    M o d b u s I / O

    BusWorks

    900MB Series

    Modbus-RTU I/O

    Introduction

    Series overview . . . . . . . . . . . . . . . . . . . . . .Page 50

    Discrete I/O Modules

    901MB active low inputs . . . . . . . . . . . . . . .Page 54

    902MB sinking outputs . . . . . . . . . . . . . . . . . . . .54

    903MB active low inputs, sinking outputs . . . . . .54

    904MB active high inputs . . . . . . . . . . . . . . . . . . .56

    905MB sourcing outputs . . . . . . . . . . . . . . . . . . .56

    906MB active high inputs, sourcing outputs . . . .56Analog I/O Modules

    913MB DC current input . . . . . . . . . . . . . . .Page 58

    914MB DC voltage input . . . . . . . . . . . . . . . . . . .58

    917MB DC current output . . . . . . . . . . . . . . . . . .60

    918MB DC voltage output . . . . . . . . . . . . . . . . . .60

    924MB Thermocouple/millivolt input . . . . . . . . . .62

    932/934MB RTD input . . . . . . . . . . . . . . . . . . . . .64

    942MB Frequency/counter input . . . . . . . . . . . . .66

    Accessories

    Software interface package . . . . . . . . . . . . .Page 69

    Power supplies . . . . . . . . . . . . . . . . . . . . . . . . . .69Mounting hardware . . . . . . . . . . . . . . . . . . . . . . .69

    RS-232/485 signal converter . . . . . . . . . . . . . . . . .70

    RS-485 network repeater . . . . . . . . . . . . . . . . . . .70

    Technical Documentation

    Application notes . . . . . . . . . . . . . . . . . . . . .Page 71

    Dimension diagrams . . . . . . . . . . . . . . . . . . . . . . .68

    901/2/3 904/5/6 913/914 917/918 924 932/934 942

    DISCRETE INPUTS

    Active low input x

    Active high input x

    ANALOG INPUTS

    DC voltage/current input x

    DC millivolt input x

    Thermocouple input x

    RTD/resistance input x

    Frequency input x

    AC current input (requires external sensor) x

    DISCRETE OUTPUTS

    Sinking output (low-side switch) x

    Sourcing output (high-side switch) x

    Limit alarm (open-drain MOSFETs or relays) x x x x x

    ANALOG OUTPUTS

    DC voltage/current x

    POWER CONFIGURATION

    DC-powered x x x x x x x

    AC-powered x x x x x x x

    Discrete I/O Modules Analog I/O Modules

  • 8/6/2019 Busworks Section

    2/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    50

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    900MB SeriesModbus-RTU

    I/O Modules

    The 900MB series is a high-performance line ofmulti-function I/O modules. These units featureuniversal input/output ranges and an intelligentmicrocontroller to provide extreme flexibility andpowerful monitoring and control capabilities.Select from a variety of analog and discrete I/Omodels to meet your application requirements.

    To ensure unsurpassed performance, these I/Omodules employ the latest digital technology.State-of-the-art flash microcontrollers plus opti-

    cally isolated input, output, power, and networkcircuits increase noise/transient immunity andprevent ground loops. Status LEDs providediagnostic feedback and visually indicate whichchannels are outside their calibrated range.

    Sophisticated watchdog timer functions allowthe application to define the module's failsafeoutput state. The watchdog timer invokes thefailsafe condition when communication betweenthe host and module exceed a duration specifiedby the application. For further security, a secondhardware watchdog timer monitors the micro-

    controller for failed operations or a lock-upcondition and automatically resets the unit.

    I Special Features

    I High-speed RS-485 communication allows datatransfers up to 115K baud

    I Modbus RTU protocol interfaces to popular

    HMI and SCADA software packages

    I Wide-range, polarity-insensitive power supplysupports 10-36V DC and 24V AC sources

    I Powerful watchdog timers allow user-definedfailsafe state when host communication is lost

    I Isolation eliminates potential ground loopsbetween I/O, power, and network circuitry

    I Default switch allows user to set module toknown communication parameters

    I Menu-based Windows configuration software

    simplifies setup and trouble-shooting

    I Discrete I/O

    These modules monitor discrete levels of variousdevices and/or provide on/off control capabilitiesdepending on the model selected. Each moduleoffers high channel density to save space andkeep costs low. Models are available with twelveinputs, twelve outputs, or twelve bidirectionalI/O channels.

    InputsI Active-high inputs, 0 to 35V DCI Active-low inputs, 0 to 35V DC

    OutputsI Sourcing outputs, 5.5 to 35V DC, 250mAI Sinking outputs, 0 to 35V DC, up to 1A

    FunctionsI Monitor discrete state or levelI On/off controlI Activate audible or visual alarmsI Transmit discrete data to other control systems

    I Analog Input

    These units monitor DC or thermocouple sensorinputs and provide alarm outputs if conditionsexceed user-defined limits. Each module has four

    analog input channels and four discrete outputsfor independent local alarms or host-controlledon/off switching.

    InputsI DC currentI DC voltageI DC millivoltsI ThermocoupleI RTD/resistanceI FrequencyI AC current

    OutputsI Open drain MOSFETs (1A solid-state switches)

    FunctionsI Temperature monitoringI Process variable measurementI Limit alarms with high and/or low setpointsI On/off control

    I Analog Output

    Analog output modules are ideal for controllinga wide variety of industrial machinery. The hostdefines the output of voltage or current signals

    to control speed, flow, temperature, frequency,level, force, torque, intensity, and many otherproperties. Each module has four analog outputchannels plus four discrete outputs for on/offswitching applications.

    OutputsI DC voltageI DC currentI Open drain MOSFETs (1A solid-state switches)

    FunctionsI Write data to local displays or recorders

    I Control drives, valves, and other equipmentI Transmit discrete data to other control systemsI On/off control (alarms)

    Modbus I/O Network

  • 8/6/2019 Busworks Section

    3/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    51

    M o d b u s I / O

    FREQUENCYINPUT

    (W/ALARMS)

    Frequency/Counter

    TTL, dry contact, high/low-sidetransistor switches, magnetic

    pickups, proximity sensors

    ANALOGINPUT

    (W/ALARMS)

    ANALOGOUTPUT

    (W/ALARMS)

    TEMPERATUREINPUT

    (W/ALARMS)

    901902

    903

    904

    905

    906

    On/Off Monitoring & Control, High/Low Status & Switching

    motors, pumps, heaters, solid-state relays, other discrete devices

    Voltage/Current Signal Generation

    variable frequency drives, valves, motors, positioners, displays, recorders

    Voltage/Current Signal Measurementsensors: flow, level, speed, pressure, etc.

    Thermocouple/Millivolt/RTD

    sensors: temperature, O2, cathodic monitor, DC shunt

    DCS

    OI Terminal

    PLC

    Workstation

    RemoteWorkstation

    Server

    Server

    EXECUT

    IVENE

    TWORK-Busi

    nessOp

    eration

    s

    PLANTN

    ETWORK

    -Moni

    toringand

    Control

    I/ONE

    TWORK

    -Modbu

    s-RTUto

    Sensors

    andAct

    uators(RS-48

    5,4000

    ft,32de

    vices,11

    5Kbps)

    DISCRETEI/O

    HMI SoftwareCitectIconicsIntellutionLabViewWonderware

    Modems

    Acromag 900MB Series I/O Modules901MB 12 DI (active low) 913MB 4 AI (mADC), 4 DO902MB 12 DO (sinking) 914MB 4AI (VDC), 4 DO903MB 12 DI/DO (as above) 917MB 4 AO (mADC), 4 DO904MB 12 DI (active high) 918MB 4 AO (VDC), 4 DO905MB 12 DO (sourc ing) 924MB 4 TC/mV, 4 DO906MB 12DI/DO (as above) 934MB 4 RTD, 4 DO 942MB 2 Freq, 2 DO

    SimplifiedEnterpriseDiagram

  • 8/6/2019 Busworks Section

    4/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    52

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    I Software Support

    Series 900 I/O modules are compatible withpopular Human-Machine Interface (HMI) softwarepackages that support Modbus communication.

    The I/O modules may be configured using genericdrivers provided with the HMI software to accessthe Modbus register maps.

    A list of popular third-party HMI softwaremanufacturers:I AB/Rockwell I National InstrumentsI Citect I SteeplechaseI Iconics I Think and DoI Intellution I Wonderware

    Acromag also offers a configuration utility forfaster and easier setup. This software provides anintuitive approach to select configuration options

    for your application. Familiar Windows pull-downselection menus and fill-in-the-blank fields speedyou through a few brief configuration screens. Noprogramming is required. The utility also helpsyou monitor and verify proper operation of themodule outside the main control software. Thisdiagnostic tool provides a simple alternative tousing Modbus register maps.

    I Easy Configuration

    Acromags configuration software is designed foroffline setup at a bench or in the field with a lap-top computer. Configuration settings can besaved to a file or printed for archival purposes.Setup is quick and easy using the steps below.

    1) Connect the module to a PC with the cableand RS-232/485 converter (typical system).Apply power.

    2) In the software, open a saved configuration

    or select the Module Upload option.3) Configure the operating parameters as

    desired and download the configuration intothe module.

    4) Use the softwares Test function to verifymodule operation and communication.

    5) Install the module on the network.

    Acromags configuration software can be used offline to set up a module and save the configuration to a file.

    Limit alarms are easy to configure with fill-in-the-blank fields in engineering units for high/low alarm setpoints.

    Module Configuration

    AcromagConfiguration Software

    for Windows

    RS-232/485 Converter and

    RS-485/3-wire Cable

    900MB Module(all models)

  • 8/6/2019 Busworks Section

    5/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    53

    M o d b u s I / O

    I Accessories

    I Configuration Tools

    Acromag provides a full set of tools to help youget your modules set up and ready to install.

    Software Interface PackageSee Page 69 for more information.Includes the following:- Configuration Software Utility- Instruction manuals- Serial port converter- Interface cable

    I Network Devices

    Everything you need to drive your network isavailable from Acromag: i solators, converters,signal boosters, and power sources.

