or fiber optic. d. All system wiring shall be installed in a workmanlike manner, and run

    parallel with or perpendicular to building steel. e. All wiring shall be protected from damage. Acceptable methods of

    installation include: 1) General Requirements

    a) Support wiring properly as indicated in NFPA 70 and 72. b) Protect wiring from mechanical damage per Sketches 4 and

    5. c) Wiring installed in areas subject to temperatures greater

    than 71C (160F) shall be listed for the application. d) All wiring shall be installed in strict compliance with all

    the provisions of NEC Article 760 A and C, Power-Limited Fire Protective Signaling Circuits or if required may be reclassified as non-power limited and wired in accordance with NEC-Article 760 A and B.

    2) Above bottom of truss in plants and warehouses a) Open wiring in bridle rings, metal raceways, and/or cable

    trays is acceptable.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 17 of 29

    b) Change of direction shall be by a 90 conduit bend, a weather head connection, or a conduit connector.

    3) Below bottom of truss in plants and warehouses All wire shall be in minimum 19 mm (3/4 in) conduit a) Wiring less than 3 m (10 ft) above the floor shall be in

    rigid conduit. b) EMT is acceptable for wiring more than 3 m (10 ft) above

    the floor. 4) Offices and similar areas

    a) Wiremold or EMT is acceptable for offices. b) Install plenum rated cable or the equivalent above

    suspended ceilings or within walls, as required by the local code.

    5) Underground a) Wiring installed underground shall be direct burial wire in

    Schedule 80 PVC pipe. b) Underground conduit shall utilize at least Schedule 80

    conduit. Where conduit will pass beneath a roadway carrying truck traffic or beneath a railroad track, concrete encasement shall be required. Underground conduits in concrete shall be a minimum of 25 mm (1 in) PVC Schedule 80 and shall be buried a minimum of 3.1 m (42 in) below finished grade. Where conduits are laid in the same trench with others, they shall be separated at least 5 cm (2 in) one from the other. Whenever entering or exiting a building, and 1.5 m (5 ft) beyond the building, rigid galvanized conduit shall be used.

    c) Conduits shall be not more than 50% filled with wires. Pull wires for future additions shall be provided.

    d) All conduits run underground shall have marker tape installed 0.3 m (12 in) above the conduit. Refer to Ford Section No. 16000 for additional requirements for installation of underground conduits and marking.

    f. Provide lightning protection as follows: 1) Furnish and install lightning protection devices on all fire alarm

    circuits that extend beyond the main building. The isolator modules shall be provided at the location the circuit leaves the first building and again as it enters the second building.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 18 of 29

    2) The lightning protection devices shall be located as close as practical to the point at which the circuits leave or enter a building and be located at a height serviceable from the floor level.

    IX. ACCEPTANCE TESTING REQUIREMENTS A. Contractor Pre-Testing

    1. Prior to any testing, the system shall be connected to primary power for a minimum of 2 weeks.

    2. System acceptance test procedures and sequence of testing for the entire system shall be submitted to the owner prior to the scheduling of any tests.

    3. Upon completion of the review and approval of these test procedures and of the sequence of operation by the owner, the installing contractor and equipment fire alarm supplier shall perform a pretest prior to the scheduled acceptance test.

    4. Upon documented or owner witnessed successful completion of the pre-test, the acceptance tests shall be scheduled.

    5. The contractor shall provide all necessary equipment and materials for testing; including equipment for airflow differential testing required to verify proper duct detector location and orientation.

    6. System testing shall be performed with test instruments and procedures required by the manufacturer, and in full conformance with NFPA guidelines. Test instruments shall be calibrated per the manufacturers recommendations.

    7. The contractor shall demonstrate proper operation of all systems, system components, devices, and functions, including attainment of prescribed dBA sound levels, during the acceptance tests. Test all devices for proper alarm and trouble indication at the FACP and at all remote annunciation locations.

    8. The contractor shall submit a report certifying that the installation is in full compliance with the contract documents and NFPA 72. The test reports shall include the following: A complete list of all equipment installed. Certification by the contractor and manufacturer's representative that all

    equipment is properly installed and functional, and conforms to the requirements of this bulletin.

    Certification by the contractor that all individual zones and devices have been tested for proper alarm, annunciation, control, and supervision.

    Technician's name, company, and date of test. Floor map/log of sound level test results (dBA).