    Universal 50W Power Supply (Page 69)

    Isolated RS-232/485 Converter (Page 70)

    Isolated RS-485 Network Repeater (Page 70)

    I Mounting HardwareInstallation is a snap with Acromag accessories.

    DIN RAIL Bars (Page 69)

    19" Rack-Mount Kit (Page 69)

    I General ModuleSpecifications

    I Communication Interface

    Network Communication

    Modbus-RTU protocol, RS485 (3-Wire). StandardProtocol implementation as defined under ModiconModbus Reference Guide PI-MBUS-300 Rev. J.Reference: http://public.modicon.com.Search on: PI-MBUS-300 for technical publication.

    Baud Rate2400, 4800, 9600, 14.4k, 19.2k, 28.8k, 38.4k, 57.6k,76.8k, or 115.2k baud. Default 9600 baud.

    Module Addressing0 to 247, selectable. Default address 247.

    Network Distance4000 feet without network repeater.

    NodesSupports up to 32 modules without the use of anetwork repeater.

    ParityOdd, even, or none. Default setting none.

    Stop BitsOne with parity, one or two with no parity.Default setting is two s top bits with no parity.

    Watchdog Timer (Hardware)A hardware watchdog timer is built into each moduleto perform a reset if the microcontroller fails to returnfrom an operation in a timely manner or "locks up".

    Watchdog Timer (Network Communication)All modules have a communication watchdog timerfunction. The watchdog timer is configurable fortimeout periods of up to 18 hours. This timerfunction monitors I/O communications with the hostcontroller. In the event of lost communications, output

    ports optionally reset to a user-defined state or level.The watchdog timer restarts with a read/write to anI/O channel.

    I Environmental

    Ambient TemperatureOperation: -25C to +70C (-13F to +158F).Storage: -40C to +85C (-40F to +185F).

    Relative Humidity5 to 95% non-condensing.

    Radiated Field Interference Immunity (RFI)Complies with EN61000-4-3 Level 2 and EN50082-1(3V/M, 80 to 1000MHz AM and 900MHz keyed).

    Electrical Fast Transient Immunity (EFT)EN61000-4-4 Level 1 and EN50082-1(0.5KV power, signal lines).

    Electrostatic Discharge (ESD) ImmunityEN61000-4-2 Level 3 and EN50082-1(8KV/4KV air/direct discharge).

    Surge ImmunityEN61000-4-5 (0.5KV) and EN50082-1.

    Radiated EmissionsMeets EN50081-1 for Class B equipment.

    ApprovalsCE marked. UL listed for US and Canada.Class I; Division 2; Groups A, B, C, D.

    I Enclosure/Physical

    EnclosureSelf-extinguishing NYLON type 6.6 polyamide thermo-plastic UL94 V-2, color beige; general purpose NEMAType 1 enclosure.

    Connectors (Removable Terminal Blocks)Wire Range: AWG #12-24, stranded or solid copper.

    Dimensions1.05W x 4.68H x 4.35D inches26.7W x 118.9H x 110.5D mm.

    DIN Rail MountingDIN rail mount, Type EN50022; "T" rail (35mm).

    Shipping Weight1 pound (0.45 Kg) packed.

  • 8/6/2019 Busworks Section

    6/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    54

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    901/902/903MBMulti-Channel

    Discrete I/OModules

    Active-Low InputsSinking Outputs(Low-Side Switching)

    Models901MB: 12 input channels902MB: 12 output channels903MB: 12 input/output channels

    InputTwelve input channels (901, 903 models only)0 to 35V DC

    OutputTwelve output channels (902, 903 models only)O to 35V DC

    Network CommunicationModbus-RTU high-speed RS-485

    Power Requirement10 to 36V DC,

    24V AC

    ApprovalsCE marked. UL, cUL listedClass I; Division 2; Groups A, B, C, D.

    I Description

    These modules provide twelve discrete inputand/or output channels. Isolation separates theI/O, power, and network circuits. Networkcommunication adheres to the industry-standardRS-485 Modbus RTU protocol. Both AC and DCpower sources are supported with wide range,nonpolarized, diode-coupled terminals.

    The open-drain outputs are intended for current-sinking or low-side switching applications. The

    buffered inputs are active-low. These models arethe complement of the 904, 905, and 906 unitswhich have open-source, high-side outputswitches and active-high inputs. Socketed pull-upresistors are easily removed or exchanged to sat-isfy your application requirements.

    The 903MB model has twelve input/outputpoints that may be used as inputs or outputs ona bit-by-bit basis. Outputs may be read back toverify output settings.

    Combining flexible I/O types, wide I/O ranges,and a network interface in a single package,

    makes this instrument extremely powerful.Multi-channel design adds cost-efficiency andallows high-density mounting. Plus, safe, ruggedconstruction makes these modules reliable foruse in both control room and distributed field I/Oapplications. Custom module configurations arealso possible (consult factory for details).

    I Special Features

    I Standard Modbus RTU protocol with high-speedRS-485 communication (up to 115K bps)

    I Twelve I/O channels in a single inch-wide unitreduces system costs and saves panel space

    I High-voltage, high-current, open-drain outputsenable direct (low-side) control of externaldevices

    I High-voltage buffered inputs monitor discrete

    levels from a variety of industrial devices

    I Tandem input/output circuitry (903 modelsonly) connects input buffers with open-drainoutputs for convenient loopback monitoring ofthe output state

    I Outputs have built-in over-temperature andover-current shut-down protection, plus activeclamping circuits for switching inductive loads

    I Watchdog timers provide a configurablefailsafe output state for use when hostI/O communication is lost

    I Three-way isolation eliminates potentialground loops between power, I/O, andnetwork circuitry

    I Self-diagnostics monitor microcontroller activityto detect operational failures (lock-up) andexecute a reset to restore communication

    ModbusRS-485

    10-36V DCor 24V AC

    Isolation

    TwelveDiscreteInputs or Outputs

    Power

    Inputs (4)

    or

    Outputs (4)

    Inputs (4)

    or

    Outputs (4)

    Inputs (4)

    or

    Outputs (4)

    High-Density Discrete I/O ModuleModbus/RS-485

  • 8/6/2019 Busworks Section

    7/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    55

    M o d b u s I / O

    I Performance

    I Discrete Inputs(901 & 903 models only)

    Input Type

    12 active-low, buffered inputs, with a common con-nection. Inputs include transient suppression devicesand series connected 100K ohm resistors, plus diodeover-voltage clamps to the internal +5V supply.

    Input Signal Voltage Range0 to 35V DC, maximum.

    Input Current293A, typical at 35V DC.

    Input Signal ThresholdTTL compatible with 100mV of hysteresis, typical.Low-to-High threshold is 1.7VDC, High-to-Low is1.6VDC, typical. Limited to TTL levels of 0.8VDC(max. LOW level) and 2.0VDC (min. HIGH level).

    Input Resistance100K ohms, typical.

    Input Hysteresis100mV DC, typical.

    I Discrete Outputs(902 & 903 models only)

    Output Type12 independent, open-drain, DMOS MOSFET switcheswith a common source connection that operate aslow-side switches.

    Output Voltage Range0 to 35V DC max. (0 to 500mA/channel continuous).External voltage source required.

    Output ON Resistance0.28 ohms maximum.

    Output Response TimeForce Single Coil: Output updates within 250s ofreceipt of a command.

    Force Multiple Coils: First coil updates in 250s,followed successively by additional coils every 180s.

    I General

    I/O Pull-ups and Socket5.6K ohm pull-up resistor SIPs are installed in socketsat each port (four-channels per port).

    Excitation (per port)External excitation voltage for each four-channel portis limited to 35V or less.

    Supported Modbus CommandsThe command/response protocol for communicatingwith this module adheres to the Modbus/RTU standardfor the following Modbus Functions.

    Read Coil (Output) StatusRead Input StatusRead Holding RegistersForce Single Coil (Output)Preset Single RegisterReset SlaveForce Multiple Coils (Outputs)Preset Multiple Registers

    Report Slave IDLED IndicatorsLEDs indicate power, status, and discrete level.

    Power Requirements10 to 36V DC,22 to 26V AC.

    Supply Current

    Supply Current Draw10V DC 80mA maximum24V DC 40mA maximum24V AC 70mA rms maximum

    Isolation1500V AC for 60 seconds or 250V AC continuous.

    3-way isolation between I/O, network, and powercircuits.

    I OrderingInformation

    Models901MB-0900

    Discrete input module902MB-0900Discrete output module

    903MB-0900Discrete input/output module

    Accessories900C-SIPConfiguration Software Interface Package(includes software CD-ROM for Windows, RS-232/485converter, and RS-485/three-wire cable)

    5034-225USB-to-RS232 adapter. See page 68 for more info.

    TBK-B02

    Optional terminal block kit, barrier strip style, 4 pcs.TBK-S02Optional terminal block kit, spring clamp style, 4 pcs.

    PS5R-D24Power supply (24V DC, 2.1A).See Power Supplies on Page 199.

    For more information on software, network hardware,and mounting accessories, please see Pages 69-71.

    DIGITAL INPUT CONNECTIONS (ACTIVE LOW) DIGITAL OUTPUT CONNECTIONS

    RTN

    +5V

    INP

    INP

    RTN

    CH 0

    RTN

    CH 1

    CH 2

    CH 3

    5V TTL LOGIC - INPUT CAN BE PULLEDUP INTERNALLY OR EXTERNALLY

    DIGITAL I/O

    SHARES

    RETURN

    EXC1

    TB1

    INTERNAL INPUT

    PULL-UPS ARE PRESENT

    DIGITALIN

    orOUT

    CH11

    RTN464544CH10

    RS485

    41

    42

    43

    EXC3

    TB4

    CH 8

    CH 9

    35

    36

    COM

    COM

    TB1DIGITALIN

    orOUT

    12

    11

    CH 0

    EXC1

    CH 1131415

    CH 2

    CH 3

    RTN16

    DIGITALINorOUT

    TB221

    EXC2

    CH 4

    22

    24

    23

    CH 6

    CH 5

    RTN

    CH 7

    2526

    3433D

    D

    31

    32

    TB3

    PWR

    DIGITAL

    I/O

    10 TO 36V DC

    OR 24V AC

    NON-POLARIZED

    DIGITAL

    I/O

    DIGITAL

    I/O AC/DC

    POWER

    NETWORK

    COMMUNICATION

    903MB shown.