    B. Owner Acceptance Tests

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 19 of 29

    1. The contractor shall coordinate all testing with the owner. If required, perform testing before or after regular working hours at no additional charge to the owner. This applies to all system testing.

    2. All costs associated with retests shall be the responsibility of the contractor. 3. As-built drawings shall be provided prior to the owners acceptance testing. 4. A full review and verification of as-built drawings, alarm point labels, and

    secondary power supplies shall be conducted. 5. A full functional test shall be conducted in the presence of the owner, the

    Corporate Fire Protection Engineer and the Loss Prevention Service Provider. Provide a minimum of 14 days advance notice of this test to the Loss Prevention Service Provider and the owner. This functional test shall include: A complete operational test of all system devices. A functional test of the system software and programming. Testing shall conform to the requirements of NFPA 72. The contractor shall provide all personnel, equipment, and materials necessary to accomplish the test.

    C. Final Acceptance Testing 1. Upon completion of the owner acceptance testing, the final acceptance test shall

    be performed in the presence of the local authority having jurisdiction and the owner.

    2. The final acceptance test shall include a complete test of all system devices and functions, and any additional testing requested by the authority having jurisdiction and the owner.

    3. The contractor shall provide all personnel, equipment, and materials necessary to accomplish the test.

    X. CERTIFICATION, DOCUMENTATION, AND TRAINING REQUIREMENTS Note: 15% of final payment will be withheld pending completion to the satisfaction of the

    owner of corrections noted during testing and receipt of the drawings and document requirements of this section. At the owners discretion, and with the concurrence of Corporate Fire Protection Engineering and Purchasing, this requirement may be reduced provided the contractor can demonstrate final project completion is delayed beyond their control.

    A. Certification 1. Upon successful completion of all testing, the contractor shall present the owner

    with a completed copy of the NFPA Fire Alarm System Certification and

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 20 of 29

    Description form (per NFPA 72). The contractor and the authority having jurisdiction signatures are required to certify system completion and acceptance.

    2. Upon satisfactory completion of system acceptance testing, provide UL Field Certification (North America only) or EN-54 Field Certification (Europe only) for all new fire alarm system installations and when existing fire alarm systems are refurbished, updated, and/or renovated. The fire alarm equipment supplier shall be authorized by Underwriters Laboratory to provide the UL certification. This is only required for the first year after installation.

    3. A copy shall also be sent to the Loss Prevention Service Provider. B. Documentation

    The owner shall receive the following documentation prior to releasing the retention compensation. 1. Fire Alarm System pre-test report described in Section IX.A.8. of this bulletin 2. A statement of a 2 year warranty including the date of warranty termination.

    The warranty period begins after final acceptance testing and correction of noted items.

    C. Operations and Maintenance Manuals Note: All information shall be provided in the local language. 1. The contractor shall provide a minimum of six copies of Operation and

    Maintenance (O&M) manuals (in indexed, three-ring binders) for all equipment furnished.

    2. O&M Manuals shall provide the name and phone number (24 hour) of the person to be called in the event of equipment failure.

    3. O&M Manuals shall contain manufacturers' data sheets and wiring diagrams for all products furnished and installed under this contract.

    4. O&M Manuals shall include detailed instructions to permit troubleshooting, diagnosis, and repair to the circuit-board replacement level for all systems. The instructions shall be site-specific.

    5. O&M Manuals shall include detailed instructions regarding recommended preventive maintenance and testing procedures, including software instructions for generating smoke detector status reports.

    6. O&M manuals shall be site-specific and not generic in nature. Submitting the equipment manufacturers installation manual is not satisfactory.

    D. As Built Drawings 1. All drawings shall be provided in the local language. 2. All drawings shall be supplied in AutoCAD format. Three paper copies of all

    drawings shall be supplied on D size (24 by 36) and on 11 x 17 in the

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 21 of 29

    manuals. Block diagrams and schematics shall also be furnished both as 11 x 17 in manuals and on D size. Three sets of electronic media files for all drawings shall be supplied.

    E. Training 1. All training shall be provided in the local language. 2. The contractor shall provide a minimum of 9 hours training (3 hours per shift)

    for the facility Engineering staff, Security officers, and all other personnel (including local Fire Department representatives) required to operate or respond to the Fire Alarm system.

    3. The contractor is also responsible for providing training regarding normal daily operation of fire alarm system for designated users and facility tenants.

    4. Training shall be conducted at dates and times agreed upon by the contractor and the owner.

    5. Only engineers or technicians highly skilled in the systems, and certified by the manufacturer as qualified to train in the particular systems, shall be used to conduct this training.