    901MB & 902MB

    are similar.

    A

    B

    TB3

    TB2

    TB4

    TB1

    CH 0

    RTN

    CH 1

    CH 2

    CH 3

    EXC1

    TB1

    OUT

    RTN

    DIGITAL I/O

    SHARES

    RETURN

    EXC

    DUP

    SPST

    RELAY

    12-24V DC,

    TYPICAL

    +

    RTN

    EXC

    RTN

    INP

    5-35V

    V

    RTN

    I/O

    902MB/903MBON

    TO OTHER 3

    CHAN OF PORT100K

    OFF

    EXC903MB

    +5V

    LOAD

    Optional terminal blocks: barrier strip (left) andspring clamp (right). Cage clamp terminal is standard.

  • 8/6/2019 Busworks Section

    8/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    56

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    904/905/906MBMulti-Channel

    Discrete I/OModules

    Active-High InputsSourcing Outputs(High-Side Switching)

    Models904MB: 12 input channels905MB: 12 output channels906MB: 12 input/output channels

    InputTwelve input channels (904, 906 models only)0 to 35V DC

    OutputTwelve output channels (905, 906 models only)5.5 to 35V DC

    Network CommunicationModbus-RTU high-speed RS-485

    Power Requirement10 to 36V DC,

    24V AC

    ApprovalsCE marked. UL, cUL listedClass I; Division 2; Groups A, B, C, D.

    I Description

    These modules provide twelve discrete inputand/or output channels. Isolation separatesthe I/O, power, and network circuits. Networkcommunication adheres to the industry-standardRS-485 Modbus RTU protocol. Both AC and DCpower sources are supported with wide range,nonpolarized, diode-coupled terminals.

    The outputs are intended for current-sourcing orhigh-side switching applications. The buffered

    inputs are active-high. These models are thecomplement of the 901, 902, and 903 unitswhich have low-side output switches andactive-low inputs. Socketed pull-down resistorsare easily removed or exchanged to satisfy yourapplication requirements.

    The 906MB model has twelve input/outputpoints that may be used as inputs or outputs ona bit-by-bit basis. Outputs may be read back toverify output settings.

    Combining flexible I/O types, wide I/O ranges,and a network interface in a single package,

    makes this instrument extremely powerful.Multi-channel design adds cost-efficiency andallows high-density mounting. Plus, safe, ruggedconstruction makes these modules reliable foruse in both control room and distributed field I/Oapplications. Custom module configurations arealso possible (consult factory for details).

    I Special Features

    I Standard Modbus RTU protocol with high-speedRS-485 communication (up to 115K bps)

    I Twelve I/O channels in a single inch-wide unitreduces system costs and saves panel space

    I High-voltage, high-current, open-sourceoutputs enable direct (high-side) control ofexternal devices

    I High-voltage buffered inputs monitor discrete

    levels from a variety of industrial devices

    I Tandem input/output circuitry (906 modelsonly) connects input buffers with open-sourceoutputs for convenient loopback monitoring ofthe output state

    I Watchdog timers provide a configurablefailsafe output state for use when hostI/O communication is lost

    I Three-way isolation eliminates potentialground loops between power, I/O, andnetwork circuitry

    I Self-diagnostics monitor microcontroller activityto detect operational failures (lock-up) andexecute a reset to restore communication

    ModbusRS-485

    10-36V DCor 24V AC

    Isolation

    TwelveDiscreteInputs or Outputs

    Power

    Inputs (4)

    or

    Outputs (4)

    Inputs (4)

    or

    Outputs (4)

    Inputs (4)

    or

    Outputs (4)

    High-Density Discrete I/O ModuleModbus/RS-485

  • 8/6/2019 Busworks Section

    9/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    57

    M o d b u s I / O

    I Performance

    I Discrete Inputs(904 & 906 models only)

    Input Type

    12 active-high, buffered inputs, with a common con-nection. Inputs include transient suppression devicesand series connected 100K ohm resistors, plus diodeover-voltage clamps to the internal +5V supply.

    Input Signal Voltage Range0 to 35V DC, maximum.

    Input Current293A, typical at 35V DC.

    Input Signal ThresholdTTL compatible with 100mV of hysteresis, typical.Thus, Low-to-High threshold is 1.5VDC, High-to-Low is1.4VDC, typical. Limited to TTL levels of 0.8VDC(max. LOW level) and 2.0VDC (min. HIGH level).

    Input Resistance5.6K ohms with s tandard factory pull-down resistorsinstalled. 100K ohms without pull-downs.

    Input Hysteresis100mV DC, typical.

    Input Response Time500ns for low-to-high, 2S for high-to-low, typical.Microcontroller samples inputs as a group every 10mS.

    I Discrete Outputs(905 & 906 models only)

    Output Type12 independent, open-source, MOSFET switches thatoperate as high-side switches.

    Output Voltage Range5.5 to 35V DC (0 to 250mA/channel continuous).External excitation voltage required.

    Output ON Resistance0.15 ohms maximum.

    Output Response TimeOutputs update within 50ms of a write command andswitch within 5mS of receipt of command. Loopbackresponse (906MB) is 1S low-to high, 5S high-to-low.

    I General

    I/O Pull-downs and Socket5.6K ohm pull-down resistor SIPs are installed insockets at each port (four-channels per port).

    Excitation (per port)External excitation voltage for each four-channel portis limited to 35V or less.

    Supported Modbus CommandsThe command/response protocol for communicatingwith this module adheres to the Modbus/RTU standardfor the following Modbus Functions.

    Read Coil (Output) StatusRead Input StatusRead Holding RegistersRead Input RegistersForce Single Coil (Output)Preset Single RegisterReset SlaveForce Multiple Coils (Outputs)Preset Multiple RegistersReport Slave ID

    LED IndicatorsLEDs indicate power, status, and discrete level.

    Power Requirements10 to 36V DC,22 to 26V AC.

    Supply Current

    Supply Current Draw

    10V DC 90mA maximum24V DC 40mA maximum24V AC 75mA rms maximum

    Isolation1500V AC for 60 seconds or 250V AC continuous.3-way isolation between I/O, network, and powercircuits.

    I OrderingInformation

    Models904MB-0900

    Discrete input module905MB-0900Discrete output module

    906MB-0900Discrete input/output module

    Accessories900C-SIPConfiguration Software Interface Package(includes software CD-ROM for Windows, RS-232/485converter, and RS-485/three-wire cable)

    5034-225USB-to-RS232 adapter. See page 68 for more info.

    TBK-B02

    Optional terminal block kit, barrier strip style, 4 pcs.TBK-S02Optional terminal block kit, spring clamp style, 4 pcs.

    PS5R-D24Power supply (24V DC, 2.1A).See Power Supplies on Page 199.

    For more information on software, network hardware,and mounting accessories, please see Pages 69-71.

    DIGITAL INPUT CONNECTIONS (ACTIVE HIGH)

    DIGITALIN

    orOUT

    45

    46

    TB4

    CH11

    COM

    TB4

    CH 9

    CH10

    CH 8

    444342

    36

    41

    TB3

    EXC3

    10 TO 36V DC

    OR 24V AC

    NON-POLARIZED

    D

    COM

    COM

    D

    RS485

    33

    34

    35

    31

    32

    A

    BPWR

    TB3

    TB1

    DIGITAL

    I/O

    DIGITAL

    I/O

    DIGITALI/O

    TB2

    AC/DCPOWER

    NETWORKCOMMUNICATION

    TB1

    EXC1

    CH 0

    12

    11

    DIGITALIN

    orOUT

    13

    CH 1

    CH 2

    CH 3

    141516 RTN

    TB2

    EXC2

    CH 4

    22

    21

    DIGITALINorOUT

    23

    CH 5

    CH 6

    CH 7

    242526 RTN

    906MB shown.

    904MB & 905MB

    are similar.

    INP

    COM

    INP

    RTN

    +5V

    COM

    INP

    TB1

    RTN

    CH 3

    CH 2

    CH 1

    CH 0

    EXC1

    DIGITAL I/OSHARESCOMMON

    INTERNAL INPUT PULL-DOWNSARE PRESENT

    5V TTL LOGIC INPUT IS ACTIVE HIGHAND PULLED DOWN INTERNALLY

    DIGITAL OUTPUT CONNECTIONS

    CH 0

    RTN

    CH 1

    CH 2

    CH 3

    EXC1

    TB1

    OUT

    RTN

    DIGITAL I/O

    SHARES

    RETURN

    UP TO

    35V DC

    SPST

    RELAY

    +

    RELAY COIL/SOLENOID DRIVER (905MB/906MB)

    LocateSnubberat Coil

    5-35VTypical

    ON (1)

    EXC

    I/O

    RTN

    905MB

    OFF (0)

    R

    TO OTHER 3

    CHAN OF PORT

    CHLED OPEN

    INTERNAL PULL-

    DOWN IS OPEN

    FOR 905MB

    +

    Optional terminal blocks: barrier strip (left) andspring clamp (right). Cage clamp terminal is standard.

  • 8/6/2019 Busworks Section

    10/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    58

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    913/914MBMulti-Channel

    Analog InputModules

    DC Current,DC Voltage orAC Current Input

    Limit Alarms orDiscrete Outputs

    Models913MB: 4 current input channels914MB: 4 voltage input channels

    Input Ranges0 to 20mA DC,10V DC,0 to 20A AC (with 5020-350 sensor)

    OutputFour output channels:Open-drain MOSFETs (1A DC loads)0 to 35V DC

    Network CommunicationModbus-RTU high-speed RS-485

    Power Requirement10 to 36V DC,24V AC

    ApprovalsCE marked. UL, cUL listedClass I; Division 2; Groups A, B, C, D.

    I Description

    This signal conditioner is a four-channel analoginput module with four discrete outputs. Itprovides isolation between input, output, power,and network circuits. Network communicationadheres to the industry-standard RS-485 ModbusRTU protocol. AC and DC power sources aresupported with nonpolarized, diode-coupledterminals.

    The inputs accommodate wide DC voltage or

    current ranges. Flexible discrete outputs operateas alarms or on/off controllers. As limit alarms,each discrete output can be configured with highand/or low setpoints exclusively tied to an analoginput channel. Alarm trips function without hostcommunication enabling low-cost stand-alonealarms, as well as local backup for the primarycontrol system. Otherwise, on/off control isbased on commands issued by the host system.

    Combining flexible transmitter functions, mixedsignal I/O, alarm support, and a network inter-face in a single package, makes this instrument

    extremely powerful. Multi-channel design addscost-efficiency and allows high-density mounting.Plus, safe, rugged construction makes thesemodules reliable for use in both control roomand distributed field I/O applications. Custommodule configurations are also possible (consultfactory for details).

    I Special Features

    I Standard Modbus RTU protocol with high-speedRS-485 communication (up to 115K bps)

    I 16-bit sigma-delta A/D yields 0.1% of rangeresolution and accuracy

    I Four inputs in a single inch-wide modulereduces system costs and saves panel space

    I Four discrete outputs enable local limit alarmsor host-controlled on/off switching

    I Heavy-duty 1A solid-state relays providedependable on/off control of industrial devices

    I Self-calibration lowers maintenance costs byreducing periodic manual calibration checks

    I Watchdog timers provide a configurablefailsafe output state for use when hostI/O communication is lost

    I Four-way isolation eliminates potential groundloops between power, input, output, andnetwork circuitry

    I Self-diagnostics monitor microcontroller activityto detect operational failures (lock-up) andexecute a reset to restore communication

    Modbus

    FourDC Current

    orDC Voltage

    Inputs RS-485

    10-36V DCor 24V AC

    Isolation

    Four

    DiscreteOutputsor

    Limit Alarms

    Power

    Outputs (4)Inputs (2)

    Inputs (2)

    DC Current/Voltage Input Module

    TB1/TB2

    IN+

    IN-

    Red

    Black

    1.35"

    1.05"

    0.375"dia.

    5020-350

    AC Current Sensor Model 5020-350

    For 913MB. Order separately (one per channel).

    Modbus/RS-485

  • 8/6/2019 Busworks Section

    11/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    59

    M o d b u s I / O

    I Performance

    I General Input

    Resolution0.005% or 1 part in 20,000.

    Noise RejectionNormal mode: 40dB @ 60Hz, typical.Common mode: 140dB @ 60Hz, typical.

    Input Filter Bandwidth-3dB at 3Hz, typical.

    Input Conversion Rate180ms per channel.

    I Current Input (913MB)

    DC Current Input RangesRange user-configured. Range selected applies to allchannels.

    0 to 1mA, 0 to 20mA, 4 to 20mA,

    0 to 11.17mA (for use with 5020-350 AC sensor).DC Current Input Resistance49.9 ohms.

    DC Current Input Accuracy0.1% of input range.

    I Voltage Input (914MB)

    DC Voltage Input RangesRange user-configured. Range selected applies to allchannels.

    10V, 5V, 2.5V, 1.25V,625mV, 313mV, 156mV, 78mV

    Input Impedance

    110.5K ohms.DC Voltage Input Accuracy0.1% of input range.

    I Discrete Output

    Output TypeFour independent open drain MOSFET switches with acommon return that operate as low-side switches.

    Output Voltage Range0 to 35V DC.External voltage source required.

    Output Current Range0 to 1A DC continuous for each output.

    Output OFF Leakage Current50A maximum.

    Output ON Resistance0.15 ohms maximum.

    Output Response Time4.1ms typical, from receipt of command to gatetransition of the output MOSFET.

    Operation

    Digital outputs are set to their OFF state following asoftware or power-on reset. Outputs can optionally beset to user-defined states following a watchdog time-out. Watchdog timeout output control takes prece-dence over limit alarm control. Alarm control takesprecedence over host control.

    I Communication

    Supported Modbus CommandsThe command/response protocol for communicatingwith this module adheres to the Modbus/RTU standardfor the following Modbus Functions.

    Read Coil (Output) StatusRead Holding RegistersRead Input Registers

    Force Single Coil (Output)Preset Single RegisterForce Multiple Coils (Output)Preset Multiple RegistersReport Slave IDReset Slave

    LED IndicatorsLEDs indicate power, status, and discrete level/alarm.

    I Power and Isolation

    Power Requirements10 to 36V DC or 22 to 26V AC.

    Supply Current

    Supply Current Draw10V DC 125mA maximum24V DC 50mA maximum24V AC 100mA rms maximum

    Isolation1500V AC for 60 seconds or 250V AC continuous.4-way isolation between input, network, power, anddiscrete I/O circuits. Inputs are isolated channel-to-channel for common mode voltage to 4V DC.

    I OrderingInformation

    Models913MB-0900914MB-0900DC current (913MB) or voltage ( 914MB) input module

    Accessories900C-SIPConfiguration Software Interface Package(includes software CD-ROM for Windows, RS-232/485converter, and RS-485/three-wire cable)

    5034-225USB-to-RS232 adapter. See page 68 for more info.

    5020-350AC current sensor for 913MB. One for each channel.(See page 205)

    TBK-B02

    Optional terminal block kit, barrier strip style, 4 pcs.TBK-S02Optional terminal block kit, spring clamp style, 4 pcs.

    PS5R-D24Power supply (24V DC, 2.1A).See Power Supplies on Page 199.

    For more information on software, network hardware,and mounting accessories, please see Pages 69-71.

    TWO-WIRE TRANSMITTER

    ANALOG INPUT

    CONNECTIONS

    TB1/TB2

    IN+

    DCCURENT

    (mA)

    IN-

    -

    +TB1/TB2

    IN+

    IN-

    DIGITALOUTPUTS

    45

    46

    TB4

    OUT3

    RTN

    DIGITAL OUTPUT

    TB4

    RTN

    OUT2

    OUT1

    444342

    36

    41

    TB3

    OUT0

    11

    TB1

    1213 IN0+

    IN0-141516

    IN1+

    IN1-

    INPUTS0,1

    TB221

    IN3+

    IN3-

    2526

    24 IN2-

    23 IN2+

    22

    INPUTS2,3

    D

    COM

    COM

    D

    RS485

    33

    34

    35

    31

    32

    A

    BPWR

    TB3

    TB1

    ANALOGINPUT

    ANALOGINPUT

    TB2

    AC/DCPOWER

    NETWORKCOMMUNICATION

    CURRENT INPUT

    VOLTAGE

    SOURCE -

    + TB1/TB2

    IN+

    IN-

    VOLTAGE INPUT

    XMTR2-WIRE

    -

    +

    DIGITAL OUTPUT CONNECTIONS

    UP TO

    35V DC

    MECHANICAL

    RELAY INTERFACE

    +

    OUT 3

    OUT

    OUT 2

    RTN

    OUT 1

    RTN

    TB4

    OUT

    RTN

    DIGITAL OUT

    SHARES

    RETURN

    RTN

    OUT

    10 TO 36V DC

    OR 24V ACNON-POLARIZED

  • 8/6/2019 Busworks Section

    12/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    60

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    917/918MBMulti-Channel

    Analog OutputModules

    DC Current orDC Voltage Outputs

    Discrete Outputs

    Models917MB: 4 current output channels918MB: 4 voltage output channels

    Analog Output917MB: 0 to 20mA, 4 to 20mA, 0 to 1mA DC918MB: 0 to 10V, 0 to 5V, 0 to 1V DC

    Discrete OutputFour output channels:Open-drain MOSFETs (1A DC loads)0 to 35V DC

    Network CommunicationModbus-RTU high-speed RS-485

    Power Requirement12 to 36V DC (917MB), 10 to 36V DC (918MB),24V AC

    ApprovalsCE marked. UL, cUL listedClass I; Division 2; Groups A, B, C, D.

    I Description

    These modules drive four analog output channelsand also feature four discrete outputs for on/offcontrol. Isolation separates the output, power,and network circuits. Network communicationadheres to the industry-standard RS-485 ModbusRTU protocol. AC and DC power sources aresupported with nonpolarized, diode-coupledterminals.

    The analog outputs generate a signal based on

    communication from the host. They accommo-date wide DC voltage or current ranges.

    Discrete outputs provide simple on/off switchingcapability (open-drain) for external devices.

    Combining analog outputs, on/off controllers,and a network interface in a single package,makes this instrument extremely powerful.Multi-channel design adds cost-efficiency andallows high-density mounting. Plus, safe, ruggedconstruction make it reliable for both controlroom and distributed field I/O use in a broadrange of temperature control applications.

    Custom module configurations are also possible(consult factory for details).

    I Special Features

    I Standard Modbus RTU protocol with high-speedRS-485 communication (up to 115K bps)

    I 12-bit D/A yields 0.1% of span resolution andaccuracy

    I Four analog outputs in an inch-wide modulereduces system costs and saves panel space

    I Four discrete outputs enable host-controlledon/off switching

    I Heavy-duty 1A solid-state relays providedependable on/off control of industrial devices

    I Self-calibration lowers maintenance costs byreducing periodic manual calibration checks

    I Watchdog timers provide a configurablefailsafe output state for use when hostI/O communication is lost

    I Three-way isolation eliminates potentialground loops between power, output, andnetwork circuitry

    I Self-diagnostics monitor microcontroller activityto detect operational failures (lock-up) andexecute a reset to restore communication

    Modbus

    FourAnalogOutputs

    DC Current

    orDC Voltage

    RS-485

    10-36V DCor 24V AC

    Isolation

    FourDiscreteOutputs

    Power

    Outputs (4)Outputs (2)

    Outputs (2)

    Analog Output ModuleModbus/RS-485

  • 8/6/2019 Busworks Section

    13/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    61

    M o d b u s I / O

    I Performance

    I General Analog Output

    ResolutionSee current/voltage output specifications for more

    information.Ambient Temperature EffectBetter than 0.001% of output span per C, or1.0uV/C, whichever is greater.