    6. Ford reserves the right to document or otherwise record (audio and/or visual) the session(s).

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 22 of 29

    Fire Alarm System Evaluation Work Sheet Appendix A

    Site Information

    Building/Plant Name Ford ID Location Date System Basics

    Manufacturer

    Model

    Ranking Poor Fair Good System Score

    Weighted Score

    Max Score Weight 0-1 2-3 4-5 5 System Design and Architecture

    Age of System 5 > 25 Years < 25 to 15 Years < 15 Years 0 0 25 Initiating Devices 2 NFPA 72 Deficient Meets NFPA 72

    Meets Bulletin 32 0 0 10

    Notification Appliances 2 NFPA 72 Deficient Meets NFPA 72 Meets Bulletin

    32 0 0 10

    Subtotal 0 45 Frequency of Service Issues

    Control Panels/Communications 8 Weekly Monthly Quarterly 0 0 40

    Nuisance Alarms (Caused by System Electrical Issues) 3 Weekly Monthly Quarterly 0 0 15

    Trouble Alarms 1 Weekly Monthly Quarterly 0 0 5

    Subtotal 0 60 Results of Testing

    Initiating Circuits 7 3 or More Less than 3 No Problems 0 0 35

    Notification Circuits 3 3 or More Less than 3 No Problems 0 0 15

    Panels (Communication Errors) 5 Comm Errors - Multi- Nodes Comm Errors -

    Single Node No Problems 0 0 25

    Subtotal 0 75

    Manufacturer Support

    Service/Design 3 Out of Service Short Supply Available 0 0 15

    Tech Response 10 Out of Service Short Supply Available 0 0 50

    Parts Availability 8 Out of Service Short Supply Available 0 0 40

    Subtotal 0 105

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 23 of 29

    Local Code Compliance

    System is Compliant with Local AHJ Requirements 5

    Notification Appliances Are

    Inadequate

    Inadequate Number of Initiating Devices

    Meets Local Requirements 0 0 25

    Future Building Use 3 Building

    Additions Planned

    No Change No future site plans 0 0 15

    Subtotal 0 40 System Evaluation Score 0% Total 0 325

    Evaluation Scoring

    Total Score 0 Possible Score 325 Percentage 0%

    Score Between

    0% -- 50% Replace System 50% -- 65% Repair as Required/Replace or Upgrade

    65% -- 80% Repair/Upgrade as Required

    81% -- 100% Continue to Maintain System

    Notes/Comments

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 24 of 29

    Bulletin 32 Appendix: Condition/Alarm Tone/Voice Announcement/Employee Action to be Taken Chart

    Condition Alarm Tone Voice Announcement Employee Action to Be Taken Evacuation (Total)

    Horn Temporal Code 3 for 10 Seconds

    Attention, Attention, an emergency has been reported. You are to leave the building by the nearest exit or exit stairway. Walk to the nearest exit. DO NOT USE ELEVATORS. Repeat 3 times, Pause Horn Temporal Code 3Repeat Until Silenced

    All building occupants are to leave the building by the nearest exit. Assemble outside at the designated evacuation areas. Report to supervision or evacuation officer. Do not reenter the building until the all clear is given.

    Weather Alert Hi-Low for 10 Seconds Attention, Attention, a severe storm emergency has been reported. Walk to the nearest designated shelter area immediately. Play 3 times. Pause. Play tone and repeat until silenced.

    All building occupants are to remain inside of the building. Move to designated shelter areas away from windows. Await further instructions.

    All Clear Continuous Horn Attention, Attention, The building emergency condition has been cleared. Please return to your normal activities. Repeat 3 times

    All building occupants return to the building and resume work.

    As a local option a facility may have the following: Earthquake Take shelter Partial building evacuation (High Rise or Large Assembly and Manufacturing Locations All voice announcements are to be in the local language(s) and the exact text is to be approved by the local

    Security/Fire Protection Activity. Tones and text shall comply with local laws, codes and customs, if any conflict exists between this document and the

    local legal requirements.

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 25 of 29

    Category A and B Facilities

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 26 of 29

    Category A, B, and C Facilities

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 27 of 29

    Category A, B, and C Facilities

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 28 of 29

    Category A and B Facilities

  • Fire Protection Bulletin No. 32 Fire Alarm Systems

    Page 29 of 29

    Category A, B, and C Facilities