    Ambient TemperatureOperation (917MB): -25C to 60C* (-13F to 140F*).Operation (918MB): -25C to 70C (-13F to 158F).Storage: -40C to +85C (-40F to +185F).

    * Limit 917MB maximum ambient to 50C (122F)when using supply voltages less than 15V DC.

    I Current Output (917MB)

    DC Current Output RangesRange user-configured. Range selected applies to all

    channels.Output Range Resolut ion Accuracy (% span)0 to 1mA 0.554% 2.0% (0.002mA)0 to 20mA 0.028% 0.1% (0.02mA)4 to 20mA 0.035% 0.1% (0.02mA)

    Maximum Output Current22.5mA DC typical.

    Integral Non-Linearity0.1% of span or 2 LSB typical, whichever is larger,for spans equal to or greater than 16mA.

    Output Compliance12V minimum, 12.7V typical.

    Output Load Resistance Range0 to 630 ohms typical.

    Response Time11ms typical into 500 ohms, for measurement toreach 98% of the final value in response to a stepcommand. Actual response time will vary with load.

    I Voltage Output (918MB)

    DC Voltage Output RangesRange user-configured. Selection applies to all channels.

    Output Range Resolut ion Accuracy (% span)0 to 1V 0.274% 0.6% (6mV)

    0 to 5V 0.055% 0.1% (5mV)0 to 10V 0.027% 0.1% (10mV)

    Maximum Output Voltage11.255V DC typical.

    Integral Non-Linearity0.1% of span or 2 LSB typical, whichever is larger,for spans equal to or greater than 5V.

    Output Current0 to 10mA DC maximum.

    Output Impedance1 ohm.

    Output Short Circuit Protection

    Included.Response Time110s rise time typical, 150s fall time typical,unloaded, for output to reach 98% of the final valuein response to a step command. Time varies with load.

    I Discrete Output

    Output TypeFour independent open drain MOSFET switches with acommon return that operate as low-side switches.

    Output Voltage Range0 to 35V DC (up to 1A/channel continuous).External voltage source required.

    Output ON Resistance0.15 ohms maximum.

    OperationDigital outputs are set to their OFF state following asoftware or power-on reset. Outputs may be set touser-defined states following a watchdog timeout.Watchdog timeout output control takes precedenceover limit alarm control. Alarm control takes prece-dence over host control.

    Output Response Time4.1ms typical, from receipt of command to gatetransition of the output MOSFET.

    I Communication

    Supported Modbus CommandsThe command/response protocol for communicatingwith this module adheres to the Modbus/RTU standardfor the following Modbus Functions.

    Read Coi l (Output) Status Report Slave IDRead Holding Registers Reset SlaveRead Input RegistersForce Single Coil (Output)Preset Single RegisterForce Multiple Coils (Output)Preset Multiple Registers

    LED IndicatorsLEDs indicate power, status, and discrete level/alarm.

    I Power and Isolation

    Power Requirements10 to 36V DC (918MB), 12 to 36V DC (917MB)22 to 26V AC.

    Supply Current

    Supply Current Draw (917) Current Draw (918)10V DC Not Recommended 100mA maximum12V DC 275mA maximum 85mA maximum24V DC 120mA maximum 45mA maximum24V AC 210mA rms max. 85mA rms max.

    Isolation1500V AC for 60 seconds or 250V AC continuous.3-way isolation between outputs, network, and powercircuits.

    I OrderingInformation

    Models917MB-0900918MB-0900DC current (917MB) or voltage (918MB) output module

    Accessories900C-SIPConfiguration Software Interface Package(includes software CD-ROM for Windows, RS-232/485converter, and RS-485/three-wire cable)

    5034-225

    USB-to-RS232 adapter. See page 68 for more info.TBK-B02Optional terminal block kit, barrier strip style, 4 pcs.

    TBK-S02Optional terminal block kit, spring clamp style, 4 pcs.

    PS5R-D24Power supply (24V DC, 2.1A).See Power Supplies on Page 199.

    For more information on software, network hardware,and mounting accessories, please see Pages 69-71.

    DC CURRENT OUTPUT

    ANALOG OUTPUT

    CONNECTIONS DIGITALOUTPUTS

    45

    46

    TB4

    OUT3

    RTN

    DIGITAL OUTPUT

    TB4

    RTN

    OUT2

    OUT1

    444342

    36

    41

    TB3

    OUT0

    D

    COM

    COM

    D

    RS485

    33

    34

    35

    31

    32

    A

    BPWR

    TB3

    TB1

    ANALOGOUTPUT

    ANALOGOUTPUT

    TB2

    AC/DCPOWER

    NETWORKCOMMUNICATION

    DC VOLTAGE OUTPUT

    TB1

    I0+

    RTN

    12

    11

    ANALOGOUTP

    UTS

    13

    RTN

    I1+

    RTN

    1415

    ANALOGOUTPUTS

    16 RTN

    TB22122

    I2+

    RTN

    I3+

    RTN

    2324

    RTN26

    25 RTN

    TB1

    V0+

    RTN

    12

    11

    ANALOGOUTP

    UTS

    13

    RTN

    V1+

    RTN

    1415

    ANALOGOUTPUTS

    16 RTN

    TB22122

    V2+

    RTN

    V3+

    RTN

    2324

    RTN26

    25 RTN

    TB1/TB2

    +LR

    I

    TB1/TB2

    +LR

    WIRING CONNECTIONS

    SAME AS 913/914MB

    10 TO 36V DC

    OR 24V ACNON-POLARIZED

    I+

    RTN

    V+

    RTN

  • 8/6/2019 Busworks Section

    14/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    62

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    924MBMulti-Channel

    TemperatureControl Modules

    Thermocouple orMillivolt Input

    Limit Alarms orDiscrete Outputs

    Model924MB: 4 input channels

    InputFour input channels:Thermocouple (types J, K, T, R, S, E, B, N),100mV DC

    OutputFour output channels:Open-drain MOSFETs (1A DC loads)0 to 35V DC

    Network CommunicationModbus-RTU high-speed RS-485

    Power Requirement10 to 36V DC,24V AC

    ApprovalsCE marked. UL, cUL listedClass I; Division 2; Groups A, B, C, D.

    I Description

    This signal conditioner is a four-channel analoginput module with four discrete outputs. It filtersand linearizes thermocouple inputs while provid-ing isolation between input, output, power, andnetwork circuits. Cold junction compensationand upscale/downscale sensor break detectionare standard. AC and DC power sources are sup-ported with nonpolarized, diode-coupled termi-nals.

    The programmable inputs accommodate eightthermocouple types plus wide-range millivoltsignals. Flexible discrete outputs operate asalarms or on/off controllers. As limit alarms, eachdiscrete output can be configured with highand/or low setpoints exclusively tied to an analoginput channel. Alarm trips function without hostcommunication enabling low-cost stand-alonealarms as well as local backup for the primarycontrol system. Otherwise, on/off control isbased on commands issued by the host system.

    Combining flexible transmitter functions, mixed

    signal I/O, alarm support, and a network inter-face in a single package, makes this instrumentextremely powerful. Multi-channel design addscost-efficiency and allows high-density mounting.Plus, safe, rugged construction makes thesemodules reliable for use in both control roomand distributed field I/O applications. Custommodule configurations are also possible (consultfactory for details).

    I Special Features

    I Standard Modbus RTU protocol with high-speedRS-485 communication (up to 115K bps)

    I 16-bit sigma-delta A/D yields 0.1C resolutionand 0.5C measurement accuracy

    I Thermocouple linearization and sensor breakdetection ensure reliable measurements

    I Four discrete outputs enable local temperaturelimit alarms or host-controlled on/off switching

    I Heavy-duty 1A solid-state relays providedependable on/off control of industrial devices

    I Self-calibration lowers maintenance costs byreducing periodic manual calibration checks

    I Watchdog timers provide a configurablefailsafe output state for use when hostI/O communication is lost

    I Four-way isolation eliminates potential groundloops between power, input, output andnetwork circuitry

    I Self-diagnostics monitor microcontroller activityto detect operational failures (lock-up) andexecute a reset to restore communication

    Modbus

    FourThermocouple

    orDC Millivolt

    Inputs RS-485

    10-36V DCor 24V AC

    Isolation

    Four

    DiscreteOutputsor

    Limit Alarms

    Power

    Outputs (4)Inputs (2)

    Inputs (2)

    Thermocouple/Millivolt Input ModuleModbus/RS-485

  • 8/6/2019 Busworks Section

    15/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    63

    M o d b u s I / O

    I Performance

    I General Input

    Resolution100mV DC input: 0.1%.

    Thermocouple input: 0.1C (0.18F).Ambient Temperature EffectBetter than 0.005% of input span per C, or1.0uV/C, whichever is greater.

    Noise RejectionNormal mode: 40dB @ 60Hz, typical.Common mode: 140dB @ 60Hz, typical.

    Input Filter Bandwidth-3dB at 3Hz, typical.

    Input Conversion Rate90ms per channel.

    I Thermocouple Input

    Thermocouple Input RangesThermocouple type user-configured. Type selectedapplies to all channels. Signal linearization, cold-junc-tion compensation, and open circuit or lead breakdetection are included.

    TC C Range (F Range) AccuracyJ -210 to 760C (-346 to 1400F) 0.5CK -200 to 1372C (-328 to 2502F) 0.5CT -260 to 400C (-436 to 752F) 0.5CR -50 to 1768C (-58 to 3214F) 1.0CS -50 to 1768C (-58 to 3214F) 1.0CE -200 to 1000C (-328 to 1832F) 0.5CB 260 to 1820C (500 to 3308F) 1.0CN -230 to 1300C (-382 to 2372F) 1.0C

    Note 1: Accuracy is given with CJC switched off.Relative inaccuracy with CJC enabled may increaseby 0.5C.

    Thermocouple Break DetectionTC sensor failure can be configured for either upscaleor downscale. Selection applies to all channels.

    I DC Millivolt Input

    Millivolt Input Ranges100mV DC.

    Millivolt Input Accuracy0.1% of input range.

    I Discrete Output

    Output TypeFour independent open drain MOSFET switches with acommon return that operate as low-side switches.

    Output Voltage Range0 to 35V DC, 1A DC maximum for each output.External voltage source required.

    Output ON Resistance0.15 ohms maximum.

    OperationDigital outputs are set to their OFF state following asoftware or power-on reset. Outputs can optionally

    be set to user-defined states following a watchdogtimeout. Watchdog timeout output control takesprecedence over limit alarm control. Alarm controltakes precedence over host control.

    Output Response Time4.1ms typical, from receipt of command to gatetransition of the output MOSFET.

    I Communication

    Supported Modbus CommandsThe command/response protocol for communicatingwith this module adheres to the Modbus/RTU standardfor the following Modbus Functions.

    Read Coil

    Read Holding RegistersRead Input RegistersForce Single CoilPreset Single RegisterForce Multiple CoilsPreset Multiple RegistersReport Slave IDReset Slave

    LED IndicatorsLEDs indicate power, status, and discrete level/alarm.

    I Power and Isolation

    Power Requirements10 to 36V DC,22 to 26V AC.

    Supply Current

    Supply Current Draw10V DC 100mA maximum24V DC 45mA maximum24V AC 85mA rms maximum

    Isolation1500V AC for 60 seconds or 250V AC continuous.4-way isolation between input, network, power anddiscrete I/O circuits. Inputs are isolated channel-to-channel for common mode voltage to 5V DC.

    I Ordering

    Information

    924MB-0900Thermocouple/millivolt input module

    900C-SIPConfiguration Software Interface Package(includes software CD-ROM for Windows, RS-232/485converter, and RS-485/three-wire cable)

    5034-225USB-to-RS232 adapter. See page 68 for more info.

    TBK-B01Optional terminal block kit, barrier strip style, 2 pcs.(Does not include terminal block for input wiring.)

    TBK-S02

    Optional terminal block kit, spring clamp style, 2 pcs.(Does not include terminal block for input wiring.)

    PS5R-D24Power supply (24V DC, 2.1A).See Power Supplies on Page 199.

    For more information on software, network hardware,and mounting accessories, please see Pages 69-71.

    TC INPUT

    ANALOG INPUT

    CONNECTIONS

    TB1/TB2

    IN+

    VOLTAGE

    IN-

    SOURCE -

    + TB1/TB2

    IN+

    IN-

    DIGITALOUTPUTS

    45

    46

    TB4

    OUT3

    RTN

    DIGITAL OUTPUT

    TB4

    RTN

    OUT2

    OUT1

    444342

    36

    41

    TB3

    OUT0

    11

    TB1

    12

    CJC-0

    13 IN0+

    IN0-141516

    IN1+

    IN1-

    INPUTS0,1

    CJC-1

    TB221

    IN3+

    IN3-

    2526

    24 IN2-

    23 IN2+

    22

    INPUTS2,3

    D

    COM

    COM

    D

    RS485

    33

    34

    35

    31

    32

    A

    BPWR

    TB3

    TB1

    ANALOGINPUT

    ANALOGINPUT

    TB2

    AC/DCPOWER

    NETWORKCOMMUNICATION

    VOLTAGE INPUT

    DIGITAL OUTPUT CONNECTIONS

    OUT 3

    OUT 0

    OUT 2

    RTN

    OUT 1

    RTN

    TB4

    OUT

    RTN

    DIGITAL OUTSHARES

    RETURN

    10 TO 36V DC

    OR 24V AC

    NON-POLARIZED

    UP TO

    35V DC

    MECHANICAL

    RELAY INTERFACE

    +

    RTN

    OUT

  • 8/6/2019 Busworks Section

    16/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    64

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    932/934MBMulti-Channel

    TemperatureControl Modules

    RTD or ResistanceInput

    Limit Alarms orDiscrete Outputs

    Models932MB: 2 input channels, 2 relay outputs934MB: 4 input channels, 4 relay outputs

    InputRTD (100 ohm Pt, 120 ohm Ni, 10 ohm Cu),Resistance (0 to 500 ohms)

    OutputSolid-state relays, Form A, SPST-NO

    Network CommunicationModbus-RTU high-speed RS-485

    Power Requirement

    10 to 36V DC,24V AC

    ApprovalsCE marked. UL, cUL listedClass I; Division 2; Groups A, B, C, D.

    I Description

    This signal conditioner is a dual or quad-channelanalog input module with one discrete/relay out-put per input channel and a Modbus interface. Itfilters and linearizes RTD or resistance inputswhile providing isolation between input, output,power, and network circuits. Lead wire compen-sation and upscale/downscale sensor breakdetection are standard. Low voltage AC and DCpower sources are supported with nonpolarized,diode-coupled terminals.

    The programmable inputs accommodate fourRTD types plus wide-range resistance signals.Flexible discrete outputs operate as alarms oron/off controllers. As limit alarms, each discreteoutput can be configured with high and/or lowsetpoints exclusively tied to an analog inputchannel. Alarm trips function without host com-munication enabling low-cost stand-alone alarmsas well as local backup for the primary controlsystem. Otherwise, on/off control is based oncommands issued by the host system.

    Combining flexible transmitter functions, mixedsignal I/O, alarm support, and a network inter-face in a single package, makes this instrumentextremely powerful. Multi-channel design addscost-efficiency and allows high-density mounting.Plus, safe, rugged construction makes thesemodules reliable for use in both control roomand distributed field I/O applications. Custommodule configurations are also possible (consultfactory for details).

    I Special Features

    I Standard Modbus RTU protocol with high-speedRS-485 communication (up to 115K bps)

    I 16-bit sigma-delta A/D yields 0.1C resolutionand 0.25C accuracy (Pt, Ni RTDs)

    I RTD linearization and sensor break detectionensure reliable measurements

    I Discrete relay outputs enable local temperaturelimit alarms or host-controlled on/off switching

    I Heavy-duty 1A solid-state relays providedependable on/off control of industrial devices

    I Self-calibration lowers maintenance costs byreducing periodic manual calibration checks

    I Watchdog timers provide a configurablefailsafe output state for use when hostI/O communication is lost

    I Four-way isolation eliminates potential groundloops between power, input, output andnetwork circuitry

    I Self-diagnostics monitor microcontroller activityto detect operational failures (lock-up) andexecute a reset to restore communication

    Modbus

    FourRTD

    orResistance

    Inputs RS-485

    10-36V DCor 24V AC

    Isolation

    Four

    DiscreteOutputsor

    Limit Alarms

    Power

    Outputs (4)Inputs (2)

    Inputs (2)

    RTD/Resistance Input ModuleModbus/RS-485

  • 8/6/2019 Busworks Section

    17/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    65

    M o d b u s I / O

    I Performance

    I RTD/Resistance Input

    Input RangesInput type user-configured. Type selected applies to all

    channels. RTD linearization, lead wire compensation,and open circuit or lead break detection are included.

    Input Type Alpha Input Range AccuracyPt 100 ohm 1.3850 -200 to 850C 0.25CPt 100 ohm 1.3911 -200 to 850C 0.25CNi 120 ohm 1.6720 -80 to 320C 0.25CCu 10 ohm 1.4272 -200 to 260C 1.00CResistance linear 0 to 500 ohms 0.05 ohm

    ResolutionInput Type Alpha ResolutionPt 100 ohm 1.3850 0.1CPt 100 ohm 1.3911 0.1CNi 120 ohm 1.6720 0.1CCu 10 ohm 1.4272 0.2CResistance linear 7.8125 milliohms

    Ambient Temperature EffectBetter than 0.005% of input span per C, or1.0uV/C, whichever is greater.

    Noise RejectionNormal mode: 40dB @ 60Hz, typical.Common mode: 130dB @ 60Hz, typical.

    Input Filter Bandwidth-3dB at 3Hz, typical.

    Input Conversion Rate300ms per channel typical.

    RTD Break DetectionSensor failure can be configured for either upscale or

    downscale. Selection applies to all channels.

    Excitation Current1mA DC typical, all types.

    Lead-Wire CompensationInherent for 3-wire RTD. The maximum lead resistanceis 25 ohms per lead (Pt), 20 ohms per lead (Ni), 10ohms per lead (Cu). All lead wires must be of equalsize and length.

    I Discrete OutputOutput TypeSolid-State Relay (SSR), one Form A (SPST-NO) switchper input channel. Outputs share a common returnconnection at the RTN terminals for low side switching

    Output Voltage Range0 to 48V DC, 1A DC.

    Output ON Resistance0.4 ohms maximum.

    Output Response Time4.1ms typical, from receipt of command to gatetransition of the output MOSFET.

    OperationDigital outputs are set to their OFF state following asoftware or power-on reset. Outputs can be set touser-defined states following a watchdog timeout.

    I Communication

    Supported Modbus CommandsThe command/response protocol for communicatingwith this module adheres to the Modbus/RTU standardfor the following Modbus Functions.

    Read Holding Registers Read CoilRead Input Registers Reset SlavePreset Single Register Report Slave IDForce Multiple Coils Force Single CoilPreset Multiple Register

    LED IndicatorsLEDs indicate power, status, and discrete level/alarm.

    I Power and Isolation

    Power Requirements10 to 36V DC (56mA max. at 24V DC).22 to 26V AC (94mA rms max. at 24V AC).

    Isolation1500V AC for 60 seconds or 250V AC continuous.4-way isolation between input, network, power anddiscrete I/O circuits. Inputs are isolated channel-to-channel for common mode voltage to 5V DC.

    I OrderingInformation

    932MB-0900Two channel RTD/Resistance input module

    934MB-0900Four channel RTD/Resistance input module

    Accessories900C-SIPConfiguration Software Interface Package(includes software CD-ROM for Windows, RS-232/485converter, and RS-485/three-wire cable)

    5034-225

    USB-to-RS232 adapter. See page 68 for more info.TBK-B02Optional terminal block kit, barrier strip style, 4 pcs.

    TBK-S02Optional terminal block kit, spring clamp style, 4 pcs.

    PS5R-D24Power supply (24V DC, 2.1A).See Power Supplies on Page 199.

    For more information on software, network hardware,and mounting accessories, please see Pages 69-71.

    ANALOG INPUT

    CONNECTIONS

    DIGITAL OUTPUT

    TB

    4

    TB3

    TB

    1

    ANALOGINPUT

    ANALOGINPUT

    TB2

    AC/DCPOWER

    NETWORKCOMMUNICATION

    DIGITAL OUTPUT CONNECTIONS

    RTN

    OUT 0

    OUT 2

    OUT 1

    RTN

    OUT 3

    TB4

    OUT

    RTN

    DIGITAL OUT

    SHARES

    RETURN

    10 TO 36V DC

    OR 24V AC

    NON-POLARIZED

    INL

    IN-

    IN+

    IN+ IN+

    INL

    TB1/TB2

    INL

    IN-

    TB1/TB2

    IN-

    TB1/TB2

    JUMP

    DECADEBOX

    JUMP

    2-WIRE RTD

    3-WIRE RTD RESISTANCE

    D

    D

    A

    TB1 TB4

    12

    IN0-

    45RTN

    13 IN0L

    44OUT2

    15

    IN1-

    42RTN

    16

    IN1L41OUT0

    TB321

    IN2+36LRTN

    23 INL2

    34

    24

    IN3+

    33

    26 INL3

    31

    PWR

    B

    11

    14

    IN0+

    IN1+

    46

    43

    OUT3

    OUT1

    22 IN2-

    TB2

    35COM

    25

    IN3-

    32

    934MBOnly

    RS485

    RTDINPUTS2,3

    932MB/934MB

    DIG.OUTDIG.OUT

    RTDINPUTS0,1

    UP TO

    48V DC

    MECHANICAL

    RELAY INTERFACE

    +

    RTN

    OUT

    Optional terminal blocks: barrier strip (left) andspring clamp (right). Cage clamp terminal is standard.

  • 8/6/2019 Busworks Section

    18/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    66

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    942MBFrequency/

    Pulse CounterModules

    Periodic or PulseWaveform Input

    Limit Alarms orDiscrete Outputs

    Model942MB: 2 input channels

    InputTwo input channels:0 to 50KHz in three selectable rangesAmplitudes up to 140V AC or 200V peakPulse counter range of 0 to 65535

    OutputTwo output channels:Solid-state relays (1A DC loads)0 to 48V DC

    Network Communication

    Modbus-RTU high-speed RS-485

    Power Requirement10 to 36V DC,24V AC

    ApprovalsCE marked. UL, cUL listedClass I; Division 2; Groups A, B, C, D.

    I Description

    This signal conditioner is a two-channel analoginput module with discrete outputs and Modbuscommunication. It conditions periodic or pulsewaveform inputs and provides solid-state relaysfor limit alarms or ON/OFF control.

    Versatile inputs accommodate many applicationsusing TTL, magnetic pickups, proximity sensors,or a variety of switches (high/low-side transistor,dry contact, open drain, open collector). Bipolar

    and unipolar waveforms are supported with aselectable input bias that accepts both zero andnon-zero crossing signals. Voltage threshold andrelative hysteresis are also user selectable.

    Inputs may also function as event counters withseparate microcontrollers for each channel. Themodule counts pulses on the positive or negativeedge. It can wrap around to zero for continuouscounting, latch at a programmed count value(setpoint), or automatically reset itself to zeroafter reaching a setpoint value. Software controlsenable remote resets. A variety of filters help

    remove noise, jitter, and other mechanical effectsto prevent false counts.

    The discrete outputs can operate as independentalarms or provide on/off control regulated by thehost system. As limit alarms, each output can beset for high and/or low setpoints exclusively tiedto an analog input. These low cost modules areideal for standalone alarms as well as for localbackup of the primary control system.

    I Special Features

    I Standard Modbus RTU protocol with high-speedRS-485 communication (up to 115K bps)

    I Separate microcontrollers on each channel forpulse counting and period measurement

    I Solid-state relay outputs enable local limitalarms or host-controlled on/off switching

    I Bipolar and unipolar input signal support

    I Programmable pulse counter functions

    I Input filtering functions include hysteresis,averaging, debounce, relay time delay, andalarm deadband controls

    I 4-way isolation (input, output, power, network)

    I Watchdog timers provide a failsafe output

    I Self-diagnostics monitor microcontroller activityto detect operational failures (lock-up) andexecute a reset to restore communication

    Modbus

    TwoFrequency

    orPulse

    WaveformInputs

    RS-485

    10-36V DCor 24V AC

    Isolation

    Two

    DiscreteOutputsor

    Limit Alarms

    Power

    Outputs (2)Inputs (2)

    Frequency/Counter Module

    Optional terminal blocks: barrier strip (left) andspring clamp (right). Cage clamp terminal is standard.

    Modbus/RS-485

  • 8/6/2019 Busworks Section

    19/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    67

    M o d b u s I / O

    I Performance

    I Frequency/Counter Input

    Input RangesInput type user-configured. Applies to both channels.

    Input Range Accuracy Accuracy over Temp.0 to 100Hz 0.04Hz 0.06Hz0 to 1000Hz 0.4Hz 0.6Hz0 to 50,000Hz 10Hz 15Hz0 to 65,535 pulses 1 pulse 1 pulse

    Unipolar Input ConfigurationAmplitude: 0 to 3V minimum range,0 to 200V peak maximum range.

    Threshold: Configurable for 1.5V or 5V, typical.

    Hysteresis: Configurable for 25mV (at 1.5V thresh-old), or 83mV (at 5.0V threshold), typical.

    Bipolar (Zero-Crossing) Input ConfigurationAmplitude (0-20KHz): 50mV minimum (with 25mVhysteresis), or 150mV minimum (with 83mV hys-teresis), to 200V peak maximum.

    Amplitude (Above 20KHz): 100mV minimum (with25mV hysteresis), or 200mV minimum (with 83mVhysteresis), to 200V peak maximum.

    Threshold: 0mV nominal, 0.01V typical with 25mVhysteresis; 0.03V typical with 83mV hysteresis.

    Hysteresis: Configurable for 25mV or 83mV, typical.

    Resolution0 to 100Hz input range: 0.01Hz0 to 1000Hz input range: 0.1Hz0 to 50,000Hz input range: 1HzPulse counter: 1 pulse

    Minimum Input Pulse Width10S (frequency input); 5mS (pulse input).

    Counting Rate100Hz maximum counting rate(5mS ON and 5mS OFF for 10mS period or 100Hz).

    Input Impedance35K ohms, typical.

    Input Filter Bandwidth-3dB at 35kHz, typical.

    Input Pullup/PulldownSoftware selectable 2.7K ohm input pullup to +5V anda 1K ohm input pulldown to return. The resistors may

    also be left floating (none).Input Debounce0 to 1.375 seconds, configurable in 5mS increments.

    Noise RejectionCommon mode: 80dB @ 60Hz, typical with 100 ohminput unbalance.

    I Discrete Output

    Output TypeSolid-State Relay (SSR), one Form A (SPST-NO) switchper input channel. Outputs share a common returnconnection at the RTN terminals for low-side switching

    Output Voltage Range

    0 to 48V DC, 1A DC.Output ON Resistance0.4 ohms maximum.

    Output Response Time4.1ms typical, from receipt of command to gatetransition of the output MOSFET.

    OperationDigital outputs are set to their OFF state following asoftware or power-on reset. Outputs can be set touser-defined states following a watchdog timeout.

    I Communication

    Supported Modbus CommandsThe command/response protocol for communicatingwith this module adheres to the Modbus/RTU standardfor the following Modbus Functions.

    Read Holding Registers Read CoilRead Input Registers Reset SlavePreset Single Register Report Slave IDForce Multiple Coils Force Single CoilPreset Multiple Registers

    LED IndicatorsLEDs indicate power, status, and discrete level/alarm.

    I Power and Isolation

    Power Requirements10 to 36V DC.22 to 26V AC.

    Isolation1500V AC for 60 seconds or 250V AC continuous.4-way isolation between input, network, power anddiscrete I/O circuits. Inputs are isolated channel-to-channel for common mode voltage to 5V DC.

    I OrderingInformation

    942MB-0900Frequency/counter input module

    Accessories900C-SIPConfiguration Software Interface Package(includes software CD-ROM for Windows, RS-232/485converter, and RS-485/three-wire cable)

    5034-225USB-to-RS232 adapter. See page 68 for more info.

    TBK-B02Optional terminal block kit, barrier strip style, 4 pcs.

    TBK-S02Optional terminal block kit, spring clamp style, 4 pcs.

    PS5R-D24Power supply (24V DC, 2.1A).See Power Supplies on Page 199.

    For more information on software, network hardware,and mounting accessories, please see Pages 69-71.

    FREQUENCY INPUT

    ANALOG INPUT

    CONNECTIONS DIGITALOUTPUTS

    45

    46

    TB4

    DIGITAL OUTPUT

    TB4

    RTN

    OUT1

    444342

    36

    41

    TB3

    OUT0

    11

    TB1

    12

    FREQ.INPUT0,1

    13 RTN

    NC

    141516

    FRQ1

    RTN

    D

    COM

    COM

    D

    RS485

    33

    34

    35

    31

    32

    A

    BPWR

    TB3

    TB1

    ANALOGINPUT

    AC/DCPOWER

    NETWORKCOMMUNICATION

    DIGITAL OUTPUT CONNECTIONS

    OUT 3

    OUT 0

    OUT 2

    RTN

    OUT 1

    RTN

    TB4

    OUT

    RTN

    DIGITAL OUTSHARES

    RETURN

    10 TO 36V DC

    OR 24V AC

    NON-POLARIZED

    FRQ0

    RTN

    FRQ1

    RTN

    FREQUENCY

    GENERATOR -

    +

    MAGNETIC

    PICKUP -

    +

    HIGH-SIDE SWITCH(Open Collector/Drain)

    FRQ0

    RTN

    FRQ0

    RTN

    FRQ0

    RTN

    MAGNETIC INPUT

    or

    FRQ0

    RTNor

    V+V+V+V+

    LOW-SIDE SWITCH(Open Collector/Drain)

    DRY CONTACT

    FRQ0

    RTN

    TTLV+V+V+

    NC

    FRQ0

    UP TO

    48V DC

    MECHANICAL

    RELAY INTERFACE

    +

    RTN

    OUT

    TB1

  • 8/6/2019 Busworks Section

    20/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    68

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    262524

    TB2TB1

    (110.5)4.35

    (99.1)3.90

    232221

    TB2

    161512 13 1411

    TB1

    D AB

    PWR

    TB3

    33 313236 3435

    TB4

    414243444546

    D

    COM

    COM

    RS485

    TB3

    TB4

    DFT

    32

    10

    ST

    (118

    .9)

    4.6

    8

    (95

    .3)

    3.7

    5

    AcromagRUN

    CL

    (26.7)1.05

    (59

    .4)

    2.3

    4

    NOTE: ALL DIMENSION ARE IN INCHES (MILLIMETERS)

    "T" Rail Din MountingDin EN 50022, 35mm

    900MB Series Technical Diagrams

    PERSONAL COMPUTERW/WINDOWS 95/98 ORNT

    RS-232 SERIALPORT CONNECTORATBACKOF PC

    RS-232 TO RS-485 CONVERTERMODEL 5034-214

    900C-SIP COMMUNICATION CONNECTIONS

    CONNECT THE RS-232SIDE OF CONVERTERTOTHE PC

    424345 44TB4

    46

    0 1

    DFT

    TB4

    STSTATUS LED (YELLOW)

    RUN/PWR LED (GREEN)

    DEFAULT MODE SWITCH-PUSH FORDEFAULT MODE.

    STATUSLED FLASHES INDEFAULT MODE.

    RUN

    Acromag

    INSTALL MODBUSCONFIGURATIONSOFTWARE

    CAUTION: DO NOTCONNECT THECABLE DIRECTLY TO THEPC WITHOUTTHECONVERTER, OR DAMAGETOTHEMODULEMAY RESULT.

    CABLE5034-202

    COM

    D

    D

    CONNECT THE RS-485SIDE OF CONVERTERTO THECABLE

    CONNECT WIRES AS SHOWN

    RS-485

    GREENC

    BLACK

    RED

    B

    A

    COLORWIRE

    BA

    C

    TB3

    D

    32

    B

    PWR

    31

    A

    TB4

    C OM D

    COM

    COM

    36 35

    DD34 33

    RS485

    41TB3

    16 22 21

    TB2

    2 3 2 4 2 6 25

    TB2TB1

    REFER TO THEUSER'S MANUALTHAT CAME WITH YOUR MODULETO COMPLETE THEMODULE'SPOWER ANDI/O CONNECTIONS

    32

    R

    TB1

    12 1311

    ANY900MB MODULE

    TB1

    14 15

    PC RUNNING

    ACROMAGMODBUS CONFIG

    SOFTWARE

    Model 5034-225USB-to-RS232 adapter

    Length: 3.15 in (8.0 cm)Height: 0.80 in (2.03 cm)Width: 1.75 in (4.44 cm)Weight: 1.6 oz (45.36 g)

    USB-to-RS232Adapter

  • 8/6/2019 Busworks Section

    21/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    69

    M o d b u s I / O

    SoftwareInterface Package

    This package includes Windows Configuration

    Software, an RS-232-to-485 Serial PortConverter, and an RS-485 Signal Cable. Thesecomponents provide everything you need to setup a Series 900 I/O module from your desktopPC before installing it on the network.

    I Ordering Information

    900C-SIPSoftware Interface Package.Includes Configuration Software (5034-186),Non-isolated RS-232 to RS-485 Serial Port Converter

    (5034-214), and RS-485 Cable (5034-202).Items can also be ordered separately below.

    5034-186Configuration Software for Windows (95/98/2000/ME/NT4/XP) on CD-ROM.

    5034-214Non-isolated RS-232 to RS-485 Serial Port Converter,DB-9F to DB-9F.

    5034-202RS-485 to 3-wire Cable Converter,DB-9M to 3 x 12AWG RS-485 Cable, 8 ft.

    Software Interface PackageModel No. 900C-SIP

    RS-232 to RS-485Converter

    (non-isolated)

    Configuration Softwarefor Windows

    RS-485 Cable

    (DB-9)

    Configuration Kit

    Universal 50WPower Supply

    The PS5R-D24 is theideal power sourceto drive yournetwork.

    Input PowerRequirementUniversal power85 to 264V AC,105 to 370V DC

    Output24V DC, 2.1A (50W)

    I Ordering Information

    PS5R-D24Universal Power Supply

    DIN-RailMounting

    For your convenience, Acromag offers severalmounting accessories to simplify your systeminstallation. Our 19 rack-mount kit provides aclean solution for mounting your I/O modulesand a power supply. Or you can buy precut DINrail strips for mounting on any flat surface.

    I Ordering Information

    20RM-16-DIN19" rack-mount kit with DIN rail.

    DIN RAIL 3.0DIN RAIL 16.7DIN rail strip, Type T, 3 inches (75mm) or16.7 inches (425mm)

    V.ADJ

    DC ON

    M3.5Terminal Screws

    10-

    6.5

    4-

    4.5

    80

    13 13 13 13

    90

    12

    7.3

    5

    75

    60

    5

    Top View(dimensions in mm)

    35.3

    6

    95

    3.8

    Side View(dimensions in mm)

    Dimensions in inches (mm).

    RS-232/485Converter

    (non-isolated)

    5034-214

    RS-485to 3-wire

    5034-202

    Network Power

    Mounting Hardware

  • 8/6/2019 Busworks Section

    22/23

    Tel: 248-295-0880 Fax: 248-624-9234 e-mail: [email protected] www.acromag.com

    70

    9 0 0 M B S e r i e s

    Modbu

    sI/O

    BusWorks

    4SCC-TTMIsolated SignalConverter

    This unit provides an isolated interface betweenthe host PCs RS-232 port and RS-485 Modbusnetwork devices. Signal conversion is bidirectionalwith operation that is transparent to all devices.The RS-485 network supports up to 32 devices(including the 4SCC-TTM Converter) across 4000foot distances. Installation of additional networkdevices or extending the distance requires the4SCR-TTM Network Repeater.

    Specifications

    Baud RatesSwitch-selectable from 300 to 38.4K baud.

    DuplexHalf duplex only.

    Network Termination ResistorsTwo terminal blocks and 120 ohm resistors provided toterminate both ends of the RS-485 network.

    Wiring ConnectorsTerminal blocks with screw clamps for 14-26AWG.

    Operating Temperature Range-25 to 60C (-13 to 140F).

    IsolationWithstands 1500V AC surge for 60 seconds(250V AC or 354V DC continuous).

    I Ordering Information

    4SCC-TTM-1Signal Converter, 115V AC (power cord included)

    4SCC-TTM-2Signal Converter, 230V AC (power cord included)

    5020-924Signal Cable, 8ft. long, DB-9 to three wires.Connects PCs RS-232 port to 4SCC-TTM-x.

    4SCR-TTMIsolated Network

    RepeaterThis unit isolates and boosts RS-485 signals toextend communication distances or increase thenumber of devices on the network. Each Repeaterpermits the addition of a network branch with upto 32 devices (including the 4SCR-TTM) and willtransmit RS-485 signals another 4000 feet.Operation is transparent to all devices and nohandshaking is required. Two terminal blocks areprovided for 120 ohm resistors to terminate bothends of the network branch.

    Specifications

    Baud RatesSwitch-selectable from 300 to 38.4K baud.

    DuplexHalf duplex only.

    Network Termination ResistorsTwo terminal blocks and 120 ohm resistors provided toterminate both ends of the RS-485 network.

    RS-485 Wiring ConnectorsTerminal blocks with screw clamps for 14-26AWG.

    Power Wiring ConnectionsTerminal block with sc rew clamps for 12-18AWG.

    Operating Temperature Range-25 to 60C (-13 to 140F).

    Isolation

    Withstands 1500V AC surge for 60 seconds(250V AC or 354V DC continuous).

    I Ordering Information

    4SCR-TTM-1Signal Converter, 115V AC power

    4SCR-TTM-2Signal Converter, 230V AC power

    40LC-GBW-1115V AC power cord

    Dimensions in inches (mm).

    Shipping Weight3.0 lbs. (1.4 kg) packed.

    Dimensions in inches (mm).

    Shipping Weight3.0 lbs. (1.4 kg) packed.

    RS-232 to RS-485

    RS-485 to RS-485

  • 8/6/2019 Busworks Section

    23/23

    M o d b u s I / O

    SystemConnection

    Isolated RS-232/485 Signal ConverterAcromag Model No. 4SCC-TTM

    Daisy-ChainTopology RS-485 Network: Up to 32 devices, 4000ft. max.

    RS-232

    RS-485

    Extendingthe Network

    Isolated RS-485 Network RepeaterAcromag Model No. 4SCR-TTM

    Network Branch: Additional 32 devices, 4000ft. extensionTo Network Host

    RS-485RS-485

    Model 5034-225USB-to-RS232 adapter

    Length: 3.15 in (8.0 cm)Height: 0.80 in (2.03 cm)Width: 1.75 in (4.44 cm)Weight: 1.6 oz (45.36 g)

    USB-to-RS232 Adapter